50
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org Technical Committee on Lightning Protection ROC Meeting Agenda October 9-12, 2012 Orlando, FL Day 1, October 9, 2012: 0800: Call to Order. 0800-0830: Roll Call/ Opening Remarks/Approval of Meeting Agenda/Approval of Meeting Minutes. 0830-0900: Introduction, 2014 cycle schedule recap, administrative topics. 0900-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 2, October 10, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 3, October 11, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 4, October 12, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments if needed. Old Business/New Business/Review Dates and Times for Future Meetings/Review new standards process/TGs/Conclusion.

Technical Committee on Lightning Protection ROC Meeting Agenda

  • Upload
    dokien

  • View
    213

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Technical Committee on Lightning Protection ROC Meeting Agenda

National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

Technical Committee on Lightning Protection

ROC Meeting Agenda

October 9-12, 2012 Orlando, FL

Day 1, October 9, 2012: 0800: Call to Order. 0800-0830: Roll Call/ Opening Remarks/Approval of Meeting Agenda/Approval of Meeting Minutes. 0830-0900: Introduction, 2014 cycle schedule recap, administrative topics. 0900-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 2, October 10, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 3, October 11, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments. 1200-1300: Lunch. 1300-1630: Address comments. 1630-1700: Review actions. Day 4, October 12, 2012: 0800: Call to Order. 0800-0830: Introduction, administrative topics. 0830-1200: Address comments if needed. Old Business/New Business/Review Dates and Times for Future Meetings/Review new standards process/TGs/Conclusion.

Page 2: Technical Committee on Lightning Protection ROC Meeting Agenda

Minutes of the Technical Committee on Standard for the Installation of Lightning Protection Systems of March 29, 2012

Item 12-3-1, Call to Order John Tobias, Chair, called the Meeting/Conference call of March 21, 2011 to order at 1:00 pm (EASTERN). Item 12-3-2, Roll Call Participants: John Tobias Robert Daley Douglas Franklin Mitchell Guthrie Thomas Harger David McAfee Robley Melton Victor Minak Mark Morgan Luke Pettross Terrance Portfleet Robert Rapp Lon Santis Russell Stubbs Richard Bouchard Stephen Humeniuk Staff: Richard Roux Attendance was sixteen (16), and one NFPA staff, for a total of seventeen (17) attendees. Item 12-3-3, Opening Remarks The Chair thanked all for their participation. Item 12-3-4, Approval of Meeting Agenda The meeting agenda was approved. Item 12-3-5, Review of Proposal ROP 780-23 (Log #70) Staff explained that during the processing of the ROP, it was noted that ROP 780-23 was incomplete as several sections were not carried into the proposal by the committee action as intended. After review and discussion by the TC, it was moved, seconded and unanimously voted affirmatively to accept the revised text. The text would be placed in the ROP replacing existing ROP 780-23 (Log #70).

Item 12-3-6, Old Business

Page 3: Technical Committee on Lightning Protection ROC Meeting Agenda

None Item 12-3-7, New Business Staff noted that the ROC is scheduled for Orlando, October 9 – 12. The meeting will end at noon on the 12th. Item 12-3-8, Review Dates and Times for Future Conference Calls No future Meeting/Conference call is scheduled. The Chair noted that when the ROP is printed and the draft available, he will reconvene some of the Task Groups. Item 12-3-9, Adjournment and Closing Remarks John Tobias thanked all for their participation. The meeting/conference call adjourned at 10:00 am (EASTERN).

Page 4: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-1 Log #30

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

N/AThere is some introduction of reversing the English and Metric designation priorities with changes

by various Proposals.We need consistency.

_______________________________________________________________________________________________780-2 Log #63

_______________________________________________________________________________________________Matthew Caie, ERICO, Inc.

780-5None provided.

Conflict over Committee Scope and Document Scope.Document now stating scope over an area not covered in the scope of the committee as stated in the document.

Propose to expand ROP-5 to address/adjust accordingly committee scope.A.1.1.2 also needs to be updated in line with scope.

_______________________________________________________________________________________________780-3 Log #1

_______________________________________________________________________________________________John F. Bender, UL LLC

780-6Revise text to read as follows:

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062–2096.ANSI/UL 1449, , Third Edition, September 29, 2006, Revised 2011.

This proposal is being re-submitted with updated revision dates as indicated, with the request that thecommittee reconsider adding such revision dates, in addition to the initial publication date of the standard, to reflect themost recent technical update of the standard as revised from time to time by the UL Standard Technical Panelresponsible for each of the respective standards. Reference to the initial publication date of the standard and anysubsequent revision date for that standard is consistent with almost all other NFPA Standards, such as NFPA 72 andNFPA 101 as two prime examples.

_______________________________________________________________________________________________780-4 Log #81

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-108Add new text:

3.3.2 Bonded (Bonding) (For the purposes of Chapter II only). Connected to establish electrical continuity andconductivity. [70:2011]

Text clarifies that this definition of bonding applies only to Chapter 11. The existing definition forbonding applies to the rest of the document.

1Printed on 9/18/2012

Page 5: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-5 Log #32

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-108Revise Definition of Couterpoise Conductor to read as follows:

A bare underground electrical conductor providing an area of protection from the effects of lightning for undergroundraceway(s) or cable(s).

The counterpoise conductor functions to protect from surges originating at another point of strike, notjust if that particular circuit is struck.

_______________________________________________________________________________________________780-6 Log #44

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aAdd new definition for I

Shows up in Section 4.15.3 and we have not defined this within our document.

_______________________________________________________________________________________________780-7 Log #45

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aAdd new definition for

Shows up in Section 4.15.3.1 and we have not defined this within our document.

_______________________________________________________________________________________________780-8 Log #33

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-7Revise text to read as follows:

byship should be changed to by shipGrammatical form correction.

_______________________________________________________________________________________________780-9 Log #17

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Revise text to read as follows:

Shoulder Pavement. Pavement designed to provide support of an aircraft for unintentional oremergency operations of the aircraft.

Shoulder pavement definition should be included under the overall 3.3.32 Pavement grouping with theother pavement related definitions. Consistent with approved ROP-108 text.Renumber definitions starting at 3.3.34.

2Printed on 9/18/2012

Page 6: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-10 Log #31

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-6a....ground electrode..... should be changed to .....grounding electrodes....

To maintain the same terminology as paragraph 3.3.18.

_______________________________________________________________________________________________780-11 Log #56

_______________________________________________________________________________________________Mitchell Guthrie, Independent Engineering Consultant

780-11Do not delete "ordinary" in Section 4.1.1.1(1).

In deleting "ordinary" from Section 1.1.1(1) there is no need to add anything else in the list as they areall structures with various occupancies and the list makes no sense. Ordinary is needed to identify the differencebetween (1) and the other items in the list. A less preferred option would be to add "with ordinary occupancies" to"structures" in (1).

_______________________________________________________________________________________________780-12 Log #34

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-13aRevise text to read as follows:

Beside or under 57,400 cir mils, add 2 AWG and beside or under 26,240 cir mils, add 6 AWG.The reader may not have the proper wire chart and it is a simple thing to add the common designation

of wire size. We have AWG listed for each strand already, so there is no introduction of something new.

_______________________________________________________________________________________________780-13 Log #35

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-13aRevise text to read as follows:

Beside or under 115,000 cir mils, add 2/0 and beside or under 26,240 cir mils, add 6 AWG.The reader may not have the proper wire chart and it is a simple thing to add the common designation

of wire size. We have AWG listed for each strand already, so there is no introduction of something new.

_______________________________________________________________________________________________780-14 Log #72

_______________________________________________________________________________________________John M. Tobias, US Army Communications Electronics Command

780-16Revise as follows:

4.1.2.4 Protection for a shed roof shall be as illustrated for the gable method typical roof types shall be as illustrated inFigure 4.1.2.4. Spacing of air terminals shall comply with 4.8.1. (Section 4.8.1 moves to 4.7.2 in ROP edition.)

Statement adds clarity to the application of the figures and affirms that the air terminal spacingrequirements remain in effect for these permitted protection schemes.

