30
BY STANFORD UNIVERSITY FIRE MARSHAL’S OFFICE AT ENVIRONMENT HEALTH & SAFETY DEPT. Fire Alarm System Basics

SU-FMO Fire Alarm System Basics Presentation to Building Managers 7-28-2014

Embed Size (px)

DESCRIPTION

fire alarm system basics

Citation preview

  • BY STANFORD UNIVERSITY

    FIRE MARSHALS OFFICE AT

    ENVIRONMENT HEALTH & SAFETY DEPT.

    Fire Alarm System Basics

  • JOE LEUNG University Fire Marshal

    Manager, Fire Safety Program

    AARON MCCARTHY Senior Fire

    Protection Engineer

    ROBERT PORTERFIELD Fire Protection

    Engineer

    JENNIFER LEE Fire Protection

    Engineer

    JARNAIL DHALLA Fire

    Protection Engineer

    Assistant University Fire Marshal

    RALPH DURHAM University

    Fire Inspector FRANK MO MIRANDA Fire

    Systems Supervisor

    FRANK GARDNER

    Fire Systems Lead Technician

    RON MORRISON Senior Fire Sprinkler Technician

    CHRIS FRAZIER

    ARTHUR RICKEY JOHNSON

    RICH WILKINS

    JOE JACKSON

    MIKE ARMSTRONG

    JAMES BAXLEY

    JASON LOPEZ

    CARLOS GONZALEZ

    ZEEB DAVID GUARNEROS

    RUDY GARAY

    BRANDON MCCLINTOCK

    Fire Sprinkler Technicians

    Fire Alarm Technicians

    Fire Extinguisher Technicians

    Building C

    JESSE TORRES

  • Fire Alarm Systems

    Several main functions:

    Provide a means to identify a developing fire through automatic methods.

    They alert building occupants to a fire condition and the need to

    evacuate. Another common function is the transmission of an alarm notification

    signal to the fire department or other emergency response organization. Fire alarm systems may also shut down electrical, air handling equipment

    or special process operations, and they may be used to initiate automatic suppression systems.

  • Fire Alarm Systems

    Requirements California Code of Regulations has 28 sections/titles. Title 24: California Building Standards

    Part 2: California Building Code Part 3: California Electric Code Part 9: California Fire Code

    Chapter 9 lists basic requirements based on occupancy type.

    Depending on the anticipated fire scenario, building and use type, number and type of occupants and criticality of contents and mission There are 3 common types of systems: Conventional, Addressable, Analog Addressable. Analog addressable type is not commonly used.

  • Fire Alarm System Types

    Conventional Lower initial equipment

    costs. Defined location of

    fire/alarm not provided at the panel or central station

    Can be easier to program. Limited expansion

    capability.

    Addressable Easier to install. More system status

    information at the panel and central station.

    Input/Output programming much more flexible.

    Usually much more room available to expand.

  • Conventional Systems

    Wiring must be installed in a supervised manner either Class A, or Class B with an EOLR. Alarm/Trouble conditions are annunciated by zone only. Inspection is required to determine the device in alarm/trouble

    Zone #1

    4.7K EOLR

    4.7K EOLR

    Zone #2

    NAC #1

    FACP

  • Addressable Systems

    Each point on the SLC loop is given a unique address when installed. Alarm/Trouble conditions are annunciated by a unique message for each device.

    001 002

    003

    004

    005 006

    FACP

    FIRE FIRE

    SILENT KNIGHT

    Addressable Pull Station

    Addressable Relay Module

    (Fan Shutdown)

    Addressable Heat Detector

    4.7K EOLR

    NAC #1

    Addressable Smoke Detector

    Addressable Input Module (Waterflow)

    Addressable Smoke Detector

  • Fire Alarm System Principles

    Manual fire detection is the oldest method of detection. In the simplest form, a person yelling can provide fire warning. In buildings, however, a person's voice may not always transmit throughout the structure. For this reason, manual alarm stations are installed. The general design philosophy is to place stations within reach along paths of escape/egress. It is for this reason that they can usually be found near exit doors. The advantage of manual alarm stations is that, upon discovering the fire, they provide occupants with a readily identifiable means to activate the building fire alarm system. The alarm system can then serve in lieu of the shouting person's voice. They are simple devices, and can be highly reliable.

  • Fire Detection Principles

    Automatic Detectors Spot type

  • Fire Detection Principles

    Automatic Detectors Photoelectric

    NFPA 72, Light Scattering Smoke Detection. The principle of using a light source and a photosensitive sensor arranged so that the rays from the light source do not normally fall onto the photosensitive sensor. When smoke particles enter the light path, some of the light is scattered by reflection and refraction onto the sensor. The light signal is processed and used to convey an alarm condition when it meets preset criteria.

