The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period -24.1°C Lowest ambient temperature during test period -12.6°C Indoor refrigeration required temperatures 0°C to 6.7°C Measurement Detail Test system – 30kw 3-stage Process Cooling plant Data taken post SolarCool installation starting 21 st August through 21 st September 2014 The test site encountered huge weather fluctuations throughout the measured period. This is not unusual for this part of the world during this time of year. The following graphs are screen shots taken directly from the 3-phase electricity monitoring system installed at the following site. The system is attached to the outdoor SolarCool refrigeration unit, cooling 23meters of indoor open deck refrigeration:. The Kay Group Texaco/Spar Rossendale Road, Burnley, Lancashire It is a well know fact that the average retail refrigeration system will run considerably more efficient in lower ambient temperatures. Nightfall being a good example of this in the UK summer months. In addition to the obvious ambient temperature reductions, as in most cases (test site included) lower consumer impact on the air curtain system employed by such systems also lowers the energy consumption. However when the sun is out, SolarCool’s energy saving capabilities are clearly demonstrated in the following graphs. Ambient temperatures and consumer throughput are at there highest in the daytime hours . Although the impact of SolarCool’s benefits are clear throughout, Sunday 24 th and Thursday 28 th August are almost perfect examples when compared to nightfall usage - Completely the opposite of what the experienced & educated in this industry would expect to see. - denotes sundown or sunlight no longer available to the SolarCool system. Go to: www.solarcoolenergy.com

The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Embed Size (px)

Citation preview

Page 1: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

The Barn, New Laund Farm,Fence, Lancashire,BB12 9NY

• Highest ambient temperature during test period -24.1°C

• Lowest ambient temperature during test period -12.6°C

• Indoor refrigeration required temperatures 0°C to 6.7°C

Measurement Detail

• Test system – 30kw 3-stage Process Cooling plant• Data taken post SolarCool installation starting 21st August through

21st September 2014• The test site encountered huge weather fluctuations throughout the

measured period. This is not unusual for this part of the world during this time of year.

The following graphs are screen shots taken directly from the 3-phase electricity monitoring system installed at the following site. The system is attached to the outdoor SolarCool refrigeration unit, cooling 23meters of indoor open deck refrigeration:.

The Kay GroupTexaco/Spar

Rossendale Road,Burnley, Lancashire

It is a well know fact that the average retail refrigeration system will run considerably more efficient in lower ambient temperatures.

Nightfall being a good example of this in the UK summer months. In addition to the obvious ambient temperature reductions, as in most cases (test site included) lower consumer impact on the air curtain system employed by such systems also lowers the energy consumption.

However when the sun is out, SolarCool’s energy saving capabilities are clearly demonstrated in the following graphs. Ambient temperatures and consumer throughput are at there highest in the daytime hours . Although the impact of SolarCool’s benefits are clear throughout, Sunday 24th and Thursday 28th August are almost perfect examples when compared to nightfall usage - Completely the opposite of what the experienced & educated in this industry would expect to see.

- denotes sundown or sunlight no longer available to the SolarCool system.

Go to: www.solarcoolenergy.com

Page 2: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Thursday 21/08/14 pm Friday 22/08/14 am

Page 3: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Sunday 24/08/14 pm Monday 25/08/14 am

Page 4: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Monday 25/08/14 pm Tuesday 26/08/14 am

Page 5: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Tuesday 26/08/14 pm Wednesday 27/08/14 am

Page 6: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Wednesday 27/08/14 pm Thursday 28/08/14 am

Page 7: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Thursday 28/08/14 pm Friday 29/08/14 am

Page 8: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Monday 01/09/14 pm Tuesday 02/09/14 am

Page 9: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Tuesday 02/09/14 pm Wednesday 03/09/14 pm

Page 10: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Wednesday 03/09/14 pm Thursday 04/09/14 am

Page 11: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Thursday 04/09/14 pm Friday 05/09/14 am

Page 12: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Sunday 07/09/14 pm Monday 08/09/14 am

Page 13: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Monday 08/09/1 pm Tuesday 09/0914 am

Page 14: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Tuesday 09/09/14 pm Wednesday 10/09/14 am

Page 15: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Wednesday 10/0914 pm Thursday 11/09/14 am

Page 16: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Thursday 11/09/14 pm Friday 12/09/14 am

Page 17: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Sunday 14/0914 pm Monday 15/09/14 am

Page 18: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Monday 15/09/14 am Tuesday 16/09/14 pm

Page 19: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Tuesday 16/09/14 pm Wednesday 17/09/14 am

Page 20: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Wednesday 17/09/14 pm Thursday 18/09/14 am

Page 21: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Thursday 18/09/14 pm Friday 19/09/14 am

Page 22: The Barn, New Laund Farm, Fence, Lancashire, BB12 9NY Highest ambient temperature during test period - 24.1°C Lowest ambient temperature during test period

Sunday 21/09/14 pm Monday 22/09/14 am