THREE-PHASE GRID-CONNECTED INVERTER USING CURRENT
REGULATOR
Tran Quang Tho, Truong Viet Anh
Faculty of Electrical & Electronic Engineering,
HCM City University of Technical Education
ABSTRACT
This paper presents an approach for a three-phase grid-connected inverter using
current regulator. The switching frequency of hystereris in the current modulation is fixed by
comparing the current error with carrier wave with the constant frequency of the multiple of
3. The LCL filter is installed at the inverter output to offer high harmonic attenuation. In
order to determine simply the parameters of PI regulators, the methods of PSO, GA and the
conventional Ziegler-Nichols are used to search the best values with high global stability. Thesimulation results in Simulink/Matlab show that the PI regulators designed by PSO method
demonstrate better results than Ziegler-Nichols and even GA technique.
Keywords: gen algorithm (GA), particle swarm optimization(PSO)
I. INTRODUCTION
The demand of renewable energy sources such as solar energy is becoming more
popular for sustainability and environment with enormous potentials [1]. In order to convert
solar DC source to three-phase AC power needs to have 3-phase inverters that have been well
researched in recent years [2].
The current modulation plays an important role in power electronic systems,especially in voltage source inverters [3]. The advantages of current regulator are very
simple, fast response, high robust and overload protection. In addition, it also keeps power
factor unity and does not depend on voltage drop of switches [15]. However, the hysteresis
PWM has unfixed switching frequency that increases loss of switches and current THD [16].
The elimination of common mode voltage in VSIs aims to reduce THD by using
compensation circuitry [4], harmonic filters [5], [6], [7] and carrier wave phase shift [8] is
very complicated. In order to meet grid-connected standard IEEE Std 929-2000 [9] with
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING
& TECHNOLOGY (IJEET)
ISSN 0976 6545(Print)ISSN 0976 6553(Online)
Volume 4, Issue 2, March April (2013), pp. 293-304 IAEME:www.iaeme.com/ijeet.aspJournal Impact Factor (2013): 5.5028 (Calculated by GISI)
www.jifactor.com
IJEET
I A E M E
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
2/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
294
harmonic attenuation [10], LCL filter is installed at inverter output. The simulation results
discussed show that the PI regulators designed by PSO demonstrate better results than
Ziegler-Nichols and even GA method.
II. MODEL OF GRID-CONNECTED THREE PHASE INVERTER AND CONTROL
STRATEGY
The principle diagram of grid-connected three phase system is shown in Fig 1.
Fig 1: Simplified model of the grid-connected inverter with L filter
II.1. Current regulationThe three phase AC quantities Ia, Ib and Ic in the stationary frame are transformed into
the DC components Id and Iq in the synchronously rotating frame by the phase angle ofPLL. With L filter in grid-connected VSI as Fig 1, voltage equation of phase A in the
stationary frame is:
)1(ViRVdtdiL gaagia
a =
And phases B and C are similar. When neglecting resistor Rg, equation (1) became:
)2(VVdt
diL gaia
a =
The equation (2) shows that phase current can be regulated by amplitude and phase angle
of Vi at inverter output with constant Vg as Fig 2.
Fig 2: Relationship between Vi and Ig in dq frame
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
3/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
295
Active and reactive powers in dq frame are calculated as (3) and (4).
( )
( ) )4(IVIV23Q
)3(IVIV2
3P
gqgdgdgq
gqgqgdgd
=
+=
With reference P_refand Q_ref, currents Idp and Iq can determine as:
( ))5(
V
V
PQ
QP
VV3
2
I
I
gq
gd
ref_ref_
ref_ref_
2
gq
2
gdq
dp
+=
The current Idp depends on DC source power status of solar. So:
)6(PP dcref =
For optimization of generation, only active power is to be injected in the grid and
reference Iq is zero. Pdc and Idp can be determined by MPPT technique. To obtain the closed
loop response, Id and Iq are taken from the outputs of the inner loop PI regulator, as (7).
Where Id and Iq are the reference currents. Kp and Ki are the proportional and integral gain
constants respectively. These gain constants are determined by tuning the regulators for
optimal response with methods of Ziegler-Nichols, GA and PSO.
