Page 1: TELARIS 0100 plus

1

UNITEST

Instruction Manual Cat.-No. 9073

®

TELARIS 0100 plus

Page 2: TELARIS 0100 plus

2

Page 3: TELARIS 0100 plus

Content ........................................................................................................Page1.0 Introduction ..............................................................................................41.1 Model and Type ........................................................................................41.2 Product description ..................................................................................42.0 Transport and Storage ..............................................................................53.0 Safety Measures ......................................................................................53.1 Appropriate Usage ..................................................................................64.0 Display and Control Elements ..................................................................74.1 Display ......................................................................................................74.2 Operation Elements ..................................................................................85.0 Carrying out Measurements......................................................................95.1 Voltage Measurement ..............................................................................105.2 Low-Ohm Resistance Measurement ........................................................115.3 Insulation Measurement ..........................................................................135.4 Mains Internal Resistance Measurement / SCC Measurement ..................155.5 Loop Impedance Measurement / PSCCurrent Measurement ....................185.6 Loop Impedance Measurement without RCD Tripping ..............................205.7 General Information about RCD Tests ......................................................215.7.1 RCD – Measurement of Contact Voltage UB and the

Earthing Resistance RE without RCD Tripping ..........................................225.7.2 RCD Trip Time Test, Contact Voltage (ta, VB / RE) ....................................245.7.3 RCD Test with Rising Residual Current, Trip Current (I, ta/VC ..................275.8 Rotary Field Test ......................................................................................296.0 Storing, Printing, and Data Transfer ..........................................................306.1 Storing Measurement Data ......................................................................306.2 Viewing Measurement Data ....................................................................316.3 Printing Measurement Data ....................................................................326.4 Deleting Saved Measurement Data/View the Memory Location Number ..326.5 Delete all Saved Measurement Values ......................................................326.6 Infrared Interface, send Measurement Data ..............................................327.0 Displays / Error Messages ........................................................................338.0 Energy Management ................................................................................369.0 Maintenance ............................................................................................369.1 Cleaning....................................................................................................3610.0 Battery Replacement ................................................................................3611.0 Built in fuses ............................................................................................3811.1 Display for Tripped Fuses ..........................................................................3812.0 Calibration Interval....................................................................................3813.0 Technical Data ..........................................................................................39

24 month Warranty ..................................................................................43

3

Page 4: TELARIS 0100 plus

References marked on instrument or in instruc-tion manual:

Warning of a potential danger, comply with in-struction manual.

Reference. Please use utmost attention.

Caution! Dangerous voltage. Danger of electri-cal shock.

Continuous double or reinforced insulationcomplies with Category II.

Warning of potential danger caused by accu-mulators and batteries.

Conformity symbol, the instrument complieswith the valid directives. It complies with theEMC Directive (89/336/EEC), Standards EN50081 and EN 50082-1 are fulfilled. It alsocomplies with the Low Voltage Directive(73/23/EEC), Standard EN 61010-1 is fulfilled.

The instruction manual contains informationand references necessary for safe operationand maintenance of the instrument. Prior tousing the instrument (commissioning / as-sembly) the user is kindly requested to thor-oughly read the instruction manual and com-ply with it in all sections.

Failure to read the instruction manual or tocomply with the warnings and references con-tained herein can result in serious bodily injuryor instrument damage.

1.0 IntroductionYou have purchased a high quality measurement in-strument from Ch. BEHA GmbH which will allow youto carry out measurement for many years to come.Ch. BEHA GmbH is a member of the world-wide op-erating BEHA Group with its head office in Glotter-tal/ Schwarzwald which also houses our develop-ment centre. The BEHA Group is a leadingorganisation for Test and Measuring instruments.

1.1 Model and Type DesignationThe type shield sticker is located on the rear of theinstrument. It contains the instrument serial num-ber and product designation. When questions ariseregarding the instrument, please always quoteproduct designation and serial number.

1.2 Product descriptionThe UNITEST TELARIS 0100 plus is a handy test andmeasurement instrument for testing in systems andinstallations in compliance with DIN VDE. All valuesrequired for FAT (Final Approval Test) reports (e.g.ZVEH) can be measured by using the TELARIS 0100plus. Reporting, filing or further processing ofmeasured values is ensured by means of an inter-nal data memory and built-in infrared interface (fordata transfer to PC).

4

Introduction/Product description

Page 5: TELARIS 0100 plus

The UNITEST TELARIS 0100 plus is characterisedby the following features:• Measurement of loop resistance and prospective

short circuit current measurement without trip-ping the RCD

• Line resistance measurement up to 440 V• Prospective short circuit current measurement• RCD measurements (contact voltage, trip time,

trip current - ramp method)• Low Ohm measurement • Insulation measurement with 100, 250 500 V• Voltage and frequency measurement • Rotary field test • Integrated socket test with contact electrode to

enable the user to quickly establish incorrectly in-stalled sockets and/or protective conductor failu-res

• Integrated memory for approx. 500 measurementvalues

• Standard, built-in IR RS-232 interface for trans-ferring measurement data to the PC

• Clear and large LCD providing the user with an op-timum visual indication of both test values and li-mits

• Auto power off

Scope of Supply1 pc. UNITEST TELARIS 0100 plus3 pc. Measurement leads1 Three-pole test lead with safety plug3 pcs Croccodile clamps3 pcs Test probe6 pcs Battery 1.5V, type IEC LR6 (Size AA) 1 pc Protective Holster1 pc Carrying Case1 pc Instruction manual

2.0 Transport and StoragePlease keep the original packaging for later trans-port, e.g. for calibration. Any transport damage dueto faulty packaging will be excluded from warrantyclaims. In order to avoid instrument damage, we recom-mend that accumulators are removed when notusing the instrument over a certain period of time.However, should the instrument be contaminatedby leaking batteries cells, you are kindly requestedto return it to the factory for cleaning and inspec-tion.Instruments must be stored in dry and closed areas.In the case of an instrument being transported in ex-treme temperatures, a recovery time of at least 2hours is required prior to instrument operation.

3.0 Safety MeasuresThe UNITEST Telaris 0100 plus has been designedand checked in accordance with the safety regula-tions for Electronic test and Measurement Instru-ments EN 61010 and IEC 61010, and left our fac-tory in a safe and perfect condition.

The instruction manual contains informationand references necessary for safe operationand maintenance of the instrument.

The respective accident prevention regulationsestablished by the professional association forelectrical systems and equipment must bestrictly met at all times.

5

Transport and Storage/Safety Measures

Page 6: TELARIS 0100 plus

In order to avoid electrical shock, the valid safe-ty and VDE regulations regarding excessivecontact voltages must receive the utmost at-tention when working with voltages exceeding120V (60V) DC or 50V (25V)rms AC. The val-ues in brackets are valid for limited ranges (forexample medicine and agriculture).

Measurements in dangerous proximity of elec-trical installations are only to be executed wheninstructed by a responsible electrical specialist,and never alone.

If the operator’s safety is no longer guaranteed,the instrument is to be put out of service andprotected against use. The safety can no longerbe guaranteed if the instrument (or leads):

• shows obvious damage• does not carry out the desired measurements• has been stored for too long under un-

favourable conditions• has been subjected to mechanical stress dur-

ing transport.

Prior to usage, inspect the instrument and testleads for external damage. Prior to any opera-tion, ensure that connecting leads used and in-struments are in perfect condition.

The test leads, the measurement accessoriesand the mains plug may only be touched at thehandle section provided. Direct contact of me-asurement ports or test probes must be avoi-ded.

Avoid any heating up of the instrument by di-rect sunlight to ensure perfect functioning andlong instrument life.

3.1 Appropriate Usage

The instrument may only be used under thoseconditions and for those purposes for which itwas built.

When modifying or changing the instrument, theoperational safety is no longer guaranteed.

The opening of the instrument for fuse re-placement, for example, may only be carriedout by professionals. Prior to opening, the in-strument has to be switched off and discon-nected from any voltages.

Any maintenance and calibration tasks mayonly be carried out by our repair service staff.

The instrument may not be operated if the bat-tery case is open.

If the instrument is subjected to an extremelyhigh electro-magnetic field, its functioning ab-ility may be impaired.

6

Safety Measures

Page 7: TELARIS 0100 plus

4.0 Display and Control Elements4.1 Display (see also chapter 7.0)

1) Attention, warning symbol2) AC voltage / DC voltage3) Exceeding the threshold4) Exceeding the Contact voltage threshold5) External voltage / extraneous voltage present6) Socket error7) Turn socket by 180°8) Battery status indication9) Unit indication10) Selective RCD has been chosen11) Contact voltage threshold12) Measurement value indication, large

resultfield13) Unit indication, small resultfield14) Measurement value indication, small

resultfield

15) Current factor display for I∆N when perfor-ming RCD checks

16) Small result field shows pre-selected I∆Nwhen performing RCD checks

17) Symbol for memory entry18) Symbol for compensating test lead resistance19) Ramp function (trip current)20) Exceeding temperature limit, instrument over-

heating

7

Display and Control Elements

1 2 3 4 5 6 7 8

9

10

1112131415

18

16

17

20

19

Page 8: TELARIS 0100 plus

4.2 Operation Elements21) Display key to select individual measurement

results22) VINS, I∆N key: select one lower insulation test

voltage or I∆N. LowΩ: start / switch off com-pensation.

23) VINS, I∆N key : select one higher insulation testvoltage or Idn.

24) VL key (contact voltage threshold)25) PE contact electrode

26) Start key27) Store key28) Send key29) Clear key30) IR-RS232 PC interface31) Print key32) Measurement range selection switch.

