Structure Design Criteria-final

Embed Size (px)

Citation preview

  • 8/19/2019 Structure Design Criteria-final

    1/15

     

    DARIYAH VILLA

    Structural Design Criteria15/5/2013

  • 8/19/2019 Structure Design Criteria-final

    2/15

    STRUCTURAL DESIGN PAGE NO. 

    1. INTRODUCTION…………………………………….………………..3

    2.  GENERAL OBJECTIVE .......................................................... 3 

    2.1 Safety and Strength .................................................... 3

    2.2 structural stability …………………….………………….3

    2.3 Durability ..................................................................... 3 

    2.4 Economy ..................................................................... 4 

    2.5 Serviceability ............................................................... 4 

    2.6 Constructability ............................................................ 4

    2.7 Spesifecation ............................................................... 5 

    3.  STRUCTURAL DESIGN PARAMETERS ................................. 5 

    3.1  Design codes and refrences ...................................... 5

    3.2  Design load ............................................................... 5

    3.3  Load combinatons ...................................................... 6

    4.  MATERIALS ............................................................................ 7 

    4.1  Concrete ................................................................. 7 

    4.2  Reinforcement ........................................................ 8 

    4.3  Structural Steelwork ............................................... 8 

    4.4  Block Work Walls ................................................... 8 

    4.5  Timber .................................................................... 8 

    4.6  Fill Material ............................................................. 8 

    5  STRUCTURAL SYSTEM ......................................................... 8 

    5.1  Substructure ........................................................... 9 

    5.2  Superstructure ..................................................... 10 

    7 EXTERNAL WORKS……………….. ................................. 19

    8 FUTURE VERTICAL EXTENSTION……………….. .......... 19 

    9 THERMAL INSULATION………………..  ........................... 19 

    11 SOFTWARE PROGRAMS………………............................20 

  • 8/19/2019 Structure Design Criteria-final

    3/15

    LIST OF FIGURES PAGE NO.

      Figure 9:: Economy beam depth, depends on Mu, beam width.................17

      Figure 10:: Economy beam reinforcment, depends on Mu, beam width.....17

      Figure 11:: Columns Schematic Sizes, depends on Pu, % of steel............18

    LIST OF TABLES PAGE NO.

      Table 1:: Concrete Grades & Basic Mix Requirements........................ . .......7

      Table2:: Structural Software's...................................................... ................20

  • 8/19/2019 Structure Design Criteria-final

    4/15

    1- Introduction:

    The purpose of this report is to clarify the design criteria, design parameters and structural system.

    The structural systems adopted for the proposed project compatible with the architectural design

    philosophy. The design reflects the particular needs of any special functional parameters of the

    project. The structural elements designed generally in accordance with Saudi Building Code(SBC)

    and American Building code and there standards.

    Project Description:

    The project consists of two basements, ground, first and roof mainly it is containing living rooms,

    bed room, and other services rooms, for more details please refer to arch drawings.

    2- General objectives:

    The objective of the structural design is to achieve the optimum structural system and requirement

    as stipulated in the relevant codes and standards that will satisfy the following criteria:

    2.1 Safety and strength: 

    Shall be as defined by the current (SBC) codes in terms of loading and strength, the design

    method for all structural elements will be in accordance to Limit State Design.

    2.2 Structural Stability:  

    The structure should be designed to adequately transmit the design ultimate dead, live,

    wind, earthquake and imposed loads safely from the highest supported level to the

    foundations.In addition, lateral stability of the structure shall be achieved for all critical load cases which

    includes seismic and wind forces. Limit of lateral drift shall be according to the code

    requirement for all load types, In order to check the lateral stability of the building, a three

    dimensional finite element model has been created using a well-known computer program

    Etabs-V9.7.4. Also the provisions of section 7.13 of SBC 304 for structural integrity should

    be achieved.

    2.3 Durability:

    Concrete mixes and cover are to be provided to protect reinforcements against corrosion for

    the soil exposure conditions to be determined based on geotechnical testing, to avoid attack

    of deleterious salts on concrete, it is recommended that foundation, basement, and other

    structure coming on contact with the soil or groundwater be constructed using ASTM Type

    "V" cement .

