Upload
arun-mishra
View
230
Download
1
Embed Size (px)
Citation preview
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
1/86
ZXWN CS Alarm Management
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
2/86
Contents
1 Introduction to Alarms....................................................................................................................................1
2 Alarm Monitoring............................................................................................................................................9
3 Alarm Settings................................................................................................................................................13
4 Alarm Operations...........................................................................................................................................55
i
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
3/86
1 Introduction to Alarms
1.1 Common Alarm Terms
Description
Every alarm term has its specific meaning. Knowing the alarm terms preciously can help
to correctly perform various operations on the alarms.
Alarm
Alarms are various faults or alerting information that occurs during the running of the
system. Operation and maintenance personnel should perform corresponding operations
based on the specific alarms.
Current Alarm
If the system generates an alarm and that alarm persists, then this kind of alarm is called
the current alarm.
History Alarm
If the system generated an alarm, but the fault has been eliminated later. This kind of
alarm is called the history alarm.
Alarm Recovery
The alarm recovery information indicates that the system has been faulty, but the fault
has been eliminated at present.
Alarm Level
The alarm level indicates the severity of an alarm.
Alarm Code
It is an indicator to distinguish various alarms. Different alarms correspond to different
alarm codes.
Alarm Management System
The alarm management system is the system maintenance tool of the OMM system. It
performs the centralized monitoring on the running condition of the whole system and
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
4/86
collects the unexpected information of the boards, links, databases and servers.
Fault Management System
The fault management system timely displays the correct fault information to the
administrator.
Notification
The notification information means the operation or unexpected information that occurs
and does not affect the system.
Alarm Filtering
It is used to filter a certain level or some types of alarm information through certain
settings.
1.2 Alarm Management
Definition
The alarm management function is a function group that manages the faults occurring to
the network equipment managed by the ZXWN network management system during the
system running. This function group generally calls the managed faults as alarms.
Functions
The alarm management function enables users to monitor and manage the faults and
events in the whole network in a centralized manner. Users can monitor and view the
alarms in the network in real time or even filter the unwanted alarms based on certain
conditions. Alarms can be presented in a vivid manner to the network maintenance staff,
such as audible alarms, visual alarms and alarm boxes.
After an alarm is generated, the user can perform such operations as
acknowledging/unacknowledging it, clearing it, informing someone through the Email or
Short Messages (SM), and viewing its detailed information and related events. If the user
has summarized the processing methods of alarms and saved them in the alarm
processing suggestion library, the user can also view the corresponding suggestions to
shorten the time spent on troubleshooting when similar alarms occur next time.
The alarm management function is capable of monitoring and managing alarms and
notification messages in the network in a centralized manner.
Alarm Categories
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
5/86
Chapter 4 Alarm Operations
According to the severity, alarms fall into critical alarms, major alarms, minor
alarms and warnings.
According to the fault types, alarms fall into the processing alarm, the Quality of
Service (QoS) alarm, the environment alarm, the equipment alarm, the
communication alarm, and the network management system alarm.
According to the system types, alarms fall into the security alarm, the alarm box
and OMM communication link alarm, the billing server alarm, the SORM server
alarm, the foreground/background communication link alarm, the MP NE
Equipment Alarm, the system management alarm, the correlation alarm and the
performance alarm.
1.3 Alarm System
1.3.1 Structure Description
Introduction
The ZXWN MSC Server has a relatively complete alarm system, including the
foreground alarm system, the OMM server alarm system, the OMM client alarm system
and the alarm box.
System Structure
The alarm system diagram is shown in Fig 1.3 -1. For detailed information, see Table
1.3 -1.
3
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
6/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 1.3-1 Alarm System Diagram
Table 1.3-1 Components and Functions Introduction
Alarm System Function
MSCS ForegroundAlarm System
Collects and processes foreground alarm information;
Executes background man-machine commands andreturn execution results
OMM Server AlarmSystem
Processes, stores and forwards the information;
Controls the alarm box
OMM Client AlarmSystem
Displays, searches and prints the alarm information;
Displays rack charts;
Executes man-machine commands.
Alarm Box
Receives the alarm information from the backgroundthrough the Ethernet interface. The alarm box can
prompt the fault during the running of the systemthrough such various modes as sound, light, screen
display, the SM and file transfer.
1.3.2 Alarm and Warning Processing Mechanism
Definition
As the system maintenance tool, the alarm processing mechanism performs centralizedmonitoring on the running condition of the ZXWN MSC Server and collects the
abnormal information of boards, links, databases and servers in real time.
For some system performance data, such as the CPU occupancy, the warning threshold
can be set by setting the critical value. When the onsite equipment just becomes
abnormal but not faulty, use the monitoring tool to send abnormal warning information
out through the alarm box. In this way, the corresponding maintenance personnel can
know the system running condition in time and eliminate the fault.
Processing flow
The processing flow of the alarm and the warning is shown in Fig 1.3 -2.
4
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
7/86
Chapter 4 Alarm Operations
Fig 1.3-2 Structure of Warning System
Flow description
The OMM alarm management system sends the alarm (its level can be set) and warning
information to the alarm box. The Mobile Station (MS) module of the alarm box converts
the alarm into a SM, and then transmits it to a series of MS numbers, including the MS
module of the alarm processing server, the local ZTE office personnel and relative
personnel of the carrier.
After receiving the alarm or warning SM, the alarm processing server converts the SM
into the alarm or warning information, and generates an Email through the mail protocol
and then sends it to the personnel among the predefined Email list; or re-generates a SM
and then sends it to the personnel among the SM receiving list predefined in the alarm
processing server.
5
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
8/86
TN_SM007_E1_0 ZXWN CS Alarm Management
1.4 Alarm Information
1.4.1 Alarm Description
Description
The alarm management system performs centralized monitoring on the running condition
of the ZXWN MSC Server and collects the abnormal information of the boards, links,
databases and servers in real time. When the system is faulty or some indices exceed the
predefined threshold, the alarm management system will generate an alarm at once. The
operation and maintenance personnel can locate and eliminate the fault through the alarm
information to ensure the stable running of the system.
Alarm Level
The alarm information can be divided into four levels based on severity.
Level-1: critical
Level-2: major
Level-3: minor
Level-4: warning.
1.4.2 Relation between Alarms and Services
Description
The alarm system monitors the running condition of the whole system in real time. When
a certain part of the system becomes abnormal, the alarm system will give an alarm. The
alarm information level indicates the alarm severity.
Relation
Among all kinds of alarm information, the service alarm information is the altering
information generated for the service faults that occurred or will occur, or the faults that
affect the service during the running of the ZXWN MSC Server. Usually, an alarm will
exist for a period of time until the problem or the fault is handled.
1.4.3 Relation between Alarms and Faults
The alarm information is the alerting information generated for the problems or faults
that occur during the running of the ZXWN MSC Server. The alarm management system
should timely show the correct fault information to the administrator when the fault
6
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
9/86
Chapter 4 Alarm Operations
occurs. Usually, an alarm will exist for a period of time until the problem or the fault is
handled.
1.4.4 Handling Measures
The handling measures for alarms of different levels are described as follows.
