TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

Embed Size (px)

Citation preview

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    1/86

    ZXWN CS Alarm Management

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    2/86

    Contents

    1 Introduction to Alarms....................................................................................................................................1

    2 Alarm Monitoring............................................................................................................................................9

    3 Alarm Settings................................................................................................................................................13

    4 Alarm Operations...........................................................................................................................................55

    i

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    3/86

    1 Introduction to Alarms

    1.1 Common Alarm Terms

    Description

    Every alarm term has its specific meaning. Knowing the alarm terms preciously can help

    to correctly perform various operations on the alarms.

    Alarm

    Alarms are various faults or alerting information that occurs during the running of the

    system. Operation and maintenance personnel should perform corresponding operations

    based on the specific alarms.

    Current Alarm

    If the system generates an alarm and that alarm persists, then this kind of alarm is called

    the current alarm.

    History Alarm

    If the system generated an alarm, but the fault has been eliminated later. This kind of

    alarm is called the history alarm.

    Alarm Recovery

    The alarm recovery information indicates that the system has been faulty, but the fault

    has been eliminated at present.

    Alarm Level

    The alarm level indicates the severity of an alarm.

    Alarm Code

    It is an indicator to distinguish various alarms. Different alarms correspond to different

    alarm codes.

    Alarm Management System

    The alarm management system is the system maintenance tool of the OMM system. It

    performs the centralized monitoring on the running condition of the whole system and

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    4/86

    collects the unexpected information of the boards, links, databases and servers.

    Fault Management System

    The fault management system timely displays the correct fault information to the

    administrator.

    Notification

    The notification information means the operation or unexpected information that occurs

    and does not affect the system.

    Alarm Filtering

    It is used to filter a certain level or some types of alarm information through certain

    settings.

    1.2 Alarm Management

    Definition

    The alarm management function is a function group that manages the faults occurring to

    the network equipment managed by the ZXWN network management system during the

    system running. This function group generally calls the managed faults as alarms.

    Functions

    The alarm management function enables users to monitor and manage the faults and

    events in the whole network in a centralized manner. Users can monitor and view the

    alarms in the network in real time or even filter the unwanted alarms based on certain

    conditions. Alarms can be presented in a vivid manner to the network maintenance staff,

    such as audible alarms, visual alarms and alarm boxes.

    After an alarm is generated, the user can perform such operations as

    acknowledging/unacknowledging it, clearing it, informing someone through the Email or

    Short Messages (SM), and viewing its detailed information and related events. If the user

    has summarized the processing methods of alarms and saved them in the alarm

    processing suggestion library, the user can also view the corresponding suggestions to

    shorten the time spent on troubleshooting when similar alarms occur next time.

    The alarm management function is capable of monitoring and managing alarms and

    notification messages in the network in a centralized manner.

    Alarm Categories

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    5/86

    Chapter 4 Alarm Operations

    According to the severity, alarms fall into critical alarms, major alarms, minor

    alarms and warnings.

    According to the fault types, alarms fall into the processing alarm, the Quality of

    Service (QoS) alarm, the environment alarm, the equipment alarm, the

    communication alarm, and the network management system alarm.

    According to the system types, alarms fall into the security alarm, the alarm box

    and OMM communication link alarm, the billing server alarm, the SORM server

    alarm, the foreground/background communication link alarm, the MP NE

    Equipment Alarm, the system management alarm, the correlation alarm and the

    performance alarm.

    1.3 Alarm System

    1.3.1 Structure Description

    Introduction

    The ZXWN MSC Server has a relatively complete alarm system, including the

    foreground alarm system, the OMM server alarm system, the OMM client alarm system

    and the alarm box.

    System Structure

    The alarm system diagram is shown in Fig 1.3 -1. For detailed information, see Table

    1.3 -1.

    3

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    6/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 1.3-1 Alarm System Diagram

    Table 1.3-1 Components and Functions Introduction

    Alarm System Function

    MSCS ForegroundAlarm System

    Collects and processes foreground alarm information;

    Executes background man-machine commands andreturn execution results

    OMM Server AlarmSystem

    Processes, stores and forwards the information;

    Controls the alarm box

    OMM Client AlarmSystem

    Displays, searches and prints the alarm information;

    Displays rack charts;

    Executes man-machine commands.

    Alarm Box

    Receives the alarm information from the backgroundthrough the Ethernet interface. The alarm box can

    prompt the fault during the running of the systemthrough such various modes as sound, light, screen

    display, the SM and file transfer.

    1.3.2 Alarm and Warning Processing Mechanism

    Definition

    As the system maintenance tool, the alarm processing mechanism performs centralizedmonitoring on the running condition of the ZXWN MSC Server and collects the

    abnormal information of boards, links, databases and servers in real time.

    For some system performance data, such as the CPU occupancy, the warning threshold

    can be set by setting the critical value. When the onsite equipment just becomes

    abnormal but not faulty, use the monitoring tool to send abnormal warning information

    out through the alarm box. In this way, the corresponding maintenance personnel can

    know the system running condition in time and eliminate the fault.

    Processing flow

    The processing flow of the alarm and the warning is shown in Fig 1.3 -2.

    4

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    7/86

    Chapter 4 Alarm Operations

    Fig 1.3-2 Structure of Warning System

    Flow description

    The OMM alarm management system sends the alarm (its level can be set) and warning

    information to the alarm box. The Mobile Station (MS) module of the alarm box converts

    the alarm into a SM, and then transmits it to a series of MS numbers, including the MS

    module of the alarm processing server, the local ZTE office personnel and relative

    personnel of the carrier.

    After receiving the alarm or warning SM, the alarm processing server converts the SM

    into the alarm or warning information, and generates an Email through the mail protocol

    and then sends it to the personnel among the predefined Email list; or re-generates a SM

    and then sends it to the personnel among the SM receiving list predefined in the alarm

    processing server.

    5

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    8/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    1.4 Alarm Information

    1.4.1 Alarm Description

    Description

    The alarm management system performs centralized monitoring on the running condition

    of the ZXWN MSC Server and collects the abnormal information of the boards, links,

    databases and servers in real time. When the system is faulty or some indices exceed the

    predefined threshold, the alarm management system will generate an alarm at once. The

    operation and maintenance personnel can locate and eliminate the fault through the alarm

    information to ensure the stable running of the system.

    Alarm Level

    The alarm information can be divided into four levels based on severity.

    Level-1: critical

    Level-2: major

    Level-3: minor

    Level-4: warning.

    1.4.2 Relation between Alarms and Services

    Description

    The alarm system monitors the running condition of the whole system in real time. When

    a certain part of the system becomes abnormal, the alarm system will give an alarm. The

    alarm information level indicates the alarm severity.

    Relation

    Among all kinds of alarm information, the service alarm information is the altering

    information generated for the service faults that occurred or will occur, or the faults that

    affect the service during the running of the ZXWN MSC Server. Usually, an alarm will

    exist for a period of time until the problem or the fault is handled.

    1.4.3 Relation between Alarms and Faults

    The alarm information is the alerting information generated for the problems or faults

    that occur during the running of the ZXWN MSC Server. The alarm management system

    should timely show the correct fault information to the administrator when the fault

    6

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    9/86

    Chapter 4 Alarm Operations

    occurs. Usually, an alarm will exist for a period of time until the problem or the fault is

    handled.