    2.3.1 Concrete Cover:

    Concrete cover to steel reinforcement shall be provided to protect the reinforcement against

    corrosion and fire according to SBC clause 7.7.

    Cast-in-place concrete (Non-Prestressed)

  • 8/19/2019 Structure Design Criteria-final

    5/15

    a) Concrete cast against and permanently exposed to earth = 75mm

    b) Concrete exposed to earth or weather

    Diameter 18 mm and smaller = 40mm

    Diameter larger than 20 mm = 50mm

    c) Concrete not exposed to weather or in contact with ground

    Slabs and Walls = 20mm

    Beams and Columns = 40mm

    Structural steel works shall be coated by protective coating in order to achieve a minimum

    fire rating of two hrs.

    2.3.2 Waterproofing of structures below ground:

    Waterproofing materials: at least two layer of bitumen coating should be applied to the

    exterior of all the foundation and other concrete coming in contact with soil.

    2.4 Economy:

    Shall be achieved by establishing a practical structural system that will yield the simplest

    structural forms in terms of geometry and logic and will be well suited for existing local

    practices, The structural system shall be conceptualized to emphasize the architectural

    concept. The self-weight of the structure also designated, as dead load is an important

    element in the economic structural design of building. This dead load accounts for

    approximately (70%) of the total strength design of structural elements, An economic

    structural design must therefore seek to reduce dead loads as much as possible, simplicity

    of form reduces the cost of shuttering and labor.

    2.5 Serviceability:Serviceability as defined by relevant codes of practice SBC shall be checked and accounted

    for in the design. Serviceability affects deflection of members, crack control, limitation of

    vibration, acoustics and fire protection.

    2.5.1 Deflection criteria:

    The structure will be designed& checked according to SBC 304.

    2.5.2 Fire resistance:

    The following fire resistance periods in accordance with ACI regulations are to be applied to

    the structural elements.

    Load bearing walls & columns = 4 hrs fire rating

    Floor construction including beams = 2 hrs fire rating

    Shafts and stair walls = 4 hrs fire rating

    2.6 Constructability:

    Ease and economy of construction will be high among the designer's priorities.

    2.7 Specification.

    Material and workmanship specification shall be based upon relevant SBC and American

    standards.

  • 8/19/2019 Structure Design Criteria-final

    6/15

    3- Structural design parameters:

    3.1 design codes and references.

    The structural design, in general, will be in accordance with the following codes of practice.

      ACI-318-05: Building Code Requirements for Structural Concrete (318M-05).

      ASCE 7-05: Minimum Design Loads for buildings and other Structures, for wind load. 

      IBC 2003 : International Building Code, for seismic load.

      SBC 301 : Saudi Building Code, Minimum load requirements for the design of buildings and

    other structures.

      SBC 304 : Saudi Building Code, concrete structure requirement.

      AISC-ASD: American Institute of Steel Construction – Allowable Stress Design.

    3.2 Loadings:

    Design dead load and live load as per ASCE 7-05 and SBC 301.

    3.2.1 Dead loads:

    Principle dead loads to be carried by the structure (except self-weight) are cladding,

    floor finishes, partitions and landscaping loads. Allowance for these loads is to be

    taken in consideration in the design.

    Reinforce concrete = 24 KN/m³

    Ceramic or quarry tile (20 mm) on

    25 mm = 1.1 KN/m2 

    Water = 10 KN/m³

    Sand  =15 KN/m3 

    Services = 0.5 KN/m2 

    Weight of hollow blocks ≥ 30 kg

    - Reference: Table 3-1 and Table 3-2 SBC 301

    3.2.2 Live loads:

    The Minimum live loading will be as specified in ASCE 7-02 and SBC 301 is 2.0 KN/m2 