3Printed on 9/18/2012

Page 7: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-15 Log #74

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-23

****Insert Include 780_L74_R.doc Here

The Joint Strike Termination/Modeling Task Groups recognized the original intent of reorganizing thesesections was not fully accomplished by the TC Meeting action on this proposal. The intent was to organize the sectionssuch that requirements for strike termination devices were first, followed by descriptions and requirements for locatingstriketermination devices on the various types of roofs and objects on roofs. These requirements are then followed byrequirements for determining where strike termination devices are not required using the protective angle methods formultiple roof levels and finally the rolling sphere method. The Joint Task Groups feel this reorganized text meets theintent. The submitter realizes that other proposals and comments will change this text. The purpose of this comment isset the order of these three sections.

_______________________________________________________________________________________________780-16 Log #64

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-19Revise text to read as follows:

A fixed metal object that has moveable components shall be allowed to be used as a strike termination deviceunder the following conditions.(1) The highest surface is greater than 4.8 m (3/16 in.) thick in accordance with Section 4.6.1.4.(2) The fixed portion is attached to the lightning protection system in accordance with Section 4.9.(3) The point of articulation between the fixed portion and the moveable portion is constructed entirely of metal.(4) All other portions of the device are electrically continuous.

The committee's reason to reject is invalid. The suggested change complies with the definition ofStrike Termination Device as set forth in Section 3.3.29 and Section 4.9 Conductors that Section 3.3.29 improperlyreferences. Section 3.3.29 should reference Section 4.8 Strike Termination Devices on Roofs, which also does notconflict with the proposal as set forth. There is another reference to Strike Termination Devices; Section 4.16.2 whichalso does not provide any contradictory criteria to that set forth in this proposal.

4Printed on 9/18/2012

Page 8: Technical Committee on Lightning Protection ROC Meeting Agenda

FORM FOR COMMENT ON NFPA REPORT ON PROPOSALS All Comments Must Be Received by 5:00 pm EST/EDST

on the Published Comment Closing Date

For further information on the standards-making process, please contact the Codes and Standards Administration at 617-984-7249 or visit www.nfpa.org/codes.

For technical assistance, please call NFPA at 1-800-344-3555.

FOR OFFICE USE ONLY

Log #:

Date Rec’d:

Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: If choosing the download option, you must view the ROP/ROC from our website; no copy will be sent to you.)

Date 8/30/2012 Name Thomas R. Harger Tel. No. 847-543-5028

Company Harger, Inc. Email [email protected]

Street Address 301 Ziegler Drive City Grayslake State IL Zip 60030

***If you wish to receive a hard copy, a street address MUST be provided. Deliveries cannot be made to PO boxes.

Please indicate organization represented (if any)

1. (a) NFPA Document Title Standard for the Installation of Lightning Protection Systems

NFPA No. & Year 780-2011

(b) Section/Paragraph 4.6, 4.7, and 4.8

2. Comment on Proposal No. (from ROP): 780-23

3. Comment Recommends (check one): new text revised text deleted text

4. Comment (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text

should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording).]

Reorganize sections 4.6 through 4.8 as follows:

4.6 Strike Termination Devices.

4.6.1 General.

4.6.1.1 Strike termination devices shall include air terminals, metal masts, permanent metal parts of

structures as described in 4.6.1.4, and overhead ground wires.

4.6.1.2 Combinations of these strike termination devices shall be permitted.

4.6.1.3 Strike termination devices shall be provided where required by other sections of this standard.

4.6.1.4 Metal parts of a structure that are exposed to direct lightning flashes and that have a metal thickness

of 4.8 mm (3⁄16 in.) or greater shall require only connection to the lightning protection system in accordance

with Section 4.7.

4.6.1.5 Strike termination devices shall not be required for those parts of a structure located within a zone

of protection.

4.6.2 Air Terminals.

4.6.2.1* The tip of an air terminal shall be not less than 10 in (254 mm) above the object or area it is to

protect, as shown in Figure 4.6.2.1.

Page 9: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.6.2.1 Air Terminal Height.

4.6.2.2 Air Terminal Support.

4.6.2.2.1 Air terminals shall be secured against overturning or displacement by one of the following

methods:

(1) Attachment to the object to be protected

(2) Braces that are permanently and rigidly attached to the structure

4.6.2.2.2 Air terminals exceeding 600 mm (24 in.) in height shall be supported at a point not less than one-

half their height, as shown in Figure 4.6.2.2.2.

Page 10: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.6.2.2.2 Air Terminal Support.

4.6.2.3 Ornaments.

4.6.2.3.1 An ornament or decoration on a freestanding, unbraced air terminal shall not present, in any plane,

a wind-resistance area in excess of 0.01 m2 (20 in.2).

4.6.2.3.2 The requirement of 4.6.2.3.1 shall permit the use of an ornamental ball 127 mm (5 in.) or less in

diameter.

4.6.3 Lightning Protection Masts.

4.6.3.1 Lightning protection masts shall be permitted to provide a zone of protection.

4.6.3.2 Metal masts shall comply with 4.6.1.4 or be protected with a strike termination device.

4.6.3.3 Nonmetallic masts shall be provided with at least one strike termination device.

4.6.3.4 The top of the metallic mast shall have a metal thickness of 4.8 mm (3⁄16 in.) or greater or be

provided with at least one strike termination device.

4.6.3.5 The mast shall be permitted to serve as the down conductor, provided it is electrically continuous

and has a wall thickness of 1.63 mm (0.064 in.) minimum.

4.6.4 Overhead Ground Wires.

4.6.4.1 Overhead ground wires shall be permitted to provide a zone of protection.

4.6.4.2 Overhead ground wire material shall be constructed of aluminum, copper, stainless steel, galvanized

steel, or protected steel such as copper-clad, aluminum-clad, or aluminum conductor steel reinforced

(ACSR).

4.6.4.3 The overhead ground wire material shall be chosen to minimize corrosion from conditions at the

site.

4.6.4.4 The overhead ground wire shall be sized to have the same cross-sectional area as a main lightning

conductor and shall be self-supporting with minimum sag under all conditions.

4.6.5* Isolated Masts and Overhead Ground Wires. To prevent sideflashes, the minimum distance

between a mast or overhead ground wire and the structure to be protected shall be calculated.

4.6.5.1 Sideflash distance from a mast shall be calculated from the following formula:

where:

D = sideflash distance from a mast

h = height of structure (or object being calculated)

4.6.5.2 The sideflash distance from an overhead ground wire shall be calculated as follows:

where:

D = sideflash distance from a mast or overhead ground wire

l = length of lightning protection conductor between its grounded point and the point being calculated

n = 1 where there is one or less overhead ground wire that exceeds 30 m (100 ft) in horizontal length

n = 1.5 where there is one or two down conductors spaced greater than 7.6 m (25 ft) and less than 30 m

(100 ft) apart

Page 11: Technical Committee on Lightning Protection ROC Meeting Agenda

n = 2.25 where there are more than two down conductors spaced more than 7.6 m (25 ft) apart within a 30

m (100 ft) wide area that are interconnected above the structure being protected

4.7 Strike Termination Devices on Roofs.

4.7.1 Roof Types. Protection requirements for the following roof types shall include the roof and

appurtenances in accordance with this Section:

(1) Pitched roofs

(2) Flat or gently sloping roofs

(3) Dormers

(4) Domed roofs

(5) Roofs with ridges, wells, chimneys, or vents

4.7.1.1 Pitched roofs shall be defined as roofs having a span of 12 m (40 ft) or less and a slope 1/8 or greater,

and roofs having a span of more than 12 m (40 ft) and a slope 1/4 or greater.

4.7.1.2 A flat or gently sloping roof is defined as a roof with a slope less than a pitched roof.

4.7.1.3 For purposes of this standard, roof pitches shall be as shown in Figure 4.7.1.3.

FIGURE 4.7.1.3 Roof Slope

4.7.1.4 Protection for typical roof types shall be as illustrated in Figure 4.7.1.4.

Page 12: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.1.4 Protection Measures for Various Roof Types

(Drawings are top and end views of each roof type.)

4.7.1.5 Roof hips shall not be considered as ridges for the protection of these types of roofs.

4.7.2* Location of Devices.

4.7.2.1 As shown in Figure 4.7.2.1, the distance between strike termination devices and ridge ends on

pitched roofs, or edges and outside corners of flat or gently sloping roofs, shall not exceed 0.6 m (2 ft).

Page 13: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.2.1 Air Terminals on a Pitched Roof.

4.7.2.2 Strike termination devices shall be placed on ridges of pitched roofs, and around the perimeter of

flat or gently sloping roofs, at intervals not exceeding 20 ft (6 m).

