TCPST

Embed Size (px)

Citation preview

  • 7/29/2019 TCPST

    1/9

    Transient stability assessment of systems comprising phase-shiftingFACTS devices by direct methods

    Rafael Mihalic*, Uros Gabrijel

    Faculty of Electrical Engineering, University of Ljubljana, Trzaska 25, Ljubljana 1000, Slovenia

    Abstract

    In this paper the concept of a control Lyapunov function is used to develop control strategies for thyristor-controlled phase-shifting

    transformers (TCPSTs). Two typical representatives of TCPSTs were chosen for consideration: a Quadrature Boosting Transformer (QBT)

    and a Phase Angle Regulator (PAR). For the case of the QBT we showed that the proposed control law can significantly improve the large

    signal stability in comparison to the control-law-based on the traditionally used injection model proposed in various references. Even if the

    system parameters are estimated very roughly, our proposed strategy gives better results than the traditional strategy. Also, some novel

    energy functions, which consider the action of an optimally controlled TCPST in a single-machine infinite-bus (SMIB) system, are presented

    and validated by a numerical example.

    q 2004 Elsevier Ltd. All rights reserved.

    Keywords: Thyristor-controlled phase-shifting transformer; Control strategy; Energy function; Direct method

    1. Introduction

    Limitations relating to the stability of an electric

    power system, technical problems connected with long-

    distance power transmission, as well as the limited

    possibility for electric power flow redirection are reasons

    why todays transmission facilities are, on average,

    loaded less than they theoretically could be. The

    expansion of electric power networks is becoming

    increasingly problematic due to the publics refusal to

    accept such solutions to the point where it is sometimes

    practically impossible to obtain permission for new rightsof way. With existing knowledge the problem can, in

    general, be solved using the so-called dynamic power

    flow control method. Such a concept of electric power

    system design and operation can be realised by applying

    Flexible AC Transmission System (FACTS) devices. The

    term FACTS is used to describe a broad spectrum of

    devices. In this article the problem of large signal

    (transient) stability enhancement, applying thyristor-con-

    trolled phase-shifting transformers (TCPSTs), is

    discussed. It is true that it is unusual to use TCPSTs

    in such a way, but if TCPSTs are already present in the

    system for other reasons (like the redirection of power

    flows according to agreements in deregulated markets) it

    possible to add a transient-stability enhancement

    module to the TCPST controller and in this way increase

    the transient-stability margin.

    A power system undergoes large system parameter

    changes during a disturbance. If this disturbance is not

    cleared in time the system experiences an escape of one

    or more generators. For TCPSTs there already exist

    several control strategies [14] for power oscillation

    damping and/or transient stability improvement. Based onfindings in [5] we can assume that damping will be more

    effective if a regulator uses global information instead of

    locally measured quantities. We obtain this global

    information from the system that is reduced to a two-

    machine equivalent and further into a single-machine

    infinite-bus (SMIB) system. The latter is the system used

    in this paper. One of the major tasks in transient stability

    assessment is determining the critical clearing time

    (CCT). In terms of improving the transient stability of a

    power system we were particularly interested in the

    maximum CCT that can be achieved through the correct

    action of a TCPST with a given rating hence we used

    a feedback design based on Lyapunovs method in thesame way as the authors in [5].

    0142-0615/$ - see front matter q 2004 Elsevier Ltd. All rights reserved.

    doi:10.1016/j.ijepes.2003.12.001

    Electrical Power and Energy Systems 26 (2004) 445453www.elsevier.com/locate/ijepes

    *Corresponding author. Tel.: 386-1-4768-438; fax: 386-1-4768-289.E-mail addresses: [email protected] (R. Mihalic); gaber@

    leoants.fe.uni-lj.si (U. Gabrijel).

    http://www.elsevier.com/locate/ijepeshttp://www.elsevier.com/locate/ijepes
  • 7/29/2019 TCPST

    2/9

    Lyapunov-like direct methods have been successfully

    competing with conventional methods in the field of

    transient stability assessment for quite some time now

    [6,7]. Their advantages lie in the fast computation of the

    CCT and the possibility of providing various types of

    margins and real-time tools for sensitivity assessment and

    preventive control [6]. Supposing that a TCPST already has

    a transient stability enhancement module implemented in its

    control unit, we are obviously presented with an obstacle

    when trying to obtain the CCT of the given system by a

    direct method. The same problem studied Hiskens, Hill [8],

    and later Padiyar, Immanuel [9] who handled only Static

    Var Compensator and presented structure-preserving energy

    functions for this device. Recently Gabrijel and Mihalic

    presented an energy function for an SSSC in a SMIB system

    in [10]. We tried to expand this knowledge by carrying outnew energy functions for optimally controlled TCPSTs in a

    SMIB system considering devices limitations.