    - Reference: Table 4-1 SBC 301

    3.2.3 Wind loads:

    Wind load calculation shall be done using ASCE 7-05 and SBC 301 according to the

    following Criteria

    Wind Speed = 170 Km/hr. Figure 6.4.1 SBC 301

    Exposure Type = B

    Importance Factor = 1.15

    Topographical Factor = 1.00

    Gust Factor = 0.85

    Directionality Factor = 0.85

    Windward Coefficient = 0.80Leeward Coefficient = -0.50

  • 8/19/2019 Structure Design Criteria-final

    7/15

    3.2.4 Seismic loads:

     According to the IBC 2003 and SBC 301; the seismic coefficient for Riyadh

    are Ss=0.271g and S1=0.098g, and according to soil investigation report soil profile

    type =C, so SDs=0.415g and SD1=0.228g these factors should be used in the

    design of the proposed project, and the importance factor equal to 1.25.

    3.3 Load combinations: 

    The load combinations shall be in accordance with ACI318-05, the following

    combinations shall apply:

    Ultimate limit state (strength) Loads:

    The principal load combinations for strength are:

    U = 1.4 (D + F) (3-1)U = 1.4 (D + F + T ) + 1.7(L + H ) + 0.5 (Lr or R ) (3-2)U = 1.2D + 1.6 (Lr or R ) + (1.0 L or 0.8 W ) (3-3)

    U = 1.2D + 1.6W + 1.0L + 0.5(Lr or R ) (3-4)U = 1.2D + 1.0E + 1.0L (3-5)U = 0.9D + 1.6W + 1.6H (3-6)U = 0.9D + 1.0E + 1.6H (3-7)

    except as follows:

    (a) The load factor on L in Eq. (3-3) to (3-5) shall be permitted to be

    reduced to 0.5 except for garages, areas occupied as places of public

    assembly, and all areas where the live load value of 5 kN/m2 to be

    consistent with the Saudi Building Code for Loading (SBC 301).

    (b) The load factor on H shall be set equal to zero in Eq. (3-6) and (3-7) ifthe structural action due to H counteracts that due to W or E. Where lateral

    earth pressure provides resistance to structural actions from other forces, it

    shall not be included in H but shall be included in the design resistance

    Vertical Seismic Components:

    The load effect resulting from the vertical component of the earthquake

    ground motion and is equal to an addition of (0.2SDSD) to the dead load

    effect, D, for Strength Design, and may taken as zero for Allowable Stress

    Design.

    Serviceability Limit State:

    Combinations of actions for serviceability limit states shall be those

    appropriate for the serviceability condition being considered. Appropriate

    combination may include one or a number of the following loads:

    1) D + L

    2) D + L+S ± W or 0.7 E

    3) D + L ± 0.5 W

    4) 0.9D ±0.7E

    Where:D: Dead Load

    L: Live Load

  • 8/19/2019 Structure Design Criteria-final

    8/15

    E: Earthquake Load in Both Directions (EX & EY)

    W: Wind Load

    4- Materials:

    In general, the main structural components and materials will comply with the following outline

    specifications:

    4.1 Concrete:

      All reinforced concrete shall have minimum characteristic cubic strength of 40

    N/mm2 at 28 days.

      Slabs on grade, shall have minimum characteristic cubic strength of 20 N/mm2 at 28

    days.

      Blinding concrete shall have minimum characteristic cubic strength of 18 N/mm2 at

    28 days.

      Admixtures will be used to improve certain properties of concrete admixtures should

    comply with the ASTM standard.

    The Following Table of Concrete Grades and Basic Concrete Mix Requirements:

    Concrete

    Grade (Cube) 

    Cube strength

    (fcu) (MPa)

    Cylinder

    strength (f ’c)

    (MPa)

    Minimum Cement

    Content (Kg/m3)

    Maximum (W/C)

    ratio

    C20  20  16 210 0.60

    C40 

    40 

    32 350 0.40

    Table 1:: Concrete Grades & Basic Mix Requirements.

    - Ordinary Portland cement (OPC) type "I" will be used for superstructure

    reinforcement concrete.

    - ASTM type "V" will be used for substructures (foundation, basement, and other

    concrete structure contact with soil.

    - Maximum aggregate size shall be of 20 mm for all concrete.