    1.4.4 Handling Measures

    The handling measures for alarms of different levels are described as follows.

    When level-1 or level-2 alarms appear, the alarm system will send the alarm

    information to the corresponding personnel as soon as possible through the alarm

    box monitoring alarm, SM monitoring alarm, Email monitoring alarm and

    background monitoring alarm, so that the fault can be handled in time. For those

    difficult to handle, notify the local ZTE office.

    When level-3 or level-4 alarms appear, the maintenance personnel in the equipment

    room can handle the fault according to the common processing methods after

    recording the problems and fault phenomena. If the fault cannot be eliminated,

    contact the local ZTE office for technical support.

    1.5 Notification Information

    1.5.1 Notification Information Description

    The notification information indicates the operation or abnormal information that has

    occurred, helping the maintenance personnel grasp the running condition of each part of

    the system. The notification information has no level and does not affect the system.

    The notification information is shown by the OMM system during the daily operation of

    the ZXWN MSCS system to prompt the system running information required by the

    maintenance personnel.

    1.5.2 Relation between Notifications and Services

    Influence Relation

    The notification information has no impact on the service.

    1.5.3 Relation between Notifications and Faults

    The notification information refers to the operations or exceptions that occurred during

    the running of the system, but had no impact on the system and the service. The fault

    brings impact on the system and service, which is required to be handled.

    7

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    10/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    8

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    11/86

    2 Alarm Monitoring

    2.1 Alarm Monitoring Policy

    Introduction

    When the onsite equipment is faulty, or becomes abnormal, the alarm management

    system sends out the alarm and warming information according to the alarm monitoring

    policies, which facilitates eliminating the fault and hidden trouble in time.

    Principle

    The alarm monitoring policies are described as follows.

    Priority policy for important alarms

    The alarm information is divided into four levels by severity. The higher the level

    is, the more serious the alarm is. When the alarms with different levels appear at the

    same time, the highest-level alarm information must be sent first.

    First time policy

    The alarm has an impact on the service. The alarm must be eliminated as soon as

    possible to quickly recover the system to the normal status and relieve the impact

    on the service. So the alarm information must be sent out as soon as possible.

    Featured by using shorter transmission time, the alarm box can send the alarm and

    warning information as soon as possible through the sound and the short message.

    Multi-receiver policy

    Multiple persons can receive the alarm information by alarm management server

    settings. In this way, it may reduce the possibility of delaying handling the fault

    because one or several persons did not receive the alarm information in time.

    Multi-way policy

    Using a single source to give an alarm will cause the alarm information unreliable

    as this procedure can become faulty. Adopting multi-way alarm monitoring policy

    can avoid this case.

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    12/86

    2.2 Alarm Report Modes

    Introduction

    The alarm reports have the following forms.

    Background monitoring alarm

    Alarm box monitoring alarm

    Short message monitoring alarm

    Multimedia Messaging Service (MMS) and Email monitoring alarm.

    Comparison

    Alarm box monitoring alarm, short message monitoring alarm, MMS monitoring alarm,

    and Email monitoring alarm must use the alarm box to transfer the information, while the

    background monitoring alarm does not.

    Besides monitoring alarms, the background monitoring alarm can query the system

    performance, while the other modes can only query the system alarm information.

    2.2.1 Background Monitoring Alarm

    Introduction

    The alarm system monitors the whole switch in real time. When a certain part of the

    switch is faulty, the alarm service process of the application server will send the message

    to the OMM server to generate the alarm or warning information.

    Functions

    The performance, running conditions and alarm information of the system can be viewed

    in detail through the background monitoring alarm, which facilitates locating and

    eliminating faults to ensure the stable running of the system.

    Query Method

    After logging in the network management system, select each sub-menu of the Alarm

    View on the main window of the alarm management, to set the alarm query conditions,

    and query the alarms.

    2.2.2 Alarm Box Monitoring Alarm

    Introduction

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    13/86

    Chapter 4 Alarm Operations

    The alarm box is the tool of the alarm monitoring system that can display the fault

    information visually and rapidly.

    Working Principle

    Connecting to the alarm box, the fault management subsystem of the OMM server

    transfers the alarm messages to the alarm box through the TCP/IP protocol, which are

    displayed on the screen and accompanied by the alarm indicator and alarm sound

    prompts.

    Functions

    The alarm box can collect the alarm (recovery)/warning information and log data of the

    equipment, and send it to the warning center. Finally, the warning center analyzes and

    processes the information, and notifies the corresponding personnel through the alarm

    short message, alarm MMS and Alarm box audible and visual information. The

    audible/visual information contains the following contents.

    Prompting the current alarm with sound

    Giving an alarm through indicators or horns

    Display relatively detailed alarm information on the screen by using the keyboard to

    turn pages.

    2.2.3 Short Message Monitoring Alarm

    Introduction

    The alarm management system sends the level-1 and level-2 alarm and warning

    information to the alarm box through the alarm management system of the OMM

    equipment. After the MS module of the alarm box converts the alarm information into

    the short message, the alarm box can also send the short message alarm to a series of

    specified MS numbers.

    Functions

    Through the short message monitoring alarm, the alarm box can send the alarm or

    warning information to the specified MS in the form of short message. The maintenance

    personnel, either from local ZTE office or the operator, can know the system running

    conditions without being on the site.

    11

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    14/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    2.2.4 MMS and Email Alarm

    Introduction

    Due to the small size of the short message, usually only 340 bits, the short message alarm

    often needs to be separated into parts before being sent, so the cost is high. The MMS can

    be adopted by performing the background settings, which can transfer 50K data at one

    time. By performing the background settings or modifying the configuration file, the

    MMS is applicable for sending the alarm information and fault logs to the mailbox or the

    mobile phone of the specified maintenance personnel through the Email server or the

    MMS center.

    12

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    15/86

    3 Alarm Settings

    3.1 Alarm Rule Settings

    Introduction

    This section describes how to set an alarm rule.

    For how to activate, pause, refresh, and delete an alarm rule, see Alarm Rule Operations.

    3.1.1 Introduction to Alarm Rules

    Type

    The alarm rule falls into the following types:

    The alarm persisting rule

    The alarm counting rule

    The alarm delaying rule

    The alarm restraining rule

    The alarm merging rule

    The alarm user filtering rule

    The alarm global filtering rule

    The alarm discarding rule

    The alarm forwarding rule

    The alarm clearing rule

    The alarm acknowledging rule

    The notification global filtering rule

    The notification discarding rule

    Valid Range

    Rule setting can contain multiple rules. The range where a rule takes effect varies with

    the type of the rule. It is called the valid range of a rule, which is divided into following

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    16/86

    four types:

    Global validity

    Once an alarm rule is set and activated, it is effective for all alarms, events and

    notifications that conform to this rule, which has no relationship with the one who

    makes it. Therefore, the alarms that all users saw are processed according to this

    rule.

    User validity

    Once an alarm rule is set and activated, it is only effective for the user who makes

    it, such as the alarm user filtering rule. It has no influence on other users.

    Forward validity

    Once an alarm is set and activated, it is effective for all current alarms, including

    the alarm that has been reported and that will be reported in the future.

    Backward validity

    Once an alarm rule is set and activated, it is only effective for the alarms that will

    be reported in the future, having no influence on the alarm that has been reported.

