STRUCTURAL NOTES CULLY GREEN APARTMENTS - VLMK JOB #20170307 DIVISION 1 - GENERAL A. GENERAL 1. THESE NOTES SET MINIMUM STANDARDS FOR CONSTRUCTION. THE DRAWINGS GOVERN OVER THE GENERAL NOTES TO THE EXTENT SHOWN. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON DRAWINGS AND IN FIELD. COORDINATE LOCATIONS OF OPENINGS THROUGH FLOORS, ROOFS AND WALLS WITH ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. NOTIFY VLMK ENGINEERING + DESIGN (VLMK) OF ANY DISCREPANCIES OR IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN OR NOTED. 3. CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY SUPPORT PRIOR TO COMPLETION OF VERTICAL AND LATERAL LOAD SYSTEMS. VLMK HAS NOT BEEN RETAINED TO PROVIDE ANY SERVICES RELATED TO JOB SITE SAFETY PRECAUTIONS, OR TO REVIEW THE MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES FOR THE CONTRACTOR TO PERFORM WORK. UNLESS WE ARE SPECIFICALLY RETAINED AND COMPENSATED TO DO OTHERWISE, OUR WORK IS LIMITED TO THE DESIGN OF WORK DESCRIBED ON OUR DRAWINGS FOR THIS PROJECT. 4. WHERE REFERENCE IS MADE TO ASTM, AISC, ACI OR OTHER STANDARDS, THE LATEST ISSUE SHALL APPLY. 5. INSPECTION AND/OR JOB SUPERVISION IS NOT PROVIDED BY VLMK. 6. ALL WORK SHALL BE IN STRICT COMPLIANCE WITH THE 2012 INTERNATIONAL BUILDING CODE (IBC) AS AMENDED BY THE STATE OF OREGON (2014 OREGON STRUCTURAL SPECIALTY CODE) AND ALL OTHER STATE AND LOCAL BUILDING REQUIREMENTS THAT APPLY. 7. DESIGN CRITERIA: a. FLOOR LIVE LOADS (PER IBC 1603.1.1) RESIDENTIAL 40 PSF b. ROOF SNOW LOAD (PER IBC 1603.1.3) FLAT-ROOF SNOW LOAD (Pf) 25 PSF SNOW EXPOSURE FACTOR (Ce) 1.0 SNOW LOAD IMPORTANCE FACTOR (Is) 1.0 THERMAL FACTOR (Ct) 1.0 c. WIND LOAD (PER IBC 1603.1.4) ULTIMATE DESIGN WIND SPEED (Vult) 120 MPH NOMINAL DESIGN WIND SPEED (Vasd) 93 MPH RISK CATEGORY II WIND EXPOSURE B INTERNAL PRESSURE COEFFICIENT (GCpi) ±0.18 d. EARTHQUAKE DESIGN DATA (PER IBC 1603.1.5) SEISMIC IMPORTANCE FACTOR (Ie) 1.0 RISK CATEGORY II MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 0.972 S1 = 0.408 SITE CLASS D DESIGN SPECTRAL RESPONSE COEFFICIENTS Sds = 0.720 Sd1 = 0.433 SEISMIC DESIGN CATEGORY D BASIC SEISMIC-FORCE-RESISTING SYSTEM SPECIAL REINFORCED MASONRY DESIGN BASE SHEAR (V) BLDG 11.5 KIPS 3L-2-3S 10.7 KIPS 2-3L 8.8 KIPS 2N-2N 9.8 KIPS 2-CH 1.9 KIPS BIKE BARN SEISMIC RESPONSE COEFFICIENTS (Cs) 0.14 RESPONSE MODIFICATION FACTOR (R) 6.5 ANALYSIS PROCEDURE USED EQUIVALENT LATERAL FORCE 8. THESE DRAWINGS HAVE BEEN PREPARED SOLELY FOR USE IN THE CONSTRUCTION OF THE CULLY GREEN APARTMENTS PROJECT LOCATED IN PORTLAND, OREGON. POSSESSION OF THESE DRAWINGS DOES NOT GRANT A LICENSE TO CONSTRUCT OR FABRICATE THE WHOLE, OR PARTS OF THIS PROJECT IN OTHER LOCATIONS. 9. PROVIDE SHOP DRAWINGS FOR ALL STRUCTURAL PRODUCTS DELIVERED TO THE PROJECT. VLMK WILL REVIEW AND MARK-UP ELECTRONIC SUBMITTALS IN PDF FORMAT OR A MAXIMUM OF THREE HARD COPIES OF SUBMITTALS. THE CONTRACTOR WILL BE RESPONSIBLE FOR DUPLICATING MARK-UPS IF ADDITIONAL COPIES ARE REQUIRED. SUBMITTALS WILL BE REVIEWED AND RETURNED TO THE GENERAL CONTRACTOR WITHIN TWO WEEKS. ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ENGINEER. UNLESS OTHERWISE INDICATED, SHOP DRAWINGS SHALL BE PROVIDED ON THE FOLLOWING: a. PREFABRICATED STRUCTURAL MEMBERS AND COMPONENTS (E.G. WOOD TRUSSES, OPEN- WEB STEEL JOISTS AND GIRDERS, ETC.). DIVISION 2 - SITE WORK A. GENERAL 1. REMOVE ALL ORGANIC MATERIAL AND TOPSOIL FROM AREAS UNDER THE BUILDING OR UNDER PAVED AREAS. 2. FILL MATERIAL TO CONSIST OF A GRANULAR MATERIAL OR CONDITIONED SITE MATERIAL. PLACE FILL IN LIFTS NOT TO EXCEED 8 INCHES AND COMPACT TO 95% STANDARD ASTM D-1557 UNDER FOOTINGS, UNDER PAVED AREAS AND UNDER FLOOR SLABS. 3. BASE MATERIAL IMMEDIATELY UNDER SLAB TO BE 6 INCH LAYER OF COMPACTED CRUSHED ROCK WITH LESS THAN 5% PASSING THE #200 SIEVE. 4. DESIGN SOIL PRESSURE 1,500 PSF LL PLUS DL PER CODE MINIMUMS. 5. ALL FOOTINGS TO BEAR A MINIMUM 18 INCHES BELOW FINAL GRADE ON FIRM, UNDISTURBED SOIL OR APPROVED COMPACTED FILL. NOTIFY VLMK BEFORE PROCEEDING IF ANY UNUSUAL CONDITIONS ARE ENCOUNTERED IN THE FOOTING EXCAVATIONS. 6. DO NOT EXCAVATE CLOSER THAN 2:1 SLOPE BELOW FOOTING EXCAVATIONS. 7. CLEAN ALL FOOTING EXCAVATIONS OF LOOSE MATERIAL. DIVISION 4 - MASONRY (NOT USED) DIVISION 3 - CONCRETE AND REINFORCING A. CONCRETE MIX/MATERIAL 1. STRENGTH: AVERAGE 28 DAY CONCRETE STRENGTH DETERMINED BY JOB CAST LAB CURED CYLINDER TO BE AS INDICATED BELOW PLUS INCREASE DEPENDING ON THE PLANT'S STANDARD DEVIATION AS SPECIFIED IN ACI 318. PROVIDE MIX DESIGNS TO THE ENGINEER FOR ALL CONCRETE TO BE USED. CLEARLY LABEL ALL MIX DESIGNS FOR PROPOSED AREA OF USE. 2. MINIMUM MIX REQUIREMENTS: LOCATION MIN. COMP. SLUMP MIN. CEMENT ADMIXTURES STRENGTH (a) CONTENT FOOTINGS AND STEMWALLS 2,500 PSI 0"-5" 470 LB NONE INTERIOR SLAB ON GRADE 2,500 PSI 2"-4" 517 LB (b) EXTERIOR SLAB ON GRADE 2,500 PSI 2"-4" 517 LB (b), (c) MISCELLANEOUS 2,500 PSI 0"-5" 470 LB (b) (a) - SLUMP EXCEEDING SPECIFIED LIMITS SHALL NOT BE INCORPORATED IN THE PROJECT EXCEPT BY WRITTEN APPROVAL FROM ENGINEER. (b) - WRA = WATER REDUCING AGENT. (c) - AE = AIR ENTRAINMENT. 3. USE TYPE I CEMENT, PER ASTM C-150 UNLESS OTHERWISE APPROVED. 4. AGGREGATES PER ASTM C33. USE 3/4 INCH MINUS UNLESS OTHERWISE NOTED OR APPROVED. 5. WATER REDUCING AGENT (WRA) SHALL BE POLYHEED R-1 OR DURACEM 55 (MINIMUM 6 OZ. PER 100 POUNDS CEMENT). COMPLY WITH ASTM C-494. 6. AIR ENTRAINMENT (AE) SHALL COMPLY WITH ASTM C-260 AND SHALL BE USED ONLY WHERE SPECIFIED AND/OR APPROVED BY ENGINEER. 7. PLACE AND CURE ALL CONCRETE PER ACI CODES AND STANDARDS. 8. PROVIDE CONTROL JOINTS IN ALL INTERIOR SLABS ON GRADE AT 15'-0" ON CENTER EACH WAY MAXIMUM UNLESS OTHERWISE SHOWN ON PLANS. PROVIDE HEAVY (3/4 INCH) TOOLED JOINTS AT 5'-0" ON CENTER IN ALL EXTERIOR WALKS UNLESS OTHERWISE NOTED. 9. SLEEVES, PIPES OR CONDUITS OF ALUMINUM SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE UNLESS EFFECTIVELY COATED. B. REINFORCING 1. ALL REINFORCING TO BE ASTM A615 GRADE 60 UNLESS OTHERWISE NOTED. 2. FABRICATE AND INSTALL REINFORCING STEEL ACCORDING TO THE MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES - ACI STANDARD 315. 3. PROVIDE 2'-0" x 2'-0" CORNER BARS TO MATCH HORIZONTAL REINFORCING IN POURED-IN-PLACE WALLS AND FOOTINGS AT ALL CORNERS AND INTERSECTIONS. 4. SPLICES IN WALL REINFORCING SHALL BE LAPPED 40 BAR DIAMETERS (2'-0" MINIMUM) AND SHALL BE STAGGERED AT LEAST 4 FEET AT ALTERNATE BARS. 5. ALL OPENINGS SMALLER THAN 30 INCHES x 30 INCHES THAT DISRUPT REINFORCING SHALL HAVE AN AMOUNT OF REINFORCING EQUAL TO THE AMOUNT DISRUPTED PLACED BOTH SIDES OF OPENING. 6. PROVIDE (2) #4 CONTINUOUS BARS AT TOP AND AT DISCONTINUOUS ENDS OF ALL WALLS. 7. PROVIDE DOWELS FROM FOOTINGS TO MATCH ALL VERTICAL WALL, PILASTER AND COLUMN REINFORCING. (POURED-IN-PLACE COLUMNS AND WALLS). 8. LAP ALL BARS IN CONTINUOUS AND INTERSECTING FOOTINGS 2'-0" OR 40 BAR DIAMETERS, WHICHEVER IS GREATER. 9. ALL VERTICAL WALL REINFORCING TO BE PLACED IN CENTER OF WALL UNLESS SHOWN OTHERWISE ON DRAWINGS. 10. EXTEND REINFORCING TO WITHIN 1 INCH OF WALL AND SLAB EDGES. DIVISION 5 - METAL (NOT USED) DIVISION 6 - WOOD A. ROUGH CARPENTRY 1. LUMBER SPECIES AND GRADES TO BE AS FOLLOWS UNLESS OTHERWISE SHOWN ON DRAWINGS: JOISTS, BEAMS & STRINGERS: DOUGLAS FIR #2 6 INCH NOMINAL AND GREATER: DOUGLAS FIR #1 BUCKS, BLOCKING, BRIDGING AND MISCELLANEOUS: DOUGLAS FIR OR HEM FIR #3 2x4 STUDS: DOUGLAS FIR #2 2x6 STUDS: DOUGLAS FIR #2 SILLS, LEDGERS, STRIPPING, ETC. IN CONTACT PRESSURE TREATED HEM FIR #2 WITH CONCRETE, AND WOOD CURBS: PLATES AND HEADERS: KILN DRIED DOUGLAS FIR #2 POSTS, COLUMNS (SAWN): DOUGLAS FIR #1 2. ROOF, FLOOR AND WALL SHEATHING: APA RATED SHEATHING, EXPOSURE 1, CONFORMING TO APA PERFORMANCE STANDARD PS 1-95 AND EXCERPT NER-108. SEE DRAWINGS FOR REQUIRED THICKNESS OF SHEATHING AND/OR SPAN RATING. INSTALL ROOF AND FLOOR SHEATHING WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS UNLESS OTHERWISE NOTED. USE SPACERS TO PROVIDE 1/8 INCH END AND EDGE JOINTS (1/4 INCH FOR JUMBO PANELS) WHENEVER SHEATHING IS EXPOSED TO WET WEATHER. FILL ANY JOINT SPACING OVER 3/8 INCH UNLESS OTHERWISE WALL SHEATHING. BLOCK ROOF OR FLOOR SHEATHING WHERE NOTED ON DRAWINGS. 3. GLULAM BEAMS: Fb = 2400 PSI, E = 1,800,000 PSI PER ANSI A190.1 SPECIFICATION. SIMPLE SPANS COMBINATION: 24F-V4 CANTILEVER SPANS COMBINATION: 24F-V8 SUBMIT CERTIFICATE OF CONFORMANCE INDICATING MEMBERS MEET THE REQUIREMENTS OF ANSI A190.1. 4. PARALLAM (PSL): ALL PSL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE. BEAMS: Fb = 2900 PSI, E = 2,000,000 PSI, Fv = 290 PSI COLUMNS: Fb = 2400 PSI, E = 1,800,000 PSI, FcII = 2500 PSI 5. TIMBERSTRAND (LSL): ALL LSL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE. STUDS (2x4 AND 2x6): Fb = 1700 PSI, E = 1,300,000 PSI, Fcll = 1835 PSI, Fv = 425 PSI STUDS (2x8): Fb = 2250 PSI, E = 1,500,000 PSI, Fcll = 2150 PSI, Fv = 505 PSI COLUMNS/RIM/HEADERS < 9 1/2" DEEP: Fb = 1700 PSI, E = 1,300,000 PSI, Fcll = 1835 PSI, Fv = 310 PSI BEAMS/HEADERS 9 1/2" AND DEEPER: Fb = 2325 PSI, E = 1,550,000 PSI, Fv = 310 PSI 6. MICROLLAM (LVL): ALL LVL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE. BEAMS/HEADERS: Fb = 2600 PSI, E = 2,000,000 PSI, Fv = 285 PSI 7. PROVIDE FIRE BLOCKING AS REQUIRED AND BLOCKING FOR ALL SPECIFIED WALL-MOUNTED ITEMS INCLUDING CABINETS, DOORSTOPS, ETC. 8. CONNECTORS: a. TIE STRAPS, FRAMING ANCHORS, HANGERS, STIRRUPS, COLUMN CAPS, COLUMN BASES, ETC., TO BE SIMPSON AS DETAILED, OR AS APPROVED. b. FULLY FASTEN ACCORDING TO MANUFACTURER'S SCHEDULE USING LARGEST SIZE SHOWN. c. ALL BEAMS AND JOISTS NOT BEARING ON ANOTHER MEMBER TO CONNECT WITH 'U' TYPE HANGERS UNLESS OTHERWISE NOTED ON DRAWINGS. d. NAILING: ALL NAILS SPECIFIED IN THE DRAWINGS TO BE "COMMON" NAILS UNLESS OTHERWISE NOTED. ALL NAILING SHALL COMPLY WITH IBC TABLE 2304.9.1, NAILING SCHEDULE. OBTAIN ENGINEERS APPROVAL OF ALL PROPRIETARY NAILING SYSTEMS. e. NAILS AT ROOF AND WALL DIAPHRAGMS TO BE DRIVEN SO THAT THEIR HEAD OR CROWN IS FLUSH WITH THE SURFACE OF THE SHEATHING. CHECK AND RESINK IF NEEDED, IMMEDIATELY BEFORE ROOFING. f. BOLTS - SEE DIVISION 5, METAL. g. CORROSION PROTECTION: 1. CONFIRM REQUIRED CORROSION PROTECTION FOR HARDWARE AND FASTENERS WITH SPECIFIC RECOMMENDATIONS FROM PRESSURE TREATING MANUFACTURER OR HANGER MANUFACTURER (USE MOST CONSERVATIVE) FOR SPECIFIC WOOD TREATMENTS USED. 2. MINIMUM CORROSION PROTECTION ON METAL CONNECTORS EXPOSED TO THE ENVIRONMENT OR PRESSURE TREATED LUMBER TO BE PER ASTM A653 CLASS 185 (SIMPSON ZMAX) OR ASTM A123. 3. FASTENERS FOR PRESSURE TREATED LUMBER MUST BE MINIMUM HOT-DIP GALVANIZED, STAINLESS STEEL, SILICON BRONZE OR COPPER. 4. HOT-DIP GALVANIZED HARDWARE AND FASTENERS MUST COMPLY WITH ASTM A153, STAINLESS STEEL FASTENERS TO BE TYPE 304 OR TYPE 316. 5. HARDWARE AND FASTENERS USED TOGETHER MUST BE THE SAME TYPE (E.G. HOT-DIP GALVANIZED NAILS WITH HOT-DIP GALVANIZED HANGERS). 9. DELIVERY AND STORAGE: ALL LUMBER AND SHEATHING DELIVERED TO THE SITE, SHALL BE STACKED OR STORED OFF THE GROUND AND PROPERLY PROTECTED AGAINST WEATHER. 10. CUTTING AND NOTCHING OF JOISTS NOT ALLOWED. A 1 INCH DIAMETER HOLE MAY BE DRILLED IN THE CENTER 1/3 OF THE MEMBER DEPTH. ALL OTHER HOLES TO BE APPROVED BY ENGINEER. 11. STUDS MAY BE NOTCHED IN THE LOWER 1/5 OF THE HEIGHT OF THE STUD FOR ELECTRIC AND PLUMBING PIPES, BUT NO PART OF THE NOTCH IS TO BE DEEPER THAN 25 PERCENT OF THE WIDTH OF THE STUD. HOLES OF DIAMETERS UP TO 1/3 OF WIDTH OF STUD MAY BE DRILLED IN THE STUD. B. WOOD CHORD PLYWOOD WEB JOISTS (TJI'S) 1. ALL TJI'S SHALL BE MANUFACTURED BY A JOIST MANUFACTURER WITH A WITH AN ICC APPROVAL. 2. ALL BRIDGING, BEARING HARDWARE, BLOCKING, HANGARS, ETC., THAT CONNECT TO THE JOISTS SHALL BE PER REDBUILT STANDARD DETAILS. 3. JOIST ERECTOR TO INSTALL JOISTS IN ACCORDANCE WITH THE TRUSS SUPPLIER DRAWINGS AND INSTALLATION GUIDELINES. 4. RESIDENTIAL (STOCK) JOISTS: PROVIDE SHOP DRAWINGS. 5. JOIST MANUFACTURER TO INSPECT ALL JOISTS AFTER THEY HAVE BEEN ERECTED AND FLOOR AND/OR ROOF SHEATHING, BRIDGING, BLOCKING, ETC., HAS BEEN INSTALLED. MANUFACTURER TO SUBMIT CERTIFICATE TO VLMK THAT THE INSPECTION WAS MADE AND THAT THE JOISTS ARE IN ACCEPTABLE CONDITION AND MEET THE MANUFACTURER'S DESIGN AND INSTALLATION REQUIREMENTS. C. LIGHT METAL PLATE-CONNECTED WOOD ROOF TRUSSES 1. ALL LIGHT METAL PLATE-CONNECTED WOOD ROOF TRUSSES SHALL BE DESIGNED BY AN ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED. 2. ALL BRIDGING, BEARING HARDWARE, BLOCKING, HANGERS, ETC., THAT ARE REQUIRED TO MEET TRUSS DESIGN CRITERIA SHALL BE INCLUDED IN THE TRUSS SHOP DRAWINGS AND SHALL BE PROVIDED BY TRUSS MANUFACTURER. 3. TRUSS ERECTOR TO INSTALL TRUSSES IN ACCORDANCE WITH TRUSS SUPPLIER DRAWINGS AND INSTALLATION GUIDELINES. 4. SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED AND STAMPED BY AN ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED. ENGINEER TO REVIEW AND CERTIFY THAT TRUSS DESIGN COMPLIES WITH BUILDING DESIGN DRAWINGS AND SPECIFICATIONS. 5. TRUSS MANUFACTURER TO INSPECT ALL TRUSSES AFTER THEY HAVE BEEN ERECTED AND ROOF SHEATHING, BRIDGING, BLOCKING, ETC., HAS BEEN INSTALLED. MANUFACTURER TO SUBMIT CERTIFICATE TO VLMK THAT THE INSPECTION WAS MADE AND THAT TRUSSES ARE IN ACCEPTABLE CONDITION AND MEET THE MANUFACTURER'S DESIGN AND INSTALLATION REQUIREMENTS. CHECKED PROJ. NO. DATE DRAWN REVISIONS PROJECT NAME SCALE # DATE DESCRIPTION AS NOTED C:\Users\Stephens\Documents\00REVIT\Cully Green Apartments_REV1_stephens07.rvt 5/25/2018 3:42:16 PM CULLY GREEN APARTMENTS S0.0 PERMIT SET STRUCTURAL NOTES AND SPECIAL INSPECTIONS 20170307 JJE SMS DECEMBER 05, 2017 4736, 4752 NE GOING ST AND 4540 NE 47TH AVE PORTLAND, OR 97218 05/25/18 19

