T TECHNICAL E ENERGY A AUDIT R REPORT FOR GRADY MUNICIPAL SCHOOLS PRESENTED BY HONEYWELL BUILDING SOLUTIONS NOVEMBER 29, 2010 AMENDED 2/4/11

TECHNICAL ENERGY AUDIT REPORT · 2012. 3. 3. · 2) Clarify interaction of energy conservation measures; 3) Clarify economizers. HEATING FUEL TYPE Grady Municipal Schools uses propane

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • TTEECCHHNNIICCAALL EENNEERRGGYY AAUUDDIITT RREEPPOORRTT

    FFOORR

    GGRRAADDYY MMUUNNIICCIIPPAALL SSCCHHOOOOLLSS

    PRESENTED BY

    HONEYWELL BUILDING SOLUTIONS NOVEMBER 29, 2010

    AMENDED 2/4/11

  • The Energy, Minerals and Natural Resources Department provides resource protection and renewable energy resource development services to the public and other state agencies.

    Energy Conservation and Management Division

    1220 South St. Francis Drive ▪ Santa Fe, New Mexico 87505 Phone: (505) 476-3310 ▪ Fax (505) 476-3322 ▪ www.CleanEnergyNM.org

    Susana Martinez Governor John H. Bemis Cabinet Secretary Designate Brett F. Woods, Ph.D. Deputy Cabinet Secretary

    Fernando Martinez, Division Director Energy Conservation and Management Division

    Addendum No. 1 Prepared March 25, 2011

    to the Grady Municipal Schools Audit Prepared February 4, 2011 by Honeywell

    PURPOSE OF ADDENDUM

    1) Clarify heating fuel type; 2) Clarify interaction of energy conservation measures; 3) Clarify economizers.

    HEATING FUEL TYPE Grady Municipal Schools uses propane for its heating fuel, as stated on page 6 of the energy audit report, and the baseline energy consumption used in analyzing energy conservation measures is based on the facility’s actual propane consumption. In Section B, “Annual Energy Use,” on page 10, the table and pie chart consumption data given is for propane, not “Natural Gas” as labeled. Propane consumption data used to establish the baseline is provided in the Appendix on pages A-7 through A-9. INTERACTION OF ENERGY CONSERVATION MEASURES A few of the interactions mentioned on page 16 in Section E, “Energy Conservation Measures,” will not be a factor in the proposed project. In the final analysis, energy management systems, economizers, heating/cooling equipment replacements, and variable frequency drives were not recommended to be implemented because they were not found to be cost-effective. These interactions do not apply. ECONOMIZERS Economizer operation recommendations in the Appendix on page A-3, items 7 and 8, do not apply. There are no existing economizer operations, because the air intake dampers of the heating/cooling systems are fixed in place and do not modulate. In the final analysis, new economizer operations to modulate the dampers were not recommended to be implemented because they were not found to be cost-effective.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 1

    Honeywell International Inc. Honeywell Building Solutions (HBS) 9201 San Mateo Blvd. NE, MS A6 Albuquerque, NM 87113 Phone: (505) 828-5260 Fax: (505 828-5263

    February 1, 2011 New Mexico Energy, Minerals, and Natural Resources Department (EMNRD) 1220 S. St. Francis Drive Santa Fe, NM 87505 Ref: Regional Education Center #6 Energy Audits

    This statement is to certify that the energy audits were conducted in accordance with the requirements of Task 4 of EMNRD contract No. 10-521-A073212-0302 with REC #6 and that the data presented is accurate and complete to the best of Honeywell’s knowledge. If you have any questions, please contact Chris Lauer at (505) 270-5640. Sincerely,

    Rory Moran, PE Honeywell International Inc. Honeywell Building Solutions

  • Grady Municipal Schools TEA Report

    02/04/11 Page 2

    Table of Contents

    Report Tab Contents Pages 1. Overview A. Executive Summary 3

    B. Contact Information 4 C. Baseline Summary 6 D. Initial Savings and Investment Summary 7

    2. Grady Main Buildings Preschool Elementary Middle High VoAg Gym (2)

    A. General Building and HVAC Descriptions 8 B. Annual Energy Use 10 C. Energy Benchmarking 13 D. Energy Consumption by End-use 14 E. Energy Conservation Measures 15 F. Measures Considered But Not Recommended 35 G. Conclusion and Recommendations 48

    3. Appendix

    A. Sample Energy Policy A-1 B Raw Energy Bill Inputs A-6 C Lighting Maintenance Formulae A-10 D Equipment Life Expectancy A-14

  • Grady Municipal Schools TEA Report

    02/04/11 Page 3

    1. OVERVIEW

    A. EXECUTIVE SUMMARY This document presents a Technical Energy Audit prepared by Honeywell Building Solutions (HBS) for energy conservation measures at Grady High School, Grady Middle Vocational Agricultural School, Grady Elementary School and Grady Preschool. The energy audits are performed under Tasks #3 and #4 of the State of New Mexico Energy, Minerals, and Natural Resources Department (EMNDR) Contract No. 10-521-A073212-0302 for Regional Education Center #6. The purpose of this contract is to identify energy efficiency measures that can be implemented under the Energy Efficiency and Renewable Energy Bonding Act, NMSA 1978, 6-21D-1 et seq. also known as the Clean Energy Revenue Bond (CERB). For the preparation of this Technical Energy Audit, HBS conducted site surveys and reviewed design, operational, and utility information provided by Grady Municipal School’s staff to determine energy use and possible energy conservation opportunities. The following energy conservation measures (ECM’s) were evaluated for each building:

    1 Energy policy2 Energy management system3 Lighting retrofit with occupancy controls4 Economizer retrofit to RTU's5 Building weatherization6 Computer power management7 Destratification fans in gyms8 Insulate domestic hot water tanks9 Submetering for buildings10 Variable frequency drives on RTUs11 Vending machine setback12 Building insulation13 Window replacement

    Table 1: Energy Conservation Measures

    See individual sections for detailed description of energy conservation measures. This Technical Energy Audit is based on Honeywell’s best practices and procedures established through years of energy auditing and performance contracting experience. The audit and recommended energy conservation measures represent an accurate and comprehensive report and forms a solid basis for making decisions on implementing the measures included in this report.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 4

    B. CONTACT INFORMATION:

    1. For the District a. Ted Trice, Superintendent

    Grady Municipal Schools P.O. Box 71 Grady, NM 88120 Tel 575-357-2192 Fax 575-357-2000

    2. For the Region

    a. Patti Harrelson, Director Regional Education Center #6 1500 South Avenue K Station 9 Portales, NM 88130 Tel 575-562-4457 Fax 575-562-4460 Cell 575-607-6990

    b. Jack Burch Regional Education Center #6 1500 South Avenue K Station 9 Portales, NM 88130 Tel 575-562-4455 Fax 575-562-4460

    3. For Honeywell

    a. Account Management 1) Chris Lauer, Account Representative

    Honeywell Building Solutions 9201 San Mateo Blvd NE Albuquerque, NM 87113 Tel 505-828-5260 Cell 505-270-5640 E-Mail [email protected]

    2) David Balderrama, Account Representative Honeywell Building Solutions 9201 San Mateo Blvd NE Albuquerque, NM 87113 Tel 505-839-9526 Cell 505-263-2516 E-Mail [email protected]

    mailto:[email protected]�mailto:[email protected]

  • Grady Municipal Schools TEA Report

    02/04/11 Page 5

    3) Ken Swanson, Sales Manager 3509 3518 Duranzo Avenue El Paso, TX 79905 Tel 915-351-3001 Cell 915-449-1373 E-Mail [email protected]

    b. Engineering 1) Rory Moran, P.E., CEM, Performance Contracting Engineer

    Honeywell Building Solutions 4412 Sweetbriar Court Concord, CA 94521 Tel 415-639-0620 Cell 650-245-9221 E-Mail [email protected]

    2) William Korol, Senior Energy Analyst Honeywell Building Solutions 2925 E. Patrick Lane, Suite F Las Vegas, NV 89120 Tel 702-895-6234 Cell 702-290-2038 E-Mail [email protected]

    3) Rick Otta, P.E., CEM, LEED 2.0 AP, Performance Contracting Engineer Principal Honeywell Building Solutions 2700 Richards Road, Suite 102 Bellevue, WA 98005 Tel 425-698-6096 Cell 206-409-6823 E-Mail [email protected]

    mailto:[email protected]�mailto:[email protected]�mailto:[email protected]�mailto:[email protected]

  • Grady Municipal Schools TEA Report

    02/04/11 Page 6

    C. BASELINE SUMMARY The basis for any energy audit is the utility usage and cost for a known period of time. Below is a summary of the annual energy usage for the buildings in the District. Two years of utilities bills were analyzed, a base year chosen, and the data normalized. The fossil fuel used at Grady Municipal Schools is propane supplied by Conway Oil and the electricity is supplied by Farmers Electric Cooperative. There is one main electric meter (and several smaller electric meters) and one source for propane, therefore the campus is analyzed as a whole.

    Area Electric Electric Fossil Total Total Total Cost perSquare Energy Demand Fuel Electrical Fossil Energy Square

    Building Acronym Feet kWh kW MMBTU Cost Fuel Cost Cost Foot Notes

    Grady Main Building GMB 40,045 168,853 0 837 $14,070 $15,609 $29,679 $0.74 APreK/Elem/Middle/High

    Grady VoAg, Gyms Building GVB 45,415 191,495 0 950 $15,956 $17,704 $33,660 $0.74 A

    85,460 360,348 0 1,787 $30,026 $33,313 $63,339 $0.74

    Table 2: Summary of Annual Energy Use and Costs by Fuel Type for Base Year (May 2009 - April 2010)

    TOTALS

    Notes:A. There is a single propane service with one main and two small electric meters for the entire campus. Usage is allocated based on building square footage.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 7

    D. INITIAL SAVINGS AND INVESTMENT SUMMARY Each school building was examined in detail for energy savings potential, energy reductions were calculated, cost to implement the measures determined, and operations and maintenance effects examined. The simple payback period (SPBP) is the total investment divided by the first year savings. The SPBP may be used to rate the cost effectiveness of performing energy conservation measures. The table below summarizes all the recommended energy conservation measures. See the individual building report for details.

