TI257P/24/ae
Technical Information
Deltapilot S DB50A/DB50S/51A/52A/53A
Hydrostatic Level Measurement
Pressure sensor with CONTITETM measuring cell;
waterproof, climatic-proofed, long-term stability; for food, fresh
water and wastewater, chemical and pharmaceutical products
Application
The devices in the Deltapilot S product family are used
for continuous level measurement in all liquid and
paste-like media. They are used in the chemical,
pharmaceutical and food industry as well as water and
wastewater.
Switching units perfectly in line with the application:
• Determine the level, volume, differential pressure,
density and product weight
• Control limit contacts
• Integrate the measuring point in various automation
systems.
Your benefits
• Hermetically sealed CONTITE™ measuring cell:
– Climatic-proofed and with long-term stability
– Maximum linearity (better than 0.1 % of the set
measuring range)
– Minimum temperature effects
better than 0.006%/10°F (0.1%/10 K).
• Compact, rod or cable versions available
• Separate mounting of housing and electronic insert
(NEMA 6P / IP 68 protection at the measuring
point)
• Easy and comfortable operation:
– Onsite with local display and operating module
– Operation via communication
• Replaceable electronic inserts:
– 4 to 20 mA HART®
– PROFIBUS® PA
– FOUNDATION™ Fieldbus
– Analog output
– PFM
Deltapilot S
2 Endress+Hauser
Table of contents
Function and system design . . . . . . . . . . . . . . . . . . . . 3
Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Local display (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DAT module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Handheld terminals – HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
FieldCare – HART, PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . 11
Commuwin II – HART, PROFIBUS PA . . . . . . . . . . . . . . . . . . . . 11
Remote operation – FOUNDATION Fieldbus . . . . . . . . . . . . . . . 11
Input (measured variable). . . . . . . . . . . . . . . . . . . . . 11
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sensitivity, PFM –FEB17(P) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Switch-on current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Performance characteristics . . . . . . . . . . . . . . . . . . . 16
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Position during calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Zero-point increase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Linearity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Influence of ambient temperature . . . . . . . . . . . . . . . . . . . . . . . 16
Influence of medium temperature . . . . . . . . . . . . . . . . . . . . . . 16
Operating conditions (installation) . . . . . . . . . . . . . . 17
Installation instructions for compact version DB50A, DB50S . . . 17
Installation instructions for rod and cable versions DB51A,
DB52A and DB53A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Housing adapter with mounting bracket for humid, damp and
difficult-to-access mounting locations . . . . . . . . . . . . . . . . . . . 17
Special measuring cells for substances with hydrogen formation 18
Special measuring cell for acids, alkalis or sea water . . . . . . . . . . 18
Operating conditions (environment) . . . . . . . . . . . . . 18
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ambient temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . 18
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operating conditions (process) . . . . . . . . . . . . . . . . . 19
Process temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Process temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Process pressure limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions of housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Process connections DB50A (compact version) . . . . . . . . . . . . . . 20
Process connection DB50S (food version) . . . . . . . . . . . . . . . . . . 22
Process connections DB51A (rod/pipe version) . . . . . . . . . . . . . 23
Dimensions of Deltapilot S DB52A (cable version) . . . . . . . . . . . 24
Dimensions of Deltapilot S DB53A (suspension
clamp and mounting bracket) . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Dimensions of connecting cable with housing adapter and
mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 31
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Hazardous area approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 32
DB50A – compact version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
DB50S – compact version for hygienic applications . . . . . . . . . . 34
DB51A – rod version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DB52A – cable version with process connection . . . . . . . . . . . . 38
DB53A – cable version with suspension clamp . . . . . . . . . . . . . 40
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Display and operating module FHB20 . . . . . . . . . . . . . . . . . . . 42
Cover with sight glass (high cover) . . . . . . . . . . . . . . . . . . . . . . . 42
Housing adapter with mounting bracket for humid, damp
and difficult-to-access mounting locations . . . . . . . . . . . . . . . . 42
Mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Extension cable shortening kit . . . . . . . . . . . . . . . . . . . . . . . . . 42
Suspension clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Welding neck for universal process adapter . . . . . . . . . . . . . . . . 43
Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Technical Information on switching unit . . . . . . . . . . . . . . . . . 44
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Installation Drawings/Control Drawings . . . . . . . . . . . . . . . . . . 44
Deltapilot S
Endress+Hauser 3
Function and system design
Device selection
Deltapilot S –
product family
DB50A (DB50, Euro
version)
P01-DB5xxxxx-14-xx-xx-xx-001
Compact version
DB50S (DB50L, Euro
version)
P01-DB5xxxxx-14-xx-xx-xx-002
Compact version for
hygienic applications
DB51A (DB51, Euro
version)
P01-DB5xxxxx-14-xx-xx-xx-003
Rod version
DB52A (DB52, Euro
version)
P01-DB5xxxxx-14-xx-xx-xx-004
Cable version
DB53A (DB53, Euro
version)
P01-DB5xxxxx-14-xx-xx-xx-005
Cable version with
suspension clamp
Field of application – Level measurement
– Differential pressure measurement (derived from level via switching unit)
Industries Food, pharmaceutical, environment (fresh water and wastewater), chemical
Process connections – Thread
– Flanges
– Flush-mounted
hygienic connections
– Thread
– Flanges
– Thread
– Flanges
– Suspension clamp
Process connection
material
– AISI 316L SS
– Alloy C4
– AISI 316L SS – AISI 316L SS
– Alloy C4
– AISI 316L SS
– Alloy C4
– AISI 316L SS with
plastic
Rod (pipe)/
extension cable material
— — – AISI 316L SS
– Alloy C4
– FEP
– PE
– FEP
– PE
Pipe/extension cable
length
— — 16 to 160 inch
(400 to 4000 mm)
1.6 ft to 656 ft
(0.5 to 200 m)1
1.6 ft to 656 ft
(0.5 to 200 m)2
Measuring ranges – US version: from –1.5 to +1.5 psi to –13 to 150 psi
– from –100 to +100 mbar to –900 to +10000 mbar
– Max. turn down: 10:1
Process temperature +14 to +212°F
(–10 to +100°C)
+14 to +212°F
(–10 to +100°C)
+14 to +176°F
(–10 to +80°C)
+14 to +176°F
(–10 to +80°C)
+14 to +176°F
(–10 to +80°C)
Supply voltage – Analog 0.2 to 1.2 mA: 15 to 20 V DC
– PFM: 14 to 16 V DC; FM IS: 14 to 19.2 V DC
– 4 to 20 mA HART: 11.5 to 30 V DC; FM IS: 11.5 to 30 V DC
– PROFIBUS PA , version without overvoltage protection: 9 to 32 V DC, FM IS: 9 to 24 V DC
Version with overvoltage protection: 9.6 to 32 V DC; FM IS: 9 to 24 V DC
– FOUNDATION Fieldbus: 9 to 32 V DC; FM IS: 9 to 24 V DC
Output 0.2 to 1.2 mA, analog, PFM, 4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options – 3.1 Inspection certificate
– Separate housing
– 3.1 Inspection certificate
– Separate housing
– Separate housing – Separate housing —
Specialties – Absolutely resistant to condensate due to hermetically sealed CONTITETM cell
– Stainless steel version (AISI 316L) for hygienic requirements as well as aluminum and polyester housing versions
– 3-A and EHEDG approval
– Maximum flexibility thanks to modular design
1) FM IS, CSA IS, EExia: 1.6 to 328 ft (0.5 to 100 m)
2) FM IS, CSA IS, EExia: 1.6 to 328 ft (0.5 to 100 m))
Deltapilot S
4 Endress+Hauser
DB50A, DB51A, DB52A universal usage
• Modular probe program for optimum process adaptation
• DB50A compact version: installation in the tank from below or from the side
• DB51A/DB52A rod and cable extension: installation from above, i.e. easy to equip and retrofit buried tanks,
no additional opening in the tank floor
DB50S optimized for the food and pharmaceutical industry
• All typical flush-mounted process connections can be supplied
• Welding flanges
• Stainless steel housing
• All food process connections are gap-free and can be cleaned without any residue left, e.g. CIP cleaning
• USDA/H1 approved transfer liquid as per FDA guidelines
• 3-A or EHEDG approvals
P01-DB5xxxxx-12-xx-xx-xx-004
DB53A for the water and wastewater industry
• The housing with the electronic insert is mounted outside shafts and tanks in such a way that it is protected
from flooding. The extension cable is secured with a suspension clamp.
• Electronic inserts with an integrated surge arrester provide protection against overvoltage if lightning strikes.
• The stainless steel measuring cell tube (AISI 316L) and the Alloy measuring diaphragm allow use in
aggressive media such as wastewater for example.
• Extension cable up to 656 ft (200 m) in length (up to 328 ft / 100 m in Ex-areas) without strain relief.
• Special measuring cell with gold-rhodium coating for applications in which severe hydrogen formation can
occur (e.g. digested sludge); see also Page 19.
• Special measuring cell with gold-platinum coating for acids, alkalis or sea water; see also Page 19.
74 - 02
®
Deltapilot S
Endress+Hauser 5
Measuring principle
P01-DB5xxxxx-15-xx-xx-xx-003
Deltapilot S hydrostatic level measurement and measuring principle
1 Measuring diaphragm2 Measuring element3 Process diaphragm (separating diaphragm)
g Gravitational accelerationh Level heightp tot Total pressure = hydrostatic pressure + atmospheric pressurep atm Atmospheric pressurep hydr. Hydrostatic pressurep meas Measured pressure in the measuring cell = hydrostatic pressureρ Density of fluid
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the hydrostatic
pressure depends solely on the height h of the liquid column.
The CONTITE™ measuring cell which works on the principle of the gauge pressure sensor constitutes the core
of Deltapilot S. In contrast to conventional gauge pressure sensors, the precision measuring element (2) in the
CONTITE™ measuring cell is absolutely protected between the process diaphragm (3) and the measuring
diaphragm (1). Thanks to this hermetic sealing of the measuring element, the CONTITE™ measuring cell is
absolutely insensitive to condensate, condensation and aggressive gases. The pressure applied is transferred
from the process diaphragm to the measuring element by means of an oil without any loss in pressure.
