Technical DataManual

EN

VIR

ON

ME

NT

AL

CO

NT

RO

L

Keeping Business in Business

LiebertLPN: SLE MT TDM E.3_r1 (10/99)

HPN:

Mini Tower

Table of Contents

System nomenclature 1

Introduction 2

Standard features - all models 3

Optional features - all models 10

Technical data - all models 14

Electrical data - all models 16

Sound data - all models 17

Dimensional drawings 18

System nomenclature

The nomenclature for Mini Tower packaged (compressor in the

indoor unit) and split (compressor located in a condensing unit)

systems is as follows:

SLE MT TDM E.3_r1 (10/99) 1

Mini Tower - Technical Data Manual

Humidifier:

M = Humidifier

X = No humidifier

Air pattern:

U = Upflow

D = Downflow

System type:

A = Air cooled

W = Water cooled

G = Glycol cooled

C = Chilled water

Model size:

Capacity in kW (Nominal)

TS = Mini Tower Packaged

TSF = Mini Tower Split (Air

Cooled only)

TS/TSF 06 A U X

TS/TSF 06 A U M

Model size System type Air pattern Humidification

Mini Tower 04 4kW nom. cap. A Air cooled D Downflow M Humidifier

06 6kW nom. cap. W Water cooled U Upflow X No humidifier

07 7kW nom. cap. G Glycol cooled

09 9kW nom. cap. C Chilled water

11 11kW nom. cap.

AIR (Packaged) AIR (Split) WATER GLYCOL CHILLEDWATER

TS04AUX/ADX TSF6AUX/ADX TS04WUX/WDX TS04GUX/GDX TS07CUX/CDX

TS04AUM/ADM TSF6AUM/ADM TS04WUM/WDM TS04GUM/GDM TS07CUM/CDM

TS06AUX/ADX TSF9AUX/ADX TS06WUX/WDX TS06GUX/GDX TS11CUX/CDX

TS06AUM/ADM TSF9AUM/ADM TS06WUM/WDM TS06GUM/GDM TS11CUM/CDM

TS09AUX/ADX TS09WUX/WDX TS09GUX/GDX

TS09AUM/ADM TS09WUM/WDM TS09GUM/GDM

Introduction

Precision environmental control may be defined as the

simultaneous control of air temperature, humidity,

distribution and cleanliness on a continual, around-the-clock

basis.

Conventional building or ‘comfort’ systems, as they are

called, are not designed for this 24-hour, year-round usage;

they lack the ability to provide the precision and reliability or

‘close control‘ that is so critical to many applications.

All units are built in accordance with European directives

98/37/CE (89/392/CEE; 91/368/CEE; 93/68/CEE),

89/336/CEE; 73/23/CEE. The Liebert Air Conditioning

Quality System is approved by LRQA in accordance with the

standards UNI EN ISO 9001: 1994.

Each unit is supplied complete with a Test Certificate and

Declaration of Conformity.

All Mini Tower units carry the “CE” mark and fully comply

with European Directives concerning mechanical, electrical

and electromagnetic safety.

Liebert technology and energy

efficiency

Liebert has become a world leader in precision environmental

control systems by providing maximum energy efficiency

without compromising precision and reliability.

Liebert takes a no-compromise approach to environmental

control system design. All enhancements to energy efficiency

are designed to reduce operating time of key components.

This is accomplished by taking advantage of alternate sources

of cooling when available or, by reducing compressor work

load when the heat load in the critical space is lower.

Applications

The Mini Tower unit is ideally suited for precision close

control of the following types of environment:

� Data centres

� Telecommunications

� Industrial applications

� Office environments

System types

The Mini Tower is available in a number of configurations:

Air cooled

Two system types are available:

Packaged

This comprises an indoor unit (consisting of an evaporator

coil, scroll compressor, direct driven fan, electric reheat and

filter section) and an outdoor air cooled condenser.

Indoor Unit Matching Condenser*

TS04A HCA07

TS06A HCA10

TS09A HCA14

*: Quoted at 32 oC outside ambient temperature. For other

ambients, consult the Condenser Technical Data Manual

(P/N SLE CD TDM).

Split

This comprises an indoor unit (consisting of an evaporator

coil, direct driven fan, electric reheat and filter section) and an

outdoor condensing unit (complete with scroll compressor).

Indoor Unit Matching Condensing Unit*

TSF6A MMC08

TSF9A MMC10

*: 32 oC outside ambient temperature.

Water/Glycol cooled

This comprises of an indoor unit (consisting of an evaporator

coil, scroll compressor, plate condenser, direct driven fan,

electric reheat and filter section) and an outdoor drycooler.

Note: This product may not be suitable for all open water

tower applications as good quality water is essential for

correct operation. Consult Liebert Hiross Applications

Engineering for further details.

Chilled Water

This comprises of an indoor unit only (consisting of a chilled

water coil, 3-way valve, direct driven fan, electric reheat and

filter section).

The unit is supplied with chilled water from a central building

chiller or other chilled water source.

2 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Standard features - all models

General

The Mini Tower series comprises both direct expansion units

and chilled water units. Cooling capacities range from 4 to 11

kW. Direct expansion units are equipped with compliant

scroll compressors. The design of the scroll compressor,

ensures a constant refrigerant pressure, thus improving

reliability, energy consumption and sound emission.

The Mini Towers compact design, facilitates a minimum unit

footprint, allowing the unit to be installed in very confined

areas, the unit is fully serviceable from the front.

Access/maintenance

Routine maintenance access to refrigerant circuit

components, the compressor, liquid reservoir, thermal

expansion valve, sight glass, filter dryer etc. is available

through the front panel of the unit. Service access to the air

filter is also through the unit front panel.

All other components of the machine, the fan, humidifier,

electric panel, electronic controller PCB, electric reheats etc.

are accessible through the front and grille panels.

Customer connections to the refrigerant circuit (hot gas and

liquid line), mains power supply, humidifier water supply and

condensate drain lines are located in the lower right-hand-side

of the unit.

Cabinet

The cabinet is manufactured from primed and treated steel, it

is then degreased and painted in RAL 9018 using dry powder

epoxy resin paint (the return air grille is finished in NCS 3502

coloured paint). The paint finish is easily cleaned and is hard

wearing to give maximum protection. The unit has removable

panels which give access to all internal components from the

front of the unit. The panels are insulated with 12mm, 30

kg/m3 density foam which reduces noise emission and heat

loss. The foam is a self-extinguishing material in compliance

with the following standards: ASTM D 1992, MVSS302,

UL94 Class 0.