    Table 3: Total Energy Cost Savings and Investment Summary

    ECM ID ECM Name

    Propane $

    Savings

    Propane MMBtu

    Savings

    Electric $

    Savings

    Electric kWh

    Savings

    O&M Other

    Savings

    Total $

    Savings RebatesTotal

    InvestmentSPBP Years

    GMS Grady Municipal Schools $3,639 195 $12,129 146,134 $459 $16,227 $0 $147,870 9.1 (Preschool, Elem, Middle, High, VoAg)

    Totals: $3,639 195 $12,129 146,134 $459 $16,227 $0 $147,870 9.1

    Base Year Cost

    Base Year

    Usage

    Total $ Savings

    Total Savings

    Percent Reduce

    Electric Utility $30,026 360,348 $12,129 146,134 40.4%

    Propane Utility $33,313 1,787 $3,639 195 10.9%

    Total Combined Utility $63,339 $15,768 24.9%

    Annual Savings and Investment Summary for Recommended ProjectGrady Municipal School

  • Grady Municipal Schools TEA Report

    02/04/11 Page 8

    2. GRADY MAIN BUILDINGS

    Gra

    dy M

    ain

    Bui

    ldin

    g

    SECTION CONTENTS:

    • GENERAL BUILDING & HVAC SYSTEM DESCRIPTIONS

    • ANNUAL ENERGY USE

    • ENERGY BENCHMARKING

    • ENERGY CONSUMPTION BY END-USE

    • ENERGY CONSERVATION MEASURES

    • MEASURES CONSIDERED BUT NOT RECOMMENDED

    • CONCLUSIONS AND RECOMMENDATIONS

    A. GENERAL BUILDING AND HVAC DESCRIPTIONS Building: The Grady Middle/High/Elementary Schools are a complex of interconnected buildings with an areas of approximately 40,045 square feet. The buildings are constructed with stone and concrete masonry units (CMU), stucco exterior walls, steel roof deck and slab-on-grade foundation The High School was originally constructed in 1934, with additions in 1994 and 1997. The building complex is presently used as a middle/high school/elementary & district administration facility. The Grady VoAg/Gymnasium is a complex of interconnected buildings with an area of approximately 45,415 square feet. The buildings are constructed with concrete masonry units (CMU) and wood framed walls, stucco exterior walls, steel roof deck and slab-on-grade foundation The Old Gym was originally constructed in 1937, with additions in 1960, 1973 and 1994. The building complex is presently used as a VoAg school, cafeteria, and gymnasium. Heating/Cooling/Ventilation System: The building is heated and cooled primarily by rooftop air handling units with indirect fired gas furnaces and direct expansion cooling. The units have a fixed 25% outside air opening. The units are controlled by programmable thermostats that cycle the fans on a call for either heating or cooling. During unoccupied periods the units cycle to maintain unoccupied setpoints.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 9

    Lighting System: The predominant interior lighting fixture is a three lamp 32 watt four foot T8 fluorescent with electronic ballasts, along with a good number of T12 fluorescent fixtures with magnetic ballasts. Exterior lighting fixtures are predominantly high intensity discharge Metal Halide, but there are a number of other HID fixtures, including high pressure sodium, as well as a couple of mercury vapor lamps. Light levels seemed overall adequate, but with very low levels in certain places. Classroom light levels ranged from 45-60 foot-candles, however the Old Gym only had light levels of below 20 foot-candles with the old style metal halide fixtures. Most of the existing exit signs are LED except for a few incandescent signs. There were no automatic lighting controls identified. Building Envelope: The buildings are constructed with stone and concrete masonry units (CMU), stucco exterior walls, steel roof deck and slab-on-grade. Most windows are double glazed with aluminum frames. The weatherstripping and caulking is deteriorated and in need of replacement.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 10

    B. ANNUAL ENERGY USE Below is annual energy usage per utility broken out by enduse.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 11

    Energy Usage Base Year Data: Energy usage printouts from the school’s database were provided by Grady Municipal Schools for two years, starting with July 2008 and going through June 2010. The propane delivery spreadsheet was missing the months of July 2008, August 2008 and September 2008. The total propane delivered from July 2009 to June 2010 was 28,047 gallons. From October 2008 to June 2009 only 5,325 gallons were recorded in the spreadsheet. Because of the large difference between these two years the base year of May 2009 to April 2010 was selected with a total of 19,564 gallons delivered in this timeframe. With bulk delivery fuels it is difficult to determine any one year’s usage since tank levels at the beginning and ending of each year are unknown. At least three full years of propane utility data would have helped resolve this issue. The base year utility bills were normalized. This is the most recent period for which utility data was available. Total propane delivered for the year has been distributed throughout all twelve months based on a base load for non-space heating uses and the amount of heating degree days per month. The base year provides a basis for performing energy end use analyses a) to understand how energy is used in a given building and b) to identify savings opportunities during the early stages of the energy audit. Projected energy unit savings are compared to base year energy consumption to ensure that the projected savings are reasonable. “Whole building” energy models were developed for the sites included in the Technical Energy Audit using eQUEST version 3.64, build 7130. The eQUEST program uses “typical meteorological year” (TMY2) weather files rather than weather data files for a particular year. One of the challenges of energy bill analysis can be sharing of meters across multiple buildings. The entire campus is fed from one large propane tank. The PreK Building is fed from the same electric meters that feed the Main Building. All buildings were modeled in eQuest Version 3.64 and the results of this modeling allowed for the allocation of energy usage within the buildings. The annual energy use index (EUI) for Grady Municipal Schools is:

    35,295 BTU/Square Foot. The annual energy cost per square foot for Grady Municipal Schools is:

    $ 0.74/Square Foot.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 12

    Customer Name: Grady Municipal SchoolsFacility Name: Main (All schools)Base Year: May'09 - Apr'10Conditioned Area: 85,460 square feetBuilding Occupants: 90 people

    May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr Annual

    Weather DataDays in Month 30 31 31 30 31 30 31 31 28 31 30 31 365Heating Degree Days 90 0 0 0 11 210 490 776 735 515 426 277 3530Cooling Degree Days 120 376 333 296 92 22 0 0 0 0 0 22 1261

    Electrical DatakW-hrs Used 35,140 24,574 24,107 29,932 42,108 29,546 26,311 29,044 29,230 36,038 29,405 24,914 360,348Daily Ave kW-hrs 1,171 793 778 998 1,358 985 849 937 1,044 1,163 980 804 987$/kW-hr $0.081 $0.088 $0.081 $0.084 $0.081 $0.080 $0.081 $0.084 $0.080 $0.082 $0.087 $0.094 $0.083Daily kW-hr Cost $95 $70 $63 $83 $110 $79 $69 $78 $84 $95 $85 $76 $82Total kW-hr Cost $2,841 $2,173 $1,944 $2,503 $3,408 $2,374 $2,138 $2,430 $2,352 $2,950 $2,565 $2,348 $30,026

    kW Used 0 0 0 0 0 0 0 0 0 0 0 0 0$/kW $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00Total Demand Cost $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Load Factor 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 0%

    Total Electric Cost $2,841 $2,173 $1,944 $2,503 $3,408 $2,374 $2,138 $2,430 $2,352 $2,950 $2,565 $2,348 $30,026Daily Electric Cost $95 $70 $63 $83 $110 $79 $69 $78 $84 $95 $85 $76 $82Cost/Square Foot $0.03 $0.03 $0.02 $0.03 $0.04 $0.03 $0.03 $0.03 $0.03 $0.03 $0.03 $0.03 $0.35

    Fossil Fuel DataGallons Total 582 120 120 120 176 1198 2636 4104 3894 2764 2307 1542 19,564MMBTUs Total 58 11 11 11 16 109 241 375 356 252 211 141 1,787Daily Ave MMBTUs 2 0 0 0 1 4 8 12 13 8 7 5 5$/MMBTU $17.03 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64 $18.64Daily MMBTU Cost $33 $7 $7 $7 $10 $68 $145 $225 $237 $152 $131 $85 $91Total MMBTU Cost $991 $204 $204 $204 $300 $2,040 $4,488 $6,988 $6,630 $4,707 $3,929 $2,626 $33,312Cost/Square Foot $0.01 $0.00 $0.00 $0.00 $0.00 $0.02 $0.05 $0.08 $0.08 $0.06 $0.05 $0.03 $0.390

    Energy Usage IndicesElec BTU/Sq Ft/Day 47 32 31 40 54 39 34 37 42 46 39 32 39kW-hrs/Sq Ft/Month 0.4 0.3 0.3 0.4 0.5 0.3 0.3 0.3 0.3 0.4 0.3 0.3 0.4Proj kW-hrs/Sq Ft/Yr 4.9 3.5 3.4 4.2 5.9 4.1 3.7 4.1 4.1 5.1 4.1 3.5 4.2

    Fossil Fuel BTU/Sq Ft/Day 23 4 4 4 6 43 91 141 149 95 82 53 57Fossil Fuel BTU/Sq Ft/Mnth 681 128 128 128 189 1,280 2,817 4,386 4,161 2,954 2,466 1,648 1,742Proj FF Btu/Sq Ft/Year 8,173 1,539 1,539 1,539 2,263 15,366 33,802 52,633 49,934 35,448 29,588 19,777 20,908

