Upload
martinezjose192
View
218
Download
0
Embed Size (px)
Citation preview
7/29/2019 TCPST
1/9
Transient stability assessment of systems comprising phase-shiftingFACTS devices by direct methods
Rafael Mihalic*, Uros Gabrijel
Faculty of Electrical Engineering, University of Ljubljana, Trzaska 25, Ljubljana 1000, Slovenia
Abstract
In this paper the concept of a control Lyapunov function is used to develop control strategies for thyristor-controlled phase-shifting
transformers (TCPSTs). Two typical representatives of TCPSTs were chosen for consideration: a Quadrature Boosting Transformer (QBT)
and a Phase Angle Regulator (PAR). For the case of the QBT we showed that the proposed control law can significantly improve the large
signal stability in comparison to the control-law-based on the traditionally used injection model proposed in various references. Even if the
system parameters are estimated very roughly, our proposed strategy gives better results than the traditional strategy. Also, some novel
energy functions, which consider the action of an optimally controlled TCPST in a single-machine infinite-bus (SMIB) system, are presented
and validated by a numerical example.
q 2004 Elsevier Ltd. All rights reserved.
Keywords: Thyristor-controlled phase-shifting transformer; Control strategy; Energy function; Direct method
1. Introduction
Limitations relating to the stability of an electric
power system, technical problems connected with long-
distance power transmission, as well as the limited
possibility for electric power flow redirection are reasons
why todays transmission facilities are, on average,
loaded less than they theoretically could be. The
expansion of electric power networks is becoming
increasingly problematic due to the publics refusal to
accept such solutions to the point where it is sometimes
practically impossible to obtain permission for new rightsof way. With existing knowledge the problem can, in
general, be solved using the so-called dynamic power
flow control method. Such a concept of electric power
system design and operation can be realised by applying
Flexible AC Transmission System (FACTS) devices. The
term FACTS is used to describe a broad spectrum of
devices. In this article the problem of large signal
(transient) stability enhancement, applying thyristor-con-
trolled phase-shifting transformers (TCPSTs), is
discussed. It is true that it is unusual to use TCPSTs
in such a way, but if TCPSTs are already present in the
system for other reasons (like the redirection of power
flows according to agreements in deregulated markets) it
possible to add a transient-stability enhancement
module to the TCPST controller and in this way increase
the transient-stability margin.
A power system undergoes large system parameter
changes during a disturbance. If this disturbance is not
cleared in time the system experiences an escape of one
or more generators. For TCPSTs there already exist
several control strategies [14] for power oscillation
damping and/or transient stability improvement. Based onfindings in [5] we can assume that damping will be more
effective if a regulator uses global information instead of
locally measured quantities. We obtain this global
information from the system that is reduced to a two-
machine equivalent and further into a single-machine
infinite-bus (SMIB) system. The latter is the system used
in this paper. One of the major tasks in transient stability
assessment is determining the critical clearing time
(CCT). In terms of improving the transient stability of a
power system we were particularly interested in the
maximum CCT that can be achieved through the correct
action of a TCPST with a given rating hence we used
a feedback design based on Lyapunovs method in thesame way as the authors in [5].
0142-0615/$ - see front matter q 2004 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijepes.2003.12.001
Electrical Power and Energy Systems 26 (2004) 445453www.elsevier.com/locate/ijepes
*Corresponding author. Tel.: 386-1-4768-438; fax: 386-1-4768-289.E-mail addresses: [email protected] (R. Mihalic); gaber@
leoants.fe.uni-lj.si (U. Gabrijel).
http://www.elsevier.com/locate/ijepeshttp://www.elsevier.com/locate/ijepes7/29/2019 TCPST
2/9
Lyapunov-like direct methods have been successfully
competing with conventional methods in the field of
transient stability assessment for quite some time now
[6,7]. Their advantages lie in the fast computation of the
CCT and the possibility of providing various types of
margins and real-time tools for sensitivity assessment and
preventive control [6]. Supposing that a TCPST already has
a transient stability enhancement module implemented in its
control unit, we are obviously presented with an obstacle
when trying to obtain the CCT of the given system by a
direct method. The same problem studied Hiskens, Hill [8],
and later Padiyar, Immanuel [9] who handled only Static
Var Compensator and presented structure-preserving energy
functions for this device. Recently Gabrijel and Mihalic
presented an energy function for an SSSC in a SMIB system
in [10]. We tried to expand this knowledge by carrying outnew energy functions for optimally controlled TCPSTs in a
SMIB system considering devices limitations.
