Testing of Circuit Breakers
K N srinivasan
CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER
VITAL LINK IN ELECTRICAL NETWORK
SAFEGAURDS COSTLY ELECTRICAL EUIPMENT
RELIABILITY - CRITICAL IMPORTANCE.
Why Tests
What Standards
RecapC-& L charging50-60 HzSym & assymInrush
Why Oscillations
Technical Terms
* Applied voltage: R.M.S voltage applied immediately before it closes.
* Recovery voltage: RMS voltage that reappears across after final arc extinction.
* Restricting voltage: appearing across the arc gap immediately after the current zero
* Making currentpeak valve of the current in the first major current loop.
* Breaking currentRMS current breaker contacts has to deal with.
TYPE TESTS
Temperature Rise
Dielectric Tests.
Dry Pf W/S
Wet Pf W/S
LI W/S
Partial Discharge
RIV
Pollution
IP
Mech. Operation
EMF & MMFMaster CBMake SwitchOptical fiber T/R
Fault MVA = 3 x VL x ILVL= Line voltage
IL = Line current
Contact separation
- ability to close on to fault at full asymmetry;- to prove that there is no significant change in arc energy (T100%, 30%, 60% & T100%) ;
- to interrupt full fault current with appropriate DC component
five Basic Short Circuit Test Duties at various current levels
Test Duty No. T10 T30 T60 T100s T100a
% of ratedS.C. Current 10% 30% 60% 100% 100%
% D.C. Component
For duties other than T100a
O-3mts-CO-3mt-CO
O-0.3Sec-CO-3Min-CO-CO for auto-reclosing breakers
For duty T100a
O-3mts-O-3mts-O
Making current
SEQUENCE
VOLTAGE WAVEFORMS ASSOCIATED WITH SHORT LINE FAULT
surge impedance Z= L/C in ohms T = 2 / LC = 6.66 sec.
SHORT LINE FAULT
Critical Current Tests
lesser than 10% of the rated S.C. breaking current.
4% to 6% and 2% to 3% of rated S.C. breaking current.
Inductive Current Switching Tests
Small inductive - transformer magnetizing current , shunt reactor or motor switching currents
unloaded transmission line, underground cable or a capacitor bank.
The trapped charge on the capacitance - twice L-G voltage breakers of 72.5kV rating and above and the cable charging breaking current tests for breakers of 24kV and above only. Two test duties - breaking current (100% and 10 to 40 %). For 3 phase tests number of applications are:
TestDuty
Test current as a % ofRated cap. breakingcurrent
1 10 to 402 Not less than 100
Capacitive current Switching Tests
withstand the dynamic and thermal stresses due to short circuits.
1.0 to 3.0 seconds.
The rated peak withstand current is equal to 2.5 times the rated short time withstand current (i.e., equal to rated short circuit making current of the breaker).
Short Time Withstand Current Test
DURING TESTNeither sign of excessive distress nor endanger the operator
copper wire of 0.1 mm diameter and 50 mm long.
AFTER TESTMaking and breaking rated normal current
A VISUAL INSPECTION of contacts
80% P F W / S. NO LOAD OPERATION
close and latch satisfactorily
CRITERIA FOR PERFORMANCE EVALUATION
Test Oscillogram of a failure
Examples
Typical oscillograms indicating a Break operation of Circuit breaker during Short circuit testing.
Examples
Parallel current injection
SYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITY
C1 - 1.44MJ, 18F. 400kV
C2 - 2.8F., 500kV
C3 - 4.0F., 400kV
MECHANICAL OPERATION TESTMECHANICAL OPERATION TESTMECHANICAL OPERATION TESTMECHANICAL OPERATION TEST
CLASS M1
2000 MECHANICAL OPERATIONS
CLASS M2
10000 MECHANICAL OPERATIONS