A safety microswitch is fitted to the front panel of the unit.

The microswitch deactivates the unit if the front panel is

removed.

The edges of the panels are fitted with seals to prevent air loss

and to keep noise levels to an absolute minimum.

Filter section

The guaranteed efficiency is EU3, (Eurovent EU4/5 (30%

efficiency), equivalent to G3 - CEN Standard). An optional

EU4 filter (G4) is available on request.

The air filter is mounted on the face of the evaporator coil and

is easily accessed/replaced by removing the front panel. The

filter is made of open-cell foam and is designed to minimise

the air pressure drop while maintaining maximum filter

efficiency.

Fan and motor assembly

The unit is fitted with a direct-drive, double-inlet forward-

curved, galvanized-steel, centrifugal fan. The fan impeller is

statically and dynamically balanced and equipped with

sealed-for-l ife bearings. The fan is mounted on

vibration-absorbing rubber supports to reduce vibration

transmission between the fan and the unit frame. This

vibration attenuation helps to keep noise emission to a

minimum.

The fan motor is a single-phase, 5-speed motor complete with

thermal overload protection. Each speed of the motor

produces a different airflow through the unit, refer to the

Technical Data section for specific model/airflow data.

Each unit is wired for two different airflows, a cooling airflow

and a lower, dehumidification airflow. The controller will

switch the unit to the lower airf low during the

dehumidification cycle.

Electric reheat

The single-stage, three element reheats are of rigid,

fin-tubular design that have extended operational life. The

reheat has ample capacity to maintain room dry-bulb

conditions during a system call for dehumidification. The

low-watt density, phase balanced, electrically enclosed

elements are surrounded by the tube and fins, reducing sheath

temperatures and eliminating ionisation.

Reheat control is of the ON-OFF type. The reheat is provided

with a manual reset, reheat safety thermostat, to disable the

reheat in the event of high temperature.

SLE MT TDM E.3_r1 (10/99) 3

Mini Tower - Technical Data Manual

Standard features - all models (continued)

Microprocessor controls

The Microface environmental control system is

microprocessor based and can be programmed to match the

unique needs of any application. The processor integrates the

separate mechanical and electrical components into a

‘state-of-the-art’ conditioned space support system that

controls and monitors temperature, humidity, air flow and air

cleanliness.

The control system offers a tailored and well proven advance

in reliability and control flexibility allowing the unit to

modify its performance in response to changing critical space

conditions.

The controller allows local monitoring and programming of

the following room conditions:

� Temperature (oC)

� Temperature setpoint (5.0oC – 40.0oC in steps of 0.1 oC)

� Temperature sensitivity (1.0oC - 10oC in steps of 0.1 oC)

� Humidity (%RH)

� Humidity setpoint (20%RH - 80%RH in steps of 1%)

� Humidity sensitivity (5%RH - 20%RH in steps of 1%)

The parameters are enunciated using symbols and text on an

LCD display. Normal operating modes are indicated by

symbols on the display. Alarm conditions activate a visual

indicator.

The following alarms are standard:

� High temperature

� Low temperature

� Fan failure

� High pressure alarm – (compressorised systems only)

� Low pressure alarm - (compressorised systems only)

� Electrical reheat high temperature

� Memory failure

� Common alarm

Other alarms are also available when the relevant option is

ordered with the unit (e.g. if a humidifier is ordered with the

unit, the High Humidity, Low Humidity etc. alarms are

enabled). For a full list of all the options and alarms available

with the Microface controller, refer to the Microface

Controller Operation Manual (P/N SLE MF OM).

The controller also incorporates a sequential auto-restart

timer, allowing field adjustable time delays to be applied to

unit restart after a power loss (or other shutdown). The timers

allow multiple units to be restarted while limiting

instantaneous inrush current.

Electrical panel

The electric panel is located at the top-front of the unit in an

airtight compartment. The electrical panel contains the

MCB’s, contactors, transformer, controller PCB and

overload relays etc. Each high voltage system component is

provided with a separate over-current protective device. All

high-voltage components are touch protected by means of a

plastic cover. Electrical design is in accordance with UNI /

EN 60204-1.

All models are supplied as standard for operation at

400V/3ph/50 Hz.

Models TS04A, TS06A, TSF6A, TS07C and TS11C can be

supplied for 230 V/1ph/50 Hz operation to special order.

Packaging

As standard, the units are wrapped in plastic film to protect

painted surfaces, enclosed in a cardboard box and mounted on

a wooden pallet.

On request, for sea transport etc., the units can be packed in

wooden crates or cases complete with silicon desiccant.

Warranty clauses

The warranty does not cover any damage or malfunction of

the unit which may occur during or as a result of operating the

unit outside of the specified application limits.

Liebert does not accept responsibility for any damage caused

by improper use of the product.

4 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Standard features - all models (continued)

Refrigerant circuit - dx models

Each unit in the range has a single refrigerant circuit. The

circuit consists of a compressor, a thermal expansion valve, a

liquid line sight glass, a filter dryer, an evaporator coil and

high and low pressure switches.

Liebert recommends the installation of a non-return valve

(supplied as an option, on request) on the liquid line from the

condenser, to protect the compressor from unexpected

refrigerant migration. All low temperature parts of the

refrigerant circuit are insulated as standard.

Compressors

The fully hermetic compliant scroll compressor incorporates

several safety features for protection during normal and the

occasional abnormal operating conditions. They are:

� Self resetting overloads to sense excessive currents and

temperatures.

� An internal pressure relief valve which limits discharge

pressure to protect mechanical parts.

� Motor insulation that is resistant to chemical attack.

� Rubber mounting to ensure reduced compressor noise and

vibration.

Schraeder connections are fitted to the unit for service access.

Refrigerant

R22 HCFC is the standard refrigerant used in the Mini Tower

range. An optional “Green” refrigerant, R407C is available to

special order. In this case the compressor is supplied with

ester oil instead of mineral oil. Air cooled units are shipped

with a nitrogen holding charge.

Evaporator coil

The evaporator coil is constructed from copper tubes with

aluminium fins to ensure maximum heat transfer. It is

designed to maximise the available surface area resulting in

low face velocities, low internal air pressure drops and the

high sensible heat ratios. A corrosion resistant drain pan is

provided on all models.