Section 2 provides mathematical models for two typical
TCPST representatives referred to as a PAR (thyristor
controlled phase angular regulator) and a QBT (thyristor-
controlled quadrature boosting transformer). Inverse opti-
mal design is applied in Section 3 to obtain optimal control
strategies for both TCPST representatives. Section 4
presents new Lyapunov-like energy functions, which
incorporate the optimal action of a TCPST in a SMIB
system. The numerical calculations in Section 5 show some
examples of the use of the new Lyapunov functions for
determining the CCT, and point out the advantages of the
proposed control strategies.
2. Modeling a TCPST in a SMIB system
There are many possible realisations of phase-shifting
transformers. While in Europe (especially the UK) QBTs
are widely used, in the USA it is the PAR that is the most
common device. The PAR terminal voltage phasors are
separated without changing their magnitude (if losses are
neglected). The QBT also separates terminal voltagephasors but the injected voltage UT phase is fixed with
regard to the input voltage phasor UPST1(b ^908-Fig. 1).
In both cases the angle a of the terminal voltage phasors
separation may be assumed to be a controllable parameter.
Although at first sight they appear to be similar devices, a
PAR and a QBT differ in terms of their impact on power
flow. While the PAR is a symmetrical device (no impact of
orientationthe way its terminals are connected to the
systemon power flow), the QBT is not, and its orientation
has an impact on the power flow. In addition, the PARs
location in the corridor does not influence power flow, while
the QBTs location is important [3]. The model of a
transmission system with a TCPST, and phasor diagrams forboth a PAR and a QBT are presented in Fig. 1.
Referring to [3] we can reproduce the PAR equation for
the real power flow that serves us as a mathematical model.
PPAR P2 P1 U1U2
X1 X2sind a 1
Doing the same with the QBT in orientation 1 we obtain:
PQBT P1 P2 U1U2
X1
cos a X2 cos a
sind a 2
2.1. Optimal control design
The development of control laws for PARs and QBTs in
SMIB systems in the literature follows the well-adopted
procedure of inverse optimal control design [11,12]. The
design is based on a control Lyapunov function (CLF). By
definition, any Lyapunov function whose time derivative
can be rendered negative is a CLF [11].
The following considerations are based on Fig. 2, which
shows a SMIB system (with a TCPST) in a transient state
and with the generator represented by the classical model.
2.2. Optimal PAR control
In order to create a closed-loop system with desirable
stability properties we take the common Lyapunov
function (5) and find its time derivative (6) along the
trajectory of the swing Eq. (3). Where d0S represents
Fig. 1. (a) Network scheme, (b) Phasor diagram of a PAR, (c) Phasordiagram of a QBT.
Fig. 2. Model of TCPST in SMIB system.
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453446
7/29/2019 TCPST
3/9
the stable equilibrium point.
MdDv
dt
Pm 2 Pe 2Ddd0
dt
;dd0
dt
Dv 3
Pe E0US
X0sind0 a 4
nd0;Dv 1
2MDv2 2 Pmd
02 d0s
2E0US
X0cos d0 2 cos d0s 5
_n 2 DvE0US
X0sind0 a2 sin d
2DDv2 6
Real power flow is defined by Eq. (4). The last termof Eq. (6)
provides damping to the system. Additional damping with a
PAR can be achieved if the term in the square brackets of Eq.
(6) retains a positive value for any value of input variable.
However, we can talk of an optimal control law if the
considered term retains an ideal maximum value for anyvalue of input variables. In this case the maximum
improvement in transient stability and damping is achieved.
Using Eq. (6), the following optimal strategy is obtained:
a signDvp
22 d0 7
where the controllable parameter a is supposedly unlimited.