When level-1 or level-2 alarms appear, the alarm system will send the alarm
information to the corresponding personnel as soon as possible through the alarm
box monitoring alarm, SM monitoring alarm, Email monitoring alarm and
background monitoring alarm, so that the fault can be handled in time. For those
difficult to handle, notify the local ZTE office.
When level-3 or level-4 alarms appear, the maintenance personnel in the equipment
room can handle the fault according to the common processing methods after
recording the problems and fault phenomena. If the fault cannot be eliminated,
contact the local ZTE office for technical support.
1.5 Notification Information
1.5.1 Notification Information Description
The notification information indicates the operation or abnormal information that has
occurred, helping the maintenance personnel grasp the running condition of each part of
the system. The notification information has no level and does not affect the system.
The notification information is shown by the OMM system during the daily operation of
the ZXWN MSCS system to prompt the system running information required by the
maintenance personnel.
1.5.2 Relation between Notifications and Services
Influence Relation
The notification information has no impact on the service.
1.5.3 Relation between Notifications and Faults
The notification information refers to the operations or exceptions that occurred during
the running of the system, but had no impact on the system and the service. The fault
brings impact on the system and service, which is required to be handled.
7
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
10/86
TN_SM007_E1_0 ZXWN CS Alarm Management
8
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
11/86
2 Alarm Monitoring
2.1 Alarm Monitoring Policy
Introduction
When the onsite equipment is faulty, or becomes abnormal, the alarm management
system sends out the alarm and warming information according to the alarm monitoring
policies, which facilitates eliminating the fault and hidden trouble in time.
Principle
The alarm monitoring policies are described as follows.
Priority policy for important alarms
The alarm information is divided into four levels by severity. The higher the level
is, the more serious the alarm is. When the alarms with different levels appear at the
same time, the highest-level alarm information must be sent first.
First time policy
The alarm has an impact on the service. The alarm must be eliminated as soon as
possible to quickly recover the system to the normal status and relieve the impact
on the service. So the alarm information must be sent out as soon as possible.
Featured by using shorter transmission time, the alarm box can send the alarm and
warning information as soon as possible through the sound and the short message.
Multi-receiver policy
Multiple persons can receive the alarm information by alarm management server
settings. In this way, it may reduce the possibility of delaying handling the fault
because one or several persons did not receive the alarm information in time.
Multi-way policy
Using a single source to give an alarm will cause the alarm information unreliable
as this procedure can become faulty. Adopting multi-way alarm monitoring policy
can avoid this case.
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
12/86
2.2 Alarm Report Modes
Introduction
The alarm reports have the following forms.
Background monitoring alarm
Alarm box monitoring alarm
Short message monitoring alarm
Multimedia Messaging Service (MMS) and Email monitoring alarm.
Comparison
Alarm box monitoring alarm, short message monitoring alarm, MMS monitoring alarm,
and Email monitoring alarm must use the alarm box to transfer the information, while the
background monitoring alarm does not.
Besides monitoring alarms, the background monitoring alarm can query the system
performance, while the other modes can only query the system alarm information.
2.2.1 Background Monitoring Alarm
Introduction
The alarm system monitors the whole switch in real time. When a certain part of the
switch is faulty, the alarm service process of the application server will send the message
to the OMM server to generate the alarm or warning information.
Functions
The performance, running conditions and alarm information of the system can be viewed
in detail through the background monitoring alarm, which facilitates locating and
eliminating faults to ensure the stable running of the system.
Query Method
After logging in the network management system, select each sub-menu of the Alarm
View on the main window of the alarm management, to set the alarm query conditions,
and query the alarms.
2.2.2 Alarm Box Monitoring Alarm
Introduction
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
13/86
Chapter 4 Alarm Operations
The alarm box is the tool of the alarm monitoring system that can display the fault
information visually and rapidly.
Working Principle
Connecting to the alarm box, the fault management subsystem of the OMM server
transfers the alarm messages to the alarm box through the TCP/IP protocol, which are
displayed on the screen and accompanied by the alarm indicator and alarm sound
prompts.
Functions
The alarm box can collect the alarm (recovery)/warning information and log data of the
equipment, and send it to the warning center. Finally, the warning center analyzes and
processes the information, and notifies the corresponding personnel through the alarm
short message, alarm MMS and Alarm box audible and visual information. The
audible/visual information contains the following contents.
Prompting the current alarm with sound
Giving an alarm through indicators or horns
Display relatively detailed alarm information on the screen by using the keyboard to
turn pages.
2.2.3 Short Message Monitoring Alarm
Introduction
The alarm management system sends the level-1 and level-2 alarm and warning
information to the alarm box through the alarm management system of the OMM
equipment. After the MS module of the alarm box converts the alarm information into
the short message, the alarm box can also send the short message alarm to a series of
specified MS numbers.
Functions
Through the short message monitoring alarm, the alarm box can send the alarm or
warning information to the specified MS in the form of short message. The maintenance
personnel, either from local ZTE office or the operator, can know the system running
conditions without being on the site.
11
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
14/86
TN_SM007_E1_0 ZXWN CS Alarm Management
2.2.4 MMS and Email Alarm
Introduction
Due to the small size of the short message, usually only 340 bits, the short message alarm
often needs to be separated into parts before being sent, so the cost is high. The MMS can
be adopted by performing the background settings, which can transfer 50K data at one
time. By performing the background settings or modifying the configuration file, the
MMS is applicable for sending the alarm information and fault logs to the mailbox or the
mobile phone of the specified maintenance personnel through the Email server or the
MMS center.
12
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
15/86
3 Alarm Settings
3.1 Alarm Rule Settings
Introduction
This section describes how to set an alarm rule.
For how to activate, pause, refresh, and delete an alarm rule, see Alarm Rule Operations.
3.1.1 Introduction to Alarm Rules
Type
The alarm rule falls into the following types:
The alarm persisting rule
The alarm counting rule
The alarm delaying rule
The alarm restraining rule
The alarm merging rule
The alarm user filtering rule
The alarm global filtering rule
The alarm discarding rule
The alarm forwarding rule
The alarm clearing rule
The alarm acknowledging rule
The notification global filtering rule
The notification discarding rule
Valid Range
Rule setting can contain multiple rules. The range where a rule takes effect varies with
the type of the rule. It is called the valid range of a rule, which is divided into following
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
16/86
four types:
Global validity
Once an alarm rule is set and activated, it is effective for all alarms, events and
notifications that conform to this rule, which has no relationship with the one who
makes it. Therefore, the alarms that all users saw are processed according to this
rule.
User validity
Once an alarm rule is set and activated, it is only effective for the user who makes
it, such as the alarm user filtering rule. It has no influence on other users.
Forward validity
Once an alarm is set and activated, it is effective for all current alarms, including
the alarm that has been reported and that will be reported in the future.
Backward validity
Once an alarm rule is set and activated, it is only effective for the alarms that will
be reported in the future, having no influence on the alarm that has been reported.
Function
Table 3.1 -2 shows the alarm rules supported by the OMM system.