SLE MT TDM E.3_r1 (10/99) 5

Mini Tower - Technical Data Manual

Split air cooled systems

Outdoor

Indoor

Condensing

Unit

Indoor

Outdoor

Air Cooled

Condenser

Packaged air cooled systems

Standard features - all models (continued)

Sight glass

Refrigerant line sight glasses serve as a means of quick visual

inspection to determine if there is moisture in the system and

if the system is properly charged.

Filter-dryer

Liquid line filter-dryers ensure a clean, moisture-free

refrigerant system for extended component life. The filter

drier is suitable for use with standard R22 and optional “Zero

ODP” refrigerant R407C.

Expansion valve

The externally equalised, adjustable, thermostatic expansion

valve smoothly controls refrigerant flow during varying

indoor heat loads and outdoor ambient temperatures by

controlling evaporator superheat.

Safety controls

Each compressor has a manual-reset high pressure switch for

high pressure protection and a high pressure alarm circuit to

warn of high system pressures, allowing corrective action to

be taken before a significant loss of temperature control

occurs.

The low pressure switch is auto-resetting and detects low

pressure conditions such as loss of refrigerant charge.

The pressure switch calibration values are shown in the

Installation, Operation & Maintenance Manual supplied with

the machine.

Packaged air-cooled models

Air cooled condensers

A matching Liebert air cooled condenser with fan speed

control should be ordered with the unit. The range includes

condensers with axial fans and centrifugal fans. Details of

standard condenser selections for 32oC ambient are provided

in this manual, full technical details of all condensers for all

outdoor ambients are available in the Condenser Technical

Data Manual, (P/N SLE CD TDM).

Note: Condenser selections/performances for each outdoor

ambient are based on calculated data. The actual selection of

a condenser should always be verified on the basis of the

specific working conditions on each site.

Water/glycol cooled models

Water/glycol-cooled Mini Tower units are fitted with a high

pressure plate heat exchanger and a 2-way water regulating

valve (rated at 1030kPa (150psi)) to maintain head pressure.

Plate heat exchanger

The compact brazed plate heat exchanger consists of a

number of parallel stainless steel pressed plates, the pressing

pattern being inverted on alternate plates. In this way, the

ridges on adjoining plates form contact points and the

refrigerant and fluid move in contra-flow through alternate

channels. The plate heat exchanger is designed to operate at a

maximum working pressure of 30 bar (3000 kPa)

(factory-tested to 40 bar (4000 kPa)).

The units operate with mains water, cooling tower water or

water in a closed circuit with an external drycooler.

When operating in a closed circuit, it may be necessary

(depending on outside temperatures) to add mono-ethylene

glycol to prevent the water freezing in winter, refer to the unit

Installation Manual for applicable percentages.

A pump is used to circulate water (water/glycol) through the

unit (not supplied by Liebert).

If mains water or tower water is used, it is recommended to fit

a mechanical filter on the water line to protect the plate heat

exchanger against possible impurities contained in the water

(for plate heat exchanger cleaning, refer to the Installation

Manual).

Note: Water cooled units may not be suitable for some open

cooling tower applications as good water quality is essential.

Contact Liebert Applications Engineering for details.

Water regulating valve

A 2-way water regulating valve is fitted as standard and is

designed to operate with fluid working pressures of 10.1 bar

(1010 kPa). The valve operates with a maximum fluid

temperature of 77 oC.

Drycooler

A matched Liebert drycooler should be ordered with the unit.

The range includes condensers with axial fans and centrifugal

fans. Details of standard drycooler selections for 32oC

ambient are provided in this manual, full technical details of

all drycoolers for all outdoor ambients are available in the

Drycooler Technical Data Manual, (P/N SLE DC TDM).

Note: Drycooler selections/performances for each outdoor

ambient are based on calculated data. The actual selection of

a drycooler should always be verified on the basis of the

specific working conditions on each site.

6 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Standard features - all models (continued)

Split air-cooled models

Condensing unit

Cabinet

The cabinet is manufactured from zinc coated steel, it is then

de-greased and painted in “Pearl White” (RAL7032) dry

powder epoxy resin paint. The paint finish is easily cleaned

and is hard wearing. The cabinet has been designed

specifically for outdoor applications, all materials, fittings

and components have been selected to provide maximum

weather protection, durability and security (vandal-proof

cabinet). The unit has removable panels (a special key is

required) which give access to all internal components. The

condenser air inlet is through the rear of the unit and

discharges through the front. A metal safety grid prevents

accidental contact with the fan and the coil. The compressor is

located in the side of the Condensing unit, separated from the

airstream.

Condenser coil

The condenser coil is manufactured from refrigeration quality

copper tubes with mechanically bonded aluminium fins, and

is vertically mounted.

Fan/motor assembly

The condensing unit is equipped with a single axial fan with

integral motor, it is statically and dynamically balanced. The

fan impeller and casing are made from zinc-coated steel to

protect against corrosion. The direct drive motor includes

sealed-for-life bearings. The fan motor is IP54 rated and

complete with internal thermal protection. The fan motor is

controlled by a pressure switch to maintain a steady

condensing temperature.

Fan speed control

A factory fitted solid state fan speed controller is installed to

maintain the refrigerant condensing pressure. The controller

varies airflow through the condenser to maintain a constant

pressure. The advantages of fan speed control are two-fold.

Higher reliability of the system due to less starts/stops of the

compressor and a lower noise level because the fan is running

at a lower speed, mainly during night-time.

Compressor

The fully hermetic compliant scroll compressor incorporates

several safety features for protection during normal and the

occasional abnormal operating conditions. They are:

� Self resetting overloads to sense excessive currents and

temperatures.

� An internal pressure relief valve which limits discharge

pressure to protect mechanical parts.

� Motor insulation that is resistant to chemical attack.

� Rubber mounting to ensure reduced compressor noise and

vibration.

The compressor is fitted with a crankcase heater as standard.

They maintain minimum refrigerant temperature and are

energised while the unit is powered and the compressor is off.

Schraeder valves are fitted to the compressor for service

access.

Refrigerant

R22 HCFC is the standard refrigerant used in this range.

Condensing units suitable for use with an optional “Zero

ODP” refrigerant, R407C are available to special order.

Controls

Pre-wired, factory installed electrical and control

components include:

� Mains and low voltage terminals.

� Compressor and fan contactor.