Plastic holster (not shown in picture)

8

Operation Elements

21 22 23 24

25

26

27282930

31

32

Page 9: TELARIS 0100 plus

33) Connection Socket L - L134) Connection Socket N - L235) Connection Socket PE - L3

Acoustic Signals

Confirmation Signal:The confirmation signal is a short beep which is au-dible once an important procedure is started (e.g.start of measurement, data memorisation or delet-ing)

Error Signal:The error signal is a sequence of two short beepsounds. It indicates either errors occurring duringthe measurement or that the selected function maynot be carried out.

5.0 Carrying out Measurements

FAT (Final Approval Test) measurements haveto be carried out in compliance with the ap-propriate applicable standards.

9

Carrying out Measurements

RINS, LowΩ

VAC/DC

33 34 35

Page 10: TELARIS 0100 plus

5.1 Voltage Measurement

Never apply voltages exceeding 440V AC/DC toinput sockets.

The instrument is equipped with an integratedinternal over voltage protection up to maxi-mum 500 V AC/DC.

When switching on or changing to VAC/DC me-asurement range, „AC" is automatically selec-ted.

5.1.1 AC Voltage and Frequency Measurement Select measurement range „VAC/DC, f" by

means of measurement range selection switch(32).

Connect mains connection cable or test lead tothe measurement instrument

Now connect the mains connection cable or theL and N connections of the test leads to the UUT.

For DC voltage measurements, thesocket L1 polarity is positive (+), theL2 polarity is negative (-).

Read measurement result on display.

AC voltage is displayed in the large result field(12), frequency in the small result field (14).

If voltage exceeds 440V, „>440V" is displayedin the large result field. Should this occur dis-connect the test instrument from the EUT im-mediately.

If the frequency value is outside 10Hz ... 99,9Hzrange, „---„ is displayed in the small result-field. This indication is also displayed on thescreen if the AC voltage is extremely low.

Measurement results may be stored by pres-sing the „Store" (27) key.

10

Voltage Measurement

RINS, LowΩ

VAC/DC

L

NPE

L

NPE

Page 11: TELARIS 0100 plus

5.2 Low-Ohm Resistance MeasurementThis measurement is used to check protective earthconductors, grounding conductors, and equipoten-tial bonding conductors for low-impedance conti-nuity. The resistance is determined by current/vol-tage measurement.

Prior to any Resistance measurement, it mustbe guaranteed that no installation parts to betested are live.

Prior to any resistance measurement it is pos-sible to compensate test lead resistance (plea-se refer to chapter 5.2.1)

Connect 2 test leads to the TELARIS 0100 plus(sockets L1 and L2).

Plug test probes or crocodile clips onto the testleads and connect the test leads to the EUT.

Set measurement range selection switch (32) to„LOW-Ω" measurement range.

If an external voltage is present, the instrumentdisplays Uext (5) and attention (1). The Low-Ohm resistance measurement is then blocked.The symbol „Uext" (5) disappears if a secondmeasurement is started without foreign volta-ge present.

Press the "Start" (26) key. During the measure-ment the display shows "-”.

Read measurement value on display.

If „>1999 Ω" appears on the display, the resi-stance is higher than 1999 Ohm.

The polarity of the test current applied may in-fluence the measurement result by means ofgalvanic elements within the EUT. For this rea-son always repeat the measurement with re-versed polarity to compare the measurementresults.

The measurement results can be falsified byparallel connection of impedances of additio-nal service circuits or by compensating cur-rents.

It is possible to store the measurement resultby pressing „Store" (27) key.

The instrument automatically remains in con-tinuous measurement mode when pressingthe "Start" key (26). The measurement lastsuntil the "Start” key (26) is released again.

11

Low-Ohm Resistance Measurement

RINS, LowΩ

VAC/DC

L

NPE

Page 12: TELARIS 0100 plus

5.2.1 Compensating Test Lead ResistanceTELARIS 0100 plus allows for compensation of testlead resistance. The test lead resistance mayamount up to 1,99Ω. Proceed as follows:

Connect 2 test leads to the TELARIS 0100 plus(sockets L1 and L2). Connect any measurementaccessories used to measurement connectionsL and N.

Short-circuit both test leads U+ and U-. Set measurement range selection switch (32) to

„LOW-Ω" measurement range. Press „COMP" (22) key.

If the test lead resistance has been properlycompensated for, the symbol „COMP" (15) andthe value 0.00 Ohm appears on the display. Fur-thermore, an acoustic signal is audible. If thetest lead resistance exceeds 1,99 Ohm, thesymbol „COMP" (15) blinks twice and the errorsignal is audible.

The compensation value is maintained evenafter switching the instrument off.

To clear the compensation value, please pressthe "COMP” key (22) again.

12

Compensating Test Lead Resistance

RINS, LowΩ

VAC/DC

Page 13: TELARIS 0100 plus

5.3 Insulation Measurement

For electrical installations the insulation measure-ment has to be carried out prior to final commis-sioning. This measurement is of basic importanceas the insulation measurement is considered to bethe only measurement for fire protection. If, due toan insulation error, a limited fault current flows be-tween two conductors, this leads to a heating up oreven to a fire. Only the insulation measurement pro-cedure can detect such a fault.

If an external voltage is present, the instrumentdisplays „Uext" and “attention” after the „Start"key has been pressed. The insulation measu-rement is then blocked. The symbol „Uext" (5)appears if a second measurement is started wi-thout an extraneous voltage present.

According to IEC 60364 (DIN VDE 0100 Part 610)the insulation resistance measurement is carriedout:• from all phase conductors (e.g. L1, L2, L3) to-

wards earth or to protective earth (PE)• between protective earth (PE) and neutral (N)

Additionally, it is advised to perform the followingmeasurements:

• between all active conductors (e.g. L1, L2, L3, N).

This measurement must be carried out individuallyfor each current circuit. The measurement is carriedout a DC voltage of 100V, 250V or 500V.

The insulation resistance is determined by cur-rent/voltage measurement. The Telaris 0100 pluscan perform an automatic measurement or a per-manent measurement. The measurement durationis dynamic for automatic measurements.

The measurement lasts until measurement valuestabilisation, however a maximum of 10s. Thus, thecorrect measurement result is determined for lesscapacitive loads within a very short time period andthe battery life is increased.

During insulation measurement, ensure that allloads are disconnected from the mains and itmust be ensured that all current circuits areswitched on.

Prior to any insulation measurement, it must beguaranteed that no installation parts to be test-ed are live.

13

Insulation Measurement

RINS, LowΩ

VAC/DC

RINS

RINS RINS RINS RINS RINS RINS RINS RINS RINS RINS

Page 14: TELARIS 0100 plus

During insulation measurements, the measu-rement voltage charges capacitive UUTs. TheUNITEST TELARIS 0100 plus automatically di-scharges the UUT after completion of the me-asurement. When interrupting the measure-ment or when removing the test leads prior totest termination, a dangerous voltage may bepresent at the UUT. If a dangerous voltage isdetected during voltage measurement, theUUT must be manually discharged using a highimpedance resistance (not via short-circuit!).

During the measurement, the operator may nottouch the UUT/the installation being tested,danger of electrical shock!

If UUTs of higher capacitance´s are tested (e.g.long cables or conductors), the automatic di-scharge may take longer.

Connect 2 test leads to the TELARIS 0100 plus(sockets L1 and L2).

Only Connect both ends to the UUT by using al-ligator clips.

The PE connection should not be connected;otherwise, the TELARIS 0100 plus cannot per-form correct measurements and displays 0.00MΩ.

Select insulation resistance measurementrange (RINS) via the rotary switch.

Select the desired test voltage (100V / 250V /500V) by means of ' VINS ' (22) or ' VINS '(23) keys.

To start automatic measurements, briefly pressthe "Start” key (26)

If the automatic measurement takes a long time(approx. 10s), then the UUT has a high capaci-tance value. In this case, you should carry outa continuous measurement, as the automaticmeasurement should be interrupted after 10s.Possibly, the correct final value has not yet sta-bilised.

During the measurement, the instrument con-tinuously shows the nominal voltage (500 V)of the insulation measurement function in thelower display part.

Read the measurement value on the display.

If „>199.9 MΩ" appears on the display, a par-ticularly good insulation resistance has beenmeasured.

It is possible to store the measurement resultby pressing the „Store" (27) key.

You may even enter continuous measurementif the instrument program is set to automaticmeasurement by pressing the "Start” key (26)and keeping it depressed. The measurementlasts until the "Start" key (26) is released again.Even during automatic measurement you mayenter continuous measurement mode whenpressing the 'Start' key (26) and keeping it de-pressed.

During the measurement process, intermedia-te results are displayed. The continuous mea-surement should be carried out until final me-asurement value stabilisation.

14

Insulation Measurement

Page 15: TELARIS 0100 plus

5.4 Mains Internal Resistance Measurement /

Short Circuit Current Measurement

The mains internal resistance is determined by ap-plying a brief mains load using a large current. Thismeasurement is not required by DIN VDE [GermanStandard], however it is considered as importantand valuable support in practical applications e.g.for evaluating an installation as well as for troubleshooting.

Terms:

Loop Impedance (ZL): Sum of impedance values within a current loop (bet-ween the L and PE conductor).

Internal Resistance (RI): Sum of resistance values within a current loop (bet-ween the L and N conductor).

RL: Phase resistance

RPE: Protective conductor resistance

RN: Neutral conductor

RE: Earth-Resistance

Short-Circuit Current (IPSC): Occurring current flow in the event of short circuit.