    4.2 Reinforcement:

     All main reinforcing bars including mesh reinforcement shall be deformed high

    strength steel bars complying with ASTM standard having minimum yield strength of

    420 MPa and minimum elongation a gauge length 14%.

    4.3 Structural Steel Work:

      Minimum Yield Strength

    Fy =250 MPa for ASTM A36 hot-rolled steel structural sections.

    Fy =345 MPa for ASTM A514 cold-rolled steel structural member.

      Bolts connections

     ASTM A325 high strength bolts for primary connection and ASTM

     A307 for secondary connections and anchor bolts  Weld connections

  • 8/19/2019 Structure Design Criteria-final

    9/15

     ASTM E70xx low hydrogen welding electrodes. All welds shall conform to

     AWS A5.1 and D1.1 Structural Welding code.

      Steel roof deck minimum yield strength

    Fy=225 MPa for ASTM A611 or ASTM A446.

    4.4 Block Work Walls:

    The minimum strength of all non-load bearing hollow concrete blocks shall not be

    less than 7 N/mm2 expressed as force per unit of cross sectional area.

    The minimum strength of all load bearing concrete blocks shall not be less than 10

    N/mm2 expressed as force per unit of cross sectional area.

    4.5 Timber:

     All timber used for architectural purposes, such as pergolas, shall be class SC5

    Hardwood with minimum grade strength of 7 N/mm2.

    4.6 Fill Material:

     All fill shall be from selected, well-graded material and shall be placed in layers not

    exceeding 200mm. Each layer shall be adequately compacted to a minimum 95%

    maximum dry density (Proctor Test) and shall be tested.

    5. Structural System:

     An important part of the total responsibility of the structural engineer is to select from

    the alternatives the best structural system for the given project. The wise choice of

    structural system is far more important in its effect on overall budget and

    serviceability than the refinement in proportioning the individual members.

    The close cooperation with the architect in the early stage of the project is essential

    in developing a structural that not only meet functional and esthetic requirements butexploits to the fullest special advantages of the reinforced concrete which include the

    following:

    1. Versatility of form:  Usually placed in the structure in the fluid state, the

    material is readily adaptable to a wide variety of the architectural and

    functional requirement.

    2.  Durability: with proper protection of the steel reinforcement. The structure

    will have long life, even under highly adverse climatic or environmental

    conditions. 

    3.  Fire resistance:  with proper protection of the reinforcement, a

    reinforcement concrete structure provides the maximum in fire protection. 

    4.  Speed on construction:  in terms of the entire period, form the date of

    approval of the contract drawings to the date of completion; a concrete

    building can often be complete in the less time than a steel structure.

     Although the filed erection of steel building in more rapid, this phase must

    necessarily be preceded by prefabrication of all part in the shop. 

    5.  Cost: in many case the first cost of concrete structure is less than that of a

    comparable steel structure. In almost every case, maintenance cost is less. 

    6.  Availability of labor and material:  it is always possible to make use of

    local source of labor, and in many inaccessible area s, a nearby sour of

  • 8/19/2019 Structure Design Criteria-final

    10/15

    good aggregate can be found, so that only the cement and reinforcement

    need to be brought in form a remote source.

    The structural concrete elements in the system can be summarized as follows:

    5.1 Substructure:

    5.1.1 Foundations:

    Introduction: 

    Footings are structural members used to support columns and walls and

    transmit their loads to the underlying soils, Reinforced concrete is a material

    admirably suited for footing and is used as such for both reinforced concrete

    and structural steel buildings, bridges, towers and other structures.

    Not only is it desired to transfer the superstructure loads to the soil beneath

    in manner that will prevent excessive or uneven settlements and rotations,

    but it is also necessary to provide sufficient resistance to sliding and

    overturning.

    The closer a foundation is to the ground surface, the more economical it will

    be to construct. There are two reasons, however, that may keep the

    designer from using very shallow foundation. First, it is necessary to locate

    the bottom of a footing below the ground freezing level to avoid vertical

    movement or heaving of the footing as the soil freezes and expands in

    volume. Second, it is necessary to excavate a sufficient distance so that a

    satisfactory bearing material is reached, and this distance may on occasionbe quite a few feet.