The control law Eq. (7) makes _n negative definitive,
therefore, the total energy of the post-fault system will
decrease with time. If a maximum transfer is requested thena
should follow p=22 d0 and vice versa.The phasor diagram according to Fig. 1a implies that the
controllable parameter a is bounded within ^1808. Within
these extremes the injected voltage UT gains doublethe value
of the terminal voltage. Theoretically, this kind of system
could sustain a fault of infinitive time and continue to
preserve stability after the fault clearance. If a is limited
between 2 amin andamax (note:amin is a positive value), the
proposed control strategy can only be applied between limits.
In order to achieve the extreme power transfer across a broad
d0 interval, switching over between amax and amin is required
(e.g. A and B are the points for maximum and C is the
point for minimum power transfer-cf. Fig. 3). From anequal-area point of view the system will be stable if there is
always enough braking surface above the mechanical power
Pm opposing the accelerating surface below Pm-Fig. 3.
In Fig. 3 the optimal control law (7) is graphi-
cally represented. The operating area is determined by the
two bold curves. The upper curve represents the maximum
transfer characteristics of the PAR limited at ^p=3; while
the lower bold curve represents its minimum transfer
characteristics.
2.3. Optimal QBT control
The control law for a QBT is derived in more-or-less the
same way as with a PAR (Section A). The main difference is
in the nature of the QBT, which is a non-symmetrical
device. This creates some difficulties in the procedure of the
control strategy determination. Following the procedurefrom Section A we take the Lyapunov function Eq. (5) and
find its time derivative along the trajectory of the swing
Eq. (3) in which we use Eq. (8) as a term for the real power
flow Pe:
Pe E0US
X0
1
cos a X2cos a
sind0 a 8
The procedure yields the time derivative of the energy
function as follows:
_n 2DvG2DDv2 9
GE0US
X0
1
cosaX2 cosa
sind0 a2E0US
X0
1 X2sind0 10
Our objective is to make the term in the square brackets of
Eq. (9) as negative as possible. In this way the reduction of
the total system energy after the fault is cleared will be a
maximum. This extreme case can easily be obtained by
searching for the zeros in the derivative of Eq. (10) of the
argument a. This gives, after taking Dv into consideration,
the following control law:
a arctan 2tand0 signDvcos d0
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1 X
2
X0
1
cos2 d0s !
11
Omitting the influence ofDv; Eq. (11) can be visualised as
in Fig. 4 E0 US 1: These, and all subsequent figures,
are in the per-unit system.
If a QBT succeeds in attaining the optimal control
strategy, the real power transfer characteristics determined
by Eq. (8) appear as shown in Fig. 5 X10 0:3;X2 0:7:
In order to demonstrate the benefits of the proposed
control strategy a comparison has been made with the
strategy derived from the injection model and presented in
Ref. [1]. In our paper the strategy presented in Ref. [1]
is referred to as the classical control strategy. It assumest hat a QBT contr ol labl e parameter i s set t o i tsFig. 3. PAR transfer characteristics with limitations.
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 447
7/29/2019 TCPST
4/9
maximum and minimum limits, the switching point being
d0 p=2 a amax; d0, p=2 and a 2amin; d
0. p=2:
The maximum real power transfers in a SMIB system
with the QBT parameter limited to ^p=6 were compared
according to the proposed PNEW and the classical control
strategy POLD: A comparison of the extreme real power
transfer using both strategies is shown in Figs. 6 and 7. Fig. 7
displays the difference between PNEW and POLD for extreme
power transfers, depending on the location of the QBT
device. It is evident that the new control law can
significantly increase the transfer of the real power flow
through the given line in the vicinity ofd0 p=2; while at
lower angles the effect drops off quickly. When considering
the minimum power transfer for the QBT phase-shift-
limitation to ^p=6; in the d0 interval between 0 and p the a
is always set to its limit (cf. Fig. 4-for 0 , d0
, p mintransfer curve does not enter the area between limits). This
means that in this case there is no difference between the
classical and our proposed strategy for minimum powers at
0 , d0 , p: Therefore, we can conclude that the classical
control strategy is appropriate for oscillation damping (a
relatively small QBT rating required), while for transient
stability enhancement the proposed strategy can be
significantly more effective. Of course this also manifests
in a longer CCT, as will be shown later in Section 5.