This measurement can be used in installations(TN systems) equipped with RCDs to detectany exchange of the PE and the neutral con-ductor (N) without opening within the divider.Any faulty connection results in RCD trippingwhen measuring the mains internal resistance.

Furthermore, this measurement may be usedto prove the low impedance of the neutral con-ductor (N).

To obtain fairly precise measurement results,it is advised to switch off all loads or to di-sconnect them from the mains and to ensurethat the UUT is faultfree.

Connect the 'Schuko-Plug – Measurement Plug'measurement adapter to the Telaris 0100 plus,by plugging the measurement plug labelled withL, N, PE into the respective sockets: L (33), N(34), and PE (35).

15

Mains Internal Resistance Measurement / Short Circuit Current Measurement

RINS, LowΩ

VAC/DC

L

N

PE

Page 16: TELARIS 0100 plus

Plug the plug into the socket under test.

Select the Mains Internal Resistance function(RI, IK) using the "Measurement Function" rota-ry dial (32).

Select the contact voltage limit by pressing the'VL' key (24).

The socket is continuously checked for faults.If the "turn plug by 180°” symbol (7) is di-splayed on the screen, you are advised to eit-her turn the Schuko-plug or the exchange theL and N connectors at the instrument.

If the symbol for socket error (6) is displayedon the screen, we are dealing with a socket wi-ring error. If a voltage exceeding the pre-selec-ted contact voltage limit is present between Nand PE, 'UB>UL' (4) is displayed on the screen.

To perform a complete socket test, touch thecontact electrode PE (25) and observe the di-splayed values on the screen. A valid result mayonly be achieved when touching the contactelectrode PE (25)!

You are dealing with a PE error, if the error sig-nal is audible and the 'Attention' symbol (1),and 'Socket Error' symbol (6) are displayed.I.e., either the PE is not connected or a high vol-tage (phase) is present at PE.

The measurement may only be started if thesocket is not faulty and if the measurementadapter has been connected by respecting cor-rect polarity.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

Read the measurement result displayed on thescreen. The mains internal resistance is di-splayed in the large result field (12). The short-circuit current IPSC is displayed in the small re-sult field (14). .

16

Mains Internal Resistance Measurement / Short Circuit Current Measurement

RINS, LowΩ

VAC/DC

L

N

PE

Page 17: TELARIS 0100 plus

If the resistance measured exceeds 1999 Ω,the attention symbol (1) and '>1999 Ω' are di-splayed on the screen. As there is no valid me-asurement value for RI, it is not possible to cal-culate and display the short-circuit current IK.'---' is displayed in the small result field (14).

The short-circuit current is calculated using themains voltage and the loop impedance. Here,the value 230V/400V is used for the mains vol-tage if it amounts close to 230V / 400V. If themeasurement value deviates considerablyfrom 230V / 400V, the actual measurementvalue is used to calculate the short-circuit cur-rent.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results.

If many measurements are performed allowingonly "short breaks", the internal over tempera-ture protection of the Telaris 0100 plus is trig-gered and the symbol for excessive tempera-ture (20) is displayed on the screen. Thefollowing mains internal resistance measure-ment may only be started once the instrumenthas cooled down and the symbol (20) has di-sappeared from the screen. Thus, any damageto the instrument can be avoided.

You may store the measurement result by pres-sing the 'Store' key (27).

If you wish to store the condition of a faulty socket, please press the "Start” key (26) first.After hearing the "Error Signal” you may pressthe "Store” key (27).

Measurements within the three-phase sy-stem: when measuring the internal resistancewithin a three-phase system, you must con-nect L1 (33) and L2 (34) to the phases to be te-sted. You may not connect L3 (35). The socketest does not make sense for the internal resi-stance measurement between two phases.Therefore, the contact electrode (25) shouldnot be touched. When touching the contactelectrode, a PE error is indicated.

17

Mains Internal Resistance Measurement / Short Circuit Current Measurement

Page 18: TELARIS 0100 plus

5.5 Loop Impedance Measurement / Prospective Short-Circuit Current Measurement

The loop impedance (L-PE / loop impedance) is un-derstood as the sum of all resistance values withina current loop, consisting of the resistors of the cur-rent source, the external conductor of the currentsource up to the measurement point and the returnline (PE conductor) and the other current sourcepole. The measurement determines the loop im-pedance between the external conductor and the PEconductor. The loop impedance value is measuredby short-term mains loading. With the instrumentthe TELARIS 0100 plus, short-circuit current is de-termined by calculation. The short-circuit current must be known such thatan excess current release having been switched inseries can trigger at an appropriate current level andthus at sufficient speed in the event of a short-cir-cuit.

This measurement is used to perform the loopmeasurement within current circuits which arenot equipped with an RCD. If this measurementis started in correct circuits equipped withRCDs, the RCD will trip!

To obtain precise measurement results, switchoff all loads or disconnect them from the mains.

To obtain fairly precise measurement results,switch off all loads or disconnect them from themains. Ensure that the UUT is faultfree.

Only the calibrated test lead which are in scopeof supply must be used!

Connect the 'Schuko-Plug - Measurement Plug'mains adapter to the Telaris 0100 plus, by in-serting the measurement plugs labelled with L,N, PE into the respective sockets L (33), N (34),and PE (35).

Connect the mains to the socket plug by re-specting the correct polarity.

Select measurement range („ZL, IPSC") bymeans of the measurement range selectionswitch (32).

Select the contact voltage limit by pressing the'VL' key (24).

18

Loop Impedance Measurement / Prospektive Short-Circuit Current Measurement

RINS, LowΩ

VAC/DC

L

NPE

Page 19: TELARIS 0100 plus

If symbol „turn plug by 180°" (7) appears, turnthe mains plug by 180° and connect to the socket or exchange the N and L connectors atthe test instrument.

If the symbol for socket error (6) is displayedon the screen, an error within the mains has oc-curred. If a voltage is present between N andPE exceeding the pre-selected contact voltagelimit (50V/25V), "UB>UL" is displayed on thescreen (4).

To perform a complete socket test touch thecontact electrode PE (25) and observe the di-splay on the screen. You may only achieve avalid result when touching the contact electro-de PE (25)!

If the error signal is audible and the 'Attention'(1) and 'Socket Error' (6) symbols are display-ed on the screen, we are dealing with a PE error.I.e., either the PE is not connected or a high vol-tage (phase) is present at PE.

The measurement may only be started if thesocket is faultfree and the measurement adap-ter has been connected by respecting correctpolarity.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

Read the measurement result displayed on thescreen. The loop resistance is displayed on thelarge result field (12), the short-circuit currentIPSC is displayed on the small result field (14).

If the resistance measured is larger than1999Ω The attention symbol (1) and '>1999Ω'are displayed on the screen. As there is no validmeasurement value for RS, the short-circuitcurrent IPSC cannot be calculated and di-splayed. '---' appears on the small result field(14).

The short-circuit current is calculated using themains voltage and the loop resistance. For this,the value 230V is used as mains voltage if theactual mains voltage amounts to approx. 230V.If the measurement value differs considerablyfrom 230V, the actual measurement value isused for short-circuit current calculation.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results

If several measurements are carried out, inter-rupted only by „short" breaks, the internal over-temperature protection of TELARIS 0100 plusis triggered and the symbol for overtempera-ture (20) appears on the display. The next loopimpedance measurement can only be started,once the instrument has cooled down and afterthe symbol (20) has gone out. Instrument da-mage is therefore avoided..

Measurement results can be saved by pressingkey „Store" (27).

If the user wishes to save the condition infor-mation of a faulty socket, first press the "Start”key (26). After hearing the "error signal”, the"Store” key (27) can be pressed.

19

Loop Impedance Measurement / Prospektive Short-Circuit Current Measurement

Page 20: TELARIS 0100 plus

5.6 Loop Impedance Measurement without

RCD Tripping

This measurement us used for loop measurementwithin current circuits equipped with RCDs withoutcausing the RCD to trip during the measurement.

To obtain precise measurement results, switchoff all loads or disconnect them from the mains.

Connect the 'Schuko-Plug – Measurement Plug'measurement adapter to the Telaris 0100 plus,by inserting the measurement plug labelled withL, N, PE into the respective sockets: L (33), N(34), and PE (35).

Plug the Schuko-plug into the socket under test.

Select measurement range („ZL, IPSC/RCD") bymeans of the measurement range selectionswitch (32).

Select contact voltage threshold by means ofthe key „VC" (24).

The socket is continuously checked for faults.If the "turn plug by 180°” symbol (7) is di-splayed on the screen, you are advised to eit-her turn the Schuko-plug or to exchange the Land N connectors at the instrument.

If the symbol for socket error (6) is displayedon the screen, we are dealing with a socket wi-ring error. If a voltage exceeding the pre-selec-ted contact voltage limit is present between Nand PE, 'UB>UL' (4) is displayed on the screen.

To perform a complete socket test, touch thecontact electrode PE (25) and observe the di-splayed values on the screen. A valid result mayonly be achieved when touching the contactelectrode PE (25)!

You are dealing with a PE error, if the error sig-nal is audible and the 'Attention' symbol (1),and 'Socket Error' (6) are displayed. I.e., eitherthe PE is not connected or a high voltage(phase) is present at PE.

The measurement may only be started if thesocket is not faulty and the measurement adap-ter has been connected by respecting correctpolarity.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

20

Loop Impedance Measurement without RCD Tripping

RINS, LowΩ

VAC/DC

L

NPE

Page 21: TELARIS 0100 plus

Read the measurement result displayed on thescreen. The loop resistance is displayed in thelarge result field (12). The short-circuit currentIk is displayed in the small result field (14).