    Section 2 provides mathematical models for two typical

    TCPST representatives referred to as a PAR (thyristor

    controlled phase angular regulator) and a QBT (thyristor-

    controlled quadrature boosting transformer). Inverse opti-

    mal design is applied in Section 3 to obtain optimal control

    strategies for both TCPST representatives. Section 4

    presents new Lyapunov-like energy functions, which

    incorporate the optimal action of a TCPST in a SMIB

    system. The numerical calculations in Section 5 show some

    examples of the use of the new Lyapunov functions for

    determining the CCT, and point out the advantages of the

    proposed control strategies.

    2. Modeling a TCPST in a SMIB system

    There are many possible realisations of phase-shifting

    transformers. While in Europe (especially the UK) QBTs

    are widely used, in the USA it is the PAR that is the most

    common device. The PAR terminal voltage phasors are

    separated without changing their magnitude (if losses are

    neglected). The QBT also separates terminal voltagephasors but the injected voltage UT phase is fixed with

    regard to the input voltage phasor UPST1(b ^908-Fig. 1).

    In both cases the angle a of the terminal voltage phasors

    separation may be assumed to be a controllable parameter.

    Although at first sight they appear to be similar devices, a

    PAR and a QBT differ in terms of their impact on power

    flow. While the PAR is a symmetrical device (no impact of

    orientationthe way its terminals are connected to the

    systemon power flow), the QBT is not, and its orientation

    has an impact on the power flow. In addition, the PARs

    location in the corridor does not influence power flow, while

    the QBTs location is important [3]. The model of a

    transmission system with a TCPST, and phasor diagrams forboth a PAR and a QBT are presented in Fig. 1.

    Referring to [3] we can reproduce the PAR equation for

    the real power flow that serves us as a mathematical model.

    PPAR P2 P1 U1U2

    X1 X2sind a 1

    Doing the same with the QBT in orientation 1 we obtain:

    PQBT P1 P2 U1U2

    X1

    cos a X2 cos a

    sind a 2

    2.1. Optimal control design

    The development of control laws for PARs and QBTs in

    SMIB systems in the literature follows the well-adopted

    procedure of inverse optimal control design [11,12]. The

    design is based on a control Lyapunov function (CLF). By

    definition, any Lyapunov function whose time derivative

    can be rendered negative is a CLF [11].

    The following considerations are based on Fig. 2, which

    shows a SMIB system (with a TCPST) in a transient state

    and with the generator represented by the classical model.

    2.2. Optimal PAR control

    In order to create a closed-loop system with desirable

    stability properties we take the common Lyapunov

    function (5) and find its time derivative (6) along the

    trajectory of the swing Eq. (3). Where d0S represents

    Fig. 1. (a) Network scheme, (b) Phasor diagram of a PAR, (c) Phasordiagram of a QBT.

    Fig. 2. Model of TCPST in SMIB system.

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453446

  • 7/29/2019 TCPST

    3/9

    the stable equilibrium point.

    MdDv

    dt

    Pm 2 Pe 2Ddd0

    dt

    ;dd0

    dt

    Dv 3

    Pe E0US

    X0sind0 a 4

    nd0;Dv 1

    2MDv2 2 Pmd

    02 d0s

    2E0US

    X0cos d0 2 cos d0s 5

    _n 2 DvE0US

    X0sind0 a2 sin d

    2DDv2 6

    Real power flow is defined by Eq. (4). The last termof Eq. (6)

    provides damping to the system. Additional damping with a

    PAR can be achieved if the term in the square brackets of Eq.

    (6) retains a positive value for any value of input variable.

    However, we can talk of an optimal control law if the

    considered term retains an ideal maximum value for anyvalue of input variables. In this case the maximum

    improvement in transient stability and damping is achieved.

    Using Eq. (6), the following optimal strategy is obtained:

    a signDvp

    22 d0 7

    where the controllable parameter a is supposedly unlimited.