Two temperature sensors are arranged between the process diaphragm and measuring element which measure
the distribution of temperature in the cell. The electronics can compensate any measuring errors resulting from
fluctuations in temperature with these temperature measured values.
hh =
pp · g
h p
hydr.p+p
atmp =
patm
hydr.p
patm
patm
totp
hydr.p+p
atm=totp
)hydr.
p+(patm
patm
pmeas = –
ptot
patm
p = –meas
= –
1
2
3
Deltapilot S
6 Endress+Hauser
Level measurement in closed pressurized tanks
You can determine the differential pressure in pressurized tanks using two Deltapilot S probes. The pressure
measured values of the two probes are sent to a signal processing unit such as Endress+Hauser RMA or a PLC.
The signal processing unit or PLC determines the difference in pressure and uses this to calculate the level and
the density where necessary.
P01-DB5xxxxx-15-xx-xx-xx-007
Level measurement in a closed pressurized tank
1 Probe 1 measures the total pressure (hydrostatic pressure and head pressure)2 Probe 2 measures the head pressure3 The signal processing unit determines the difference in pressure and uses this to calculate the level
Note!
• When selecting the Deltapilot S probes, make sure you select large enough measuring ranges
(→ see example).
• The measuring diaphragm of probe 2 must not be flooded. This generates additional hydrostatic pressure
which distorts the measurement.
• The ratio of hydrostatic pressure to head pressure should be max. 1:6.
Example:
• Max. hydrostatic pressure = 8.71 psi (600 mbar)
• Max. top pressure (probe 2) = 4.35 psi (300 mbar)
• Max. total pressure, measured with probe 1 = 4.35 + 8.71 psi = 13 psi
(300 mbar + 600 mbar = 900 mbar)
⇒ Measuring cell to be selected: 0 to 17 psi (0 to 1200 mbar)
• Max. pressure, measured with probe 2: 4.35 psi (300 mbar)
⇒ Measuring cell to be selected: 0 to 5.8 psi (400 mbar)
1
3
2
Deltapilot S
Endress+Hauser 7
Density measurement
You can measure the density in tanks that are pressurized using two Deltapilot S probes and a signal processing
unit or a PLC. The signal processing unit or the PLC calculates the density from the known distance Δh
between the two probes and the two measured values p1 and p2.
P01-DB5xxxxx-15-xx-xx-xx-005
Level measurement in a closed pressurized tank
1 Deltapilot S determines pressure measured value p12 Deltapilot S determines pressure measured value p23 Signal processing unit determines the density from the two measured values p1 and p2 and the distance Δh.
Level measurement with automatic density correction (with changing media in the tank)
Level measurement with automatic density correction is possible in conjunction with a limit switch such as
Liquiphant and a PLC. The limit switch always switches at the same level. In the switch point, the signal
processing unit determines the corrected density from the pressure of the Deltapilot S probe currently
measured and the known distance between Deltapilot S and the limit switch. The signal processing unit then
calculates the level from the new density and the measured pressure from the Deltapilot S probe.
P01-DB5xxxxx-15-xx-xx-xx-006
Level measurement with automatic density correction
1 Deltapilot S2 Liquiphant3 PLC
p2
p1
Dh
1
2 3
Dh
1
2 3
Deltapilot S
8 Endress+Hauser
Communication protocol • 4 to 20 mA with HART communication protocol
• PROFIBUS PA
– The Endress+Hauser Deltapilot S devices meet the FISCO model requirements.
– Due to the low current consumption of 10 ± 1 mA, the following can be operated at one bus segment
with installation as per FISCO:
– Up to 9 Deltapilot S for FM IS, CSA IS and EEx ia applications
– Up to 32 Deltapilot S for all other applications, e.g. in non-hazardous areas.
Further information on PROFIBUS PA can be found in Operating Instructions BA034S "PROFIBUS DP/PA:
Guidelines for planning and commissioning" and in the PNO guideline.
• FOUNDATION Fieldbus
– The Endress+Hauser Deltapilot S devices meet the FISCO model requirements.
– Due to the low current consumption of 11 ± 1 mA, the following can be operated at one bus segment
with installation as per FISCO:
– Up to 9 Deltapilot S for FM IS, CSA IS and EEx ia applications
– Up to 32 Deltapilot S for all other applications, e.g. in non-hazardous areas.
Further information on FOUNDATION Fieldbus such as bus system component requirements are provided
in Operating Instructions BA013S "FOUNDATION Fieldbus Overview".
Measuring system Measuring system with 0.2 to 1.2 mA analog – FEB11(P)
The electronic insert returns a current signal of 0.2 to 1.2 mA that is proportional to the pressure. The FMC420
silometer provides voltage to the electronic insert and evaluates the current signal that is in proportion to the
level. The standardized signals of 0 to 10 V and 4 to 20 mA (0 to 20 mA) are then available at the output of
the silometer. → See also Technical Information TI077F and Operating Instructions BA179F.
Measuring system with PFM – FEB17(P)
The electronic insert returns a pulse-frequency-modulated signal of 200 to 1200 Hz. The evaluation and
operating unit Prolevel FMB662 provides power to the electronic insert and converts the PFM signal of the
probe to a standardized current or voltage signal. → See also Technical Information TI234F and Operating
Instructions BA144F.
Measuring system with 4 to 20 mA HART – FEB22(P)
HART is a field-tested industry standard accepted worldwide. In HART technology, the 4 to 20 mA analog
transmission and the digital communication take place simultaneously via the same wire pair. The 4 to 20 mA
analog signal is used for rapid measured value transmission. The digital HART signal allows device data to be
read and written, e.g. for diagnosis and maintenance information.
Measuring system with PROFIBUS PA – FEB24(P)
PROFIBUS PA is an open fieldbus standard. It allows multiple sensors and actuators to be connected, even in
hazardous areas. By means of PROFIBUS PA, energy is supplied to the devices with two-wire technology and
the process information is transmitted digitally from the sensor.
Further information on PROFIBUS PA, such as bus system component requirements, can be found in Operating
Instructions BA034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO
guideline.
Measuring system with FOUNDATION Fieldbus – FEB26
FOUNDATION Fieldbus is an open fieldbus standard. It allows multiple sensors and actuators to be connected,
even in hazardous areas. By means of FOUNDATION Fieldbus, energy is supplied to the devices with two-wire
technology and the process information is transmitted digitally from the sensor.
Further information on FOUNDATION Fieldbus such as bus system component requirements are provided in
Operating Instructions BA013S "FOUNDATION Fieldbus Overview".
Deltapilot S
Endress+Hauser 9
Human interface
Local display (optional) The FHB20 display and operating module is available as an option for the following electronic inserts. → See
also Page 32, feature 70 "Electronic insert":
• 4 to 20 mA HART – FEB22(P)
• PROFIBUS PA – FEB24(P)
• FOUNDATION Fieldbus – FEB26
The parameters are illustrated in a 10 x 10 matrix (→ see Figure, No. p). With the display module, you can
access every parameter directly at the place of measurement. Dry calibration, linearization and operation
enabling and disabling are possible without any further tools.
P01-DB5xxxxx-07-xx-xx-xx-001
User interface of the electronic insert with the FHB20 display and operating module
1 4 1/2-digit display of measured values and parameters 2 Current matrix position3 Bar graph of the measured value4 Operating matrix5 Operating keys6 Signal for reporting an error7 Communication signal, lights up when operating using the handheld terminal or via remote operation
V H+
V H V
H
V H
+
V0
V1
V2
V3
V4
H0 H1 H2 H3 H4
1
2
5
6
7
3
4
Deltapilot S
10 Endress+Hauser
Operating elements Operating keys and elements on the electronic insert
DAT module All the specific data of the measuring cell are saved in the DAT module. When the device is switched on, these
data are read out of the DAT module and into the electronic insert memory.
The DAT module can be ordered as a spare part (order number: 542585-0000). However, the measuring cell
number must be stated when ordering.
Handheld terminals – HART With the handheld terminal Universal-HART-Communicator DXR275 or DXR375, all the parameters can be
configured anywhere along the 4 to 20 mA line via menu operation.
P01-DB5xxxxx-19-xx-xx-xx-006
Electronic insert FEB11(P) – 0.2 to 1.2 mA and electronic insert FEB17(P) – PFM
1 Red LED to indicate a fault2 Slot for the DAT module
P01-DB5xxxxx-19-xx-xx-xx-003
Electronic insert FEB22(P) – 4 to 20 mA HART
1 Operating keys for empty and full calibration, calibration with partially full tanks, lock/unlock operation and reset
2 Green LED flashes when accepting the value for empty and full calibration, during a reset and if operation is locked or unlocked
3 Slot for optional FHB20 display and operating module
4 Slot for the DAT module
P01-DB5xxxxx-19-xx-xx-xx-004
Electronic insert FEB24(P) – PROFIBUS PA
1 DIP switches for bus address2 Red LED to indicate a warning or a fault3 Slot for optional FHB20 display and operating
module 4 Slot for the DAT module
P01-DB5xxxxx-19-xx-xx-xx-005
Electronic insert FEB26 – FOUNDATION Fieldbus
1 DIP switch to lock/unlock operation2 Slot for optional FHB20 display and operating
module 3 Slot for the DAT module4 DIP switch for switching simulation mode on/off
DAT-Modul
RED
+–S1 2 3 4
FEB
xx
1
2FHB 20
GREEN
DAT-Modul
+
+1 2 34…20 mA
–
4–
FEB22(P)
1
324
PA– PA+
Alarm LED
DAT-Modul
FHB 20
1 2 3 4 5 6 7 8
FEB
24(P)
1
3
24 FF– FF+
Alarm LED
DAT-Modul
FHB 20
FEB
26
SIMMOD WPM
1
3
2
4
Deltapilot S
Endress+Hauser 11
FieldCare –
HART, PROFIBUS PA
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can
configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT
standard. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
FieldCare supports the following functions:
• Configuration of transmitters in offline and online operation
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Commuwin II –
HART, PROFIBUS PA
Commuwin II is a graphically supported operating program for intelligent measuring devices with the
communication protocols HART and PROFIBUS PA. The following operating systems are supported:
Win 3.1/3.11, Win 95, Win 98, WinNT4.0 and Win2000.
Commuwin II supports the following functions:
• Configuration of measuring devices in online operation via matrix operation
• Loading and saving device data (upload/download)
• Visualization of measured values and limit values
• Presentation and recording of measured values with a line recorder.