    Function

    Table 3.1 -2 shows the alarm rules supported by the OMM system.

    Table 3.1-2 Functions of Alarm Rules

    Rule Name Valid Range Function

    Alarm Persisting

    Rule

    Global validity;

    Backward validity

    Upgrading the alarm severity orgenerating a new alarm when theduration of acknowledging the alarmsatisfying this rule or the alarm being inthe active status exceeds that specifiedby this rule. The persisting duration isobtained by deducting the generation

    time from the acknowledging time orthe current time

    Alarm CountingRule

    Global validity;

    Backward validity

    Generating a new counting alarm,saving the reported alarms and theamount into the database, and showingthem on the Realtime Alarms window,when the amount of the current alarmsthat satisfy this rule reaches the rule-specified threshold within a period oftime specified by the rule

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    17/86

    Chapter 4 Alarm Operations

    Rule Name Valid Range Function

    Alarm DelayingRule

    Global validity;Backward validity

    Delaying showing the reported alarm

    that satisfies this rule on the RealtimeAlarms window for a period of time,which is specified by this rule

    AlarmRestraining Rule

    Global validity;

    Backward validity

    Not showing the consequential alarmspecified by this rule on the RealtimeAlarms window when the root alarm ofa current alarm exists or occurs

    Alarm MergingRule

    Global validity;

    Backward validity

    Only showing one of the alarms that

    satisfy this rule on the RealtimeAlarms window instead of all of them

    Alarm User

    Filtering Rule

    User Validity;

    Forward validity

    Not showing the alarm satisfying the

    rule on the Realtime Alarms window

    of the client of the user who set thisrule

    Alarm GlobalFiltering Rule

    Global validity;

    Backward validity

    Only saving the reported alarm thatsatisfies this rule in the database, notshowing it on the Realtime Alarmswindow of the client

    Alarm DiscardingRule

    Global validity;

    Backward validity

    Discarding the reported alarm thatsatisfies this rule directly, and neither

    saving it into the database nor showingit on the Realtime Alarms window of

    the client

    AlarmForwarding Rule

    Global validity;

    Backward validity

    Notifying the user specified in the rulethrough the Email or SMS when thereported alarm satisfies this rule

    Auto alarmclearing rules

    Global validity;

    Backward validity

    Clearing the reported alarm thatsatisfied this rule directly from thecurrent alarms, and moving it to thehistory alarm database, that is, thealarm is automatically recovered

    AlarmAcknowledgingRule

    Global validity;

    Backward validity

    Acknowledging the alarm that satisfiesthis rule when it is reported

    The notification

    global filteringRule

    Global validity;

    Backward validity

    Clearing the reported notification thatsatisfied this rule directly from theRealtime Notifications window of theclient, and moving it to the database

    NotificationDiscarding Rule

    Global validity;

    Backward validity

    Discarding the reported notification that

    satisfies this rule directly, and neithersaving it into the database nor showing

    it on the Realtime Notificationswindow of the client

    15

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    18/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    3.1.2 Setting an Alarm Persisting Rule

    Purpose

    When the duration of acknowledging an alarm or its being in the active status exceeds the

    time that specified by the alarm persisting rule, the alarm severity will be raised or a new

    alarm will be generated.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm persisting rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears, as shown in Fig 3.1 -3.

    Fig 3.1-3 Management Rule Setting

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Persisting Rule radio button, and then clickOK, as shown in Fig 3.1 -4.

    16

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    19/86

    Chapter 4 Alarm Operations

    Fig 3.1-4 Selecting Alarm Persisting Rule

    4. The Alarm Persisting Rule dialog box pops up, as shown in Fig 3.1 -5. The

    parameters on the Information page are described in Table 3.1 -3.

    17

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    20/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.1-5 Alarm Persisting Rule, Information

    Table 3.1-3 Parameter Descriptions for Alarm Persisting Rule

    Parameters Descriptions

    Name The name of an alarm persisting rule

    Description The description of an alarm persisting rule

    Persist Time The interval for an alarm persisting rule to take effect

    Persist State The persisting state of the alarm information, eitherunacknowledged state or active state

    Rule Action When the conditions of duration and state are satisfied, the

    system will automatically change the alarm severity orgenerate a new alarm.

    Alarm severity change means that the severity of an alarmchanges from the original level to the specified one when therule takes effect.

    5. Select the Selection tab, as shown in Fig 3.1 -6. Select the alarm type suitable for

    this rule.

    18

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    21/86

    Chapter 4 Alarm Operations

    NOTE:

    The left column shows the conditions distinguishing different alarm types, while the rightcolumn shows the alarm types corresponding to different alarm conditions. It is available

    to select several alarm conditions and alarm types.

    Fig 3.1-6 Alarm Persisting Rule, Selection

    6. When the setting is over, clickOKto complete creating an alarm persisting rule.

    Result

    An alarm persisting rule is created.

    3.1.3 Setting an Alarm Counting Rule

    Purpose

    An alarm counting rule setting is to set to generate a new alarm separately and report it

    when the number of same alarms has exceeded the threshold in a specified period.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm counting rule, perform the following steps.

    19

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    22/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Counting Rule radio button, and then clickOK.

    4. The Alarm Counting Rule dialog box pops up, as shown in Fig 3.1 -7. The

    parameters on the Information page are described in Table 3.1 -4.

    Fig 3.1-7 Alarm Counting Rule, Information

    Table 3.1-4 Parameter Descriptions for the Alarm Counting Rule

    Parameters Descriptions

    Name The name of a rule

    Description Details of a rule

    20

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    23/86

    Chapter 4 Alarm Operations

    Parameters Descriptions

    If in _ _ there are _

    suitable alarms,then new a _ alarmautomatically

    The duration for the rule to take effect, meaning that a

    new alarm of specified severity is generated when thespecified number of alarms is generated within specifiedtime.

    New AlarmInformation

    The description of the new generated alarm

    5. Select the Selection tab, as shown in Fig 3.1 -8. Select the alarm type suitable for

    this rule.

    NOTE:

    The left column shows the conditions distinguishing different alarm types, while the right

    column shows the alarm types corresponding to different alarm conditions. It is available

    to select several alarm conditions and alarm types.

    Fig 3.1-8 Alarm Counting Rule, Selection

    6. Click OKto complete setting an alarm counting rule.

    Result

    21

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    24/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    An alarm counting rule is created.

    3.1.4 Setting an Alarm Delaying Rule

    Purpose

    The alarm delaying rule allows a user to defer showing some unimportant alarms. If the

    alarm is automatically recovered within the specified period, it will not be displayed any

    longer.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm delaying rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select theAlarm Delaying Rule radio button, and then clickOK.

    4. The Alarm Delaying Rule dialog box pops up, as shown in Fig 3.1 -9. Enter

    Name, Description and Delay Time, and select the alarm filtering conditions on

    the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    22

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    25/86

    Chapter 4 Alarm Operations

    Fig 3.1-9 Alarm Delaying Rule

    5. When the setting is over, clickOKto complete setting an alarm delaying rule.

    Result

    An alarm delaying rule is created.

    3.1.5 Setting an Alarm Restraining Rule

    Purpose

    When the system generates a root alarm and a consequential alarm at the same time, the

    alarm restraining rule allows a user to set that only the root alarm is reported and also to

    set whether to report the consequential alarm after the root alarm is recovered according

    to the requirements.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm restraining rule, perform the following steps.