    Total BTUs/Sq Ft/Day 69 36 35 44 60 82 125 179 190 142 121 85 97Energy Cost/Sq Ft $0.04 $0.03 $0.03 $0.03 $0.04 $0.05 $0.08 $0.11 $0.11 $0.09 $0.08 $0.06 $0.74EUI in BTUs/Sq Ft 2,084 1,109 1,091 1,323 1,870 2,460 3,867 5,546 5,328 4,393 3,640 2,643 35,295Year to Date Usage 2,084 3,193 4,284 5,607 7,477 9,937 13,805 19,350 24,678 29,071 32,711 35,354

    Tot Energy & Demand Cost $3,832 $2,377 $2,148 $2,708 $3,708 $4,414 $6,627 $9,419 $8,982 $7,657 $6,493 $4,974 $63,339Year to Date Cost $3,832 $6,209 $8,358 $11,065 $14,774 $19,188 $25,814 $35,233 $44,215 $51,872 $58,365 $63,339

    Base Year Utility Report for Grady Municipal Schools

  • Grady Municipal Schools TEA Report

    02/04/11 Page 13

    C. ENERGY BENCHMARKING Energy Benchmarking: Each building was entered in the Environmental Protection Agency’s Portfolio Manager Software to generate a benchmark for the building compared to other K-12 schools throughout the United States. The facility report shows a low energy intensity rating for this building and gives it an Energy Performance Rating of 88, i.e. this building’s energy usage is lower than 88% of the existing schools in the survey database.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 14

    D. ENERGY CONSUMPTION BY END-USE Energy Consumption by End-use: The building was modeled in eQuest Version 3.64 Building Simulation software to allocate energy usage in the building and to provide a baseline for energy savings calculations for certain energy conservation measures. The eQuest model predicted electrical energy usage 1.6% below measured use and propane usage 0.8% below measured use.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 15

    E. ENERGY CONSERVATION MEASURES SCOPE OF WORK, COST AND SAVINGS SUMMARY:

    Below is a list of recommended Energy Conservation Measures. These are measures that have a simple payback of fifteen years or less and have an expected life expectancy that is greater than the simple payback period. Each measure is discussed in detail with estimated energy savings and costs given.

    ECM ID ECM Name

    Equip Live

    Years

    Propane $

    Savings

    Propane MMBtu

    Savings

    Electric $

    Savings

    Electric kWh

    Savings

    O&M Other

    Savings

    Total $

    Savings RebatesTotal

    InvestmentSPBP Years

    GMS1 Energy policy NA $0 0 $0 0 $0 $0 $0 $0

    GMS3 Lighting retrofit with occupancy 16 $0 0 $11,588 139,619 $459 $12,047 $0 $121,112 10.1

    GMS5 Building weatherization 15 $2,119 114 $53 637 $0 $2,171 $0 $7,500 3.5GMS6 Computer power management 5 $0 0 $307 3,702 $0 $307 $0 $650 2.1

    GMS8 Insulate domestic hot water tanks 20 $136 7 $0 0 $0 $136 $0 $270 2.0

    GMS11 Vending machine setback 15 $0 0 $71 850 $0 $71 $0 $400 5.7GMS12 Building insulation 20 $1,384 74 $110 1,325 $0 $1,494 $0 $17,939 12.0

    Totals: $3,639 195 $12,129 146,134 $459 $16,227 $0 $147,870 9.1

    Base Year Cost

    Base Year

    Usage

    Total $ Savings

    Total Savings

    Percent Reduce

    Electric Utility $30,026 360,348 $12,129 146,134 40.4%

    Propane Utility $33,313 1,787 $3,639 195 10.9%

    Total Combined Utility $63,339 $15,768 24.9%

    Annual Savings and Investment Summary for Recommended ProjectGrady Municipal School

    Commercial rebates are not currently offered by either the electric utility or the propane supplier. Energy Conservation Measure Interaction Measure interaction effects have not been calculated since the intent of this study is to identify and prioritize energy savings opportunities. If multiple energy conservation measures are implemented total energy savings could be slightly reduced due to interactive effects depending on which combination of measures are implemented. Implementing lighting retrofits will reduce the heat generated by the lighting system. During the heating season the reduced heat produced by the lights will need to be replaced by the building heating system. During the cooling season the reduced heat produced by the lights will result in

  • Grady Municipal Schools TEA Report

    02/04/11 Page 16

    reduced energy needed to cool the space. The added heating costs will be roughly negated by the reduced cooling costs. Building weatherization/insulation/windows energy conservation measures will reduce both heating and cooling costs. These measures will reduce the savings attributed to the heating/cooling of the building since it will reduce the base load for the building. The energy conservation measures affected by weatherization/insulation/windows include the energy management system, economizer retrofits, as well as the heating/cooling equipment replacements. Variable frequency drives on supply fan motors will reduce the fan speed depending on the building load thereby reducing the heat generated by the fan. This results in reduced cooling costs during cooling season and increased heating costs during heating season. These load changes are negligible because of the size of the fan motors. Computer power management and indoor vending machine setback will have an effect on the building heating/cooling loads similar to the lighting retrofits, only on a much smaller scale. Insulating domestic hot water tanks will not influence the other loads in the building because most of the water heaters are located in areas that are not actively heated or cooled.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 17

    LMS1. Energy Policy:

    Existing Conditions: The Grady Municipal School District works to manage its energy use. Most thermostats were set up correctly and teachers seem conscientious about turning off lights when leaving the classroom. The school currently has an energy policy that is not highly publicized or well known by members of the school community.

    Proposed Upgrades: An active, dynamic Energy Policy is fundamental in order for the District to (a.) reduce the impact utility costs have on the budget, (b.) ensure that energy is used efficiently, and to (c.) maintain a reliable supply of energy to meet the functional needs of the District.

    The school district should re-examine their current energy policy and review it to make sure it embraces all aspects of energy conservation. The update of this policy is the joint responsibility of board members, administrators, teachers, students and support personnel and its success is based on cooperation at all levels.

    The energy policy should also be highly conspicuous and known to all stakeholders. Copies of the policy and energy conserving posters should be posted in public areas. The policy should be available on the district’s web site. A sample Energy Policy is included in the appendix. The Grady Municipal School District may wish to use this sample as a guide to modify/updating their existing policy. Savings Calculations: No additional savings were calculated for implementing an Energy Policy. Implementation Costs: An Energy Policy is developed and maintained by all stakeholders. The primary cost of implementation is the labor involved to review the policy and to make modifications to it. This work should be accomplished during the normal course of doing business and should not be an additional expense.

    Operations and Maintenance: This measure is primarily an operations and maintenance activity. It is the summation of many small activities done by everyone involved in the school district.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 18

    LMS3. Lighting Upgrades:

    Existing Conditions: A lighting survey has been performed to evaluate the need for lighting efficiency upgrades.

    Proposed Upgrades: The following table details the existing and proposed lighting system in this building. The Burn Hour Code references the table following this table and indicates the run hours for each lighting area. The Lighting Code indicates the type of new lighting. If the Lighting Code starts with an N then this indicates a new fixture and includes new ballasts. If the Lighting Code starts with an R then this indicates a retrofit fixture and includes new ballasts for fixtures using ballasts. The type of ballast is indicated by the last set of digits of the Lighting Code – LP for Low Power, SP for Standard Power, and HP for High Power. Recommend the following lighting upgrades and occupancy sensors for the school:

    Burn Hour Lighting Code Exist Exist New NewRoom Type Code (Upgraded System) Lighting Description (Existing System) Lighting Description (Upgraded System) Qty Watts Qty WattsOFFICE MAIN OO RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 6 86 6 47OFFICE BUSINESS O RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 4 86 4 47OFFICE O-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 4 86 4 47OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0OFFICE O-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 4 86 4 47OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0OFFICE O-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 6 86 6 47OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42SERVER S RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47CONF ROOM CF-EXST-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 6 86 6 47CONFROOM CF-EXST-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0RESOURCE CENTER RC-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 21 86 21 47RESOURCE CENTER RC-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 2 0 2 0LOUNGE OO-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0LOUNGE OO-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 3 72 3 42CLASSROOM C-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F40T12 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 144 9 64CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47W RESTROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 5 58 5 42W RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0JANITOR CLOSET JC ZZ DD EXISTING (2) 20 WATT COMPACT FLUOR DON'T DO: NOT INCLUDED IN PROJECT 1 40 1 40M RESTROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 3 58 3 42M RESTROOM RR-OS R 2L(V)[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42M RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F40T12 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 144 9 64CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F40T12 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 144 9 64CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0HALLWAY H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 5 72 5 42HALLWAY H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 5 58 5 42HALLWAY H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 2 0 2 0HALLWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4FOYER Z R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM C-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0HALLWAY H-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 5 86 5 47HALLWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4W RESTROOM RR-EXST-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 5 111 5 64M RESTROOM RR-EXST-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 5 111 5 64HALLWAY H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0