    Types of footing

     Among the several type of reinforced concrete footing in common use are

    the wall, isolated, combined, raft and pile cap types.

    1. Wall footing, Simple an enlargement of the bottom of a wall that will

    sufficiently distribute the load to the foundation soil. Wall footing are

    normally used around the perimeter of a building and perhaps for some the

    interior walls.

    2. An isolated or single column footing is used to support the load of single

    column. These are the most commonly used footing.

    3. Combined footing, is used to support two or more columns, it is economic

    where two or more heavily loaded columns are so spaced that normally

    designed single column footing would run into each other.

    4. Mat or raft foundation, is a continuous reinforced concrete slab over a

    large area used to support many columns and walls. This kind of foundation

    is used where the soil strength is low or where column loads are large but

    where piles or caissons are not used.

    Types of loads on foundations:

  • 8/19/2019 Structure Design Criteria-final

    11/15

    10 

    Dead, live, wind, inclined thrusts and uplift, water table and earthquake

    forces.

    Types of settlements:

    Uniform and differential, Differential settlement must be minimized, depends

    on site soil conditions and distribution of loads on columns that supporting

    the building.

    Foundation design:

    In this project depend on the soli investigation with soil bearing capacity

    =400 KN/m2 the designer will be use wall footing and isolation footing .

    5.1.2 Ground water:

    Ground water table effect will be taken in consideration according to soil investigation

    and recommendations

    5.2 Superstructure:

    5.2.1 Slabs:

    Considering the architectural layouts and configurations, it is expected to use Ribbed

    Slab (two ways and one way) and Solid Slabs within project buildings, where the

    thickness of slabs according to length of spans supposed to be 37 cm.

    Mixed of drop and hidden beams will be used throughout slabs and again thickness

    varies according to spans. Drop beams expected to be between (60-150) cm.5.2.2 Columns: 

    Concrete columns are provided to suit Architectural layout and structural integrity, the

    columns dimensions, In general, from 25x60 cm to 30x150cm.

    5.2.3 Bearing walls:

    Concrete bearing walls will be provided at elevator shafts and wherever needed,

    distribution of bearing walls are fit with Architectural layout as needed.

    5.2.4 Lateral Force Resisting System (LFRS):

    In order to take benefits for the presence of concrete columns and shear walls and

    considering the irregularity in the building geometry, dual system from shear walls

    (bearing) and ordinary frame system will be used. Response modification factor expected

    to be 5.5 special care of steel reinforcement distribution and details shall be provided

    according to IBC in order to ensure ductile performance of the LFRS.

    5.2.2 Beams:

    In-situ beams provide support: they transfer loads from slabs to columns and

    walls. They offer strength, robustness and versatility, e.g. In accommodating

    cladding support details. In overall terms, wide flat beams are less costly to

    construct than narrow deep beams; the deeper and narrower, the more

    costly they are. Beams and columns of the same width give maximum

  • 8/19/2019 Structure Design Criteria-final

    12/15

    11 

    formwork efficiency as formwork can proceed along a continuous line.

    However, used internally, these relatively deep beams result in additional

    perimeter cladding and tend to disrupt service runs. Deep edge beams may

    limit the use of flying form systems on the slab. Up stand perimeter beams

    (designed as rectangular beams) can reduce overall cost. Parapet wall

    beams are less disruptive and less costly to form than deep down stand

    beams.

    The intersections of beams and columns require special consideration of

    reinforcement details. Sufficient width is required to get both beam and

    column steel through; end supports need to be long enough to allow bends

    in bottom reinforcement to start beyond half the support length yet maintain

    cover for links and/or lacers.

    Initial beam size and reinforcement

    In this project the designer will be use cubic concrete strength equal to Fcu

    40N/mm2 (f'c= 32N/mm2) and reinforcement steel with Fy=420 N/mm2, the

    next chart describes the economical beam schematic design (the

    reinforcement ratio =0.5ρmax) depends on Mu, d and the percentage of steel

    parameters, for example if the beam carry load=1200 KN.m and using

    width=500 mm then the economy beam depth=800 mm with steel

    reinforcement= 4820 mm2.