    The control law Eq. (7) makes _n negative definitive,

    therefore, the total energy of the post-fault system will

    decrease with time. If a maximum transfer is requested thena

    should follow p=22 d0 and vice versa.The phasor diagram according to Fig. 1a implies that the

    controllable parameter a is bounded within ^1808. Within

    these extremes the injected voltage UT gains doublethe value

    of the terminal voltage. Theoretically, this kind of system

    could sustain a fault of infinitive time and continue to

    preserve stability after the fault clearance. If a is limited

    between 2 amin andamax (note:amin is a positive value), the

    proposed control strategy can only be applied between limits.

    In order to achieve the extreme power transfer across a broad

    d0 interval, switching over between amax and amin is required

    (e.g. A and B are the points for maximum and C is the

    point for minimum power transfer-cf. Fig. 3). From anequal-area point of view the system will be stable if there is

    always enough braking surface above the mechanical power

    Pm opposing the accelerating surface below Pm-Fig. 3.

    In Fig. 3 the optimal control law (7) is graphi-

    cally represented. The operating area is determined by the

    two bold curves. The upper curve represents the maximum

    transfer characteristics of the PAR limited at ^p=3; while

    the lower bold curve represents its minimum transfer

    characteristics.

    2.3. Optimal QBT control

    The control law for a QBT is derived in more-or-less the

    same way as with a PAR (Section A). The main difference is

    in the nature of the QBT, which is a non-symmetrical

    device. This creates some difficulties in the procedure of the

    control strategy determination. Following the procedurefrom Section A we take the Lyapunov function Eq. (5) and

    find its time derivative along the trajectory of the swing

    Eq. (3) in which we use Eq. (8) as a term for the real power

    flow Pe:

    Pe E0US

    X0

    1

    cos a X2cos a

    sind0 a 8

    The procedure yields the time derivative of the energy

    function as follows:

    _n 2DvG2DDv2 9

    GE0US

    X0

    1

    cosaX2 cosa

    sind0 a2E0US

    X0

    1 X2sind0 10

    Our objective is to make the term in the square brackets of

    Eq. (9) as negative as possible. In this way the reduction of

    the total system energy after the fault is cleared will be a

    maximum. This extreme case can easily be obtained by

    searching for the zeros in the derivative of Eq. (10) of the

    argument a. This gives, after taking Dv into consideration,

    the following control law:

    a arctan 2tand0 signDvcos d0

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1 X

    2

    X0

    1

    cos2 d0s !

    11

    Omitting the influence ofDv; Eq. (11) can be visualised as

    in Fig. 4 E0 US 1: These, and all subsequent figures,

    are in the per-unit system.

    If a QBT succeeds in attaining the optimal control

    strategy, the real power transfer characteristics determined

    by Eq. (8) appear as shown in Fig. 5 X10 0:3;X2 0:7:

    In order to demonstrate the benefits of the proposed

    control strategy a comparison has been made with the

    strategy derived from the injection model and presented in

    Ref. [1]. In our paper the strategy presented in Ref. [1]

    is referred to as the classical control strategy. It assumest hat a QBT contr ol labl e parameter i s set t o i tsFig. 3. PAR transfer characteristics with limitations.

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 447

  • 7/29/2019 TCPST

    4/9

    maximum and minimum limits, the switching point being

    d0 p=2 a amax; d0, p=2 and a 2amin; d

    0. p=2:

    The maximum real power transfers in a SMIB system

    with the QBT parameter limited to ^p=6 were compared

    according to the proposed PNEW and the classical control

    strategy POLD: A comparison of the extreme real power

    transfer using both strategies is shown in Figs. 6 and 7. Fig. 7

    displays the difference between PNEW and POLD for extreme

    power transfers, depending on the location of the QBT

    device. It is evident that the new control law can

    significantly increase the transfer of the real power flow

    through the given line in the vicinity ofd0 p=2; while at

    lower angles the effect drops off quickly. When considering

    the minimum power transfer for the QBT phase-shift-

    limitation to ^p=6; in the d0 interval between 0 and p the a

    is always set to its limit (cf. Fig. 4-for 0 , d0

    , p mintransfer curve does not enter the area between limits). This

    means that in this case there is no difference between the

    classical and our proposed strategy for minimum powers at

    0 , d0 , p: Therefore, we can conclude that the classical

    control strategy is appropriate for oscillation damping (a

    relatively small QBT rating required), while for transient

    stability enhancement the proposed strategy can be

    significantly more effective. Of course this also manifests

    in a longer CCT, as will be shown later in Section 5.