Table 3.1-2 Functions of Alarm Rules
Rule Name Valid Range Function
Alarm Persisting
Rule
Global validity;
Backward validity
Upgrading the alarm severity orgenerating a new alarm when theduration of acknowledging the alarmsatisfying this rule or the alarm being inthe active status exceeds that specifiedby this rule. The persisting duration isobtained by deducting the generation
time from the acknowledging time orthe current time
Alarm CountingRule
Global validity;
Backward validity
Generating a new counting alarm,saving the reported alarms and theamount into the database, and showingthem on the Realtime Alarms window,when the amount of the current alarmsthat satisfy this rule reaches the rule-specified threshold within a period oftime specified by the rule
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
17/86
Chapter 4 Alarm Operations
Rule Name Valid Range Function
Alarm DelayingRule
Global validity;Backward validity
Delaying showing the reported alarm
that satisfies this rule on the RealtimeAlarms window for a period of time,which is specified by this rule
AlarmRestraining Rule
Global validity;
Backward validity
Not showing the consequential alarmspecified by this rule on the RealtimeAlarms window when the root alarm ofa current alarm exists or occurs
Alarm MergingRule
Global validity;
Backward validity
Only showing one of the alarms that
satisfy this rule on the RealtimeAlarms window instead of all of them
Alarm User
Filtering Rule
User Validity;
Forward validity
Not showing the alarm satisfying the
rule on the Realtime Alarms window
of the client of the user who set thisrule
Alarm GlobalFiltering Rule
Global validity;
Backward validity
Only saving the reported alarm thatsatisfies this rule in the database, notshowing it on the Realtime Alarmswindow of the client
Alarm DiscardingRule
Global validity;
Backward validity
Discarding the reported alarm thatsatisfies this rule directly, and neither
saving it into the database nor showingit on the Realtime Alarms window of
the client
AlarmForwarding Rule
Global validity;
Backward validity
Notifying the user specified in the rulethrough the Email or SMS when thereported alarm satisfies this rule
Auto alarmclearing rules
Global validity;
Backward validity
Clearing the reported alarm thatsatisfied this rule directly from thecurrent alarms, and moving it to thehistory alarm database, that is, thealarm is automatically recovered
AlarmAcknowledgingRule
Global validity;
Backward validity
Acknowledging the alarm that satisfiesthis rule when it is reported
The notification
global filteringRule
Global validity;
Backward validity
Clearing the reported notification thatsatisfied this rule directly from theRealtime Notifications window of theclient, and moving it to the database
NotificationDiscarding Rule
Global validity;
Backward validity
Discarding the reported notification that
satisfies this rule directly, and neithersaving it into the database nor showing
it on the Realtime Notificationswindow of the client
15
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
18/86
TN_SM007_E1_0 ZXWN CS Alarm Management
3.1.2 Setting an Alarm Persisting Rule
Purpose
When the duration of acknowledging an alarm or its being in the active status exceeds the
time that specified by the alarm persisting rule, the alarm severity will be raised or a new
alarm will be generated.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm persisting rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears, as shown in Fig 3.1 -3.
Fig 3.1-3 Management Rule Setting
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Persisting Rule radio button, and then clickOK, as shown in Fig 3.1 -4.
16
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
19/86
Chapter 4 Alarm Operations
Fig 3.1-4 Selecting Alarm Persisting Rule
4. The Alarm Persisting Rule dialog box pops up, as shown in Fig 3.1 -5. The
parameters on the Information page are described in Table 3.1 -3.
17
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
20/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.1-5 Alarm Persisting Rule, Information
Table 3.1-3 Parameter Descriptions for Alarm Persisting Rule
Parameters Descriptions
Name The name of an alarm persisting rule
Description The description of an alarm persisting rule
Persist Time The interval for an alarm persisting rule to take effect
Persist State The persisting state of the alarm information, eitherunacknowledged state or active state
Rule Action When the conditions of duration and state are satisfied, the
system will automatically change the alarm severity orgenerate a new alarm.
Alarm severity change means that the severity of an alarmchanges from the original level to the specified one when therule takes effect.
5. Select the Selection tab, as shown in Fig 3.1 -6. Select the alarm type suitable for
this rule.
18
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
21/86
Chapter 4 Alarm Operations
NOTE:
The left column shows the conditions distinguishing different alarm types, while the rightcolumn shows the alarm types corresponding to different alarm conditions. It is available
to select several alarm conditions and alarm types.
Fig 3.1-6 Alarm Persisting Rule, Selection
6. When the setting is over, clickOKto complete creating an alarm persisting rule.
Result
An alarm persisting rule is created.
3.1.3 Setting an Alarm Counting Rule
Purpose
An alarm counting rule setting is to set to generate a new alarm separately and report it
when the number of same alarms has exceeded the threshold in a specified period.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm counting rule, perform the following steps.
19
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
22/86
TN_SM007_E1_0 ZXWN CS Alarm Management
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Counting Rule radio button, and then clickOK.
4. The Alarm Counting Rule dialog box pops up, as shown in Fig 3.1 -7. The
parameters on the Information page are described in Table 3.1 -4.
Fig 3.1-7 Alarm Counting Rule, Information
Table 3.1-4 Parameter Descriptions for the Alarm Counting Rule
Parameters Descriptions
Name The name of a rule
Description Details of a rule
20
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
23/86
Chapter 4 Alarm Operations
Parameters Descriptions
If in _ _ there are _
suitable alarms,then new a _ alarmautomatically
The duration for the rule to take effect, meaning that a
new alarm of specified severity is generated when thespecified number of alarms is generated within specifiedtime.
New AlarmInformation
The description of the new generated alarm
5. Select the Selection tab, as shown in Fig 3.1 -8. Select the alarm type suitable for
this rule.
NOTE:
The left column shows the conditions distinguishing different alarm types, while the right
column shows the alarm types corresponding to different alarm conditions. It is available
to select several alarm conditions and alarm types.
Fig 3.1-8 Alarm Counting Rule, Selection
6. Click OKto complete setting an alarm counting rule.
Result
21
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
24/86
TN_SM007_E1_0 ZXWN CS Alarm Management
An alarm counting rule is created.
3.1.4 Setting an Alarm Delaying Rule
Purpose
The alarm delaying rule allows a user to defer showing some unimportant alarms. If the
alarm is automatically recovered within the specified period, it will not be displayed any
longer.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm delaying rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select theAlarm Delaying Rule radio button, and then clickOK.
4. The Alarm Delaying Rule dialog box pops up, as shown in Fig 3.1 -9. Enter
Name, Description and Delay Time, and select the alarm filtering conditions on
the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
22
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
25/86
Chapter 4 Alarm Operations
Fig 3.1-9 Alarm Delaying Rule
5. When the setting is over, clickOKto complete setting an alarm delaying rule.
Result
An alarm delaying rule is created.
3.1.5 Setting an Alarm Restraining Rule
Purpose
When the system generates a root alarm and a consequential alarm at the same time, the
alarm restraining rule allows a user to set that only the root alarm is reported and also to
set whether to report the consequential alarm after the root alarm is recovered according
to the requirements.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm restraining rule, perform the following steps.
23
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
26/86
TN_SM007_E1_0 ZXWN CS Alarm Management
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Restraining Rule radio button, and then clickOK.
4. The Alarm Restraining Rule dialog box pops up, as shown in Fig 3.1 -10. Enter
the Name and Description.