� Factory pre-wired high pressure switch.

Electrical design is in accordance with UNI / EN 60204-1.

Sight glass

Refrigerant line sight glasses serve as a means of quick visual

inspection to determine if there is moisture in the system

and/or if the system is properly charged.

Filter-dryer

Liquid line filter-dryers ensure a clean, moisture-free

refrigerant system for extended component life. The filter

drier is suitable for use with standard R22 and optional “Zero

ODP” refrigerant R407C.

Liquid receiver in indoor unit

In split air-cooled models, a welded steel liquid receiver is

provided to maintain constant and even refrigerant flow to the

expansion valve, under all circumstances. It is installed in the

indoor unit. Shut-off valves are fitted as standard on the inlet

and outlet of the receiver to assist maintenance of the circuit,

if required.

A suitably rated pressure relief valve is installed on the liquid

receiver. The valve is equipped with a threaded connection to

allow the refrigerant to be discharged outside of the

conditioned space, if required.

SLE MT TDM E.3_r1 (10/99) 7

Mini Tower - Technical Data Manual

Standard features - all models (continued)

Chilled water systems

Cooling coil

The chilled water coil is manufactured from refrigeration

quality copper tubes with mechanically bonded aluminium

fins. Coils are circuited from a header to ensure low water

pressure drops. It is designed to maximise the available

surface area resulting in low face velocities, low internal air

pressure drops and the high sensible heat ratios. A corrosion

resistant drain pan is provided on all models.

3-way control valve

The chilled water valve provides on/off control action in

response to room temperature and humidity as sensed by the

microprocessor. This is a slow acting, motorised ball-valve

offering on/off control without water-hammer. The valve is

rated to 862 kPa (125 psi).

Operating limits - dx models

Mini Tower dx units are designed for operation within the

following working limits (the limits are applicable to newly

commissioned machines which have been correctly installed

and maintained).

Indoor operating range

TS04A/W/G from 18.0°C, 45% R.H. to 30.0°C, 55% R.H.

TS06A/W/G from 18.0°C, 35% R.H. to 30.0°C, 70% R.H.

TS09A/W/G from 18.0°C, 35% R.H. to 27.0°C, 70% R.H.

To minimise the possibility of water carry-over, (i.e. too much

condensate on the evaporator coil leading to the formation of

water droplets), it is critical to ensure that the latent load

(difference between total and sensible load) does not exceed

the following values:

TS04A/W/G 1.4 kW

TS06A/W/G 2.0 kW

TS09A/W/G 2.8 kW

Outdoor operating range

Lower limit

-25°C (with fan speed control in the condenser).

Upper limit

This is determined by the capacity of the condenser coupled to

the unit (at the relevant outdoor ambient). If the limit is

exceeded, the High Pressure Switch will shut the compressor

down. The switch must then be manually reset after the

problem has been rectified.

Air flow

The minimum and maximum air flows and available external

static pressure are given in the Technical Data section of this

manual. The fan motor thermal overload protects the unit

from any damage which could result from operating outside

the specified values.

Voltage tolerance

All models: 400 V � 10%

Frequency tolerance

All models: 50 Hz � 2 Hz.

Condenser installation (packaged air cooled)

Condenser above indoor unit

Maximum distance between indoor unit and external air

condenser: 30 meters equivalent length.

Condenser below indoor unit

Maximum geodetic height difference between condenser and

unit: 3 meters.

Condensing unit installation (split air cooled)

Maximum distance between indoor unit and condensing unit:

15 meters equivalent length. Refer to the unit Installation,

Operation and Maintenance for further details.

8 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Standard features - all models (continued)

Operating limits - chilled water

models

Mini Tower chilled water units are designed for operation

within the following working limits (the limits are applicable

to newly commissioned machines which have been correctly

installed and maintained).

Indoor operating range

TS07C from 18.0°C, 45% R.H. to 27.0°C, 55% R.H.

TS11C from 18.0°C, 35% R.H. to 30.0°C, 70% R.H.

Note: Consult Liebert Applications Engineers for use of the

units outside this range.

To minimise the possibility of water carry-over, (i.e. too much

condensate on the evaporator coil leading to the formation of

water droplets), it is critical to ensure that the latent load

(difference between total and sensible load) does not exceed

the following values:

TS07C 1.4 kW

TS11C 2.0 kW

Outdoor operating range

The entering chilled water temperature to the cooling coil

should normally be at least 5oC lower than the return air

temperature to the cooling coil.

Chilled water temperatures below 6oC require careful unit

selections.

Maximum recommended water pressure: 16 bar

Air flow

The minimum and maximum air flows and available external

static pressure are given in the Technical Data Section of this

manual. The fan motor thermal overload protects the unit

from any damage which could result from operating outside

the specified values.

Voltage tolerance

All models: 400 V � 10%

Frequency tolerance

All models: 50 Hz � 2 Hz.

SLE MT TDM E.3_r1 (10/99) 9

Mini Tower - Technical Data Manual

Optional features - all models

Electrode boiler steam humidifier

Provides humidification control and consists of a steam

generator, steam distribution tube, fill valve, drain pump and

electronic controls, located within the evaporator module.

The 2.4 kW (at 380V) humidifier produces a maximum steam

output of 3 kg/hr (adjustable).

Note: These humidifiers should only be used where the supply

water has a conductivity between 80 and 1000 �S/cm and a

water pressure of 0.3 to 8 bar (Max. supply water temperature

30 oC).

Modulating chilled water valve

Optional fully modulating (2 or 3-way) chilled water valve for

close control applications. The valve body is rated for 27.5 bar

(2750 kPa) operating pressure for closed systems. For high

pressure open systems, consult Applications Engineering for

valve and actuator selections.

Plenum

A 400mm high top discharge plenum, with insulated side

panels and painted to match the unit colour, is available for

applications where the supply air side of the unit is to be

connected to a ceiling void. Plenums with discharge grilles

(both fixed and adjustable) are available to special order.

Fresh air kit

A fresh air supply kit is available comprising a spigot

connection for 100mm I.D. duct hose (hose not supplied by

Liebert) and a cylindrical intake filter.

3-way water regulating valve

A 3-way water regulating valve can be fitted and is designed

to operate with fluid working pressures of 10.1 bar (1010

kPa). The valve is rated for a maximum fluid temperature of

77 oC.

Note: This valve is supplied loose for fitting externally to the

machine and comes complete a 1m capillary line.