In the case of a reverse orientation of a QBT the correct
transmission characteristics are the same as Eq. (8) except
that X1
0 should be replaced with X2
(and vice versa), dwith -
dand a with-a. It can be shown that in the case of reverse
orientation the correct control law follows from replacing
X1
0 with X2
in the term (11).
A special case occurs when the QBT is located at the grid
terminals, orientation 2 (this orientation is reasonable in this
case). In this situation it is possible to modify Eq. (8), which
can be rewritten as:
Pe E0US
X0tan a cos d0 sin d0 12
The control strategy can be obtained from Eq. (11) where
the reverse orientation and X2 0 is considered:
a amax; Dvcos d0$ 0
13a 2amin; Dvcos d
0, 0
Evidently this control law is the same as the classical
control strategy and hence it can be concluded that the
proposed and the classical control strategies do not differ at
the grid terminals (orientation 2parallel branch at grid).
The differences arise when the QBT is moved electrically
away from the grid (also shown in Fig. 7).
The rating of the device again defines the maximum and
minimum phase angle shift: amin and amax: The maximum
and minimum transfer characteristics for E0 1; US 1
and amin amax p=6 are shown in Fig. 8.
Presented control laws for TCPSTs are globally optimal,
however, for a practical application it is reasonable to use
locally measurable electric quantities. A good example ofFACTS control based on local measurements is presented in
[2] and references therein. In this case control laws are not
Fig. 4. Control law for a QBT.
Fig. 5. Extreme QBT transfer characteristics.
Fig. 6. Comparison of maximum QBT transfer characteristics.
Fig. 7. Difference in maximum transfer characteristics.
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453448
7/29/2019 TCPST
5/9
globally optimal anymore. Furthermore, instead of
the generators internal electro-motive force and infinite
busbar voltage, voltage measurements from both ends of the
transmission path can be also used to obtain a local
optimum.
3. Developing energy function
According to the specific bangbang control strategy a
TCPST must jump between maximum and minimum
transfer characteristics. Thus, we can speculate that during
the first swing the TCPST control parameter is always set so
that the maximum transfer characteristic is attained. We
have used this fact to develop several energy functions that
can be used in any system that can be reduced to SMIBsystem without loosing the information on FACTS location
e.g. longitudinal or interconnected systems. Note that a
radial system topology can also be a consequence of a relay
protection response to a disturbance in meshed systems. The
proposed energy functions meet all the conditions for a
Lyapunov function.
3.1. PAR energy function
From the direct-method point of view it is sufficient to
know the behaviour of the TCPST for the period of the fault-
on. Hence for the purposes of CCT determination we can
omit the sign of Dv (it does not change during theacceleration), which affects the PAR control law. We only
have to examine the PAR maximum transfer characteristic
shown in Fig. 9. This characteristic is composed of the
intervals defined in Eq. (14).
Ped0 d0 interval
Pmaxe sind
0amax; 2R k2p,d
0,p
22amax k2p
Pmaxe ;
p
22amax k2p#d#
p
2amin k2p
P
max
e sind
02amin;
p
2 amin k2p,d
0#
2pk12
R14
where Pmaxe is defined as
E0US
X0 and
k
IntegerPartR d0
2p
; d0$R
IntegerPartR d0
2p
21; d0,R
15
Ifamin amax then R equals p=2; otherwise R is defined as
shown in Fig. 9 (the point where curves sind0 amax and
sind02amin meet).
Energy functions are always constructed for the post-
fault system. In accordance with the general agreement that
the first integral of the swing equation constitutes a proper
energy function we integrated the swing Eq. (3) over all theintervals of Eq. (14). The integration yields the following
energy function:
nPARd0;Dv nKEDv nPE PARd
0 16
nKEDv 1
2MDv2 17
The term (17) as a kinetic energy is also used later on in theQBT case.
nPE PARd0 nPE PARi21
nPE PARiAd02R k2p, d0 ,
p
22amax k2p
nPE PAR iBd0p
22 amax k2p# d
0#
p
2
amin k2p
nPE PAR iCd0p
2 amin
k2p, d0 # 2pk 12R
8>>>>>>>>>>>>>>>>>>>>>>>>>:
18
where:
nPE PAR iA 2
Pmd
02 ^
d
0S
2
P
max
e cosd
0
amax2 cosd0S amax 19
Fig. 8. Transmission characteristics-QBT at grid.