)7(II
II
s
KK0
0s
KK
I
I
qgref_q
dgref_d
iq_i
iq_p
id_i
id_p
*
q
*
d
+
+=
The LCL filter of the inverter output is proposed as Fig 3.
Fig 3: The proposed diagram of three phase inverter with LCL filter
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
4/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
296
II.2. DC link voltage control
The DC voltage is held at a constant value by using a PI regulator which provides the
real current reference as (8). Where V*dc is the DC voltage of MPPT.
[ ] )8(VVsKKII dc
*dc
dc_idc_pdpref_d
+=
II.3. PWM modulation
Current error: )9(III gref_gerror_ =
Then:( )
)10(VVdt
IdL iref_i
error_=
Current errors are compared with carrier wave of fixed frequency and amplitude. If
the current error is positive and larger than the carrier wave, the switches are activated to
apply +Vdc. On the other hand, if current error is positive and smaller than the carrier wave,
the switches are activated to apply Vdc as Fig 4.
Fig 4: PWM modulation
II.4. Tuning parameters of PI regulator:With LCL filter, parameters of PI regulators effect significantly on THD of inverter
output current [11].
The conventional tuning methods of PI regulator such as Ziegler-Nichols rules and
GA have been applied to tune the controller recently. Randomly searching technique such as
GA that has high efficient computational and global searching capabilities has been applied
successfully to optimize the complex problems. But the premature convergence of GA
degrades its performance and reduces its searching capabilities. The PSO algorithm is
proposed in this paper to tune PI regulator.
The Ziegler-Nichols method:
Fig 5: Single phase equivalent circuit of LCL filter
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
5/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
297
In Fig 5, when assuming no harmonic at PCC, then Vg=0. For a balanced system the
transfer function of the LCL filter for every phase is given by (11).
;RRC;RRCLLC
;RLCRLCC;LLCC:where
)11(CsCsCsC
1sRCsLC
)s(V
)s(I
ig4igfig3
gifigf2igf1
43
2
2
3
1
gf
2
gf
i
i
+=++=
+==
+++
++=
and Ri and Rg are resistors of inductances Li and Lg respectively.
System parameters: Vdc=650V; Ldc=3mH; Rdc=1; Cdc=500F; grid voltage =380V;
50Hz; short-circuit power=40KVA; Lg=1mH; Rg=0.1; Cf=5F; Li=2mH; Ri=0.2; carrierwave frequency fc=9KHz.
Kgh=30 and Tgh=3.888 are determined by Ziegler-Nichols method in (11).
In the GA method with flowchart in Fig 6a
Fig 6a: GA flowchart Fig 6b: PSO flowchart
In the PSO method, velocity and position are updated by equations (12) and (13) in flowchart
in Fig 6b.
)13(V.PP
)12()PP(R.)PP(R.)t(V.wV
curcurcur
curglobes2curlobes1cur
+=
++=
Results of tuned parameters are shown in table 1
Method Kp_Id Ki_Id Kp_Iq Ki_Iq
Ziegler-
Nichols13.5 4.182 13.5 4.182
GA 5.6208 200.046 3.4441 1.0156
PSO 4.3523 179.534 2.442 4.0112
Table 1: parameters of PI regulators
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
6/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
298
III. SIMULATION RESULTS AND DISCUSSION
Fig 7: Simulation model in Simulink/Matlab.
The current Id increases from 5A up to 10A at 3.803s.