Crankcase heaters

Crankcase heaters are available as an option with all

compressorised models (standard on split air-cooled models).

They maintain minimum refrigerant temperature and are

energised while the unit is powered and the compressor is off.

Condensate pump ( units with

humidifier)

The condensate pump is provided for mounting either under

the raised floor or local to the unit and is complete with sump,

motor, pump and automatic control. The pump has a capacity

of 548 l/hr at a head of 6 meters of water. (max. water

temperature 82 oC).

Condensate pump (units without

humidifier)

The condensate pump is provided for mounting within the

unit and is complete with an internal sump which will switch

the pump motor on when water is detected. When water has

been removed from the sump, the pump will automatically

stop.

10 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

0

1

2

3

0 10 20 30

5

6

7

8

9

10

Lift inmetres

Horizontal Distance Pumped in metres

Flow RateLtrs/Hour

Figure 1 - Condensate pump capacity chart (units

without humidifier)

Optional features - all models (continued)

Refrigerant non-return valves

Refrigerant non-return valves for air-cooled units are

available as an option.

The valve is installed on the liquid line, close to the condenser

and mounted vertically.

High efficiency filters

Optional high efficiency filters are available for all models.

The high efficiency filters are interchangeable with the

standard filters. The filters are EU4 (Eurovent 4/5), filtration

class G4 (CEN standards).

Filter clog switch

An adjustable diaphragm-type, differential pressure switch

can be fitted to initiate a change filter alarm when a

pre-selected pressure drop across the filter bank is exceeded.

Hot water reheat

The economical hot water reheaters have the capacity to

maintain dry bulb conditions when the system is calling for

dehumidification. The reheats are controlled by a 3-way

(on/off) valve from the microprocessor control panel. The

system is completely pre-piped and includes an air bleed

valve. The reheat coil is single row, constructed of copper

tubes with aluminium fins. The coil is tested to a pressure of

30 bar.

A hot water thermostat (provided by the customer) is used in

the valve control sequence to determine the availability of

reheat capacity.

Water detection options

The water detection sensor LT410 contains an isolated switch

that closes when water (or other conductive liquid) is detected

by the sensor probes. The sensor is hermetically sealed,

robust and should be fitted in the location where water

problems might occur.

The LT460 is a water detection cable. The cable is placed on

the floor around the base of the unit. It will generate an alarm

(via contact closure) if water (or other conductive liquid)

comes in contact with the cable.

Full details are available from your Liebert representative.

Smoke alarm

The smoke detector will activate an audible alarm and stop the

unit if smoke is detected in the return air. The sensor is an

optic smoke detector (Tyndall effect) which is insensitive to

light or air movement.

Firestat

The firestat deactivates the unit when the return air

temperature is too high. The firestat can be mounted in the

unit or remotely, consult Liebert Applications Engineers for

further details.

Environmental Alarm Package

The Electronic Environmental Alarm Package (EEAP) is a

remote temperature and relative humidity sensor (additional

to the internal sensor) connected to the unit controller.

The sensor can be installed up to 20m from the unit and

generates an alarm if the temperature or the relative humidity

exceeds one of the 4 user-set limits:

� High Temperature Limit

(Adjustable from 10°C to 50°C)

� Low Temperature Limit

(Adjustable from 0°C to 30°C)

� High Humidity Limit

(Adjustable from 30% to 99%)

� Low Humidity Limit

(Adjustable from 10% to 70%).

Floorstand

Floorstands are available in a range of heights: 230mm,

305mm, 380mm, 460mm, 530mm and 610mm. Each height

of floorstand is adjustable over a � 38mm range. The

floorstands permit installation and connection of the unit

prior to installation of the raised floor.

Turning vane

A factory installed turning vane may be specified to direct the

air as required within the floorstand.

SLE MT TDM E.3_r1 (10/99) 11

Mini Tower - Technical Data Manual

Optional features - all systems (continued)

Hiromatic graphic*

The Hiromatic Graphic sets even higher standards in

purpose-designed control systems for precis ion

air-conditioning. It simultaneously monitors the critical space

and signals alarms either locally or remotely. The graphics

screen displays all the major parameters, including symbolic

representation of unit functions, such as heating, cooling etc.;

in addition temperature and humidity variations with time can

be presented graphically on the screen. All diagnostic

procedures, including the checking and calibration of input

and output signals, and of the microprocessor itself, can be run

from the front panel

Features

� Backlit LCD graphics display

� User interface via pushkeys

� Battery-backed clock for date/time and real time functions

� Password control for setpoints, unit/control setup and

service functions

� Graphics display of temperature and humidity over a 24

hour period

The Hiromatic Graphic is specifically designed for group

management of a number of individual units although it can

be used in stand-alone applications. Due to its large graphical

display area, combined with exceptional contrast, it allows

the user to move around easily within the network of

connected unit controllers (up to max. 16). It is possible to

control/adjust each connected units operations from a single

point.

The controller is menu-driven and user menu’s are available

in 10 languages. The controller records the last 120 “events”

(Alarms, Warnings etc.) occurring in the system along with a

“Graphic Data Record” for each connected unit. The Graphic

Data Record displays the temperature and humidity readings

from each unit for the last 24 hours (stored since the last

start-up of the unit).

The Hiromatic Graphic controls date and time functions using

them as operating information for the customer and as a

reference whenever a status change occurs, logging the status

change in the “Status Report”. Details of the event which

occurred, the date and time at which the event occurred are

also stored. Using buffered RAM, the Hiromatic also stores

the operating hours of each component (compressor, fan,

electric heaters, humidifier etc.) for each connected unit.

A feature uniquely available with the Hiromatic controller is

“Sleep Mode” Sleep Mode allows units to be programmed to

switch on and off at different times of the day, and on different

days of the week.

*: The Hiromatic Graphic is supplied in a wall-mounted box

for remote installation.

BEMS Interface

The Hiromatic Graphic allows units on a network to be

integrated with the Hirolink Communications Bus when an

RS422 card is installed at the back of Hiromatic. Hiromatic

can control up to 8 Microface units in this configuration and

communicate the relevant data to Hirolink.

Hirolink works as a communications manager between the

Hiromatic Graphic and Microface units and industry standard

field busses and protocols used in Building Management

Systems such as Mod-Bus, J-Bus, Satchwell, etc.