4.7.2.3 Strike termination devices 2 ft (0.6 m) or more above the object or area to be protected shall be

permitted to be placed at intervals not exceeding 25 ft (7.6 m).

4.7.3 Pitched Roof Areas

4.7.3.1 For pitched roofs with eave heights over 15 m (50 ft) but less than46 m (150 ft) above grade, it shall

be permitted to omit strike termination devices at the eaves if the slope of that roof is equal to or steeper than

the tangent of the arc at the eave elevation of a rolling sphere having a 46 m (150 ft) radius. (See Figure

4.7.3.1.)

Page 14: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.3.1 Illustration of Tangent of Rolling Sphere Method.

4.7.3.2 Except for the gutter, any portion of the building that extends beyond that tangent shall be protected.

4.7.3.4 Eaves over 150 ft (46 m) above grade shall be protected in accordance with 4.7.2.

4.7.3.5 The tangent of the rolling sphere arc shall be considered a vertical line over 46 m (150 ft) above

grade, except as permitted by 4.8.2.4.

4.7.3.6 Roofs with Intermediate Ridges. Strike termination devices shall be located along the outermost

ridges of buildings that have a series of intermediate ridges at the same intervals as required by 4.7.1.

4.7.3.7.1 Strike termination devices shall be located on the intermediate ridges in accordance with the

requirements for the spacing of strike termination devices on flat or gently sloping roofs.

4.7.3.7.2 If any intermediate ridge is higher than the outermost ridges, it shall be treated as a main ridge and

protected according to 4.7.1.

4.7.4 Flat or Gently Sloping Roofs. Flat or gently sloping roofs that exceed 50 ft (15 m) in width or length

shall have additional strike termination devices located at intervals not to exceed 50 ft (15 m) on the flat or

gently sloping areas, as shown in Figure 4.7.4(a) and Figure 4.7.4(b), or such area can also be protected using

taller strike termination devices that create zones of protection using the rolling sphere method so the sphere

does not contact the flat or gently sloping roof area.

Page 15: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.4(a) Air Terminals on a Flat Roof.

FIGURE 4.7.4(b) Air Terminals on a Gently Sloping Roof.

4.7.5 Flat or Gently Sloping Roofs with Irregular Perimeters. Structures that have exterior wall designs

that result in irregular roof perimeters shall be treated on an individual basis.

4.7.5.1 The imaginary roof edge formed by the outermost projections shall be used to locate the strike

termination devices in accordance with 4.7.1.

4.7.5.2 In all cases, however, strike termination devices shall be located in accordance with Section 4.7 as

Page 16: Technical Committee on Lightning Protection ROC Meeting Agenda

shown in Figure 4.7.6.2.

FIGURE 4.7.5.2 Flat or Gently Sloping Roof with an Irregular Perimeter.

4.7.6* Dormers.

4.7.6.1 Dormers as high as or higher than the main roof ridge shall be protected with strike termination

devices, conductors, and grounds.

4.7.6.2 Dormers and projections below the main ridge shall require protection only on those areas

extending outside a zone of protection.

4.7.7 Strike termination devices installed on vertical roof members shall be permitted to use a single main-

size cable to connect to a main roof conductor.

4.7.7.1 The main roof conductor shall be run adjacent to the vertical roof members so that the single cable

from the strike termination device is as short as possible and in no case longer than 4.9 m (16 ft).

4.7.7.2 The connection of the single cable to the down conductor shall be made with a tee splice or other

fitting listed for the purpose, as shown in Figure 4.7.6.2.

Page 17: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.7.2 Irregular Roof Perimeter.

4.7.8 Open Areas in Flat Roofs. The perimeter of open areas, such as light or mechanical wells, shall be

protected if the open area perimeter exceeds 92 m (300 ft), provided both rectangular dimensions exceed 15

m (50 ft).

4.7.9 Domed or Rounded Roofs. Strike termination devices shall be located so that no portion of the

structure is located outside a zone of protection, as set forth in Section 4.8.

4.7.10 Chimneys and Vents. Strike termination devices shall be required on all objects on roofs that are not

located within a zone of protection, including metal having a metal thickness of less than 4.8 mm (3⁄16 in.).

4.7.10.1 Chimneys or vents with a metal thickness of 4.8 mm (3⁄16 in.) or more shall require connection to

the lightning protection system.

4.7.10.2 The connection for 4.7.9.1 shall be made using a main size lightning conductor and a connector

that has a surface contact area of not less than 1940 mm2 (3 in.2) and shall provide two or more paths to

ground, as is required for strike termination devices.

4.7.10.3* Required strike termination devices shall be installed on objects on roofs, as shown in Figure

4.7.10.3, so that the distance from a strike termination device to an outside corner or the distance

perpendicular to an outside edge is not greater than 0.6 m (2 ft).

Page 18: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.7.10.3 Air Terminals on a Chimney.

4.7.10.4 Where only one strike termination device is required on a an object, at least one main-size

conductor shall connect the strike termination device to a main conductor at the location where the object

meets the roof surface and provides two or more paths to ground from that location in accordance with

Section 4.9 and 4.9.2.

4.7.11 Metal Roof Top Units. Strike termination devices shall be required in accordance with 4.7.10.1

through 4.7.10.3.2 on all roof top mechanical units with continuous metal housings less than 4.8 mm (3⁄16 in.)

thick such as air-conditioning/heating units, metal air intake/exhaust housings, and cooling towers, that are

not located in a zone of protection.

4.7.11.1 Air terminals shall be installed in accordance with 4.7.1 through 4.7.3.

4.7.11.2 The air terminals shall be mounted on bases having a minimum contact area of 1940 mm2 (3 in.2),

each secured to bare metal of the housing or mounted by drilling and tapping to the unit's frame in

accordance with 4.16.3.2 and 4.16.3.3.

4.7.11.3 At least two main-size conductors shall be installed to connect the unit to the lightning protection

system.

4.7.11.3.1 The connection shall be made to bare metal at the base or lower edges of the unit using main-size

lightning conductors and bonding devices that have a surface contact area of not less than 1940 mm2 (3 in.2)

and shall provide two or more paths to ground, as is required for strike termination devices.

4.7.11.3.2 The two main bonding plates shall be located as far apart as practicable at the base or lower

edges of the unit's electrically continuous metal housing and connected to the lightning protection system.

4.8 Zones of Protection. The geometry of the structure shall determine the zone of protection.

4.8.1 One or more of the methods described in 4.7.1 through 4.8 shall be use to determine the overall zone

of protection.

Page 19: Technical Committee on Lightning Protection ROC Meeting Agenda

4.8.2 Multiple-Level Roofs.

4.8.2.1 For structures with multiple-level roofs no more than 15 m (50 ft) in height, the zone of protection

shall include areas as identified in 4.8.2.3 and 4.8.2.4.

4.8.2.2 The zone of protection shall be permitted to be delineated by a cone with the apex located at the

highest point of the strike termination device, with its surface formed by a 45-degree or 63-degree angle from

the vertical, based on the height of the strike termination device above the ground as defined in 4.8.2.3 and

4.8.2.4.

4.8.2.3 Structures that do not exceed 7.6 m (25 ft) above earth shall be considered to protect lower portions

of a structure located within a one-to-two zone of protection as shown in Figure 4.8.2.3(a) and Figure 4.8.2.3

(b).

FIGURE 4.8.2.3(a) Lower Roof Protection for Flat-Roof Buildings 7.6 m (25 ft) or Less in Height.

FIGURE 4.8.2.3 (b) Lower Roof Protection Provided by Pitched-Roof Buildings 7.6 m (25 ft) or Less

in Height.

4.8.2.4* Structures that do not exceed 15 m (50 ft) above earth shall be considered to protect lower portions

of a structure located within a one-to-one zone of protection as shown in Figure 4.8.2.4(a) and Figure

4.8.2.4(b).

Page 20: Technical Committee on Lightning Protection ROC Meeting Agenda

FIGURE 4.8.2.4 (a) Lower Roof Protection for Buildings 15 m (50 ft ) or Less in Height.

FIGURE 4.8.2.4 (b) Lower Roof Protection Provided by Pitched-Roof Buildings 15 m (50 ft) or Less

in Height.

4.8.3 Rolling Sphere Method.

4.8.3.1* The zone of protection shall include the space not intruded by a rolling sphere having a radius of the

striking distance determined for the type of structure being protected, as shown in Figure 4.8.3.1.