STRUCTURAL NOTES DIVISION 3 - CONCRETE AND … · 2018. 8. 9. · structural notes cully green apartments - vlmk job #20170307 division 1 - general a. general 1. these notes set minimum

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • STRUCTURAL NOTES

    CULLY GREEN APARTMENTS - VLMK JOB #20170307

    DIVISION 1 - GENERAL A. GENERAL

    1. THESE NOTES SET MINIMUM STANDARDS FOR CONSTRUCTION. THE DRAWINGS GOVERN OVER THE GENERAL NOTES TO THE EXTENT SHOWN.

    2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON DRAWINGS AND IN FIELD. COORDINATE LOCATIONS OF OPENINGS THROUGH FLOORS, ROOFS AND WALLS WITH ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. NOTIFY VLMK ENGINEERING + DESIGN (VLMK) OF ANY DISCREPANCIES OR IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN OR NOTED.

    3. CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY SUPPORT PRIOR TO COMPLETION OF VERTICAL AND LATERAL LOAD SYSTEMS. VLMK HAS NOT BEEN RETAINED TO PROVIDE ANY SERVICES RELATED TO JOB SITE SAFETY PRECAUTIONS, OR TO REVIEW THE MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES FOR THE CONTRACTOR TO PERFORM WORK. UNLESS WE ARE SPECIFICALLY RETAINED AND COMPENSATED TO DO OTHERWISE, OUR WORK IS LIMITED TO THE DESIGN OF WORK DESCRIBED ON OUR DRAWINGS FOR THIS PROJECT.

    4. WHERE REFERENCE IS MADE TO ASTM, AISC, ACI OR OTHER STANDARDS, THE LATEST ISSUE SHALL APPLY.

    5. INSPECTION AND/OR JOB SUPERVISION IS NOT PROVIDED BY VLMK.

    6. ALL WORK SHALL BE IN STRICT COMPLIANCE WITH THE 2012 INTERNATIONAL BUILDING CODE (IBC) AS AMENDED BY THE STATE OF OREGON (2014 OREGON STRUCTURAL SPECIALTY CODE) AND ALL OTHER STATE AND LOCAL BUILDING REQUIREMENTS THAT APPLY.

    7. DESIGN CRITERIA:a. FLOOR LIVE LOADS (PER IBC 1603.1.1)

    RESIDENTIAL 40 PSF b. ROOF SNOW LOAD (PER IBC 1603.1.3)

    FLAT-ROOF SNOW LOAD (Pf) 25 PSFSNOW EXPOSURE FACTOR (Ce) 1.0SNOW LOAD IMPORTANCE FACTOR (Is) 1.0THERMAL FACTOR (Ct) 1.0

    c. WIND LOAD (PER IBC 1603.1.4)ULTIMATE DESIGN WIND SPEED (Vult) 120 MPHNOMINAL DESIGN WIND SPEED (Vasd) 93 MPHRISK CATEGORY IIWIND EXPOSURE BINTERNAL PRESSURE COEFFICIENT (GCpi) ±0.18

    d. EARTHQUAKE DESIGN DATA (PER IBC 1603.1.5)SEISMIC IMPORTANCE FACTOR (Ie) 1.0RISK CATEGORY IIMAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 0.972 S1 = 0.408SITE CLASS DDESIGN SPECTRAL RESPONSE COEFFICIENTS Sds = 0.720 Sd1 = 0.433SEISMIC DESIGN CATEGORY DBASIC SEISMIC-FORCE-RESISTING SYSTEM SPECIAL REINFORCED MASONRYDESIGN BASE SHEAR (V) BLDG

    11.5 KIPS 3L-2-3S 10.7 KIPS 2-3L8.8 KIPS 2N-2N9.8 KIPS 2-CH1.9 KIPS BIKE BARN

    SEISMIC RESPONSE COEFFICIENTS (Cs) 0.14RESPONSE MODIFICATION FACTOR (R) 6.5ANALYSIS PROCEDURE USED EQUIVALENT LATERAL FORCE

    8. THESE DRAWINGS HAVE BEEN PREPARED SOLELY FOR USE IN THE CONSTRUCTION OF THE CULLY GREEN APARTMENTS PROJECT LOCATED IN PORTLAND, OREGON. POSSESSION OF THESE DRAWINGS DOES NOT GRANT A LICENSE TO CONSTRUCT OR FABRICATE THE WHOLE, OR PARTS OF THIS PROJECT IN OTHER LOCATIONS.

    9. PROVIDE SHOP DRAWINGS FOR ALL STRUCTURAL PRODUCTS DELIVERED TO THE PROJECT. VLMK WILL REVIEW AND MARK-UP ELECTRONIC SUBMITTALS IN PDF FORMAT OR A MAXIMUM OF THREE HARD COPIES OF SUBMITTALS. THE CONTRACTOR WILL BE RESPONSIBLE FOR DUPLICATING MARK-UPS IF ADDITIONAL COPIES ARE REQUIRED. SUBMITTALS WILL BE REVIEWED AND RETURNED TO THE GENERAL CONTRACTOR WITHIN TWO WEEKS. ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ENGINEER. UNLESS OTHERWISE INDICATED, SHOP DRAWINGS SHALL BE PROVIDED ON THE FOLLOWING:a. PREFABRICATED STRUCTURAL MEMBERS AND COMPONENTS (E.G. WOOD TRUSSES, OPEN-

    WEB STEEL JOISTS AND GIRDERS, ETC.).

    DIVISION 2 - SITE WORK

    A. GENERAL1. REMOVE ALL ORGANIC MATERIAL AND TOPSOIL FROM AREAS UNDER THE BUILDING OR UNDER

    PAVED AREAS.