Fig. 9. PAR maximum transfer characteristics (a is bounded).
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 449
7/29/2019 TCPST
6/9
nPE PARiB Pmaxe 2 Pm d
02
p
22 amax
nPE PAR iC 2Pm d02 p
2 amin
2 Pmaxe cosd
02amin
d0S is the PAR stable equilibrium point (SEP) at the
maximum transfer characteristic. It equals d0S2 amax:
d0S represents the SEP of a post-fault system without a
PAR. nPE i21 expresses the constant value of the
potential energy with which we enter the current
interval. The initial value of nPE i21 is zero. In Appendix
A it is shown that Eq. (16) is a Lyapunov function in
the usual sense.
3.2. QBT energy function
3.2.1. QBT energy function for the proposed new strategy
The considerations that are valid for the PAR
case (Section A) are also valid for a QBT. Starting with
an examination of Eq. (11) it was established that neglecting
Dv has no impact on (11) if we consider the fault-ontrajectory, hence we can rewrite the control law as:
a arctan 2tan d0 sec d0ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
1 X2
X0
1
cos2d0
s !20
We again executed the first integral of motion and took into
account Eq. (20) for Pe: However, the analytical solution of
the referred integral could not be found. We thereforesuggest that the problem is handled numerically. Hence
energy function can be denoted as:
WQBTd0;Dv WKEDv WPE QBTd
0 21
WPE QBTd0 2Pmd
02 d0S
d0d0S
E0US
X0
1
cosaX2 cosa
sind0 add0 22
where a varies as described in Eq. (20). In the special case
when a QBT is located at the grid (orientation 2) it is
possible to construct a strict Lyapunov function. As inSection 3.1 we make a similar assumption that the device
follows the maximum transfer characteristic (Fig. 10). The
latter is based on the transfer characteristic Eq. (12) and the
proposed bang bang control law (13) with the influence of
Dvneglected.
After an examination ofFig. 10 we chose to carry out the
integration of the swing equation over the following two
intervals:
Ped0 d0 interval
E0US
X0sin d0 tan amaxcos d
0; d0 ,
p
2
E0US
X0sin d0 2 tan amincos d
0; d0 $
p
2
23
If we suppose that Pmaxe . Pm; the post-fault system yields
only one SEP. Pmaxe is defined as E0US=X
0: Otherwise we
could deal with two SEP cases, which is evident from Fig. 10
if mechanical power Pm is increased. After the integration
of Eq. (3), keeping Eq. (23) in mind, we get:
nQBTd0;Dv nKEDv nPE QBTd
0 24
nPE QBTd0 2Pmd
02 d0 S2Pmaxe cosd
02cos d0S
nPE QBT i21 Pmax
e amaxsind02
sin^d
0S
;
d0,p
2
nPE QBT i212Pmaxe tanamin sind
02 sin
p
2
d0$p
2
8>>>>>>>>>>>>>>>>>:
25
nPE QBT i21 represents the constant value of the potential
energy from the previous interval. Its initial value is zero.
3.2.2. QBT energy function for classical control strategy
The classical control strategy has the same effect on the
transmission characteristic as Eq. (13), therefore weconstruct the energy function in the same way as in Sections
3, 3.1, 3.2, 3.2.1, by integrating the swing Eq. (3) over two
intervals of Eq. (26):
PEd0 d0 intervals
E0US
X0
1
cos amax X2cos amax
sind0 amax; d0,
p
2
E0US
X0
1
cos amin X2cos amin
sind0 2 amin; d0$
p
2
26
Fig. 10. Maximum transfer characteristics-QBT at grid (a limitations
considered).