Connection option:
• HART via Commubox FXA191 with the serial interface RS 232 C of a computer or via Commubox FXA195
with the USB interface of a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
Remote operation –
FOUNDATION Fieldbus
An FF configuration program is required to integrate a device with "FOUNDATION Fieldbus signal" into an FF
network or to set the FF-specific parameters. Please contact your local Endress+Hauser Sales Center for more
information.
Input (measured variable)
Measured variable Hydrostatic pressure
Measuring range
Measuring range Measuring limit Recommended
span
Overload Vacuum
resistance
Order code 1
lower (LRL) upper (URL) min./max. US version
psi (bar) psi (bar) psi (bar) psia (barabs) psi (bar) (Euro version)
0 to 1.5 psi (0 to +100 mbar) 0 +1.5 (+0.1) 0.4/1.5 (0.025/0.1) 116 (8) -1.5 (–0.1) FA (BA)
0 to 6 psi (0 to +400 mbar) 0 +6 (+0.4) 0.6/6 (0.04/0.4) 116 (8) -6 (–0.4) FB (BB)
0 to 15 psi (0 to +1200 mbar) 0 +17 (+1.2) 1.7/17 (0.12/1.2) 348 (24) -13 (–0.9) FC (BC)
0 to 60 psi (0 to +4 bar) 0 +60 (+4) 6/60 (0.4/4) 348 (24) -13 (–0.9) FD (BD)
0 to 145 psi (0 to +10 bar) 0 +145 (+10) 14.5/145 (1/10) 580 (40) -13 (–0.9) FE (BE)
-1.5 to +1.5 psi (–100 to +100 mbar) -1.5 (–0.1) +1.5 (+0.1) 0.4/1.5 (0.025/0.1) 116 (8) -1.5 (–0.1) GA (DA)
-6 to +6 psi (–400 to +400 mbar) -6 (–0.4) +6 (+0.4) 0.6/6 (0.04/0.4) 116 (8) -6 (–0.4) GB (DB)
-13 to +15 psi (–900 to +1200 mbar) -13 (–0.9) +1.2 1.7/17 (0.12/1.2) 348 (24) -13 (–0.9) GC (DC)
-13 to +60 psi (–900 to +4000 mbar) -13 (–0.9) +60 (+4) 6/60 (0.4/4) 348 (24) -13 (–0.9) GD (DD)
-13 to +145 psi (–0.9 to +10 bar) -13 (–0.9) +145 (+10) 14.5/145 (1/10) 580 (40) -13 (–0.9) GE (DE)
1) See also Page 32, "Ordering information" chapter, feature 40 "Measuring range"
Deltapilot S
12 Endress+Hauser
Explanation of terms • A turn down of TD = 10:1 is possible with the following electronic inserts:
– 4 to 20 mA HART – FEB22(P)
– PROFIBUS PA – FEB24(P)
– FOUNDATION Fieldbus – FEB26
Turn down is possible via the signal processing units for electronic inserts 0.2 to 1.2 mA analog – FEB11(P)
and PFM – FEB17(P). → See "Function and system design" chapter (page 3), "Measuring device" section.
Explanation of terms: turn down (TD),
set span and span based on zero point
Case 1:• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value
(URV)⏐
Example:• Lower range value (LRV) = 0 mbar
• Upper range value (URV) = 0.6 psi (40 mbar)
• Nominal value (URL) = 6 psi (400 mbar)
Turn down:• Nominal value /⏐upper range value (URV)⏐=
6 psi/0.6 psi (400 mbar/40 mbar)
TD = 10:1
Set span:
• Upper range value (URV) – lower range value (LRV) =
0.6 psi - 0 psi (40 mbar – 0 mbar)
Set span = 0.6 psi (40 mbar)
This span is based on the zero point.
P01-DBxxxxxx-05-xx-xx-xx-001
Example: 6 psi (400 mbar) measuring cell
Case 2:• ⏐Lower range value (LRV)⏐ ≥ ⏐Upper range value
(URV)⏐
Example:• Lower range value (LRV) = -3 psi (–200 mbar)
• Upper range value (URV) = 0 psi (0 bar)
• Nominal value (URL) = 6 psi (400 mbar)
Turn down:• Nominal value /⏐lower range value (LRV)⏐
= 6 psi/3psi (400 mbar/200 mbar)
TD 2:1
Set span:• Upper range value (URV) – lower range value (LRV) =
0 psi - (-3 psi)
0 mbar – (–200 mbar)
Set span = 3 psi (200 mbar)
This span is based on the zero point.
P01-DBxxxxxx-05-xx-xx-xx-002
Example: 6 psi (400 mbar) measuring cell
1 Set span2 Span based on zero point3 Nominal value i upper range limit (URL)4 Nominal measuring range5 Sensor measuring rangeLRL Lower range limitURL Upper range limitLRV Lower range valueURV Upper range value
-6 psi
(-400 mbar)
0 +6 psi
(400 mbar)
0.6 psi
(40 mbar)
LRL LRV URLURV
=1
5
3
2
4
-6 psi
(-400 mbar)+6 psi
(+400 mbar
LRV URLURV
0
LRL
-3 psi
(-200 mbar)
=1
5
3
2
4
Deltapilot S
Endress+Hauser 13
Output
Output signal • 0.2 to 1.2 mA analog signal, 3-wire
• 200 to 1200 Hz PFM signal, 2-wire
– f0 = 200 Hz ± 5 Hz
– 1.5 psi (100 mbar) measuring range: f0 = 200 Hz ± 10 Hz
• 4 to 20 mA with superimposed communication protocol HART, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0), 2-wire
• Digital communication signal FOUNDATION Fieldbus, 2-wire
Signal on alarm • 0.2 to 1.2 mA analog: ≥ 1.5 mA
• PFM ≤ 20 Hz
• 4 to 20 mA HART
Options:
– Min. = 3.6 mA; local display: 0
– Max. = 22 mA (factory setting); local display: 1
– Hold: last measured value is held; local display: 2
• PROFIBUS PA:
– Options configurable in the Analog Input Block for the output signal:
Last Valid Out Value, FSafe Value (factory setting), Status bad
– Options configurable in the Transducer Block for the "Measured value" parameter and the local display:
Min. (local display: –19999), Max. (local display: +19999), Hold: last measured value is held
• FOUNDATION Fieldbus:
– Output signal: last measured value is held; status change from "Uncertain" or "Bad"
– Options configurable in the Transducer Block for the "Measured value" parameter and the local display:
Min. (local display: –19999), Max. (local display: +19999), Hold: last measured value is held
Load
Sensitivity, PFM –FEB17(P)
Damping • 0 to 99 s configurable via the FHB20 display and operating module, PC with operating program or handheld
terminal
• Factory setting: 0 s
0.1 to 1.2 mA analog PFM 4 to 20 mA HART
Max. 25 Ω/core Max. 25 Ω/core
P01-DB5xxxxx-05-xx-xx-xx-002
820
0
3011.5 Ub[V]
Rb[ ]W
Measuring range Resolution Measuring range Resolution
0 to 1.5 psi (0 to 100 mbar) 10 Hz/0.01 psi (10 Hz/mbar) -1.5 to 1.5 psi
(–100 to 100 mbar)
5 Hz/0/01 psi
(5 Hz/mbar)
0 to 6 psi (0 to 400 mbar) 2.5 Hz/0.01 psi (2.5 Hz/mbar) -6 to 6 psi
(–400 to 400 mbar)
1.25 Hz/0.01 psi
(1.25 Hz/mbar)
0 to 17 psi (0 to 1200 mbar) 0.833 Hz/0.01 psi (0.833 Hz/mbar) -13 to 17 psi
(–900 to 1200 mbar)
0.476 Hz/0.01 psi
(0.476 Hz/mbar)
0 to 58 psi (0 to 4000 mbar) 0.25 Hz/0.01 psi (0.25 Hz/mbar) -13 to 58 psi
(–900 to 4000 mbar)
0.204 Hz/psi
(0.204 Hz/mbar)
0 to 145 psi (0 to 10000 mbar) 0.1 Hz/0.01 psi (0.1 Hz/mbar) -13 to 145 psi
(–900 to 10000 mbar)
0.092 Hz/0.01 psi
(0.092 Hz/mbar)
Deltapilot S
14 Endress+Hauser
Power supply
Electrical connection Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Installation or Control Drawings (ZDs). → See also Page 44,
"Installation/Control Drawings" sections.
• Protective circuits against reverse polarity and HF influences are integrated.
• The housing must be grounded for electronic inserts with an integrated overvoltage protection.
• The system is optimally shielded against interference influences if the shielding is connected on both sides.
If you have potential equalization currents in the system, only ground the shielding at one end, preferably at
the Deltapilot S probe.
4 to 20 mA HART electronics – FEB22(P)
P01-DB5xxxxx-04-xx-xx-xx-005
0.2 to 1.2 mA analog electronics – FEB11(P)
The two-wire cable must be connected to terminals 2 (–) and 3 (+).
PFM electronics – FEB17(P)
The two-wire cable must be connected to terminals 2 (–) and 3 (+).
PRODFIBUS PA electronics – FEB24(P)
The two-wire cable must be connected to the "PA+" and "PA–" terminal.
More information on laying out and grounding the network is provided in Operating Instructions BA034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning".
FOUNDATION Fieldbus electronics – FEB26
The two-wire cable must be connected to the "FF+" and "FF–" terminal.
More information on laying out and grounding the network is provided in Operating Instructions BA013S
"FOUNDATION Fieldbus Overview".
+
+1 2 3 4
–
–4…20 mA
DAT
FHB 20
FEB22P
FEB
22(P)
+–
U +–
2 3
Deltapilot S
Endress+Hauser 15
Supply voltage Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Installation or Control Drawings (ZDs).
• All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas. → See
also Page 44, "Installation/Control Drawings" sections.
0.2 to 1.2 mA analog
15 to 20 V DC
PFM
Version for non-hazardous areas: 14 to 16 V DC
4 to 20 mA HART
Version for non-hazardous areas: 11.5 to 30 V DC
PROFIBUS PA
• Version for non-hazardous areas and electronics without overvoltage protection: 9 to 32 V DC
• Version for non-hazardous areas and electronics with overvoltage protection: 9.6 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Current consumption PROFIBUS PA
10 mA ± 1 mA
FOUNDATION Fieldbus
11 mA ± 1 mA
Switch-on current 0.1 to 1.2 mA analog, PFM and 4 to 20 mA HART
100 mA for 30 V, pulse width half-life 20 ms
PROFIBUS PA and FOUNDATION Fieldbus
Switch-on current corresponds to Table 4, IEC 611158-2, Clause 2
Cable entry →See also Page 33, feature 80 "Housing; Cable entry".