    2. FILL MATERIAL TO CONSIST OF A GRANULAR MATERIAL OR CONDITIONED SITE MATERIAL. PLACE FILL IN LIFTS NOT TO EXCEED 8 INCHES AND COMPACT TO 95% STANDARD ASTM D-1557 UNDER FOOTINGS, UNDER PAVED AREAS AND UNDER FLOOR SLABS.

    3. BASE MATERIAL IMMEDIATELY UNDER SLAB TO BE 6 INCH LAYER OF COMPACTED CRUSHED ROCK WITH LESS THAN 5% PASSING THE #200 SIEVE.

    4. DESIGN SOIL PRESSURE 1,500 PSF LL PLUS DL PER CODE MINIMUMS.

    5. ALL FOOTINGS TO BEAR A MINIMUM 18 INCHES BELOW FINAL GRADE ON FIRM, UNDISTURBED SOIL OR APPROVED COMPACTED FILL. NOTIFY VLMK BEFORE PROCEEDING IF ANY UNUSUAL CONDITIONS ARE ENCOUNTERED IN THE FOOTING EXCAVATIONS.

    6. DO NOT EXCAVATE CLOSER THAN 2:1 SLOPE BELOW FOOTING EXCAVATIONS.

    7. CLEAN ALL FOOTING EXCAVATIONS OF LOOSE MATERIAL.

    DIVISION 4 - MASONRY (NOT USED)

    DIVISION 3 - CONCRETE AND REINFORCING

    A. CONCRETE MIX/MATERIAL1. STRENGTH: AVERAGE 28 DAY CONCRETE STRENGTH DETERMINED BY JOB CAST LAB CURED

    CYLINDER TO BE AS INDICATED BELOW PLUS INCREASE DEPENDING ON THE PLANT'S STANDARD DEVIATION AS SPECIFIED IN ACI 318. PROVIDE MIX DESIGNS TO THE ENGINEER FOR ALL CONCRETE TO BE USED. CLEARLY LABEL ALL MIX DESIGNS FOR PROPOSED AREA OF USE.

    2. MINIMUM MIX REQUIREMENTS:LOCATION MIN. COMP. SLUMP MIN. CEMENT ADMIXTURES

    STRENGTH (a) CONTENTFOOTINGS AND STEMWALLS 2,500 PSI 0"-5" 470 LB NONEINTERIOR SLAB ON GRADE 2,500 PSI 2"-4" 517 LB (b)EXTERIOR SLAB ON GRADE 2,500 PSI 2"-4" 517 LB (b), (c)MISCELLANEOUS 2,500 PSI 0"-5" 470 LB (b)(a) - SLUMP EXCEEDING SPECIFIED LIMITS SHALL NOT BE INCORPORATED IN THE PROJECT

    EXCEPT BY WRITTEN APPROVAL FROM ENGINEER. (b) - WRA = WATER REDUCING AGENT.(c) - AE = AIR ENTRAINMENT.

    3. USE TYPE I CEMENT, PER ASTM C-150 UNLESS OTHERWISE APPROVED.

    4. AGGREGATES PER ASTM C33. USE 3/4 INCH MINUS UNLESS OTHERWISE NOTED OR APPROVED.

    5. WATER REDUCING AGENT (WRA) SHALL BE POLYHEED R-1 OR DURACEM 55 (MINIMUM 6 OZ. PER 100 POUNDS CEMENT). COMPLY WITH ASTM C-494.

    6. AIR ENTRAINMENT (AE) SHALL COMPLY WITH ASTM C-260 AND SHALL BE USED ONLY WHERE SPECIFIED AND/OR APPROVED BY ENGINEER.

    7. PLACE AND CURE ALL CONCRETE PER ACI CODES AND STANDARDS.

    8. PROVIDE CONTROL JOINTS IN ALL INTERIOR SLABS ON GRADE AT 15'-0" ON CENTER EACH WAY MAXIMUM UNLESS OTHERWISE SHOWN ON PLANS. PROVIDE HEAVY (3/4 INCH) TOOLED JOINTS AT 5'-0" ON CENTER IN ALL EXTERIOR WALKS UNLESS OTHERWISE NOTED.

    9. SLEEVES, PIPES OR CONDUITS OF ALUMINUM SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE UNLESS EFFECTIVELY COATED.

    B. REINFORCING1. ALL REINFORCING TO BE ASTM A615 GRADE 60 UNLESS OTHERWISE NOTED.

    2. FABRICATE AND INSTALL REINFORCING STEEL ACCORDING TO THE MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES - ACI STANDARD 315.

    3. PROVIDE 2'-0" x 2'-0" CORNER BARS TO MATCH HORIZONTAL REINFORCING IN POURED-IN-PLACE WALLS AND FOOTINGS AT ALL CORNERS AND INTERSECTIONS.

    4. SPLICES IN WALL REINFORCING SHALL BE LAPPED 40 BAR DIAMETERS (2'-0" MINIMUM) AND SHALL BE STAGGERED AT LEAST 4 FEET AT ALTERNATE BARS.

    5. ALL OPENINGS SMALLER THAN 30 INCHES x 30 INCHES THAT DISRUPT REINFORCING SHALL HAVE AN AMOUNT OF REINFORCING EQUAL TO THE AMOUNT DISRUPTED PLACED BOTH SIDES OF OPENING.

    6. PROVIDE (2) #4 CONTINUOUS BARS AT TOP AND AT DISCONTINUOUS ENDS OF ALL WALLS.

    7. PROVIDE DOWELS FROM FOOTINGS TO MATCH ALL VERTICAL WALL, PILASTER AND COLUMN REINFORCING. (POURED-IN-PLACE COLUMNS AND WALLS).

    8. LAP ALL BARS IN CONTINUOUS AND INTERSECTING FOOTINGS 2'-0" OR 40 BAR DIAMETERS, WHICHEVER IS GREATER.

    9. ALL VERTICAL WALL REINFORCING TO BE PLACED IN CENTER OF WALL UNLESS SHOWN OTHERWISE ON DRAWINGS.

    10. EXTEND REINFORCING TO WITHIN 1 INCH OF WALL AND SLAB EDGES.

    DIVISION 5 - METAL (NOT USED)

    DIVISION 6 - WOOD

    A. ROUGH CARPENTRY1. LUMBER SPECIES AND GRADES TO BE AS FOLLOWS UNLESS OTHERWISE SHOWN ON DRAWINGS:

    JOISTS, BEAMS & STRINGERS: DOUGLAS FIR #26 INCH NOMINAL AND GREATER: DOUGLAS FIR #1BUCKS, BLOCKING, BRIDGING AND MISCELLANEOUS: DOUGLAS FIR OR HEM FIR #32x4 STUDS: DOUGLAS FIR #22x6 STUDS: DOUGLAS FIR #2SILLS, LEDGERS, STRIPPING, ETC. IN CONTACT PRESSURE TREATED HEM FIR #2WITH CONCRETE, AND WOOD CURBS:PLATES AND HEADERS: KILN DRIED DOUGLAS FIR #2POSTS, COLUMNS (SAWN): DOUGLAS FIR #1

    2. ROOF, FLOOR AND WALL SHEATHING:APA RATED SHEATHING, EXPOSURE 1, CONFORMING TO APA PERFORMANCE STANDARD PS 1-95 AND EXCERPT NER-108. SEE DRAWINGS FOR REQUIRED THICKNESS OF SHEATHING AND/OR SPAN RATING. INSTALL ROOF AND FLOOR SHEATHING WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS UNLESS OTHERWISE NOTED. USE SPACERS TO PROVIDE 1/8 INCH END AND EDGE JOINTS (1/4 INCH FOR JUMBO PANELS) WHENEVER SHEATHING IS EXPOSED TO WET WEATHER. FILL ANY JOINT SPACING OVER 3/8 INCH UNLESS OTHERWISE WALL SHEATHING. BLOCK ROOF OR FLOOR SHEATHING WHERE NOTED ON DRAWINGS.

    3. GLULAM BEAMS:• Fb = 2400 PSI, E = 1,800,000 PSI PER ANSI A190.1 SPECIFICATION.• SIMPLE SPANS COMBINATION: 24F-V4• CANTILEVER SPANS COMBINATION: 24F-V8• SUBMIT CERTIFICATE OF CONFORMANCE INDICATING MEMBERS MEET THE

    REQUIREMENTS OF ANSI A190.1.

    4. PARALLAM (PSL):• ALL PSL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE.• BEAMS: Fb = 2900 PSI, E = 2,000,000 PSI, Fv = 290 PSI• COLUMNS: Fb = 2400 PSI, E = 1,800,000 PSI, FcII = 2500 PSI

    5. TIMBERSTRAND (LSL):• ALL LSL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE.• STUDS (2x4 AND 2x6): Fb = 1700 PSI, E = 1,300,000 PSI, Fcll = 1835 PSI, Fv = 425 PSI• STUDS (2x8): Fb = 2250 PSI, E = 1,500,000 PSI, Fcll = 2150 PSI, Fv = 505 PSI• COLUMNS/RIM/HEADERS < 9 1/2" DEEP:

    Fb = 1700 PSI, E = 1,300,000 PSI, Fcll = 1835 PSI, Fv = 310 PSI• BEAMS/HEADERS 9 1/2" AND DEEPER:

    Fb = 2325 PSI, E = 1,550,000 PSI, Fv = 310 PSI6. MICROLLAM (LVL):

    • ALL LVL SHALL BE MANUFACTURED BY TRUSJOIST OR APPROVED ALTERNATE.• BEAMS/HEADERS: Fb = 2600 PSI, E = 2,000,000 PSI, Fv = 285 PSI

    7. PROVIDE FIRE BLOCKING AS REQUIRED AND BLOCKING FOR ALL SPECIFIED WALL-MOUNTED ITEMS INCLUDING CABINETS, DOORSTOPS, ETC.

    8. CONNECTORS:a. TIE STRAPS, FRAMING ANCHORS, HANGERS, STIRRUPS, COLUMN CAPS, COLUMN BASES, ETC.,

    TO BE SIMPSON AS DETAILED, OR AS APPROVED. b. FULLY FASTEN ACCORDING TO MANUFACTURER'S SCHEDULE USING LARGEST SIZE SHOWN. c. ALL BEAMS AND JOISTS NOT BEARING ON ANOTHER MEMBER TO CONNECT WITH 'U' TYPE

    HANGERS UNLESS OTHERWISE NOTED ON DRAWINGS.d. NAILING: ALL NAILS SPECIFIED IN THE DRAWINGS TO BE "COMMON" NAILS UNLESS OTHERWISE

    NOTED. ALL NAILING SHALL COMPLY WITH IBC TABLE 2304.9.1, NAILING SCHEDULE. OBTAIN ENGINEERS APPROVAL OF ALL PROPRIETARY NAILING SYSTEMS.

    e. NAILS AT ROOF AND WALL DIAPHRAGMS TO BE DRIVEN SO THAT THEIR HEAD OR CROWN IS FLUSH WITH THE SURFACE OF THE SHEATHING. CHECK AND RESINK IF NEEDED, IMMEDIATELY BEFORE ROOFING.

    f. BOLTS - SEE DIVISION 5, METAL.g. CORROSION PROTECTION:

    1. CONFIRM REQUIRED CORROSION PROTECTION FOR HARDWARE AND FASTENERS WITH SPECIFIC RECOMMENDATIONS FROM PRESSURE TREATING MANUFACTURER OR HANGER MANUFACTURER (USE MOST CONSERVATIVE) FOR SPECIFIC WOOD TREATMENTS USED.

    2. MINIMUM CORROSION PROTECTION ON METAL CONNECTORS EXPOSED TO THE ENVIRONMENT OR PRESSURE TREATED LUMBER TO BE PER ASTM A653 CLASS 185 (SIMPSON ZMAX) OR ASTM A123.

    3. FASTENERS FOR PRESSURE TREATED LUMBER MUST BE MINIMUM HOT-DIP GALVANIZED, STAINLESS STEEL, SILICON BRONZE OR COPPER.

    4. HOT-DIP GALVANIZED HARDWARE AND FASTENERS MUST COMPLY WITH ASTM A153, STAINLESS STEEL FASTENERS TO BE TYPE 304 OR TYPE 316.

    5. HARDWARE AND FASTENERS USED TOGETHER MUST BE THE SAME TYPE (E.G. HOT-DIP GALVANIZED NAILS WITH HOT-DIP GALVANIZED HANGERS).

    9. DELIVERY AND STORAGE: ALL LUMBER AND SHEATHING DELIVERED TO THE SITE, SHALL BE STACKED OR STORED OFF THE GROUND AND PROPERLY PROTECTED AGAINST WEATHER.

    10. CUTTING AND NOTCHING OF JOISTS NOT ALLOWED. A 1 INCH DIAMETER HOLE MAY BE DRILLED IN THE CENTER 1/3 OF THE MEMBER DEPTH. ALL OTHER HOLES TO BE APPROVED BY ENGINEER.

    11. STUDS MAY BE NOTCHED IN THE LOWER 1/5 OF THE HEIGHT OF THE STUD FOR ELECTRIC AND PLUMBING PIPES, BUT NO PART OF THE NOTCH IS TO BE DEEPER THAN 25 PERCENT OF THE WIDTH OF THE STUD. HOLES OF DIAMETERS UP TO 1/3 OF WIDTH OF STUD MAY BE DRILLED IN THE STUD.

    B. WOOD CHORD PLYWOOD WEB JOISTS (TJI'S)1. ALL TJI'S SHALL BE MANUFACTURED BY A JOIST MANUFACTURER WITH A WITH AN ICC APPROVAL.