    23

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    26/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Restraining Rule radio button, and then clickOK.

    4. The Alarm Restraining Rule dialog box pops up, as shown in Fig 3.1 -10. Enter

    the Name and Description.

    Fig 3.1-10 Alarm Restraining Rule

    5. On the Root alarm area, click the Setting button to pop up the Root alarm dialog

    box, as shown in Fig 3.1 -11

    NOTE:The left column shows the conditions distinguishing different alarm types, while the right

    column shows the alarm types corresponding to different alarm conditions. It is available

    to select several alarm conditions and alarm types.

    24

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    27/86

    Chapter 4 Alarm Operations

    Fig 3.1-11 Root Alarm

    6. Click OKafter the setting is over. Return to the Alarm Restraining Rule dialog

    box.

    7. Click New on the Consequential alarm area, to pop up the Consequential alarm

    dialog box, as shown in Fig 3.1 -12.

    Fig 3.1-12 Consequential Alarm Dialog Box

    8. Click OKafter the setting is over. Return to the Alarm Restraining Rule dialog

    box.

    25

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    28/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    9. Click OKto complete the setting of an alarm restraining rule.

    Result

    An alarm restraining rule is created.

    3.1.6 Setting an Alarm Merging Rule

    Purpose

    An alarm merging rule allows the system to merge the alarms of the same type generated

    within a certain position range. And then, only one of them is reported.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm merging rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar to pop up the New dialog box. Select the Alarm

    Merging Rule radio button, and then clickOK, as shown in Fig 3.1 -13.

    26

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    29/86

    Chapter 4 Alarm Operations

    Fig 3.1-13 Selecting Alarm Merging Rule

    4. The Alarm Merging Rule dialog box pops up. EnterName and Description, and

    select the alarm merging conditions on the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    5. After completing the settings, clickOKto complete creating an alarm merging rule.

    Result

    An alarm merging rule is created.

    3.1.7 Setting an Alarm User Filtering Rule

    Purpose

    An alarm user filtering rule only takes effect on the current client. If the client receives an

    alarm reported by the server, it uses the filter conditions of the login user to filter alarms.

    27

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    30/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    The selected alarms will be discarded by the client and not be displayed in the alarm list

    or counted as the alarms of an NE.

    A user filtering rule is valid only for a specific login user and will not take effect on the

    clients that other users log in.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm user filtering rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm User Filtering Rule radio button, and then clickOK.

    4. The Alarm User Filtering Rule dialog box pops up, as shown in Fig 3.1 -14.

    Enter Name and Description, select For User parameter, and select the alarm

    filtering conditions on the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    28

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    31/86

    Chapter 4 Alarm Operations

    Fig 3.1-14 Alarm User Filtering Rule

    5. When the setting is over, clickOKto complete setting an alarm user filtering rule.

    Result

    An alarm user filtering rule is created.

    3.1.8 Setting an Alarm Global Filtering Rule

    Purpose

    An alarm global filtering rule is used to filter alarms during pre-processing of alarms.

    The chosen alarms will not be sent to the client.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm global filtering rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    29

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    32/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Global Filtering Rule radio button, and then clickOK.

    4. The Alarm Global Filtering Rule dialog box pops up, as shown in Fig 3.1 -15.

    Enter Name and Description, and select the alarm filtering conditions on the

    Selection area.

    NOTE:

    In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    Fig 3.1-15 Alarm Global Filtering Rule

    5. When the setting is over, clickOK to complete setting an alarm global filtering

    rule.

    30

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    33/86

    Chapter 4 Alarm Operations

    Result

    An alarm global filtering rule is created.

    3.1.9 Setting an Alarm Discarding Rule

    Purpose

    An alarm discarding rule is used to filter the alarms during the alarm collection. The

    selected alarms are neither saved in the database nor displayed in the Realtime Alarms

    window.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm discarding rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Discarding Rule radio button, and then clickOK.

    4. The Alarm Discarding Rule dialog box pops up, as shown in Fig 3.1 -16. Enter

    Name and Description, and select the alarm filtering conditions on the Selection

    area.

    NOTE:

    In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    31

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    34/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.1-16 Alarm Discarding Rule

    5. When the setting is over, clickOKto complete setting an alarm discarding rule.

    Result

    An alarm discarding rule is created.

    3.1.10 Setting an Alarm Forwarding Rule

    Purpose

    An alarm forwarding rule is used to forward the matched alarm to the corresponding

    destination when alarms are reported.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm forwarding rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    32

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    35/86

    Chapter 4 Alarm Operations

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Forwarding Rule radio button, and then clickOK.

    4. The Alarm Forwarding Rule dialog box pops up, as shown in Fig 3.1 -17. Enter

    the Name and Description on the Information page.

    Fig 3.1-17 Alarm Forwarding Rule Dialog Box

    5. From the List of Forwarded-to Users area, click the Custom button to pop up

    the Setting a Forwarded-to User dialog box. Enter Forwarding User, Email

    Address and Phone Number, as shown in Fig 3.1 -18.

    33

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    36/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.1-18 Customizing a Forwarded-to User

    NOTE:ClickSelect to add a user who already exists in the system to the List of Forwarded-

    to Users.

    6. Click OK to add the customized forwarded-to user to the List of Forwarded-to

    Users, as shown in Fig 3.1 -19.

    Fig 3.1-19 Customized Forwarded-to User List

    34

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    37/86

    Chapter 4 Alarm Operations

    7. Select the Selection tab, as shown in Fig 3.1 -20. Select the alarm type suitable for

    this rule.

    NOTE:The left column shows the conditions distinguishing different alarm types, while the right

    column shows the alarm types corresponding to different alarm conditions. It is available

    to select several alarm conditions and alarm types.

    Fig 3.1-20 Alarm Forwarding Rul, Selection

    8. Click OKto complete the setting of an alarm forwarding rule.

    Result

    An alarm forwarding rule is created.

    3.1.11 Setting an Alarm Clearing Rule

    Purpose

    An alarm clearing rule is used to automatically clear the matched alarms when alarms are

    reported. That is, alarm clearing information is added automatically and the reported

    alarms directly become history alarms and are saved in the data table of history alarms.

    In this way, the system can record the alarms and reduce the number of current alarms as

    35

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    38/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    well, so that the maintenance personnel can better focus their attentions on important

    alarms.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm clearing rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting. The

    Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Alarm Clearing Rule radio button, and then click OK.

    4. The Alarm Clearing Rule dialog box pops up, as shown in Fig 3.1 -21. Enter Name

    and Description, and select the alarm filtering conditions on the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    36

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    39/86

    Chapter 4 Alarm Operations

    Fig 3.1-21 Alarm Clearing Rule

    5. After setting all filtering conditions, clickOKto complete setting an alarm clearing

    rule.

    Result

    An alarm clearing rule is created.

    3.1.12 Setting an Alarm Acknowledging Rule

    Purpose

    An alarm acknowledging rule is used to automatically acknowledge the matched alarms

    when alarms or alarm recovery messages are reported. In this way, the system reduces

    the workload of network management personnel and enables them to focus more on

    important alarms. Through the alarm acknowledging rule, the system will automatically

    set the acknowledgement state, time and information of alarms.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm acknowledging rule, perform the following steps.