Cable specification 0.1 to 1.2 mA analog
• Endress+Hauser recommends using a shielded, three-wire instrument cable with max. 25 Ω per core.
• Terminals for wire cross-section: 16 to 18 AWG (0.08 to 2.5 mm2)
PFM
• Endress+Hauser recommends using a shielded, two-wire instrument cable with max. 25 Ω per core.
• Terminals for wire cross-section: 16 to 18 AWG (0.08 to 2.5 mm2)
4 to 20 mA HART, PROFIBUS PA and FOUNDATION Fieldbus
• Endress+Hauser recommends using a twisted, shielded two-wire cable.
• Terminals for wire cross-section: 16 to 18 AWG (0.08 to 2.5 mm2)
Deltapilot S
16 Endress+Hauser
Residual ripple 4 to 20 mA HART
• Max. ripple (measured at 500 Ω) 47 to 125 kHz: Uss ≤ 200 mV
• Max. noise (measured at 500 Ω) 500 Hz to 10 kHz: Ueff≤ = 2.2 mV
0.1 to 1.2 mA analog
In the range 1 Hz to 100 kHz: max. failsafe value USS ≤ 1 V
Performance characteristics
Reference operating
conditions
• As per DIN 16086
• Calibration temperature: +77°F (+25°C)
Position during calibration
Zero-point increase 90% of measuring range
Long-term stability ±0.1% of URL1 per 6 months
Linearity Linearity as per the limit point method:
– ±0.2% of the set span1
– Optional: ±0.1% of the set span1
Hysteresis ±0.1% of URL1
Influence of ambient
temperature
±0.01%/10 K of URL1
Influence of medium
temperature
±0.1%/10 K of URL1
1 - DB50A, DB50S
2 - DB51A, DB 52A, DB53A
P01-DB5xxxxx-11-xx-xx-xx-009
EN
DR
ES
S+
HA
US
ER
DE
LTAP
ILOT
S
ENDRESS+HAUSERDELTAPILOT S
1
2
1) For an explanation of terms, see Page 12
Deltapilot S
Endress+Hauser 17
Operating conditions (installation)
Installation instructions for
compact version DB50A,
DB50S
• Always install the device under the lowest measuring point.
• Do not install the device at the following positions:
In the filling curtain, in the tank outlet or at a point in the tank that can be reached by pressure pulses from
an agitator.
• The calibration and functional test can be carried out more easily if you mount the device after a shut-off
device.
• Deltapilot S must be included in the insulation for media that can harden when cold. The use of rod or cable
versions is also possible.
Installation instructions for
rod and cable versions DB51A,
DB52A and DB53A
• When mounting the rod and cable versions, make sure that the probe head is located at a point as free as
possible from flow. To protect the probe from impact from lateral movement, mount the probe in a guide
tube (preferably made of plastic) or secure it with a clamping fixture. For devices for hazardous areas, see
Safety Instructions (XAs).
• The length of the extension cable or the probe rod is based on the planned level zero point. The top of the
probe should be at least 2" (5 cm) under this.
• If there are extreme differences in temperature between calibration and operation, the device needs approx.
10 to 14 minutes until measurement is correct.
Housing adapter with
mounting bracket for humid,
damp and difficult-to-access
mounting locations
With the housing adapter and mounting bracket, you have the option of mounting the housing with the
electronic insert away from the measuring point which allows problem-free measurement
• under particularly difficult measuring conditions (in confined or difficult-to-access mounting locations)
• in the event of extreme fluctuations in temperature at the tank wall.
You can operate and control the device quickly and comfortably away from the measuring point by means of
the FHB20 display and operating module or via remote operation. NEMA 6P (IP 68) ingress protection applies
for the housing adapter.
The mounting bracket is suitable for pipe and wall mounting.
P01-DB5xxxxx-11-xx-xx-xx-006
Measuring point with housing adapter and mounting bracket
1 Housing adapter2 Mounting bracket for pipe and wall mounting3 Pipe bend
Note!
• When mounting, observe a bending radius of at least 8" (200 mm).
NEMA 6P (IP 68)
Max. bendingradius 7.9”(200 mm)
1
3
2
Deltapilot S
18 Endress+Hauser
Special measuring cells for
substances with hydrogen
formation
In the case of materials in which hydrogen formation occurs (e.g. digested sludge), hydrogen atoms can diffuse
through the metal diaphragm. This can result in incorrect measurement results.
For such instances, Endress+Hauser offers diaphragms with a gold-rhodium coating.
→ Order through 50 "Linearity, fill fluid", type Z "Additional specification". In addition, for version "Z", quote
the order number 52009331.
Note!
• To reduce the formation of hydrogen, you should refrain from using galvanized assemblies.
Special measuring cell for
acids, alkalis or sea water
For acids, alkalis or sea water, Endress+Hauser offers diaphragms with a gold-platinum coating.
→ Order through 50 "Linearity, fill fluid", type Z "Additional specification". In addition, indicate the order
number 52009332 for Version 'Z'.
Operating conditions (environment)
Ambient temperature range • –4 to +140°F (–20 to +60°C)
• With separate electronics: –4 to +185°F (–20 to +85°C)
For devices for use in hazardous areas, Installation or Control Drawing (ZDs).
Ambient temperature limits –40 to +185°F (–40 to +85°C)
The device can be operated in this temperature range. When commissioning the device, the temperature
cannot go below –4°F (–20°C). The values of the specification such as accuracy can be overshot here.
Storage temperature range –40 to +185°F (–40 to +85°C)
Vibration resistance 10 to 55 Hz, 2 g, as per DIN EN 60068-2-6
Degree of protection • → See Page 33, feature 80 "Housing; Cable entry".
• Housing: NEMA 4X (IP 66)
• Housing adapter: NEMA 6P (IP 68), 1 mH2O for 24 h
Electromagnetic compatibility
(EMC)
Interference emission as per EN 61326, electrical device B; interference immunity as per EN 61326 appendix
A (industrial use) and NAMUR EMC recommendation (NE21).
Overvoltage protection The following electronic inserts are equipped with an surge arrester:
– 0.2 to 1.2 mA analog – FEB11P
– PFM – FEB17P
– 4 to 20 mA HART – FEB22P
– PROFIBUS PA – FEB24P
Protective diodes: gas tube surge arrester 230 V, nominal discharge current 10 kA
Deltapilot S
Endress+Hauser 19
Operating conditions (process)
Process temperature range
For devices for use in hazardous areas, see Installation or Control Drawing (ZDs).
Process temperature limits • DB51A, DB52A and DB53A: –40 to +185°F (–40 to +85°C)
• The DB50S versions can be exposed to +275°F (+135°C) for a brief period (maximum 30 minutes) for
cleaning purposes.
Process pressure limits → For overload and vacuum resistance see Page 11, "Measuring range" section.
Mechanical construction
Dimensions of housing
P01-DB5xxxxx-06-xx-xx-xx-008
Deltapilot S housing versions
1 Aluminum housing2 Polyester housing3 Stainless steel housing
Device Process temperature range
– DB50A
– DB50S
+14 to +212°F (–10 to +100°C)
– DB51A
– DB52A with FEP extension cable
– DB53A with FEP extension cable
+14 to +176°F (–10 to +80°C)
– DB52A with PE extension cable
– DB53A with PE extension cable
+14 to +158°F (–10 to +70°C)
2.68”
(68)
* Dimension applies to units with a cover that includes sight glass. Units with FHB20 local
display are always supplied with a cover with sight glass.
2.68” (68)
3.50” (89) *
2.68”
(68)2.48”
(63)
ø3.38”
(86)
ø3.38”
(86)
ø3.38”
(86)
~2.95”
(75)
~2.95”
(75)
2.99” (76)
2.99” (76) *2.83” (72)
3.46” (88) *
21 3~2.60”
(66)
Deltapilot S
20 Endress+Hauser
Process connections DB50A
(compact version)
Threaded connection ISO 228 and NPT
P01-DB5xxxxx-06-xx-xx-xx-023
DB50A with thread
1 DB50A with thread G 1 1/2 or 1-1/2" NPT without flame barrier2 DB50A with thread G 1 1/2 or 1-1/2" NPT with flame barrier
(flame barrier for use in hazardous areas, Zone 0)
Installation height H, devices with a thread
5.75”
(146)
H
1.84”
(46.7)
0.89”
(22.5)0.89”
(22.5)
H
0.98”
(25)0.98”
(25)
AF 60 AF 60
21
Cover Aluminum housing
inch (mm)
Polyester housing
inch (mm)
Stainless steel
housing, inch (mm)
Without a flame
barrier
Flat 8.08 (205.2) 8.39 (213.2) 8.04 (204.2)
High (with sight glass) 1
1) Devices with the FHB20 display and operating module are always supplied with a high cover or with a cover with a
sight glass.
8.91 (226.2) 8.39 (213.2) 8.67 (220.2)
With a flame barrier Flat 12.0 (304.5) 12.3 (312.5) 8.04 (204.2)
High (with sight glass) 1 12.8 (325.5( 12.3 (312.5) 9.11 (231.5)
Deltapilot S
Endress+Hauser 21
ANSI flanges
P01-DB5xxxxx-06-xx-xx-xx-024
DB50A with flange; surface roughness of the surfaces in contact with the medium, ANSI: Ra = 126 to 248 μin (3.2 to 6.3 μm)
1 DB50A, flange without flame barrier2 DB50A, flange with flame barrier (flame barrier for use in hazardous areas, Zone 0)H For installation height H, see below
ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF
Installation height H, devices with a flange
7.28”
(185)
b
H
kD
fg
2
2.19”
(55.7)
b
H
g
21
ANSI Flange Bolt holes
Version Material 1 Nominal
diameter
Class Diameter Thickness Raised face
diameter
Raised
face
height
Quantity Diameter Hole
circle
Flange
weight 2
D b g f g2 k
lbf./in2 in
(mm)in
(mm)in
(mm)in
(mm)in
(mm)in
(mm)lbs
(kg)
31 AISI 316/
316L
2" 150 6
(152.4)0.75
(19.1)3.62
(91.9)0.06
(1.6)4 0.75
(19.1)4.75
(120.7)6 (2.7)
32 AISI 316/
316L
3" 150 7.5
(190.5)0.94
(23.9)5
(127)0.06
(1.6)4 0.75
(19.1)6
(152.4)12 (5.4)
33 AISI 316/
316L
4" 150 9
(228.6)
0.94
(23.9)6.19
(157.2)0.06
(1.6)8 0.75
(19.1)7.5
(190.5)17 (7.5)
1) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
2) Weight incl. pipe, housing weight, see Page 28
Cover Aluminum housing
in (mm)
Polyester housing
in (mm)
Stainless steel
housing, in (mm)
Without a flame
barrier
Flat 7.91 (201) + flange
thickness b
7.91 (201) + flange
thickness b
7.44 (189) + flange
thickness b
High (with sight glass) 1
1) Devices with the FHB20 display and operating module are always supplied with a high cover or with a cover with a
sight glass.