    In the case of a reverse orientation of a QBT the correct

    transmission characteristics are the same as Eq. (8) except

    that X1

    0 should be replaced with X2

    (and vice versa), dwith -

    dand a with-a. It can be shown that in the case of reverse

    orientation the correct control law follows from replacing

    X1

    0 with X2

    in the term (11).

    A special case occurs when the QBT is located at the grid

    terminals, orientation 2 (this orientation is reasonable in this

    case). In this situation it is possible to modify Eq. (8), which

    can be rewritten as:

    Pe E0US

    X0tan a cos d0 sin d0 12

    The control strategy can be obtained from Eq. (11) where

    the reverse orientation and X2 0 is considered:

    a amax; Dvcos d0$ 0

    13a 2amin; Dvcos d

    0, 0

    Evidently this control law is the same as the classical

    control strategy and hence it can be concluded that the

    proposed and the classical control strategies do not differ at

    the grid terminals (orientation 2parallel branch at grid).

    The differences arise when the QBT is moved electrically

    away from the grid (also shown in Fig. 7).

    The rating of the device again defines the maximum and

    minimum phase angle shift: amin and amax: The maximum

    and minimum transfer characteristics for E0 1; US 1

    and amin amax p=6 are shown in Fig. 8.

    Presented control laws for TCPSTs are globally optimal,

    however, for a practical application it is reasonable to use

    locally measurable electric quantities. A good example ofFACTS control based on local measurements is presented in

    [2] and references therein. In this case control laws are not

    Fig. 4. Control law for a QBT.

    Fig. 5. Extreme QBT transfer characteristics.

    Fig. 6. Comparison of maximum QBT transfer characteristics.

    Fig. 7. Difference in maximum transfer characteristics.

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453448

  • 7/29/2019 TCPST

    5/9

    globally optimal anymore. Furthermore, instead of

    the generators internal electro-motive force and infinite

    busbar voltage, voltage measurements from both ends of the

    transmission path can be also used to obtain a local

    optimum.

    3. Developing energy function

    According to the specific bangbang control strategy a

    TCPST must jump between maximum and minimum

    transfer characteristics. Thus, we can speculate that during

    the first swing the TCPST control parameter is always set so

    that the maximum transfer characteristic is attained. We

    have used this fact to develop several energy functions that

    can be used in any system that can be reduced to SMIBsystem without loosing the information on FACTS location

    e.g. longitudinal or interconnected systems. Note that a

    radial system topology can also be a consequence of a relay

    protection response to a disturbance in meshed systems. The

    proposed energy functions meet all the conditions for a

    Lyapunov function.

    3.1. PAR energy function

    From the direct-method point of view it is sufficient to

    know the behaviour of the TCPST for the period of the fault-

    on. Hence for the purposes of CCT determination we can

    omit the sign of Dv (it does not change during theacceleration), which affects the PAR control law. We only

    have to examine the PAR maximum transfer characteristic

    shown in Fig. 9. This characteristic is composed of the

    intervals defined in Eq. (14).

    Ped0 d0 interval

    Pmaxe sind

    0amax; 2R k2p,d

    0,p

    22amax k2p

    Pmaxe ;

    p

    22amax k2p#d#

    p

    2amin k2p

    P

    max

    e sind

    02amin;

    p

    2 amin k2p,d

    0#

    2pk12

    R14

    where Pmaxe is defined as

    E0US

    X0 and

    k

    IntegerPartR d0

    2p

    ; d0$R

    IntegerPartR d0

    2p

    21; d0,R

    15

    Ifamin amax then R equals p=2; otherwise R is defined as

    shown in Fig. 9 (the point where curves sind0 amax and

    sind02amin meet).

    Energy functions are always constructed for the post-

    fault system. In accordance with the general agreement that

    the first integral of the swing equation constitutes a proper

    energy function we integrated the swing Eq. (3) over all theintervals of Eq. (14). The integration yields the following

    energy function:

    nPARd0;Dv nKEDv nPE PARd

    0 16

    nKEDv 1

    2MDv2 17

    The term (17) as a kinetic energy is also used later on in theQBT case.

    nPE PARd0 nPE PARi21

    nPE PARiAd02R k2p, d0 ,

    p

    22amax k2p

    nPE PAR iBd0p

    22 amax k2p# d

    0#

    p

    2

    amin k2p

    nPE PAR iCd0p

    2 amin

    k2p, d0 # 2pk 12R

    8>>>>>>>>>>>>>>>>>>>>>>>>>:

    18

    where:

    nPE PAR iA 2

    Pmd

    02 ^

    d

    0S

    2

    P

    max

    e cosd

    0

    amax2 cosd0S amax 19

    Fig. 8. Transmission characteristics-QBT at grid.