Note: For full details of the controller, refer to the Hiromatic

Graphics Controller Manual, (P/N SLE HG OM).

Special packaging

Where the unit is to be transported by sea or in other cases

where heavy duty packaging is required, special crating is

available.

This can consist of either a wooden crate over the standard

carboard/bubble wrap packaging or the entire unit can be

encased in a wooden box.

Alternative refrigerant R407C

An optional “green” refrigerant, R407C can be supplied with

all compressorised models.

The compressor is filled with a special ester oil required for

R407C. Air cooled units are filled ex-factory with a holding

charge of dry nitrogen. Water and glycol units are charged

with R407C.

12 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Optional features - all systems (continued)

Special colour

Where required by the installation, the unit can be supplied in

any RAL colour. Minimum order quantities may apply,

consult Liebert Applications Engineering.

Extended warranty

The standard, parts-only, warranty is 15 months from the unit

ship date. This can be extended to 21, 27 or 39 months as an

option.

Flow switch

The flow switch is available as an option with chilled water

units. It is fitted as standard on the chilled water inlet line but

can be fitted on the bypass-leg (3-way valves) or between the

valve and the coil, if required by the application.

The switch is of the paddle type and is complete with volt-free

contacts. It can be wired to activate an alarm and/or shut down

the unit should the chilled water supply be interrupted.

Epoxy coated fins

- condensing unit

If the condensing unit is to be installed in a potentially

corrosive environment or close to salt water, epoxy/acrylic

coated fins are available to maximise the operating life of the

condenser coil. Capacity will be derated, contact Liebert

Applications Engineering for specific details.

SLE MT TDM E.3_r1 (10/99) 13

Mini Tower - Technical Data Manual

Technical data - all models

14 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Gross Cooling1Capacities Data in kW

Air

Cooled

Water2

Cooled

Glycol

Cooled

Chilled3

Water

MODEL TS04TS06/

TSF6

TS09/

TSF9

TS04 TS06 TS09 TS04 TS06 TS09 TS07 TS11

26 ºC DB,

50% RH

Total 5.5 7.2 9.5 5.9 7.5 10.4 6.0 7.4 9.4 8.3 11.9

Sensible 4.8 6.2 8.4 4.9 6.3 8.7 5.7 6.6 8.3 6.8 9.4

24 ºC DB,

50% RH

Total 5.3 6.9 9.1 5.6 7.1 9.8 6.0 7.0 9.1 6.8 9.7

Sensible 4.7 6.1 8.2 4.8 6.2 8.5 6.0 6.5 8.2 6.1 8.5

24 ºC DB,

45% RH

Total 5.3 7.2 9.4 5.4 7.4 9.6 6.0 7.3 9.4 6.3 8.9

Sensible 4.7 7.2 9.4 5.1 7.4 9.1 6.0 7.3 9.4 6.3 8.9

22 ºC DB,

50% RH

Total 5.0 6.6 8.7 5.3 6.7 9.3 5.8 6.7 8.7 5.5 7.8

Sensible 4.6 6.0 8.0 4.7 6.0 8.3 5.8 6.3 8.0 5.5 7.8

1: Capacity data is based on gross cooling capacity. To obtain nett figures, deduct the fan motor kW.2: 24 oC Entering Water Temperature and 43 oC Condensing Temperature3:7.2 oC Entering Water Temperature and 5.5 oC Temperature Rise4: Air cooled capacities, packaged/split, are stated at 32 oC outside ambient.

Fan Section - Single Fan, Direct Drive

Air Flow m3/h

(m3/s)

1600

(0.44)

1800

(0.5)

2300

(0.64)

1600

(0.44)

1800

(0.5)

2300

(0.64)

1600

(0.44)

1800

(0.5)

2300

(0.64)

1800

(0.5)

2300

(0.64)

Ext. Static Press. Pa 25 25 25 25 25 25 25 25 25 25 25

Evaporator Coil - Copper Tube/Aluminium Fin Chilled

Water Coil

Face Area m2

0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37

Rows of Coil 2 3 4 2 3 4 2 3 4 3 4

Face Velocity m/s 1.2 1.34 1.72 1.2 1.34 1.72 1.2 1.34 1.72 1.34 1.72

Flowrate/Pressure Drop Water Cooled Condensers Chilled

Water Coil

Flowrate (l/s) - - - - - - 0.1 0.2 0.3 0.1 0.2 0.3 0.4 0.5

Pressure Drop (kPa) - - - - - - 0.7 2.6 5.6 0.7 2.6 5.6 15.7 29.9

Technical data - all models (continued)

SLE MT TDM E.3_r1 (10/99) 15

Mini Tower - Technical Data Manual

Weight (unpacked) - indoor unit

Model TS04/6/9A1

TSF6/9A TS04/6/9W & G TS07/11C

Weight kg 164.3 136.8 170.5 136.8

1: For air cooled condenser weights and pipe sizes, refer to the Condenser Technical Data Manual P/N SLE CD TDM.

BSP = British Standard Pipe; 1: Male Thread Connections; 2: Female Thread Connections; 3: Male flare connector, 4: O.D. Copper

Condensing Unit Section

MMC08 MMC10

Air Volume m3/h (m

3/s) 5510 (1.53) 5510 (1.53)

Face Area m2

0.60 0.60

Face Velocity m/s 2.5 2.5

Rows of Coil 4 4

Weight kg 87 90

Pipe Connections

Model Chilled

Water

Return

Chilled

Water

Supply

Hot

Gas

Line

Liquid

Line

Water

Connections

Humidifier

Supply

Steam

Distributor

Drain

Humidifier

& Coil

Drain

TS04 A - - 12 in.3 3

8 in.3 -

14in. OD

14 in.

Male

Flared

34"

Female

BSP

TS06 /TSF6 A - - 12 in.3 3

8 in.3 -

TS09 /TSF9 A - - 12 in.3 3

8 in.3 -

TS 04 W/G - - - - 34 in. BSP2

TS 06 W/G - - - - 34in. BSP2

TS 09 W/G - - - - 34in. BSP2

TS 07 C 34 in. BSP1

34 in. BSP1 - - -

TS 11 C 34 in. BSP1

34 in. BSP1 - - -

MMC08 - - 10mm4 18mm4 - - - -

MMC10 - - 12mm4 18mm4 - - - -

Reheat/Humidifier section - all models

Electric Reheat - Single Stage, Fin Tubular

Total reheat capacity at 400V 3kW (3 number 1kW (400V) elements)

Electrode Boiler Steam Humidifier

Max. Capacity 3.0 kg/h

Filter - all models

Cleanable, open cell foam EU3 Filter 1 no.