If the resistance measured exceeds 1999 Ω,the attention symbol (1) and '>1999 Ω' are di-splayed on the screen. As there is no valid me-asurement value for ZL, it is not possible to cal-culate and display the short-circuit current IK.'---' is displayed in the small result field (14

The short-circuit current is calculated using themains voltage and the loop impedance. Here,the value 230V is used for the mains voltage ifthe mains voltage amounts close to 230V. If themeasurement value deviates considerablyfrom 230V, the actual measurement value isused to calculate the short-circuit current.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results.

If many measurement are performed allowingonly "short breaks", the internal over tempera-ture protection of the Telaris 0100 plus is trig-gered and the symbol for excessive tempera-ture (20) is displayed on the screen. Thefollowing mains internal resistance measure-ment may only be started once the instrumenthas cooled down and the symbol (20) has di-sappeared from the screen. Thus, any damageto the instrument can be avoided.

You may store the measurement result by pres-sing the 'Store' key (27).

If you wish to store the condition of a faulty socket, please press the "Start” key (26) first.After hearing the "Error Signal” you may pressthe "Store” key (27).

5.7 General Information about RCD TestsThe contact voltage UB and the trip time t requiredby the RCD to disconnect the subsequent currentcircuit from the mains represent important meas-urement units for the assessment of an RCD.

For this reason, IEC 60364 prescribes that

a) the maximum allowable value for the contactvoltage (25V/50V) may not be exceeded withinany system during tripping at nominal residualcurrent.

b) the RCD must trip within a time limit of 300ms.

The task of an residual current device (RCD) con-sists in switching off a system within a defined timeperiod after an error prior the contact voltage reach-es the permissible limit value of 25V / 50V.

The system testing should be started by carryingout a visual inspection, in particular of the protec-tive earth connection.

1. Within the IT system, the protective earth con-ductor does not have to be connected with thePEN but with the protective earth connection.

2. The protective earth conductor must be connect-ed to the PEN prior to the RCD within the TN sys-tem.

3. An insulation measurement as described in Sec-tion 5.3 must be performed. In particular it mustbe proofed, that there is no connection betweenN and PE following the RCD.

4. Proof regarding the low impedance connection ofequipotential bonding conductors in compliancewith Section 5.2 must be available.

21

General Information about RCD Tests

Page 22: TELARIS 0100 plus

Time-delayed residual current devices trip atnominal residual current within 130…500ms,for double nominal fault current within60…200 ms. Such RCDs are im-plemented asmain residual current protection devices(please refer to IEC 61008-1) and are markedwith the symbol .

The contact voltage represents the voltage pre-sent during an insulation error between two si-multaneously touchable components.

At a measuring circuit without probe, availablevoltages between PE and earth can influencethe measurement..

At use of the N-conductor as probe, the N-con-ductor should be check first for all of correctand low-ohm connection to neutral point of sy-stem. An available voltage of the N conductorto the earth can influence the measurement.

Leakage currents by preconnected loads caninfluence the measuring.

Attached loads or operating supplies whichcontains capacitors or circulating machinescan elongate the trip time.

Any test and measurement procedures in cir-cuits equipped with residual current devicesshould only be performed after having con-sulted the operator terminals (data processingsystems, material processing, motors, etc.).

For measurements on earthed sockets orequipment with protective conductor connec-tion, the protective earth must be checked forcorrect connection by touching contact elec-trode "PE". If an error is indicated via the sock-et error symbol (6), the PE connection must bechecked ! The user may only start the test, oncethe protective conductor is properly connect-ed.

Prior to testing, we recommend all loads areswitched off as they could falsify the measure-ment result.

The protective earth must be free of externalvoltage for the RCD test. However if an extra-neous voltage is present, the instrument onlyindicates the voltage VC having been generat-ed by the measurement. The measurement in-terruption caused by excess of VL by VC is onlygenerated by the actual voltage present be-tween the neutral conductor (N) and the pro-tective earth (PE).

5.7.1 RCD – Measurement of Contact

Voltage UB and the Earthing Resistance

RE without RCD Tripping

The instrument UNITEST TELARIS 0100 plus offersthe facility to test contact voltage or the earthing re-sistance with reference to the nominal current of theRCD within supply systems equipped with RCDs wi-thout causing the RCD to trip. The contact voltagemeasurement is performed at approximately 1/3 ofthe pre-selected nominal current. The measuredcontact voltage is then extrapolated to nominal tripcurrent and finally displayed.The contact voltage is determined by short-termmains loading, the measurement current flows wit-hin the PE and L conductors.

To achieve a precise measurement result, weadvise to switch off all loads or to disconnectthem from the mains, and to ensure that theUUT is faultfree.

Leakage currents within the current circuit fol-lowing the residual current circuit breaker mayfalsify the measurement, like any possible vol-tage present between PE and ground, and anypossible voltage present between neutral con-ductor and ground.

22

RCD – Measurement of Contact Voltage UB

Page 23: TELARIS 0100 plus

Prior to performing the measurement, checkthe connection of the neutral conductor bet-ween the mains neutral point and the earth.

The contact voltage only refers to the contactvoltage generated by the measurement and notto the actual contact voltage present.

Connect the "Schuko-plug Measurement Plug"mains adapter to the Telaris 0100 plus, by in-serting the measurement plugs labelled with L,N, PE into the respective sockets L (33),N (34),and PE (35).

Plug the Schuko-plug into the socket under test.

Select the contact voltage measurement func-tion (UB/RE [RCD/FI] ) by means of the rotarydial (32).

Select the nominal current of the installed RCDusing the 'I∆N ' (22) and ' I∆N ' keys (23).

The following nominal trip currents are availa-ble: 10mA, 30mA, 100mA, 300mA, 500mA, se-lective 100mA, selective 300mA, and selective500mA.

Select the contact voltage limit by pressing the'VL' key (24).

The socket is continuously tested for perfectfunctioning. If the display indicates the symbol„Turn plug by 180°", turn the plug by 180° orthe connection N and L of the instrument mustbe exchanged.

If the symbol for socket error (6) is displayedon the screen, we are dealing with a socket wi-ring error. If a voltage exceeding the preselec-ted contact voltage limit is present between Nand PE, 'UB>UL' (4) is displayed on the screen.

To perform a complete socket test, touch thecontact electrode PE (25) and observe the di-splayed values on the screen. A valid result mayonly be achieved when touching the contactelectrode PE (25)!

You are dealing with a PE error, if the error sig-nal is audible and the 'Attention' symbol (1),and 'Socket Error' (6) are displayed. I.e., eitherthe PE is not connected or a high voltage(phase) is present at PE.

23

RCD – Measurement of Contact Voltage UB

RINS, LowΩ

VAC/DC

L

NPE

Page 24: TELARIS 0100 plus

The measurement may only be started if thesocket is not faulty and the measurement adap-ter has been connected by respecting correctpolarity.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

If the RCD trips during the measurement, theattention symbol (1) is then illuminated as wellas the symbol for socket error (6). In this in-stance, please check if the correct nominal tripcurrent has been selected. Possibly, the cur-rent preload of the PE is at such a high level thatthe RCD trips orderly caused by the test, or theRCD itself might even be faulty.

If the contact voltage measured exceeds the 50V or 100 V measurement range, the attentionsymbol (1) and '>50V' or '>100V' are display-ed on the screen.

The short-circuit current is calculated using thecontact voltage and the selected nominal tripcurrent of the RCD.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results

If many measurement are performed allowingonly "short breaks", the internal over tempera-ture protection of the Telaris 0100 plus is trig-gered and the symbol for excessive tempera-ture (20) is displayed on the screen. Thefollowing measurement may only be startedonce the instrument has cooled down and thesymbol (20) has disappeared from the screen.Thus, any damage to the instrument can beavoided.

You may store the measurement result by pres-sing the 'Store' key (27).

If you wish to store the condition of a faulty socket, please press the "Start” key (26) first.After hearing the "Error Signal” you may pressthe "Store” key (27).

5.7.2 RCD Trip Time Test, Contact

Voltage (ta, UB / RE)

This test is used to check the trip time of standardand selective RCDs. Additionally, the contact volta-ge (UB) generated during the test is measured.This RCD test is divided into two tests: the prelimi-nary test is performed at 1/3 I∆N, the RCD not trip.The contact voltage UB is measured during this pre-liminary test and extrapolated to the nominal tripcurrent I∆N (or 2 I∆N for selective RCDs). Duringthe main test, the selected nominal trip current (I∆Nor 2 I∆N) flows. The RCD must trip.

To obtain a precise measurement result, we ad-vise to switch off all loads or to disconnectthem from the mains.

Connect the 'Schuko-Plug – Measurement Plug'measurement adapter to the Telaris 0100 plus,by inserting the measurement plugs labelled L,N, PE into the respective sockets: L (33), N (34),and PE (35).

Plug the Schuko-plug into the socket under test.

Select the trip time measurement (tA/UB [RCD])using the "Measurement Function" rotary dial(32)..

Select the nominal current of the installed RCDusing the 'I∆N ' (22) and ' I∆N ' (23) keys.

24

RCD Trip Time Test, Contact Voltage (ta, UB / RE)

Page 25: TELARIS 0100 plus

The following nominal trip currents are availa-ble:10mA, 30mA, 0.5x 30mA, 5x 30mA,100mA, 300mA, 500mA, selective 100mA, se-lective 300mA, and selective 500mA.