    2. ALL BRIDGING, BEARING HARDWARE, BLOCKING, HANGARS, ETC., THAT CONNECT TO THE JOISTS SHALL BE PER REDBUILT STANDARD DETAILS.

    3. JOIST ERECTOR TO INSTALL JOISTS IN ACCORDANCE WITH THE TRUSS SUPPLIER DRAWINGS AND INSTALLATION GUIDELINES.

    4. RESIDENTIAL (STOCK) JOISTS: PROVIDE SHOP DRAWINGS.

    5. JOIST MANUFACTURER TO INSPECT ALL JOISTS AFTER THEY HAVE BEEN ERECTED AND FLOOR AND/OR ROOF SHEATHING, BRIDGING, BLOCKING, ETC., HAS BEEN INSTALLED. MANUFACTURER TO SUBMIT CERTIFICATE TO VLMK THAT THE INSPECTION WAS MADE AND THAT THE JOISTS ARE IN ACCEPTABLE CONDITION AND MEET THE MANUFACTURER'S DESIGN AND INSTALLATION REQUIREMENTS.

    C. LIGHT METAL PLATE-CONNECTED WOOD ROOF TRUSSES1. ALL LIGHT METAL PLATE-CONNECTED WOOD ROOF TRUSSES SHALL BE DESIGNED BY AN

    ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED.

    2. ALL BRIDGING, BEARING HARDWARE, BLOCKING, HANGERS, ETC., THAT ARE REQUIRED TO MEET TRUSS DESIGN CRITERIA SHALL BE INCLUDED IN THE TRUSS SHOP DRAWINGS AND SHALL BE PROVIDED BY TRUSS MANUFACTURER.

    3. TRUSS ERECTOR TO INSTALL TRUSSES IN ACCORDANCE WITH TRUSS SUPPLIER DRAWINGS AND INSTALLATION GUIDELINES.

    4. SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED AND STAMPED BY AN ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED. ENGINEER TO REVIEW AND CERTIFY THAT TRUSS DESIGN COMPLIES WITH BUILDING DESIGN DRAWINGS AND SPECIFICATIONS.

    5. TRUSS MANUFACTURER TO INSPECT ALL TRUSSES AFTER THEY HAVE BEEN ERECTED AND ROOF SHEATHING, BRIDGING, BLOCKING, ETC., HAS BEEN INSTALLED. MANUFACTURER TO SUBMIT CERTIFICATE TO VLMK THAT THE INSPECTION WAS MADE AND THAT TRUSSES ARE IN ACCEPTABLE CONDITION AND MEET THE MANUFACTURER'S DESIGN AND INSTALLATION REQUIREMENTS.

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:1

    6 P

    M

    CULLY GREENAPARTMENTS

    S0.0PERMIT SET

    STRUCTURALNOTES AND

    SPECIALINSPECTIONS

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    05/25/18

    19

  • GRADE

    NOTE:SEE PLAN AND FOUNDATION SCHEDULE FOR FOOTING INFORMATION, TYPICAL

    UNDER-SLAB INSULATION

    SUBGRADE INSULATION SCHEDULE (SEE ARCHITECTURAL DRAWINGS FOR THICKNESS / R-VALUE REQ'D)

    UNDER SLAB

    LOCATION

    EPS TYPE I / EPS15

    INSULATION TYPE

    3.6 PSI (518 PSF)

    MIN. COMPRESSIVE STRENGTH AT 1% DEFORMATION

    SLAB AND FOOTING PER PLAN

    WOOD STUD SHEARWALL SCHEDULE NOTES

    WOOD STUD SHEARWALL SCHEDULE - 8d NAILS

    A364 PLF

    (260 PLF)

    TYPICALEXTERIOR

    WALLSU.O.N.

    15/32" APA RATED, EXPOSURE 1 SHEATHING, ONE SIDE, ALL EDGES BLOCKED, WITH 8d COMMON WIRE NAILS AT 6" O.C. ALL PANEL EDGES AND 12" O.C. IN-FIELD

    UPPER WALL:

    FOUNDATION:

    2x SOLE PLATE WITH 16d NAILS AT 6" O.C. STAGGERED2x P.T. SILL PLATE WITH 5/8" DIA. ANCHOR BOLTS AT 48" O.C.

    1. INSTALL SHEATHING HORIZONTAL OR VERTICAL. NO PIECE SMALLER THAN 2'-0" x 2'-0".

    2. ALL INTERIOR WALLS WITHOUT A SCHEDULE SHEAR ASSEMBLY TO BE SHEATHED PER ARCHITECTURAL DRAWINGS.

    3. APPLY GYPSUM BOARD OVER SHEATHING AS REQUIRED BY ARCHITECTURAL DRAWINGS.

    4. AT POSTS EMBEDDED IN SHEAR WALLS, ATTACH SHEATHING PER THE EDGE NAILING REQUIREMENTS FOR THAT SHEAR WALL.

    5. ALL SHEAR WALL NAILS TO BE COMMON WIRE (8d DIA = 0.113") OR GALVANIZED BOX NAILS (8d DIA = 0.113"). MINIMUM PENETRATION TO BE 1 3/8" FOR 10d NAILS. STAPLES ARE NOT AN ACCEPTABLE SUBSTITUTION.

    6. ANCHOR BOLTS TO BE STANDARD CAST-IN-PLACE J-BOLTS WITH 7" MINIMUM EMBED AND 3" MINIMUM EDGE DISTANCE. PROVIDE A MINIMUM OF (2) ANCHOR BOLTS PER WALL SECTION.

    7. PROVIDE PLATE WASHERS - MINIMUM OF 1/4" x 3" x 3" IN SIZE, AT ALL SILL PLATE ANCHOR BOLTS.

    B686 PLF

    (380 PLF)

    15/32" APA RATED, EXPOSURE 1 SHEATHING, ONE SIDE, ALL EDGES BLOCKED, WITH 8d COMMON WIRE NAILS AT 3" O.C. ALL PANEL EDGES AND 12" O.C. IN-FIELD

    UPPER WALL:

    FOUNDATION:

    3x SOLE PLATE WITH SIMPSON SDS 1/4" x 6" AT 12" O.C.2x P.T. SILL PLATE WITH 5/8" DIA. ANCHOR BOLTS AT 32" O.C.

    WIND(SEISMIC)

    NOTES

    1

    C896 PLF

    (640 PLF)

    15/32" APA RATED, EXPOSURE 1 SHEATHING, ONE SIDE, ALL EDGES BLOCKED, WITH 8d COMMON WIRE NAILS AT 2" O.C. ALL PANEL EDGES AND 12" O.C. IN-FIELD

    UPPER WALL:

    FOUNDATION:

    3x SOLE PLATE WITH SIMPSON SDS 1/4" x 6" AT 6" O.C.2x P.T. SILL PLATE WITH 5/8" DIA. ANCHOR BOLTS AT 24" O.C.

    HOLDOWN NOTES:

    SIMPSON SPECIFIED FASTENERS

    WOOD POST PER PLAN

    SIMPSON HOLDOWN PER SCHEDULE

    P.T. SILL PLATE PER SHEARWALL SCHEDULE

    CONCRETE STEMWALL OR FOOTING PER PLAN

    ANCHOR BOLT PER SCHEDULE

    POST THICKNESS PER SCHEDULE

    1. HOLDOWNS, SSTB BOLTS AND EPOXY BOLTS MANUFACTURED BY SIMPSON STRONG TIE, INC. INSTALL PER SIMPSON RECOMMENDATIONS.

    2. USE SIMPSON 'SSTB' OR A36 ANCHORS AT STEMWALLS. USE SIMPSON 'SET-XP' A307 THREADED ROD EPOXY ANCHORS AT FOOTINGS OR THICKENED SLABS. EXPANSION ANCHORS SHALL NOT BE USED AT HOLDOWNS.

    3. SHEARWALL SHEATHING TO BE ATTACHED TO VERTICAL MEMBER WITH EDGE NAILING REQUIREMENTS PER SHEARWALL SCHEDULE.

    4. MULTIPLE STUDS TO BE ATTACHED TOGETHER WITH 16d NAILS AT 8" O.C. STAGGERED. ANY POST WITH THICKNESS 5 1/2" AND GREATER TO BE A SOLID MEMBER.

    SIMPSON 'SSTB' BOLTHOLDOWNSIMPSON EPOXY BOLT (NOT AT STEMWALL)

    MINIMUM POST THICKNESS

    SIMPSON HOLDOWN SCHEDULE

    3"SIMPSON 'HDU2-SDS2.5' 5/8" DIA x 6" EMBEDSIMPSON 'SSTB16'

    1,2

    3,4

    3"SIMPSON 'HDU4-SDS2.5' 5/8" DIA x 8" EMBEDSIMPSON 'SSTB24'

    3 1/2"SIMPSON 'HDU8-SDS2.5' 7/8" DIA x 13" EMBEDSIMPSON 'SSTB28'

    3"SIMPSON 'SSTB24'SIMPSON 'HDU5-SDS2.5' 5/8" DIA x 9" EMBED

    WEB STIFFENER EACH SIDE: TJI 210 JOISTS: 7/8" x 3" MIN

    (3) 8d x 2" CLINCHED NAILS

    TIGHT FIT AT BOTTOM

    GAP 1/8" MIN AT TOP

    1 1

    /2"

    TY

    P

    WALL FRAMING PER PLAN, TYPICAL

    DOUBLE TOP PLATE

    PLATE SPLICE

    (8) 10d NAILS SPACED AT 4" O.C. STAGGERED, ALL NAILS INTO COMMON MEMBER, TYPICAL

    1

    POST PER PLAN, TYPICAL

    SIMPSON 'LS50' EACH SIDE OF POST

    SIMPSON 'PCZ' POST CAP

    2x6 T&G DECKING

    2x6 DF#2 AT 2'-0" O.C. WITH SIMPSON 'LRUZ' RAFTER HANGER, TYPICAL

    RIDGE BEAM PER PLAN

    4x4 HF#2 POSTSIMPSON 'H3' AT EACH RAFTER

    L3x3x1/4 x 0'-3" WITH 5/8" DIA x 3" EMBED LAG SCREW

    VARIES PER PLAN

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:1

    7 P

    M

    CULLY GREENAPARTMENTS

    S0.1PERMIT SET

    TYPICAL DETAILSAND SCHEDULES

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S0.1 1" = 1'-0"1

    FDN_SUBGRADE INSULATION SCHEDULE

    SUBGRADE INSULATION SCHEDULEN.T.S.S0.1

    5SW_HOLDOWN SCHEDULE/DETAIL

    SHEARWALL HOLDOWN SCHEDULE

    FOOTING SCHEDULE

    COLUMN/WALL FOOTING REINFORCING NOTES

    1 TYPICAL EXTERIOR 1'-4" WIDE x 8" DEEP x CON'T (3) #4 BOTTOM SEE FOUNDATION DETAILS

    2 INTERIOR WALL 1'-4" WIDE x 8" DEEP x CON'T THICKENED SLAB (3) #4 BOTTOM SEE FOUNDATION DETAILS

    3 COLUMN 1'-6" x 1'-6" x 8" DEEP (2) #4 BARS EACH WAY AT BOTTOM SEE FOUNDATION DETAILS

    4 COLUMN 2'-6" x 2'-6" x 8" DEEP (3) #4 BARS EACH WAY AT BOTTOM SEE FOUNDATION DETAILS

    5 COLUMN 3'-0" x 3'-0" x 8" DEEP (3) #4 BARS EACH WAY AT BOTTOM SEE FOUNDATION DETAILS

    6 BIKE BARN 8" THICKENED SLAB EDGE (2) #4 BOTTOM SEE FOUNDATION DETAILS

    7 BIKE BARN COVERING 1'-0" x 1'-0" x 8" DEEP (2) #4 BARS EACH WAY AT BOTTOM SEE FOUNDATION DETAILS

    S0.1 1 1/2" = 1'-0"2

    FLR_WEB STIFFENER

    JOIST WEB STIFFENING DETAIL

    S0.1 1" = 1'-0"4

    DOUBLE TOP PLATE SPLICE

    DOUBLE TOP PLATE SPLICE DETAIL

    S0.1 3/4" = 1'-0"6

    CANOPY_ELEVATION

    TYPICAL CANOPY

    1 5/25/18 REVISION 1

    DETAIL OMITTED

    1

    05/25/18

    19

  • 4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    5' -

    0"

    33

    ' -

    1"

    4' - 7" 7' - 5"

    1A2A3A4A

    AA

    BA

    CA

    67' - 0"

    34

    ' -

    0"

    26

    ' -

    0"

    8' -

    0"

    1S1.5

    _____

    TYP1

    S1.5_____

    TYP

    1S1.5

    _____

    TYP

    B

    A

    A A

    A

    B

    24' - 0 1/2"15' - 11 1/2"27' - 0"

    A

    A

    4S1.5

    _____

    TYP

    4S1.5

    _____

    TYP

    3S1.5

    _____

    TYP

    3S1.5

    _____

    TYP

    6' -

    0"

    A5' -

    0" A

    2' - 7"4' - 0"

    CC

    5' - 0"

    B

    HDU8

    HDU8

    HDU8H

    DU8

    HDU4

    HDU4

    HDU4

    HDU4

    HDU2 HD

    U2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    2S1.5

    _____

    TYP2

    S1.5_____

    TYP

    6x6

    HF#

    2 (P

    .T.)

    6x6 HF#2 (P

    .T.)