  • Grady Municipal Schools TEA Report

    02/04/11 Page 19

    Burn Hour Lighting Code Exist Exist New NewRoom Type Code (Upgraded System) Lighting Description (Existing System) Lighting Description (Upgraded System) Qty Watts Qty WattsCLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0W RESTROOM RR-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 72 2 42MRESTROOM RR-EXST-OS RF 2LR[T8-2-32-IS-HP] EXISTING (4) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 6 111 6 64CLASSROOM C-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM C-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0HALLWAY NURSE H-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 10 86 10 47HALLWAY NURSE Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4HALLWAY H-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 11 86 11 47HALLWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4HALLWAY OFFICE H-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 3 86 3 47HALLWAY OFFICE Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4HALLWAY OFFICE H-OS R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 72 2 41HALLWAY OFFICE H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 3 0 3 0BREEZEWAY H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 11 72 11 42BREEZEWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4BREEZEWAY H-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0BREEZEWAY Z N LEDBB EXISTING COMPACT FLUORESCENT EX NEW: LED EXIT SIGN 1 12 1 4MRESTROOM RR CF 18CFL EXISTING 75 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 2 75 2 18MRESTROOM RR ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0W RESTROOM RR CF 18CFL EXISTING 75 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 2 75 2 18W RESTROOM RR ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0KITCHEN K R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 18 58 18 41KITCHEN K R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42PANTRY K R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42COOLERS K-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0COOLERS K-OS R 2L(W)[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42CAFÉ Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4CAFÉ L R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 18 58 18 41CAFÉ L CF 4-18CFL EXISTING (4) 100 WATT INCANDESCENT COMPACT FLUORESCENT LAMP: SCREW- 2 400 2 72CAFÉ L CF 23CFL EXISTING 100 WATT INCANDESCENT, LUCOMPACT FLUORESCENT LAMP: SCREW- 4 100 4 23CAFÉ VEND ZZZ OS SODAMISER EXISTING VENDING MACHINE SODA NEW: OCCUPANCY SENSOR 1 460 1 460CAFÉ VEND ZZZ OS SNACKMISER EXISTING VENDING MACHINE SNACK NEW: OCCUPANCY SENSOR 1 120 1 120CAFÉ L ZZZ OS CIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 2 0 2 0WEST GYM HALL H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0WEST GYM HALL H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 7 72 7 42WEST GYM HALL H-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0WEST GYM HALL H-OS R 2L(W)[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0OFFICE O-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0OFFICE O-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42GYM LOBBY S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 9 72 9 42M RESTROOM RR-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 72 2 42W RESTROOM RR-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 3 72 3 42GYMNASIUM Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 3 4 3 4GYMNASIUM G-OS N 3T5HO-GYM EXISTING 500 WATT INCANDESCENT LUNEW: T5HO LUMINAIRE 6 500 6 159GYMNASIUM G-OS N 5T5HO-GYM EXISTING 400 WATT METAL HALIDE LUMNEW: T5HO LUMINAIRE 44 460 44 264GYMNASIUM G-OS ZZZ CIR-GYM NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 6 0 6 0WEIGHT ROOM Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4OFFICE O-OS R 3L[T8-3-32-IS-LP] EXISTING (3) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 115 1 63RESTROOM RR R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42RESTROOM RR CF 13CFL EXISTING 60 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 1 60 1 13M LOCKER ROOM GL-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42M LOCKER ROOM GL-EXST-OS R 2L(W)[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 5 58 5 42M RESTROOM GL R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42W LOCKER ROOM GL-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42W LOCKER ROOM GL-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 7 58 7 42MECH ROOM M R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42STORAGE Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4H2O HEATER M-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42THERAPY G-EXST-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 18 86 18 47THERAPY G-EXST-OS ZZ DD EXISTING (2) 26 WATT PLUG IN COMPAC DON'T DO: NOT INCLUDED IN PROJECT 1 54 1 54THERAPY G-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42M LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42M LOCKER ROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0M LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42M LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42M LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42V LOCKER ROOM GL-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42

  • Grady Municipal Schools TEA Report

    02/04/11 Page 20

    Burn Hour Lighting Code Exist Exist New NewRoom Type Code (Upgraded System) Lighting Description (Existing System) Lighting Description (Upgraded System) Qty Watts Qty WattsLOCKER HALLWAY H-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 6 72 6 42LOCKER HALLWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4LOCKER HALLWAY H-EXST-OS R 2L(W)[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 72 2 42OLD WEIGHT ROOM S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 8 58 8 42OLD WEIGHT ROOM Z N LEDBB EXISTING COMPACT FLUORESCENT EX NEW: LED EXIT SIGN 1 12 1 4W LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42W LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42W LOCKER ROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0W LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42W LOCKER ROOM RR-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42V LOCKER ROOM GL-EXST-OS R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 41V LOCKER ROOM GL-EXST-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42STORAGE S R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 41SMALL GYM Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4SMALL GYM G-OS ZZZ CIR-GYM NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 4 0 4 0SMALL GYM G-OS N 5T5HO-GYM EXISTING 400 WATT METAL HALIDE LUMNEW: T5HO LUMINAIRE 30 460 30 264STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42HALL A R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42STAGE A R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 12 58 12 42STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42JANITOR CLOSET OO-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0JANITOR CLOSET OO-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 3 58 3 42CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 19 86 19 47STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42STORAGE S RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47H20 HTR M CF 23CFL EXISTING 100 WATT INCANDESCENT LUCOMPACT FLUORESCENT LAMP: SCREW- 1 100 1 23CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 9 86 9 47STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 58 1 42CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47STORAGE S R 1L[T8-1-32-IS-LP] EXISTING (1) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 43 1 22CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47STORAGE S RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47SHOP CHS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 40 58 40 42CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47STORAGE S R 3L[T8-3-32-IS-LP] EXISTING (3) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 3 86 3 63M RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0M RESTROOM RR-OS CF 13CFL EXISTING 60 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 1 60 1 13M RESTROOM RR-OS R 4L[T8-4-32-IS-LP] EXISTING (4) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 111 2 82W RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0W RESTROOM RR-OS R 4L[T8-4-32-IS-LP] EXISTING (4) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 111 2 82BACK HALL H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 5 58 5 42BACK HALL H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0BACK HALL Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4KITCHEN HALL H-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 6 58 6 42KITCHEN HALL H-OS ZZZ OS CUS-HALL NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 2 0 2 0KITCHEN HALL Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 2 4 2 4JANITOR CLOSET JC CF 13CFL EXISTING 60 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 1 60 1 13CLASSROOM CHS-OS R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 12 58 12 41HALLWAY H R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 1 72 1 42HALLWAY Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4HALLWAY H R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 72 2 41HALLWAY H R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F40T12 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 7 72 7 42CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS ZZZ OS CDT NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0CLASSROOM CHS-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 12 86 12 47CLASSROOM Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4CLASSROOM CHS-OS R 2LT[T8-4-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 6 58 6 41HALL H RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47HALL Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 1 4 1 4M RESTROOM RR-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47M RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0M RESTROOM RR-OS ZZ DD EXISTING 18 WATT COMPACT FLUORES DON'T DO: NOT INCLUDED IN PROJECT 1 36 1 36W RESTROOM RR-OS RF 2LR[T8-2-32-IS-SP] EXISTING (3) LAMP F32T8 LUMINAIRE REFLECTOR KIT: T8 LAMP AND ELECTRON 2 86 2 47W RESTROOM RR-OS ZZZ OS WUS NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0W RESTROOM RR-OS ZZ DD EXISTING 18 WATT COMPACT FLUORES DON'T DO: NOT INCLUDED IN PROJECT 1 36 1 36GARAGE Z ZZ DD EXISTING LED LUMINAIRE DON'T DO: NOT INCLUDED IN PROJECT 3 4 3 4GARAGE CHS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 24 58 24 42RESTROOM RR R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42OFFICE O-OS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 2 58 2 42BALCONY S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 8 58 8 42STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42STORAGE S R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 8 58 8 42

  • Grady Municipal Schools TEA Report

    02/04/11 Page 21

    Burn Hour Lighting Code Exist Exist New NewRoom Type Code (Upgraded System) Lighting Description (Existing System) Lighting Description (Upgraded System) Qty Watts Qty WattsWOOD SHOP CHS R 2L[T8-2-32-IS-LP] EXISTING (2) LAMP F32T8 LUMINAIRE RETROFIT: RETROFIT WITH 4' T8 LAMPS A 4 58 4 42EXTERIOR X IND N 100FL EXISTING 250 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 5 295 5 111EXTERIOR X R 50MH-PS-KIT EXISTING 70 WATT HIGH PRESSURE SO RETROFIT: RETROFIT WITH 50 WATT PUL 2 91 2 71EXTERIOR X IND N 150FL EXISTING 400 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 1 460 1 165EXTERIOR X IND N 100WPK EXISTING 400 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 1 460 1 111EXTERIOR X ZZ DD EXISTING 20 WATT COMPACT FLUORES DON'T DO: NOT INCLUDED IN PROJECT 1 20 1 20EXTERIOR X IND N 70COBRA EXISTING 175 WATT MERCURY VAPOR LNEW: INDUCTION LUMINAIRE 1 220 1 78EXTERIOR X IND N 70WPK EXISTING 150 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 6 185 6 78EXTERIOR X R 50MH-PS-KIT EXISTING 70 WATT HIGH PRESSURE SO RETROFIT: RETROFIT WITH 50 WATT PUL 5 91 5 71EXTERIOR X R 50MH-PS-KIT EXISTING 70 WATT HIGH PRESSURE SO RETROFIT: RETROFIT WITH 50 WATT PUL 3 91 3 71EXTERIOR X ZZ DD EXISTING (2) 26 WATT PLUG IN COMPAC DON'T DO: NOT INCLUDED IN PROJECT 1 54 1 54EXTERIOR X R 50MH-PS-KIT EXISTING 70 WATT METAL HALIDE LUM RETROFIT: RETROFIT WITH 50 WATT PUL 1 91 1 71EXTERIOR X CF 13CFL EXISTING 60 WATT INCANDESCENT LUMCOMPACT FLUORESCENT LAMP: SCREW- 1 60 1 13EXTERIOR X CF 2-18CFL-PAR EXISTING (2) 75 WATT INCANDESCENT LCOMPACT FLUORESCENT LAMP: SCREW- 3 150 3 36EXTERIOR X IND N 40WPK EXISTING 100 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 4 129 4 44EXTERIOR X IND N 150FL EXISTING 400 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 1 460 1 165EXTERIOR X IND N 40WPK EXISTING 100 WATT METAL HALIDE LUMNEW: INDUCTION LUMINAIRE 2 129 2 44EXTERIOR X R 50MH-PS-KIT EXISTING 70 WATT HIGH PRESSURE SO RETROFIT: RETROFIT WITH 50 WATT PUL 5 91 5 71EXTERIOR X IND N 70COBRA EXISTING 175 WATT MERCURY VAPOR LNEW: INDUCTION LUMINAIRE 2 220 2 78OFFICE O-OS ZZZ OS WIR NO EXISTING LIGHTING CONTROL NEW: OCCUPANCY SENSOR 1 0 1 0 The hours of operation were figured for the existing lighting system per the following table:

    Existing Hours

    Weekly Weekly Weekly Weekly Total Total Total Total DiversityNumber Number Winter Winter Summer Summer Winter Winter Summer Summer Total Factor

    Burn Hour Area Winter Summer Peak Off Peak Peak Off Peak Peak Off Peak Peak Off Peak Annual (DF)Code Description Months Months Hours Hours Hours Hours Hours Hours Hours Hours Hours for kWA Auditorium 8 4 30 10 30 10 1044 348 522 174 2088 0.95C Classrooms 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95CES Classrooms-Elementary School 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95CES-OS Classrooms-Elem, add new sensor 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95C-EXST-OS Classrooms-Elem, existing sensor 8 2.5 24 7 24 7 835.2 243.6 261 76.125 1415.9 0.9CF Conf. Room 8 4 30 10 30 10 1044 348 522 174 2088 0.95CF-EXST-OS Conf. Room, existing sensor 8 4 24 7 24 7 835.2 243.6 417.6 121.8 1618.2 0.9CF-OS Conf. Room, add new sensor 8 4 30 10 30 10 1044 348 522 174 2088 0.95CHS Classrooms-High School 8 2.5 40 10 40 10 1392 348 435 108.75 2283.8 0.95CHS-OS Classrooms-HS, add new sensor 8 2.5 40 10 40 10 1392 348 435 108.75 2283.8 0.95CMS Classrooms-Middle School 8 2.5 35 10 35 10 1218 348 380.625 108.75 2055.4 0.95CMS-OS Classrooms-MS, add new sensor 8 2.5 35 10 35 10 1218 348 380.625 108.75 2055.4 0.95C-OS Classrooms- add new sensor 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95G Gyms 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95GL Gym lockers 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95GL-EXST-OS Gym lockers, existing sensor 8 4 27.5 22 27.5 22 957 765.6 478.5 382.8 2583.9 0.9GL-OS Gym lockers, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95G-OS Gyms, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95H Halls & common areas 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95H-EXST-OS Hallways, existing sensor 8 4 27.5 22 27.5 22 957 765.6 478.5 382.8 2583.9 0.85H-OS Hallways, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95JC Janitor Closet 8 4 5 5 5 5 174 174 87 87 522 0.2JC-OS Janitor Closet, add new sensor 8 4 5 5 5 5 174 174 87 87 522 0.2K Kitchen 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95K-EXST-OS Kitchen , existing sensor 8 2.5 25 7.5 25 7.5 870 261 271.875 81.5625 1484.4 0.9K-OS Kitchen, add new sensor 8 2.5 30 10 30 10 1044 348 326.25 108.75 1827 0.95L Cafeteria 8 4 30 10 30 10 1044 348 522 174 2088 0.95L-EXST-OS Cafeteria, existing sensor 8 4 20 6 20 6 696 208.8 348 104.4 1357.2 0.85L-OS Cafeteria, add new sensor 8 4 30 10 30 10 1044 348 522 174 2088 0.95M Maintenance Areas 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95M-EXST-OS Maitenance Areas, existing sensor 8 4 32 27.2 32 27.2 1114 946.56 556.8 473.28 3090.2 0.9M-OS Maintenance Areas, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95O Offices 8 4 40 20 40 20 1392 696 696 348 3132 0.95O-EXST-OS Offices, existing sensor 8 4 32 16 32 16 1114 556.8 556.8 278.4 2505.6 0.9OO Open Office 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95OO-EXST-OS Open Offices, existing sensor 8 4 30 25.5 30 25.5 1044 887.4 522 443.7 2897.1 0.9OO-OS Open Offices, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95O-OS Offices, add new sensor 8 4 40 20 40 20 1392 696 696 348 3132 0.95P Pool 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95RC Library 8 4 30 10 30 10 1044 348 522 174 2088 0.95RC-OS Library, add new sensor 8 4 30 10 30 10 1044 348 522 174 2088 0.95RR Restrooms 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95RR-EXST-OS Restrooms, existing sensor 8 4 13 9 13 9 452.4 313.2 226.2 156.6 1148.4 0.85RR-OS Restrooms, add new sensor 8 4 40 34 40 34 1392 1183.2 696 591.6 3862.8 0.95RR-P Restrooms, private 8 4 5 5 5 5 174 174 87 87 522 0.2RR-P-EXST-ORestrooms, private, existing sensor 8 4 4 4 4 4 139.2 139.2 69.6 69.6 417.6 0.2RR-P-OS Restrooms, private, add new sensor 8 4 5 5 5 5 174 174 87 87 522 0.2S Storage Areas 8 4 5 5 5 5 174 174 87 87 522 0.2S-EXST-OS Storage Areas, existing sensor 8 4 4 4 4 4 139.2 139.2 69.6 69.6 417.6 0.2S-OS Storage Areas, add new sensor 8 4 5 5 5 5 174 174 87 87 522 0.2X Outside Areas 8 4 0 84 0 84 0 2923.2 0 1461.6 4384.8 0.05Z 24 Hour Areas 8 4 40 128 40 128 1390 4451.9 693.5 2224.7 8759.6 1Z-OS 24 Hour Areas, add new sensor 8 4 40 128 40 128 1390 4451.9 693.5 2224.7 8759.6 1

  • Grady Municipal Schools TEA Report

    02/04/11 Page 22

    The proposed hours of operation were then figured with the addition of occupancy sensors per the following table:

    Upgraded Hours

    Total Total Total Total Diversity% Hour % Diversity Number Number Winter Winter Summer Summer Total Factor

    Area Reduction/ Factor (DF) Winter Summer Peak Off Peak Peak Off Peak Annual (DF)Description Sensors Reduct / Sensors Months Months Hours Hours Hours Hours Hours for kWAuditorium 8 4 1044 348 522 174 2088 0.95Classrooms 8 2.5 1044 348 326.25 108.75 1827 0.95Classrooms-Elementary School 8 2.5 1044 348 326.25 108.75 1827 0.95Classrooms-Elem, add new sensor 0.33 0.1 8 2.5 699.48 233.16 218.5875 72.8625 1224.09 0.85Classrooms-Elem, existing sensor 8 2.5 835.2 243.6 261 76.125 1415.925 0.9Conf. Room 8 4 1044 348 522 174 2088 0.95Conf. Room, existing sensor 8 4 835.2 243.6 417.6 121.8 1618.2 0.9Conf. Room, add new sensor 0.33 0.1 8 4 699.48 233.16 349.74 116.58 1398.96 0.85Classrooms-High School 8 2.5 1392 348 435 108.75 2283.75 0.95Classrooms-HS, add new sensor 0.33 0.1 8 2.5 932.64 233.16 291.45 72.8625 1530.113 0.85Classrooms-Middle School 8 2.5 1218 348 380.625 108.75 2055.375 0.95Classrooms-MS, add new sensor 0.33 0.1 8 2.5 816.06 233.16 255.0188 72.8625 1377.101 0.85Classrooms- add new sensor 0.2 0.05 8 2.5 835.2 278.4 261 87 1461.6 0.9Gyms 8 4 1392 1183.2 696 591.6 3862.8 0.95Gym lockers 8 4 1392 1183.2 696 591.6 3862.8 0.95Gym lockers, existing sensor 8 4 957 765.6 478.5 382.8 2583.9 0.9Gym lockers, add new sensor 0.5 0.1 8 4 696 591.6 348 295.8 1931.4 0.85Gyms, add new sensor 0.33 0.1 8 4 932.64 792.744 466.32 396.372 2588.076 0.85Halls & common areas 8 4 1392 1183.2 696 591.6 3862.8 0.95Hallways, existing sensor 8 4 957 765.6 478.5 382.8 2583.9 0.85Hallways, add new sensor 0.33 0.1 8 4 932.64 792.744 466.32 396.372 2588.076 0.85Janitor Closet 8 4 174 174 87 87 522 0.2Janitor Closet, add new sensor 0.2 8 4 139.2 139.2 69.6 69.6 417.6 0.2Kitchen 8 2.5 1044 348 326.25 108.75 1827 0.95Kitchen , existing sensor 8 2.5 870 261 271.875 81.5625 1484.438 0.9Kitchen, add new sensor 0.2 0.05 8 2.5 835.2 278.4 261 87 1461.6 0.9Cafeteria 8 4 1044 348 522 174 2088 0.95Cafeteria, existing sensor 8 4 696 208.8 348 104.4 1357.2 0.85Cafeteria, add new sensor 0.33 0.1 8 4 699.48 233.16 349.74 116.58 1398.96 0.85Maintenance Areas 8 4 1392 1183.2 696 591.6 3862.8 0.95Maitenance Areas, existing sensor 8 4 1113.6 946.56 556.8 473.28 3090.24 0.9Maintenance Areas, add new sensor 0.2 0.05 8 4 1113.6 946.56 556.8 473.28 3090.24 0.9Offices 8 4 1392 696 696 348 3132 0.95Offices, existing sensor 8 4 1113.6 556.8 556.8 278.4 2505.6 0.9Open Office 8 4 1392 1183.2 696 591.6 3862.8 0.95Open Offices, existing sensor 8 4 1044 887.4 522 443.7 2897.1 0.9Open Offices, add new sensor 0.25 0.05 8 4 1044 887.4 522 443.7 2897.1 0.9Offices, add new sensor 0.2 0.05 8 4 1113.6 556.8 556.8 278.4 2505.6 0.9Pool 8 4 1392 1183.2 696 591.6 3862.8 0.95Library 8 4 1044 348 522 174 2088 0.95Library, add new sensor 0.2 0.05 8 4 835.2 278.4 417.6 139.2 1670.4 0.9Restrooms 8 4 1392 1183.2 696 591.6 3862.8 0.95Restrooms, existing sensor 8 4 452.4 313.2 226.2 156.6 1148.4 0.85Restrooms, add new sensor 0.75 0.2 8 4 348 295.8 174 147.9 965.7 0.75Restrooms, private 8 4 174 174 87 87 522 0.2Restrooms, private, existing sensor 8 4 139.2 139.2 69.6 69.6 417.6 0.2Restrooms, private, add new sensor 0.2 8 4 139.2 139.2 69.6 69.6 417.6 0.2Storage Areas 8 4 174 174 87 87 522 0.2Storage Areas, existing sensor 8 4 139.2 139.2 69.6 69.6 417.6 0.2Storage Areas, add new sensor 0.2 8 4 139.2 139.2 69.6 69.6 417.6 0.2Outside Areas 8 4 0 2923.2 0 1461.6 4384.8 0.0524 Hour Areas 8 4 1389.5 4451.9 693.5 2224.7 8759.6 124 Hour Areas, add new sensor 0.33 0.1 8 4 930.97 2982.77 464.645 1490.549 5868.932 0.9