    37

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    40/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar to pop up the New dialog box. Select the Alarm

    Acknowledging Rule radio button, and then clickOK.

    4. The Alarm Acknowledging Rule dialog box pops up, as shown in Fig 3.1 -22.

    EnterName and Description, select the acknowledgement parameter, and select the

    alarm filtering conditions on the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    Fig 3.1-22 Alarm Acknowledging Rule

    5. Click OKto complete setting an alarm acknowledging rule.

    38

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    41/86

    Chapter 4 Alarm Operations

    Result

    An alarm acknowledging rule is created.

    3.1.13 Setting a Notification Global Filtering Rule

    Purpose

    A notification global filtering rule is used to filter the notifications during the notification

    collection. The selected notifications are not displayed in the Realtime Notification

    interface, but they are saved in the database.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set a notification global filtering rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.

    The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Notification Global Filtering Rule radio button, and then click OK.

    4. Click OK, the Notification Global Filtering Rule dialog box pops up, as shown in

    Fig 3.1 -23. Enter Name and Description, and select the notification filtering

    conditions on the Selection area.

    NOTE:

    In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    39

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    42/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.1-23 Notification Global Filtering Rule

    5. When the setting is over, clickOKto complete setting a notification global filtering

    rule.

    Result

    A notification global filtering rule is created.

    3.1.14 Setting a Notification Discarding Rule

    Purpose

    A notification discarding rule is used to filter the notifications during the notification

    collection. The selected notifications are neither saved in the database nor displayed in

    the Realtime Notification window.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set a notification discarding rule, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    40

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    43/86

    Chapter 4 Alarm Operations

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Management Rule Setting.The Management Rule Setting page appears.

    3. Click the icon on the toolbar, and the New dialog box pops up. Select the

    Notification Discarding Rule radio button, and then clickOK.

    4. The Alarm Acknowledging Rule dialog box pops up, as shown in Fig 3.1 -24.

    Enter Name and Description, and select the alarm filtering conditions on the

    Selection area.

    NOTE:

    The left column shows the conditions distinguishing different alarm types, while the right

    column shows the alarm types corresponding to different alarm conditions. It is available

    to select several alarm conditions and alarm types.

    Fig 3.1-24 Notification Discarding Rule

    5. When the setting is over, clickOK to complete setting a notification discarding

    rule.

    Result

    A notification discarding rule is created.

    41

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    44/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    3.2 Redefining Alarm Severity

    Purpose

    Each alarm corresponds to an alarm level. Alarms are divided into the following four

    levels based on the severity: critical alarms, major alarms, minor alarms and warning.

    The default severity has been set for each alarm during the system initialization.

    Redefining the severity is to modify the alarm severity as required during the running of

    the system.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To redefine the severity of an alarm, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Severity Regrading Setting

    to pop up the Severity Regrading Setting page, as shown in Fig 3.2 -25.

    Fig 3.2-25 Severity Regrading Setting

    3. After the System type is selected, all alarms corresponding to this system type will

    42

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    45/86

    Chapter 4 Alarm Operations

    be displayed on the Severity Redegrading Setting page automatically, as shown in

    Fig 3.2 -26.

    Fig 3.2-26 Alarm List

    4. Select the alarm item whose severity is to be redefined. Select the new severity

    from the drop-down list ofNew Severity, as shown in Fig 3.2 -27.

    Fig 3.2-27 Alarm Severity List

    5. Click the icon on the toolbar to save the modification on the server. At this

    time, the mark on the Modify Status column will be cleared automatically, as shown in

    43

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    46/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.2 -28.

    Fig 3.2-28 Completing Severity Redefinition

    3.3 Setting the Alarm Sound

    Purpose

    Setting the alarm sound is to specify the alarm sound for each alarm level that is given on

    the network management client.

    NOTE:By default, the sound mode is set as Silence.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the sound file exists, whose default format is *.wav.

    Steps

    To set the alarm sound, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Preferences to pop up the

    Preferences dialog box. On the Alarm Sound Setup page, select the sound mode

    from the Sound Mode drop-down list in each alarm level area. The sound mode

    falls into the continuous sound and the short beeps. At this time, the Select and Play

    buttons next to the Sound File text box are activated, as shown in Fig 3.3 -29.

    44

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    47/86

    Chapter 4 Alarm Operations

    Fig 3.3-29 Preferences, Alarm Sound Setup

    3. Click the Select button to select the sound file. Click the Play button to play the

    selected alarm sound.

    4. Click OKto complete the settings.

    3.4 Setting an Alarm ColorPurpose

    Setting an alarm color is to specify the color for each alarm level that is displayed on the

    network management client. Use different colors to distinguish the alarm severity.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    45

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    48/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    To set an alarm color, perform the following steps.

    1. In the main window of the network management client, choose View > FaultManagement. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Preferences to pop up the

    Preferences dialog box. Select the Alarm Color Setup tab, as shown in Fig 3.4

    -30.

    Fig 3.4-30 Preferences, Alarm Color Setup

    3. On the Alarm Color Setup page, set the alarm colors of different alarm severities.

    4. Click OKfor the system to save the color parameters that have been set.

    3.5 Setting a Forwarding Template

    Purpose

    Setting a forwarding template is to set the information format of the forwarded SM and

    Email, so that the system alarm information can be sent to the specified mobile phone or

    46

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    49/86

    Chapter 4 Alarm Operations

    mailbox through the SM or Email.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To set a forwarding template, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Preferences to pop up the

    Preferences dialog box. Select the Forward Template Setup tab, as shown in Fig

    3.5 -31. Check and recover the settings of the forwarding template of the short

    message and Email title and content.

    Fig 3.5-31 Preferences, Forward Template Setup

    3. In the Setup the forwarding content template of the mail area, input [ to select

    the required parameters from the pop-up choice box, as shown in Fig 3.5 -32.

    47

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    50/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    NOTE:

    The operation to set the forwarding template of the handset short message andforwarding title template of the mail are similar to this operation.

    Fig 3.5-32 Setting Email Forwarding Content Template

    4. Click OKfor the system to save the forwarding template parameters.

    3.6 Setting an Alarm Box

    Purpose

    Setting an alarm box is necessary for normally reporting the system alarm information to

    the alarm box.

    Prerequisite

    48

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    51/86

    Chapter 4 Alarm Operations

    Confirm that the user has logged in the network management server normally.

    Steps

    To set an alarm box, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Alarm Box Setting. The

    Alarm Box Setting page appears, as shown in Fig 3.6 -33.

    Fig 3.6-33 Alarm Box Setting

    3. Click the icon on the page to pop up the Alarm Box Detail dialog box, as

    shown in Fig 3.6 -34.

    For the details of the alarm box settings, refer to Table 3.6 -5.

    49

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    52/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.6-34 Setting Information of the Alarm Box

    Table 3.6-5 Alarm Box Information Parameters

    Parameters Description

    Alarm Box Name The name of the alarm box, which must be input.

    Alarm Box DescriptionThe description of the alarm box. Input the parameter

    as required

    Initial StateSelects the initial state of the alarm box, eitherEnable or Disable. When selecting Enable, the alarm

    box works normally.

    Alarm Box IPThe IP address of the alarm box, which is in the samenetwork segment as the address of the network

    management server, which must be input.

    Server PortThe port number for alarm box for communicatingwith the server is 6700.

