Thinner is Better 3M TM FireDam TM Intumescent Coating WB 1000 1 Installation Manual 3

Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

Embed Size (px)

Citation preview

Page 1: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

Thinner isBetter

3MTM FireDamTM Intumescent Coating WB 1000

1

Installation Manual

3

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 1

Page 2: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

2

1. Product Description page 3

2. Instruction page 3

3. Specifications page 3

4. Precautions & Limitations page 4

5. Packaging & Shelf Life page 4

6. Preparatory Work page 4

7. Masking page 4

8. Primers page 5

9. Application Rates page 5

10. Coverage page 6

11. Topcoats page 7

12. Precautions & Safe Handling Information page 7

13. Maintenance page 7

Index

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 2

Page 3: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

3

3MTM FireDamTM Intumescent Coating WB 1000 is a single component water-based thin film coating to fireproof interior structural steel.

3MTM FireDamTM Intumescent Coating WB 1000 for steel should be installed by trained and certified 3M authorized applicators.

3MTM FireDamTM Intumescent Coating WB 1000 is listed by independent test agencies such as ULC and UL and is tested to,and passes the criteria of, Standard “Fire Tests of Building Construction and Materials, “CAN/ULC-S101-07 Edition (ANSI/UL263 – 13TH Edition, ASTM E119-2000 Edition).

Typically Specified Division

Division 7

Section 07812 – Intumescent Fire Resistive Material

Related Sections

Section 05100 – Structural Steel

Section 05120 – 05500 – Structural steel and metal fabrications with reference to primer receiving fire protection materials

Section 07811 – Spray-Applied Fire Resistive Material

Section 09900 – Painting

Fire Test Designs3MTM FireDamTM Intumescent Coating WB 1000 was tested by ULC/UL on a large scope of columns, beams, floor assembliesand passed.

Refer to the ULC/UL Directory for the 3MTM FireDamTM Intumescent Coating WB 1000 designs or please contact 3M.

1. Product Description

2. Instruction

3. Specifications

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 3

Page 4: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

4

3MTM FireDamTM Intumescent Coating WB 1000 for steel must be stored indoor in dry conditions between 10˚C and 40˚C.

Protect from frost and freezing, excessive heat and strong radiant sunlight. Not intended for exterior applications.

Comply with manufacturing recommendations for temperature and humidity conditions before, during and after installation offireproofing. Refer to section 9. Application Rates & Conditions

Packaging: Volume 18.9 liter (5 gal.) / Weight per pail: 61.6 Lbs (27.8 Kg)

Shelf Life

3MTM FireDamTM Intumescent Coating WB 1000 shelf life is 6 months in original unopened containers from date of packagingwhen stored above 10˚C (50˚F).

Lot numbering: First digit = last digit of yearSecond to fourth digit = 3 digit day of the year (from 001 to 365/366)Fifth indicator = dash symbol (-)Sixth to eighth = batch # (may only be 1 or 2 digits long)

3MTM FireDamTM Intumescent Coating WB 1000 for steel should be installed with an Airless spray pump such as SpraytechEP2355 or Graco 1595 / Ultra Max 795 or brush. All surfaces receiving the 3MTM FireDamTM Intumescent Coating WB 1000 forsteel should be thoroughly cleaned of oil, grease, dirt, loose paint, loose mill scale and any other matter that will impair bond.

Existing Conditions:

(1) Verify existing conditions and substrates before starting work. Correct unsatisfactory conditions before proceeding.

(2) Proceed with installation only after steel components are primed with compatible recommended primer. *Refer to section 8. Primers

Provide masking and drop cloths to prevent contamination of adjacent surfaces by fireproofing material.

5. Packaging & Shelf Life

6. Preparatory Work

7. Masking

4. Precautions & Limitations

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 4

Page 5: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

5

General instructions for installing 3MTM FireDamTM Intumescent Coating WB 1000 for steel include confirmation of primer compatibility such as recommended Alkyd and Epoxy primers to receive 3MTM FireDamTM Intumescent Coating WB 1000.

Note: Primers containing zinc metal are generally not recommended.