  • Grady Municipal Schools TEA Report

    02/04/11 Page 23

    Savings Calculations:

    The following formulae were used to calculate the energy saving from the lighting upgrades:

    1) Kilowatts (kW) Existing kW = pre-retrofit unit kW Proposed kW = post-retrofit unit kW Total Existing kW = Existing kW * Existing Qty * Global Diversity Total Proposed kW = Proposed kW * Proposed Qty * Global Diversity Total Saved kW = Total Existing kW – Total Proposed kW Total kW Dollars Saved = Total Saved kW * kW rate 2) Kilowatt-hours (kWh) Total Existing kWh = Total Existing kW * Hours of Operation Total Proposed kWh = Total Proposed kW * Hours of Operation Total Saved kWh = Total Existing kWh – Total Proposed kWh Total kWh Dollars Saved = Total Saved kWh * kWh rate 3) Total Dollars Saved Total Dollars Saved = Total kW Dollars Saved + Total kWh Dollars Saved + O&M Saved The life expectancy of the lighting upgrades depends on the type of fixture/bulb installed and the annual hours of usage of the lights. Global Diversity and Diversity Factor (DF) are the probability that a particular lighting fixture will be on at the time of the facility’s peak load. Savings Calculations Summary: The existing and proposed lighting system run hours from the hour tables above were reduced to 73% of the table values to match the lighting load with the utility bills: GRADY MAIN BUILDINGS

    Upgraded Quantity of Luminaires 930 kW Used (Existing System) with DF 82.97 kW used (Existing System) without DF 100.11 kW Used (Upgraded System) with DF 43.25 kW used (Upgraded System) without DF 56.53 kW Saved 39.72 kW Saved - Max Potential 43.59 kWh Used (Existing System) 217,223.46 kWh Used (Upgraded System) 106,156.32 kWh Saved 111,067.14 Occupancy Sensor Savings kWh (Included in totals) 33,621.21 Occupancy Sensor Savings (Included in totals) 2,790.56 Savings (Energy) 11,588.39 HVAC Penalty or Savings 0.00 Maint. Savings (Material & Labor) 458.62 Savings (Maint, HVAC, Energy) 12,047.01

    Turnkey Installation Cost Estimate $121,111.71Simple Payback (years) 10.1

  • Grady Municipal Schools TEA Report

    02/04/11 Page 24

    Below is a chart with typical life expectancy for different lighting components:

    REFERENCE SOURCEEQUIPMENT USE CA CPUC WA ELCCA

    (YEARS) 2010 2005(Curr)Lighting

    Electronic ballasts 16 16 12Compact fluorescent 16 16 12Exit sign 16 16Fixtures HID 16 16 20Fixtures T8 16 16 20Lighting controls 16 16Occupancy sensors 10 10Time clock 10 8 10

    Implementation Costs: The cost to remove the existing lighting system and install the new lighting system was figured using actual cost for the new bulbs, ballasts and fixtures and standard labor factors for their installation. Costs were figured by a lighting contractor who specializes in lighting upgrades. Operations and Maintenance: Operations and maintenance savings for the lighting retrofit are based on the difference between the existing lamp and ballast replacement rate and lamp and ballast replacement rate for the proposed upgrade. The first step is to calculate the Existing Average Annual Lamp Burn Outs (EAALB). This is the percentage of annual percentage of burned out lamps expected each year. It is calculated by dividing the annual hours of operation by the manufacturers stated lamp life, then multiplying by the number of lamps/ballast in each fixture.

    Next, the Existing Average Annual Lamp Burn Outs percentage is multiplied by the Existing Estimated Lamp Purchase Cost (EELPC), giving us the Existing Estimated Lamp Replacement Cost (EELRC). This cost is assumed based on historical data.

    The total annual cost of replacement lamps per fixture which is then multiplied by the Total Number of Existing Fixtures (TNEF) resulting in the Existing Total Lamp Replacement Material Cost (ETLRMC).

  • Grady Municipal Schools TEA Report

    02/04/11 Page 25

    The above equations are then repeated for the proposed lighting system. The difference between the Existing Total Lamp Replacement Material Cost and the Proposed Total Lamp Replacement Material Cost will yield the Total Lamp Material Savings (TLMS).

    Similar calculations are repeated for ballasts. Labor costs are calculated for replacing the number of units defined by the above equations. It is assumed lamps will be changed by custodial staff and ballasts will be replaced by an electrician. The total lamp labor savings and total ballast labor savings are then added together to yield the Total Labor Savings (TLS).

    Finally, the Total Labor Savings is added to the Total Material Savings to yield the Total Maintenance Savings.

    Total Labor Savings = Total Labor Savings + Total Material Savings See Appendix for full set of equations.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 26

    GMS5. Building Weatherization: Existing Conditions: Localized damage of the stucco exterior walls (staining and cracks) should be repaired. There is extra risk of hidden damage in such areas caused by previous or present leaks that should be sealed.

    Damaged Stucco

    Caulk all windows and install weatherstripping at all exterior doors. The caulking and weatherstripping will reduce air leakage through the building envelope. Air leakage represents from 5% to 40% of the space-conditioned costs. Controlling air leakage is one of the most important functions of weatherization. The main goals of air leakage control are to: save energy, increase comfort, protect insulation’s thermal integrity, reduce direct cooling or heating of people and building components by outdoor air, and avoid moisture migration into building cavities. The twenty-eight exit doors are in serviceable condition. The damaged or missing weatherstripping on the majority of the doors should be replaced. The caulking around the windows, expansion joints and door frames is deteriorated and should be renewed. Old caulking should be removed and new applied, estimated to be 1,543 linier feet.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 27

    Library room, large south facing picture windows

    IR20101111_0052.is2 11/11/2010 1:17:12 PM Radiant heat from the sun

    Visible Light Image

    Image Info Background temperature 68.0°F Emissivity 0.95 Transmission 1.00 Average Temperature 86.4°F Image Range 66.2°F to 125.7°F Camera Model FLXR2 Camera serial number FLXR2-0606097 Camera Manufacturer Infrared Solutions Image Time 11/11/2010 1:17:12 PM Main Image Markers Name Temperature Emissivity Background Hot 125.7°F 0.95 68.0°F

  • Grady Municipal Schools TEA Report

    02/04/11 Page 28

    Office in district admin area, south facing window

    IR20101111_0055.is2 11/11/2010 1:21:46 PM Radiant heat from the sun

    Visible Light Image

    Image Info Background temperature 68.0°F Emissivity 0.95 Transmission 1.00 Average Temperature 79.2°F Image Range 65.4°F to 120.9°F Camera Model FLXR2 Camera serial number FLXR2-0606097 Camera Manufacturer Infrared Solutions Image Time 11/11/2010 1:21:46 PM Main Image Markers Name Temperature Emissivity Background Hot 120.9°F 0.95 68.0°F

  • Grady Municipal Schools TEA Report

    02/04/11 Page 29

    Admin main entrance, south facing double doors

    IR20101111_0056.is2 11/11/2010 1:23:36 PM Radiant heat from the sun

    Visible Light Image

    Image Info Background temperature 68.0°F Emissivity 0.95 Transmission 1.00 Average Temperature 80.4°F Image Range 66.9°F to 118.9°F Camera Model FLXR2 Camera serial number FLXR2-0606097 Camera Manufacturer Infrared Solutions Image Time 11/11/2010 1:23:36 PM Main Image Markers Name Temperature Emissivity Background Hot 118.9°F 0.95 68.0°F

    Proposed Upgrades:

    Caulk all windows and exterior wall expansion joints and replace weather stripping on all exterior doors. The caulking and weather stripping will reduce air leakage through the building envelope. Controlling air leakage is one of the most important functions of weatherization, and often the most difficult. The main goals of air leakage control are to: save energy, increase comfort, protect insulation’s thermal integrity, reduce direct cooling or heating of people and building components by outdoor air, and avoid moisture migration into building cavities.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 30

    Savings Calculations: ANNUAL ENERGY SAVINGS Units Saved Rate Savings

    KWH Saved Weatherstripping & Caulking 637 $0.083 $52.87MMBtu Saved Weatherstripping and Caulking 113.7 $18.640 $2,118.55

    $2,171.43Weatherstripping & Caulking

    Heating Savings Installation Cost Estimate $7,500.00% CFM Used 90%

    Existing CFM 1,398 Simple Payback 3.45 BTU/Deg/CFM/hr 1.08

    DEG/DIF.= 24.9BTU/HR 33,826

    Hours/Day 24.00Days/ Year 140

    Total Hours / Year 3,360MMBTU Savings 113.7

    Weatherstripping & CaulkingCooling Savings

    % CFM Used 10%Existing CFM 1,398

    BTU/Deg/CFM/hr 1.08DEG/DIF.= 10

    BTU/HR 1,509Hours/Day 24.00

    Days/ Year 60Total Hours / Year 1,440

    kWH Savings 637

    Work to be complet No. of UnitsPerimeter

    (ft)

    Crackage

    (in)Conversion to feet Product

    SingleExit-VoAg 22 20 1/64 1/12 = 0.573SingleExit-Schools 6 20 1/64 1/12 = 0.156Masonry-VoAg 1 903 1/64 1/12 = 1.176Masonry-Schools 1 640 1/64 1/12 = 0.833Windows 0 24 1/64 1/12 = 0.000

    Total = 2.738

    Infiltration Savings

    Total CrackArea(SF)

    AverageWind Speed

    (MPH)

    AverageWind Speed

    (FPM)

    Windward

    Diversity(%)

    InfiltrationSavings(CFM)

    A B C =B x 5280 / 60 DE =

    A x C x D2.74 11.6 1020.8 50% 1397.619

    Note: Avg winter outside air temp used to determine DEG/DIF is based on: (3482 degree days from METRIX)/(7 days/wk)/(20 wks/year) = 24.9 degree delta T.

    65 degree F balance point (from METRIX) - 24.9.0 degree F = 40.1 Avg Outside Air Temp.

    Average Wind Speed (Clovis AFB) = 11.6 MPH (Western Regional Climate Center) Implementation Costs: The implementation costs for weatherstripping and caulking were provided by a building inspection firm.

    Operations and Maintenance: The proposed building weatherization upgrades do not affect operations and maintenance costs.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 31

    GMS6 Computer Power Management: Existing Conditions: The sixty-five identified computers in the classrooms and offices are turned on and off by the teachers or administrative staff. Some individuals turn their computers off daily and some leave them running.

    Proposed Upgrades: Install free power management software by Verdiem that allows for scheduling standby modes. This software needs to be loaded on each computer and provides enhanced power management. Savings Calculations: The following formulae were used to calculate the energy saving for the computer management upgrades:

    1) Kilowatt-hours (kWh) Existing Existing Active Mode = 200 watts per PC/monitor combination Existing Standby Mode = 22 watts per PC/monitor combination Average Hours per Week of Active Mode = 40 Average Hours per Week of Standby Mode = 56 Weeks per Year = 40 Total Existing Active kWh per PC/Monitor = Existing W * Hours/Week * Weeks/1000 = 320 Total Existing Standby kWh per PC/Monitor = Existing W * Hours/Week * Weeks/1000 = 49 Total Existing kWh per PC = Active kWh + Standby kWh =369 Total Existing kWh = # (65) of PC/Monitors * Total kWh/PC =24,003 2) Kilowatt-hours (kWh) Proposed Proposed Active Mode = 200 watts per PC/monitor combination Proposed Standby Mode = 22 watts per PC/monitor combination Average Hours Per Week of Active Mode = 32 Average Hours per Week of Standby Mode = 64 Weeks per Year = 40 Total Proposed Active kWh per PC/Monitor = Proposed W * Hours/Week * Weeks/1000 =256 Total Proposed Standby kWh per PC/Monitor = Proposed W * Hours/Week * Weeks/1000 = 56 Total Proposed kWh per PC = Active kWh + Standby kWh =312 Total Proposed kWh = # (65) of PC/Monitors * Total kWh/PC =20,301 3) Total Dollars Saved Total Dollars Saved = (Existing kWh – Proposed kWh)*Dollars/kWh = $ 307.30

    Implementation Costs: The software program to manage PC power is a free program available from Verdiem. The cost for installing the program on each computer and making the necessary settings is based on an average of twenty minutes per computer or $ 10.00 labor cost.

    Operations and Maintenance: The additional time the computers spend in standby mode should slightly increase their life since hard disks are not spinning in standby mode and power supplies are at minimum output.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 32

    GMS8. Insulate Domestic Hot Water Tank: Existing Conditions: Two older identified propane-fired domestic hot water heaters located in the janitorial/equipment rooms provide domestic hot water for the school. The existing water heater jackets have an approximate R-value of 7.

    Proposed Upgrades: Install water heater insulating blankets with an R-value of 7 around each domestic hot water tank. The total R-value for the tanks will now be 14. Savings Calculations: Water heater base case and modifications were run in the eQuest simulation software with the following results:

    Number of units 2

    Hot water tank usage in MMBTU (per eQuest)Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total

    Existing 7.7 9 8.3 7.6 9.2 5 2 1.9 6 7.7 8.6 5.3 78.3Insulated 7 8.4 7.7 7 8.6 4.5 1.4 1.4 5.4 7.1 7.9 4.6 71

    Savings 7.3

    Rate: $18.64

    Energy Cost Savings $136.07

    Installation cost estimate ($135 ea) $270.00

    Simple Payback 1.98424

    Insulate Domestic Hot Water Tank

    Propane Annual cost savings = MMBTU Base – MMBTU DHW * Dollars/MMBTU

    Implementation Costs: The installation cost estimate is $135 per tank. This assumes $65 for materials and $70 for outside labor. Cost could be reduced by installation with in-house staff.

    Operations and Maintenance: This measure does not impact operations and maintenance cost.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 33

    GMS11. Vending Machine Setback: Existing Conditions: There are two identified vending machines on campus, one cold drink machines and one snack machine.

    Proposed Upgrades: Install a vending miser controller on the cold drink vending machine. The vending miser uses an occupancy sensor that will automatically set back the vending machine when the area around the machine has been vacant for fifteen minutes or so (adjustable). The controller will periodically re-power the machine to ensure the vended products stay cold. The controller senses the vending machines compressor status and will delay power-down of the vending machine until the compressor has completed its cooling cycle. Savings Calculations and Implementation Costs:

    JOB: Grady Municipal Schools

    ANNUAL ENERGY SAVINGS Units Installed Per Unit $/kwh Annual SavingsMECHANICAL KWH Saved 1 850 $0.083 = $70.55

    MECHANICAL KW Saved Installed CostTOTAL INSTALLED COST 1 $400 = $400.00

    Existing kWh Proposed kWh Saved kWh Unit Installed Cost3,500 2,650 850 VM170 $400Per Unit Calculation

    Vending Misers

    Operations and Maintenance: The vending machines are leased from and maintained by others, but the campus pays the electricity to operate it.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 34

    GMS12. Building Insulation: Existing Conditions: A building envelope survey has been performed to evaluate the need for building envelope insulation.. Thermal images were taken of different areas to assess current building conditions. Ceiling insulation was spot checked and determined to be R19 in most areas. However, no ceiling insulation was found in the cafeteria/kitchen, VoAg shop, and certain areas of the hallways.

    Proposed Upgrades: Install R30 fiberglass ceiling insulation in the areas where there is currently no insulation. These areas are the cafeteria/kitchen, VoAg shop as well as various hallways (approximately 14,351sf). Savings Calculations: These calculations are for adding building ceiling insulation:

    ANNUAL ENERGY SAVINGS Units Saved Rate Savings KWH Saved Insulation 1,325 $0.083 $110.01

    MMBtu Saved Insulation 74.3 $18.640 $1,384.20$1,494.22

    Installation Cost Estmate 17,938.75Simple Payback 12.01

    Insulation InsulationHeating Savings Cooling Savings

    Area 14,351 Area 14,351Existing 'U' Value 0.29 Existing 'U' Value 0.29

    Proposed 'U' Value 0.032 Proposed 'U' Value 0.032Difference 0.258 Difference 0.258

    Annual Heating Degree Days 3,482 Annual Cooling Degree Days 1,236Heating Efficiency 0.80 SEER 8.50

    Diversity/safety factor 0.30 Diversity/safety factor 0.35MMBtu Savings 74.3 kWH Savings 1,325

    Note: Proposed R30 VoAg / Hallways = 14,351 SFAvg winter outside air temp used to determine DEG/DIF is based on: (3482 degree days from METRIX)/(7 days/wk)/(20 wks/year) = 24.9 degree delta T.

    65 degree F balance point (from METRIX) - 24.9.0 degree F = 40.1 Avg Outside Air Temp.

    Building Insulation Savings

    Implementation Costs: The estimated implementation cost for the insulation was provided by supplier building inspection firm. Operations and Maintenance: There are no changes to the maintenance of the buildings by implementing this measure.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 35

    F. MEASURES CONSIDERED BUT NOT RECOMMENDED A number of energy conservation measures were considered during the technical energy audit that will not be recommended for implementation due to paybacks exceeding fifteen years or the expected useful life of the new equipment. These measures may still be feasible if combined with other ongoing renovation projects or if equipment affected needs major repairs or replacement. Each measure is discussed with estimated energy savings and costs given.