Select the contact voltage limit by pressing the'VL' (24) key.

The socket is continuously checked for faults.If the "turn plug by 180°” symbol (7) is di-splayed on the screen, you are advised to eit-her turn the Schuko-plug or the exchange theL and N connectors at the instrument.

If the symbol for socket error (6) is displayedon the screen, we are dealing with a socket wi-ring error. If a voltage exceeding the preselec-ted contact voltage limit is present between Nand PE, 'UB>UL' (4) is displayed on the screen

To perform a complete socket test, touch thecontact electrode PE (25) and observe the di-splayed values on the screen. A valid result mayonly be achieved when touching the contactelectrode PE (25)!

You are dealing with a PE error, if the error sig-nal is audible and the 'Attention' symbol (1),and 'Socket Error' (6) are displayed. I.e., eitherthe PE is not connected or a high voltage(phase) is present at PE.

The measurement may only be started if thesocket is not faulty and the measurement adap-ter has been connected by respecting correctpolarity.

When testing a selective RCD a waiting time of30s is respected between preliminary test andmain test. The remaining waiting time is conti-nuously displayed on the screen. You mayinterrupt the test by turning the rotary dial.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

If a contact voltage UB is generated betweenconductors N and PE exceeding the pre-selec-ted contact voltage limit VL, the measurementis interrupted and the 'Attention' (1), 'UB>UL'(4) symbols are displayed on the screen.

25

RCD Trip Time Test, Contact Voltage (ta, UB / RE)

RINS, LowΩ

VAC/DC

L

NPE

Page 26: TELARIS 0100 plus

If the contact voltage measured exceeds the50V or 100V measurement range, the attentionsymbol (1) and '>50V' or '>100V' are display-ed on the screen.

The trip time tA is displayed in the large result field(12). The measured contact voltage may be calledfor display by pressing the 'display' key (21).

If the RCD trips during the measurement, thesymbol for socket error (6) is displayed. If theRCD already trips during the preliminary test,the "Attention” symbol (1) is displayed, in ad-dition. In this instance, please check whetherthe correct nominal trip current has been se-lected. Possibly, the current preload of the PEis at such a high level that the RCD trips order-ly caused by the test, or the RCD itself mighteven be faulty.

If the trip time tA is not within the admissiblerange (standard RCD: A < 300ms; selectiveRCD: 60ms < tA < 200ms), the 'Attention' sym-bol (1) is displayed and the symbol for 'LimitValue exceeded' (3) appears to indicate the triptime. The test time is set to respectively 500ms.

Two additional test currents are integrated asspecial options for the RCD with a nominal cur-rent of 30mA and may be selected using the 'I∆N' (22) and ' I∆N ' (23) keys:

a) 0.5x 30mA (=15mA). The test time is set to 2s,the RCD may not trip.

b) 5x 30mA (=150mA). The test time is set to50ms, the RCD must trip within 40 ms.

Failure for RCD tripping could be a wrong set-ting of the nominal current or a faulty RCD.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results.

If many measurement are performed allowingonly "short breaks", the internal over tempera-ture protection of the Telaris 0100 plus is trig-gered and the symbol for excessive tempera-ture (20) is displayed on the screen. Thefollowing measurement may only be startedonce the instrument has cooled down and thesymbol (20) has disappeared from the screen.Thus any damage to the instrument can be avo-ided.

You may store the measurement result by pres-sing the 'Store' key (27).

If you wish to store the condition of a faulty sok-ket, please press the "Start” key (26) first. Afterhearing the "Error Signal” you may press the"Store” key (27).

26

RCD Trip Time Test, Contact Voltage (ta, UB / RE)

Page 27: TELARIS 0100 plus

5.7.3 RCD Test with Rising Residual Current

(Ramp Method), Trip Current

(I , ta/VC

For this test, the trip current I of the RCD is meas-ured. The contact voltage VC is measured during thepreliminary test at a current of 1/3 I∆N. The RCDtest is resumed after the successful preliminary testat a residual current, rising in steps of 10 % from40 % I∆N until maximum 140 % I∆N. The present-ly active residual current is indicated on the displayand in the event of the RCD tripping the trip time ofthe RCD is measured. The contact voltage VC isevaluated for the trip current I .

To obtain a precise measurement result, we ad-vise to switch off all loads or to disconnectthem from the mains.

Connect the 'Schuko-Plug – Measurement Plug'measurement adapter to the Telaris 0100 plus,by inserting the measurement plugs labelled L,N, PE into the respective sockets: L (33), N (34),and PE (35).

Connect mains plug or test lead to UUT, re-specting correct polarity.

Select the trip time measurement (IR, tA/UB[RCD]) using the "Measurement Function" rota-ry dial (32).

Select the nominal current of the installed RCDusing the 'I∆N ' (22) and ' I∆N ' (23) keys.

The following nominal trip currents are availa-ble:10mA, 30mA, 100mA, 300mA, and 500mA.

Select the contact voltage limit by pressing the'VL' (24) key.

The socket is continuously checked for faults.If the "turn plug by 180°” symbol (7) is di-splayed on the screen, you are advised to eit-her turn the Schuko-plug or the exchange theL and N connectors at the instrument.

If the socket symbol (6) is displayed, a mainserror is present. If the voltage present betweenN and PE exceeds the preselected contact vol-tage limit (50V/25V), „UB>UL" (4) is displayed.

To perform a complete socket test, touch thecontact electrode PE (23) and observe the di-splayed values on the screen. If the symbol "socket error" (6) occurs, a PE error is present.

27

RCD Test with Rising Residual Current (Ramp Method), Trip Current (I , ta/VC

RINS, LowΩ

VAC/DC

L

NPE

Page 28: TELARIS 0100 plus

You are dealing with a PE error, if the error sig-nal is audible and the 'Attention' symbol (1),and 'Socket Error' (6) are displayed. I.e., eitherthe PE is not connected or a high voltage(phase) is present at PE.

The measurement may only be started if thesocket is not faulty and the measurement adap-ter has been connected by respecting correctpolarity.

Press the "Start" key (26) to start the measure-ment. During the measurement ' - ' is displayedon the screen.

If a contact voltage UB is generated betweenconductors N and PE exceeding the pre-selec-ted contact voltage limit VL, the measurementis interrupted and the 'Attention' (1), 'UB>UL'(4) symbols are displayed on the screen.

If the contact voltage measured exceeds the50V or 100V measurement range, the attentionsymbol (1) and '>50V' or '>100V' are display-ed on the screen..

The trip time tA is displayed in the large result field(12). The measured trip time tA and the contact vol-tage with reference to the trip current may be calledfor display by pressing the 'display' key (21).

If the RCD trips during the measurement, thesymbol for socket error (6) is displayed. If theRCD already trips during the preliminary test,the "Attention” symbol (1) is displayed in addi-tion. In this instance, please check whether thecorrect nominal trip current has been selected.Possibly, the current preload of the PE is atsuch a high level that the RCD trips cirrectlycaused by the test, or the RCD itself might evenbe faulty.

If the trip time tA measured is not within the ad-missible range (tA: < 300ms; 50% I∆N ? IR∆100% I∆N), the 'Attention' symbol (1) is di-splayed and for the display of the respectivelevel the symbol for 'Limit Value exceeded' (3)appears. To make a safe decision whether theRCD is defective, a trip test should be perfor-med at nominal trip current (tA, UB). For exam-ple, an RCD is in perfect condition when havinga trip time > 300ms at 60 % I∆N, and when te-sting at nominal trip current (at 100% I∆N)showing however a trip time < 300ms.

Failure for RCD tripping could be a wrong set-ting of the nominal current or a faulty RCD.

Supply system preloading and voltage fluctu-ations can lead to erroneous measurement re-sults. Therefore, you are advised to performseveral measurements and to compare the me-asurement results.

If many measurement are performed allowingonly "short breaks", the internal over tempera-ture protection of the Telaris 0100 plus is trig-gered and the symbol for excessive tempera-ture (20) is displayed on the screen. Thefollowing mains internal resistance measure-ment may only be started once the instrumenthas cooled down and the symbol (20) has di-sappeared from the screen. Thus, any damageto the instrument can be avoided.

You may store the measurement result by pres-sing the 'Store' key (27).

If you wish to store the condition of a faulty socket, please press the "Start” key (26) first.After hearing the "Error Signal” you may pressthe "Store” key (27).

28

RCD Test with Rising Residual Current (Ramp Method), Trip Current (I , ta/VC

Page 29: TELARIS 0100 plus

5.8 Rotary Field Test

The UNITEST Telaris 0100 plus allows to check therotary field within systems of nominal user voltagesof approx. approx. 100 to 440V.

Connect the test leads supplied with the Telaris0100 plus, by inserting the measurement plugslabelled L1, L2, L3 into the respective socketsL1 (33) ,L2 (34), and L3 (35).

Plug test probe or alligator clips onto the plugsof the test leads and connect to the socket or theconnection field.

Select the rotary field function using the rotarydial (32).

Once the three test leads have been connectedto the three phases L1, L2, and L3 and a rota-ry field is present, the instrument will displaythe respective rotary field:

1.2.3 for clockwise rotary field, 2.1.3 for anti-clockwise rotary field.

In addition to the rotary field, display can bemade of the external conductor voltages. Forthis, you have to press the 'Display (21) key (se-veral times). Thus, the voltage for U12 (forU[L1-L2]), U23, and U31 can be subsequentlydisplayed.

Correct display of the rotary field can only beperformed if the ratio between maximum sin-gle conductor voltage and minimum singleconductor voltage does not exceed 1.8. .