III.1. Results with Ziegler-Nichols:
Fig 8a: Three-phase voltage (V)
Terminator3
PI_Idq
PI_idq
PI_Vdc
PI_Vdc
0
Iq=0
Idp
[gates]
Goto
[Vdc_ref]
From6
[Vdc]
From5
[Iabc]
From4
[Iabc]
From3
wt
From2
wt
From1
abc
wt
dq0
abc_dq0
Embedded
MATLAB Function1
dq
wt
abcdq0_abc
Embedded
MATLAB Function
9KHz
I*_abc
Carrier
I_abc
gates
6 xung
wt
wt
650
Vsol
A
B
C
Three-Phase Source
VabcA
B
C
a
b
c
Three-Phase
V-I Measurement
IabcA
B
C
a
b
c
Three-Phase
I Measurement
a
b
c
A
B
C
Ri_Li
a
b
c
A
B
C
Rg_Lg
Gates
Vso
VDCA
B
C
Inverter
[Iabc]
I
Vdc
Goto3
[gates]
From
a b c
A B C
C
Vabc (pu)wt
3-phase PLL
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-400
-300
-200
-100
0
100
200
300
400
3-phase voltage (V)
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
7/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
299
Fig 8b: Three-phase current (A)
Fig 8c: Active power P (w) and reactive power Q (var)
Fig 8d: THD spectrum of current
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-10
-5
0
5
10
3-phase current (A)
0 1 2 3 4 5 6 7
x 105
-2000
0
2000
4000
6000
3.63 3.64 3.65 3.66 3.67 3.68 3.69 3.7 3.71 3.72
-4
-2
0
2
4
FFT window: 5 of 288.7 cycles of selected signal
Time (s)
0 200 400 600 800 10000
1
2
3
4
Frequency (Hz)
Fundamental (50Hz) = 4.521 , THD= 5.20%
Mag(%ofFun
damental)
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
8/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
300
III.2. RESULTS WITH GA:
Fig 9a: Three-phase voltage (V)
Fig 9b: Three-phase current (A)
Fig 9c: Active power P (w) and reactive power Q (var)
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-400
-300
-200
-100
0
100
200
300
400
3-phase voltage (V)
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-10
-5
0
5
10
3-phase current (A)
0 1 2 3 4 5 6 7
x 10
5
-2000
0
2000
4000
6000
P (w) & Q (var)
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
9/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
301
Fig 9d: THD spectrum of current
III.3. RESULTS WITH PSO:
Fig 10a: Three-phase voltage (V)
Fig 10b: Three-phase current (A)
3.61 3.62 3.63 3.64 3.65 3.66 3.67 3.68 3.69 3.7-5
0
5
FFT window: 5 of 305.3 cycles of selected signal
Time (s)
0 200 400 600 800 10000
0.5
1
1.5
2
2.5
Frequency (Hz)
Fundamental (50Hz) = 5.007 , THD= 3.41%
Mag(%ofFundamental)
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-400
-300
-200
-100
0
100
200
300
400
3-phase voltage (A)
3.75 3.76 3.77 3.78 3.79 3.8 3.81 3.82 3.83 3.84 3.85
x 105
-10
-5
0
5
10
3-phase Current (A)
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
10/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
302
Fig 10c: Active power P (w) and reactive power Q (var)
Fig 10d: THD spectrum of current
thod % THD of output current
Ziegler-Nichols 5.20
GA 3.41
PSO 2.93
Table 2: THD of output current at PCC
IV. DISCUSSION
Parameters of PI regulators in GA and PSO methods always give Kp_Id Kp_Iq and
Ki_Id Ki_Iq.
Power responses in figures 8c, 9c and 10c demonstrate that GA and PSO methods
give results better than Ziegler-Nichols method.
The output currents harmonics in figures 8d, 9d and 10d also show that PSO method
in the table 2 gives the best result current THD is 2.93%.
0 1 2 3 4 5 6 7
x 105
-2000
0
2000
4000
6000
P (w) & Q (var)
3.63 3.64 3.65 3.66 3.67 3.68 3.69 3.7 3.71 3.72
-5
0
5
FFT window: 5 of 264.4 cycles of selected signal
Time (s)
0 200 400 600 800 10000
0.5
1
1.5
2
Frequency (Hz)
Fundamental (50Hz) = 5.009 , THD= 2.93%
Mag(%ofFundamental)
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
11/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
303
V. CONCLUSION
This paper presents an approach for a three-phase grid-connected inverter using
current regulator with low current THD by using LCL filter at inverter output and good
response.
The PSO algorithm is proposed in this paper to tune parameters of PI regulator gives
global results better than Ziegler-Nichols and even GA method.
Control strategies proposed is a good alternative to implement an inverter system
control with reduced harmonic content injected into the grid and less computational load than
other methods.
REFERENCES
[1] Stphan Astier, Systmes solaires photovoltaques, Seminar on 15/02/2011 at Technical
University HCM city.
[2] Amirnaser Yazdani and Prajna Paramita Dash, A Control Methodology and
Characterization of Dynamics for a Photovoltaic (PV) System Interfaced With a Distribution
Network, IEEE Transactions on Power Delivery, Vol. 24, No. 3, July 2009.[3] Jos Rodrguez, Jorge Pontt, Predictive Current Control of a Voltage Source Inverter,
IEEE Transactions on Industrial Electronics, Vol. 54, No. 1, February 2007.