FIGURE 4.8.3.1 Zone of Protection Depicting Rolling Sphere Method.

4.8.3.1.1 Where the sphere is tangent to earth and resting against a strike termination device, all space in

the vertical plane between the two points of contact and under the sphere shall be considered to be in the zone

of protection.

Page 21: Technical Committee on Lightning Protection ROC Meeting Agenda

4.8.3.1.2 A zone of protection shall also be formed where such a sphere is resting on two or more strike

termination devices and shall include the space in the vertical plane under the sphere and between those

devices, as shown in Figure 4.8.3.1

4.8.3.1.3 All possible placements of the sphere shall be considered when determining the overall zone of

protection using the rolling sphere method.

4.8.3.1.4 The striking distance shall not exceed 46 m (150 ft).

4.8.3.2* For structure heights exceeding the striking distance above earth or above a lower strike termination

device, the zone of protection shall be the space in the vertical plane between the points of contact, and also

under the sphere where the sphere is resting against a vertical surface of the structure and the lower strike

termination device(s) or earth.

4.8.3.3 Under the rolling sphere method, the horizontal protected distance found geometrically by Figure

A.4.8.3.1 also shall be permitted to be calculated using the following formula (units shall be consistent, m or

ft):

where:

d = horizontal protected distance (m or ft)

h 1 = height of the higher roof (m or ft)

R = rolling sphere striking distance radius (m or ft)

h 2 = height of the lower roof (top of the object)(m or ft)

4.8.3.3.1 For the formula to be valid, the sphere shall be either tangent to the lower roof or in contact with

the earth, and in contact with the vertical side of the higher portion of the structure.

4.8.3.3. 2 In addition, the difference in heights between the upper and lower roofs or earth shall be the

striking distance or less.

Also: Renumber existing Annex A items as follows:

Old A.4.7.3.4 to new A.4.8.2.4

Old figure A.4.7.3.4 to Figure A.4.8.2.4

Old A.4.7.4.1 to new A.4.8.3.1

Old Figure A.4.7.4.1 to Figure A.4.8.3.1

OldA.4.7.4.2 to new A.4.8.3.2

Old A.4.8.1 to new A.4.7.2

Old A.4.8.4 to new A.4.7.6

Old Figure A.4.8.4 to new Figure A.4.7.6

Old A.4.8.9.3 to new A.4.7.10.3

5. Statement of Problem and Substantiation for Comment: (Note: State the problem that would be resolved by your

recommendation; give the specific reason for your Comment, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.)

The Joint Strike Termination/Modeling Task Groups recognized the original intent of reorganizing these sections was not fully accomplished by the TC Meeting action on this proposal. The intent was to organize the sections such that requirements for strike termination devices were first, followed by descriptions and requirements for locating strike termination devices on the various types of roofs and objects on roofs. These requirements are then followed by requirements for determining where strike termination devices are not required using the protective angle methods for multiple roof levels and finally the rolling sphere method. The Joint Task Groups feel this reorganized text meets the intent. The submitter realizes that other proposals and comments will change this text. The purpose of this comment is set the order of these three sections.

Page 22: Technical Committee on Lightning Protection ROC Meeting Agenda

6. Copyright Assignment

(a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Comment.

(b) Some or all of the text or other material proposed in this Comment was not authored by me. Its source is as

follows: (please identify which material and provide complete information on its source)

Text is a reorganization of current text of NFPA 780-2011

I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Comment and that I have full power and authority to enter into this assignment.

Signature (Required)

PLEASE USE SEPARATE FORM FOR EACH COMMENT

Mail to: Secretary, Standards Council ∙ National Fire Protection Association 1 Batterymarch Park ∙ Quincy, MA 02169-7471 OR

Fax to: (617) 770-3500 OR Email to: [email protected] 9/10/2012

Page 23: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-17 Log #84

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc.

780-20Revise Figure 4.6.2.2.2 so that the leader for dimension "A" extends down to the support point.

****Insert Artwork Here****Figure 4.6.2.2.2

Bottom of leader points to top of parapet which is not the point of support as stated in the text. Asshown, it would be interpreted to be 24 inches above the top of the parapet.

_______________________________________________________________________________________________780-18 Log #36

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-21Propose the addition of drawings or sketches to illustrate the use of n=1, n=1.5 and n=2.25, and a

re-Iook at the wording of the description for when each "n" is used.With typical overhead systems, the masts are always greater than 100 feet apart, so 1.5 and 2.25

might rarely be applicable, as written. Even if masts are tied together in a grid-type system (two overhead wires off thesame mast), at a distance between masts of greater than 100 feet we could never meet the "more than 25 feet within a100 foot wide area" because the "interconnection" is basically at a distance of zero. I see the "100 foot wide area" as a100 foot radius. The intent of the distances in this section is unclear.

_______________________________________________________________________________________________780-19 Log #38

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-21Add new text to read as follows:

Add the asterisk to note additional information in the appendix (if separate comment is accepted).

5Printed on 9/18/2012

Page 24: Technical Committee on Lightning Protection ROC Meeting Agenda
Page 25: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-20 Log #73

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-21Revise 4.6.5.2 as follows:

4.6.5.2 The sideflash distance from an overhead ground wire shall be calculated as follows:

****Insert Equation 4.6.5.2 Here****

where:

= sideflash distance from a mast or overhead ground wire= length of lightning protection conductor between its grounded point and the point being calculated= 1 where there is one or less overhead ground wire that exceeds 30 m (I 00 ft) in horizontal length= 1.5 where there is one or two down conductors connected to the overhead ground wire spaced greater than 7.6 m

(25 ft) and less than 30 m (100 ft) apart along the length of the overhead ground wire.= 2.25 where there are more than two down conductors connected to the overhead ground wire spaced more than 7.6

m (25 ft) apart within a and less than 30 m (100 ft) wide area that are interconnected above the structure beingprotected apart along the length of the overhead ground wire.

Add new Figure 4.6.5.2.

****Insert Artwork Figure 4.6.5.2 Here****

Revised text clarifies that down conductors must be connected to the overhead ground wire and that r ismeasured along the wire, not just in the "area"Figure is added to show an example of how n = 2.25.

_______________________________________________________________________________________________780-21 Log #65

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-23Review text as written and edit to comply with the manual of style.

Language as set forth does not meet the criteria as set forth in the manual of style.

6Printed on 9/18/2012

Page 26: Technical Committee on Lightning Protection ROC Meeting Agenda

NFPA 780 L73 Rec A2013 ROC

𝐷 =𝑙

6𝑛

Page 27: Technical Committee on Lightning Protection ROC Meeting Agenda

780_L73_Figure 4.6.5.2_ROC_A2013

Page 28: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-22 Log #77

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-29Revise as follows:

4.7.11.2' Movable or rotating metal objects on roofs that do not pose an additional sideflash hazard to the protectedstructure shall be pennitted to be connected to the lightning protection system in accordance with 4.7.9.1

Add Annex material:A.4.7.11.2 Examples include windsocks, window washing davits and weathervanes where connection of the supportingmasts or sockets to the lightning protection system comply with the requirements of Chapter 4 and arcing within themetal object will not damage the protected structure.

Changes in requirement attempt to clarify actual hazard and offer relief where acceptable. Annexmaterials were added to further explain intent.

_______________________________________________________________________________________________780-23 Log #39

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-26Revise text to read as follows:

To integrate with adjacent numbering system and numbered paragraphs.

_______________________________________________________________________________________________780-24 Log #75

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-26Add missing text as indicated in TC action.

4.8.2.2 For pitched roofs with a span of 30 m (100 ft) or less and eave heights greater than or equal to 15 m (50 ft) butless than 46 m (150 ft) above grade, it shall be permitted to omit strike termination devices at the eaves if the slope ofthat roof is equal to or steeper than the tangent of the arc at the eave elevation of a rolling spherehaving a 46 m (150 ft) radius.

Added text appeared in 780-2011 and the submitters proposal but was inadvertently left out of thecommittee action.