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453450
7/29/2019 TCPST
7/9
The integration yields:
nQBTd0;Dv nKEDv nPE QBTd
0 27
nPE QBTd0 2Pmd
02 d0S nPE QBT i21
2
Pmaxe1 cosd
0amax2cosd
0Samax;
d0 ,p
2
Pmaxe2 cosd
02amin2cos
p
22amin
;
d0 $p
2
8>>>>>>>>>>>>>>>>>:
28
where:
Pmaxe1
E0US
X0
1
cos amaxX2cos amax
29
Pmaxe2
E0US
X0
1
cosaminX2cosamin
nPE QBT i21 is denominated in the same way as in Section
3.2.1.
4. Numerical examples
In order to demonstrate the effectiveness of the proposed
control laws and the usefulness of the developed energy
functions some numerical examples were made. The test
case is the one from [3], where it is thoroughly examined. Its
scheme is presented in Fig. 11 while some of the system data
is presented in Table 1. The QBT device in orientation 2 is
located at the Grid (BUS 3 node). The transmitted pre-fault
real power equals 0.9 pu of the generator rated power. For
the purposes of the digital simulation in the NETOMAC
(Siemens AG) environment both the generator and the
excitation control (Semipol) are modelled in detail. On the
other hand, the generator classical model served to the direct
method and the transmission lines were presented as a
reactance calculated from 100-km-long p-sections.
The disturbance in the system is represented by three-
phase faults in the outgoing line near the generator terminal
(BUS1) and as a result the faulty line is disconnected.
The results obtained by both the direct and conventional
(simulation) methods are presented in Table 2. We can see
two different CCTs obtained with the direct method, where
one fault-on simulation takes into account the effect of the
damper windings D 0: The CCTs calculated by direct
methods approach the simulation results (which are
considered a reference) in a few ms. These results are
very promising, especially if the simplifications made byapplying direct methods are kept in mind.
As shown, the estimates of the CCTs obtained using the
direct method are not conservative. The reason for this may
be the fact that in the case of the direct method application
the system resistances are not taken into consideration (they
cannot be unless an integration is carried out numerically
along the swing trajectory). In addition, the generator model
is far simpler than one used for simulation purposes.
Next,the effectiveness of theproposedQBTcontrol strategy
compared to the classical control strategy is demonstrated. If
the QBT is positioned at BUS3 (supposing orientation 2)
there is,of course, no difference between theapplied strategies.
If on the other hand the QBT is, with the specific limitsregarding controllable parameter a, placed at the BUS 2,
differences become evident. The results based on various QBT
ratings and orientations are presented in Table 3.
Deviations in percent were calculated as a CCT difference
between the proposed and the classical control strategies.
Discussing the results in Table 3 it is evident that a step
forward has been made in searching for an optimal control
strategy. The developed control law (12) not only improves
the transient stability but also provides us with a strategy to
maximise or minimise the transfer capability of the given
corridor with a QBT for any of the operating states.
Fig. 11. The test system.
Table 1
System data
Generator data Lines data Grid data
Pn 1500 MVA xd00 0:182 pu r 0:03 V/km Un 500 kV
xd0 0:270 pu x 0:33 V/km Pg 1350 MVA
Tm 6:6 s xd 1:47 pu c 12 nF/km
Td00 0:034 s xq
00 0:211 pu
Td0 2 s xq
0 0:636 pu
Tq00 0:041 s xq xd
Table 2Obtained CCT
Direct method Digital simulation
D 0:0167pu D 0 pu
CCT DCCT CCT DCCT CCT
QBTamax;min [deg] [ms] [%] [ms] [%] [ms]
19.2 107 7.0 102 2.0 100.0
40.4 167 11.3 157 4.7 150.0
51.5 209 4.5 195 2 2.5 200.0
PARamax;min [deg]
39 109 9.0 104 4.0 100.0
157 171 14.0 159 6.0 150.0322 235 17.5 214 7.0 200.0
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 451
7/29/2019 TCPST
8/9
Calculations have shown that the proposed control
strategy is quite insensitive with regard to mistakes in
the evaluation of system reactances. In order to demonstrate
this, it was assumed that X2 was not known exactly. In the
calculations of the optimal a, 290% and 400% of X2deviations were considered. The results with the QBT in
orientation 2 are summarised in Table 4. As shown, the
CCTs are no longer optimal (as in Table 3), but they are still
better than when a classical control strategy is applied. This
has been anticipated because the classical control strategy
ignores X2: The differences Dwere calculated with regard to
the optimal CCT from Table 3.
