Upload
rajesh-bodduna
View
225
Download
0
Embed Size (px)
Citation preview
8/3/2019 TestingDirectionalRelayElements
1/14
Testing Directional Relay Elements
Mike Childers, PE, Application [email protected]
Scott Schnell, PE Application [email protected]
Doble Engineering Company
PTUG 2010
8/3/2019 TestingDirectionalRelayElements
2/14
Current Polarized Element
The current polarized element uses the internal
calculated ground current and compares the phaseangle to the neutral current from a Y connectedTransformer.
-
PTUG Austin Texas 2010
other and above minimum current level comparators thefault is forward.
The two current level settings are 50GFP Forward
Directional Ground Current Pickup and a0 PositiveSequence Current Restraint Factor
8/3/2019 TestingDirectionalRelayElements
3/14
Tests
The 50GFP setting / comparator can be checked by
ramping the Residual (Ground) current until the 50GFword bit asserts. The 50GF word bit is mapped to theOUT104 relay contact.
PTUG Austin Texas 2010
with a balanced 3 phase current and increasing one ofthe phase currents until the 32IF word bit asserts. The32IF word bit is mapped to the OUT104 relay contact.
The F32I element will assert when the ground andneutral currents are within +/- 90 degrees. The F32I wordbit is mapped to the OUT104 relay contact.
8/3/2019 TestingDirectionalRelayElements
4/14
Current Polarized Element Logic
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
5/14
50GFP
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
6/14
A0 Pickup
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
7/14
MTA Test
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
8/14
Zero-Sequence Voltage
Polarized Element
The Zero-Sequence Voltage polarized element uses the
ground current and the zero-sequence voltage. The relay calculates the Z0 impedance and compares
the result to the forward threshold value. If the
PTUG Austin Texas 2010
fault is forward. The threshold value is determined by theZ0F Setting.
The operation of this element is supervised by the Loss
of Potential Logic and two current level settings 50GFPForward Directional Ground Current Pickup and a0Positive Sequence Current Restraint Factor.
8/3/2019 TestingDirectionalRelayElements
9/14
Tests
The Loss of Potential logic needs to turned off during
testing. The forward threshold can be measured by applying a
phase to ground fault at the line angle and changing the
PTUG Austin Texas 2010
.
word bits 50GF and 32VE test need to asserted duringthe fault condition.
The F32V relay word bit is mapped to the OUT104 relay
contact. A maximum torque angle or reach test can plot the
shape of the forward threshold curve.
8/3/2019 TestingDirectionalRelayElements
10/14
Zero-Sequence Voltage
Polarized Element Logic
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
11/14
Negative-Sequence Voltage
Polarized Element
The Negative-Sequence Voltage polarized element
uses the negative sequence voltage and current tocalculate the negative sequence impedance.
The relay calculates the Z2 impedance and compares
PTUG Austin Texas 2010
,
Z2RT. If the calculation is less than the Z2FT the fault isforward, greater than the Z2RT the fault is reverse.
The operation of this element is supervised by the Loss
of Potential Logic and two current level settings 50QFPand 50QRP Directional Ground Current Pickup and a2Positive Sequence Current Restraint Factor.
8/3/2019 TestingDirectionalRelayElements
12/14
Tests The Loss of Potential logic needs to turned off during
testing.
The R32Q relay word bit is mapped to the OUT107 relaycontact, F32Q to OUT106. Relay word bits 50QF and32QE test need to asserted during the fault condition.
PTUG Austin Texas 2010
The reverse threshold can be measured by applying aphase to ground fault at 180 - line angle and increasingthe I2 value until the R32Q word bit asserts. IncreasingI2 beyond 3 times Z2R deasserts R32Q. I2 greater than
Z2F asserts F32Q.
A maximum torque angle or reach test can plot theshape of the forward threshold curve.
8/3/2019 TestingDirectionalRelayElements
13/14
Negative-Sequence Voltage
Polarized Element Logic
PTUG Austin Texas 2010
8/3/2019 TestingDirectionalRelayElements
14/14
Questions
PTUG Austin Texas 2010