7Printed on 9/18/2012

Page 29: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-25 Log #76

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-27Revise text of committee action as follows:

4,8.9 Chimneys, Vents and Other Objects on Roofs not in a zone of protection. Strike termination devices shall berequired on all objects on roofs that are not located within a zone of protection, including metal objects having a metalthickness of less than 4.8 mm (~6 in.) except as permitted in this section.4.8.9.1 Metal objects on roofs not located in a zone of protection with a metal thickness of 4.8 mm (3/16 in.) or moreshall require connection to the lightning protection system using a main-size lightning conductor and a main-sizeconnector in accordance with thc following:(1) Has a surface contact area of not less than 1940 mm2 (3 in.2) or a minimum of 38 mm (1 1/2 in.) of contact along theaxis of a round surface(2) Provide two or more paths to ground, as is required for strike termination devices.4.8.9.2* Required strike termination devices shall be installed on objects on roofs, as shown in Figure 4.8.9.2, so thatthe distance from a strike termination device to an outside comer or the distance perpendicular to an outside edge is notgreater than 0.6 m (2 ft).4.8.9.3 Where only one strike termination device is required on a an object, at least one main-size conductor shallconnect the strike termination device to a main conductor at the location where the object meets the roof surface andprovides two or more paths to ground from that location in accordance with Section 4.9 and 4.9. 2.4.8.9.4 Small o Objects on roofs that arc less than 254 mm (10 in.) above the surface of the roof shall not require striketermination devices unless they are located within 0.9 m (3 ft) of the ridge or roof edge.

In 4.8.9. 4.8.9.1 and 4.8.9.2 the Objects may not be located on the roof. They may be located alongside the roof but extend above the roof.In 4.8.9.1 it is important that a main·size connector be used.In 4.8.9.3 the word "Small" is vague and not necessary in this case.

_______________________________________________________________________________________________780-26 Log #40

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-29Revise text to read as follows:

or lighting masts should be changed to or a mast systemThere is no definition or terminology elsewhere in this document specified as "lightning masts."

Consistency would be achieved with this change.

8Printed on 9/18/2012

Page 30: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-27 Log #66

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-32Modify the existing text as follows:

4.10.1 Attached by nails, screws, bolts or adhesive as necessary, the fasteners shall not be subject to breakage.4.10.2 Fasteners shall be of the same materials as the conductor or of a material equally resistant to corrosion as that

of the conductor.Renumber existing Sections 4.10.2 to Section 4.10.3.

The existing text does not conform to the Manual of Style. There is more than one requirement in thistext. A committee proposal was put forward at the ROP meeting that was not addressed.

_______________________________________________________________________________________________780-28 Log #29

_______________________________________________________________________________________________Mark P. Morgan, East Coast Lightning Equipment, Inc.

780-34Add new text\ as follows:

4.13.1.1 Each down conductor shall terminate at a grounding electrode dedicated to the lightning protection system orto a grounding electrode system in the case of a building, structure or facility that has multiple grounding electrodes thatare bonded together with a ground ring electrode to form the grounding electrode system.The size of the ground ring electrode shall be equal to or greater than that of a main size conductor found in Table

4.1.1.1.1 and 4.1.1.1.1.2.The original proposal addresses a problem but some guidance is needed with regard to conductor size

for Class I and Class II installations.

_______________________________________________________________________________________________780-29 Log #78

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc.

780-34Add text as follows:

4.13.1.1 Each down conductor shall terminate at a grounding electrode dedicated to the lightning protection system or toa grounding electrode system in the case of a building, structure or facility that has multiple grounding electrodes thatare bonded together with a ground ring electrode sized in accordance with 4.13.4.2 to form the grounding electrodesystem.

Text is added to ensure that the facility ground electrode system meets the requirements for a main-sizeconductor.

9Printed on 9/18/2012

Page 31: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-30 Log #60

_______________________________________________________________________________________________Richard Kithil, National Lightning Safety Institute

780-37Add: "galvanized steel is an acceptable material for grounding purposes."

Justification:The electric power industry uses galvanized steel below grade for substation grounding. This practice has been in

effect for 100+ years.

_______________________________________________________________________________________________780-31 Log #41

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-37The ground ring electrode shall be a main-size lightning conductor as specified in Table 4.1.1.1.1

or a grounding conductor of equivalent or greater cross-sectional area.Two sizes of main-size conductors are listed in 4.1, depending on height.

_______________________________________________________________________________________________780-32 Log #42

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-37The ground ring electrode shall be a Class I main-size lightning conductor, or a grounding

conductor of equivalent or greater cross-sectional area.There are two main-size conductors, Class I and Class II.

Tables 4.1.1.1.1 and 4.1.1.1.2 call them main-size conductors, not main size lightning conductors.

10Printed on 9/18/2012

Page 32: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-33 Log #55

_______________________________________________________________________________________________Mitchell Guthrie, Independent Engineering Consultant

780-38Add an asterisk to 4.13.8.1.2 and add the following new text to Annex A:

For applications involving shallow topsoil, the overall earth resistivity is generally high; leading to a highgrounding system resistance. In such applications, the use of radials extending from the structure is encouraged.However, the high earth resistivity may require a greater radial length than that specified in Section 4.13.5. It is

recommended that the length of radials used in these applications meet the criteria for Type II lightning protectionsystem as shown in the graph below.

******Insert Figure A.4.13.8.1.2 Here******

This section deals with an application where there is insufficient topsoil to meet the standardrequirements in Section 4.13. For such applications, it is suggested that the overall earth resistivity is increased and theuse of radials is typically the preferred grounding system electrode solution. Since this requirement is applicable for allapplications, it is suggested that the user be encouraged to select a radial length that meets the lEe 62305-3requirements for Type II lightning protection system.

_______________________________________________________________________________________________780-34 Log #5

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-115Delete asterisk:

4.14* Common Grounding Bonding of Grounded Systems.

There is no annex material referenced to this title (paragraph) – delete asterisk

_______________________________________________________________________________________________780-35 Log #43

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-40Delete text as follows:

"...due to the use of plastic pipe sections or other reasons, the"Not necessary verbiage.

11Printed on 9/18/2012

Page 33: Technical Committee on Lightning Protection ROC Meeting Agenda

A2013/ROC/NFPA 780/Log #55/Figure A.4.13.8.1.2/Rec

Page 34: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-36 Log #4

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-40Revise text to read as follows:

4.14.6 Where bonding of the lightning protection grounding system, grounded media, and buried metallic conductorshas not been accomplished at a common point, interconnection shall be provided according to the following:(1) Grounded media and buried metallic conductors shall be bonded to the lightning protection grounding system below

a height 12 ft. (3.6 m) vertically above the base of the structure.(2) Grounded media and buried metallic conductors inherently bonded through construction to the lightning protection

grounding system shall not require further bonding.(3) The continuous metal framework of a structure shall be connected to the lightning protection system (See 4.9.13

and 4.16 4.19).(4) Main size lightning conductors shall be used for direct connection of grounded media and buried metallic

conductors to the lightning protection system.(5) A ground bar designed for interconnection of building grounded systems shall have one connection to the lightning

protection system.(6) A continuous metal water pipe system designed for interconnection of building grounded systems shall be

connected to the lightning protection system.(7)* Interconnection to a gas line shall be made on the customer’s side of the meter.(8)* Where galvanic corrosion is a concern or where a direct bond is prohibited by local code, an isolating spark gap

shall be permitted.

Reference in item 4.14.6 (3) should be to new section 4.19, not the old section 4.16.Added asterisk to paragraph 4.14.6 (7) to designate reference for annex materials A.4.14.6 (7)

_______________________________________________________________________________________________780-37 Log #67

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-42aAll value in text and formulas have to be changed to express "English" values first.

It was the decision of the 780 Committee that all numeric values were to be expressed with the"English" Values, with the SI Values in parenthesis.

_______________________________________________________________________________________________780-38 Log #6

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-42aDelete asterisk:

4.15.1*Ground-Level Potential Equalization. Ground-level potential equalization shall be required in accordance withSection 4.14.

Annex materials moving to paragraph A.4.14.2, so there is no longer Annex materials related to 4.15.1(remove the asterisk)

12Printed on 9/18/2012

Page 35: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-39 Log #59

_______________________________________________________________________________________________Richard Kithil, National Lightning Safety Institute

780-42aRef. Section 4.15.1.1 (now 4.18.1.1 ROP 780-42a, CP5) permitting conductors carrying 50,000°F.

Lightning next to potentially flammable materials is dangerous.There is evidence that residential fires have been the result of such concealed conductors. Contact us

for photos and fire reports.