8.35 (212) + flange
thickness b
7.91 (201) + flange
thickness b
8.07 (205) + flange
thickness b
With a flame barrier Flat 12.3 (312) + flange
thickness b
12.7 (322) + flange
thickness b
12.2 (310) + flange
thickness b
High (with sight glass) 13.1 (333) + flange
thickness b
12.7 (322) + flange
thickness b
12.8 (326) + flange
thickness b
Deltapilot S
22 Endress+Hauser
Process connection, DB50S
(food version)
Universal process adapter
P01-DB5xxxxx-06-xx-xx-xx-021
Process connection DB50S, material: AISI 316L SS/1.4435;Surface roughness of the surfaces in contact with the medium Ra ≤ 32 μin (0.8 μm) as standard. Lower surface roughness on request.
1 Version 00: universal process adapter incl. silicone molded seal2 Version 57: universal process adapter, extension 6 inch incl. silicone molded seal
Installation height H, devices with universal process adapter
Tri-Clamp ISO 2852
P01-DB5xxxxx-06-xx-xx-xx-015
Process connection DB50S, version 50: Tri-Clamp ISO 2852 DN 40 – DN 51 (2")/DIN 32676 DN 50, EHEDG, 3-A; Material: AISI 316L SS/1.4435; surface roughness of surfaces in contact with the medium Ra ≤ 32 μin (0.8 μm) as standard. Lower surface roughness on request.
Installation height H, devices with universal process adapter, Tri-Clamp
ø 1.69”
(43)ø 1.69”
(43)
ø 2.48”
(63)ø 2.48”
(63)
HH
21
Cover Aluminum housing
in (mm)
Polyester housing
in (mm)
Stainless steel
housing, in (mm)
Universal process
adapter
Flat 8.70 (221) 8.70 (221) 8.23 (209)
High (with sight glass) 1
1) Devices with the FHB20 display and operating module are always supplied with a high cover or with a cover with a
sight glass.
9.13 (232) 8.70 (221) 8.86 (225)
Universal process
adapter with 6 inch
extension
Flat 12.5 (318) 12.5 (318) 12.0 (306)
High (with sight glass) 12.9 (329) 12.5 (318) 12.7 (322)
Ø 2.52”
(64)
H
Cover Aluminum housing
in (mm)
Polyester housing
in (mm)
Stainless steel
housing, in (mm)
Without a flame
barrier
Flat 8.70 (221) 8.70 (221) 8.23 (209)
High (with sight glass) 1
1) Devices with the FHB20 display and operating module are always supplied with a high cover or with a cover with a
sight glass.
9.13 (232) 8.70 (221) 8.86 (225)
Deltapilot S
Endress+Hauser 23
Process connections DB51A
(rod/pipe version)
Threaded connection ISO 228 and NPT
P01-DB5xxxxx-06-xx-xx-xx-026
DB51A, rod version with thread
1 DB51A, thread G 1 1/2 or 1-1/2" NPT without flame barrier2 DB51A, thread G 1 1/2 or 1-1/2" NPT with flame barrier
(flame barrier for use in hazardous areas, Zone 0)H For installation height H, see Page 21
ANSI flanges
P01-DB5xxxxx-06-xx-xx-xx-027
DB51A, rod version with flange
1 DB51A, flange without flame barrier2 DB51A, flange with flame barrier
(flame barrier for use in hazardous areas, Zone 0)H For installation height H, see Page 21→ For process connection dimensions, see Page 21.
5.75”
(146)
H
AF 60
ø 1.67”
(42.5)
1.84”
(46.7)
0.89”
(22.5) 0.89”
(22.5)
0.98”
(25)0.98”
(25)
H
ø 0.68”
(17.2)
9.06”
(230)
DB 51:
L = 400 to 4000 mm
DB 51 A:
L = 16 to 160 inch
AF 60
21
7.28”
(185)
b
H
fg 2
2.19”
(55.7)
b
H
gkD
ø 1.67”
(42.5)
ø 0.68”
(17.2)
9.06”
(230)
DB 51:
L = 400 to 4000 mm
DB 51 A:
L = 16 to 160 inch
21
Deltapilot S
24 Endress+Hauser
Dimensions of Deltapilot S
DB52A (cable version)
Threaded connection ISO 228 and NPT
P01-DB5xxxxx-06-xx-xx-xx-028
DB52A, cable version with thread
1 DB52A, thread G 1 1/2 and 1-1/2" NPT without flame barrier2 DB52A, thread G 1 1/2 and 1-1/2" NPT with flame barrier
(flame barrier for use in hazardous areas, Zone 0)3 Clamp for clamping fixtureH For installation height H, see Page 20L Probe length:
Without approvals: 1.6 to 656 ft (0.5 to 200 m)FM IS, CSA IS: 1.6 to 328 ft (0.5 to 100 m)
1.84”
(46.7)
0.89”
(22.5
0.89”
(22.50.98”
(25)
0.98”
(25)
ø 0.41”
(10.4)
ø 1.67”
(42.5)10.1”
(257)
L
H
AF 60 AF 60
5.75”
(146)
H21
3
Deltapilot S
Endress+Hauser 25
ANSI flanges
P01-DB5xxxxx-06-xx-xx-xx-029
DB52A, cable version with flange
1 DB52A, flange without flame barrier2 DB52A, flange with flame barrier
(flame barrier for use in hazardous areas, Zone 0)3 Clamp for clamping fixtureH For installation height H, see Page 21L Probe length:
Without approvals: 1.6 to 656 ft (0.5 to 200 m)FM IS, CSA IS: 1.6 to 328 ft (0.5 to 100 m)
→ For process connection dimensions, see Page 20.
f g2
2.19”
(55.7)
b
H
7.28”
(185)
b
H
g
21
3
D
k
Deltapilot S
26 Endress+Hauser
Dimensions of Deltapilot S
DB53A (suspension clamp and
mounting bracket)
P01-DB5xxxxx-06-xx-xx-xx-007
DB53A with suspension clamp and mounting bracket
1 Pipe bend2 Mounting bracket for pipe and wall mounting3 Suspension clamp (Part Number 52010869)4 Measuring cell tubeL Probe length:
Without approvals: 1.6 to 656 ft (0.5 to 200 m)FM IS, CSA IS: 1.6 to 328 ft (0.5 to 100 m)
Dimension A
Dimension H
~2.60”
(66)~11.0”
(280)
H max. 9.49”
(241)
A max. 11.3”
(286)
ø 3.39”
(86)
~2.95”
(75)
1
2
23
4
ø 1.67”
(42.5)
2"
(50.8)ø 0.24”
(6)
L
ø 0.41”
(10.4)
9.45”
(240)
Cover Aluminum housing Polyester housing Stainless steel housing
Flat 10.4" (265 mm) 10.7" (273 mm) 10.4" (264 mm)
High (with sight glass) 11.3" (286 mm) 10.7" (273 mm) 11.0" (280 mm)
Cover Aluminum housing Polyester housing Stainless steel housing
Flat 8.63" (219 mm) 8.94" (227 mm) 8.58" (218 mm)
High (with sight glass) 9.45" (240 mm) 8.94" (227 mm) 9.21" (234 mm)
Deltapilot S
Endress+Hauser 27
Dimensions of connecting
cable with housing adapter
and mounting bracket
P01-DB5xxxxx-06-xx-xx-xx-013
Connecting cable with housing adapter and mounting bracket, here shown with a DB52A
1 Pipe bend2 Mounting bracket for pipe and wall mounting3 Housing adapter4 Clamp for clamping fixture5 Measuring cell tubeL Probe length
Note!
• For DB50A, DB51A, DB52A, order the housing adapter and the mounting bracket via feature 90 "Additional
option" or subsequently as an accessory. → See also Page 17 and Page 33, "Housing adapter with mounting
bracket" section.
• When using a housing adapter in the FM IS or CSA IS area, the total cable length (connecting cable (L1) +
extension cable (L2)) must not exceed 328 ft (100 m).
2”
ø 0.24”
(6)
7.87”
(218)
L1 max. 65 ft (20 m)
R 7.87”
(200 mm)
³
ø1.57”
(40)
10.1”
(257)
L2
FM IS, CSA IS,
328 ft (
Eex ia:
L1 + L2 100 m)£
1
2
3
4
5
Deltapilot S
28 Endress+Hauser
Weight Housing
Process connection DB50A
Note!
• Total weight of device with threaded connection = weight of housing + weight of process connection DB50A
• Total weight of device with flange connection = weight of housing + weight of process connection DB50A
+ weight of flange (→ see Page 21)
Deltapilot process connections DB50S (food version)
Note!
• Total weight of device = weight of housing + weight of process connection DB50S
Aluminum housing Polyester housing Stainless steel housing
With flat cover, incl.
electronic insert
1.8 lb (0.8 kg) 1.5 lb (0.7 kg) 2 lb (0.9 kg)
With high cover, incl.
electronic insert
3.3 lb (1.15 kg) 1.5 lb (0.7 kg) 2.2 lb (1.0 kg)
Process connection incl. sensor Weight
Threaded connection without a flame barrier incl. sensor 1.8 lb (0.8 kg)
Threaded connection with a flame barrier incl. sensor 3.0 lb (1.35 kg)
Flange connection without a flame barrier incl. sensor, without a flange 1.0 lb (0.45 kg)
Flange connection with a flame barrier incl. sensor, without a flange 2.2 lb (1.0 kg)
Process connection incl. sensor Weight
Tri-Clamp ISO 2852 DN 40 – DN 51 (2")/DIN 32676 DN 50 1.3 lb (0.6 kg)
Universal process adapter 1.5 lb (0.7 kg)
Universal process adapter with 6 inch extended diaphragm seal 3.3 lb (1.5 kg)
Deltapilot S
Endress+Hauser 29
Process connection and pipe DB51A
Note!