Electrical data - all models

Mini Tower Electrical Ratings

Model Compressor* Fan Motor Electric

Reheat

Steam

Humidifier

FLA kW OA FLA kW FLA kW FLA

230/1/50 400/3/50 Nom. 230/1/50 230/1/50 400/3/50 Nom. 400/3/50 Nom. 400/3/50

TS04A/W/G 9.7 — 0.40 2.43 3.6 — 3.0 4.3 2.5 7.0

TS06A/W/G 12.3 — 0.40 2.70 3.6 — 3.0 4.3 2.5 7.0

TS09A/W/G — 6.2 0.40 3.10 3.6 — 3.0 4.3 2.5 7.0

TS07C — — 0.40 2.70 3.6 — 3.0 4.3 2.5 7.0

TS11C — — 0.40 3.10 3.6 — 3.0 4.3 2.5 7.0

TSF6A — — 0.40 2.70 3.6 — 3.0 4.3 2.5 7.0

TSF9A — — 0.40 3.10 3.6 — 3.0 4.3 2.5 7.0

MMC08 — 4.8 0.40 — — 3.5 — — — —

MMC10 — 6.6 0.40 — — 3.5 — — — —

Electrical Ratings - Other Matching Equipment

Air Cooled

Condenser

Drycooler

Indoor Model Model FLA Model FLA

230/1/50 230/1/50

TS04A HCA07 1.0 — —

TS06A HCA10 2.0 — —

TS09A HCA14 1.25 — —

TS04G — — DSL009 3.0

TS06G — — DSL009 3.0

TS09G — — DSL009 3.0

*: Quoted for R22

Note 1 : FLA = Full Load Amps

Note 2: OA = Operating Amps

Note 3 : Nom. = Nominal

Note 4 : All units require a Neutral.

Note 5: Condenser/Drycooler selection based on an ambient temperature of 32 oC. For other ambient temperatures, consult the

Drycooler or Condenser Technical Data Manuals (P/N’s SLE DC TDM & SLE CD TDM).

16 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Sound data - all models

Sound Pressure Levels dB(A)

SLE MT TDM E.3_r1 (10/99) 17

Mini Tower - Technical Data Manual

Figure 3 - Measurement

directions for noise data

TSF6/9 A & TS07/11C

Sound

Pre

ssure

Lev

eldB

(A)

Air Volume m /h (t )3

housands

Standard Air Volumes TSF6A & TS07C TSF9A & TS11C

At 1.5m

FreeField

TS04/6/9 A/W/G

Sound

Pre

ssure

Lev

eldB

(A)

Air Volume m /h ( )3

thousands

Standard Air Volumes TS/04A/W/G TS06A/W/G TS09A/W/G

At 1.5m

FreeField

Notes:

1. Sound pressure levels (at 1.5m) were measured in a room with a reverberation time of 0.476 seconds and a net volume of 270m3.

2. For unit standard air volumes and capacities, refer to the unit capacity section of this manual.3. For more information on air volumes other than standard, consult the Liebert Applications Engineering Department.4. The above graphs are for a constant 25 Pascals external static pressure, all figures are quoted at standard operating conditions.5. Free field sound pressure levels are calculated from the dBX & dBY/ dBZ Sound Power components.6. General Tolerance 1.5 dB(A)

Model Hz 31.5 63 125 250 500 1k 2k 4k

TS04A/W/G

dBx 68.8 60.8 65.5 58.8 54.2 49.3 43.2 36.8

dBy 79.9 72.1 60.8 56.9 57.5 50.9 44.4 35.1

dBz 80.8 72.5 61.2 57.2 57.9 51.3 44.8 35.5

TS06A/W/G

dBx 72.8 64.1 68.9 62.8 57.3 52.6 46.8 40.1

dBy 83.2 75.4 64.5 60.2 60.8 54.2 47.8 38.4

dBz 83.6 75.8 64.5 60.5 61.2 54.6 48.1 38.2

TS09A/W/G

dBx 75.9 68.8 72.2 66.3 61.2 56.5 50.8 44.3

dBy 87.3 79.2 68.1 64.2 64.7 58.0 51.6 42.5

dBz 87.5 79.7 68.4 64.4 65.1 58.8 52.0 42.8

TSF6A &

TS07C

dBx 69 61.1 65.9 59.2 54.3 49.6 43.8 37.1

dBy 80.2 72.4 61.8 57.2 57.8 51.2 44.7 35.4

dBz 80.6 72.7 61.5 57.5 58.2 51.6 45.1 35.8

TSF9A &

TS11C

dBx 72.3 65.8 69.3 63.5 58.9 53.6 47.1 41.0

dBy 84.1 76.0 65.2 61.8 61.5 55.0 48.2 39.5

dBz 84.5 76.7 65.4 61.4 62.1 55.5 49.9 37.9

Condensing units - MMC08/10

Sound Pressure level at 2m in the Free Field: MMC08: 56dB(A). MMC10: 57 dB(A).

Note: For condenser sound data - refer to the Condenser Technical Data Manual.

Sound Power Levels dB (re: 1 pW)

Dimensional data - air, water/glycol cooled (packaged)

18 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

EN

DVIE

W

A

SEC

TIO

NA

-A

A

ELE

CTR

ICPA

NEL

BLO

WER

DRIV

E

DIR

EC

T

AIR

FIL

TER

CO

MPRESS

OR

HU

MID

IFIE

R

MA

INS

SUPPLY

INPU

T

&A

LARM

TERM

INA

LS

DX

AIR

HO

T

GA

S

LIQ

UID

LIN

E

HU

MID

IFIE

R

SUPPLY

DRA

IN

FLA

RE

DRA

IN

SUPPLY

HU

MID

IFIE

R

OU

TLET

WATE

R

INLE

T

WATE

R

WATE

R

DX

CO

ND

EN

SER

CA

BLE

EN

TRIE

S

ALT

ERN

ATI

VE

PIP

ING

EN

TRIE

S

(REFER

TOD

ETA

IL'A

')

ALT

ERN

ATI

VE

(REFER

TOD

ETA

IL'B

')

PIP

ING

EN

TRIE

S

RETU

RN

AIR

RETU

RN

AIR

FAN

DIS

CH

ARG

EO

PE.