Save the measurement result by pressing the'Store' key (27).

The external conductor voltages are not saved.

29

Rotary Field Test

RINS, LowΩ

VAC/DC

L3

NPE

L1

L2

Page 30: TELARIS 0100 plus

6.0 Storing, Printing

and Data Transfer

After a successful measurement, it is possible tosave the measurement value by means of „Store”key (27). Approximately 500 measurement valuescan be saved. Proceed as follows:

After the saving process, it is possible to view thelast saved measurement result and to print a reportcontaining the measurement results using the pro-tocol printer (option Cat. No. 1196).

If desired, the data may be transferred via a serialinterface to a PC for the reporting using the softwarees control 0100 (option Cat. No. 1251).

6.1 Storing Measurement Data

To save the measurement data, please proceed asfollows:

Perform a measurement. Store the measurement result by pressing the

“Store” (27) key. After successful saving, a brief signal is audi-

ble and the symbol "M” (17) is displayed, fol-lowed by the brief display of the continuousmemory location number.

If the memory is full and the key “Store” (27) ispressed, the symbol "M" (17) is briefly displayed andan error signal is audible.

The saved data is kept in the memory evenwhen the appliance is switched off.

It is not possible to save a measurement valuetwice!

Under certain unfavourable conditions, datamay be lost or modified with any electronicmemory. The company CH. BEHA GmbH willnot be held responsible, neither for financialnor for any other losses caused by data loss,incorrect handling, or any other reason.

We highly recommend to perform a dailymeasurement data transfer to a PC and tosave the data. The measurement data with-in the measurement appliance might be lostby unforeseeable and exterior influences(drop, electro-magnetic influence, etc.).

6.2 Viewing Measurement Data

Respectively, the last measurement value can bedisplayed.

To view measurement data, please proceed as fol-lows: Briefly press the key “Clear/Recall” (29). The

last memory location number is displayed. After this, the measurement data and the pre-

selected limit values are displayed for approx.2 seconds.

Attention, extended pressing (longer than 2s)of the key “Clear/Recall” (29) causes the lastmeasurement value to be deleted.

30

Storing, Printing and Data Transfer

Page 31: TELARIS 0100 plus

6.3 Printing Measurement Data

Saving after the measurement result, it is possibleto print the datas. For this, the UNITEST ProtocolPrinter (Cat. No. 1196) and the Interface Adapter(Cat. No. 1157) are required (option).

Selection can be made whether the last saved re-sult, all results, or part of the results should be prin-ted.

To print the measurement data, please proceed asfollows:

Perform the desired measurements and savethese measurements by pressing the key“Store” (17), please refer to section 6.1.

Remove holster

Apply the TELARIS Interface Adapter (Cat. No.1157) onto the TELARIS 0100 plus.

Connect the serial connection cable with theprotocol printer.

Switch on the printer and set the interface pa-rameter on the protocol printer in compliancewith the TELARIS 0100 plus .

To print the last saved result, briefly press the"Print” key (31). "Prt" is displayed on the screen,the data is transmitted to the protocol printer.

To print all memorised data, press the "Print" key(31) for a longer time (approx. 3 seconds). "Prt”is displayed on the screen, The data is trans-mitted to the protocol printer.

Now, all data is printed starting from the last me-morised result. During printing, the currentlyprinted memory address number is displayed

The printout of all results can be cancelled at anytime. This is done by pressing the "Print” key(31) again during the printing of the last reque-sted data string. Keep the key pressed until theprint job has been cancelled.

This function allows partial printing of data.

It is important to observe the interface settingsof the protocol printer and accordingly set theinterface parameter of the TELARIS 0100 plus(9600 Baud, even parity, 8 data bit, 1 stop bit,1 start bit, please refer to the technical data sec-tion). Please refer to the instruction manualsupplied with the protocol printer (Cat. No.1196) for printer parameter setting.

31

Printing Measurement Data

Page 32: TELARIS 0100 plus

6.4 Deleting Saved Measurement

Data/View the Memory Location Number

It is possible to delete the last measurement valueor all measurement values by pressing the key"Clear/Recall” (29).

6.4.1 Delete Last Saved Measurement Value: Press the key “Clear/Recall” (29) and keep it de-

pressed.

An acoustic signal is audible and the last me-mory location number is briefly displayed.

Now release the key “Clear/Recall” (29) to avoiddeletion of the complete memory.

Deleting the last saved measurement value orlast entered UUT number can be repeated asdesired, i.e. as long as data is available withinthe memory.

6.5 Delete all Saved Measurement Values:

Press the key “Clear/Recall” (29) for and keep itdepressed for approx. 5 s

An acoustic signal is audible and the last mem-ory location number is briefly displayed. After-wards, the measurement value or the UUT num-ber saved at this memory location is displayed

A beep signal is audible after 2 sec. and the laststored value is deleted.

A beep signal is audible after 2 sec. and allstored values are deleted.

“0“ appears on the LC-display. The memory iscompletely deleted, the „M" symbol in the dis-play disappears.

6.6 Infrared Interface, send Measurement Data

Additionally, all stored measurement data may betransferred to the PC (for reporting) by the InfraredInterface. For this purpose, the interface adapterand the Software "es control 0100” (Cat. No. 1251)and Interface (Cat. No. 1157), available as an op-tional feature, are required.

The data transfer procedure is a simple process:

Carry out measurements and save these bypressing key “Store” (27), see also section 6.1.

Remove holster

Apply the Interface adapter (Cat. No. 1157) toTELARIS 0100 plus.

Connect interface cable via 9pole D-sub con-nector to serial interface of PC (ie COM 1).

Call the "es control 0100” Software (pleaserefer to user manual "es control 0100”).

If PC is ready for receiving data, press the keySend (28)

Data transfer is carried out. After a succesfuldata transfer all stored data is available for fur-ther processing in the PC.

32

Deleting Saved Measurement Data/View the Memory Location Number

Page 33: TELARIS 0100 plus

7.0 Displays / Error Messages

33

Displays / Error Messages

Functions Message CauseAll

All

All is blinking

All

MAll FunctionsAll Functions Vac

Vac

Vdc

Vdc

Rins

Rins

Low Ω

Low Ω

RinsLow Ω

Batteries are virtually empty and have to be replaced.Measurement results no longer comply with the specifications. Batteries are empty. No function of the Telaris

TELARIS is ready for measurement.

TELARIS is active (active measurement).

Overflow, voltage present exceeds 440 VAC

Overflow, voltage present exceeds 440 VDC

Overflow, voltage present falls below -440V DC

Insulation resistance exceeds or is greater than 199,99MOhm

Selected voltage is 500V

Test lead resistance has been compensated.

External voltage present, measurement may not be carried out.

Low ohm resistance higher than 1999 Ohm

Frequency of AC voltage outside range 10.0 ... 99,9Hz

Minimum one measurement result has been stored in memory.

Test leads are short curcuited orPE test leads are connected to one ofthe other test leadsSelected test voltage is 250 V

Attention symbol for exceeding limit values

Page 34: TELARIS 0100 plus

34

Displays / Error Messages

Function Message CauseRs, IPSCRI, IPSC

Rs, IPSCRI, IPSC

Rs, IIPSCRI, IPSCRCD

Rs, IPSCRI, IPSCRCDRs, Ik; RI, IPSC;RCD PE - Error

Rs, IPSCRI, IPSCRCD

RCD

RCD

RCD

RCD has not tripped.

RCD

RCD

RCD

RCD

RCD

Loop impedance is higher than 1999 Ohm

Contact voltage has exceeded preset limit during the socket test.

Measurement therefore not carried out, until instrument has beenallowed to cool down.

TELARIS 0100 is overheated, therefore no further measurements can be carried out.

Socket incorrectly connected, or RCD has tripped.

Insert plug after turning it by180°C or change L and N of test leads.

Trip time exceeds 500ms

Trip time exceeds 1999 ms or RCD has not tripped

Trip time exceeds 50 ms or RCD has not tripped

Trip time exceeds 300 ms or RCD has not tripped

Selective RCD has tripped after 19 ms. RCD error, trip time is less than 60 ms

Measurement of trip time Ia

(only at nominal fault current I∆N = 5 x 30 mA)

(only at nominal fault current I∆N = 0.5 x 30 mA)

Test of selective RCD´sTest of selective RCD´s

Measurement of trip current, Display of trip current

For correct measuremet touch contact electrode

For correct measurement touch contact electrode

Contact-electrode hastouched

Page 35: TELARIS 0100 plus

35

Displays / Error Messages

Function Message CauseRCD

RCD

RCD

RCD

RCD

Rotary field

Rotary field

Rotary field

RCD has tripped at 345 ms. As trip time exceeds 300ms, the RCD has failled!

Selective RCD has tripped at 219 ms. As trip time exceeds 200ms, the RCD has failled!

The contact voltage exceeded the pre-set limitMeasurement therefore not carried out

The contact voltage exceeded the pre-set limit, more than 100 V. Measurement therefore not carried out

The contact voltage exceeded the pre-set limit already during the socket test. Measurement therefore not carried out

No rotary field is present or one voltage is out of specific. range

Rotary field (right) is present at L1, L2, L3

Rotary field (left) is present at L1, L2, L3

Page 36: TELARIS 0100 plus

8.0 Energy Management Approximately 5 minutes after the last key operation,the instrument switches off automatically (auto-power-off). To switch the instrument on again, turnthe rotary switch from the „OFF" position to the de-sired function or press the key “Start” (26) again . If the battery symbol (8) appears in the display thebattery is low. The instrument might still function,however, without fulfilling the specifications. If thebatteries are used further and discharged, the in-strument will automatically switch off once the bat-tery voltage falls below the minimum level. The bat-tery symbol (8) will blink for several seconds. Youcannot switch on the instrument with dischargedbatteries.