    Fig. 9. PAR maximum transfer characteristics (a is bounded).

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 449

  • 7/29/2019 TCPST

    6/9

    nPE PARiB Pmaxe 2 Pm d

    02

    p

    22 amax

    nPE PAR iC 2Pm d02 p

    2 amin

    2 Pmaxe cosd

    02amin

    d0S is the PAR stable equilibrium point (SEP) at the

    maximum transfer characteristic. It equals d0S2 amax:

    d0S represents the SEP of a post-fault system without a

    PAR. nPE i21 expresses the constant value of the

    potential energy with which we enter the current

    interval. The initial value of nPE i21 is zero. In Appendix

    A it is shown that Eq. (16) is a Lyapunov function in

    the usual sense.

    3.2. QBT energy function

    3.2.1. QBT energy function for the proposed new strategy

    The considerations that are valid for the PAR

    case (Section A) are also valid for a QBT. Starting with

    an examination of Eq. (11) it was established that neglecting

    Dv has no impact on (11) if we consider the fault-ontrajectory, hence we can rewrite the control law as:

    a arctan 2tan d0 sec d0ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi

    1 X2

    X0

    1

    cos2d0

    s !20

    We again executed the first integral of motion and took into

    account Eq. (20) for Pe: However, the analytical solution of

    the referred integral could not be found. We thereforesuggest that the problem is handled numerically. Hence

    energy function can be denoted as:

    WQBTd0;Dv WKEDv WPE QBTd

    0 21

    WPE QBTd0 2Pmd

    02 d0S

    d0d0S

    E0US

    X0

    1

    cosaX2 cosa

    sind0 add0 22

    where a varies as described in Eq. (20). In the special case

    when a QBT is located at the grid (orientation 2) it is

    possible to construct a strict Lyapunov function. As inSection 3.1 we make a similar assumption that the device

    follows the maximum transfer characteristic (Fig. 10). The

    latter is based on the transfer characteristic Eq. (12) and the

    proposed bang bang control law (13) with the influence of

    Dvneglected.

    After an examination ofFig. 10 we chose to carry out the

    integration of the swing equation over the following two

    intervals:

    Ped0 d0 interval

    E0US

    X0sin d0 tan amaxcos d

    0; d0 ,

    p

    2

    E0US

    X0sin d0 2 tan amincos d

    0; d0 $

    p

    2

    23

    If we suppose that Pmaxe . Pm; the post-fault system yields

    only one SEP. Pmaxe is defined as E0US=X

    0: Otherwise we

    could deal with two SEP cases, which is evident from Fig. 10

    if mechanical power Pm is increased. After the integration

    of Eq. (3), keeping Eq. (23) in mind, we get:

    nQBTd0;Dv nKEDv nPE QBTd

    0 24

    nPE QBTd0 2Pmd

    02 d0 S2Pmaxe cosd

    02cos d0S

    nPE QBT i21 Pmax

    e amaxsind02

    sin^d

    0S

    ;

    d0,p

    2

    nPE QBT i212Pmaxe tanamin sind

    02 sin

    p

    2

    d0$p

    2

    8>>>>>>>>>>>>>>>>>:

    25

    nPE QBT i21 represents the constant value of the potential

    energy from the previous interval. Its initial value is zero.

    3.2.2. QBT energy function for classical control strategy

    The classical control strategy has the same effect on the

    transmission characteristic as Eq. (13), therefore weconstruct the energy function in the same way as in Sections

    3, 3.1, 3.2, 3.2.1, by integrating the swing Eq. (3) over two

    intervals of Eq. (26):

    PEd0 d0 intervals

    E0US

    X0

    1

    cos amax X2cos amax

    sind0 amax; d0,

    p

    2

    E0US

    X0

    1

    cos amin X2cos amin

    sind0 2 amin; d0$

    p

    2

    26

    Fig. 10. Maximum transfer characteristics-QBT at grid (a limitations

    considered).