• Total weight of device with threaded connection = weight of housing + weight of pipe incl. cable x length
+ weight of process connection DB51A
• Total weight of device with flange connection = weight of housing + weight of pipe incl. cable x length +
weight of process connection DB51A+ weight of flange (→ see Page 21)
Process connection and cable DB52A
Note!
• Total weight of device with threaded connection = weight of housing + weight of cable x length + weight
of process connection DB52A
• Total weight of device with flange connection = weight of housing + weight of cable x length + weight of
process connection DB52A+ weight of flange (→ see Page 21)
Process connection DB53A – securing with suspension clamp and mounting bracket
Note!
• Total weight of device = weight of housing + weight of cable x length + weight of mounting bracket +
weight of pipe bend + weight of suspension clamp + weight of measuring cell tube
Process connection incl. sensor Weight
Pipe incl. cable 1.7 lb/3 ft (0.77 kg/m)
Threaded connection without a flame barrier incl. measuring cell tube and
sensor
3.6 lb (1.65 kg)
Threaded connection with a flame barrier incl. measuring cell tube and sensor 4.8 lb (2.2 kg)
Flange connection without a flame barrier incl. measuring cell tube and sensor,
without a flange
3 lb (1.3 kg)
Flange connection with a flame barrier incl. measuring cell tube and sensor,
without a flange
4 lb (1.85 kg)
Process connection incl. sensor Weight
PE cable 0.3 lb/3 ft (0.13 kg/m)
FEP cable 0.4 lb/3 ft (0.18 kg/m)
Threaded connection without a flame barrier incl. measuring cell tube and
sensor
3.6 lb (1.65 kg)
Threaded connection with a flame barrier incl. measuring cell tube and sensor 4.8 lb (2.2 kg)
Flange connection without a flame barrier incl. measuring cell tube and sensor,
without a flange
3 lb (1.3 kg)
Flange connection with a flame barrier incl. measuring cell tube and sensor,
without a flange
4 lb (1.85 kg)
Process connection incl. sensor Weight
PE cable 0.3 lb/3 ft (0.13 kg/m)
FEP cable 0.4 lb/3 ft (0.18 kg/m)
Mounting bracket 0.4 lb (0.2 kg)
Pipe bend incl. cable entry 1.4 lb (0.65 kg)
Suspension clamp 0.9 lb (0.4 kg)
Measuring cell tube incl. sensor 2.2 (1.0 kg)
Deltapilot S
30 Endress+Hauser
Weight of additional options
Material Housing
• Electronic insert: plastic ABS housing, cast electronic insert
• Process connections: AISI 316L SS (1.4435) or Alloy C4 (2.4610)
• Process diaphragm: Alloy C276 (2.4819)
• Measuring cell: AISI 316L SS (1.4435) or C276 (2.4819)
• Probe tube DB51A: AISI 316L SS (1.4435) or Alloy C4 (2.4610)
• Extension cable DB52A and DB53A: multi-core cable with steel wire braiding, FEP or PE insulation
• Measuring cell tube DB51A, DB52A and DB53A: AISI 316L SS (1.4435) or
Alloy C4 (2.4610)/C22 (2.4602)
• Suspension clamp: AISI 316L SS (1.4404) and fiberglass reinforced polyamide (PA)
• Seals
– For measuring cell sealing, see Ordering information, Page 35
– Universal process adapter: silicone profile packing, suitable for foodstuffs in accordance with BGA XV
FDA 21 CRF 177.2600
– Process connection DRD: PTFE seal
• Protection cap for diaphragm DB51A, DB52A, DB53A: PFA (perflouralkoxy) plastic
• Housing adapter and pipe bend:
– Housing adapter: AISI 316L SS(1.4435) and AISI 316 Ti SS (1.4571)
– Multi-core cable with steel braiding, PE insulation
– Pipe bend:
– AISI 316 SS Ti (1.4571) and AISI 321 (1.4541)
– Cable gland:
– CuZn nickel-plated
– O-ring: NBR
– Sealing insert: TPE-V
– O-ring: EPDM
• Mounting bracket: AISI 304 SS (1.4301)
Accessories Weight
Mounting bracket 0.4 lb (0.2 kg)
Pipe bend incl. cable entry 1.4 lb (0.65 kg)
Housing adapter for DB51A and DB52A 1.9 lb (0.85 kg)
Housing adapter for DB50A and DB50S 1.5 lb (0.7 kg)
Aluminum housing Polyester housing Stainless steel housing
Housing EN AC-44300
(GD-AISi12) with synthetic
coating, blue/gray
Fiberglass reinforced
polyester, blue/gray
(PBT-GF)
AISI 316L SS(1.4404)
Flat cover EN AC-44300 with
synthetic coating, gray
Fiberglass reinforced
polyester, gray (PBT-GF)
AISI 316L SS (1.4404)
High cover with sight glass EN AC-44300 with
synthetic coating, gray
Polycarbonate (PC) AISI 316L SS (1.4404)
Sight glass Glass Polycarbonate (PC) Glass
Seal for housing cover EPDM O-ring Silicone O-ring (VQM) Silicone molded seal (VQM)
Deltapilot S
Endress+Hauser 31
Certificates and approvals
CE mark The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has
been successfully tested by applying the CE mark.
Hazardous approvals All explosion protection data are given in separate documentation which is available upon request. The
Hazardous area documentation is supplied as standard with all devices approved for use in explosion hazardous
areas.
→ See also Page 44, "Installation/Control Drawings" sections.
Standards and guidelines DIN EN 60770 (IEC 60770):
Transmitters for controlling in systems used in industrial process technology
Part 1: Methods for evaluating the operating behavior
DIN 16086:
Electrical pressure measuring devices, pressure sensors, transmitters, pressure measuring devices
Terms, specifications in data sheets
EN 61326:
Electrical equipment for control technology and laboratory application – EMC requirements
Deltapilot S
32 Endress+Hauser
Ordering information
DB50A – compact version
→For continuation of ordering information for DB50A, see the following page.
10 Approval:
A Version for non-hazardous area
O FM IS, Class I, Division 1, 2, Groups A – D
S CSA IS, Class I, Division 1, Groups A – D
T CSA IS, Class I, Division 2, Groups A – D
20 Probe:
C Compact version
30 Process connection:
12 Threaded, ANSI 1-1/2" NPT, AISI 316L SS
31 2" 150 lb ANSI flange RF, AISI 316/316L SS
32 3" 150 Ib ANSI flange RF, AISI 316/316L SS
33 4" 150 lb ANSI flange RF, AISI 316/316L SS
40 Measuring range:
FA 0 to 1.5 psi/1 mH2O/40 inH2O
FB 0 to 6 psi/4 mH2O/160 inH2O
FC 0 to 15 psi/12 mH2O/480 inH2O
FD 0 to 60 psi/40 mH2O/1600 inH2O
FE 0 to 150 psi/100 mH2O/4000 inH2O
GA –1.5 to 1.5 psi/1 mH2O/40 inH2O
GB –6 to 6 psi/4 mH2O/160 inH2O
GC –13 to 15 psi/12 mH2O/480 inH2O
GD –13 to 60 psi/40 mH2O/1600 inH2O
GE –13 to 150 psi/100 mH2O/4000 inH2O
50 Linearity; Fill fluid:
1 < 0.2 % of measuring range; FDA compliant
2 < 0.2 % of measuring range; inert oil
3 < 0.1 % of measuring range; FDA compliant
4 < 0.1 % of measuring range; inert oil
Z See additional specification
60 Measuring sensor seal:
1 Viton
2 EPDM
5 Kalrez
3 Sensor welded
70 Electronics; Output:
Electronic inserts without integrated overvoltage protection
A Without integrated electronic insert (e.g. for ordering spare parts)
B FEB11, 3-wire analog signal
C FEB17, 2-wire PFM signal
E FEB22, 4 to 20 mA, HART
G FEB22, 4 to 20 mA, HART, with FHB20 local display
H FEB24, PROFIBUS PA
K FEB24, PROFIBUS PA, with FHB20 local display
1 FEB26, FOUNDATION Fieldbus
2 FEB26, FOUNDATION Fieldbus, with FHB20 local display
Electronic inserts with integrated overvoltage protection
M FEB11P, 3-wire analog signal
N FEB17P, 2-wire PFM signal
R FEB22P, 4 to 20 mA, HART
T FEB22P, 4 to 20 mA, HART, with FHB20 local display
U FEB24P, PROFIBUS PA
W FEB24P, PROFIBUS PA, with FHB20 local display
DB50A Order code
Deltapilot S
Endress+Hauser 33
DB50A – compact version
(continued)80 Housing; Cable entry:
A0 Without housing (e.g. for ordering spare parts)
P2 Aluminum housing, IP 66, plug M 12x1
P3 AISI 316L housing, IP 66, plug M 12x1
T2 Aluminum housing, IP 66, plug 7/8"
T3 AISI 316L housing, IP 66, plug 7/8"
E1 Polyester housing, NEMA 4X, thread 1/2 NPT
E2 Aluminum housing, NEMA 4X, thread 1/2 NPT
E3 AISI 316L housing, NEMA 4X, thread 1/2 NPT
90 Additional option:
0 Basic version
5 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics
7 …inch connecting cable with housing adapter, NEMA 6P, separate
electronics, max. 800 inch
A Basic version, adjusted measuring range
D 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics, adjusted measuring range
DB50A Complete order code
Deltapilot S
34 Endress+Hauser
DB50S – compact version for
hygienic applications
→For continuation of ordering information for DB50S, see the following page.