_______________________________________________________________________________________________780-40 Log #46

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aRevise text to read as follows:

The lightning protection system. Ddown conductors and other grounded media shall be interconnected with a loopconductor at intermediate levels not exceeding 60 m (200 ft).

Not necessary.

_______________________________________________________________________________________________780-41 Log #47

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aRevise text as follows:

The lightning protection system. Ddown conductors and other grounded media shall be interconnected with a loopconductor at intermediate levels not exceeding 60 m (200 ft).

Not necessary.

_______________________________________________________________________________________________780-42 Log #7

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-42aRevise text as follows:

4.16* Bonding of Metal Bodies. Metal bodies, not covered by other sections of this Standard, located outside or insidea structure that contribute to lightning hazards because they are grounded or assist in providing a path to ground forlightning currents shall be bonded to the lightning protection system in accordance with Section 4.21 .

Added asterisk (*) after 4.16 to designate Annex paragraphs which relate to this paragraph.andReference at end changed from old section 4.21 (no longer exists) to 4.16.

13Printed on 9/18/2012

Page 36: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-43 Log #48

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aRevise text as follows:

h = vertical distance between the bond being considered in question and the nearest lightning protection system bondcomponent.

"h" is a parameter that I have received many, many questions on. It appears to be unclear to thereader/user.

_______________________________________________________________________________________________780-44 Log #49

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aAdd diagram.

"h" is a parameter that I have received many, many questions on. It appears to be unclear to thereader/user.

_______________________________________________________________________________________________780-45 Log #50

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aRevise text as follows:

FIGURE 4.16.3.1 Effect of Isolated (Nongrounded) (Ungrounded) Metallic Bodies, Such as a Window Frame, inNonconductive Media.

Change to terminology consistent with codes.

_______________________________________________________________________________________________780-46 Log #79

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-42aRevise text to read as follows:

4.19.2.2 Where such an exterior conductor is used, it shall be connected to the metal framework of the structure atintervals not exceeding an average distance or 30 m ( 100 ft), as widely spaced as practicable around the perimeter ofthe building, and at intervals not exceeding a distance of 45 m (150 ft) along a cross-run conductor.

Installers and inspectors have been applying the concept in the added text to the designs of structuralmetal framed systems for many years. This change is an attempt to coordinate with standard industry practice.

14Printed on 9/18/2012

Page 37: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-47 Log #80

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-42aChange the word "steel" to metal".

4.19.3.4 Bonding plates shall have bolt-pressure cable connectors and shall be bolted, welded, or brazed to thestructural steel metal framework so as to maintain electrical continuity.

Editorial change that was missed in the 2011 cycle.

_______________________________________________________________________________________________780-48 Log #62

_______________________________________________________________________________________________Matthew Caie, ERICO, Inc.

780-42a, 780-45Revise text to read as follows:

Signal, data, and communications SPDs’ shall have a maximum discharge current ( ) rating of at least10kA 8/ 20 us or greater when installed at the entrance.

Editorial comment - as its stated at least 10kA... then term or greater is redundant.

15Printed on 9/18/2012

Page 38: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-49 Log #28

_______________________________________________________________________________________________Morris Kline, HMT Inc.

780-1aRevise text as follows:

Chapter 7 Protection for Structures Containing Flammable Liquids - suggested title change7.1.1.1 This chapter shall apply to the protection of structures containing flammable liquids.7.1.2.1 Delete7.1.2.2 Delete7.1.3* Delete7.2 through 7.2.5 Delete7.3.1 Material and Installation. Metallic aboveground storage tanks are considered inherently grounded. The use of

conductors, strike termination devices, surge protection, and grounding connections are not required for lightningprotection and have been observed to introduce a hazard. The use of strike termination devices, lightning protectionmasts and overhead ground wires on aboveground storage tanks is prohibited.7.3.2 Delete7.3.2.1 DeleteFigure 7.3.2.2 Delete7.3.2.3 Delete7.3.2.4 DeleteFigure 7.3.2.4 Delete7.3.2.5 through 7.3.2.7.4 Delete7.4.1 Metallic aboveground tanks at atmospheric pressure containing flammable vapors or liquids7.4.1.2* External Floating-Roof Tanks. Needs to be reworded completely to address the situation of an owner operator

that operates their tanks in a drain dry situation on a frequent basis. A risk analysis indicates that shunts that are locatedbelow the floating roof deck could add a hazard in this potential vapor area.7.4.1.6 Reword to: Metallic Tanks with Nonmetallic Roofs. Metallic tanks with wooden or other nonmetallic roofs shall

not be considered self-protected.7.4.1.6.1 through 7.4.1.6.4 Delete7.4.1.7 Grounding Tanks. Metallic flat-bottom tanks resting on the ground need not be grounded by the use of external

grounding rods for the purpose of lightning protection. Grounding for other purposes is not addressed by this document.7.4.1.7.1 and 7.4.1.7.2 Delete7.4.2 Delete "That give off Flammable Vapors.7.4.2.2 Aboveground nonmetallic tanks including an exposed tank roof shall not be used for storage of flammable

liquids.The API Subcommittee on Aboveground Storage Tanks (SCAST) has reviewed the changes proposed

in this ROP and is considering removing any reference to NFPA 780 from API 650 and API 653 documents. Additionally,they are moving forward to revise and improve the API RP 545 document that also addresses Lightning Protection.

_______________________________________________________________________________________________780-50 Log #52

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-67Renumber to Section 8.7 and adjust sub-paragraphs to the new number.

Section 8.7 is skipped in the new numbering.

16Printed on 9/18/2012

Page 39: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-51 Log #53

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-67Change "8.7.1.1" to the proper reference.

None given.

_______________________________________________________________________________________________780-52 Log #54

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-67Change to Section 8.8 and 8.9.

None given.

_______________________________________________________________________________________________780-53 Log #70

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-108Edit text to comply with the Manual of Style.

Some text does not comply with the Manual of Style. Section 11.4.2.6 has a note without mandatorylanguage, making it Annex material. This section also adds another definition of Bonded (bonding) as 3.3a where onealready exists under Section 3.3.2. The committee needs to decide which definition it wants.

_______________________________________________________________________________________________780-54 Log #18

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Add text to read as follows:

11.2.4 All requirements of 4.2 Materials. 4.3 Corrosion Protection. 4.4 Mechanical Damage or Displacement. 4.9.5Conductor Bends. 4.13 Grounding Electrodes and 4.14 Common Grounding shall apply. except as modified by thischapter.

Noted text was included in ROP-108 text, but omitted from published draft. Consistent with approvedROP-108 text.

17Printed on 9/18/2012

Page 40: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-55 Log #26

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Insert new paragraph 11.4.2.3 and renumber balance of section.

I When raceway is installed by the directional bore, jack and bore or other drilling method the counterpoiseconductor shall be installed concurrently with the directional bore, jack and bore or other drilling method raceway,external to the raceway or sleeve.I Insert new paragraph A.11.4.2.3 and renumber balance of section.'I Compliance could be difficult with the requirements of this chapter when designing a new lighting system orwhen replacing all or a portion of a lighting system at an existing airport. When existing pavement cannot be cut: !raceway is typically installed under the pavement by the directional bore. jack and bore or other drilling method. When :raceway is installed by a drilling method it is permissible to install the counterpoise conductor concurrent with the drillingmethod raceway, external to the raceway or sleeve. This could result in the counterpoise conductor being wrappedaround the raceway in an unknown position relative to the raceway or cable being protected. The installation of thecounterpoise conductor is required to maintain the equipotential bonding of the overall lightning protection system. Thelightning protection afforded by this process is reduced; however, this manner of installation is more effective thanomission of the counterpoise conductor. This method is not recommended for projects where the pavement is beingoverlaid or replaced. The counterpoise conductor should be placed prior to any paving operations in accordance withthe requirements of Chapter 11.

_______________________________________________________________________________________________780-56 Log #19

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Add text to read as follows:

Note: Light base ground rod can be installed either through the bottom of the light base or exterior to the light base.Note text for figure 11.4.2.6 is included in the draft ROP artwork and in the body of the draft ROP. The

note should be included only once in Figure 11.4.2.6. Consistent with approved ROP-108 text.

_______________________________________________________________________________________________780-57 Log #14

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Change hatch patterns to gray scale in Figures 11.4.2.6, 11.4.3.2 and A.11.4.2 .7.5.

The hatch patterns at the current intensity tend to over shadow the details and dimensional lines.