9.0 MaintenanceWhen using the instrument in compliance with theinstruction manual, no special maintenance is re-quired.Should operational problems occur during daily use,our Hotline Support (phone 0049(0)7684/8009-29)will be at your disposal, free of charge. For anyqueries regarding the instrument, please alwaysquote product designation and serial number, bothmarked on the typed shield label on the rear of the in-strument.

If functional errors occur after expiration of warran-ty, our after sales service will repair your instrumentwithout delay.

9.1 CleaningIf the instrument is dirty after daily usage, it is advisedto clean it by using a damp cloth and a mild house-hold detergent.

Prior to cleaning, ensure that the instrument isswitched off and disconnected from externalvoltage supply and any other instruments con-nected (such as EUT, control instruments, etc.).

Never use acid detergents or dissolvants forcleaning.

Do not use the instrument after cleaning untilis has completely dried off.

10.0 Battery ReplacementIf the battery symbol (8) appears in the display, pro-ceed with battery replacement.

Prior to storage battery replacement, discon-nect the instrument from any connected testleads.

When replacing or changing the battery, makecertain of correct polarity.

Reverse polarity of batteries may destroy theinstrument. Furthermore, they may explode orignite.

Only use batteries in compliance with the speci-fications in the technical data section 1,5VMignon Typ IEC LR6 (size AA).

Never try to disassemble battery cells !The bat-tery contains highly alkaline electrolyte. If elec-trolyte gets in contact with skin or clothing,rinse immediately with water. If electrolyte getsin contact with the eyes, immediately flush byusing pure water and consult a doctor.

Never try to make contact between both bat-tery cell poles, for example by using a wire con-nection. The resulting short-circuit current isvery high and causes extreme heat. Danger offire and explosion !

36

Energy Management /Maintenance/Battery Replacement

Page 37: TELARIS 0100 plus

Switch off the instrument via the rotary switch anddisconnect the instrument from the connectedmeasurement circuits.

Remove holster Loosen the screws on the rear of the instrument

Lift the battery case cover (by gently hitting the in-strument in the palm of your hand).

Remove the discharged batteries. Insert new batteries and ensure there is correct

polarity. Replace the battery case cover and retighten the

screws. The instrument is now ready for further measu-

rements.

Please consider your environment when youdispose of your used batteries or accumula-tors. They belong in a rubbish dump for haz-ardous waste. In most cases, the batteriescan be returned to their point of sale.

Please, comply with the appropriate regulationsconcerning the return, recycling and disposal ofused batteries.

If an instrument is not used over an extended pe-riod of time, the batteries must be removed.Should the instrument be contaminated by leak-ing battery cells, the instrument has to be re-turned for cleaning and inspection to the facto-ry.

37

Battery Replacement

Page 38: TELARIS 0100 plus

11.0 Built in fuses

The instrument measurement inputs are protectedby fuses, described in Section 13, Technical Data.

Both fuses are housed within the test instru-ment: Fuse F1 is located within the input circu-it of L1 (or L). Fuse F2 is located within the inputcircuit of L3 (or PE). To replace the fuses, youmust open the instrument TELARIS 0100 plus.

The fuses may only be replaced by our factoryservice department.

You may only use fuses complying with thecurrent values, voltage values, switch off cha-racteristics and capacities as stipulated in ourtechnical data section.

11.1 Display for Tripped Fuses

If during the measurement, the TELARIS 0100plus displays the measurement data describedbelow, this indicates that the respective fuse hastripped.

The fuse must be replaced and the measure-ment instrument must be returned to our fac-tory or an authorised service department foroverhauling.

Function "Low Ohm": Display >19.99 Ohm in spite of short-circuitedtest leads: Fuse F1 has tripped.

For the function "Rins": Display >199.9 MOhm in spite of short-circuitedtest leads: Fuse F1 has tripped or the measurementis cancelled. The following symbols are briefly di-splayed: 'Attention' (1) and 'Uext' (5): Fuse F1 hastripped.

For the function RI, IPSC - Internal Line Resistance

Display >1999Ohm also for sockets, which pos-sess a known low internal resistance (other elec-trical loads do function): Fuse F1 has tripped. If the fuse F2 is faulty, the socket test will indicate aPE error, which will disappear when touching the PEelectrode (25). During the PE electrode contact themeasurement may be started. The internal resi-stance measurement between both phases workscorrectly if the fuse F1 is in good condition.

Functions "Rs”: Display >1999Ohm also for sockets, which pos-sess a lower loop resistance: Fuse F1 has tripped. If the fuse F2 is faulty, the socket test will indicate aPE error, which will disappear when touching the PEelectrode (25).

RCD-Test

Display UB>UL also for sockets, which are in goodcondition: Fuse F1 has tripped. If the fuse F2 is faulty, the socket test will indicate aPE error, which will disappear when touching the PEelectrode (25).

The rotary field recognition and the voltage me-asurement facilities function even if fuses F1and/or F2 have tripped.

12.0 Calibration IntervalWe suggest a calibration interval of one year. If theinstrument is used very often or if it is used underrough conditions we recommend shorter intervals.If the instrument is used few times only the calibra-tion interval can be extended on to 3 years.

38

Built in fuses

Page 39: TELARIS 0100 plus

13.0 Technical Data

General technical data:Display: 3 1/2 digit or 3 digit LCDReference-Range: +17°C to 27°C, max. 70% rel. humidityTemperature-Range: 0°C to 40°C, relative humidity max. 80%Storage temperature: -10°C...+60°CHeight above MSL: up to 2000mBattery type: 6x 1,5V Mignon Typ IEC LR6 (size AA)Current-consumption: 20mA (Stand-by) Battery life: for average use approx. 1 yearAuto-Power-Off: after approx. 5minFuses: F1/F2: T 1,26A/500 V 1000 A, 6 x 32 mmData memory Interface: 9600 Baud, 1 startbit, 8 data bits, even parity, 1 stoppbitOvervoltage Category: CAT III / 440V against groundPollution degree: 2Protection Category: 2, IP50Dimensions: 235 x 103 x 70 mmWeight: 650g incl. Batteries

Voltage measurement Vac, Vdc:Measurement Range Vac: 1 ... 440VAC (Frequency f: 10 ... 99.9 Hz) Measurement Range Vdc: 1 ... ±440VDCResolution: 1 VTolerance: ±(3% rdg. +3 Digit)Internal Resistance: 1 MΩ

Frequency Measurement f:Measurement Range: 10,0 ... 99,9HzResolution: 0,1HzTolerance: ±(1% rdg. +1 Digit)Voltage Range: 5 ... 440VAC

Low Ω Measurement:Measurement range: 0,01...19,99 Ω, 20,0 ... 199,9 Ω, 200 ... 1999ΩResolution: 0,01 Ω, 0,1Ω, 1ΩTolerancy: ± (3% + 5digits)Output voltage Uq: 4V...9V DCTest Current: ≥ 200mA (at resistance < 2Ω+Rcomp)Measurement time: approx. 1s (automatic) (continous)Number of Measurements: approx. 4000 (1Ω, 1 measurement- 25s break)Compensated test lead resistance: max. 1,99 Ω

39

Technical Data

Page 40: TELARIS 0100 plus

40

Technical Data

Insulation Measurement Rins:Measurement Range: 0,05 ... 19,99 MΩ, 20,0 ... 199,9 MΩResolution: 0,01 MΩ, 0,1 MΩTolerance: ±(5% rdg. + 5 Digit)

Nominal- Max. open-circuit Numbers of measurement with 1mA output voltage voltage Uq Load (1 Measurement - 25s break)100V DC UN + 50% approx. 6000250V DC UN + 50% approx. 4000500V DC UN + 50% approx. 3000

Max. open-circuit voltage Un + 50 %Test current: ≥1 mA at VnShort-circuit current: < 3 mAMeasurement time: 1 - 3 s (automatic)

1 - 10 s (automatic, at capacitive Load)optional (continous)

Overload-Protection: 500V AC/DC continous, 600V AC/DC for 10sAutomatic measurement range selection.EUT automatically discharged after measurement.