Fig 3.1-10 Alarm Restraining Rule
5. On the Root alarm area, click the Setting button to pop up the Root alarm dialog
box, as shown in Fig 3.1 -11
NOTE:The left column shows the conditions distinguishing different alarm types, while the right
column shows the alarm types corresponding to different alarm conditions. It is available
to select several alarm conditions and alarm types.
24
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
27/86
Chapter 4 Alarm Operations
Fig 3.1-11 Root Alarm
6. Click OKafter the setting is over. Return to the Alarm Restraining Rule dialog
box.
7. Click New on the Consequential alarm area, to pop up the Consequential alarm
dialog box, as shown in Fig 3.1 -12.
Fig 3.1-12 Consequential Alarm Dialog Box
8. Click OKafter the setting is over. Return to the Alarm Restraining Rule dialog
box.
25
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
28/86
TN_SM007_E1_0 ZXWN CS Alarm Management
9. Click OKto complete the setting of an alarm restraining rule.
Result
An alarm restraining rule is created.
3.1.6 Setting an Alarm Merging Rule
Purpose
An alarm merging rule allows the system to merge the alarms of the same type generated
within a certain position range. And then, only one of them is reported.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm merging rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar to pop up the New dialog box. Select the Alarm
Merging Rule radio button, and then clickOK, as shown in Fig 3.1 -13.
26
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
29/86
Chapter 4 Alarm Operations
Fig 3.1-13 Selecting Alarm Merging Rule
4. The Alarm Merging Rule dialog box pops up. EnterName and Description, and
select the alarm merging conditions on the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
5. After completing the settings, clickOKto complete creating an alarm merging rule.
Result
An alarm merging rule is created.
3.1.7 Setting an Alarm User Filtering Rule
Purpose
An alarm user filtering rule only takes effect on the current client. If the client receives an
alarm reported by the server, it uses the filter conditions of the login user to filter alarms.
27
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
30/86
TN_SM007_E1_0 ZXWN CS Alarm Management
The selected alarms will be discarded by the client and not be displayed in the alarm list
or counted as the alarms of an NE.
A user filtering rule is valid only for a specific login user and will not take effect on the
clients that other users log in.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm user filtering rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm User Filtering Rule radio button, and then clickOK.
4. The Alarm User Filtering Rule dialog box pops up, as shown in Fig 3.1 -14.
Enter Name and Description, select For User parameter, and select the alarm
filtering conditions on the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
28
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
31/86
Chapter 4 Alarm Operations
Fig 3.1-14 Alarm User Filtering Rule
5. When the setting is over, clickOKto complete setting an alarm user filtering rule.
Result
An alarm user filtering rule is created.
3.1.8 Setting an Alarm Global Filtering Rule
Purpose
An alarm global filtering rule is used to filter alarms during pre-processing of alarms.
The chosen alarms will not be sent to the client.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm global filtering rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
29
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
32/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Global Filtering Rule radio button, and then clickOK.
4. The Alarm Global Filtering Rule dialog box pops up, as shown in Fig 3.1 -15.
Enter Name and Description, and select the alarm filtering conditions on the
Selection area.
NOTE:
In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
Fig 3.1-15 Alarm Global Filtering Rule
5. When the setting is over, clickOK to complete setting an alarm global filtering
rule.
30
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
33/86
Chapter 4 Alarm Operations
Result
An alarm global filtering rule is created.
3.1.9 Setting an Alarm Discarding Rule
Purpose
An alarm discarding rule is used to filter the alarms during the alarm collection. The
selected alarms are neither saved in the database nor displayed in the Realtime Alarms
window.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm discarding rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Discarding Rule radio button, and then clickOK.
4. The Alarm Discarding Rule dialog box pops up, as shown in Fig 3.1 -16. Enter
Name and Description, and select the alarm filtering conditions on the Selection
area.
NOTE:
In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
31
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
34/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.1-16 Alarm Discarding Rule
5. When the setting is over, clickOKto complete setting an alarm discarding rule.
Result
An alarm discarding rule is created.
3.1.10 Setting an Alarm Forwarding Rule
Purpose
An alarm forwarding rule is used to forward the matched alarm to the corresponding
destination when alarms are reported.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm forwarding rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
32
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
35/86
Chapter 4 Alarm Operations
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Forwarding Rule radio button, and then clickOK.
4. The Alarm Forwarding Rule dialog box pops up, as shown in Fig 3.1 -17. Enter
the Name and Description on the Information page.
Fig 3.1-17 Alarm Forwarding Rule Dialog Box
5. From the List of Forwarded-to Users area, click the Custom button to pop up
the Setting a Forwarded-to User dialog box. Enter Forwarding User, Email
Address and Phone Number, as shown in Fig 3.1 -18.
33
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
36/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.1-18 Customizing a Forwarded-to User
NOTE:ClickSelect to add a user who already exists in the system to the List of Forwarded-
to Users.
6. Click OK to add the customized forwarded-to user to the List of Forwarded-to
Users, as shown in Fig 3.1 -19.
Fig 3.1-19 Customized Forwarded-to User List
34
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
37/86
Chapter 4 Alarm Operations
7. Select the Selection tab, as shown in Fig 3.1 -20. Select the alarm type suitable for
this rule.
NOTE:The left column shows the conditions distinguishing different alarm types, while the right
column shows the alarm types corresponding to different alarm conditions. It is available
to select several alarm conditions and alarm types.
Fig 3.1-20 Alarm Forwarding Rul, Selection
8. Click OKto complete the setting of an alarm forwarding rule.
Result
An alarm forwarding rule is created.
3.1.11 Setting an Alarm Clearing Rule
Purpose
An alarm clearing rule is used to automatically clear the matched alarms when alarms are
reported. That is, alarm clearing information is added automatically and the reported
alarms directly become history alarms and are saved in the data table of history alarms.
In this way, the system can record the alarms and reduce the number of current alarms as
35
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
38/86
TN_SM007_E1_0 ZXWN CS Alarm Management
well, so that the maintenance personnel can better focus their attentions on important
alarms.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm clearing rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting. The
Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Alarm Clearing Rule radio button, and then click OK.
4. The Alarm Clearing Rule dialog box pops up, as shown in Fig 3.1 -21. Enter Name
and Description, and select the alarm filtering conditions on the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
36
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
39/86
Chapter 4 Alarm Operations
Fig 3.1-21 Alarm Clearing Rule
5. After setting all filtering conditions, clickOKto complete setting an alarm clearing
rule.
Result
An alarm clearing rule is created.
3.1.12 Setting an Alarm Acknowledging Rule
Purpose
An alarm acknowledging rule is used to automatically acknowledge the matched alarms
when alarms or alarm recovery messages are reported. In this way, the system reduces
the workload of network management personnel and enables them to focus more on
important alarms. Through the alarm acknowledging rule, the system will automatically
set the acknowledgement state, time and information of alarms.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm acknowledging rule, perform the following steps.
37
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
40/86
TN_SM007_E1_0 ZXWN CS Alarm Management
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar to pop up the New dialog box. Select the Alarm
Acknowledging Rule radio button, and then clickOK.