18Printed on 9/18/2012

Page 41: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-58 Log #20

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108FIGURE 11.4.2.7 Raceways Installed Under Pavement, Raceways and Cables not Installed

Adjacent to the Full Strength Pavement Edge, . Fixtures Installed in Full Strength Pavement and Shoulder Pavementand Optional Method of Edge Lights Installed in Turf (stabilized soils)iand Raceways and Cables Adjacent to FullStrength Pavement Edge.

Original ROP text had a comma following edge instead of the period. Consistent with approvedROP-108 text.

_______________________________________________________________________________________________780-59 Log #15

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Figures 11.4.3.2 and A.11.4.2 .7.5, increase the size of the filled circle representing the

counterpoise conductor and the lines representing the area of protection as they are hard to see.The counterpoise conductors and area of protection lines are difficult to distinguish from the

background.

_______________________________________________________________________________________________780-60 Log #21

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108FIGURE 11.4.3.3 Multiple Counterpoise Conductor Installation Interconnection Plan View .

Consistent with approved ROP-108 text.

_______________________________________________________________________________________________780-61 Log #22

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Add text to read as follows:

11.4.5.2* Grounding electrodes shall comply with all the requirements of 4.13.2 Ground Rods.4.13.5 Radials. 4.13.6 Plate Electrode or Ground Plate Electrode, 4.13.7 Combinations. and4.13.8 Grounding Electrode Selection Criteria. except as modified by this chapter.

Consistent with approved ROP-108 text.

19Printed on 9/18/2012

Page 42: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-62 Log #82

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc. / Rep. Harger Lightning & Grounding

780-109Add new text

12.3.2 Strike termination devices shall be located at the ends of the uppermost edge or nearest support of solar panelsor panel arrays not to exceed 0.6 m (2 ft) from the end of the panel or array unless the uppermost edge or nearestsupport is within a zone of protection.

Added text clarifies intent.

_______________________________________________________________________________________________780-63 Log #83

_______________________________________________________________________________________________Thomas R. Harger, Harger Inc.

780-109Revise existing text as follows:

12.5 Grounding.12.5.1 Ground Mounted Systems.12.5.1.1 Systems that rely on the metallic structure to form part of the lightning protection system shall be grounded inaccordance with 4.13.4 utilizing a ground ring electrode encompassing the perimeter of each array.12.5.1 .1.1 Combinations of other grounding electrodes in 4.13 shall be permitted.12.5.1.1 .2 Ground ring electrodes of adjacent ground mounted systems within 25 ft (7 .6 m) shall be interconnected.12.5.1.2 Systems that rely on the metallic structure to form parts of the lightning protection system shall be madeelectrically continuous by the methods specified in 4.16.3.12.5.1.3 For solar arrays that do not rely on the metallic structure to form part of the lightning protection system, eachseparate row or structure shall be bonded at one location direct to the ground ring electrode.12.5.1.4 Solar arrays that do not rely on the metallic structure to form part of the lightning protection system shall bemade electrically continuous by means of bonding in accordance with the NEC.12.5.2 Roof Mounted Systems.12.5.2.1 Solar arrays shall be bonded in accordance with 4.20.3.12.5.2.2 Solar arrays shall be made electrically continuous by means of bonding in accordance to the NEC.12.5.2.3 If the structure forms part oL or is within the required separation distance from the lightning protection system.the metallic structure of the system shall be made electrically continuous in accordance with Chapter 4.12.5.2.4 Roof conductors interconnecting strike termination devices protecting roof mounted solar panel shall beprovided with down conductors and grounding electrodes in accordance with Chapter 4.12.5.2.5 Roof conductors interconnecting strike termination devices protecting roof mounted solar panels shall beconnected to the structure lightning protection system in accordance with Chapter 4.

Added text in 12.5.1 permits the use of combinations of electrodes to supplement the ring electrodesand requires that adjacent systems be interconnected.Added text in 12.5.1.2 clarifies how to make the structures "electrically continuous".Added text in 12.5.2.4 addresses roof mounted systems mounted on structures without lightning protection systems.Added text in 12.5.2.5 addresses roof mounted systems mounted on structures with lightning protection systems.

20Printed on 9/18/2012

Page 43: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-64 Log #61

_______________________________________________________________________________________________Matthew Caie, ERICO, Inc.

780-109Revise text to read as follows:

Systems that rely on the comprising of a metallic structure to form part of the lightning protection system shallbe grounded in accordance with Section 4.13.4 utilizing a ground ring electrode encompassing the perimeter of eacharray.

In review of Section 12.5.1 its clear that a ground ring electrode is desired for all metallic structuresystems when lightning protection is to be applied. The above clarifies this and helps with the flow thereafter for metallicstructures that either form or don’t form part of the lightning protection system.

_______________________________________________________________________________________________780-65 Log #37

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-21Add new text to read as follows:

The "grounded point" is the point of connection of the overhead ground wire to the down conductor, at thetop of the mast.

The down conductor is essentially the "grounded point" since it is directly connected to the ground loopor grounding electrode, typically by thermo-weld. Inclusion of the additional height of masts will drive the side flashcalculation, "0," to a distance that will raise the poles to a height which results in no added protection. The addedexpense (both installation and testing) of taller poles contributes no added protection.

_______________________________________________________________________________________________780-66 Log #10

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-115Revise text to read as follows:

When separate but adjacent buildings and/or facilities are interconnected directly (not through a utility)by electric, CATV, CCTV, data, or communications wiring, the grounding systems of those buildings should be directlyinterconnected to each other using a main-size conductor. The need for this interconnection can be eliminated by theuse of fiber optic cable, shielded wire, wire run in grounded metallic conduit, or redundant surge protection (SPD¡¯sinstalled at entrance /exit of both buildings/facilities).

Corrected Annex paragraph number to the new paragraph location

21Printed on 9/18/2012

Page 44: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-67 Log #8

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-117Revise text to read as follows:

There could be installations where multiple sections of piping and associated junctions existbetween the gas meter/regulator and the entrance of the line to the structure. Such junctions can create increasedimpedances at frequencies that are associated with overvoltages. Where there is internal piping that could besusceptible to overvoltages, care should be taken to ensure that the interconnection of the lightning protection groundingsystem is made to pipe sections that will not increase the impedance between the pipe and the grounding section. Thiscould be accomplished by connection to the last section of the pipe entering the structure. This interconnection could bemade either external or internal to the structure. [ROP-40]

Definitions in the NEC (NFPA 70) and 780 for bonding or bonded, grounded or grounding and groundingelectrode are similar. The actual standards sections that define what constitutes these various items point to differencesin application, equipment, and requirements.NEC paragraph 250.50 (Grounding Electrode System) requires all electrodes present at each building or structure be

bonded together to form the grounding electrode system. This coordinates to the requirements of Section 4.14. Thedifferences occur in NEC Section 250.52 which describes grounding electrode devices not shown in Section 4.13.Grounding electrode devices described in Section 250.52, but not referenced in this document include:(1) 250.52 (A) (1) 10 ft. of metallic underground water pipe extending from the structure in contact with earth(2) 250.52 (A) (2) (1) The metal frame of the structure in contact with earth(3) 250.52 (A) (3) (2) The concrete encased electrode described as #4 AWG would need to be a main size conductor

per Paragraph 4.13.3.2(4) 250.52 (A) (4) The ground ring electrode not smaller than #2 AWG is acceptable for Class I, but would not be

acceptable for Class II (See Table 4.1.1.1.2)(5) 250.52 (A) (5) Pipe electrodes shown under section (a) are not included. Rod electrodes described in (b) as zinc

coated steel are not covered (4.13.2.5)(6) 250.52 (A) (6) Other listed electrodes would need to comply with the various sections of 4.13(7) 250.52 (A) (7) Plate electrodes would need to comply with 4.13.6(8) 250.52 (A) (8) “Other local metal underground systems or structures” are not referenced as grounding electrodes in

this StandardThe lightning protection system designer must be familiar with these differences for coordination of interconnection with

other building grounding electrodes or the structural grounding electrode system as required by paragraph 4.14.3.[ROP-117]

The first paragraph is moved to the proper location under another comment.The balance of the information shown under new A.4.14.3 needs to begin with the correct paragraph reference

(added).