    2

    2

    1

    1

    1

    11

    1

    1

    1

    1

    3

    3

    33

    33

    4

    3

    4

    4x4 DF#2

    4x4 DF#2TYP

    5S1.5

    _____

    4x4 DF#2TYP

    TYP

    (2) 2

    x6 D

    F#2

    (2) 2

    x6 D

    F#2

    (2) 2

    x6 D

    F#2

    (2) 2

    x6 D

    F#2

    (2) 2

    x6 D

    F#2

    (2) 2

    x6 D

    F#2

    (2) 2x6 DF#2

    (2) 2x6 DF#2

    (4) 2x4 DF#2(4

    ) 2x4

    DF#

    2

    5

    5

    6' -

    0"

    4x6

    DF#

    2

    4x6

    DF#

    2

    (3) 2x4 DF#2

    (3) 2

    x4 D

    F#2

    (2) 2

    x6 D

    F#2

    2

    2

    1S1.5

    _____

    TYP

    2 2 (3) 2x6 DF#2

    (3) 2

    x6 D

    F#2

    (3) 2

    x6 D

    F#2

    (3) 2

    x6 D

    F#2

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    4

    HDU2

    1

    HDU2

    1

    HDU2

    1

    HDU2

    1

    1

    1

    111

    3' - 2" 4' - 2"

    33

    ' -

    1"

    CONCRETE FOOTING PER SCHEDULE ON SHEET S0.1

    FOUNDATION LEGEND:

    WOOD POST PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    HDUX

    SIMPSON HOLDOWN PER PLAN, SEE DETAIL5

    S0.1

    X

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12" BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING TO BE A MINIMUM OF 18" BELOW FINISH GRADE.

    3. AT THE OWNER'S DIRECTION, FOUNDATION DESIGN PARAMETERS ASSUMED AS FOLLOWS IN ACCORDANCE WITH IBC GUIDELINES:

    ALLOWABLE BEARING PRESSURE = 1,500 PSF

    CONTRACTOR IS RESPONSIBLE FOR SITE PREPARATION, INCLUDING VERIFICATION OF SUITABLE SOIL CONDITIONS AND COMPACTION.

    4. WHERE UNDER SLAB VAPOR BARRIER IS USED, PLACE IN ACCORDANCE WITH MANUFACTURER, OR ARCHITECT RECOMMENDATIONS.

    USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR BARRIERS. DO NOT WET CURE.

    5. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    6. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM BASE PLATE ANCHORAGE TO BE 1/2" DIA x 3" EMBED ANCHOR BOLTS AT 48" O.C. AT FOUNDATION. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    FOUNDATION NOTES:

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    0 P

    M

    CULLY GREENAPARTMENTS

    S1.0PERMIT SET

    FOUNDATIONPLAN - 3L-2-3S

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S1.0 1/4" = 1'-0"A

    S_100 FOUNDATION PLAN (BLDG 3L-2-3S)

    FOUNDATION PLAN - BUILDING A, B, C, F, H

    KEY PLAN (3L-2-3S)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • 4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    1B2B3B

    43' - 0"

    27' - 0"16' - 0"

    AB

    BB

    CB

    33

    ' -

    9"

    26

    ' -

    0"

    7' -

    9"

    1S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    4S1.5

    _____

    TYP

    3S1.5

    _____

    TYP

    2S1.5

    _____

    1S1.5

    _____ TYP

    4

    3

    1

    1

    1

    1

    1

    33

    3

    3

    3

    1

    1

    2

    1

    4' - 0"4' - 4"3' - 0"

    4' -

    0"

    6' -

    0"

    5' -

    0"

    4x4

    DF#

    2

    5S1.5

    _____

    6x6

    HF#

    2 (P

    .T.)

    4x4 DF#2

    TYP

    A

    A

    A

    A A A

    30

    ' -

    1"

    A

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    3' - 9"

    5' - 6"6' - 3"

    2' - 11"

    C

    A A

    C

    4' -

    9"

    6' -

    3"

    A

    A

    HDU4

    HDU2

    HDU2

    HDU2

    HDU4

    HDU4

    HDU4

    HDU8

    HDU8

    HDU8

    HDU8

    HDU2

    HDU2 H

    DU2

    HDU2

    1S1.5

    _____

    TYP

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    2S1.5

    _____

    3

    2

    2

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6 HF#2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    TYP

    HDU2

    1

    1

    HDU2

    1

    HDU2

    1

    HDU2

    1

    HDU2

    1

    (3) 2x6 DF#2

    4x6 DF#2

    4x6 DF#2

    (3) 2x6 DF#2

    2

    3

    CONCRETE FOOTING PER SCHEDULE ON SHEET S0.1

    FOUNDATION LEGEND:

    WOOD POST PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    HDUX

    SIMPSON HOLDOWN PER PLAN, SEE DETAIL5

    S0.1

    X

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12" BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING TO BE A MINIMUM OF 18" BELOW FINISH GRADE.

    3. AT THE OWNER'S DIRECTION, FOUNDATION DESIGN PARAMETERS ASSUMED AS FOLLOWS IN ACCORDANCE WITH IBC GUIDELINES:

    ALLOWABLE BEARING PRESSURE = 1,500 PSF

    CONTRACTOR IS RESPONSIBLE FOR SITE PREPARATION, INCLUDING VERIFICATION OF SUITABLE SOIL CONDITIONS AND COMPACTION.

    4. WHERE UNDER SLAB VAPOR BARRIER IS USED, PLACE IN ACCORDANCE WITH MANUFACTURER, OR ARCHITECT RECOMMENDATIONS.

    USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR BARRIERS. DO NOT WET CURE.

    5. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    6. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM BASE PLATE ANCHORAGE TO BE 1/2" DIA x 3" EMBED ANCHOR BOLTS AT 48" O.C. AT FOUNDATION. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    FOUNDATION NOTES:

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    1 P

    M

    CULLY GREENAPARTMENTS

    S1.1PERMIT SET

    FOUNDATIONPLAN - 2-3L

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S1.1 1/4" = 1'-0"B

    S_101 FOUNDATION PLAN (BLDG 2-3L)

    FOUNDATION PLAN - BUILDING G, I

    KEY PLAN (2-3L)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • 4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    AC

    BC

    38

    ' -

    0"

    1C2C3C

    15' - 6"15' - 6"

    31' - 0"

    1S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    4S1.5

    _____

    TYP

    3S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    5S1.5

    _____

    3

    3

    33

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    1

    1

    3

    4x4

    DF#

    2

    1

    3

    4x4

    DF#

    2

    1

    1

    1

    2S1.5

    _____

    TYP

    2

    5' -

    0"

    5' -

    0"

    3' - 5"3' - 0"

    3' - 5" 3' - 0"

    5' -

    0"

    5' -

    0"

    5' -

    0"

    5' -

    0"

    AA A

    AA

    A

    A

    A

    B

    B

    A

    A

    A

    HDU2H

    DU2

    HDU2 HD

    U2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU4H

    DU4

    HDU4

    HDU4

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    33

    ' -

    1"

    A

    HDU2

    2

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    2S1.5

    _____

    TYP

    1

    1

    4' - 4"

    3' - 8"

    3' - 3"

    4x6

    DF#

    2

    2S1.5

    _____

    CONCRETE FOOTING PER SCHEDULE ON SHEET S0.1

    FOUNDATION LEGEND:

    WOOD POST PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    HDUX

    SIMPSON HOLDOWN PER PLAN, SEE DETAIL5

    S0.1

    X

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12" BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING TO BE A MINIMUM OF 18" BELOW FINISH GRADE.

    3. AT THE OWNER'S DIRECTION, FOUNDATION DESIGN PARAMETERS ASSUMED AS FOLLOWS IN ACCORDANCE WITH IBC GUIDELINES:

    ALLOWABLE BEARING PRESSURE = 1,500 PSF

    CONTRACTOR IS RESPONSIBLE FOR SITE PREPARATION, INCLUDING VERIFICATION OF SUITABLE SOIL CONDITIONS AND COMPACTION.

    4. WHERE UNDER SLAB VAPOR BARRIER IS USED, PLACE IN ACCORDANCE WITH MANUFACTURER, OR ARCHITECT RECOMMENDATIONS.

    USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR BARRIERS. DO NOT WET CURE.

    5. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    6. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM BASE PLATE ANCHORAGE TO BE 1/2" DIA x 3" EMBED ANCHOR BOLTS AT 48" O.C. AT FOUNDATION. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    FOUNDATION NOTES:

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    3 P

    M

    CULLY GREENAPARTMENTS

    S1.2PERMIT SET

    FOUNDATIONPLAN - 2N-2N

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S1.2 1/4" = 1'-0"C

    S_102 FOUNDATION PLAN (2N-2N)

    FOUNDATION PLAN - BUILDING E

    KEY PLAN - (2N-2N)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • 4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    1D2D3D

    36' - 0"18' - 0"

    54' - 0"

    CD

    BD

    AD

    24

    ' -

    0"

    7' -

    9 1

    /2"

    31

    ' -

    9 1

    /2"

    1S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    4S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    1S1.5

    _____

    TYP

    5S1.5

    _____

    TYP

    3

    3

    3

    3

    6x6 HF#2 (P

    .T.)

    3

    3

    4x4

    DF#

    2

    3S1.5

    _____

    3

    3

    3

    3

    6x6 HF#2 (P

    .T.)

    2

    8' - 0"8' - 0"5' - 0"6' - 2"

    AAAA

    5' -

    6"

    3' -

    9"

    5' - 1"3' - 6"

    3' - 0"

    7' -

    0"

    4' -

    0"

    A

    A

    A A

    C C

    B

    B

    2

    2

    2

    HDU4

    HDU4

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    31

    ' -

    1"

    A

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2

    HDU2 HD

    U2

    HDU2

    6x6 HF#2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6 HF#2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6

    HF#

    2 (P

    .T.)

    6x6 HF#2 (P

    .T.)

    6x6 HF#2 (P

    .T.)

    2S1.5

    _____

    TYP

    2S1.5

    _____

    TYP

    11

    3' - 5"

    CONCRETE FOOTING PER SCHEDULE ON SHEET S0.1

    FOUNDATION LEGEND:

    WOOD POST PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    HDUX

    SIMPSON HOLDOWN PER PLAN, SEE DETAIL5

    S0.1

    X

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12" BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING TO BE A MINIMUM OF 18" BELOW FINISH GRADE.

    3. AT THE OWNER'S DIRECTION, FOUNDATION DESIGN PARAMETERS ASSUMED AS FOLLOWS IN ACCORDANCE WITH IBC GUIDELINES:

    ALLOWABLE BEARING PRESSURE = 1,500 PSF

    CONTRACTOR IS RESPONSIBLE FOR SITE PREPARATION, INCLUDING VERIFICATION OF SUITABLE SOIL CONDITIONS AND COMPACTION.

    4. WHERE UNDER SLAB VAPOR BARRIER IS USED, PLACE IN ACCORDANCE WITH MANUFACTURER, OR ARCHITECT RECOMMENDATIONS.

    USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR BARRIERS. DO NOT WET CURE.

    5. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    6. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM BASE PLATE ANCHORAGE TO BE 1/2" DIA x 3" EMBED ANCHOR BOLTS AT 48" O.C. AT FOUNDATION. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    FOUNDATION NOTES:

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-2+BUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    4 P

    M

    CULLY GREENAPARTMENTS

    S1.3PERMIT SET

    FOUNDATIONPLAN - 2-2+

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S1.3 1/4" = 1'-0"D

    S_103 FOUNDATION PLAN (BLDG 2-2+)

    FOUNDATION PLAN - BUILDING D

    KEY PLAN (2-CH)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • 1E2E

    BE

    AE

    4" CONCRETE SLAB ON GRADE WITH #3 BARS AT 48" O.C. EACH WAY OVER 6" COMPACTED CRUSHED ROCK

    15' - 1"

    31

    ' -

    0"

    6S1.5

    _____

    TYP

    6S1.5

    _____

    TYP

    7

    7

    4x4

    HF#

    2

    4x4

    HF#

    2

    6

    6

    6

    6

    8' - 1"

    A

    6' -

    0"

    4' -

    6"

    5' -

    0"

    6' -

    0"

    A

    A

    A

    A

    8' - 1"

    A

    A

    6S1.5

    _____

    TYP

    6S1.5

    _____

    TYP

    5S1.5

    _____

    TYP

    HDU2HD

    U2

    HDU2

    7S1.5

    _____

    7S1.5

    _____

    HDU2

    TYP

    TYP

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    1E2E

    BE

    AE

    J-4

    AT

    2' -

    0"

    O.C

    .

    B-1

    B-1

    B-1

    B-1

    0

    B-1

    B-1

    7S3.4

    _____

    7S3.4

    _____

    5S3.4

    _____

    TYP

    15' - 1"

    31

    ' -

    0"

    TYP

    TYP

    6S3.4

    _____

    8S3.4

    _____

    TYP

    J-3

    J-3

    J-3

    J-3

    J-3

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. ROOF DESIGN CRITERIA: DEAD LOAD = 15 PSFSNOW LOAD = 25 PSF + DRIFT DEFLECTION = SMALLER OF LL/240, TL/180

    3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING WITH MINIMUM SPAN RATING OF 32/16 AND A MINIMIM THICKNESS OF 15/32".

    4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS BY LAPPING 6'-0" MINIMUM AND NAILING WITH 16d AT 6 O.C. STAGGERED. SEE TOP PLATE DETAIL ON SHEET S0.1 FOR MORE INFORMATION.

    6. TYPICAL HEADERS (HDR) TO BE 4x6 DF#2. SUPPORT ON (1) 2x4 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    ROOF FRAMING NOTES:

    STRUCTURAL BEARING WALL BELOW

    ROOF FRAMING LEGEND:

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    WOOD POST BELOW PER ROOF FRAMING NOTES

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12" BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING TO BE A MINIMUM OF 18" BELOW FINISH GRADE.

