Testing of Circuit Breakers

Embed Size (px)

DESCRIPTION

A very useful information on CB

Citation preview

  • Testing of Circuit Breakers

    K N srinivasan

  • CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER

    VITAL LINK IN ELECTRICAL NETWORK

    SAFEGAURDS COSTLY ELECTRICAL EUIPMENT

    RELIABILITY - CRITICAL IMPORTANCE.

  • Why Tests

    What Standards

  • RecapC-& L charging50-60 HzSym & assymInrush

    Why Oscillations

  • Technical Terms

    * Applied voltage: R.M.S voltage applied immediately before it closes.

    * Recovery voltage: RMS voltage that reappears across after final arc extinction.

    * Restricting voltage: appearing across the arc gap immediately after the current zero

    * Making currentpeak valve of the current in the first major current loop.

    * Breaking currentRMS current breaker contacts has to deal with.

  • TYPE TESTS

    Temperature Rise

    Dielectric Tests.

    Dry Pf W/S

    Wet Pf W/S

    LI W/S

    Partial Discharge

    RIV

    Pollution

    IP

    Mech. Operation

  • EMF & MMFMaster CBMake SwitchOptical fiber T/R

  • Fault MVA = 3 x VL x ILVL= Line voltage

    IL = Line current

    Contact separation

  • - ability to close on to fault at full asymmetry;- to prove that there is no significant change in arc energy (T100%, 30%, 60% & T100%) ;

    - to interrupt full fault current with appropriate DC component

    five Basic Short Circuit Test Duties at various current levels

    Test Duty No. T10 T30 T60 T100s T100a

    % of ratedS.C. Current 10% 30% 60% 100% 100%

    % D.C. Component

  • For duties other than T100a

    O-3mts-CO-3mt-CO

    O-0.3Sec-CO-3Min-CO-CO for auto-reclosing breakers

    For duty T100a

    O-3mts-O-3mts-O

    Making current

    SEQUENCE

  • VOLTAGE WAVEFORMS ASSOCIATED WITH SHORT LINE FAULT

    surge impedance Z= L/C in ohms T = 2 / LC = 6.66 sec.

    SHORT LINE FAULT

  • Critical Current Tests

    lesser than 10% of the rated S.C. breaking current.

    4% to 6% and 2% to 3% of rated S.C. breaking current.

    Inductive Current Switching Tests

    Small inductive - transformer magnetizing current , shunt reactor or motor switching currents

  • unloaded transmission line, underground cable or a capacitor bank.

    The trapped charge on the capacitance - twice L-G voltage breakers of 72.5kV rating and above and the cable charging breaking current tests for breakers of 24kV and above only. Two test duties - breaking current (100% and 10 to 40 %). For 3 phase tests number of applications are:

    TestDuty

    Test current as a % ofRated cap. breakingcurrent

    1 10 to 402 Not less than 100

    Capacitive current Switching Tests

  • withstand the dynamic and thermal stresses due to short circuits.

    1.0 to 3.0 seconds.

    The rated peak withstand current is equal to 2.5 times the rated short time withstand current (i.e., equal to rated short circuit making current of the breaker).

    Short Time Withstand Current Test

  • DURING TESTNeither sign of excessive distress nor endanger the operator

    copper wire of 0.1 mm diameter and 50 mm long.

    AFTER TESTMaking and breaking rated normal current

    A VISUAL INSPECTION of contacts

    80% P F W / S. NO LOAD OPERATION

    close and latch satisfactorily

    CRITERIA FOR PERFORMANCE EVALUATION

  • Test Oscillogram of a failure

    Examples

  • Typical oscillograms indicating a Break operation of Circuit breaker during Short circuit testing.

    Examples

  • Parallel current injection

  • SYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITYSYNTHETIC TESTING FACILITY

    C1 - 1.44MJ, 18F. 400kV

    C2 - 2.8F., 500kV

    C3 - 4.0F., 400kV

  • MECHANICAL OPERATION TESTMECHANICAL OPERATION TESTMECHANICAL OPERATION TESTMECHANICAL OPERATION TEST

    CLASS M1

    2000 MECHANICAL OPERATIONS

    CLASS M2

    10000 MECHANICAL OPERATIONS