    Figure 9:: Economic beam depth, depends on Mu, beam width. 

  • 8/19/2019 Structure Design Criteria-final

    13/15

    12 

    Figure 10:: Economic beam reinforcement, depends on Mu, beam width. 

    5.2.3 Columns: 

    In-situ columns offer strength, economy, versatility, mouldability, fire

    resistance and robustness. They are often the most obvious and intrusive

    part of a structure and judgment is required to reconcile position, size,

    shape, spans of horizontal elements and economy. Generally the best

    economy comes from using regular square grids and constantly sized

    columns. Ideally, the same size of column should be used at all levels at all

    locations. If this is not possible, the alternative to keep the number of profiles

    to a minimum, for example, one for internal columns and one for perimeter

    columns. Certainly up to about eight stories, the same size and shape

    should be used throughout a column’s height. The outside of edge  columns

    should be flush with or inboard of the edges of slabs. Chases, service

    penetrations and horizontal offsets should be avoided. Offsets are the cause

    of costly transition beams which can be very disruptive to site progress.

    High-strength concrete columns can decrease the size of columns required.

    Smaller columns occupy less let table space and should be considered on

    individual projects. However, up to about five stories the size of perimeter

    columns is dominated by moment: concrete strengths greater than Fcu

    35N/mm2 appears to make little difference to the size of perimeter column

    required. Rectangular columns can be less obtrusive than square columns.

    Initial column size

    In this project the designer will be use concrete strength equal Fcu 40

    N/mm2 (f'c=32 N/mm2) and reinforcement steel with Fy=420 N/mm2, the next

    chart describes the columns schematic sizes depends on Pu andpercentage of steel parameters, for example if the column carry load =2500

  • 8/19/2019 Structure Design Criteria-final

    14/15

    13 

    KN and using reinforcement ratio=2% then the column area=105050 mm 2,

    so if we assume the column width =250 mm then the depth =450 mm.

    Figure 11:: Columns Schematic Sizes, depends on Pu, % of steel. 

    5.2.4 Bearing walls:

    Concrete bearing walls will be provided at elevator shafts and wherever needed,

    distribution of bearing walls are fit with Architectural layout as needed.

    5.2.5 Lateral Force Resisting System (LFRS):

    In order to take benefits for the presence of concrete columns and shear walls and

    considering the irregularity in the building geometry, dual system from shear walls

    (bearing) and ordinary frame system will be used. Response modification factor expected

    to be 5.5 special care of steel reinforcement distribution and details shall be provided

    according to IBC and SBC301 in order to ensure ductile performance of the LFRS.

    6- External works:

    Retaining walls, water tanks, water ways, water features, and other structural works will be

    designed as required by the landscape requirements and will be designed as watertight concrete

    elements in accordance BS 8007 " Design of concrete structures for retaining aqueous liquids " to

    reduce cracking and thus reducing corrosion of steel.

    7- Future vertical extension:

    No vertical extension will be taken into consideration in the design.

    8- Thermal Insulation:

    Thermal expansion of concrete roofs caused by solar radiation is a common cause of distress to

    buildings. Such stresses shall be minimized by applying thermal insulation on top of the roof toreduce the temperature differences. This material may include the application of foam or

    lightweight concrete to the top of the roof.

  • 8/19/2019 Structure Design Criteria-final

    15/15

    14 

    9- Software programs:

    The next table shows the structural software's which the designer of the project shall made the

    calculations by.

    Software Program Adoption contents Remark

    PROKON VW2.0.1

    Structural analysis and

    Design for different

    structural elements.

    Prokon Software Consultants Ltd. Mainly

    used for foundations and earth retaining

    structures.

    SAFE V12.3Slab analysis by the

    finite element method.

    Computers and structures Inc. (CSI).Used to

    model slabs and rafts.

    ETABS V9.7.4Structural analysis and

    design program.

    Computers and structures Inc. (CSI). Used

    for analysis and design of 3D models.

    Table2:: Structural Software's.