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453450

  • 7/29/2019 TCPST

    7/9

    The integration yields:

    nQBTd0;Dv nKEDv nPE QBTd

    0 27

    nPE QBTd0 2Pmd

    02 d0S nPE QBT i21

    2

    Pmaxe1 cosd

    0amax2cosd

    0Samax;

    d0 ,p

    2

    Pmaxe2 cosd

    02amin2cos

    p

    22amin

    ;

    d0 $p

    2

    8>>>>>>>>>>>>>>>>>:

    28

    where:

    Pmaxe1

    E0US

    X0

    1

    cos amaxX2cos amax

    29

    Pmaxe2

    E0US

    X0

    1

    cosaminX2cosamin

    nPE QBT i21 is denominated in the same way as in Section

    3.2.1.

    4. Numerical examples

    In order to demonstrate the effectiveness of the proposed

    control laws and the usefulness of the developed energy

    functions some numerical examples were made. The test

    case is the one from [3], where it is thoroughly examined. Its

    scheme is presented in Fig. 11 while some of the system data

    is presented in Table 1. The QBT device in orientation 2 is

    located at the Grid (BUS 3 node). The transmitted pre-fault

    real power equals 0.9 pu of the generator rated power. For

    the purposes of the digital simulation in the NETOMAC

    (Siemens AG) environment both the generator and the

    excitation control (Semipol) are modelled in detail. On the

    other hand, the generator classical model served to the direct

    method and the transmission lines were presented as a

    reactance calculated from 100-km-long p-sections.

    The disturbance in the system is represented by three-

    phase faults in the outgoing line near the generator terminal

    (BUS1) and as a result the faulty line is disconnected.

    The results obtained by both the direct and conventional

    (simulation) methods are presented in Table 2. We can see

    two different CCTs obtained with the direct method, where

    one fault-on simulation takes into account the effect of the

    damper windings D 0: The CCTs calculated by direct

    methods approach the simulation results (which are

    considered a reference) in a few ms. These results are

    very promising, especially if the simplifications made byapplying direct methods are kept in mind.

    As shown, the estimates of the CCTs obtained using the

    direct method are not conservative. The reason for this may

    be the fact that in the case of the direct method application

    the system resistances are not taken into consideration (they

    cannot be unless an integration is carried out numerically

    along the swing trajectory). In addition, the generator model

    is far simpler than one used for simulation purposes.

    Next,the effectiveness of theproposedQBTcontrol strategy

    compared to the classical control strategy is demonstrated. If

    the QBT is positioned at BUS3 (supposing orientation 2)

    there is,of course, no difference between theapplied strategies.

    If on the other hand the QBT is, with the specific limitsregarding controllable parameter a, placed at the BUS 2,

    differences become evident. The results based on various QBT

    ratings and orientations are presented in Table 3.

    Deviations in percent were calculated as a CCT difference

    between the proposed and the classical control strategies.

    Discussing the results in Table 3 it is evident that a step

    forward has been made in searching for an optimal control

    strategy. The developed control law (12) not only improves

    the transient stability but also provides us with a strategy to

    maximise or minimise the transfer capability of the given

    corridor with a QBT for any of the operating states.

    Fig. 11. The test system.

    Table 1

    System data

    Generator data Lines data Grid data

    Pn 1500 MVA xd00 0:182 pu r 0:03 V/km Un 500 kV

    xd0 0:270 pu x 0:33 V/km Pg 1350 MVA

    Tm 6:6 s xd 1:47 pu c 12 nF/km

    Td00 0:034 s xq

    00 0:211 pu

    Td0 2 s xq

    0 0:636 pu

    Tq00 0:041 s xq xd

    Table 2Obtained CCT

    Direct method Digital simulation

    D 0:0167pu D 0 pu

    CCT DCCT CCT DCCT CCT

    QBTamax;min [deg] [ms] [%] [ms] [%] [ms]

    19.2 107 7.0 102 2.0 100.0

    40.4 167 11.3 157 4.7 150.0

    51.5 209 4.5 195 2 2.5 200.0

    PARamax;min [deg]

    39 109 9.0 104 4.0 100.0

    157 171 14.0 159 6.0 150.0322 235 17.5 214 7.0 200.0

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 451

  • 7/29/2019 TCPST

    8/9

    Calculations have shown that the proposed control

    strategy is quite insensitive with regard to mistakes in

    the evaluation of system reactances. In order to demonstrate

    this, it was assumed that X2 was not known exactly. In the

    calculations of the optimal a, 290% and 400% of X2deviations were considered. The results with the QBT in

    orientation 2 are summarised in Table 4. As shown, the

    CCTs are no longer optimal (as in Table 3), but they are still

    better than when a classical control strategy is applied. This

    has been anticipated because the classical control strategy

    ignores X2: The differences Dwere calculated with regard to

    the optimal CCT from Table 3.