5. Conclusions
In this paper new control laws based on a Control
Lyapunov Function for a PAR and a QBT have been
presented. They prove that we can squeeze the
maximum out of a device in any given situation and
can therefore be called optimal. For a QBT we showed
that the proposed strategy is more effective in the area of
large transmission angles than the classical control
strategy, while for small angles the differences are of
minor importance. Hence it can be concluded that for
oscillation damping purposes there is practically no
difference between the classical and proposed strategies.
On the other hand, for transient stability purposes the new
strategy has advantages. Furthermore, it has also been
shown that the proposed QBT control strategy is robustwith regard to the selection of inappropriate parameters.
For SMIB systems with TCPSTs new energy functions
have been constructed that take the effect of FACTS
devices and their control (optimal and classical) into
consideration. Any multimachine system with a TCPST that
can be reduced to a SMIB without losing the information
about the TCPST location can be treated with developed
energy functions (e.g. remote generation or interconnec-
tion). In this case a system is first reduced into a twomachine equivalent and then further reduced into a SMIB
system [6].
The results of test calculations are promising, especially
if the simplifications made by applying direct methods are
kept in mind.
Future research work in this field should also endeavour
to construct structure-preserving energy functions that are
more versatile.
Acknowledgements
The authors gratefully acknowledge the JuniorResearcher Scholarship awarded to U. Gabrijel by Ministry
of Education, Science and Sport of the Republic of Slovenia.
Appendix A
Proving a Lyapunov function for a PAR mainly follows a
procedure from the literature [2]. A function must satisfy
three conditions to be recognised as a Lyapunov function:
(a1) it must have the same stationary points as the maximum
transfer characteristic (14); (a2) it is positive definite in the
vicinity of one of the equilibrium points; (a3) its derivative
is not positive.(a1) Satisfying the first condition can be checked by the
determination of the nd0;Dv gradient. Assuming that
Pm , Pmaxe we only check the functions on lateral intervals
(note:nPE PAR iA;iC are constant):
gradnPAR
n
Dv
n
d0
2664
3775
nKE
Dv
nPEd0
2664
3775 A1
(a1-1) First interval 2R , d0 ,p
22 amax verification:
gradnPAR int: 1 MDv
2Pm 2 Pmaxe sind
0 amax
" #A2
Table 3
CCT obtained applying different control strategies
amax;min [deg] Orientation 1 Orientation 2
Classical Proposed Classical Proposed
CCT [ms] D[%] CCT [ms] D[%]
19.2 88 93 25.4 96 98 22.0
28.8 79 96 217.7 102 107 24.7
40.4 27 97 272.2 103 117 212.8
51.5 97 81 123 234.1
Table 4
CCT obtained by applying false X2 in optimal a calculation
amax;min [deg] 10% X2 500% X2
CCT [ms] D[%] CCT [ms] D[%]
19.2 96 22.0 97 21.0
28.8 103 23.7 105 21.9
40.4 107 28.5 112 24.251.5 107 213.0 109 211.4
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453452
7/29/2019 TCPST
9/9
The gradient is equal to zero at the stationary point whereDv 0 and the electrical power is equal to the mechanical
power given by d0
1
d0S: This point is the equilibrium point
of the maximum transfer characteristic.
(a1-2) Third intervalp
2 amin , d
0# 2p2R verifica-
tion:
gradnPAR int:3 MDv
2Pm 2 Pmaxe sind
02 amin
" #A3
The gradient Eq. (A3) is equal to zero at the stationary point
where Dv 0 and the electrical power is equal to the
mechanical power given by d02 d0U: As can be visualised
from Fig. 9 this is also an equilibrium point of the maximum
transfer characteristic.