FRO

NT

ELE

VATI

ON

EN

DVIE

WFRO

NT

VIE

W

SHO

WIN

GM

AJO

RC

OM

PO

NEN

TS

REM

OVA

BLE

FRO

NT

PAN

ELS

REA

RPA

NEL

REM

OVA

BLE

LEFT

RIG

HT

1/4

"O

DFLA

RE

3/4

"ID

CO

NTR

OL

DIS

PLA

Y

(PA

NELS

REM

OVED

)

3/4

"ID

FEM

ALE

1/4

"O

DFEM

ALE

(DO

WN

FLO

WU

NIT

SO

NLY

)

(DIM

'NS

INC

LUD

EPA

NELS

)

(OPTI

ON

AL)

CA

BLE

EN

TRIE

S&

(WATE

R,

GLY

CO

L)

1/2

"3

/8"

3/4

"BSP

3/4

"BSP

60

84

70

75

0

69

0

95

39

21

79

95

188

10

205

25

45

35

(SEE

DETA

IL'A

')

1749

20

5

43

1

165

LIQ

UID

LIN

E/W

ATE

RO

UTL

ET

HO

TG

AS

/W

ATE

RIN

LET

HU

MID

IFIE

RSU

PPLY

DETA

IL'A

'

110

55

(SEE

DETA

IL'B

')

DIS

CH

ARG

EG

RIL

LE

(UPFLO

WU

NIT

SO

NLY

)

69

42

8

17030

GRIL

LED

IM

236

50

100

150

DETA

IL'B

'

Dimensional data - chilled water

SLE MT TDM E.3_r1 (10/99) 19

Mini Tower - Technical Data Manual

EN

DVIE

W

AA

ELE

CTR

ICPA

NEL

BLO

WER

DRIV

E

DIR

EC

T

AIR

FIL

TER

HU

MID

IFIE

R

MA

INS

SUPPLY

INPU

T

&A

LARM

TERM

INA

LS

DRA

INSU

PPLY

HU

MID

IFIE

R

INLE

T

WATE

R

OU

TLET

WATE

R

CW

CA

BLE

EN

TRIE

S

ALT

ERN

ATI

VE

PIP

ING

EN

TRIE

S

(REFER

TOD

ETA

IL'A

')

ALT

ERN

ATI

VE

(REFER

TOD

ETA

IL'B

')

RETU

RN

AIR

RETU

RN

AIR

FRO

NT

ELE

VATI

ON

EN

DVIE

WFRO

NT

VIE

W

SHO

WIN

GM

AJO

RC

OM

PO

NEN

TS

REM

OVA

BLE

FRO

NT

PAN

ELS

REA

RPA

NEL

REM

OVA

BLE

LEFT

RIG

HT

CO

NTR

OL

DIS

PLA

Y

(PA

NELS

REM

OVED

)

3/4

"BSP

T1

/4"O

D3

/4"BSP

T3

/4"ID

(OPTI

ON

AL)

MA

LEM

ALE

FLA

RE

CO

NN

1/4

"SA

E

HU

MID

IFIE

R

STEA

MD

RA

IN

CA

BLE

EN

TRIE

S&

(DO

WN

FLO

WU

NIT

SO

NLY

)

FAN

DIS

CH

ARG

EO

PE.

PIP

ING

EN

TRIE

S

(DIM

'NS

INC

LUD

EPA

NELS

)

SEC

TIO

NA

-A

CH

ILLE

DW

ATE

RVA

LVE

VA

LVE

HO

TW

ATE

R

(OPTI

ON

AL)

55

110

DETA

IL'A

'

60

84

70

75

0

69

0

25

45

25

1749

23

6

43

1

HU

MID

IFIE

RSU

PPLY

CH

ILLE

DW

ATE

RO

UTL

ET

CH

ILLE

DW

ATE

RIN

LET

CO

ND

EN

SATE

DRA

IN

165

DIS

CH

ARG

EG

RIL

LE

(UPFLO

WU

NIT

SO

NLY

)

69

42

8

17030

GRIL

LED

IM

DETA

IL'B

'

150

100

50

236 HU

MID

IFIE

RST

EA

MD

RA

IN

(SEE

DETA

IL'B

')

(SEE

DETA

IL'A

')

205

10

188

95

17

93

92

95

Dimensional data - air cooled (split)

20 SLE MT TDM E.3_r1 (10/99)

Mini Tower - Technical Data Manual

Dimensional data - air cooled condensing unit (split)

SLE MT TDM E.3_r1 (10/99) 21

Mini Tower - Technical Data Manual

1050

887==

52

6

4 no. ø8 mm Mounting Holes

AIR FLOW

AIR FLOW

AIR FLOW AIR FLOW

TOP VIEW

REAR VIEW

FRONT VIEW6

90

69

0

500

SIDE VIEW

LiebertEuropean Headquarters

Liebert EuropeZona Industriale Tognana,Via Leonardo da Vinci, 8,35028 Piove di Sacco (PD), Italy.Tel: +39-049-9719111Fax: +39-049-9719455Internet: http://www.liebert.com

International Headquarters

Liebert Corporation1050 Dearborn Drive, P.O. Box 29186Columbus, Ohio 43229 USATel: +1-614-888-0246Fax: +1-614-841-6022Internet: http://www.liebert.com

LPN: SLE MT TDM E.3_r1 (10/99)HPN:

While every precaution has been taken to ensure accuracy and completeness

in thismanual, Liebert assumesno responsibility and disclaimsall liability for

damages resulting from the use of the information contained herein or any

errors or omissions.

A World Leader in

Computer Support

Systems.

Environmental Control

Power Protection

Site Monitoring

Liebert Corporation designs,

manufactures and markets complete

systems for improved uptime and

performance of electronic

equipment, including computer

rooms, networks, medical, industrial,

and other critical systems. The result

is improved business operations,

increased productivity and higher

return on the customer's electronic

equipment investment. Liebert

Systems provide dependable

environmental control and electrical

power protection, combined with

centralised monitoring. This

approach represents a single-source

integrated support network. Based on

over two decades of experience and

over 100,000 installations

worldwide, Liebert is committed to

offering the highest quality products

and services for critical electronics.

© Liebert Corporation® All rights reserved throughout the world. Specificationssubject to change without notice. Liebert and the logo, areregistered trademarks of Liebert Corporation.