    3. AT THE OWNER'S DIRECTION, FOUNDATION DESIGN PARAMETERS ASSUMED AS FOLLOWS IN ACCORDANCE WITH IBC GUIDELINES:

    ALLOWABLE BEARING PRESSURE = 1,500 PSF

    CONTRACTOR IS RESPONSIBLE FOR SITE PREPARATION, INCLUDING VERIFICATION OF SUITABLE SOIL CONDITIONS AND COMPACTION.

    4. WHERE UNDER SLAB VAPOR BARRIER IS USED, PLACE IN ACCORDANCE WITH MANUFACTURER, OR ARCHITECT RECOMMENDATIONS.

    USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR BARRIERS. DO NOT WET CURE.

    5. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    FOUNDATION NOTES:

    CONCRETE FOOTING PER SCHEDULE ON SHEET S0.1

    FOUNDATION LEGEND:

    WOOD POST PER FLOOR FRAMING NOTES, U.O.N. ON PLAN

    X

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    HDUX

    SIMPSON HOLDOWN PER PLAN, SEE DETAIL5

    S0.1

    2x4 DOUG FIR #2 STUDS AT 16" O.C. TYPICAL

    STRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    6 P

    M

    CULLY GREENAPARTMENTS

    S1.4PERMIT SET

    BIKE BARNFOUNDATION AND

    ROOF FRAMINGPLANS

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    KEY PLAN (BIKE STORAGE)

    05/25/18

    19

  • 1/2" MAX

    STUD WALL PER PLAN

    CONCRETE SLAB AND REINFORCING PER PLAN

    FOOTING SIZE AND REINFORCING PER FOUNDATION PLAN

    PORCH SLAB ON GRADE AS OCCURS BY OTHERS

    PLATE WASHER PER WOOD STUD SHEARWALL SCHEDULE NOTES

    INSULATION AS OCCURS PER ARCHITECT, SEE DETAIL

    MIN

    IMU

    M

    1'-6

    " +

    /-

    MIN6"

    #4 VERTICAL BARS AT 48" O.C. MAXIMUM, ALTERNATE BEND AT FOOTING

    #4 x CONTINUOUS HORIZONTAL BAR AT 24" O.C. MAXIMUM, (2) BARS MINIMUM

    P.T. SILL PLATE AND ANCHORAGE PER SHEARWALL SCHEDULE

    SHEARWALL SHEATHING PER PLAN

    FINISHES PER ARCHITECT

    1S0.1

    6"

    3"

    CLR

    3" CLR

    1

    FOOTING SIZE AND REINFORCING PER FOUNDATION PLAN

    3" CLR

    3"

    CLR

    CONCRETE SLAB AND REINFORCING PER PLAN

    P.T. SILL PLATE AND ANCHORAGE PER SHEARWALL SCHEDULE

    STUD WALL PER PLAN, TYPICAL

    SHEARWALL SHEATHING PER PLAN

    FINISHES PER ARCHITECT, TYPICAL

    12"

    MIN

    1

    POST PER PLAN

    FOOTING SIZE AND REINFORCING PER FOUNDATION PLAN

    CONCRETE SLAB AND REINFORCING PER PLAN

    3" CLR

    3"

    CLR

    P.T. SILL PLATE AND ANCHORAGE PER FOUNDATION NOTES

    FINISHES PER ARCHITECT

    4"

    3"

    CLR

    3" CLR

    FINISHES PER ARCHITECT

    P.T. SILL PLATE AND ANCHORAGE PER SHEARWALL SCHEDULE

    CONCRETE SLAB AND REINFORCING PER PLAN

    FOUNDATION AND STEMWALL PER DETAIL

    ANCHOR BOLT PER HOLDOWN SCHEDULEPROVIDE EXTRA

    VERTICAL BAR AT HOLDOWN ANCHOR

    POST PER SHEARWALL SCHEDULE AT HOLDOWN

    1S1.5

    HOLDOWN PER PLAN

    NOTE:FOR MORE INFO SEE DETAIL

    1S1.5

    1

    MIN6"

    FOOTING SIZE AND REINFORCING PER FOUNDATION PLAN

    3"

    CLR

    3" CLR

    MIN

    IMU

    M

    1' -

    6"

    +/-

    MIN6"

    6" CONCRETE PIER WITH (2) #4 BARS INTO FOOTING

    POST PER PLAN

    SIMPSON 'ABU' POST BASE WITH 5/8" DIA x 5" EMBED EXPANSION ANCHOR

    PORCH SLAB ON GRADE AS OCCURS BY OTHERS

    1

    CONCRETE SLAB AND REINFORCING PER PLAN

    8"

    WALL STUD PER PLAN

    60.0

    P.T. SILL PLATE AND ANCHORAGE PER SHEARWALL SCHEDULE

    SHEARWALL SHEATHING PER PLAN

    #4 x CONTINUOUS

    COMPACTED FILL PER STRUCTURAL NOTES

    1'-6"

    MIN

    MIN6"

    1

    CONCRETE SLAB AND REINFORCING PER PLAN

    8"

    WALLSTUD PER PLAN

    60.0

    P.T. SILL PLATE AND ANCHORAGE PER SHEARWALL SCHEDULE

    6S1.5

    HOLDOWN PER PLAN

    NOTE:FOR MORE INFO SEE DETAIL

    ANCHOR BOLT PER HOLDOWN SCHEDULE

    MIN6"

    1

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:2

    8 P

    M

    CULLY GREENAPARTMENTS

    S1.5PERMIT SET

    FOUNDATIONDETAILS

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218S1.5 1" = 1'-0"1

    FDN_PERIMETER WALL_SLAB

    FOUNDATION DETAIL

    S1.5 1" = 1'-0"4

    FDN_INTERIOR FTG_DOUBLE WALL

    FOUNDATION DETAILS1.5 1" = 1'-0"

    3FDN_INTERIOR FTG_THICKENED POST

    FOUNDATION DETAIL

    S1.5 1" = 1'-0"2

    SW_PERIMETER WALL

    FOUNDATION DETAIL

    S1.5 1" = 1'-0"5

    FDN_COVERING POST

    FOUNDATION DETAILS1.5 1" = 1'-0"

    6FDN_THICKENED EDGE

    FOUNDATION DETAILS1.5 1" = 1'-0"

    7SW_THICKENED EDGE

    FOUNDATION DETAIL

    1 5/25/18 REVISION 1

    05/25/18

    19

  • B-2

    B-2B-1B-2

    B-1B-1

    B-2B-1

    B-2

    B-2

    B-2

    B-1 B-1

    B-1

    B-1

    B-1

    B-1 B-1

    B-1

    B-1 B-1

    B-2

    B-6

    B-8 B-8

    B-5

    B-9

    8' - 2" 7' - 2"

    7' -

    0"

    4' -

    6"

    7' - 0"10' - 0"9' - 0"10' - 0"

    3' -

    11

    "7

    ' -

    6"

    27

    ' -

    1"

    31

    ' -

    1"

    1A2A3A4A

    AA

    BA

    CA

    67' - 0"

    34

    ' -

    0"

    2' -

    0"

    26

    ' -

    0"

    8' -

    0"

    24' - 0 1/2"15' - 11 1/2"27' - 0"

    A A A A

    A

    A

    AA

    A

    A

    A

    A

    B-4

    B-7

    B-4

    B-7

    B-4

    B-4

    B-4

    B-4

    B-5

    B-4

    B-7

    B-4

    2S2.4

    _____

    TYP

    2S2.4

    _____

    TYP

    4S2.4

    _____

    TYP

    4S2.4

    _____

    TYP

    7S2.4

    _____

    TYP

    7S2.4

    _____

    TYP

    MST37

    MST37

    MST37

    MST37

    MST37

    MST37

    MST37

    MST

    37

    MST37

    MST37

    MST37

    MST37

    J-3 AT 1' - 4" O.C.J-3 AT 1' - 4" O.C.

    (FLUSH) (FLUSH)

    B-7 (FLUSH)

    B-4

    (DROP) (DROP)

    (DROP)

    6

    S0.1

    6

    S0.1

    6

    S0.1

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    8S2.4

    _____

    B-4

    6S2.4

    _____

    TYP

    6S2.4

    _____

    TYP

    6S2.4

    _____

    TYP

    6S2.4

    _____

    SIM

    8S2.4

    _____

    B-4

    B-4

    B-4

    B-2

    B-8

    B-8

    B-8

    B-2

    B-8

    B-2B-8

    9S2.4

    _____9S2.4

    _____OPP

    B-8

    B-8

    3S2.4

    _____

    TYP

    1S2.4

    _____3S2.4

    _____

    B-4

    B-4

    1

    1

    1

    1

    4' - 5 3/4" 19' - 6 1/4"

    1

    SIMPSON STRAP PER LEGEND, TYPICAL

    PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH

    1

    11

    SIMPSON STRAP PER LEGEND, TYPICAL

    STRUCTURAL BEARING WALL BELOW

    FLOOR FRAMING LEGEND:

    WOOD POST PER ROOF FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    MTT

    X

    SIMPSON STRAP PER PLAN, SEE DETAIL3

    S2.4

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    LEDGER PER DETAIL8

    S2.4

    WOOD POST BELOW PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON FOUNDATION PLAN

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    SIMPSON 'CS16' STRAP WITH MINIMUM END LENGTH OF 13", SEE FLOOR FRAMING NOTE 13 FOR MORE INFORMATION

    1

    FLOOR FRAMING NOTES:

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. FLOOR DESIGN CRITERIA:DEAD LOAD = 15 PSFLIVE LOAD = 40 PSFDEFLECTION = SMALLER OF LL/360, TL/240

    3. FLOOR SHEATHING TO BE T&G APA RATED STURD-I-FLOOR SHEATHING WITH A MINIMUM SPAN RATING OF 48/24 AND MINIMUM THICKNESS OF 3/4". GLUE WITH CONTINUOUS WAVY 3/8" BEAD AT ALL SUPPORTS AND NAIL AS INDICATED BELOW. ORIENT STRONG AXIS OF SHEATHING PERPENDICULAR TO SUPPORTS.

    4. FLOOR NAILING TO BE 10d RING OR SCREW SHANK NAILS WITH A MINIMUM 1 5/8" PENETRATION. NAIL AT 6" O.C. AT ALL SUPPORTED EDGES AND AT 12" O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    10. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    11. PROVIDE DOUBLE JOIST BELOW INTERIOR NON-BEARING WALLS RUNNING PARALLEL WITH JOISTS.

    12. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    13. INSTALL STRAP OVER SHEATHING AT LOCATIONS INDICATED ON THE PLAN PRIOR TO INSTALLATION OF SECOND FLOOR WALLS.

    1

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    STRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:3

    1 P

    M

    CULLY GREENAPARTMENTS

    S2.0PERMIT SET

    FLOOR FRAMINGPLAN - 3L-2-3S

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S2.0 1/4" = 1'-0"A

    S_200 SECOND FLOOR FRAMING PLAN (BLDG 3L-2-3S)

    FLOOR FRAMING PLAN - BUILDING A, B, C, F, H

    KEY PLAN (3L-2-3S)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • B-6

    B-3

    B-2B-1

    B-1B-1

    B-1B-2

    B-2

    B-2

    B-1B-1

    B-2

    B-2

    B-2

    1B2B3B

    AB

    BB

    CB

    43' - 0"

    27' - 0"16' - 0"

    33

    ' -

    9"

    26

    ' -

    0"

    7' -

    9"

    B-4

    B-7

    B-4

    B-4

    B-4

    B-4

    B-5

    B-5

    2S2.4

    _____

    TYP

    2S2.4

    _____

    TYP

    7S2.4

    _____

    TYP

    4S2.4

    _____

    TYP 6' - 0"9' - 0"10' - 0"

    4' -

    0"

    7' -

    6"

    4' -

    0"

    4' - 7"

    6' -

    2"

    9' -

    0"

    31

    ' -

    1"

    AAA

    A

    A

    A

    A A

    A

    A

    A

    A

    (DROP)

    6S2.4

    _____

    J-3 AT 2' - 0" O.C.

    6S2.4

    _____(DROP)

    8S2.4

    _____

    TYP

    6S2.4

    _____

    SIM

    6

    S0.1

    6

    S0.1

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    B-6

    B-4

    B-4

    B-4

    8' - 0"

    9S2.4

    _____

    MST

    37

    MST37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    B-8

    B-2 B-8

    B-2

    B-8

    B-8

    B-8

    B-4

    B-2

    1S2.4

    _____3S2.4

    _____

    TYPTYP

    3S2.4

    _____

    TYP

    TYP

    1

    1

    B-1

    5' - 10"

    8' - 0" (MIN)

    SIMPSON STRAP PER LEGEND, TYPICAL

    PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH

    1

    1

    1

    STRUCTURAL BEARING WALL BELOW

    FLOOR FRAMING LEGEND:

    WOOD POST PER ROOF FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    MTT

    X

    SIMPSON STRAP PER PLAN, SEE DETAIL3

    S2.4

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    LEDGER PER DETAIL8

    S2.4

    WOOD POST BELOW PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON FOUNDATION PLAN

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    SIMPSON 'CS16' STRAP WITH MINIMUM END LENGTH OF 13", SEE FLOOR FRAMING NOTE 13 FOR MORE INFORMATION

    1

    FLOOR FRAMING NOTES:

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. FLOOR DESIGN CRITERIA:DEAD LOAD = 15 PSFLIVE LOAD = 40 PSFDEFLECTION = SMALLER OF LL/360, TL/240

    3. FLOOR SHEATHING TO BE T&G APA RATED STURD-I-FLOOR SHEATHING WITH A MINIMUM SPAN RATING OF 48/24 AND MINIMUM THICKNESS OF 3/4". GLUE WITH CONTINUOUS WAVY 3/8" BEAD AT ALL SUPPORTS AND NAIL AS INDICATED BELOW. ORIENT STRONG AXIS OF SHEATHING PERPENDICULAR TO SUPPORTS.