10 Approval:
A Version for non-hazardous area
O FM IS, Class I, Division 1 and 2, Groups A – D
S CSA IS, Class I, Division 1, Groups A – D
T CSA IS, Class I, Division 2, Groups A – D
20 Probe:
C Compact version
30 Process connection:
00 Universal process adapter incl. silicone molded seal
57 Universal process adapter, extension 6 inch, incl. silicone molded seal
50 Tri-Clamp ISO 2852 DN 40 – 51 (2") AISI 316L, EHEDG, 3-A
Only in conjunction with an approved process connection
40 Measuring range
FA 0 to 1.5 psi/1 mH2O/40 inH2O
FB 0 to 6 psi/4 mH2O/160 inH2O
FC 0 to 15 psi/12 mH2O/480 inH2O
FD 0 to 60 psi/40 mH2O/1600 inH2O
FE 0 to 150 psi/100 mH2O/4000 inH2O
GA –1.5 to 1.5 psi/1 mH2O/40 inH2O
GB –6 to 6 psi/4 mH2O/160 inH2O
GC –13 to 15 psi/12 mH2O/480 inH2O
GD –13 to 60 psi/40 mH2O/1600 inH2O
GE –13 to 150 psi/100 mH2O/4000 inH2O
74 - 02
®
50 Linearity; Fill fluid:
1 < 0.2 % of measuring range; FDA compliant
3 < 0.1 % of measuring range; FDA compliant
60 Measuring sensor seal:
5 Kalrez
4 Viton (only with universal process adapter)
3 Sensor welded
70 Electronics; Output:
Electronic inserts without integrated overvoltage protection
A Without integrated electronic insert (e.g. for ordering spare parts)
B FEB11, 3-wire analog signal
C FEB17, 2-wire PFM signal
E FEB22, 4 to 20 mA, HART
G FEB22, 4 to 20 mA, HART, with FHB20 local display
H FEB24, PROFIBUS PA
K FEB24, PROFIBUS PA, with FHB20 local display
1 FEB26, FOUNDATION Fieldbus
2 FEB26, FOUNDATION Fieldbus, with FHB20 local display
Electronic inserts with integrated overvoltage protection
M FEB11P, 3-wire analog signal
N FEB17P, 2-wire PFM signal
R FEB22P, 4 to 20 mA, HART
T FEB22P, 4 to 20 mA, HART, with FHB20 local display
U FEB24P, PROFIBUS PA
W FEB24P, PROFIBUS PA, with FHB20 local display
DB50S Order code
Deltapilot S
Endress+Hauser 35
DB50S – compact version for
hygienic applications
(continued)
80 Housing; Cable entry:
A0 Without housing (e.g. for ordering spare parts)
E1 Polyester housing NEMA 4X, thread 1/2" NPT
E2 Aluminum housing NEMA 4X, thread 1/2" NPT
E3 AISI 316L housing, NEMA 4X, thread 1/2" NPT
P2 Aluminum housing, IP 66, plug M12x1
P3 AISI 316L SS housing, IP 66, plug M12x1
T2 Aluminum housing, IP 66, plug 7/8"
T3 AISI 316L SS housing, IP 66, plug 7/8"
90 Additional option:
0 Basic version
5 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics
7 …inch connecting cable with housing adapter, NEMA 6P, separate
electronics, max. 800 inch
A Basic version, adjusted measuring range
D 200 inch connecting cable with housing adapter, NEMA 6P,
separate electronics, adjusted measuring range
DB50S Complete order code
Deltapilot S
36 Endress+Hauser
DB51A – rod version
→For continuation of ordering information for DB51A, see the following page.
10 Approval:
A Version for non-hazardous area
O FM IS, Class I, Division 1, 2, Groups A – D
S CSA IS, Class I, Division 1, Groups A – D
T CSA IS, Class I, Division 2, Groups A – D
20 Probe:
Probe length 16 to 160 inch
G … inch, AISI 316L
30 Process connection:
12 Threaded, ANSI 1-1/2" NPT, AISI 316L SS
31 2" 150 lb ANSI flange RF, AISI 316/316L SS
32 3" 150 Ib ANSI flange RF, AISI 316/316L SS
33 4" 150 lb ANSI flange RF, AISI 316/316L SS
40 Measuring range:
FA 0 to 1.5 psi/1 mH2O/40 inH2O
FB 0 to 6 psi/4 mH2O/160 inH2O
FC 0 to 15 psi/12 mH2O/480 inH2O
FD 0 to 60 psi/40 mH2O/1600 inH2O
FE 0 to 150 psi/100 mH2O/4000 inH2O
GA –1.5 to 1.5 psi/1 mH2O/40 inH2O
GB –6 to 6 psi/4 mH2O/160 inH2O
GC –13 to 15 psi/12 mH2O/480 inH2O
GD –13 to 60 psi/40 mH2O/1600 inH2O
GE –13 to 150 psi/100 mH2O/4000 inH2O
50 Linearity; Fill fluid:
1 < 0.2 % of measuring range; FDA compliant
2 < 0.2 % of measuring range; inert oil
3 < 0.1 % of measuring range; FDA compliant
4 < 0.1 % of measuring range; inert oil
Z Additional specification
60 Measuring sensor seal:
1 Viton
2 EPDM
5 Kalrez
3 Sensor welded
70 Electronics; Output:
Electronic inserts without integrated overvoltage protection
A Without integrated electronic insert (e.g. for ordering spare parts)
B FEB11, 3-wire analog signal
C FEB17, 2-wire PFM signal
E FEB22, 4 to 20 mA, HART
G FEB22, 4 to 20 mA, HART, with FHB20 local display
H FEB24, PROFIBUS PA
K FEB24, PROFIBUS PA, with FHB20 local display
1 FEB26, FOUNDATION Fieldbus
2 FEB26, FOUNDATION Fieldbus, with FHB20 local display
Electronic inserts with integrated overvoltage protection
M FEB11P, 3-wire analog signal
N FEB17P, 2-wire PFM signal
R FEB22P, 4 to 20 mA, HART
T FEB22P, 4 to 20 mA, HART, with FHB20 local display
U FEB24P, PROFIBUS PA
W FEB24P, PROFIBUS PA, with FHB20 local display
DB51A Order code
Deltapilot S
Endress+Hauser 37
DB51A – rod version
(continued)80 Housing; Cable entry:
A0 Without housing (e.g. for ordering spare parts)
E1 Polyester housing NEMA 4X, thread 1/2" NPT
E2 Aluminum housing NEMA 4X, thread 1/2" NPT
E3 AISI 316L SS housing, NEMA 4X, thread 1/2" NPT
P2 Aluminum housing, IP 66, plug M12x1
P3 AISI 316L SShousing, IP 66, plug M12x1
T2 Aluminum housing, IP 66, plug 7/8"
T3 AISI 316L SS housing, IP 66, plug 7/8"
90 Additional option:
0 Basic version
5 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics
7 …inch connecting cable with housing adapter, NEMA 6P, separate
electronics, max. 800 inch
A Basic version, adjusted measuring range
D 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics, adjusted measuring range
DB51A Complete order code
Deltapilot S
38 Endress+Hauser
DB52A – cable version with
process connection
→For continuation of ordering information for DB52A, see the following page.
10 Approval:
A Version for non-hazardous area
O FM IS, Class I, Division 1, 2, Groups A – D
S CSA IS, Class I, Division 1, Groups A – D
T CSA IS, Class I, Division 2, Groups A – D
20 Probe:
P … inch FEP extension cable (probe length: 20 to 7874 inch)
R … inch PE extension cable (probe length: 20 to 7874 inch)
S … inch FEP extension cable for EEx ia, CSA IS, FM IS (probe length: 20 to 3937 inch)
T … inch PE extension cable for EEx ia, CSA IS, FM IS (probe length: 20 to 3937 inch)
30 Process connection:
12 Threaded, ANSI 1-1/2" NPT, AISI 316L SS
31 2" 150 lb ANSI flange RF, AISI 316/316L SS
32 3" 150 Ib ANSI flange RF, AISI 316/316L SS
33 4" 150 lb ANSI flange RF, AISI 316/316L SS
40 Measuring range:
FA 0 to 1.5 psi/1 mH2O/40 inH2O
FB 0 to 6 psi/4 mH2O/160 inH2O
FC 0 to 15 psi/12 mH2O/480 inH2O
FD 0 to 60 psi/40 mH2O/1600 inH2O
FE 0 to 150 psi/100 mH2O/4000 inH2O
GA –1.5 to 1.5 psi/1 mH2O/40 inH2O
GB –6 to 6 psi/4 mH2O/160 inH2O
GC –13 to 15 psi/12 mH2O/480 inH2O
GD –13 to 60 psi/40 mH2O/1600 inH2O
GE –13 to 150 psi/100 mH2O/4000 inH2O
50 Linearity; Fill fluid:
1 < 0.2 % of measuring range; FDA compliant
2 < 0.2 % of measuring range; inert oil
3 < 0.1 % of measuring range; FDA compliant
4 < 0.1 % of measuring range; inert oil
Z Additional specification
60 Measuring sensor seal:
1 Viton
2 EPDM
5 Kalrez
3 Sensor welded
70 Electronics; Output:
Electronic inserts without integrated overvoltage protection
A Without integrated electronic insert (e.g. for ordering spare parts)
B FEB11, 3-wire analog signal
C FEB17, 2-wire PFM signal
E FEB22, 4 to 20 mA, HART
G FEB22, 4 to 20 mA, HART, with FHB20 local display
H FEB24, PROFIBUS PA
K FEB24, PROFIBUS PA, with FHB20 local display
1 FEB26, FOUNDATION Fieldbus
2 FEB26, FOUNDATION Fieldbus, with FHB20 local display
Electronic inserts with integrated overvoltage protection
M FEB11P, 3-wire analog signal
N FEB17P, 2-wire PFM signal
R FEB22P, 4 to 20 mA, HART
T FEB22P, 4 to 20 mA, HART, with FHB20 local display
U FEB24P, PROFIBUS PA
W FEB24P, PROFIBUS PA, with FHB20 local display
DB51A Order code
Deltapilot S
Endress+Hauser 39
DB52A – cable version with
process connection
(continued)
80 Housing; Cable entry:
A0 Without housing (e.g. for ordering spare parts)
E1 Polyester housing NEMA 4X, thread 1/2" NPT
E2 Aluminum housing NEMA 4X, thread 1/2" NPT
E3 AISI 316L SS housing, NEMA 4X, thread 1/2" NPT
P2 Aluminum housing, IP 66, plug M12x1
P3 AISI 316L SS housing, IP 66, plug M12x1
T2 Aluminum housing, IP 66, plug 7/8"
T3 AISI 316L SS housing, IP 66, plug 7/8"
90 Additional option:
0 Basic version
5 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics
7 …inch connecting cable with housing adapter, NEMA 6P, separate
electronics, max. 800 inch
A Basic version, adjusted measuring range
D 200 inch connecting cable with housing adapter, NEMA 6P, separate
electronics, adjusted measuring range
DB52A Complete order code
Deltapilot S
40 Endress+Hauser
DB53A – cable version with
suspension clamp
→For continuation of ordering information for DB53A, see the following page.
