Configuration of a system for access control, time management and production data collection.
Three levels
1. Supervision levelStandard PC with Ethernet as line supervisor, may be connected with an ERP system
2. Control levelLocal intelligent control units for access control and terminals for time & attendance or production data collection / machine data collection, working autonomic when Ethernet fails
3. Reader levelInput units with RFID (barcode, chip card…), keypad or biometric sensor
Aug 2018Topology INTUS 2
con
tro
l lev
elre
ader
/
sub
term
inal
s
sup
ervi
sio
n
leve
l
LBus
access T&A PDC/MDC
ERP
system
Ethernet
Networks and protocols.
І Network supervisor control levelNetwork Ethernet with TCP/IP protocol
І Network control level readerNetwork RS485 with LBus protocol
Aug 2018Topology INTUS 3
con
tro
l lev
elre
ader
sup
ervi
sio
n
leve
l
access access
Network Protocol
Ethernet TCP/IP
RS485 LBus
PC connection: INTUS and Ethernet.
Connection of INTUS Terminals to an EthernetStar topology betweenEthernet switch and controllers / terminals
• INTUS 5200/5200Compact terminal for T&A. Can control one door
• INTUS 5300Compact T&A terminal. Can control one door
• INTUS 5500/5540/5600T&A terminal with connection of max. 2x8 readers
• INTUS ACM40Access control manager for up to 4 doors
• INTUS ACM80eAccess control manager for up to 8 or 16 doors
Aug 2018Topology INTUS 4
Ethernet
10/100BaseT Switch
10/100BaseT
cabling
max. 100m
1
8
9
16
1
4
INTUS 5200 – connections.
Standard• 1 x Ethernet (10/100 BaseT)
Option: Interface module• 1 x LBus (not opto-decoupled)
connection for 1 reader• 1 x Digital Out (for 1 door strike)• 2 x Digital In (for 2 contacts)
Aug 2018Topology INTUS 5
DO
DI
Ethernet
DI
standard
option
LBus, 2 wire
INTUS 5300 – connections.
Standard• 1 x Ethernet (10/100 BaseT)• 1 x Digital Out 1
(for 1 door strike)• 2 x Digital In 1
(for 2 contacts)
Option: serial module 1
• 1 x RS485 (opto-decoupled) for host connection or
• 1 x V.24 (not opto-decoupled) for host connection or
• 1 x RS485 reader modulefor connection of 1 reader (depending on host interface)
1 not for INTUS 5300-PoE and INTUS 5300FP
Aug 2018Topology INTUS 6
DO
DI
Ethernet
DI
standard
option
1 serial module
RS485, 2 wire
V.24, 4 wire
LBus, 2 wire
INTUS 3460plus – connections.
Standard• 1 x Ethernet (10/100 BaseT)• 2 x Digital Out (for 2 door strikes)• 2 x Digital In (for 2 contacts)
Option: serial module 1
• 1 x RS485 (opto-decoupled) for host connection or
• 1 x V.24 (not opto-decoupled) for host connection and/or
• 2 x RS485 reader modulefor connection of 1 reader (depending on host interface)
Aug 2018Topology INTUS 7
2 x DO
2 x DI
Ethernet
standard
option
2 x serial modules
RS485, 2 wire
V.24, 4 wire
LBus, 2 wire
INTUS 5500 – connections.
Standard• 1 x Ethernet (10/100 BaseT)
Option Interface Module• 2 x Digital Out (for 2 door strikes)• 2 x Digital In (for 2 contacts)
Option: serial module• 2 x RS485-LBus (opto-decoupled)
for connection of 1-16 readers (depending on host interface)
Aug 2018Topology INTUS 8
LBus, 2 wire
2 x DO
Ethernet
2 x DI
standard
option
2 x serial module
INTUS 5540 – connections.
Standard• 1 x Ethernet (10/100 BaseT)
Option Interface Module• 2 x Digital Out (for 2 door strikes)• 2 x Digital In (for 2 contacts)
Option: serial module• 2 x RS485-LBus (opto-decoupled)
for connection of 1–16 readers (depending on host interface)
Aug 2018Topology INTUS 9
LBus, 2 wire
2 x DO
Ethernet
2 x DI
standard
option
2 x serial module
INTUS 5600 – connections.