    5. Conclusions

    In this paper new control laws based on a Control

    Lyapunov Function for a PAR and a QBT have been

    presented. They prove that we can squeeze the

    maximum out of a device in any given situation and

    can therefore be called optimal. For a QBT we showed

    that the proposed strategy is more effective in the area of

    large transmission angles than the classical control

    strategy, while for small angles the differences are of

    minor importance. Hence it can be concluded that for

    oscillation damping purposes there is practically no

    difference between the classical and proposed strategies.

    On the other hand, for transient stability purposes the new

    strategy has advantages. Furthermore, it has also been

    shown that the proposed QBT control strategy is robustwith regard to the selection of inappropriate parameters.

    For SMIB systems with TCPSTs new energy functions

    have been constructed that take the effect of FACTS

    devices and their control (optimal and classical) into

    consideration. Any multimachine system with a TCPST that

    can be reduced to a SMIB without losing the information

    about the TCPST location can be treated with developed

    energy functions (e.g. remote generation or interconnec-

    tion). In this case a system is first reduced into a twomachine equivalent and then further reduced into a SMIB

    system [6].

    The results of test calculations are promising, especially

    if the simplifications made by applying direct methods are

    kept in mind.

    Future research work in this field should also endeavour

    to construct structure-preserving energy functions that are

    more versatile.

    Acknowledgements

    The authors gratefully acknowledge the JuniorResearcher Scholarship awarded to U. Gabrijel by Ministry

    of Education, Science and Sport of the Republic of Slovenia.

    Appendix A

    Proving a Lyapunov function for a PAR mainly follows a

    procedure from the literature [2]. A function must satisfy

    three conditions to be recognised as a Lyapunov function:

    (a1) it must have the same stationary points as the maximum

    transfer characteristic (14); (a2) it is positive definite in the

    vicinity of one of the equilibrium points; (a3) its derivative

    is not positive.(a1) Satisfying the first condition can be checked by the

    determination of the nd0;Dv gradient. Assuming that

    Pm , Pmaxe we only check the functions on lateral intervals

    (note:nPE PAR iA;iC are constant):

    gradnPAR

    n

    Dv

    n

    d0

    2664

    3775

    nKE

    Dv

    nPEd0

    2664

    3775 A1

    (a1-1) First interval 2R , d0 ,p

    22 amax verification:

    gradnPAR int: 1 MDv

    2Pm 2 Pmaxe sind

    0 amax

    " #A2

    Table 3

    CCT obtained applying different control strategies

    amax;min [deg] Orientation 1 Orientation 2

    Classical Proposed Classical Proposed

    CCT [ms] D[%] CCT [ms] D[%]

    19.2 88 93 25.4 96 98 22.0

    28.8 79 96 217.7 102 107 24.7

    40.4 27 97 272.2 103 117 212.8

    51.5 97 81 123 234.1

    Table 4

    CCT obtained by applying false X2 in optimal a calculation

    amax;min [deg] 10% X2 500% X2

    CCT [ms] D[%] CCT [ms] D[%]

    19.2 96 22.0 97 21.0

    28.8 103 23.7 105 21.9

    40.4 107 28.5 112 24.251.5 107 213.0 109 211.4

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453452

  • 7/29/2019 TCPST

    9/9

    The gradient is equal to zero at the stationary point whereDv 0 and the electrical power is equal to the mechanical

    power given by d0

    1

    d0S: This point is the equilibrium point

    of the maximum transfer characteristic.

    (a1-2) Third intervalp

    2 amin , d

    0# 2p2R verifica-

    tion:

    gradnPAR int:3 MDv

    2Pm 2 Pmaxe sind

    02 amin

    " #A3

    The gradient Eq. (A3) is equal to zero at the stationary point

    where Dv 0 and the electrical power is equal to the

    mechanical power given by d02 d0U: As can be visualised

    from Fig. 9 this is also an equilibrium point of the maximum

    transfer characteristic.