Mains internal resistance RI, IPSCMeasurement range: 0,15...19,99 Ω (Dispay range: 0,05 Ω ... )

20,0 ... 199,9 Ω200 ... 1999 Ω

Resolution: 0,01 Ω, 0,1 Ω, 1 ΩTolerancy: ± (6% v.M. + 5 Digit)Test current: < 4.5 A (230 V), < 8A (400 V)Load time: < 200 msNominal mains voltage: 230V (-15 %) ... 400V (+10 %), 50 ... 60Hz, cos ϕ > 0,95Measurement time: approx. 3s

Prospective Short-Circuit Current :Measurement Range: 0,10...9,99 A, 10,0 A...99,9 A, 100 A...999 A,

1,00 ... 8,80 kAResolution: 0,01 A, 0,1 A, 1 A, 0,01 kAShort-circuit current is calculated by the measured mains internal resistance

Max. mains fluctuations during measurement: 1%Automatic measurement range selection

Page 41: TELARIS 0100 plus

Loop Impedance ZL:Mains nominal voltag: 230 V +10 % -15 % (50...60 Hz), cos ϕ 0,95Measurement Range: 0,15 ... 19,99 Ω, 20,0 ... 199,9 Ω, 200 ... 1999 ΩDisplay Range: 0,05 Ω...1999 ΩResolution: 0,01 Ω, 0,1 Ω, 1 ΩTolerance: ±(6% rdg. +5 Digit)Test current: < 4,5 ALoad time: < 200 msMeasurement time: approx. 3sMax. nominal voltage fluctuation during the measurement: 1%Protective conductor must not be live.RCD´s have to be bridgedAutomatic measurement range selection

Prospective Short-Circuit Current :Measurement Range: 0,10...9,99 A, 10,0 A...99,9 A, 100 A...999 A,

1,00...5,06 kAResolution: 0,01 A, 0,1 A, 1 A, 0,01 kAShort-circuit current is calculated by the measured mains internal resistance

Some limit values for measured short-circuit currents Ik for low voltage fuses DIN VDE 0636, Characteristics gL:

Nominal Current min. IPSC for save blowing < 5 s min. IPSC for save blowing < 0,2 s 6 A 33 A 71 A10 A 56 A 120 A16 A 86 A 181 A26 A 145 A 342 A35 A 213 A 617 A

Loop Resistance RCD/FIMeasurement range: 0,50..19,99 Ω (Dispay range: 0,05 Ω .)/20,0 ... 199,9 Ω / 200 ... 1999 ΩResolution: 0,01 Ω, 0,1 Ω, 1 ΩTolerancy: ± (6% v.M. + 5Digit)Test current: < 4.5 ANominal mains voltage: 230V (-15%, +10%), 50 ... 60 Hz, cos ϕ > 0,95Measurement time: approx. 7 s

Prospective Short-Circuit CurrentDisplay range: 0,10...9,99 A, 10,0 A...99,9 A, 100 A...999 A, 1,00 ... 5,06 kAResolution: 0,01 A, 0,1 A, 1 A, 0,01 kAShort-circuit current is calculated by the measured mains internal resistanceMax. mains voltage fluctuations during measurement: 1 %Max. mains internal resistance: 50 ΩMax. resistance of RN: 20 ΩAn RCD does not trip during measurement!The protective conductor must be free of noise voltage; automatic range selection

41

Technical Data

Page 42: TELARIS 0100 plus

RCD-Test:Nominal Voltage: 230 V, +10 % -15 %, (50...60 Hz)Measurement time: approx. 2s, approx. 31s (selektive RCD/FI),

max. 18s (measurement of trip current)Current switch-off: immediately at RCD tripping or at true excess of contact voltage limit.The protective conductor must be free of noise voltage.

Measurement of Contact Voltage UB:Measurement current: 1/3 nominal fault current I∆NMeasurement duration: < 100 ms, when exeeding limits immediate measurementMeasurement Range: 1...100 VResolution: 1 VTolerance: -0%...+10%, +5 DigitThreshold values: VL selection between 25V / 50VContact voltage is measured at 1/3 I∆N and may be extrapolated to nominal current I∆N or double nominalcurrent 2 I∆N for time delayed residual current circuit breakers.

Measurement of Ground Resistance:Nominal fault Current I∆N: 10, 30, 100, 300, 500mA standard 100, 300, 500mA selectivMeasurement current: 1/3 nominal fault current I∆NMeasurement duration: < 100 ms, when exeeding limits immediate measurementMeasurement range: 10 ... 1999 Ω, 0,20 ... 10,00 kΩ at I∆N = 10mA, 30mA.Display range: 1...1999 Ω, 0,01...10,00 kΩ

Maximum RE is defined by the contact voltage limit VL. For UB > 2x UL, the measurement is interruptedand, thus, no measurement values can be obtained.

Resolution: 1 Ω, 0,01 kΩTolerancy: ± (6% v. M. + 10 digit)

* Maximum RE is defined by the contact voltage UB. For UB>UL, the measurement is interrupted and, thus,no measurement values can be obtained.

42

Technical Data

Page 43: TELARIS 0100 plus

Measurement of trip Time tA:Nominal fault current I∆N: 10, 0.5x 30, 30, 5x 30, 100, 300, 500mA Standard

100, 300, 500mA selctiveTest current type: ACMeasurement time: 500ms, not at: 0.5x 30mA - 1999ms, 5x 30mA - 50ms

each 300ms when measuring trip timeMeasurement range: 1 ... tmax, tmax is th max. test time.Resolution: 1msTolerancy: ± (2% v. M. + 2 digit)

Measurement of trip Current I :Nominal fault current I∆N: 10, 30, 100, 300, 500mA StandardMeasurement Current: 40 ... 140% of the nominal fault current I∆NResolution: 10% I∆NTolerancy: -0% ... +10%Measurement time: max. each 300msCurrent cut off: immediately for RCD tripping or when exeeding

contact voltage (25V / 50V)

Rotary FieldNominal Voltage: 100V ... 440V, 3~, 50 ... 60HzMax. difference of phase voltage: ± 30%

24 month WarrantyUNITEST instruments are subject to strict quality control. However, should the instrument function improperlyduring daily use, you are protected by our 24 months warranty (valid only with invoice). We will repair free ofcharge any defects in workmanship or material, provided the instrument is returned unopened and untamperedwith, i.e. with undamaged warranty label. Any damage due to dropping or incorrect handling are not covered bythe warranty. If the instrument shows failure following expiration of warranty, our service department can offeryou a quick and economical repair.

43

Technical Data

Subject to technical changes without notice ! 08/2003 PTDB90730000-01

CH. BEHA GmbHElektronik - ElektrotechnikIn den Engematten 1479286 Glottertal /GermanyTel.: +49 (0) 76 84/80 09-0Fax: +49 (0) 76 84/80 09-410Techn. Hotline: +49 (0) 76 84/80 09-429internet: http://www.beha.come-mail: [email protected]

®

Reg.No. 3335

Page 44: TELARIS 0100 plus

44

Die BEHA-Gruppe bestätigthiermit, dass das erworbeneProdukt gemäß den festgeleg-ten Beha-Prüfanweisungenwährend des Fertigungspro-zesses kalibriert wurde. Alleinnerhalb der Beha-Gruppedurchgeführten, qualitätsrele-vanten Tätigkeiten und Prozes-se werden permanent durchein Qualitätsmanagement-System nach ISO 9000 über-wacht.

Die BEHA-Gruppe bestätigtweiterhin, dass die während derKalibrierung verwendeten Prüf-einrichtungen und Instrumenteeiner permanenten Prüfmittel-überwachung unterliegen. DiePrüfmittel und Instrumentewerden in festgelegten Abstän-den mit Normalen kalibriert,deren Kalibrierung auf nationa-le und internationale Standardsrückführbar ist.

The BEHA Group confirmsherein that the unit you havepurchased has been calibrated,during the manufacturingprocess, in compliance withthe test procedures defined byBEHA. All BEHA proceduresand quality controls are moni-tored on a permanent basis incompliance with the ISO 9000Quality Management Stan-dards.

In addition, the BEHA Groupconfirms that all test equip-ment and instruments used du-ring the calibration process aresubject to constant control. Alltest equipment and instru-ments used are calibrated atdetermined intervals, using re-ference equipment which hasalso been calibrated in com-pliance with (and traceable to)the calibration standards ofnational and international labo-ratories.

Le groupe BEHA déclare quel´appareil auquel ce documentfait référence a été calibré aucours de sa fabrication selonles procédures de contrôle dé-finies par BEHA. Toutes cesprocédures et contrôles dequalité sont régis par le systé-me de gestion ISO 9000.

Le groupe BEHA déclare parailleurs que les équipements decontrôle et les instruments uti-lisés au cours du processus decalibrage sont eux-mêmessoumis à un contrôle techniquepermanent.

Ces mêmes équipements decontrôle sont calibrés réguliè-rement à l´aide d´appareils deréférence calibrés selon les di-rectives et normes en vigueurdans les laboratoires de re-cherche nationaux et interna-tionaux.

El grupo BEHA declara que elproducto adquirido ha sido ca-librado durante la producciónde acuerdo a las instruccionesde test BEHA. Todos los proce-sos y actividades llevados a ca-bo dentro del grupo BEHA enrelación con la calidad del pro-ducto son supervisados per-manentemente por el sistemaISO 9000 de control de calidad.

Adicionalmente, el grupo BEHAconstata que los equipos e ins-trumentos de prueba utilizadospara la calibración también sonsometidos a un permanentecontrol. Estos equipos e instru-mentos de prueba son a su vezcalibrados en intervalos regu-lares valiéndose de equipos dereferencia calibrados de acuer-do a directivas de laboratoriosnacionales e internacionales.

®

Connemara Electronics Beha GmbH Industrial ParkCarrigaline, Co. Cork Republic of IrelandTel. (+353) 21 4919000Fax (+353) 21 4919010e-mail: [email protected]

IQ NETAENOR Spain AFAQ France AIB-Vincotte Inter Belgium APCER Portugal BSI United Kingdom CSIQ Italy

CQS Czech Republic DQS Germany DS Denmark ELOT Greece FCAV Brazil IRAM Argentina JQA JapanKEMA Netherlands KSA-QA Korea MSZT Hungary NCS Norway NSAI Ireland ÖQS Austria PCBC Poland PSB Singapore

QAS Australia QMI Canada SFS Finland SII Israel JQA Japan SIQ Slovenia SIS-SAQ Sweden SQS SwitzerlandIQNet is represented in the USA by the following IQNet members: AFAQ, AIB-Vinçotte Inter, BSI, DQS, KEMA, NSAI and QMI

Qualitätszertifikat • Certificate of Quality