    50

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    53/86

    Chapter 4 Alarm Operations

    Parameters Description

    Display Alarm Severity

    Controls the alarm severity displayed on the alarm

    box, which is divided into five types: none, warningand above, minor and above, major and above andcritical.

    Speak Alarm Severity

    Sets that the alarm box gives sound corresponding toa certain level and above among all levels in thecurrent alarm pool, including none, warning andabove, minor and above, major and above and critical.

    Alarms send to AlarmBox

    Selects the alarm of a certain severity that can be

    received by the alarm box, including Critical, Major,Minor, Warning.

    4. After setting the Alarms send to Alarm Box, click the Advanced button to pop

    up the Alarm Box Rule Setting dialog box, as shown in Fig 3.6 -35.

    Fig 3.6-35 Alarm Box Rule Setting

    5. Click New in the Alarm Box Rule Setting dialog box to pup-up the Details of

    Alarm Box Rule dialog box, as shown in Fig 3.6 -36. Enter Rule Name and

    Description, and select the alarm filtering conditions on the Selection area.

    NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm

    types, while the right column shows the alarm types corresponding to different alarm

    conditions. It is available to select several alarm conditions and alarm types.

    51

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    54/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 3.6-36 Details of Alarm Box Rule

    6. Click OKto completing setting the alarm box rule. The system will add a record in

    the Alarm Box Rule Setting dialog box, as shown in Fig 3.6 -37.

    Fig 3.6-37 Completing an Alarm Box Rule

    7. Click OKto pop up the Alarm Box Detail dialog box.

    8. Click OK in the Alarm Box Detail dialog box, the system adds an alarm box

    52

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    55/86

    Chapter 4 Alarm Operations

    record in the Alarm Box Setting window, as shown in Fig 3.6 -38.

    Fig 3.6-38 Completing an Alarm Box

    9. Click the icon on the Alarm Box Setting window. The Confirm dialog box

    pops up, clickOKto activate the alarm box.

    53

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    56/86

    4 Alarm Operations

    4.1 Alarm Information Operations

    Introduction

    This section mainly describes the operations related to the alarm information.

    4.1.1 Monitoring Real-Time Alarm Information

    Purpose

    The real-time monitoring is responsible for monitoring the notifications and alarms

    (including current alarms and history alarms) in real time. Monitoring the notifications in

    real time can obtain the notification messages of the equipment and network in time.

    Monitoring current alarms in real time can obtain the alarm information of the equipment

    and network in time. Monitoring history alarms in real time reflects the processing

    conditions of alarms that have been processed or recovered in the system.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Step

    To monitor real-time alarm information, perform the following step.

    In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    For detailed procedures of monitoring the real-time information, refer to Table 4.1 -6.

    Table 4.1-6 Procedures for Monitoring the Real-time Information

    Command Detailed Procedure Description

    Realtime AlarmMonitor

    In the FaultManagement window,choose Query >Realtime AlarmMonitor to pop up theRealtime Alarmswindow

    The window is displayed incolumns. The current alarmsare being monitored in real inthe upper column; while thehistory alarms are beingmonitored in real time in thelower column

    Realtime In the Fault Notifications are being

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    57/86

    Command Detailed Procedure Description

    NotificationMonitor

    Management window,

    choose Query >Realtime NotificationMonitor to pop up theRealtime Notificationwindow

    monitored in real time on this

    window

    4.1.2 Querying Current Alarms

    Purpose

    Current alarm query is to query current alarms according to certain conditions. The

    current alarm data can be queried according to such conditions as the specified location,time, alarm severity, alarm type, status and alarm causes. These conditions can be set as

    required.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the communication between the network management server and the

    equipment is normal.

    Steps

    To query current alarms, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Query > View CurrentAlarms to pop

    up the Current Alarm Query Conditions window.

    3. Click the icon on this tab to pop up the Current Alarm Query Condition

    dialog box, as shown in Fig 4.1 -39. Specify the query conditions as required.

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    58/86

    Chapter 4 Alarm Operations

    Fig 4.1-39 Current Alarm Query Condition Dialog Box

    4. Click OKto add a query record of alarm conditions on the Current Alarm QueryConditions window, as shown in Fig 4.1 -40.

    Fig 4.1-40 Current Alarm Query Condition List

    5. After selecting a query condition on the Current Alarm Query Conditions

    window, click the icon. The View Current Alarms page pops up, listing the

    57

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    59/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    query results, as shown in Fig 4.1 -41.

    Fig 4.1-41 Query Results of Current Alarm

    4.1.3 Querying History Alarms

    Purpose

    History alarm query is to query the history alarms according to certain conditions. The

    history alarm data can be queried according to such conditions as the specified location,time, alarm severity, alarm type, status and alarm causes. These conditions can be set as

    required.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the communication between the network management server and the

    equipment is normal.

    Steps

    To query the history alarms, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Query > View HistoryAlarms to pop

    up the History Alarm Query Conditions window.

    3. Click the icon on the toolbar to pop up the History Alarm Query Condition

    dialog box, as shown in Fig 4.1 -42.

    58

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    60/86

    Chapter 4 Alarm Operations

    Fig 4.1-42 History Alarm Query Condition Dialog Box

    4. Set the query conditions as required, enterName and Description, and select the

    suitable query conditions from the Selection area. The data filtered by the system

    can be queried by selecting the Visibility check box.

    5. Click OKto add a query record of alarm conditions on the History Alarm Query

    Conditions page, as shown in Fig 4.1 -43.

    59

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    61/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.1-43 History Alarm Query Condition List

    6. After selecting a query condition on the History Alarm Query Conditions page,

    click the icon. The View History Alarmspage pops up, listing the query results.

    4.1.4 Synchronizing Alarm Information

    Purpose

    The alarm synchronization function is to synchronize the Network Element (NE) alarms.

    Users can select the system type and the NE location information to be synchronized.

    When the alarm data of the network management system are possibly inconsistent with

    those of the foreground equipment, manually synchronize the alarm data of the

    foreground equipment to the network management server through this function.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the communication between the network management server and the

    equipment is normal.

    Steps

    To synchronize alarm information, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    60

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    62/86

    Chapter 4 Alarm Operations

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Query > Alarm Synchronization topop up the Alarm Synchronization dialog box, as shown in Fig 4.1 -44. Set the

    conditions of alarm synchronization.

    Fig 4.1-44 Alarm Synchronization

    3. Click Selectbutton to set the type of system to be synchronized, as shown in Fig

    4.1 -45.

    Selecting the BILL Server radio box means synchronizing thealarms on the billing server.

    Selecting the NE Alarm radio box means synchronizing thealarms on the foreground NE equipment.

    Selecting the SORM Alarm radio box means synchronizing thealarms on the SORM server.

    61

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    63/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.1-45 System Type

    4. Click OK. The system synchronizes the alarm data in the specified location. The

    alerting box pops up when the synchronization is successful.

    4.1.5 Alarm Information Statistics

    Purpose

    The alarm statistics function provides the alarm statistics templates that are frequently

    used. Through these templates, the user can perform statistics on the alarm data from

    different angles and generate corresponding reports that can be exported to be files in

    different formats or printed directly.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To perform alarm statistics, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Query > History Alarm Statistics to

    62

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    64/86

    Chapter 4 Alarm Operations

    pop up the Report Management window. From the resource pane of the Report

    Management window, choose Report Template Tree > Server (OMM server ID)

    to pop up the List of Report Templates page, as shown in Fig 4.1 -46.