    4. FLOOR NAILING TO BE 10d RING OR SCREW SHANK NAILS WITH A MINIMUM 1 5/8" PENETRATION. NAIL AT 6" O.C. AT ALL SUPPORTED EDGES AND AT 12" O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    10. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    11. PROVIDE DOUBLE JOIST BELOW INTERIOR NON-BEARING WALLS RUNNING PARALLEL WITH JOISTS.

    12. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    13. INSTALL STRAP OVER SHEATHING AT LOCATIONS INDICATED ON THE PLAN PRIOR TO INSTALLATION OF SECOND FLOOR WALLS.

    1

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    STRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:3

    3 P

    M

    CULLY GREENAPARTMENTS

    S2.1PERMIT SET

    FLOOR FRAMINGPLAN - 2-3L

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S2.1 1/4" = 1'-0"B

    S_201 SECOND FLOOR FRAMING PLAN (BLDG 2-3L)

    FLOOR FRAMING PLAN - BUILDING G, I

    KEY PLAN (2-3L)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • B-3

    B-3

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    B-2

    AC

    BC

    1C2C3C

    38

    ' -

    0"

    15' - 6"15' - 6"

    31' - 0"

    B-7

    B-7

    B-4

    B-4B-4

    TYP

    2S2.4

    _____

    TYP

    7S2.4

    _____

    TYP

    1S2.4

    _____

    TYP

    1S2.4

    _____

    TYP

    B-4

    B-4

    B-4

    B-4

    B-4

    B-4

    (DROP)

    (DROP) (FLUSH)

    (FLUSH)

    5S2.4

    _____ 6S2.4

    _____

    5S2.4

    _____6S2.4

    _____

    6

    S0.1

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    B-2

    B-8

    B-8

    B-8

    B-8

    B-8

    B-2B-8

    9S2.4

    _____

    9S2.4

    _____

    5' - 0"

    5' - 2" 4' - 7"

    AA

    AA

    11

    ' -

    0"

    7' -

    0"

    A

    A

    5' - 6"

    5' - 6"

    A A

    A A

    7' -

    0"

    11

    ' -

    0"

    A

    A

    33

    ' -

    1"

    B-4

    A

    MST

    37

    MST

    37

    MST37

    MST37 M

    ST37

    MST37

    MST

    37M

    ST37 MST

    37

    MST

    37

    TYP

    TYP

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    6

    S0.1

    2S2.4

    _____

    11

    11

    1 1

    1 1

    1

    5' - 4"

    4' - 8"

    5' - 10"

    4' - 0" (MIN)

    PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH

    1

    MIN

    4' - 0"

    STRAP PER LEGEND, PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH

    1

    STRUCTURAL BEARING WALL BELOW

    FLOOR FRAMING LEGEND:

    WOOD POST PER ROOF FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    MTT

    X

    SIMPSON STRAP PER PLAN, SEE DETAIL3

    S2.4

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    LEDGER PER DETAIL8

    S2.4

    WOOD POST BELOW PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON FOUNDATION PLAN

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    SIMPSON 'CS16' STRAP WITH MINIMUM END LENGTH OF 13", SEE FLOOR FRAMING NOTE 13 FOR MORE INFORMATION

    1

    FLOOR FRAMING NOTES:

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. FLOOR DESIGN CRITERIA:DEAD LOAD = 15 PSFLIVE LOAD = 40 PSFDEFLECTION = SMALLER OF LL/360, TL/240

    3. FLOOR SHEATHING TO BE T&G APA RATED STURD-I-FLOOR SHEATHING WITH A MINIMUM SPAN RATING OF 48/24 AND MINIMUM THICKNESS OF 3/4". GLUE WITH CONTINUOUS WAVY 3/8" BEAD AT ALL SUPPORTS AND NAIL AS INDICATED BELOW. ORIENT STRONG AXIS OF SHEATHING PERPENDICULAR TO SUPPORTS.

    4. FLOOR NAILING TO BE 10d RING OR SCREW SHANK NAILS WITH A MINIMUM 1 5/8" PENETRATION. NAIL AT 6" O.C. AT ALL SUPPORTED EDGES AND AT 12" O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    10. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    11. PROVIDE DOUBLE JOIST BELOW INTERIOR NON-BEARING WALLS RUNNING PARALLEL WITH JOISTS.

    12. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    13. INSTALL STRAP OVER SHEATHING AT LOCATIONS INDICATED ON THE PLAN PRIOR TO INSTALLATION OF SECOND FLOOR WALLS.

    1

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    HSTRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:3

    6 P

    M

    CULLY GREENAPARTMENTS

    S2.2PERMIT SET

    FLOOR FRAMINGPLAN - 2N-2N

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S2.2 1/4" = 1'-0"C

    S_202 SECOND FLOOR FRAMING PLAN (BLDG 2N-2N)

    FLOOR FRAMING PLAN - BUILDING E

    KEY PLAN - (2N-2N)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • B-2B-2B-1B-1B-2

    B-2B-2B-1

    B-1

    B-1

    B-2

    B-1

    B-2

    B-2

    B-2

    1D2D3D

    CD

    BD

    AD

    36' - 0"18' - 0"

    54' - 0"

    24

    ' -

    0"

    7' -

    9 1

    /2"

    31

    ' -

    9 1

    /2"

    B-5

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    11 7/8" TJI 110 JOISTS (J-1) AT 1' - 4" O.C.

    J-3 AT 2' - 0" O.C.

    J-3 AT 2' - 0" O.C.

    J-3

    AT

    2' -

    0" O

    .C.

    J-3

    AT

    2' -

    0"

    O.C

    .

    B-8

    B-8

    B-8B-8B-8

    B-8

    B-3

    B-4

    B-4

    B-46

    S2.4_____

    (DROP)

    2S2.4

    _____TYP

    7S2.4

    _____

    1S2.4

    _____TYP

    10S2.4

    _____

    10S2.4

    _____

    (FLUSH)

    8S2.4

    _____

    9S2.4

    _____

    B-1

    B-8

    7' - 0"

    9' -

    3"

    16' - 0"5' - 6"9' - 6"

    27

    ' -

    1"

    5' -

    0"

    5' -

    0"

    4' -

    0"

    A

    AAA

    A

    A

    A

    A

    A

    A

    B-4

    B-4

    MST37

    MST37

    MST

    37

    MST

    37

    MST

    37

    MST

    37

    3S2.4

    _____

    TYP

    3S2.4

    _____

    TYP

    TYP

    1S2.4

    _____

    TYP

    11 7/8" TJI 360 JOISTS (J-2) AT 1' - 4" O.C.

    B-4

    TYPICAL, U.O.N.

    8' - 6"

    SIMPSON 'CS16' x REQ'D STRAP, PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH1

    1' - 4"

    1' -

    4"

    (M

    IN)

    MIN

    3' - 0"

    SIMPSON 'CS16' x REQ'D STRAP, PROVIDE BLOCKING BETWEEN JOISTS ALONG STRAP LENGTH

    MST

    37

    MST

    37

    STRUCTURAL BEARING WALL BELOW

    FLOOR FRAMING LEGEND:

    WOOD POST PER ROOF FRAMING NOTES, TYPICAL U.O.N. ON PLAN

    X

    MTT

    X

    SIMPSON STRAP PER PLAN, SEE DETAIL3

    S2.4

    SHEAR WALL TYPE PER SCHEDULE ON SHEET S0.1. ALL EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS UNLESS OTHERWISE NOTED

    2x4 DOUG FIR #2 STUDS AT 16" O.C.

    2x6 DOUG FIR #2 STUDS AT 16" O.C., TYPICAL U.O.N. ON PLAN

    LEDGER PER DETAIL8

    S2.4

    WOOD POST BELOW PER FLOOR FRAMING NOTES, TYPICAL U.O.N. ON FOUNDATION PLAN

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    SIMPSON 'CS16' STRAP WITH MINIMUM END LENGTH OF 13", SEE FLOOR FRAMING NOTE 13 FOR MORE INFORMATION

    1

    FLOOR FRAMING NOTES:

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. FLOOR DESIGN CRITERIA:DEAD LOAD = 15 PSFLIVE LOAD = 40 PSFDEFLECTION = SMALLER OF LL/360, TL/240

    3. FLOOR SHEATHING TO BE T&G APA RATED STURD-I-FLOOR SHEATHING WITH A MINIMUM SPAN RATING OF 48/24 AND MINIMUM THICKNESS OF 3/4". GLUE WITH CONTINUOUS WAVY 3/8" BEAD AT ALL SUPPORTS AND NAIL AS INDICATED BELOW. ORIENT STRONG AXIS OF SHEATHING PERPENDICULAR TO SUPPORTS.

    4. FLOOR NAILING TO BE 10d RING OR SCREW SHANK NAILS WITH A MINIMUM 1 5/8" PENETRATION. NAIL AT 6" O.C. AT ALL SUPPORTED EDGES AND AT 12" O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.

    10. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    11. PROVIDE DOUBLE JOIST BELOW INTERIOR NON-BEARING WALLS RUNNING PARALLEL WITH JOISTS.

    12. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    13. INSTALL STRAP OVER SHEATHING AT LOCATIONS INDICATED ON THE PLAN PRIOR TO INSTALLATION OF SECOND FLOOR WALLS.

    1

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-2+BUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    HSTRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:3

    8 P

    M

    CULLY GREENAPARTMENTS

    S2.3PERMIT SET

    FLOOR FRAMINGPLAN - 2-2+

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S2.3 1/4" = 1'-0"D

    S_203 SECOND FLOOR FRAMING PLAN (BLDG 2-2+)

    FLOOR FRAMING PLAN - BUILDING D

    KEY PLAN (2-CH)

    1 5/25/18 REVISION 1

    05/25/18

    19

  • 1 1/4" TIMBERSTRAND RIM JOIST

    FLOOR SHEATHING PER PLAN

    FRAMING PER PLAN

    STUD WALL PER PLAN

    HEADER AS OCCURS

    EDGE NAILING

    SHEARWALL SHEATHING PER PLAN

    STUD WALL PER PLAN

    SOLE PLATE AND ATTACHMENT PER SHEARWALL SCHEDULE

    EDGE NAILING

    (2) 16d NAILSSIMPSON 'A35' AT 48 O.C. TYPICAL, PROVIDE 16" SPACING AT DESIGNATED SHEARWALLS

    1 1/4" TIMBERSTRAND RIM JOIST

    SOLE PLATE AND ATTACHMENT PER SHEARWALL SCHEDULE

    SHEARWALL SHEATHING PER PLAN

    STUD WALL PER PLAN

    FLOOR SHEATHING PER PLAN

    TJI BLOCKING AT 48" O.C.

    SIMPSON 'A35' AT 48 O.C. TYPICAL, PROVIDE 16" SPACING AT DESIGNATED SHEARWALLS

    STUD WALL PER PLAN

    EDGE NAILING

    FRAMING PER PLAN

    SIMPSON 'IUS' FACE MOUNT HANGER

    HEADER AS OCCURS

    (2) 16d NAILS

    STIFFENER PER DETAIL 2

    S0.1

    EDGE NAILING

    STUD WALL PER PLANFRAMING PER PLAN WITH SIMPSON 'ITS' HANGER

    FLOOR SHEATHING PER PLAN

    EDGE NAILING

    STIFFENER PER DETAIL 2

    S0.1

    HEADER AS OCCURS

    SOLE PLATE AND ATTACHMENT PER SHEARWALL SCHEDULE

    SHEARWALL SHEATHING PER PLAN, TYPICAL

    1 1/4" TIMBERSTRAND RIM JOIST

    SIMPSON 'IUS' FACE MOUNT HANGER, INVERTEDPER ARCHITECT

    STUD WALL PER PLAN

    BOUNDARY NAILING PER PLAN

    1

    SIMPSON 'A34' CLIP AT 48" O.C.

    1

    EDGE NAILING, TYPICAL

    1

    EDGE NAILING, TYPICAL

    FRAMING PER PLAN, TYPICAL

    STUD WALL PER PLAN, TYPICAL

    FLOOR SHEATHING PER PLAN

    SOLE PLATE AND ATTACHMENT PER SHEARWALL SCHEDULE

    SHEARWALL SHEATHING PER PLAN

    SHEARWALL SHEATHING PER PLAN

    FRAMING PER PLAN

    NOTE:FOR MORE INFO SEE DETAILS AND

    STUD WALL PER PLAN

    SHEARWALL SHEATHING PER PLAN

    STUD WALL PER PLAN

    1S2.4

    STRAP PER PLAN, CENTER ON RIM JOIST

    WRAP STRAP AROUND BEAM AS REQ'D AT LOCATIONS WHERE STUD FRAMING DOES NOT EXIST

    2S2.4

    SECURE BEAM TO POST WITH SIMPSON 'HUC46' FACE MOUNT HANGER EACH END

    1

    FLOOR NAILING PER PLAN

    SIMPSON 'IUS' FACE MOUNT HANGER

    FLOOR SHEATHING PER PLAN

    FRAMING PER PLAN, TYPICAL

    BEAM PER PLAN

    FLOOR NAILING PER PLAN

    FLOOR SHEATHING PER PLAN

    FRAMING PER PLAN, TYPICAL

    BEAM PER PLAN

    1 1/4" BLOCKING

    PROVIDE WEB STIFFENERS WHERE JOISTS RUN CONTINUOUS OVER INTERIOR BEARING WALL, SEE DETAIL

    (2) 10d TOENAILS

    NOTE:WALL OCCURS AT SIM CONDITION

    2S0.1

    COORDINATE EAVE EXTENSION AND FRAMING WITH ARCHITECT

    POST PER PLAN

    BEAM PER PLAN WITH SIMPSON 'PC66' POST CAP

    4x8 LEDGER WITH (2) 3/8" x REQ'D LAG SCREWS AT EACH STUD (16" O.C.)

