25
C:\Users\danielle morales.RCC-SEREGION\Desktop\I-10 Replacement 2013\Appendix A\FigH3_ChipleyDOT_InteriorWestWall_20050401.vsd 04/15/13 Figure H3 Chipley DOT (3-3428) Interior West Wall Scale: 1/2" = 1'-0" Main Braker Panel 2 of 2 VoIP Main Braker Panel 1 of 2 Alarm 66 Block BACS WebManager DC/DC Converter Ethernet SPD Page H6 of 7 78

State of Florida One Eltek Valere Compact Power System shall be installed in accordance with this Appendix and Section 2.3 of this Scope of Services. IP Address: 172.16.76.20 ... BC2000-A51-10VC

  • Upload
    lykiet

  • View
    226

  • Download
    0

Embed Size (px)

Citation preview

C:\Users\danielle morales.RCC-SEREGION\Desktop\I-10 Replacement 2013\Appendix A\FigH3_ChipleyDOT_InteriorWestWall_20050401.vsd04/15/13

Figure H3Chipley DOT (3-3428)

Interior West Wall

Scale: 1/2" = 1'-0"

Main Braker Panel2 of 2

VoIP

Main Braker Panel1 of 2

Alarm66 Block

BACS

WebManager

DC/DC

Converter

Ethernet

SPD

Page H6 of 7 78

Figure H4Chipley DOTBattery Plant

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigH4_Chipley_BatteryPlant.vsd04/12/13

Vendor Shall install new battery in existing rack.

Page H7 of 7 79

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Appendix I – Marianna FHP

80

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page I2 of 7

Appendix I – Table of Contents – Figures and Drawings

Figure I1 – Marianna FHP Shelter Floor Plan ........................................................... I5 of 7

Figure I2 – Marianna FHP -48VDC Power Distribution Rack Profile ......................... I6 of 7

Figure I3 – Marianna FHP Battery Plant Photo......................................................... I7 of 7

81

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page I3 of 7

Marianna FHP Site Requirements

The Vendor shall furnish and install the following equipment at the Marianna FHP site located at 3613 US-90, Marianna, FL.

A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall

be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.

The new battery plant shall be installed in the same location as the removed battery plant.

The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable

shall be used for -48 VDC connections and black jacketed cable shall be used for the return.

B. The Generex BACS battery management system shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.76.22

Subnet Mask: 255.255.254.0

Gateway: 172.16.76.19

C. One Eltek Valere Compact Power System shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.76.20

Subnet Mask: 255.255.254.0

Gateway: 172.16.76.19

82

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page I4 of 7

TABLE I1 – MAJOR EQUIPMENT LIST

Model Number Description QTY.

50G05 Exide Battery 19" rack mount 1

AMGBACS 1001 24-2V Master Kit

BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables

1

TCL 024-112DC TracoPower DC/DC Converter 1

DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager

1

Q4820N-F19DB01-VC Integrated Power System 1

CBB060E Battery Disconnect 1

CBB010M 10 A Circuit breakers 8

BC2000-A51-10VC System Controller w/ Ethernet Port 1

TPP10 Battery Thermal Probe? 1

V1500A-VC V-Series 30A rectifier 2

BAF19 19”single top baffle - 1U 1

VBLANK-VC Blank V-series rectifier chassis 2

ZB24540 Atlantic Scientific Ethernet SPD 4

83

Forestry

Base

Station

CB + NMS

Rack ER-6

47 MHz

Repeater

47 MHz

Base Station

DVM6-45

MW

Repeater

Rack ER-2

MACBS

ER-1

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI1_MariannaFHP_ShelterFloorPlan_20110524.vsd

04/12/13

Figure I1

Marianna FHP (3-3427)

Shelter Floor Plan

Scale: 3/8" = 1'-0"

-48V DC

Battery

Plant

Duplexer

Page I5 of 7 84

Scale: 1 1/4" = 1'-0"

Figure I2Marianna FHP

-48VDC Power Distribution Rack

Eltek Valere Integrated Power System

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI2_MariannaFHP-PwrPlantRack_20021101.vsd04/12/13

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank81 9 16 17 24

72 10 15 18 23

63 11 14 19 22

54 12 13 20 21

+-

Page I6 of 7

BACS

WebManager

DC/DC Converter

85

Figure I3Marianna FHPBattery Plant

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI3_Marianna_BatteryPlant.vsd04/12/13

Vendor Shall install new battery in existing rack.

Page I7 of 7 86

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Appendix J – Sneads Weigh Station

87

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page J2 of 6

Appendix J – Table of Contents – Figures and Drawings

Figure J1 – Sneads Weigh Station Shelter Floor Plan .............................................. J4 of 6

Figure J2 – Sneads Weigh Station -48VDC Power Distribution Rack Profile ............ J5 of 6

Figure J3 – Sneads Weigh Station Battery Plant Photo ............................................ J6 of 6

88

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page J3 of 6

Sneads Weigh Station Site Requirements

The Vendor shall furnish and install the following equipment at the Sneads Weigh Station site located 2 miles west of SR-286 and I-10 at East Bound side of weigh station.

A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall

be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.

The new battery plant shall be installed in the same location as the removed battery plant.

The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable

shall be used for -48 VDC connections and black jacketed cable shall be used for the return.

B. The Generex BACS battery management system shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.74.22

Subnet Mask: 255.255.254.0

Gateway: 172.16.74.19

TABLE J1 – MAJOR EQUIPMENT LIST

Model Number Description QTY.