    Fig 4.1-46 Alarm Template List

    3. Double-click the required alarm statistics template from the list to pop up the

    Parameter Input Box, as shown in Fig 4.1 -47. Specify the parameters of alarm

    selection conditions and other conditions. For the parameter descriptions, refer to

    Table 4.1 -7.

    63

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    65/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.1-47 Parameter Input

    Table 4.1-7 Parameter Descriptions for Alarm Statistics

    Alarm Selection Description

    System Type Including such types as the Alarm Box Link BreakAlarm, Bill Server Alarm, Correlation Alarm, LinkAlarm, Local and RemoteOMC Linkdown Alarm, NEAlarm, Performance QoS Alarm, SORM Server Alarm,and System Management.

    Location The System Type must beselected before selecting thelocation, which is selected based on the different systemtypes.

    Alarm Code The System Type must be selected before selecting thealarm code. The available alarm codes on the right panevary with different system types.

    Severity Including critical, major, minor and warning.

    Alarm Type Including Communication Alarm, Environment Alarm,Equipment Alarm, OMS Alarm, Processing Alarm and

    QoS Alarm

    Probable Cause The System Type must be selected before selecting theprobable causes. The available probable causes on the

    64

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    66/86

    Chapter 4 Alarm Operations

    Alarm Selection Description

    right pane vary with different system types.

    Happen Time Including By Time Range and By Relative Time

    Acknowledgment

    Status

    Including Acknowledged and Unacknowledged.

    (Un)acknowledgeOperator

    Sets the operator who acknowledges/unacknowledgesalarms.

    (Un)acknowledgingTime

    Sets the range of time alarms to beacknowledged/unacknowledged.

    Restore Type Including such options as Normal, Cleared by User,Restoration upon NE Restart, Restoration uponSynchronization, Restoration upon Alarm Pool Fill-up, Restoration upon UMS Restart, Auto Cleared andRestoration upon NE Delete

    Clear Operator Sets the operator who clears alarms.

    Restore Time Sets the range of time alarms to be restored.

    Details Sets the detailed information of statistics.

    4. Click OKto start statistics. The statistical results will be listed on the View Report

    page, as shown in Fig 4.1 -48.

    Fig 4.1-48 Alarm Statistics Results

    Subsequent Optional Operations

    The subsequent optional operations are as follows.

    Viewing chart: on the toolbar of the View Report page, click the

    icon to view the statistical result through a chart.

    65

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    67/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Exporting: on the toolbar of the View Report page, click the

    corresponding icon to export and save the report in

    the corresponding file format.

    Printing: click the icon on the toolbar of the View Report pageto print the report results.

    4.2 Alarm Record Operations

    Introduction

    This section mainly describes the operations related to the alarm records.

    4.2.1 Acknowledging an Alarm

    Purpose

    Acknowledging an alarm is to change the status of an alarm from the unacknowledged

    status to the acknowledged status. Acknowledge an alarm in the unacknowledged status

    through this function when the maintenance personnel have known it and started to

    process it.

    Prerequisite

    Confirm that the queried alarm information is the one to be acknowledged.

    For the operation of querying alarms, refer to Querying Current Alarms and Querying

    History Alarms.

    Steps

    To acknowledge an alarm, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. From the alarm list of the Realtime Alarms window, right-click the alarm required

    to be acknowledged, and select Acknowledge from the short-cut menu, as shown in

    Fig 4.2 -49.

    66

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    68/86

    Chapter 4 Alarm Operations

    Fig 4.2-49 Selecting Acknowledge from the Short-cut Menu

    3. Enter the acknowledging information in the popup Acknowledge Alarm dialog box.

    Users can enter the information based on the actual alarm processing, as shown in

    Fig 4.2 -50.

    Fig 4.2-50 Acknowledging Alarm Dialog Box

    4. Click OKto acknowledge the alarm.

    Result

    The status of this alarm is changed from the unacknowledged status to the acknowledged

    status.

    67

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    69/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    4.2.2 Unacknowledging an Alarm

    Purpose

    Unacknowledging an alarm is to change the status of analarm from the acknowledged

    status to the unacknowledged status. This operation can only be performed on the alarm

    information that has been acknowledged.

    Prerequisite

    Confirm that the queried alarm information is the one to be unacknowledged. For the

    operation of querying alarms, refer to Querying Current Alarms and Querying History

    Alarms.

    Steps

    To unacknowledge an alarm, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. From the alarm list, right-click the alarm to be unacknowledged, select

    Unacknowledge from the short-cut menu.

    3. Enter the information in the popup Unacknowledge Alarm dialog box. Users can

    enter the information based on the actual alarm processing.

    4. Click OKto complete the operation.

    Result

    The status of this alarm is changed from the acknowledged status to the unacknowledged

    status.

    4.2.3 Clearing an Alarm

    Purpose

    Clearing an alarm is to clear the alarm shown in the Realtime Current Alarms page of

    the Realtime Alarms window. The cleared alarm will be automatically shown in the

    Realtime History Alarms page of the Realtime Alarms window, and can be queried by

    performing history alarm query.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    68

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    70/86

    Chapter 4 Alarm Operations

    Steps

    To clear an alarm, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Realtime Current Alarms page of the Realtime Alarms window, right-click

    the alarm to be cleared, and select Clear from the short-cut menu.

    3. The Confirm dialog box pops up. Click OKto clear the alarm. The cleared alarm

    will be automatically shown in the Realtime History Alarms page.

    Reference

    For querying the history alarm information, refer to Querying History Alarms.

    4.2.4 Forwarding an Alarm

    Purpose

    Forwarding an alarm is to forward an alarm to the other specified administrators by

    sending the SM or Email, for the administrators to handle the alarm in time.

    Prerequisite

    Confirm that the user has logged in the network management servernormally.

    Confirm that the ZXWN network management server is connected tothe Short Message Center (SMC) and the Email server normally.

    Steps

    To forward an alarm, perform the following steps:

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Realtime Current Alarms page of the Realtime Alarms window, right-click

    the alarm to be forwarded, and select Forward from the short-cut menu.

    3. The Forwarding Setup dialog box pops up, as shown in Fig 4.2 -51. Enter the

    Forwarded-to Email Address and Forwarded-to Phone Number of the

    personnel to process the alarm. It is available to select Forward by Email and

    Forward by SMS.

    When selecting the Forwarded-to Email Address check box,

    input contents in the Forward by Email page.

    69

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    71/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    When selecting the Forwarded-to Phone Number check box,input contents in the Forward by SMS page.

    Fig 4.2-51 Forwarding Setup

    4. Click OKto forward the alarm to specified personnel.

    4.2.5 Viewing Detailed Alarm Information

    Purpose

    By viewing the detailed information of alarms and referring to the corresponding

    maintenance suggestions, users can locate and handle faults in time.

    Prerequisite

    Confirm that the user has logged in the network management servernormally.

    Confirm that the queried alarm information is the one to be viewed.

    For the operation of querying alarms, refer to Querying Current Alarms and Querying

    History Alarms.

    Steps

    To view the detailed alarm information, perform the following steps:

    1. In the Realtime Current Alarms page of the Realtime Alarms window, right-click

    the alarm to be viewed, and select Details from the short-cut menu.