  • Fire Detection Principles

    Automatic Detectors Photoelectric

    A Light Source B Photo Sensor

    In the normal case, the light from the light source on the left shoots straight across and misses the sensor. When smoke enters the chamber, however, the smoke particles scatter the light and some amount of light hits the sensor.

  • Fire Detection Principles

    Automatic Detectors Ionization This type is better at detecting the smaller amounts of smoke produced by flaming fires. An ionization chamber consists of two plates with a voltage across them, along with a radioactive source of ionizing radiation.Inside the ionization detector is a small amount (about 1/5000th of a gram) of Americium-241. This radioactive element has a half-life of 432 years, and is a good source of alpha particles.

    NFPA 72, Ionization Smoke Detection. The principle of using a small amount of radioactive material to ionize the air between two differentially charged electrodes to sense the presence of smoke particles. Smoke Particles entering the ionization volume decrease the conductance of the air by reducing ion mobility. The reduced conductance signal is processed and used to convey an alarm condition when it meets preset criteria.

  • Fire Detection Principles

    Automatic Detectors Ionization

    The alpha particles generated by the americium ionize the oxygen and nitrogen atoms of the air in the chamber. To "ionize" means to "knock an electron off an atom ending with a free electron (with a negative charge) and an atom missing one electron (with a positive charge). The negative electron is attracted to the plate with a positive voltage, and the positive atom is attracted to the plate with a negative voltage (opposites attract, just like with magnets). The electronics in the smoke detector sense the small amount of electrical current that these electrons and ions moving toward the plates represent.

    When smoke enters the ionization chamber, it disrupts this current -- the smoke particles attach to the ions and neutralize them. The smoke detector senses the drop in current between the plates and sets off the horn.

  • Fire Detection Principles

    Automatic Detectors Combination

    NFPA 72, Combination Detector. A device that either responds to more than one of the fire phenomena or employs more than one operating principle to sense one of these phenomena. Typical examples are a combination of a heat detector with a smoke detector or a combination of rate-of-rise and fixed temperature heat detector. This device has listings for each sensing method employed.

    Combination detectors contain more than one element which responds to fire. These detectors may be designed to respond from either element, or from the combined partial or complete response of both elements. An example of the former is a heat detector that operates on both the rate-of-raise and fixed-temperature principles. Its advantage is that the rate-of-rise element will respond quickly to rapidly developing fire, while the fixed-temperature element will respond to a slowly developing fire when the detecting element reaches its set point temperature.

  • Building Notification

    Notification Appliances

    NFPA 72, Notification Appliance. A fire alarm system component such as a bell, horn, speaker, light or text display that provides audible, tactile, or visible outputs, or any combination thereof.

    NFPA 72, Audible Notification Appliance. A notification appliance that alerts by the sense of hearing.

    NFPA 72, Visible Notification Appliance. A notification appliance that alerts by the sense of sight.

  • Fire Alarm Circuit Classes

    NFPA 72, Classes. Initiating device circuits, notification appliance circuits, and signaling line circuits shall be permitted to be designated as either Class A or Class B, depending on their performance during non-simultaneous single circuit fault conditions as specified by the following:

    (1) Initiating device circuits and signaling line circuits that transmit an alarm or supervisory signal, or notification appliance circuits that allow all connected devices to operate during a single open or a non-simultaneous single ground fault on any circuit conductor, shall be designated as Class A (2) Initiating device circuits and signaling line circuits that do not transmit an alarm or supervisory signal, or notification appliance circuits that do not allow all connected devices to operate beyond the location of a single open on any circuit conductor, shall be designated as Class B

  • Class B Initiating Device Circuit

    4.7K EOLR

    4.7K EOLR

    Class B Notification Appliance Circuit

    Conventional Class B Circuits

    FACP

  • Single open circuit condition causes a trouble on the panel and renders all devices beyond the fault inoperative.

    Class B Initiating Device Circuit

    4.7K EOLR

    4.7K EOLR

    Class B Notification Appliance Circuit

    Conventional System Class B Circuits

    FACP

  • Class A Initiating Device Circuit

    Class A Notification Appliance Circuit

    Class A Circuits

    End of line supervision resistors are not necessary as the loop returns to the panel and is driven from both ends.

    FACP

  • Class A Initiating Device Circuit

    Class A Notification Appliance Circuit

    Class A Circuits

    Single open circuit condition causes a trouble on the panel. All devices on the loop remain operative.