Standard• 1 x Ethernet (10/100 BaseT)
Option Interface Module• 2 x Digital Out (for 2 door strikes)• 2 x Digital In (for 2 contacts)
Option: serial module• 2 x RS485-LBus (opto-decoupled)
for connection of 1–16 readers (depending on host interface
Aug 2018Topology INTUS 10
LBus, 2 wire
2 x DO
Ethernet
2 x DI
standard
option
2 x serial module
INTUS ACM40 – connections.
Standard• 1 x Ethernet 10/100 BaseT• 4 x Digital Out• 8 x Digital In • 2 x RS485 / LBus protocol
• 4 x Digital In, 2 x Digital Out just for system jobs• 1 x switching relays (for door strike, alarm,…)
Option for host connection• 1 x RS485 (opto-decoupled) or• 1 x V.24 (not opto-decoupled)
Option for reader• 2 x RS485 LBus (opto-decoupled) for one reader
Aug 2018Topology INTUS 11
standard
option
4 x DO
Ethernet
2 x RS485 (LBus)
4 x DI/2xDO (system)
1 x ser. module (host)
1 x bistab. relays
8 x DI
2 x RS485 (LBus)
INTUS ACM80e Rack – connections.
Standard• 1 x Ethernet 10/100 BaseT• 16 x Digital Out• 16 x Digital In • 8 x RS485 / LBus protocol
• 4 x digital in, 4 x digital out only for system tasks (activating, alarm,…)
Option for host connection• 1 x RS485 (opto-decoupled) or• 1 x V.24 (not opto-decoupled)
Option for readers• 1 x RS485 LBus (opto-decoupled) for
connection of further 1–8 readers
Aug 2018Topology INTUS 12
Ethernet
8 x RS485 (LBus)
16 x DO
16 x DI
1 x RS485 (LBus)
1 x ser. module (host)
standard
option
4 x DI/ 4xDO (System)
INTUS ACM80e Wand – connections.
Standard• 1 x Ethernet 10/100 BaseT• 16 x Digital Out• 16 x Digital In • 8 x RS485 / LBus protocol,
unlocked for 4 readers
• 4 x digital in, 4 x digital out only for system tasks (activating, alarm,…)
Option for host connection• 1 x RS485 (opto-decoupled) or• 1 x V.24 (not opto-decoupled)
Option for readers• Unlock reader 5-8• 1 x RS485 LBus (opto-decoupled) for
connection of further 1–8 readers
Aug 2018Topology INTUS 13
4(+4) x RS485 (LBus)
Ethernet
16 x DO
16 x DI
1 x RS485 (LBus)
1 x ser. module (host)
standard
option
4 x DI/ 4xDO (system)
Combined access control and time & attendance with one door.
Connection of one door to the INTUS 5200• Line length: max. 10m• Reader module: connection reader.
If mounting the INTUS 5200 directly beside the door also the integrated reader can be used
• Digital Output: Connection of door strike• Digital Inputs: Connection of door contact and/or
frame contact• Power Supply: Local power supply separately for
reader and door opener
Aug 2018Topology INTUS 14
RS485 (2 wire)
DO: door strike
DI: door contact
Ethernet
DI: frame contact
10m
PS PS
Access control for one door with I/O module.
Connection of one doorto the INTUS 5300• Line length:
terminal – reader: max. 10 mreader – I/O module: max. 5 m
• I/O module: connection to reader via I2C bus.• Digital Output: Connection of door strike• Digital Inputs: Connection of door contact
and/or frame contact• Power Supply: Local power supply for reader,
I/O Module and door strike
Aug 2018Topology INTUS 15
RS485 (2 wire) – LBus
DO:
door strike
DI:
door contact
Ethernet
DI: frame contact
10m
PS
I/O-MI2C
5m
Access control for one door with I/O module.
Connection of one doorto the INTUS ACM80e• Line length:
ACM80e – reader: max. 1.200 mreader – I/O module: max. 5 m
• I/O Module: connection to reader via I2C bus.• Digital Output: Connection of door strike• Digital Inputs: Connection of door contact
and/or frame contact• Local Power Supplies:
for INTUS 620/420/520IP reader 1-4 (supply also for I/O modules) and door strike
Aug 2018Topology INTUS 16
RS485 (2 wire) – LBus
DO:
door strike
DI:
door contact
Ethernet
DI: frame contact
1.200m
PS PS
I2C
5m
reader + I/O Module 1…4
(door 1 and 2)
reader + I/O Module 5…8
(door 3 and 4)
I/O-M
Combined access control and time & attendance with 8 up to 16 doors.