Apply 3MTM FireDamTM Intumescent Coating WB 1000 only to primed surfaces. Site conditions and end-use may dictate spe-cific primer specifications. Follow primer manufacturer’s instructions.

Refer to the 3MTM FireDamTM Intumescent Coating WB 1000 fire test design information to determine the minimum dry filmthickness required for the size and orientation of steel element to be protected and for the required fire resistance rating.

3MTM FireDamTM Intumescent Coating WB 1000 should be applied in sufficient wet film thicknesses to achieve the required fireresistive rating with as many passes as necessary, to attain required (DFT) dry film thickness.

3M™ FireDam™ Intumescent Coating WB 1000 should not be applied when relative humidity exceeds 80% or the surface tobe coated is less than 3˚C above the dewpoint. The product is recommended to be applied only when temperatures are above10˚C or 50˚F.

To ensure an even coating thickness, the desired thickness should be achieved by the application of successive coats of no more than 500 microns dft (760 microns wft) per coat. Apply in sufficient thickness to achieve rating to uniform density and texture.

The completed dry film thickness should be checked to ensure the required thickness has been applied.

When multiple coats of 3M™ FireDam™ Intumescent Coating WB 1000 are required to achieve the prescribed dry film thickness, adequate drying time between the coats should be allowed. At 20˚C the minimum overcoating time is typically 4-6 hours. (The time will vary depending upon the prevailing temperature, relative humidity, air movement and thickness of material applied).

9. Application Rates

8. Primers

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 5

Page 6: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

6

Chart based on laboratory results of 3MTM FireDamTM Intumescent Coating WB 1000.

MetricArea (sq. meter) Volume / Pail (L) Volume % WFT (mm) DFT (mm)10 18.93 1.8920 18.93 0.9530 18.93 0.6340 18.93 0.4750 18.93 0.3860 18.93 0.3270 18.93 0.2780 18.93 0.2490 18.93 0.21100 18.93 0.19

10. Coverage

ImperialArea (sq. feet) Volume / Pail (gal) Volume % WFT (mil) DFT (mil)100 5 66 80.21200 5 40.10300 5 26.74400 5 20.05500 5 16.04600 5 13.37700 5 11.46800 5 10.03900 5 8.911000 5 8.02

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 6

6666

66

6666

6666

66

66

6666

66

6666

6666

6666

66

52.94

26.47

17.65

13.23

10.59

8.82

7.56

6.62

5.88

5.29

1.25

0.62

0.42

0.31

0.25

0.21

0.18

0.16

0.14

0.12

Page 7: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

3MTM FireDamTM Intumescent Coating WB 1000

7

A compatible topcoat with 3MTM FireDamTM Intumescent Coating WB 1000 is recommended for all installations, in order to givethe desired colour. All topcoats should be applied in accordance with the topcoat manufacturer’s recommendations.

Either acrylic or silicone alkyd paint to match surroundings are recommended.

Ensure the 3MTM FireDamTM Intumescent Coating WB 1000 is thoroughly dry before application of topcoat.

Follow approved working practices. Wear government approved respirators and proper clothing, reading all warning labels, andfollow instruction on the MSDS.

No maintenance is required when installed in accordance with the 3M installation manual. Once installed, if any section of the3MTM FireDamTM Intumescent Coating WB 1000 is damaged, the damaged section should be repaired (touched up) by a 3Mtrained and certified applicator.

11. Topcoats

12. Precautions & Safe Handling Information

13. Maintenance

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 7

Page 8: Thinner Bettermultimedia.3m.com/mws/media/536712O/intumescent... · Thinner is Better 3MTM FireDamTM Intumescent Coating WB 1000 1 Installation Manual 3 0808-3086E 3M FD Intumescent

8

3M Fire Protection ProductsriF dna M3.cnI adanaC M3 eDam are trademarks of 3M.

London, Ontario, Canada Used under licence in Canada.r sthgir llA M3 ,8002 ©0481 562 008 eserved. Printed in Canada

1009-03119Eci/ac.m3.www

0808-3086E 3M FD Intumescent Coating WB 1000 - INSTALLATION MANUAL:Layout 1 9/30/08 2:32 PM Page 8