(a2) Satisfying the second condition for a Lyapunov
function can be checked by determining the Hessian matrixfor the first SEP:
HPAR
2nPAR
Dv2
2nPAR
d0 Dv
2nPAR
d0 Dv
2nPARd02
26664
37775
M 0
0 Pmaxe cosd0
amax
" #A4
Silvesters theorem says that this matrix is positive definite
when the diagonal elements are greater than zero: hence
M. 0 (which is always true) and in the long term (A4)must be greater than zero, which holds true for the first
stationary point d0S:
(a3) The third condition can be checked by determining
_n dn=dtalong the trajectory of the swing Eq. (3). First we
express the derivative as:
_nPAR dn
dt
dnKEdt
dnPE PAR
dtA5
and calculate each component respectively:
dnKEdt
nKEDv
dDv
dtMDv
dDv
dt M
dDv
dt
Dv A6
The factor in the square brackets corresponds to left-handside of Eq. (3). Replacing it by the right-hand side and
considering Eq. (14) as Pe yieldsdnKE
dt:
Similarly, the derivative of the potential energy can be
calculated (note: nPE PARi A;B;C are constant):
dnPE PARdt
nPE PAR
d0
dd0
dtA7
Summing the results of Eqs. (A6) and (A7) gives:
_nPAR dnPAR
dt 2D Dv2 A8
whichrepresentsthetotalsystemenergydecay.Itcorresponds
to the natural damping and its positive damping coefficient.
Therefore the _nPAR derivative is negative and hence nPARmeets all three conditions for a Lyapunov function.
QBT Lyapunov functions Eqs. (24) and (27) can be
verified in a similar way.
References
[1] Noroozian M, Angquist L, Ghandari M, Andersson G. Improving
Power System Dynamics by Series-Connected FACTS Devices. IEEE
Trans Power Delivery 1997;12(4):163541.
[2] Machowski J, Bialek JW, Bumby JR. Power system dynamics and
stability. Wiley; 1997.
[3] Yong Hua Song Allan T, editor. Flexible ac transmission systems
(FACTS), vol. 30. London: IEE, cop; 1999. p. 443505. (IEE power
and energy series).
[4] Mihalic R, Zunko P. Phase-shifting transformer with fixed phase
between terminal voltage and voltage boost-tool for transient stabilitymargin enhancement. IEE Proc., Gener. Transm. Distrib. 1995;
142(3):25762.
[5] Ghandhari M, Andersson G, Pavella M, Ernst D. A control strategy for
controllable series capacitor in electric power systems. Automatica
2001;37:157583.
[6] Pavella M, Murthy PG. Transient stability of power systems. Wiley;
1994.
[7] Peter Sauer W, Pai MA. Pai, power system dynamics and stability.
Prentice Hall; 1998.
[8] Hiskens IA, Hill DJ. Incorporation of SVCs into energy function
methods. Trans Power Syst 1992;7(1).
[9] Padiyar KR, Immanuel V. Modelling of SVC for stability evaluation
using structure preserving energy function. Electric Power Energy
Syst 1994;16(5).
[10] Gabrijel U, Mihalic R. Direct methods for transient stability
assessment in power systems comprising controllable series devices.
IEEE Trans Power Syst 2002;September:111622.
[11] Sepulchre R, Jankovic M, Kokotovic PV. Constructive nonlinear
control. Springer; 1997.
[12] Freeman RA, Kokotovic PV. Robust nonlinear control design.
Boston: Birkhauser; 1996.
Uros Gabrijel (1972) received his Dr Sc Degree in electrical
engineering from the University of Ljubljana, Slovenia, in 2003.
After a year with a local electric energy distribution company he joined
the LPEE Laboratory at the Faculty of Electrical Engineering in
Ljubljana where he is currently working as a researcher. His areas of
interest include system analysis and FACTS devices.
Rafael Mihalic (1961) received his diploma Engineer, MSc and Dr Sc
degrees from The University of Ljubljana, Slovenia, in 1986, 1989, and
1993, respectively. After finishing his basic technical education in 1986
he became a teaching assistant at the Department of Power Systems and
Devices of the Faculty for Electrical and Computer Engineering in
Ljubljana. Between 1988 and 1991 he was a member of the Siemens
Power Transmission and Distribution Group, Erlangen, Germany.
Since 2000 he has been an associate professor at the University of
Ljubljana. His areas of interest include system analysis and FACTS
devices. Prof. Mihalic is an IEEE, NY and Cigre, Paris member.
R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 453