[4] K. H. Edelmoser, Common Mode Problematic of Solar Inverter Systems, Proceedings
of the 11th WSEAS International Conference on Circuits, 2007 .
[5] Eftichios Koutroulis, Frede Blaabjerg, Methods for the Optimal Design of Grid-
Connected PV Inverters, International Journal of Renewable Energy Research, IJRER-
vol.1,No.2,pp.54
[6] Hyosung Kim, Kyoung-Hwan Kim, Filter design for grid connected PV inverters,
ICSET 2008.
[7] H. R. Karshenas, and H. Saghafi, Performance Investigation of LCL Filters in Grid
Connected Converters, IEEE PES Transmission and Distribution Conference and
Exposition Latin America, Venezuela, 2006.[8] M. Brenna, R. Chiumeo and C. Gandolfi, Harmonic analysis: comparison between
different modulation strategies for three phase inverter connecting Distributed Generation,
Politecnico di Milano-Department of Energy, Italy-2011 .
[9] IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) systems, IEEE
Standard 929-2000, Jan. 2000.
[10] M.A.A. Younis, N. A. Rahim, and S. Mekhilef, Harmonic Reduction In Three-Phase
Parallel Connected Inverter, World Academy of Science, Engineering and Technology 50
2009 - 64,2011
[11] Erika Twining, Donald Grahame Holmes, Modelling grid-connected voltage source
inverter operation, Power Electronics Group-Department of Electrical and Computer
Systems Engineering Monash University, Clayton
[12] Byeong-Mun Song, Youngroc Kim, Hanju Cha, Hakju Lee, Current HarmonicMinimization of a Grid-Connected Photovoltaic 500kW Three-Phase Inverter using PR
Control, IEEE 2011
[13] Miguel Castilla, Jaume Miret, Antonio Camacho, Jos Matas, and Luis Garca de
Vicua, Reduction of Current Harmonic Distortion in Three-phase Grid-connected
Photovoltaic Inverters via Resonant Current Control, IEEE 2011
7/30/2019 THREE PHASE GRID-CONNECTED INVERTER USING CURRENT.pdf
12/12
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME
304
[14] X.Q. Guo W.Y. Wu, Improved current regulation of three-phase grid-connected
voltage-source inverters for distributed generation systems, IET Renewable Power
Generation, September 2009
[15] Leonardo Augusto Serpa, Current Control Strategies for Multilevel Grid Connected
Inverters, Swiss Federal Institute of Technology Zurich, 2007
[16] George Alin Raducu, Control of Grid Side Inverter in a B2B Configuration for WT
Applications, Aalborg University, 2008
[17] Satyaranjan Jena, B.Chitti Babu, S.R.Samantaray and Mohamayee Mohapatra,
Comparative Study between Adaptive Hysteresis and SVPWM Current Control for Grid-
connected Inverter System,
[18] R. Arivoli Dr. I. A. Chidambaram Multi-Objective Particle Swarm Optimization
Based Load-Frequency Control Of A Two-Area Power System With Smes Inter Connected
Using Ac-Dc Tie-Lines International Journal of Electrical Engineering & Technology
(IJEET), Volume 3, Issue 1, 2012, pp. 1- 20, ISSN Print : 0976-6545, ISSN Online: 0976-
6553.
[19] Mr. Laith O. Maheemed, Prof. D.S. Bankar, Harmonic Mitigation For Non-Linear
Loads Using Three-Phase Four Wire Upqc Control Strategy International Journal of
Electrical Engineering & Technology (IJEET), Volume 3, Issue 1, 2012, pp. 247- 260, ISSNPrint : 0976-6545, ISSN Online: 0976-6553.
[20] Pradeep B Jyoti, J.Amarnath and D.Subbarayudu The Scheme of Three-Level Inverters
Based On Svpwm Overmodulation Technique for Vector Controlled Induction Motor Drives
International Journal of Electrical Engineering & Technology (IJEET), Volume 4, Issue 2,
2013, and pp. 245- 260, ISSN Print: 0976-6545, ISSN Online: 0976-6553.