4. The Alarm Acknowledging Rule dialog box pops up, as shown in Fig 3.1 -22.
EnterName and Description, select the acknowledgement parameter, and select the
alarm filtering conditions on the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
Fig 3.1-22 Alarm Acknowledging Rule
5. Click OKto complete setting an alarm acknowledging rule.
38
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
41/86
Chapter 4 Alarm Operations
Result
An alarm acknowledging rule is created.
3.1.13 Setting a Notification Global Filtering Rule
Purpose
A notification global filtering rule is used to filter the notifications during the notification
collection. The selected notifications are not displayed in the Realtime Notification
interface, but they are saved in the database.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set a notification global filtering rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.
The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Notification Global Filtering Rule radio button, and then click OK.
4. Click OK, the Notification Global Filtering Rule dialog box pops up, as shown in
Fig 3.1 -23. Enter Name and Description, and select the notification filtering
conditions on the Selection area.
NOTE:
In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
39
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
42/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.1-23 Notification Global Filtering Rule
5. When the setting is over, clickOKto complete setting a notification global filtering
rule.
Result
A notification global filtering rule is created.
3.1.14 Setting a Notification Discarding Rule
Purpose
A notification discarding rule is used to filter the notifications during the notification
collection. The selected notifications are neither saved in the database nor displayed in
the Realtime Notification window.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set a notification discarding rule, perform the following steps.
1. In the main window of the network management client, choose View > Fault
40
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
43/86
Chapter 4 Alarm Operations
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Management Rule Setting.The Management Rule Setting page appears.
3. Click the icon on the toolbar, and the New dialog box pops up. Select the
Notification Discarding Rule radio button, and then clickOK.
4. The Alarm Acknowledging Rule dialog box pops up, as shown in Fig 3.1 -24.
Enter Name and Description, and select the alarm filtering conditions on the
Selection area.
NOTE:
The left column shows the conditions distinguishing different alarm types, while the right
column shows the alarm types corresponding to different alarm conditions. It is available
to select several alarm conditions and alarm types.
Fig 3.1-24 Notification Discarding Rule
5. When the setting is over, clickOK to complete setting a notification discarding
rule.
Result
A notification discarding rule is created.
41
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
44/86
TN_SM007_E1_0 ZXWN CS Alarm Management
3.2 Redefining Alarm Severity
Purpose
Each alarm corresponds to an alarm level. Alarms are divided into the following four
levels based on the severity: critical alarms, major alarms, minor alarms and warning.
The default severity has been set for each alarm during the system initialization.
Redefining the severity is to modify the alarm severity as required during the running of
the system.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To redefine the severity of an alarm, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Severity Regrading Setting
to pop up the Severity Regrading Setting page, as shown in Fig 3.2 -25.
Fig 3.2-25 Severity Regrading Setting
3. After the System type is selected, all alarms corresponding to this system type will
42
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
45/86
Chapter 4 Alarm Operations
be displayed on the Severity Redegrading Setting page automatically, as shown in
Fig 3.2 -26.
Fig 3.2-26 Alarm List
4. Select the alarm item whose severity is to be redefined. Select the new severity
from the drop-down list ofNew Severity, as shown in Fig 3.2 -27.
Fig 3.2-27 Alarm Severity List
5. Click the icon on the toolbar to save the modification on the server. At this
time, the mark on the Modify Status column will be cleared automatically, as shown in
43
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
46/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.2 -28.
Fig 3.2-28 Completing Severity Redefinition
3.3 Setting the Alarm Sound
Purpose
Setting the alarm sound is to specify the alarm sound for each alarm level that is given on
the network management client.
NOTE:By default, the sound mode is set as Silence.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the sound file exists, whose default format is *.wav.
Steps
To set the alarm sound, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Preferences to pop up the
Preferences dialog box. On the Alarm Sound Setup page, select the sound mode
from the Sound Mode drop-down list in each alarm level area. The sound mode
falls into the continuous sound and the short beeps. At this time, the Select and Play
buttons next to the Sound File text box are activated, as shown in Fig 3.3 -29.
44
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
47/86
Chapter 4 Alarm Operations
Fig 3.3-29 Preferences, Alarm Sound Setup
3. Click the Select button to select the sound file. Click the Play button to play the
selected alarm sound.
4. Click OKto complete the settings.
3.4 Setting an Alarm ColorPurpose
Setting an alarm color is to specify the color for each alarm level that is displayed on the
network management client. Use different colors to distinguish the alarm severity.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
45
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
48/86
TN_SM007_E1_0 ZXWN CS Alarm Management
To set an alarm color, perform the following steps.
1. In the main window of the network management client, choose View > FaultManagement. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Preferences to pop up the
Preferences dialog box. Select the Alarm Color Setup tab, as shown in Fig 3.4
-30.
Fig 3.4-30 Preferences, Alarm Color Setup
3. On the Alarm Color Setup page, set the alarm colors of different alarm severities.
4. Click OKfor the system to save the color parameters that have been set.
3.5 Setting a Forwarding Template
Purpose
Setting a forwarding template is to set the information format of the forwarded SM and
Email, so that the system alarm information can be sent to the specified mobile phone or
46
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
49/86
Chapter 4 Alarm Operations
mailbox through the SM or Email.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To set a forwarding template, perform the following steps:
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Preferences to pop up the
Preferences dialog box. Select the Forward Template Setup tab, as shown in Fig
3.5 -31. Check and recover the settings of the forwarding template of the short
message and Email title and content.
Fig 3.5-31 Preferences, Forward Template Setup
3. In the Setup the forwarding content template of the mail area, input [ to select
the required parameters from the pop-up choice box, as shown in Fig 3.5 -32.
47
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
50/86
TN_SM007_E1_0 ZXWN CS Alarm Management
NOTE:
The operation to set the forwarding template of the handset short message andforwarding title template of the mail are similar to this operation.
Fig 3.5-32 Setting Email Forwarding Content Template
4. Click OKfor the system to save the forwarding template parameters.
3.6 Setting an Alarm Box
Purpose
Setting an alarm box is necessary for normally reporting the system alarm information to
the alarm box.
Prerequisite
48
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
51/86
Chapter 4 Alarm Operations
Confirm that the user has logged in the network management server normally.
Steps
To set an alarm box, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Alarm Box Setting. The
Alarm Box Setting page appears, as shown in Fig 3.6 -33.
Fig 3.6-33 Alarm Box Setting
3. Click the icon on the page to pop up the Alarm Box Detail dialog box, as
shown in Fig 3.6 -34.
For the details of the alarm box settings, refer to Table 3.6 -5.
49
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
52/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.6-34 Setting Information of the Alarm Box
Table 3.6-5 Alarm Box Information Parameters
Parameters Description
Alarm Box Name The name of the alarm box, which must be input.
Alarm Box DescriptionThe description of the alarm box. Input the parameter
as required
Initial StateSelects the initial state of the alarm box, eitherEnable or Disable. When selecting Enable, the alarm
box works normally.
Alarm Box IPThe IP address of the alarm box, which is in the samenetwork segment as the address of the network
management server, which must be input.
Server PortThe port number for alarm box for communicatingwith the server is 6700.
50
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
53/86
Chapter 4 Alarm Operations
Parameters Description
Display Alarm Severity
Controls the alarm severity displayed on the alarm
box, which is divided into five types: none, warningand above, minor and above, major and above andcritical.