10 Approval:
A Version for non-hazardous area
O FM IS, Class I, Division 1, 2, Groups A – D
S CSA IS, Class I, Division 1, Groups A – D
T CSA IS, Class I, Division 2, Groups A – D
20 Probe:
P … inch FEP extension cable (probe length: 20 to 7874 inch)
R … inch PE extension cable (probe length: 20 to 7874 inch)
S … inch FEP extension cable for EEx ia, CSA IS, FM IS (probe length: 20 to 3937 inch)
T … inch PE extension cable for EEx ia, CSA IS, FM IS (probe length: 20 to 3937 inch)
30 Process connection:
70 Cable probe without suspension clamp
71 Suspension clamp AISI 316L SS
7C Flange JIS 10 K 50 A RF, AISI 316L SS
40 Measuring range:
FA 0 to 1.5 psi/1 mH2O/40 inH2O
FB 0 to 6 psi/4 mH2O/160 inH2O
FC 0 to 15 psi/12 mH2O/480 inH2O
FD 0 to 60 psi/40 mH2O/1600 inH2O
FE 0 to 150 psi/100 mH2O/4000 inH2O
50 Linearity; Fill fluid:
1 < 0.2 % of measuring range; FDA compliant
2 < 0.2 % of measuring range; inert oil
3 < 0.1 % of measuring range; FDA compliant
4 < 0.1 % of measuring range; inert oil
Z Additional specification
60 Measuring sensor seal:
1 Viton
2 EPDM
5 Kalrez
3 Sensor welded
70 Electronics; Output:
Electronic inserts without integrated overvoltage protection
A Without integrated electronic insert (e.g. for ordering spare parts)
B FEB11, 3-wire analog signal
C FEB17, 2-wire PFM signal
E FEB22, 4 to 20 mA, HART
G FEB22, 4 to 20 mA, HART, with FHB20 local display
H FEB24, PROFIBUS PA
K FEB24, PROFIBUS PA, with FHB20 local display
1 FEB26, FOUNDATION Fieldbus
2 FEB26, FOUNDATION Fieldbus, with FHB20 local display
Electronic inserts with integrated overvoltage protection
M FEB11P, 3-wire analog signal
N FEB17P, 2-wire PFM signal
R FEB22P, 4 to 20 mA, HART
T FEB22P, 4 to 20 mA, HART, with FHB20 local display
U FEB24P, PROFIBUS PA
W FEB24P, PROFIBUS PA, with FHB20 local display
DB53A Order code
Deltapilot S
Endress+Hauser 41
DB53A – cable version with
suspension clamp
(continued)
80 Housing; Cable entry:
A0 Without housing (e.g. for ordering spare parts)
E1 Polyester housing NEMA 4X, thread 1/2" NPT
E2 Aluminum housing NEMA 4X, thread 1/2" NPT
E3 AISI 316L housing, NEMA 4X, thread 1/2" NPT
P2 Aluminum housing, IP 66, plug M12x1
P3 AISI 316L housing, IP 66, plug M12x1
T2 Aluminum housing, IP 66, plug 7/8"
T3 AISI 316L housing, IP 66, plug 7/8"
90 Additional option:
0 Basic version
A Basic version, adjusted measuring range
DB53A Complete order code
Deltapilot S
42 Endress+Hauser
Accessories
Display and operating module
FHB20
The FHB20 display and operating module is available for local operation for the following electronic inserts.
• HART – FEB22(P)
• PROFIBUS PA – FEB24(P)
• FOUNDATION Fieldbus – FEB26
• Material: POM (polyoxymethylene)
• Order number: 942512-0100
Note!
• The display and operating module only fits under a cover with a sight glass (high cover), see this chapter,
"Cover with sight glass" section. If you order the FHB20 local display by means of the order structure, the
Deltapilot S with a high cover is delivered (→ see Page 32, "Ordering information" chapter, feature 70
"Electronic insert").
• Once you have configured a device with the FHB20 display and operating module, you can remove the
display and use it to configure other devices. Only remove the display from an electronic insert, or attach it
to an electronic insert, in a de-energized state.
• → See also Page 9, "Human interface" chapter.
Cover with sight glass (high
cover)
Cover with sight glass depending on the housing version:
Housing adapter with
mounting bracket for humid,
damp and difficult-to-access
mounting locations
With the housing adapter and mounting bracket, you have the option of mounting the housing with the
electronic insert away from the measuring point. The allows problem-free measurement
• under particularly difficult measuring conditions (in confined or difficult-to-access mounting locations)
• in the event of extreme fluctuations in temperature at the tank wall
NEMA 6P (IP 68) protection applies for the housing adapter. The mounting bracket is suitable for pipe and wall
mounting. → See also page 17, "Housing adapter with mounting bracket" section and Page 30, "Dimensions"
section.
Mounting bracket Mounting bracket for pipe and wall mounting:
• Material: AISI 304 SS (1.4301)
• Order number: 919806-1000
→ See also Page 17, "Housing adapter with mounting bracket" section and Page 29, "Dimensions of
Deltapilot S DB53A "Suspension clamp and mounting bracket" section.
Extension cable shortening kit Extension cable shortening kit for cable between housing adapter and mounting bracket:
• Order number: 935666-0020
Suspension clamp Suspension clamp for Deltapilot S DB53A:
• Material: stainless steel AISI 316L SS (1.4435), clamping jaw: fiberglass reinforced PA (polyamide)
• Order number: 52010869
→ See also Page 26, "Dimensions of Deltapilot S DB53A" "Suspension clamp and mounting bracket" section.
For aluminum housing For polyester housing For stainless steel
housing
Material EN AC-44200 with
synthetic coating, gray,
sight glass: glass
Cover (transparent):
polycarbonate (PC)
AISI 316L SS (1.4404),
sight glass: glass
Order number 942828-0010 942828-0001 942828-0100
Order code Version
HDB50-A 16 ft (5 m) PE cable with mounting bracket AISI 304 (1.4301)
HDB50-B … m PE cable (3 to 100 ft / 1 to 30 m) with mounting bracket AISI 304 (1.4301)
HDB50-C 16 ft (5 m) FEP cable with mounting bracket AISI 304 (1.4301)
HDB50-D … m FEP cable (3 to 100 ft / 1 to 30 m) with mounting bracket AISI 304 (1.4301)
Deltapilot S
Endress+Hauser 43
Protective cover
P01-DB5xxxxx-00-xx-xx-xx-001
Protection cover
For the aluminum and polyester housing, Endress+Hauser offers protective covers with two cable entries.
• Max. ambient temperature: +158°F (+70°C)
• Material: polyamide (PA)
• Order number for protection cover for devices with a flat cover: 942262-0000
• Order number for protection cover for devices with a high cover: 942262-0001
Welding neck adapter for
universal process adapter
P01-PMC45xxx-06-xx-xx-xx-000
Welding neck adapter for flush mounting a Deltapilot S DB50S with a universal process adapter
Adapter You can use the following adapter to mount a DB50L with a universal process connection in a Clamp
connection:
4.33”
(110)
6.1”
(155)
5.4”
(137)
ø 1.73”
(44)
1.56”
(39.5)
Rd 52 x 1/6
D
Diameter D Material Order number
2.56" (65 mm) AISI 316L SS 214880-0002
2.56" (65 mm) AISI 316L SS with inspection certificate EN 10204 3.1 material 52010174
3.35" (85 mm) AISI 316L SS 52006262
3.35" (85 mm) AISI 316L SS with inspection certificate EN 10204 3.1 material 52010173
Version Order number
Tri-Clamp ISO 2852 DN 40-51 (2")/DIN 32676 DN 50, AISI 304 SS (1.4301) 917650-0002
Deltapilot S
44 Endress+Hauser
Documentation
Field of Activities • Pressure measurement, powerful measuring devices for process pressure, differential pressure, level and
flow: FA004P/00/en
Technical Information on
switching unit
• Level measurement, silometer FMC4120: TI077F/00/en
• Level measurement, Prolevel FMB662: TI234F/00/en
Operating Instructions • Deltapilot S HART: BA152F/00/en
• Deltapilot S PROFIBUS PA: BA164F/00/en
• Deltapilot S FOUNDATION Fieldbus: BA232F/00/en
• PROFIBUS DP/PA, Guidelines for planning and commissioning: BA034S/04/en
• FOUNDATION Fieldbus Overview, Installation and Commissioning Guidelines: BA013S/04/en
Installation Drawings/
Control DrawingsCertificate/explosion
protection
Device Electronics Documentation
CSA IS Class I, Division 1,
Groups A-D
DB50A, DB50S,
DB51A, DB 52A,
DB53A
– PFM
– 4 to 20 mA HART
– PROFIBUS PA
– FOUNDATION Fieldbus
– Order number: 016586-0000
– Order number: 960351-1034
– ZD036F + ZD021F
– ZD068F + ZD021F
FM IS Class I, Division 1, 2
Groups A-D
DB50A, DB50S,
DB51A, DB52A,
DB53A
– PFM
– 4 to 20 mA HART
– PROFIBUS PA
– FOUNDATION Fieldbus
– Order number: 017054-0000
– Order number: 017054-0000
– ZD024F + ZD021F
– ZD067F + ZD021F
United States
Endress+Hauser, Inc.
2350 Endress Place
Greenwood, IN 46143
Tel. 317-535-7138
Sales 888-ENDRESS
Service 800-642-8737
fax 317-535-8498
www.us.endress.com
TI257P/24/ae/02.07
© 2007 Endress+Hauser
Canada
Endress+Hauser Canada
1075 Sutton Drive
Burlington, ON L7L 5Z8
Tel. 905-681-9292
800-668-3199
Fax 905-681-9444
www.ca.endress.com
Mexico
Endress+Hauser, México, S.A. de C.V.
Av. Gustavo Baz No. 43
Fracc. Bosques de Echegaray
Naucalpan de Juárez, C.P. 53310, Estado
de México
México
Tel: (52) 55-5371-1110
Fax (52) 55-5371-1128