TestingDirectionalRelayElements

Embed Size (px)

Citation preview

  • 8/3/2019 TestingDirectionalRelayElements

    1/14

    Testing Directional Relay Elements

    Mike Childers, PE, Application [email protected]

    Scott Schnell, PE Application [email protected]

    Doble Engineering Company

    PTUG 2010

  • 8/3/2019 TestingDirectionalRelayElements

    2/14

    Current Polarized Element

    The current polarized element uses the internal

    calculated ground current and compares the phaseangle to the neutral current from a Y connectedTransformer.

    -

    PTUG Austin Texas 2010

    other and above minimum current level comparators thefault is forward.

    The two current level settings are 50GFP Forward

    Directional Ground Current Pickup and a0 PositiveSequence Current Restraint Factor

  • 8/3/2019 TestingDirectionalRelayElements

    3/14

    Tests

    The 50GFP setting / comparator can be checked by

    ramping the Residual (Ground) current until the 50GFword bit asserts. The 50GF word bit is mapped to theOUT104 relay contact.

    PTUG Austin Texas 2010

    with a balanced 3 phase current and increasing one ofthe phase currents until the 32IF word bit asserts. The32IF word bit is mapped to the OUT104 relay contact.

    The F32I element will assert when the ground andneutral currents are within +/- 90 degrees. The F32I wordbit is mapped to the OUT104 relay contact.

  • 8/3/2019 TestingDirectionalRelayElements

    4/14

    Current Polarized Element Logic

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    5/14

    50GFP

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    6/14

    A0 Pickup

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    7/14

    MTA Test

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    8/14

    Zero-Sequence Voltage

    Polarized Element

    The Zero-Sequence Voltage polarized element uses the

    ground current and the zero-sequence voltage. The relay calculates the Z0 impedance and compares

    the result to the forward threshold value. If the

    PTUG Austin Texas 2010

    fault is forward. The threshold value is determined by theZ0F Setting.

    The operation of this element is supervised by the Loss

    of Potential Logic and two current level settings 50GFPForward Directional Ground Current Pickup and a0Positive Sequence Current Restraint Factor.

  • 8/3/2019 TestingDirectionalRelayElements

    9/14

    Tests

    The Loss of Potential logic needs to turned off during

    testing. The forward threshold can be measured by applying a

    phase to ground fault at the line angle and changing the

    PTUG Austin Texas 2010

    .

    word bits 50GF and 32VE test need to asserted duringthe fault condition.

    The F32V relay word bit is mapped to the OUT104 relay

    contact. A maximum torque angle or reach test can plot the

    shape of the forward threshold curve.

  • 8/3/2019 TestingDirectionalRelayElements

    10/14

    Zero-Sequence Voltage

    Polarized Element Logic

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    11/14

    Negative-Sequence Voltage

    Polarized Element

    The Negative-Sequence Voltage polarized element

    uses the negative sequence voltage and current tocalculate the negative sequence impedance.

    The relay calculates the Z2 impedance and compares

    PTUG Austin Texas 2010

    ,

    Z2RT. If the calculation is less than the Z2FT the fault isforward, greater than the Z2RT the fault is reverse.

    The operation of this element is supervised by the Loss

    of Potential Logic and two current level settings 50QFPand 50QRP Directional Ground Current Pickup and a2Positive Sequence Current Restraint Factor.

  • 8/3/2019 TestingDirectionalRelayElements

    12/14

    Tests The Loss of Potential logic needs to turned off during

    testing.

    The R32Q relay word bit is mapped to the OUT107 relaycontact, F32Q to OUT106. Relay word bits 50QF and32QE test need to asserted during the fault condition.

    PTUG Austin Texas 2010

    The reverse threshold can be measured by applying aphase to ground fault at 180 - line angle and increasingthe I2 value until the R32Q word bit asserts. IncreasingI2 beyond 3 times Z2R deasserts R32Q. I2 greater than

    Z2F asserts F32Q.

    A maximum torque angle or reach test can plot theshape of the forward threshold curve.

  • 8/3/2019 TestingDirectionalRelayElements

    13/14

    Negative-Sequence Voltage

    Polarized Element Logic

    PTUG Austin Texas 2010

  • 8/3/2019 TestingDirectionalRelayElements

    14/14

    Questions

    PTUG Austin Texas 2010