Speak Alarm Severity
Sets that the alarm box gives sound corresponding toa certain level and above among all levels in thecurrent alarm pool, including none, warning andabove, minor and above, major and above and critical.
Alarms send to AlarmBox
Selects the alarm of a certain severity that can be
received by the alarm box, including Critical, Major,Minor, Warning.
4. After setting the Alarms send to Alarm Box, click the Advanced button to pop
up the Alarm Box Rule Setting dialog box, as shown in Fig 3.6 -35.
Fig 3.6-35 Alarm Box Rule Setting
5. Click New in the Alarm Box Rule Setting dialog box to pup-up the Details of
Alarm Box Rule dialog box, as shown in Fig 3.6 -36. Enter Rule Name and
Description, and select the alarm filtering conditions on the Selection area.
NOTE:In the Selection area, the left column shows the conditions distinguishing different alarm
types, while the right column shows the alarm types corresponding to different alarm
conditions. It is available to select several alarm conditions and alarm types.
51
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
54/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 3.6-36 Details of Alarm Box Rule
6. Click OKto completing setting the alarm box rule. The system will add a record in
the Alarm Box Rule Setting dialog box, as shown in Fig 3.6 -37.
Fig 3.6-37 Completing an Alarm Box Rule
7. Click OKto pop up the Alarm Box Detail dialog box.
8. Click OK in the Alarm Box Detail dialog box, the system adds an alarm box
52
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
55/86
Chapter 4 Alarm Operations
record in the Alarm Box Setting window, as shown in Fig 3.6 -38.
Fig 3.6-38 Completing an Alarm Box
9. Click the icon on the Alarm Box Setting window. The Confirm dialog box
pops up, clickOKto activate the alarm box.
53
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
56/86
4 Alarm Operations
4.1 Alarm Information Operations
Introduction
This section mainly describes the operations related to the alarm information.
4.1.1 Monitoring Real-Time Alarm Information
Purpose
The real-time monitoring is responsible for monitoring the notifications and alarms
(including current alarms and history alarms) in real time. Monitoring the notifications in
real time can obtain the notification messages of the equipment and network in time.
Monitoring current alarms in real time can obtain the alarm information of the equipment
and network in time. Monitoring history alarms in real time reflects the processing
conditions of alarms that have been processed or recovered in the system.
Prerequisite
Confirm that the user has logged in the network management server normally.
Step
To monitor real-time alarm information, perform the following step.
In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
For detailed procedures of monitoring the real-time information, refer to Table 4.1 -6.
Table 4.1-6 Procedures for Monitoring the Real-time Information
Command Detailed Procedure Description
Realtime AlarmMonitor
In the FaultManagement window,choose Query >Realtime AlarmMonitor to pop up theRealtime Alarmswindow
The window is displayed incolumns. The current alarmsare being monitored in real inthe upper column; while thehistory alarms are beingmonitored in real time in thelower column
Realtime In the Fault Notifications are being
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
57/86
Command Detailed Procedure Description
NotificationMonitor
Management window,
choose Query >Realtime NotificationMonitor to pop up theRealtime Notificationwindow
monitored in real time on this
window
4.1.2 Querying Current Alarms
Purpose
Current alarm query is to query current alarms according to certain conditions. The
current alarm data can be queried according to such conditions as the specified location,time, alarm severity, alarm type, status and alarm causes. These conditions can be set as
required.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the communication between the network management server and the
equipment is normal.
Steps
To query current alarms, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Query > View CurrentAlarms to pop
up the Current Alarm Query Conditions window.
3. Click the icon on this tab to pop up the Current Alarm Query Condition
dialog box, as shown in Fig 4.1 -39. Specify the query conditions as required.
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
58/86
Chapter 4 Alarm Operations
Fig 4.1-39 Current Alarm Query Condition Dialog Box
4. Click OKto add a query record of alarm conditions on the Current Alarm QueryConditions window, as shown in Fig 4.1 -40.
Fig 4.1-40 Current Alarm Query Condition List
5. After selecting a query condition on the Current Alarm Query Conditions
window, click the icon. The View Current Alarms page pops up, listing the
57
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
59/86
TN_SM007_E1_0 ZXWN CS Alarm Management
query results, as shown in Fig 4.1 -41.
Fig 4.1-41 Query Results of Current Alarm
4.1.3 Querying History Alarms
Purpose
History alarm query is to query the history alarms according to certain conditions. The
history alarm data can be queried according to such conditions as the specified location,time, alarm severity, alarm type, status and alarm causes. These conditions can be set as
required.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the communication between the network management server and the
equipment is normal.
Steps
To query the history alarms, perform the following steps:
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Query > View HistoryAlarms to pop
up the History Alarm Query Conditions window.
3. Click the icon on the toolbar to pop up the History Alarm Query Condition
dialog box, as shown in Fig 4.1 -42.
58
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
60/86
Chapter 4 Alarm Operations
Fig 4.1-42 History Alarm Query Condition Dialog Box
4. Set the query conditions as required, enterName and Description, and select the
suitable query conditions from the Selection area. The data filtered by the system
can be queried by selecting the Visibility check box.
5. Click OKto add a query record of alarm conditions on the History Alarm Query
Conditions page, as shown in Fig 4.1 -43.
59
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
61/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.1-43 History Alarm Query Condition List
6. After selecting a query condition on the History Alarm Query Conditions page,
click the icon. The View History Alarmspage pops up, listing the query results.
4.1.4 Synchronizing Alarm Information
Purpose
The alarm synchronization function is to synchronize the Network Element (NE) alarms.
Users can select the system type and the NE location information to be synchronized.
When the alarm data of the network management system are possibly inconsistent with
those of the foreground equipment, manually synchronize the alarm data of the
foreground equipment to the network management server through this function.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the communication between the network management server and the
equipment is normal.
Steps
To synchronize alarm information, perform the following steps:
1. In the main window of the network management client, choose View > Fault
60
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
62/86
Chapter 4 Alarm Operations
Management. The Fault Management window appears.
2. In the Fault Management window, choose Query > Alarm Synchronization topop up the Alarm Synchronization dialog box, as shown in Fig 4.1 -44. Set the
conditions of alarm synchronization.
Fig 4.1-44 Alarm Synchronization
3. Click Selectbutton to set the type of system to be synchronized, as shown in Fig
4.1 -45.
Selecting the BILL Server radio box means synchronizing thealarms on the billing server.
Selecting the NE Alarm radio box means synchronizing thealarms on the foreground NE equipment.
Selecting the SORM Alarm radio box means synchronizing thealarms on the SORM server.
61
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
63/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.1-45 System Type
4. Click OK. The system synchronizes the alarm data in the specified location. The
alerting box pops up when the synchronization is successful.
4.1.5 Alarm Information Statistics
Purpose
The alarm statistics function provides the alarm statistics templates that are frequently
used. Through these templates, the user can perform statistics on the alarm data from
different angles and generate corresponding reports that can be exported to be files in
different formats or printed directly.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To perform alarm statistics, perform the following steps:
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Query > History Alarm Statistics to
62
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
64/86
Chapter 4 Alarm Operations
pop up the Report Management window. From the resource pane of the Report
Management window, choose Report Template Tree > Server (OMM server ID)
to pop up the List of Report Templates page, as shown in Fig 4.1 -46.