50G05 Exide Battery 19" rack mount 1

AMGBACS 1001 24-2V Master Kit

BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables

1

TCL 024-112DC TracoPower DC/DC Converter 1

DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager

1

ZB24540 Atlantic Scientific Ethernet SPD 2

89

Figure J1

Sneads Weigh Station (3-3510)

Shelter Floor Plan

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigJ1_Sneads-FloorPlanShelter-

20061102.vsd

03/12/13

Scale: 1/2" = 1'-0"

-48 VDC

Distribution

Rack

Channel Bank

Rack QR-6

DVM6-45 MW

Repeater

Rack QR-5

Page J4 of 6 90

Figure J2

Sneads Weigh Station (3-3510)

-48 VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigJ2_SneadsWeighStation_-48VDCPowerDistributionRack.vsd

04/12/13

EMPTY EMPTYTWINPACKPLUS

COVER PLATE

HI/LO DC ALARM PANEL

SSD2 PANEL

NAME TAG

COVER PLATE

CONNECTOR PLATE(CONNECTS ON BACK)

COVER PLATE

DIGITAL EQUALIZER

Scale: 1 1/4" = 1'-0"

BREAKER PANEL

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank81 9 16 17 24

72 10 15 18 23

63 11 14 19 22

54 12 13 20 21

+-

Page J5 of 6

BACS

WebManager

DC/DC Converter

91

Figure J3Sneads Weigh Station

Battery PlantG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigJ3_SneadsWeighStation_BatteryPlant.vsd

03/12/13

Vendor Shall install new battery in existing rack.

Page J6 of 6 92

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Appendix K – Aspalaga

93

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page K2 of 6

Appendix K – Table of Contents – Figures and Drawings

Figure K1 – Aspalaga Shelter Floor Plan ................................................................. K4 of 6

Figure K2 – Aspalaga -48VDC Power Distribution Rack Profile ............................... K5 of 6

Figure K3 – Aspalaga Battery Plant Photo ............................................................... K6 of 6

94

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page K3 of 6

Aspalaga Site Requirements

The Vendor shall furnish and install the following equipment at the Aspalaga site located 3.5 miles east of SR-286 and I-10 interchange at rest area (off east-bound on-ramp), Aspalaga, FL.

A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall

be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.

The new battery plant shall be installed in the same location as the removed battery plant.

The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable

shall be used for -48 VDC connections and black jacketed cable shall be used for the return.

B. The Generex BACS battery management system shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.72.22

Subnet Mask: 255.255.254.0

Gateway: 172.16.72.19

TABLE K1 – MAJOR EQUIPMENT LIST

Model Number Description QTY.

50G05 Exide Battery 19" rack mount 1

AMGBACS 1001 24-2V Master Kit

BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables

1

TCL 024-112DC TracoPower DC/DC Converter 1

DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager

1

ZB24540 Atlantic Scientific Ethernet SPD 2

95

CB/NMS

Rack

-48 VDC

Distribution

Rack

MACBS

EAST

RACK

DVM6-45

REPEATER

RACK

MACBS

WEST

RACK

BO

OK

CA

SE

+

+

+

Figure K1Aspalaga

Shelter Floor Plan

G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigK1_Aspalaga_ShelterFloorPlan_20111228.vsd03/12/13

Page K4 of 6 96

Figure K2

Aspalaga (3-3426)

-48 VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigK2_Aspalaga_-48VDCPowerDistributionRack_20061002.vsd

04/12/13

Empty

TWIN

PACK

PLUS

25A

TWIN

PACK

PLUS

25A

Scale: 1 1/4" = 1'-0"

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank

Absolyte Battery Bank81 9 16 17 24

72 10 15 18 23

63 11 14 19 22

54 12 13 20 21

+-

Page K5 of 6

BACS

WebManager

DC/DC Converter

97

Figure K3Aspalaga

Battery PlantG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigK3_Aspalaga_BatteryPlant.vsd

03/12/13

Vendor Shall install new battery in

existing rack.

Page K6 of 6 98

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Appendix L – Quincy FHP

99

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page L2 of 7

Appendix L – Table of Contents – Figures and Drawings

Figure L1 – Quincy FHP Shelter Floor Plan ............................................................. L5 of 7

Figure L2 – Quincy FHP -48VDC Power Distribution Rack Profile............................ L6 of 7

Figure L3 – Quincy FHP Battery Plant Photo ........................................................... L7 of 7

100

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page L3 of 7

Quincy FHP Site Requirements

The Vendor shall furnish and install the following equipment at the Quincy FHP site located at 18290 US-90, Quincy, FL.

A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall

be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.

The new battery plant shall be installed in the same location as the removed battery plant.

The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable

shall be used for -48 VDC connections and black jacketed cable shall be used for the return.

B. The Generex BACS battery management system shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.70.22

Subnet Mask: 255.255.254.0

Gateway: 172.16.70.19

C. One Eltek Valere Compact Power System shall be installed in accordance with this

Appendix and Section 2.3 of this Scope of Services.

IP Address: 172.16.70.20

Subnet Mask: 255.255.254.0

Gateway: 172.16.70.19

101

FLORIDA DEPARTMENT OF TRANSPORTATION

I-10 BATTERY PLANT REPLACEMENT

Page L4 of 7

TABLE L1 – MAJOR EQUIPMENT LIST

Model Number Description QTY.

50G05 Exide Battery 19" rack mount 1

AMGBACS 1001 24-2V Master Kit

BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables

1

TCL 024-112DC TracoPower DC/DC Converter 1

DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager

1

Q4820N-F19DB01-VC Integrated Power System 1

CBB060E Battery Disconnect 1

CBB010M 10 A Circuit breakers 8

BC2000-A51-10VC System Controller w/ Ethernet Port 1

TPP10 Battery Thermal Probe? 1

V1500A-VC V-Series 30A rectifier 2

BAF19 19”single top baffle - 1U 1

VBLANK-VC Blank V-series rectifier chassis 2

ZB24540 Atlantic Scientific Ethernet SPD 4

102