DH1539B Type of Site:OUTDOOR
INDOOR (PU Cabin)
INDOOR (BRICK) R1
AIRTEL OUTDOOR R2
R3
R1
10-Jan-13
STRUCTURAL FEASIBILITY REPORT WITH RECOMMENDATION
Region
Date
RECOMMENDATION
TOWER
/POLE
HEIGHT (m)
LOCATION
OF TOWER/
POLE (m )
Site ID:
Address
Project
ARRANGEME
NT OF
TOWER
TOTAL
HEIGHT
(m)
GENERATOR
POSITION
WIND SPEED 210 KPH, 6.0M POLES WITH OUTDOOR
OPTION REMARKSSELECTED
(YES/N0)
Arun Alo, H#79, Cercular road, Siddeswari, Dhaka-1217.
Remarks:
Signature
M/24108
RAJUK NO-DMINB/CE-0334
Company Name
Prudential Consultant
Address TOWER EXISTING ROOF TOPGa, 40/5, Shahjadpur, Gulshan, Dhaka-1212. POLE EXISTTING GROUND FLOOR
E 20 EXISTING ROOM
A 6 BESIDE BUILDING
B 9 NOT AVAILABLE
C 12
D 15
E 20
F
Md. Saiful Hoque Sohel
YES
MIEB NO.
Name of the Engineer
NOT AVAILABLE36POLE306
IT IS RECOMMENDED TO BUILD MENTIONING TOWER/POLE
B SAFE
7/30/2019 Structural Feasibility Report of Dh1539b
2/7
Site ID DH1539B
Address Arun Alo, H#79, Cercular road, Siddeswari, Dhaka-1217.
Project AIRTEL
Date 10-Jan-13
Uplift Down force Share Uplift Down force Share
WIND
SPEED
85
TOWER/ POLE REACTION
CRITICAL COLUMN C27(SEE DRAWING) BRIEF ANALYSIS
WIND SPEED 210 KPH, 6.0M POLES WITH OUTDOOR
85
LEG TO LEG
DISTANCE
GENERAL INFORMATION
Un factored (KN) Factored(KN)TOWER/
POLE TYPE
6M POLE 2.5 210KPH 12
UNIT SYSTEM MKSUSD ACCORDING TO BANGLADESH NATIONAL BUILDING CODE
(BNBC)1993,UBC 1997
WEIGHT OF EQUIPMENT
ITEMRBS-2206(IDU)
RBS-2106(ODU)
SIZE (MM) WEIGHT(KG )600X 400 X1850 230 kg
FIRE EXTINGUISHER
620 X 300 X 900 100 kg
400 X 350 X 250 15 kg
SDH
MDB
ROXTEC 4X6 294 X 665 20 kg
KRONE 450 X 220 X 125 5 kg
AC INDOOR UNIT 1100 X 290 X 300
800 kg
20 kg
GENSET (FG WILSON) 1684 X 860 X 1453 721 kg
ROXTEC 3X6 294 X 550 20 kg
GENSET (PARAMAC) 2000 X 920 X 1300 875 kg
TRANSMISSION RACK 600 X 600 X 1650 50 kg
500X 1000 X 21001294 X 846 X 480
750 X 500 X 210 15 kg
PBC 6500 RECTIFIER 600 X 400 X 1917
BBU (8 BATTERIES)
1300 X 925 X 1617 685 kg
597 kg50 kg
5 kg
DESIGN METHOD
AVR
FMS
7/30/2019 Structural Feasibility Report of Dh1539b
3/7
Force kN Flexure 0.90
Distance m Tension 0.90Moment kN-m Shear & Torsion 0.85
Area sqm Bearing on Concrete 0.70
Unit Weight kN/cum
Member Dimension mm
PressureN/sqmm
(Mpa)
Unit Weight of RCC 23.60 kN/cum
Dead Load 1.40 Unit Weight of Brick 18.86 kN/cum
Live Load 1.700 FF 0.5 kN/sqm
Equipment Load 1.00 kN
Concrete strength fc'
20.60 Mpa Generator Load 1.00 kNSteel strength fy 400.00 Mpa Live Load 2.00 kN/sqm
Load factors
Strength of Materials
General Information
Load Consideration
Strength Reduction factorUNIT
No. of Floors 10 No(s) No. of Floors No(s)
Height of Floors 3 m Height of Floors m
Height of Brick Wall 2.6 m Height of Brick Wall m
Thickness of Brick Wall 125 mm Thickness of Brick Wall mm
Column Dimension Column Dimension
Width 425 mm Width mmBreadth 300 mm Breadth mm
Beam Dimension Beam Dimension
Depth 400 mm Depth mm
Width 250 mm Width mm
Slab Dimension Slab Dimension
Length, a 5.4 m Length, a m
Length, b 2.43 m Length, b m
Length, c 3.6 m Length, c m
Length, d 4 m Length, d m
Thickness of Slab 160 mm Thickness of Slab mm
Column (form PL to Top of Footing) Beam DimensionLength m Length m
Width 475 mm Depth 375 mm
Breadth 350 mm Width 300 mm
Footing Dimension Slab Dimension