    (a2) Satisfying the second condition for a Lyapunov

    function can be checked by determining the Hessian matrixfor the first SEP:

    HPAR

    2nPAR

    Dv2

    2nPAR

    d0 Dv

    2nPAR

    d0 Dv

    2nPARd02

    26664

    37775

    M 0

    0 Pmaxe cosd0

    amax

    " #A4

    Silvesters theorem says that this matrix is positive definite

    when the diagonal elements are greater than zero: hence

    M. 0 (which is always true) and in the long term (A4)must be greater than zero, which holds true for the first

    stationary point d0S:

    (a3) The third condition can be checked by determining

    _n dn=dtalong the trajectory of the swing Eq. (3). First we

    express the derivative as:

    _nPAR dn

    dt

    dnKEdt

    dnPE PAR

    dtA5

    and calculate each component respectively:

    dnKEdt

    nKEDv

    dDv

    dtMDv

    dDv

    dt M

    dDv

    dt

    Dv A6

    The factor in the square brackets corresponds to left-handside of Eq. (3). Replacing it by the right-hand side and

    considering Eq. (14) as Pe yieldsdnKE

    dt:

    Similarly, the derivative of the potential energy can be

    calculated (note: nPE PARi A;B;C are constant):

    dnPE PARdt

    nPE PAR

    d0

    dd0

    dtA7

    Summing the results of Eqs. (A6) and (A7) gives:

    _nPAR dnPAR

    dt 2D Dv2 A8

    whichrepresentsthetotalsystemenergydecay.Itcorresponds

    to the natural damping and its positive damping coefficient.

    Therefore the _nPAR derivative is negative and hence nPARmeets all three conditions for a Lyapunov function.

    QBT Lyapunov functions Eqs. (24) and (27) can be

    verified in a similar way.

    References

    [1] Noroozian M, Angquist L, Ghandari M, Andersson G. Improving

    Power System Dynamics by Series-Connected FACTS Devices. IEEE

    Trans Power Delivery 1997;12(4):163541.

    [2] Machowski J, Bialek JW, Bumby JR. Power system dynamics and

    stability. Wiley; 1997.

    [3] Yong Hua Song Allan T, editor. Flexible ac transmission systems

    (FACTS), vol. 30. London: IEE, cop; 1999. p. 443505. (IEE power

    and energy series).

    [4] Mihalic R, Zunko P. Phase-shifting transformer with fixed phase

    between terminal voltage and voltage boost-tool for transient stabilitymargin enhancement. IEE Proc., Gener. Transm. Distrib. 1995;

    142(3):25762.

    [5] Ghandhari M, Andersson G, Pavella M, Ernst D. A control strategy for

    controllable series capacitor in electric power systems. Automatica

    2001;37:157583.

    [6] Pavella M, Murthy PG. Transient stability of power systems. Wiley;

    1994.

    [7] Peter Sauer W, Pai MA. Pai, power system dynamics and stability.

    Prentice Hall; 1998.

    [8] Hiskens IA, Hill DJ. Incorporation of SVCs into energy function

    methods. Trans Power Syst 1992;7(1).

    [9] Padiyar KR, Immanuel V. Modelling of SVC for stability evaluation

    using structure preserving energy function. Electric Power Energy

    Syst 1994;16(5).

    [10] Gabrijel U, Mihalic R. Direct methods for transient stability

    assessment in power systems comprising controllable series devices.

    IEEE Trans Power Syst 2002;September:111622.

    [11] Sepulchre R, Jankovic M, Kokotovic PV. Constructive nonlinear

    control. Springer; 1997.

    [12] Freeman RA, Kokotovic PV. Robust nonlinear control design.

    Boston: Birkhauser; 1996.

    Uros Gabrijel (1972) received his Dr Sc Degree in electrical

    engineering from the University of Ljubljana, Slovenia, in 2003.

    After a year with a local electric energy distribution company he joined

    the LPEE Laboratory at the Faculty of Electrical Engineering in

    Ljubljana where he is currently working as a researcher. His areas of

    interest include system analysis and FACTS devices.

    Rafael Mihalic (1961) received his diploma Engineer, MSc and Dr Sc

    degrees from The University of Ljubljana, Slovenia, in 1986, 1989, and

    1993, respectively. After finishing his basic technical education in 1986

    he became a teaching assistant at the Department of Power Systems and

    Devices of the Faculty for Electrical and Computer Engineering in

    Ljubljana. Between 1988 and 1991 he was a member of the Siemens

    Power Transmission and Distribution Group, Erlangen, Germany.

    Since 2000 he has been an associate professor at the University of

    Ljubljana. His areas of interest include system analysis and FACTS

    devices. Prof. Mihalic is an IEEE, NY and Cigre, Paris member.

    R. Mihalic, U. Gabrijel / Electrical Power and Energy Systems 26 (2004) 445453 453