Upload
sara-ramsey
View
214
Download
0
Tags:
Embed Size (px)
Citation preview
Sustainable School DesignCreating Healthy, High Performance School Facilities
Presented byPresented byStephen M. Koontz, Energy Services Leader, Tampa Bay TraneStephen M. Koontz, Energy Services Leader, Tampa Bay Trane
CEFPI High Performance Schools Symposium 2009
LEED for Schools2
Adv. Energy Design Guides
Collaboration of: ASHRAE AIA IESNA USGBC U.S. DOE SBIC CHPS NCEF
www.ashrae.org/freeaedg
LEED for Schools3
AEDG for K-12 School Buildings Overview
Climate-specific recommendations to achieve 30% energy savings
Promotes off-the-shelf technology (no special expertise to design/install)
Addresses whole building and the interaction of sub-systems (envelope, lighting, HVAC, service water heating)
LEED for Schools4
LEED® for Schools
Can be used to achieve four points under Energy and Atmosphere Credit 1
LEED for Schools5
Chapter 3
Climate Zone Map
LEED for Schools6
Chapter 3
Recommendation Tables
LEED for Schools7
4b
smallpackagedrooftops
unitventilators
water-sourceheat pumps
Prescriptive HVAC recommendations for K-12What Type of HVAC System?
chilled-waterVAV
LEED for Schools8
Prescriptive recommendations forSix HVAC System Types
HV-1: Single-zone, packaged DX units (or split DX systems)
HV-2: Water-source (or ground-source) heat pumps with dedicated OA system
HV-3: Unit ventilators with water chiller and boiler HV-4: Fan coils with water chiller and boiler and
dedicated OA system HV-5: Multiple-zone, VAV packaged DX rooftop units HV-6: Multiple-zone, VAV air handlers with water chiller
LEED for Schools9
Climate-specific and system-specificRecommendation Tables
Unique recommendations are included for each HVAC system type in the climate-specific tables (Chapter 3)
LEED for Schools10
Climate-specific and system-specificRecommendation Tables
Some system types are not recommended for certain climate zones because of the impact of humidity on energy use
LEED for Schools11
Chapter 5Good Design Practice
Load calculations
Dehumidification
Energy recovery
Equipment efficiencies
Ventilation air
Dedicated OA systems
Economizer
Demand ventilation
Exhaust air systems
Fan motor efficiencies
System-level controls
Chilled-water system
Hot-water heating
Thermal zoning
Filters
Duct design, construction
Duct insulation
Duct sealing, leak testing
Air balancing
Commissioning
Relief versus return fans
Heating sources
Noise control
Proper maintenance
Zone temperature control
Operable windows
LEED for Schools12
HV-10HVAC Equipment Efficiencies
Recommended efficiencies based on: Climate zone HVAC system type System size (capacity) Fuel type (electricity or natural gas)
for climate zone 5
LEED for Schools13
HV-11Ventilation Air
Determine based on ASHRAE 62.1 Use actual occupancy
for calculations, not exit population
Use population diversity (D)when using multiple-zonerecirculating systems
Use time-of-day schedulesto introduce ventilation aironly when a zone isexpected to be occupied
LEED for Schools14
HV9 or HV14Energy Used to Condition OA
Because conditioning OA for ventilation is such a big contributor to energy use in K-12 schools, either exhaust-air energy recovery or demand-controlled ventilation (DCV) is recommended
LEED for Schools15
HV-8Part-Load Dehumidification
Design system to minimize number of hours that space relative humidity remains above 60%
Recommends methods for improving part-load dehumidification (by HVAC system type)
LEED for Schools16
HV-12Dedicated OA Systems
LEED for Schools17
Proper Maintenance
Neglecting preventive maintenance practices can quickly negate any energy savings expected Filters should be
replaced regularly ERVs need to be
cleaned periodically Dampers, valves,
louvers, and sensors must all be periodically inspected and calibrated
LEED for Schools18
Commissioning
Selection of commissioningauthority
Include commissioningactivities in the project schedule
Recommendedcommissioningactivities
Advanced Energy Design Guidefor K-12 School Buildings
www.ashrae.org/freeaedg