Fig 4.1-46 Alarm Template List
3. Double-click the required alarm statistics template from the list to pop up the
Parameter Input Box, as shown in Fig 4.1 -47. Specify the parameters of alarm
selection conditions and other conditions. For the parameter descriptions, refer to
Table 4.1 -7.
63
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
65/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.1-47 Parameter Input
Table 4.1-7 Parameter Descriptions for Alarm Statistics
Alarm Selection Description
System Type Including such types as the Alarm Box Link BreakAlarm, Bill Server Alarm, Correlation Alarm, LinkAlarm, Local and RemoteOMC Linkdown Alarm, NEAlarm, Performance QoS Alarm, SORM Server Alarm,and System Management.
Location The System Type must beselected before selecting thelocation, which is selected based on the different systemtypes.
Alarm Code The System Type must be selected before selecting thealarm code. The available alarm codes on the right panevary with different system types.
Severity Including critical, major, minor and warning.
Alarm Type Including Communication Alarm, Environment Alarm,Equipment Alarm, OMS Alarm, Processing Alarm and
QoS Alarm
Probable Cause The System Type must be selected before selecting theprobable causes. The available probable causes on the
64
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
66/86
Chapter 4 Alarm Operations
Alarm Selection Description
right pane vary with different system types.
Happen Time Including By Time Range and By Relative Time
Acknowledgment
Status
Including Acknowledged and Unacknowledged.
(Un)acknowledgeOperator
Sets the operator who acknowledges/unacknowledgesalarms.
(Un)acknowledgingTime
Sets the range of time alarms to beacknowledged/unacknowledged.
Restore Type Including such options as Normal, Cleared by User,Restoration upon NE Restart, Restoration uponSynchronization, Restoration upon Alarm Pool Fill-up, Restoration upon UMS Restart, Auto Cleared andRestoration upon NE Delete
Clear Operator Sets the operator who clears alarms.
Restore Time Sets the range of time alarms to be restored.
Details Sets the detailed information of statistics.
4. Click OKto start statistics. The statistical results will be listed on the View Report
page, as shown in Fig 4.1 -48.
Fig 4.1-48 Alarm Statistics Results
Subsequent Optional Operations
The subsequent optional operations are as follows.
Viewing chart: on the toolbar of the View Report page, click the
icon to view the statistical result through a chart.
65
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
67/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Exporting: on the toolbar of the View Report page, click the
corresponding icon to export and save the report in
the corresponding file format.
Printing: click the icon on the toolbar of the View Report pageto print the report results.
4.2 Alarm Record Operations
Introduction
This section mainly describes the operations related to the alarm records.
4.2.1 Acknowledging an Alarm
Purpose
Acknowledging an alarm is to change the status of an alarm from the unacknowledged
status to the acknowledged status. Acknowledge an alarm in the unacknowledged status
through this function when the maintenance personnel have known it and started to
process it.
Prerequisite
Confirm that the queried alarm information is the one to be acknowledged.
For the operation of querying alarms, refer to Querying Current Alarms and Querying
History Alarms.
Steps
To acknowledge an alarm, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. From the alarm list of the Realtime Alarms window, right-click the alarm required
to be acknowledged, and select Acknowledge from the short-cut menu, as shown in
Fig 4.2 -49.
66
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
68/86
Chapter 4 Alarm Operations
Fig 4.2-49 Selecting Acknowledge from the Short-cut Menu
3. Enter the acknowledging information in the popup Acknowledge Alarm dialog box.
Users can enter the information based on the actual alarm processing, as shown in
Fig 4.2 -50.
Fig 4.2-50 Acknowledging Alarm Dialog Box
4. Click OKto acknowledge the alarm.
Result
The status of this alarm is changed from the unacknowledged status to the acknowledged
status.
67
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
69/86
TN_SM007_E1_0 ZXWN CS Alarm Management
4.2.2 Unacknowledging an Alarm
Purpose
Unacknowledging an alarm is to change the status of analarm from the acknowledged
status to the unacknowledged status. This operation can only be performed on the alarm
information that has been acknowledged.
Prerequisite
Confirm that the queried alarm information is the one to be unacknowledged. For the
operation of querying alarms, refer to Querying Current Alarms and Querying History
Alarms.
Steps
To unacknowledge an alarm, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. From the alarm list, right-click the alarm to be unacknowledged, select
Unacknowledge from the short-cut menu.
3. Enter the information in the popup Unacknowledge Alarm dialog box. Users can
enter the information based on the actual alarm processing.
4. Click OKto complete the operation.
Result
The status of this alarm is changed from the acknowledged status to the unacknowledged
status.
4.2.3 Clearing an Alarm
Purpose
Clearing an alarm is to clear the alarm shown in the Realtime Current Alarms page of
the Realtime Alarms window. The cleared alarm will be automatically shown in the
Realtime History Alarms page of the Realtime Alarms window, and can be queried by
performing history alarm query.
Prerequisite
Confirm that the user has logged in the network management server normally.
68
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
70/86
Chapter 4 Alarm Operations
Steps
To clear an alarm, perform the following steps:
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Realtime Current Alarms page of the Realtime Alarms window, right-click
the alarm to be cleared, and select Clear from the short-cut menu.
3. The Confirm dialog box pops up. Click OKto clear the alarm. The cleared alarm
will be automatically shown in the Realtime History Alarms page.
Reference
For querying the history alarm information, refer to Querying History Alarms.
4.2.4 Forwarding an Alarm
Purpose
Forwarding an alarm is to forward an alarm to the other specified administrators by
sending the SM or Email, for the administrators to handle the alarm in time.
Prerequisite
Confirm that the user has logged in the network management servernormally.
Confirm that the ZXWN network management server is connected tothe Short Message Center (SMC) and the Email server normally.
Steps
To forward an alarm, perform the following steps:
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Realtime Current Alarms page of the Realtime Alarms window, right-click
the alarm to be forwarded, and select Forward from the short-cut menu.
3. The Forwarding Setup dialog box pops up, as shown in Fig 4.2 -51. Enter the
Forwarded-to Email Address and Forwarded-to Phone Number of the
personnel to process the alarm. It is available to select Forward by Email and
Forward by SMS.
When selecting the Forwarded-to Email Address check box,
input contents in the Forward by Email page.
69
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
71/86
TN_SM007_E1_0 ZXWN CS Alarm Management
When selecting the Forwarded-to Phone Number check box,input contents in the Forward by SMS page.
Fig 4.2-51 Forwarding Setup
4. Click OKto forward the alarm to specified personnel.
4.2.5 Viewing Detailed Alarm Information
Purpose
By viewing the detailed information of alarms and referring to the corresponding
maintenance suggestions, users can locate and handle faults in time.
Prerequisite
Confirm that the user has logged in the network management servernormally.
Confirm that the queried alarm information is the one to be viewed.
For the operation of querying alarms, refer to Querying Current Alarms and Querying
History Alarms.
Steps
To view the detailed alarm information, perform the following steps:
1. In the Realtime Current Alarms page of the Realtime Alarms window, right-click
the alarm to be viewed, and select Details from the short-cut menu.