    NOTE:FOR MORE INFO SEE DETAILS AND8

    S2.4

    EDGE NAILING, TYPICAL

    SIMPSON 'H3' AT EACH JOIST

    SIMPSON 'LSSU26' SLOPEABLE HANGER

    2x6 T&G DECKING

    FRAMING PER PLAN, DO NOT OVERCUT

    1S2.4

    SHEARWALL SHEATHING PER PLAN, EXTEND FULL HEIGHT

    FRAMING PER PLAN, DO NOT OVERCUT

    COORDINATE EAVE EXTENSION AND FRAMING WITH ARCHITECT

    2x8 LEDGER WITH (2) #10 WOOD SCREWS AT EACH STUD (16" O.C.) WITH 2" MINIMUM PENETRATION

    NOTE:FOR MORE INFO SEE DETAIL 1

    S2.4

    EDGE NAILING, TYPICAL

    2x BLOCKING WITH EDGE NAILING, PROVIDE SIMPSON 'RBC' CLIPS AT 48" O.C.

    STUD WALL PER PLANSIMPSON 'LSSU26' SLOPEABLE HANGER

    ROOF SHEATHING PER PLAN

    BEAM PER PLAN

    2x6 x CONT. PLATE WITH 10d NAILS AT 6" O.C INTO RIM JOIST

    HEADER PER PLAN AS OCCURS

    STUD WALL PER PLAN

    2x8 CEILING JOISTS AT 24" O.C.

    SIMPSON 'LUS26' FACE MOUNT HANGER

    FRAMING PER PLAN WITH SIMPSON 'IUS' FACE MOUNT HANGER

    2x4 x REQ'D WITH (3) 10d NAILS INTO JOIST AND RAFTER

    SIMPSON 'H3' AT EACH JOIST

    EDGE NAILING, TYPICAL

    SIMPSON 'A34' CLIP AT 48" O.C. 1

    1

    2x6 T&G DECKING

    BEAM PER PLAN WITH SIMPSON 'HUC410' FACE MOUNT HANGER

    L3x3x1/4 x 0'-3" WITH 5/8" DIA x 3" EMBED LAG SCREW

    SIMPSON 'HDU2' WITH 5/8" DIA x REQ'D BOLT

    BLOCKING AS REQ'D AT HOLDOWN LOCATION

    NOTE:FOR MORE INFO SEE DETAILS AND6

    S0.1

    2x6 LEDGER WITH FASTENERS PER DETAIL 8

    S2.4

    1S2.4

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:4

    0 P

    M

    CULLY GREENAPARTMENTS

    S2.4PERMIT SET

    FLOOR FRAMINGDETAILS

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S2.4 1" = 1'-0"1

    FLR_JOIST PERP_STUD WALL

    FLOOR FRAMING DETAILS2.4 1" = 1'-0"

    2FLR_JOIST PAR_STUD WALL

    FLOOR FRAMING DETAILS2.4 1" = 1'-0"

    4FLR_BUMPOUT_HDR

    FLOOR FRAMING DETAIL

    S2.4 1" = 1'-0"7

    FLR_INT_JOIST PAR_WALL STACK

    FLOOR FRAMING DETAIL

    S2.4 1" = 1'-0"3

    SW_STRAP

    FLOOR STRAP DETAIL

    S2.4 1" = 1'-0"5

    FLR_INT_FLUSH BEAM

    FLUSH BEAM FRAMING DETAILS2.4 1" = 1'-0"

    6FLR_INT_DROP BEAM

    DROP BEAM FRAMING DETAIL

    S2.4 1" = 1'-0"10

    FLR_PATIO COVERING

    PORCH COVERING DETAIL

    S2.4 1" = 1'-0"8

    FLR_KITCHEN

    FLOOR / ROOF FRAMING DETAIL

    S2.4 1" = 1'-0"9

    PORCH ROOF LEDGER CONNECTION

    PORCH ROOF DETAIL

    1 5/25/18 REVISION 1

    05/25/18

    19

  • B-1B-2B-2B-2

    B-1

    B-1

    B-1

    B-2B-1

    B-3

    B-1B-2

    B-1

    B-1

    B-1

    B-1 B-2

    1A2A3A4A

    AA

    BA

    CA

    67' - 0"

    34

    ' -

    0"

    26

    ' -

    0"

    8' -

    0"

    24' - 0 1/2"15' - 11 1/2"27' - 0"

    PRE-MANUFACTURED TRUSS AT 2' - 0" O.C.PRE-MANUFACTURED TRUSS AT 2' - 0" O.C.PRE-MANUFACTURED TRUSS AT 2' - 0" O.C.

    2S3.4

    _____

    1S3.4

    _____

    1S3.4

    _____

    2S3.4

    _____

    TYP

    TYP

    TYP

    TYP

    3S3.4

    _____3S3.4

    _____

    TYP TYP

    STRUCTURAL BEARING WALL BELOW

    ROOF FRAMING LEGEND:

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    WOOD POST BELOW PER ROOF FRAMING NOTES

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. ROOF DESIGN CRITERIA: DEAD LOAD = 15 PSFSNOW LOAD = 25 PSF + DRIFT DEFLECTION = SMALLER OF LL/240, TL/180

    3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING WITH MINIMUM SPAN RATING OF 32/16 AND A MINIMIM THICKNESS OF 15/32".

    4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    ROOF FRAMING NOTES:

    9. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    10. ROOF TRUSSES ARE TO BE DESIGNED AND PRE-FABRICATED BY ROOF TRUSS MANUFACTURER. TRUSS LOADS IMPOSED ON THE STRUCTURE ARE TO BE INDICATED ON THE SUBMITTAL CALCULATIONS. SEE STRUCTURAL NOTES FOR ADDITIONAL TRUSS REQUIREMENTS.

    DESIGN DRAWINGS AND SPECIFICATIONS TO ENSURE THAT THE TRUSSES HAVE BEEN DESIGNED CONSIDERING THE CORRECT LOADS, FRAMING CONDITIONS, AND PROJECT REQUIREMENTS. A LETTER FROM THE TRUSS ENGINEER CERTIFYING THEIR REVIEW AND AGREEMENT OF THE DESIGN WITH THESE DOCUMENTS IS TO ACCOMPANY THE TRUSS DESIGN SUBMITTAL.

    11. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    STRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:4

    1 P

    M

    CULLY GREENAPARTMENTS

    S3.0PERMIT SET

    ROOF FRAMINGPLAN - 3L-2-3S

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S3.0 1/4" = 1'-0"A

    S_300 ROOF FRAMING PLAN (BLDG 3L-2-3S)

    ROOF FRAMING PLAN - BUILDING A, B, C, F, H

    KEY PLAN (3L-2-3S)

    05/25/18

    19

  • B-1B-2B-2

    B-1 B-2

    B-2

    B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    1B2B3B

    AB

    BB

    CB

    43' - 0"

    27' - 0"16' - 0"

    33

    ' -

    9"

    26

    ' -

    0"

    7' -

    9"

    PRE-MANUFACTURED TRUSS AT 2' - 0" O.C.

    PRE-MANUFACTURED TRUSS AT 2' - 0" O.C.

    2S3.4

    _____

    1S3.4

    _____

    1S3.4

    _____

    2S3.4

    _____

    TYP

    TYP

    TYP

    TYP

    3S3.4

    _____

    TYP

    STRUCTURAL BEARING WALL BELOW

    ROOF FRAMING LEGEND:

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    WOOD POST BELOW PER ROOF FRAMING NOTES

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. ROOF DESIGN CRITERIA: DEAD LOAD = 15 PSFSNOW LOAD = 25 PSF + DRIFT DEFLECTION = SMALLER OF LL/240, TL/180

    3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING WITH MINIMUM SPAN RATING OF 32/16 AND A MINIMIM THICKNESS OF 15/32".

    4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP PLATE SPLICE DETAIL ON SHEET S0.1.

    6. HEADERS PER PLAN TO BE SUPPORTED ON (1) 2x6 STUD U.O.N. ON PLAN. PROVIDE (1) KING STUD EACH END OF HEADER.

    7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE' POST CAP TYPICAL, U.O.N.

    8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.

    ROOF FRAMING NOTES:

    9. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR ASSEMBLY TO BE PER DRAWINGS. MINIMUM SILL PLATE ANCHORAGE TO BE 16d AT 8" O.C. AT UPPER WALLS.

    10. ROOF TRUSSES ARE TO BE DESIGNED AND PRE-FABRICATED BY ROOF TRUSS MANUFACTURER. TRUSS LOADS IMPOSED ON THE STRUCTURE ARE TO BE INDICATED ON THE SUBMITTAL CALCULATIONS. SEE STRUCTURAL NOTES FOR ADDITIONAL TRUSS REQUIREMENTS.

    DESIGN DRAWINGS AND SPECIFICATIONS TO ENSURE THAT THE TRUSSES HAVE BEEN DESIGNED CONSIDERING THE CORRECT LOADS, FRAMING CONDITIONS, AND PROJECT REQUIREMENTS. A LETTER FROM THE TRUSS ENGINEER CERTIFYING THEIR REVIEW AND AGREEMENT OF THE DESIGN WITH THESE DOCUMENTS IS TO ACCOMPANY THE TRUSS DESIGN SUBMITTAL.

    11. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP STUDS ARE BEARING.

    BUILDING KEYA. TOWNHOMES - UNITS 1-2-3B. TOWNHOMES - UNITS 4-5-6C. TOWNHOMES - UNITS 7-8-9D. DUPLEX - UNITS 10a-10bE. DUPLEX - UNITS 11a-11bF. TOWNHOMES - UNITS 12-13-14G. DUPLEX - UNITS 15a-15bH. TOWNHOMES - UNITS 16-17-18I. DUPLEX - UNITS 19a-19bJ. ACCESSORY - BIKE STORAGE

    BUILDING TYPESBUILDINGS: A, B, C, F & H - MODEL 3L-2-3SBUILDINGS: G & I - MODEL 2-3LBUILDING: D - MODEL 2-CHBUILDING: E - MODEL 2N-2NBUILDING: J - BIKE BARN

    A

    B

    C

    D

    I

    G

    F

    E

    EXISTINGHOUSE

    J

    H

    STRUCTURAL FRAMING LEGEND

    FRAMING I.D.

    B-1

    FRAMING TYPE

    4x6 DF#2

    B-2 4x10 DF#2

    B-3 3 1/2 x 9 GLB

    B-4 1 3/4 x 11 7/8 LSL

    B-5 3 1/2 x 12 GLB

    B-6 3 1/2 x 15 GLB

    B-7 3 1/2 x 11 7/8 GLB

    B-8 5 1/2 x 12 GLB

    B-9

    B-10 4x8 HF#2

    5 1/2 x 15 GLB

    J-1 11 7/8 TJI 110

    J-2 11 7/8 TJI 360

    J-3 2x6 DF#2

    J-4 2x12 DF#2

    CHECKED

    PROJ. NO.

    DATE

    DRAWN

    REVISIONS

    PROJECT NAME

    SCALE

    # DATE DESCRIPTION

    AS NOTED

    C:\U

    sers

    \Ste

    ph

    ens\D

    ocu

    me

    nts

    \00

    RE

    VIT

    \Cully

    Gre

    en

    Ap

    art

    me

    nts

    _R

    EV

    1_

    ste

    ph

    ens07

    .rvt

    5/2

    5/2

    018

    3:4

    2:4

    3 P

    M

    CULLY GREENAPARTMENTS

    S3.1PERMIT SET

    ROOF FRAMINGPLAN - 2-3L

    20170307

    JJESMS

    DECEMBER 05, 2017

    4736, 4752 NE GOING STAND 4540 NE 47TH AVE

    PORTLAND, OR 97218

    S3.1 1/4" = 1'-0"B

    S_301 ROOF FRAMING PLAN (BLDG 2-3L)

    ROOF FRAMING PLAN - BUILDING G, I

    KEY PLAN (2-3L)

    05/25/18

    19

  • B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    B-1

    AC

    BC

    1C2C3C

    38

    ' -

    0"

    15' - 6"15' - 6"

    31' - 0"

    1S3.4

    _____

    2S3.4

    _____

    1S3.4

    _____

    2S3.4

    _____

    TYP

    TYP

    TYP

    TYP

    PR

    E-M

    AN

    UF

    AC

    TU

    RE

    D T

    RU

    SS

    AT

    2' -

    0"

    O.C

    .

    PR

    E-M

    AN

    UF

    AC

    TU

    RE

    D T

    RU

    SS

    AT

    2' -

    0"

    O.C

    .

    STRUCTURAL BEARING WALL BELOW

    ROOF FRAMING LEGEND:

    BEAM ID PER STRUCTURAL FRAMING LEGENDB-#

    WOOD POST BELOW PER ROOF FRAMING NOTES

    1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

    2. ROOF DESIGN CRITERIA: DEAD LOAD = 15 PSFSNOW LOAD = 25 PSF + DRIFT DEFLECTION = SMALLER OF LL/240, TL/180

    3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING WITH MINIMUM SPAN RATING OF 32/16 AND A MINIMIM THICKNESS OF 15/32".

    4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT REQUIRED.

    5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND SHEARWALLS PER TOP