    ECM ID ECM Name

    Equip Live

    Years

    Propane $

    Savings

    Propane MMBtu

    Savings

    Electric $

    Savings

    Electric kWh

    Savings

    O&M Other

    Savings

    Total $

    Savings RebatesTotal

    InvestmentSPBP Years

    GMS2 Energy management system 15 $611 33 $1,285 15,480 $200 $2,096 $0 $89,250 42.6

    GMS4 Economizer retrofit to RTU's 15 $77 4 $679 8,180 $169 $925 $0 $26,000 28.1

    GMS7 Destratification fans in gyms 10 $1,285 69 -$180 -2,168 $0 $1,105 $0 $14,400 13.0

    GMS9 Submetering for buildings 15 $0 0 $0 0 $0 $0 $0 $2,000 0.0GMS10 Variable frequency drives on RTUs 15 $0 0 $966 11,638 $0 $966 $0 $27,040 28.0

    GMS13 Window replacement 30 $145 8 $8 90 $0 $152 $0 $2,550 16.8

    Totals: $2,118 114 $2,757 33,220 $369 $5,244 $0 $161,240 30.7

    Base Year Cost

    Base Year

    Usage

    Total $ Savings

    Total Savings

    Percent Reduce

    Electric Utility $30,026 360,348 $2,757 33,220 9.2%

    Propane Utility $33,313 1,787 $2,118 114 6.4%

    Total Combined Utility $63,339 $4,875 7.7%

    Annual Savings and Investment Summary for NOT RECOMMENDED Projects:Grady Municipal School

  • Grady Municipal Schools TEA Report

    02/04/11 Page 36

    GMS2. Energy Management System:

    Existing Conditions: Controls throughout the building are electronic programmable thermostats wired to rooftop air handling units. The programmable thermostats are set for occupied/unoccupied periods based on a seven day clock. The system does not allow for holiday scheduling and thermostat setpoints can be overridden by anyone in the building. Once overridden the system will remain in that mode indefinitely. Proposed Upgrades: Remove existing electric/electronic controls and provide new direct digital control (DDC) system. Provide DDC controls for rooftop air handlers. A new DDC control system will allow the use of additional energy saving control strategies and will provide additional operational benefits. Provide a graphical user interface with user friendly graphics that will allow simple adjustments of schedules and temperature setpoints by authorized building occupants. Interface the new controls to the school district’s central operator workstation through the district wide computer LAN. Provide graphical user interface software, and provide sufficient training as required to allow the customer to perform setpoint and schedule adjustments. Some examples of energy saving strategies that are available with DDC controls are:

    1. Enhanced time of day scheduling and automatic holiday scheduling. 2. Data trending. Status of points can be electronically monitored to aid in troubleshooting. 3. Tighter space temperature control. 4. Graphical user interface allows the on-staff facilities personnel to monitor and make

    adjustments to the control system parameters. 5. All DDC space sensors can be individually monitored to help with identifying

    temperature control problems. 6. Night setback savings are maximized because each room can be set back during

    unoccupied times. 7. Mount all new space sensors at ADA approved height.

    The energy management system payback exceeds the typical payback period for other energy conservation measures. The benefits of an energy management system go beyond the hard savings from reduced utility bills and the system can provide the basis for ongoing energy management strategies and operations.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 37

    Points List for Energy Management Systems CONNECTED POINTS ENERGY MANAGEMENT

    SYSTEM INPUTS OUTPUTS APPLICATION SOFTWARE SOFTWAREDESCRIPTION DIGITAL ANALOG DIGITAL ANALOG

    RTU-1

    AU

    XILL

    AR

    Y C

    ON

    TAC

    TD

    IFFE

    REN

    TIA

    L PR

    ESSU

    RE

    LOW

    TEM

    PER

    ATU

    RE

    ALA

    RM

    SMO

    KE

    DET

    ECTO

    RFL

    OW

    SW

    ITC

    HC

    UR

    REN

    T SE

    NSI

    NG

    PRES

    SUR

    ETE

    MPE

    RA

    TUR

    EH

    UM

    IDIT

    YD

    EWPO

    INT

    STA

    RT/

    STO

    PO

    N/O

    FF/A

    UTO

    HI/L

    OW

    /OFF

    OPE

    N/C

    LOSE

    POSI

    TIO

    NIN

    GSP

    EED

    CO

    NTR

    OL

    POSI

    TIO

    N/M

    OD

    E D

    ISPL

    AY

    BU

    TC

    FMG

    PMPR

    OPO

    RTI

    ON

    AL

    (P)

    P +

    INTE

    GR

    AL

    (PI)

    P +

    I + D

    ERIV

    ATI

    VE (P

    ID)

    AD

    APT

    IVE

    HIG

    H A

    LAR

    MLO

    W A

    LAR

    MFL

    OA

    TIN

    G A

    LAR

    MA

    BN

    OR

    MA

    L O

    N/O

    FFA

    IRFL

    OW

    CO

    NTR

    OL

    SMO

    KE

    CO

    NTR

    OL

    SETP

    OIN

    T D

    ISPL

    AY

    & A

    DJU

    STR

    UN

    TIM

    E TO

    TALI

    ZATI

    ON

    TIM

    ED S

    TAR

    T/ST

    OP

    OPT

    IMU

    M S

    TAR

    T/ST

    OP

    ECO

    NO

    MIZ

    ER C

    HA

    NG

    EOVE

    REN

    THA

    LPY

    CH

    AN

    GEO

    VER

    DEM

    AN

    D L

    IMIT

    ING

    ZER

    O E

    NER

    GY

    BA

    ND

    NIG

    HT

    CYC

    LEN

    IGH

    T PU

    RG

    ELO

    AD

    RES

    ET

    NO

    TES

    GRAPHIC XSUPPLY FAN X X X X X

    FILTERM IXED AIR X X X XM IXED AIRDISCH. AIR X X X X

    RETURN AIR X X X XRETURN AIR

    OA/RA DAM PERM IN O.A.

    ECON. M ODEECON. SET PT.

    CHW VALVEOUTSIDE AIR X

    SPACE X X XNOTES: Savings Calculations: Changes to the building operation from installing an energy management system were modeled in the eQuest simulation software. Energy savings are calculated as follows: Electrical Annual Savings = (kWh Base – kWh EMS)* Dollars/kWh Propane Annual Savings=MMBTU Base – MMBTU EMS * Dollars/MMBTU Total Annual EMS Savings = Electrical Savings + Propane Savings See the eQuest report title TStat Management EEM on the following page:

  • Grady Municipal Schools TEA Report

    02/04/11 Page 38

  • Grady Municipal Schools TEA Report

    02/04/11 Page 39

    Implementation Costs: The cost to furnish and install the energy management system for twenty-six rooftop units and a building management workstation with software was calculated using the actual cost of the direct digital control system components and standard labor factors. These costs were figured by a major energy management manufacturer/contractor. Operations and Maintenance: This measure involves the installation of new controls. New controls will need to be mainained and software will need to be periodically updated following the manufacturer’s recommendations. The new control system will simplify the maintenance of occupancy schedules and setpoints. The current system requires physically going to each thermostat and reprogramming the thermostat to account for holiday and summer shutdown periods. With the new system thermostat management can all be done from the front end computer.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 40

    GMS4. Economizer Retrofit of Rooftop Air Handlers: Existing Conditions: The building is heated and cooled by predominantly Carrier packaged rooftop air handling units with indirect fired gas furnaces and direct expansion cooling. The units have a fixed 25% outside air opening.

    Proposed Upgrades:

    Modify the ductwork and provide new automatic control dampers and actuators to allow for free cooling when outdoor air temperature is low. The addition of automatic dampers would also not allow outside air intake when the units cycle to maintain unoccupied setpoints. Savings Calculations:

  • Grady Municipal Schools TEA Report

    02/04/11 Page 41

    Propane Annual Savings = (Existing MMBTU – Proposed MMBTU) * Dollars/MMBTU Electricity Annual Savings = (Existing kWh – Proposed kWh)*Dollars/kWh Total Annual Savings = Propane Annual Savings + Electricity Annual Savings

    Implementation Costs: The estimated implementation costs for the economizer retrofit were provided by the air handling equipment distributor. Operations and Maintenance: This measure would increase maintenance costs since economizer controls and dampers would need to be checked and adjusted annually.

  • Grady Municipal Schools TEA Report

    02/04/11 Page 42

    GMS7. Destratification Fans in Gyms: Existing Conditions: Both the old gym and the new gym have high ceilings. During the heating season warm air rises to the upper sections of the gyms while areas near the floor are considerably cooler. It takes additional energy to get the temperature at five feet off the floor comfortable.

    Proposed Upgrades:

    Install four destratification fans in each gym near the ceiling and run them continuously during the heating season. This measure is not recommended because the payback period exceeds the useful life of the fans. Savings Calculations:

    ANNUAL ENERGY SAVINGS Units Saved $/kwh SavingsMECHANICAL KWH Saved (2,168) $0.083 -$180

    MECHANICAL KW Saved $/MMBtuMMBtu Saved 69 $18.64 $1,285

    ECM OPERATIONAL Savings $$$ Net Saving =$1,105

    LOCATION: New Gym Old Gym Installed Cost Each =QUANTITY: 4 4 1800

    Room Dimensions (ft): X 102 96 Total Installed Cost = Qty Of X Walls That Are Outside Walls: 2 2 14400

    Y 92 80Qty Of Y Walls That Are Outside Walls: 1 1

    Simple payback years = Wind