    FACP

  • Licensing Requirements

    Requirements for technicians per NFPA 72

    State Certified in Fire/Life Safety or Electrician

    NICET Certification

    Fire Alarm Manufacturer Certification

  • FireFinder XLS (252 devices, expandable to 2500 devices)

    NFS-320 (318 devices) NFS2-640 (636 devices) NFS2-3030 (3,180 devices)

    Fire Alarm Panel Options

  • 3 Types of Fire Alarm Signals

    1. TROUBLE Local sounding (beeping) on FACP and Annunciators No horn/strobes sounding or flashing Low battery, smoke detector removed, ground fault, open horn circuit,

    etc. Alarm Tech responds

    2. SUPERVISORY Local sounding (beeping) on FACP and Annunciators No horn/strobes sounding or flashing Sprinkler valve closed, duct detector activated*, low-air on pre-action

    system Fire Department responds

    3. ALARM All horn/strobes sounding and flashing Building occupants to evacuate Smoke detector, manual pull, waterflow, duct detector, or heat detector

    activated Fire Department responds

  • SUFMO Fire Alarm Techs

    Preventive Maintenance

    Semiannual visual inspections

    Annual testing

    Annual fire smoke damper testing (with HVAC)

    Quarterly student evacuation drills (with Inspectors & FPEs)

    Monthly evacuation drills at child day care centers (with Inspectors)

    Annual elevator recall testing (with Kone A)

    Construction Projects

    Initial acceptance testing with FPEs per Stanford FDG and applicable codes

    Final acceptance testing with FPEs and the Authority Having Jurisdiction (Santa Clara County or Palo Alto)

    Isolating system components for contractors to work (i.e., SESI)

    Other Responsibilities

    Respond to all fire system troubles 24/7 (On-Call)

    Provide fire department assistance with technical issues or nuisance alarms

    Program fire alarm systems with laptop and proprietary software

    Troubleshoot and repair fire alarm systems

    Maintain the Remote Monitoring Station

    Providing services to

    University Main Campus

    Various off campus locations (Hopkins, Boathouse, Porter Drive, and others)

    Fire smoke damper

    There is a smoke detector up there?

    No smoking please

  • Remote Monitoring Station

    Mesh network Licensed FCC Radio Frequency (RF) Antennas and receiving equipment in Building C Dispatcher located at Palo Alto Communications (250 Hamilton) Fire Department contacted by dispatcher directly Over 300 monitored systems

    ESF BLDG C

    Remote Alarm Transmitter (RAT)

    Mesh Network Concept

    Antennas on Building C Palo Alto Communications

  • Benefits of RF Mesh Network

    All of these are monitored systems

    ESF

    Speed (5-10 seconds) Monthly expenses Reliability Natural disasters

    Monitoring equipment in Building C

  • Key Changes 2010/2013 Edition

    Renaming NFPA 72 - Both New Sections on Gas Detection - Both Direction on Intelligibility- Both Low Frequency sounders - 2013 Emergency Communications Systems (ECS) Chapter Circuits and Pathways Chapter Emergency Control Functions and Interfaces Chapter New Annex System Performance and Design Guide

  • Key Changes 2013 Edition

    14.2.10 Test Plan

    14.2.10.1 A test plan shall be written to clearly establish the scope of testing14.2.10.2 The test plan and results shall be documented

    with the testing records. Annex material to explain test plan

  • Key Changes 2010/2013 Edition

    Section 23.8.4.8 was revised to require signals from CO

    detectors or CO detection systems to initiate a CO alarm signal (Temporal 4).

    A new exception to 23.8.4.8 permits supervisory signals where permitted by the building response plan.

    Fire Alarm System BasicsSlide Number 2Fire Alarm SystemsFire Alarm SystemsFire Alarm System TypesConventional SystemsAddressable SystemsFire Alarm System PrinciplesFire Detection PrinciplesFire Detection PrinciplesFire Detection PrinciplesFire Detection PrinciplesFire Detection PrinciplesFire Detection PrinciplesBuilding NotificationFire Alarm Circuit ClassesConventional Class B CircuitsConventional System Class B CircuitsClass A CircuitsClass A CircuitsLicensing RequirementsFire Alarm Panel Options3 Types of Fire Alarm SignalsSlide Number 24SUFMO Fire Alarm TechsRemote Monitoring StationSlide Number 27Key Changes 2010/2013 EditionKey Changes 2013 EditionKey Changes 2010/2013 Edition