Connection of 8 / 16 RFID readers to the INTUS 5600• Line length: max. 200m
(depending on cable cross-section)• LBus: Connection of 1–8 readers per LBus (max. 2 LBus)• I/O Module: Connection of door strike and door contact• Local Power Supplies:
separately for reader (also for I/O module) and door strike
Aug 2018Topology INTUS 17
200m
Ethernet
LBus 1
8
1
PS
2
.
.
.
16
9
10
.
.
.
LBus 2
PS
I/O-M
Two doors with enhanced safety requirements.
Connection of two doors to INTUS ACM40 • Enhanced safety requirement by control of the
door contact and frame contact as well as additionally scanning of the fingerprints with INTUS 600FP
• Line length: max. 200m(depending on cable cross-section)
• Power Supply : INTUS 600FP and door strike by the INTUS ACM40
• Control of door contacts and door opener via Digital-In / Digital-Out interfaces
Aug 2018Topology INTUS 18
Ethernet
RS485 (2 wire) LBus + supply
DO: door strike + supply
DI: door contact
DI: frame contact
200m
Two doors with very high safety requirements.
Connection of two doors to theINTUS 1600PS • Very high safety requirement by control of the door
contact and frame contact as well as additionally authentication of the palm veins with INTUS 1600PS
• Line length: max. 200m100m door – INTUS PS controller100m INTUS PS controller – ACM40
• Power Supply : INTUS 1600PS by the INTUS PS Controller, door opener by INTUS ACM40
• Control of door contacts and door opener via Digital-In / Digital-Out interfaces
Aug 2018Topology INTUS 19
Ethernet
Cat 5 cable + supply
DO: door opener + supply
DI: door contact
DI: frame contact
100m
LBus
100m
PS-
Controller
INTUS
ACM40
16 doors on several floors.
Connection of four doors to four INTUS ACM40 with direct control• Enhanced safety requirement by control of the door
contact and frame contact as well as additionally requesting the PIN on the readers
• Line length: max. 200m using non-opto-decoupled readers (depending on cable cross-section)
• Reader: INTUS 600 with PIN keypad• Power Supply: Readers and door strikes via INTUS
ACM40• Control of door contacts and door opener via Digital-In /
Digital-Out interfaces
Aug 2018Topology INTUS 20
Ethernet
1. floor 2. floor 3. floorgroundLBus+
supplyDO+
supplyDI
Connection of 16 doors on two floors.
Connection of eight doors each via INTUS ACM80e Wall with direct control• Line length: max. 200m using non-opto-
decoupled readers (depending on cable cross-section)
• Power Supply: Readers and door strikes via INTUS ACM80e
Aug 2018Topology INTUS 21
Ethernet
1. floor 2. floor
LBus+supply
DO+supply
DI
Connection of 16 doors via second LBus.
Connection of additional eightdoors via LBus2 of the INTUS ACM80e• Point-to-point connection of the
reader 1–8 via eight standard LBus interfaces• Multipoint connection of reader 9–16 via the optional LBus2
interface• Control of 16 door strikes and the
16 door contacts by the 16 standard Digital-In/Digital-Out interfaces
• Line length: max. 200m (depending on cable cross-section)• Power Supply:
- reader 1–8 and door strikes via INTUS ACM80e- reader 9–16 and door strikes with separately local power supply
Aug 2018Topology INTUS 22
Ethernet
LBus2
LBus+supply
DO+supply
DI
1
9
10
11
12
13
14
15
16
200m
23
45
67
8
PSPS
Connection of 16 doors via eight LBus interfaces.
Connection of 16 doorsvia LBus of the INTUS ACM80e• Combined Point-to-point and multipoint connection
of the reader 1–16 via eight standard LBus interfaces
• Multipoint connection: max. 8 readers on 4 LBus interfaces
• Control of 16 door strikes and the 16 door contacts by the 16 standard Digital-In/Digital-Out interfaces
• Line length: max. 200m (depending on cable cross-section)
• Power Supply: - reader 1–8 and door strikes via INTUS ACM80e - reader 9–16 and door strikes withlocal power supply
Aug 2018Topology INTUS 23
Ethernet
LBus 1
DO
DI
1
200m
2 3
8
9
16
LBus 2
LBus 3
LBus 4
Access control center in a 19“ rack for 32 doors.