70
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
72/86
Chapter 4 Alarm Operations
2. The Details window pops up to show the detailed information of the alarm, as
shown in Fig 4.2 -52. For parameter descriptions, refer to Table 4.2 -8.
Fig 4.2-52 Details
3. Select the Maintenance suggestion tab to display the maintenance suggestions of
the alarm, as shown in Fig 4.2 -53.
Fig 4.2-53 Maintenance Suggestion
71
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
73/86
TN_SM007_E1_0 ZXWN CS Alarm Management
4. Click Close to close the window.
Reference
The main contents about the alarm details are shown in Table 4.2 -8.
Table 4.2-8 Parameter Descriptions for Alarm Information
Parameters Description Example
Node No. The number of the OMMnode that generates alarms
100001
System Type The system type of thealarm
Link Alarm
ID System ID 1200935849140
Internal ID Internal number of thesystem
1200935849141
Location The location where alarmsare generated
Subnet = 0,
Ne = 1,
Module = 1
Alarm Code The brief description andalarm code of an alarm
Broken link between OMCand NE (1000)
Severity Advanced national severity Critical
Alarm Type Alarm type Communication Alarm
Probable Cause The probable cause of the
alarm
Communication abnormal (0)
Happen Time The time when an alarm isgenerated
2008-01-21 09:19:25
AcknowledgmentStatus
Acknowledged/unacknowledged status ofthe alarm
Unacknowledged
(Un)acknowledgeOperator
The operator toacknowledge/
unacknowledge this alarm
Admin
(Un)acknowledgeSystem
The network managementsystem to acknowledge/unacknowledge this alarm
100001
(Un)acknowledgeInformation
The information enteredwhen acknowledging/unacknowledging this alarm
OK
(Un)acknowledgeTime
The time when this alarm isacknowledged/unacknowledged
2008-01-26 14:49:25
Comment
Information
The information of comment
72
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
74/86
Chapter 4 Alarm Operations
Parameters Description Example
Details Detailed information related
to this alarm
Netype=
MSCServer
Last Update Time
NE Type The type of the NE wherethis alarm is generated
MSCServer
4.2.6 Printing Alarm Information
Purpose
The print function is used to print the alarm data among the alarm list that is opened by
the current user. Set such items as the print range, copies, page setup and appearancebefore printing to satisfy the requirements of the printing effect.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the queried alarm information is the one to be printed.
For the operation of querying alarms, refer to Querying Current Alarms and Querying
History Alarms.
Confirm that the printer is connected and set correctly.
Steps
To print alarm information, perform the following steps.
1. On the alarm list window, click the on the toolbar. The Print Setup dialog box
pops up, and performs the General settings, as shown in Fig 4.2 -54.
73
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
75/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.2-54 Print Setup, General
2. Select the Page Setup tab to set the page parameters, as shown in Fig 4.2 -55.
Fig 4.2-55 Print Setup, Page Setup
3. Select the Advance tab to set the parameters as required, as show in Fig 4.2 -56.
74
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
76/86
Chapter 4 Alarm Operations
Fig 4.2-56 Print Setup, Advance
4. When completing the setting, click Print to start printing the alarm list. Click
Preview All to preview the printing effect.
4.2.7 Exporting Alarm Information
Purpose
The export function is used to export the data of all alarms on the alarm list window that
is opened by the current user to a file, whose format can be text, EXCEL, PDF, HTML or
CSV.
Prerequisite
Confirm that the user has logged in the network management server normally.
Confirm that the queried alarm information is the one to be exported.
For the operation of querying alarms, refer to Querying Current Alarms and Querying
History Alarms.
Steps
To export the alarm data, perform the following steps:
1. On the alarm list window, click the on the toolbar to pop up the Save dialog
box. Set the Save In, File Name and Files of Type, as shown in Fig 4.2 -57.
75
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
77/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.2-57 Saving Dialog Box
2. Click Save to export the data of the selected alarm list to the specified file in the
specified path.
4.3 Alarm Maintenance Suggestions
Introduction
This section mainly describes the operation related to the alarm maintenance suggestions.
4.3.1 Adding an Alarm Maintenance Suggestion
Purpose
Based on the long-term running of the network, the maintenance experience on common
problems can be summarized as the reference for solving similar problems in the future.
The summary of such maintenance experience is the customized alarm maintenance
suggestion.
Adding a new alarm maintenance suggestion is to add a new suggestion of processing
one type of alarms based on the actual operations.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To add an alarm maintenance suggestion, perform the following steps.
76
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
78/86
Chapter 4 Alarm Operations
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Maintenance Suggestion
Setting to pop up the Maintenance Suggestion Setting window, as shown in Fig
4.3 -58.
Fig 4.3-58 Maintenance Suggestion Setting
3. On the Maintenance Suggestion Setting window, from the System Type drop-
down list, select the alarm type to be set, including All System Type, Alarm Box
Link Break Alarm, Bill Server Alarm, Correlation Alarm, Link Alarm, Local
and Remote OMC Linkdown Alarm, NE Alarm, Performance QoS Alarm,
SORM Server Alarm and System Management.
4. Click the icon on the toolbar to pop up the Maintenance suggestion dialog
box. Select Alarm Code and Reason Description, and enter the suggestion in the
Customized Suggestions text box, as shown in Fig 4.3 -59.
77
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
79/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Fig 4.3-59 Maintenance Suggestion
5. Click OKto finish the configuration of the alarm maintenance suggestion.
4.3.2 Modifying an Alarm Maintenance Suggestion
Purpose
Modifying an alarm maintenance suggestion is to improve the established suggestions
based on the actual operations. The modified alarm maintenance suggestion will be
shown in the Customized Suggestions text box, which will not replace the default
suggestion.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To modify an alarm maintenance suggestion, perform the following steps.
1. In the main window of the network management client, choose View > Fault
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Maintenance Suggestion
Setting to pop up the Maintenance Suggestion Setting window.
3. On the Maintenance Suggestion Setting window, from the System Type drop-
down list, select the alarm type to be modified.
78
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
80/86
Chapter 4 Alarm Operations
4. From the suggestion list on the Maintenance Suggestion Setting window, click the
suggestion to be modified.
5. Click the on the toolbar to pop up the Maintenance suggestion dialog box, as
shown in Fig 4.3 -60. Enter the modified suggestion in the Customized
Suggestions text box.
Fig 4.3-60 Modifying an Alarm Maintenance Suggestion
6. Click OKto finish the modification of the alarm maintenance suggestion.
4.3.3 Exporting an Alarm Maintenance Suggestion
Purpose
The ZXWN network management system allows the user to export alarm maintenance
suggestions in the system to a file. It supports exporting alarm data to a text, EXCEL,
PDF or HTML file.
Prerequisite
Confirm that the user has logged in the network management server normally.
Steps
To export an alarm maintenance suggestion, perform the following steps.
1. In the main window of the network management client, choose View > Fault
79
7/27/2019 TN_SM007_E1_0 ZXWN CS Alarm Management-92.doc
81/86
TN_SM007_E1_0 ZXWN CS Alarm Management
Management. The Fault Management window appears.
2. In the Fault Management window, choose Setting > Maintenance S