22Printed on 9/18/2012

Page 45: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-68 Log #9

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-40Revise text to read as follows:

There could be installations where multiple sections of piping and associatedjunctions exist between the gas meter/regulator and the entrance of the line to the structure. Such junctions can createincreased impedances at frequencies that are associated with overvoltages. Where there is internal piping that could besusceptible to overvoltages, care should be taken to ensure that the interconnection of the lightning protection groundingsystem is made to pipe sections that will not increase the impedance between the pipe and the grounding section. Thiscould be accomplished by connection to the last section of the pipe entering the structure. This interconnection could bemade either external or internal to the structure.

Corrected Annex reference to proper paragraph A.4.14.6 (7).

_______________________________________________________________________________________________780-69 Log #68

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-118Edit text to comply with the Manual of Style.

The text does not comply with the Manual of Style.As modified by the committee the English value should be listed with SI values in parentheses following those values.

5 feet should be 5 ft (1.52 m) 3/16" should be 3/16 in. (4.8 mm).

_______________________________________________________________________________________________780-70 Log #11

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-42aRevise text to read as follows:For structures 18 m (60 ft) or less in height, a loop conductor should be provided for the

interconnection of all grounding electrodes and other grounded media. Regardless of the building height, ground loopconductors should be installed underground in contact with earth. Ground-level potential equalization allows use of aground ring electrode as a ground loop conductor. A ground ring electrode conforming to 4.13.4 can be utilized for theground loop conductor.

Annex paragraph fits best with new paragraph 4.14.2 of document.

23Printed on 9/18/2012

Page 46: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-71 Log #12

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-42aRevise text to read as follows:

In addition to the bonding of metal bodies, surge suppression should be provided to protect power,communication, and data lines from dangerous overvoltages and sparks caused by the lightning strikes. (See Annex Cfor a discussion of bonding and an understanding of problems often encountered.)

This annex material is referenced to section 4.16.3 covering “isolated (nongrounded) metallic bodies”.I will not argue that service lines for communication or power are ungrounded, but I believe the user would be morelikely to access this information if it is keyed to paragraph 4.16 – Bonding of Metal bodies

_______________________________________________________________________________________________780-72 Log #13

_______________________________________________________________________________________________Harold VanSickle, III, Lightning Protection Institute

780-42aRevise text to read as follows:

See Annex C for a technical discussion of lightning protection potential-equalization bonding.

Potential equalization is moved in the new version from 4.19 to 4.16.

_______________________________________________________________________________________________780-73 Log #51

_______________________________________________________________________________________________Joanie A. Campbell, US Department of the Air Force

780-42aAdd new text to read as follows:

Surge protection alone is not intended to prevent or limit physical damage from a direct lightning strike to afacility or structure. Rather, it is intended to defend against indirect lightning effects imposed upon the electrical servicesto a structure as part of a coordinated lightning protection system installed in accordance with the requirements of thisstandard. However, if calculations indicate that LPS is required, but there is no significant dollar value to facilitycontents, surge suppression may meet the requirement for LPS.

Specifically, administrative facilities and dormitories only require protection for electronic devices.Surge suppression would meet the requirement for LPS if a tiered system is provided. Surge suppression simply at themain distribution panel would NOT meet the requirement for LPS unless it is the only panel for the facility. I have not yetperformed a calculation where LPS is not required. I even inserted 25 SF for a fictional building and it came out as beingrequired.

_______________________________________________________________________________________________780-74 Log #69

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-123Values are to be changed expressing the "English" values first.

It was the decision of the 780 Committee that all numeric values were to be expressed with the"English" Values, with the SI Values in parenthesis.

24Printed on 9/18/2012

Page 47: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-75 Log #16

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Correct spelling in Figures A.11.1.1(a) and A.11.1.1(b). Change from "elctrode" to "electrode" in

two places on each figure.Correct spelling.

_______________________________________________________________________________________________780-76 Log #23

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108Revise text to read as follows:

A.11.4.2.6 This subsection addresses items installed in turf adjacent to the full strength pavement edge. Items within4.6 m (15 ft) of the full strength pavement edge could be considered adjacent to the full strength pavement edge for thepurpose of this subsection. The exact routing of the counterpoise conductor could be subject to field conditions such asrock or other obstructions. The counterpoise conductor should be routed as close as practical to the midpoint betweenthe full strength pavement edge and itt:)m being protected .

Insert space between "strength pavement" in third line of text. Consistent with approved ROP-108 text.

_______________________________________________________________________________________________780-77 Log #24

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108FIGURE A.l1.4.2.7.5 Are Area of Protection.

Correct spelling of word "area". Consistent with approved ROP-108 text.

_______________________________________________________________________________________________780-78 Log #25

_______________________________________________________________________________________________Carl S. Johnson II, AVCON, Inc.

780-108A.11.4.5.2 The often accepted earth resistance value of 25 ohms should not be interpreted as

satisfactory for all installations. refer to Annex B.4.4. Reduced earth resistance values could be necessary to provideeffective lightning protection where the lightning risk assessment is high. A.11.4.1 could be used to determine if reducedearth resistance is necessary for protection of the airfield lighting system. The AHJ could define the required groundingelectrode , earth resistance value .

Delete hard return after the word "protection" and insert space so sentence reads correctly. Consistentwith approved ROP-108 text.

25Printed on 9/18/2012

Page 48: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-79 Log #58

_______________________________________________________________________________________________Richard Kithil, National Lightning Safety Institute

780-126Delete: "TENKA peak current represents 91 percent of all lightning events."

Add: About 95% of negative first studies exceed 14 kA, 50% exceed 30 kA, and 5% exceed 80 kA.Reference: Rakov, V.A.: 2012, Journal Lightning Research, 2012, 4 (Suppl L:m2) 3-11.

_______________________________________________________________________________________________780-80 Log #57

_______________________________________________________________________________________________Mitchell Guthrie, Independent Engineering Consultant

780-125, 780-126Change 46m back to 45m in the body of the text and associated figure.

The change is not necessary based on the action taken on ROP 780-1a that indicates English unitsare the dominant values. This change makes NFPA 780 different from any other standard in the world as all othersreference 45 meters and 150 feet as the value for ordinary or Type III rolling sphere radius.

_______________________________________________________________________________________________780-81 Log #27

_______________________________________________________________________________________________David E. McAfee, B&W Technical Services Y-12, LLC

780-138Replace the Figure in the ROP that uses Fl/sq-mi/yr with the attached Figure that uses Fl/sq-m/yr.

Flashes/sq-milyr and Flashes/sq-m/yr

*** Insert figure here****All of the units for the Risk Assessment Methods in Annex L utilize Fl/sq-m/yr NOT Fl/sq-mi/yr. The

attached figure utilizes the correct units.

_______________________________________________________________________________________________780-82 Log #2

_______________________________________________________________________________________________John F. Bender, UL LLC

780-139

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.ANSI/UL 1449, , Third Edition, 2006, Revised 2011.

Update the referenced standard to the most recent edition.

26Printed on 9/18/2012

Page 49: Technical Committee on Lightning Protection ROC Meeting Agenda
Page 50: Technical Committee on Lightning Protection ROC Meeting Agenda

Report on Comments – June 2013 NFPA 780_______________________________________________________________________________________________780-83 Log #3

_______________________________________________________________________________________________John F. Bender, UL LLC

780-1Revise text as follows:

ANSI/UL 497, , 2001, Revised 2009.ANSI/UL 497A, , 2001, Revised 2008.ANSI/UL 497B, , 2004, Revised2008.ANSI/UL 497C, , 2001, Revised 2008.UL 497E, , Edition 4, 2011.

This proposal is being re-submitted with updated revision dates as indicated, with the request that thecommittee reconsider adding such revision dates, in addition to the initial publication date of the standard, to reflect themost recent technical update of the standard as revised from time to time by the UL Standard Technical Panelresponsible for each of the respective standards. Reference to the initial publication date of the standard and anysubsequent revision date for that standard is consistent with almost all other NFPA Standards, such as NFPA 72 andNFPA 101 as two prime examples.

_______________________________________________________________________________________________780-84 Log #71

_______________________________________________________________________________________________Stephen Humeniuk, Warren Lightning Rod Company / Rep. United Lighting Protection Association

780-109Edit text to comply with the Manual of Style.

Section 12.3.4.1 does not meet the Manual of Style. It mandates "compliance with one of thefollowing," then only lists Section 12.3.4.1.1. There is no Section 12.3.4.1.2. Either add other options or rewrite the text.

27Printed on 9/18/2012