Four INTUS ACM80e in a 19 rack with
Panel PC
Patchpanels
Four INTUS ACM80e access control managers
USV (Uninterruptible power supply)
Aug 2018Topology INTUS 24
LBus
LBus
LBus
LBus8
8
8
8
UPS
Patch Panel
PC
Patch Panel
ACM80e
ACM80e
Patch Panel
Patch Panel
ACM80e
ACM80e
Access control center in a 19“ rack for 64 doors.
Four INTUS ACM80e in a 19” rack and use ofLBus2 interfaces
Using the second LBus interface up to 64 readers can be connected.
LBus1: with point-to-point
LBus2: with multipoint
Aug 2018Topology INTUS 25
UPS
Patch Panel
PC
Patch Panel
ACM80e
ACM80eLBus2
9 16
8 LBus11 8
LBus241 48
8 LBus133 40
LBus257 64
8LBus149 56
LBus225 32
8LBus117 24
Patch Panel
Patch Panel
ACM80e
ACM80e
100% galvanic isolation.
Potential difference in industrial environment• 100% secure with large potential difference
between access control manager and remote building / gate
• Line length: more than 1 km; depending on used technology also several kilometers possible
• Digital In / Digital Out for gate control by local I/O module in secure area
• Power Supply: local power supply of I/O module and reader
Aug 2018Topology INTUS 26
Ethernet
P
>1km
fiber opticI/O
PS
Remote gate control.
Large distance reader – access card• Line length INTUS ACM40 –
gate: 150m (depending on cable cross-section)
• Reader: TagMaster long-distance reader
• Distance reader – card: 2-3 m typically
• Power Supply: local power supply of the readers
Aug 2018Topology INTUS 27
Ethernet
3m
LBus
LBus
DO
DO
P PSP PS
Video documentation of critical access points.
Video documentation• Automatic video recording of unauthorized
access attempts• Control of two doors with INTUS ACM40• Pick up of the pictures from the video server
starting with INTUS COM version 3.2
Aug 2018Topology INTUS 28
Ethernet
LBus
DO
DI
INTUS
ACM40
Videoserver
Convision
NVS basic
Video surveillance with network cameras.
Aug 2018Topology INTUS 29
Ethernet
CONVISION NVS 19“ -8
with SeeTec server
SeeTec client CONVISION CC-7433
network cameraCONVISION CC-7333
network camera
CONVISION CC-7634
network camera
Video surveillance with status information.
Aug 2018Topology INTUS 30
EthernetC
on
tro
l lev
elR
ead
er /
sub
term
inal
s
Su
per
visi
on
leve
l
SeeTecClient
ADAM-6060 module
6 input/ 6 output
DO DIDI
ADAM-6050 module
12 input / 6 output
SeeTecServer
CONVISION
CC-7433
Video surveillance with analog and network cameras.
Aug 2018Topology INTUS 31
Ethernet
CONVISION NVS 19“ -8
with SeeTec Server
SeeTec Client
analog camera
AXIS M7011
1 channel video encoder
analog camera
coax or
2 wire
AXIS P7216
16-channel video encoder
CONVISION CC-7634
network camera
CONVISION CC-7433
network camera
CONVISION CC-7333
network camera
Integration of existing analog cameras
Recommended wiring of analog cameras.
Aug 2018Topology INTUS 32
2-wire transmitter
receiver
A.C.
power supply 24V
2-wire transmitter
sender
voltage adapter
(for 12V cameras)
~230V
RS485 control lines
(for controllable cameras)
Cat 5 or Cat 6 cable
4 pairs of wire
outdoor
installation box
AXIS M7011
video encoder
License Plate Recognition (LPR).
Aug 2018Topology INTUS 33
SeeTec Cayuga S100/Infinity (X)
SeeTec License Plate Recognition
ARH ParkIT
License plate camera
DO
Ethernet
Vehicle Access Control – based on LPR.
Aug 2018Topology INTUS 34
SeeTec Cayuga S100/Infinity (X)
SeeTec License Plate Recognition
ARH ParkIT
license plate camera
DO
Ethernet
Access control software
DO DI
DO
DI
Access Control Manager
INTUS ACM80e
Access reader
INTUS 620
Attachment.
Color definitions of the connection R G B
Ethernet light brown 255 204 102
LBus / RS485 2 wire / V.24 4 wire light green 99 198 0
DI orange 255 102 0
DO blue-grey 132 151 176
Cat5 + power (INTUS PS) blue 0 102 255
DI or DO black 0 0 0
Coax / 2 wire (analog video) purple 204 0 204
Aug 2018Topology INTUS 35