Length m Lenghth, a m
Width m Lenghth, c m
Depth mm Thickness of Slab 125 mm
Equimpent room Information
Foundation Informatin Generator Installation Structrue
Building Information
7/30/2019 Structural Feasibility Report of Dh1539b
4/7
A. Load From Existing BuildingLoad from Slab
Effective area 14.88 sqm
SW 56.18 kN
FF 7.44 kN
Load from Beam
Effective Length 7.72 m
SW 3.93 kN
Partition Wall 47.29 kN
Load from Column
SW 9.03 kNLoad per Floor 123.86 kN
Total Number of floor 10 No(s)
Calculation of Load
Dead Laod
Load on critical column upto GL from Existing Building 1238.63 kN
B. Load from Equipment room
Load from Slab
Effective area 0.00 sqmSW 0.00 kN
FF 0.00 kN
Load from Beam
Effective Length 0.00 m
SW 0.00 kN
Partition Wall 0.00 kN
Load from Column
SW 0.00 kN
Load on critical column From Equipment Room 0.00 kN
C. Load From Generator Installation structure
Beam 0.00 kNSlab 0.00 kN
Load on critical columnfrom Generator Installation stucture 0.00 kN
D. Load on critical column from PL to Face of Footing (SW) 0.00 kN
7/30/2019 Structural Feasibility Report of Dh1539b
5/7
E. Load From Antenna support Structure
(Analysis by Moment Distribution method or STAAD.Pro or by any other software )
Load on Critical Column from Antenna Support Structure 85.00 kN
Total DL on Footing 1238.63 kN
Live Load
F. Load from Existing Building
Effective area 14.88 sqm
Load per Floor 29.75 kN
Total Number of floor 10 No(s)
Load on critical column from Existing Building 297.54 kN
G. Load from Equipment room
Effective area 0.00 sqm
Load on critical column from Equipment room 0.00 kN
H. Load on critical column from Generator 0.00 kN
Total LL on Critical Column 297.54 kN
Other Load
I. Load from Appendix 1
J. Load from Appendix 2
Total Load on critical column from Other sourced 0.00 kN
Total Load on Critical Column
2324.90 kN
520.78 Kip
1.4DL + 1.7LL + TL+ Other Load
7/30/2019 Structural Feasibility Report of Dh1539b
6/7
Serial No. Load Source Load TypeUnfactored
(kN)
Factored
(kN)
DEAD LOAD = 1238.63 1734.08LIVE LOAD = 297.54 505.82
DEAD LOAD = 0.00 0.00
LIVE LOAD = 0.00 0.00
DEAD LOAD = 0.00 0.00
LIVE LOAD = 0.00 0.00
4Load from PL to face of
footingDEAD LOAD = 0.00 0.00
Loadfrom equimpment
room
3
Load from Existing Building
Load from Generator
Installation structure
1
2
Summary of Load Calculation :
5 Load from Antenna support Tower Load = 70.83 85.00
6 Load from Other sources MISC = 0.00
TOTAL LOAD ON CRITICALLY LOADED COLUMN: 1607.00 2324.90
7 Load from Self Weight of Dead Load = 0 0.00
1607.00 2324.90
17.48
TOTAL LOAD ON SOIL:
7/30/2019 Structural Feasibility Report of Dh1539b
7/7
STRENGTH REDUCTION FACTOR, 0.70COLUMN SIZE Width 475.00 mmBreadth 350.00 mm
REBAR :
ReBar Size (mm) 16.00 20 22 25
ReBar Area (sqmm) 201.06 314.16 380.13 490.87
b) BAR NO.
c) TOTAL BAR AREA AS 3325.00 sqmm
Concrete strength fc' 20.60 Mpa
Steel strength fy 400.00 Mpa
MAXIMUM ALLOWABLE: AXIAL LOAD 2342.38 KN OK
REPORT SUMMARY
1. COLUMN CAPACITY CALCULATION:
2. PUNCHING SHEAR CHECK N/AVALUE OF STRENGTH REDUCTION FACTOR, COLUMN SIZE Width
Breadth
FOOTING SIZE
LengthWidth
Depth
Effective Depth
MAXIMUM ALLOWABLE: AXIAL LOA
3. BEARING CAPACITY of SOILFOOTING SIZE
Length
Width
Area
Load on SOIL
Allowable Capacity of Soil
F.S.