    70

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    72/86

    Chapter 4 Alarm Operations

    2. The Details window pops up to show the detailed information of the alarm, as

    shown in Fig 4.2 -52. For parameter descriptions, refer to Table 4.2 -8.

    Fig 4.2-52 Details

    3. Select the Maintenance suggestion tab to display the maintenance suggestions of

    the alarm, as shown in Fig 4.2 -53.

    Fig 4.2-53 Maintenance Suggestion

    71

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    73/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    4. Click Close to close the window.

    Reference

    The main contents about the alarm details are shown in Table 4.2 -8.

    Table 4.2-8 Parameter Descriptions for Alarm Information

    Parameters Description Example

    Node No. The number of the OMMnode that generates alarms

    100001

    System Type The system type of thealarm

    Link Alarm

    ID System ID 1200935849140

    Internal ID Internal number of thesystem

    1200935849141

    Location The location where alarmsare generated

    Subnet = 0,

    Ne = 1,

    Module = 1

    Alarm Code The brief description andalarm code of an alarm

    Broken link between OMCand NE (1000)

    Severity Advanced national severity Critical

    Alarm Type Alarm type Communication Alarm

    Probable Cause The probable cause of the

    alarm

    Communication abnormal (0)

    Happen Time The time when an alarm isgenerated

    2008-01-21 09:19:25

    AcknowledgmentStatus

    Acknowledged/unacknowledged status ofthe alarm

    Unacknowledged

    (Un)acknowledgeOperator

    The operator toacknowledge/

    unacknowledge this alarm

    Admin

    (Un)acknowledgeSystem

    The network managementsystem to acknowledge/unacknowledge this alarm

    100001

    (Un)acknowledgeInformation

    The information enteredwhen acknowledging/unacknowledging this alarm

    OK

    (Un)acknowledgeTime

    The time when this alarm isacknowledged/unacknowledged

    2008-01-26 14:49:25

    Comment

    Information

    The information of comment

    72

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    74/86

    Chapter 4 Alarm Operations

    Parameters Description Example

    Details Detailed information related

    to this alarm

    Netype=

    MSCServer

    Last Update Time

    NE Type The type of the NE wherethis alarm is generated

    MSCServer

    4.2.6 Printing Alarm Information

    Purpose

    The print function is used to print the alarm data among the alarm list that is opened by

    the current user. Set such items as the print range, copies, page setup and appearancebefore printing to satisfy the requirements of the printing effect.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the queried alarm information is the one to be printed.

    For the operation of querying alarms, refer to Querying Current Alarms and Querying

    History Alarms.

    Confirm that the printer is connected and set correctly.

    Steps

    To print alarm information, perform the following steps.

    1. On the alarm list window, click the on the toolbar. The Print Setup dialog box

    pops up, and performs the General settings, as shown in Fig 4.2 -54.

    73

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    75/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.2-54 Print Setup, General

    2. Select the Page Setup tab to set the page parameters, as shown in Fig 4.2 -55.

    Fig 4.2-55 Print Setup, Page Setup

    3. Select the Advance tab to set the parameters as required, as show in Fig 4.2 -56.

    74

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    76/86

    Chapter 4 Alarm Operations

    Fig 4.2-56 Print Setup, Advance

    4. When completing the setting, click Print to start printing the alarm list. Click

    Preview All to preview the printing effect.

    4.2.7 Exporting Alarm Information

    Purpose

    The export function is used to export the data of all alarms on the alarm list window that

    is opened by the current user to a file, whose format can be text, EXCEL, PDF, HTML or

    CSV.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Confirm that the queried alarm information is the one to be exported.

    For the operation of querying alarms, refer to Querying Current Alarms and Querying

    History Alarms.

    Steps

    To export the alarm data, perform the following steps:

    1. On the alarm list window, click the on the toolbar to pop up the Save dialog

    box. Set the Save In, File Name and Files of Type, as shown in Fig 4.2 -57.

    75

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    77/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.2-57 Saving Dialog Box

    2. Click Save to export the data of the selected alarm list to the specified file in the

    specified path.

    4.3 Alarm Maintenance Suggestions

    Introduction

    This section mainly describes the operation related to the alarm maintenance suggestions.

    4.3.1 Adding an Alarm Maintenance Suggestion

    Purpose

    Based on the long-term running of the network, the maintenance experience on common

    problems can be summarized as the reference for solving similar problems in the future.

    The summary of such maintenance experience is the customized alarm maintenance

    suggestion.

    Adding a new alarm maintenance suggestion is to add a new suggestion of processing

    one type of alarms based on the actual operations.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To add an alarm maintenance suggestion, perform the following steps.

    76

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    78/86

    Chapter 4 Alarm Operations

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Maintenance Suggestion

    Setting to pop up the Maintenance Suggestion Setting window, as shown in Fig

    4.3 -58.

    Fig 4.3-58 Maintenance Suggestion Setting

    3. On the Maintenance Suggestion Setting window, from the System Type drop-

    down list, select the alarm type to be set, including All System Type, Alarm Box

    Link Break Alarm, Bill Server Alarm, Correlation Alarm, Link Alarm, Local

    and Remote OMC Linkdown Alarm, NE Alarm, Performance QoS Alarm,

    SORM Server Alarm and System Management.

    4. Click the icon on the toolbar to pop up the Maintenance suggestion dialog

    box. Select Alarm Code and Reason Description, and enter the suggestion in the

    Customized Suggestions text box, as shown in Fig 4.3 -59.

    77

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    79/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Fig 4.3-59 Maintenance Suggestion

    5. Click OKto finish the configuration of the alarm maintenance suggestion.

    4.3.2 Modifying an Alarm Maintenance Suggestion

    Purpose

    Modifying an alarm maintenance suggestion is to improve the established suggestions

    based on the actual operations. The modified alarm maintenance suggestion will be

    shown in the Customized Suggestions text box, which will not replace the default

    suggestion.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To modify an alarm maintenance suggestion, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Maintenance Suggestion

    Setting to pop up the Maintenance Suggestion Setting window.

    3. On the Maintenance Suggestion Setting window, from the System Type drop-

    down list, select the alarm type to be modified.

    78

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    80/86

    Chapter 4 Alarm Operations

    4. From the suggestion list on the Maintenance Suggestion Setting window, click the

    suggestion to be modified.

    5. Click the on the toolbar to pop up the Maintenance suggestion dialog box, as

    shown in Fig 4.3 -60. Enter the modified suggestion in the Customized

    Suggestions text box.

    Fig 4.3-60 Modifying an Alarm Maintenance Suggestion

    6. Click OKto finish the modification of the alarm maintenance suggestion.

    4.3.3 Exporting an Alarm Maintenance Suggestion

    Purpose

    The ZXWN network management system allows the user to export alarm maintenance

    suggestions in the system to a file. It supports exporting alarm data to a text, EXCEL,

    PDF or HTML file.

    Prerequisite

    Confirm that the user has logged in the network management server normally.

    Steps

    To export an alarm maintenance suggestion, perform the following steps.

    1. In the main window of the network management client, choose View > Fault

    79

  • 7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc

    81/86

    TN_SM007_E1_0 ZXWN CS Alarm Management

    Management. The Fault Management window appears.

    2. In the Fault Management window, choose Setting > Maintenance S