Split-type Air-ConditionerMXZ-6E120VAD
EnglishInstallation Manual For INSTALLER• This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of indoor unit.
BH79A274H01_en.indd 1 2016/03/23 10:42:14
En-1
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.• Besuretoobservethewarningsandcautionsspecifiedhereastheyincludeimportantitemsrelatedtosafety.• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.• EquipmentcomplyingwithIEC/EN61000-3-12.
1-2. SPECIFICATIONS
Model
Powersupply*1 Wirespecifications*2 Pipelengthandheightdifference*3,*4,*5,*6,*7,*8
Rated Voltage
Fre-quency
Breakercapacity
Powersupply
Indoor/outdoorconnectingwire
Max.pipelengthper
indoorunit/formulti-system
Max. height difference*9
Max. no. of bends perindoorunit/for multi system
Refrigerant adjustment
A*10
MXZ-6E120VAD 230V 50Hz 32A 3-core 4.0mm2
4-core 1.0/1.5mm2 25m/80m 15m 25/80 20g/m
*1 Connecttothepowerswitchwhichhasagapof3mmormorewhenopentointerruptthesourcepowerphase.(Whenthepowerswitchisshutoff,itmustinterruptallphases.)
*2 Usewiresinconformitywithdesign60245IEC57.Usetheindoor/outdoorconnectingwireinconformitywiththewirespecificationsspecifiedintheinstallation manual of the indoor unit.
*3 Neverusepipeswiththicknesslessthanspecified.Thepressureresistancewillbeinsufficient.
*4 Useacopperpipeoracopper-alloyseamlesspipe.*5 Becarefulnottocrushorbendthepipeduringpipebending.
*6 Refrigerantpipebendingradiusmustbe100mmormore.*7 Insulationmaterial:Heatresistingfoamplastic0.045specificgravity*8 Besuretousetheinsulationofspecifiedthickness.Excessivethickness
maycauseincorrectinstallationoftheindoorunitandinsufficientthicknessmaycausedewdrippage.
*9 If the outdoor unit is installed higher than the indoor unit, max. height differenceisreducedto10m.
*10 Ifpipelengthexceeds30m,additionalrefrigerant(R410A)chargeisre-quired.(Noadditionalchargeisrequiredforpipelengthlessthan30m.)
Additionalrefrigerant=A×(pipelength(m)-30)
Required Tools for InstallationPhillipsscrewdriverLevelScaleUtilityknifeorscissorsTorquewrenchWrench(orspanner)4mmhexagonalwrench
FlaretoolforR410AGaugemanifoldforR410AVacuumpumpforR410AChargehoseforR410APipecutterwithreamer
EN
GLI
SH CONTENTS
1.BEFOREINSTALLATION ............................................................ 12.OUTDOORUNITINSTALLATION ...............................................43.FLARINGWORKANDPIPECONNECTION ...............................54.PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN .........55.PUMPINGDOWN ........................................................................7
CAUTION (Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
n Do not install the unit by yourself (user). Incompleteinstallationcouldcausefireorelectricshock,injuryduetotheunit
falling,orleakageofwater.Consultthedealerfromwhomyoupurchasedtheunitoraqualifiedinstaller.
n Perform the installation securely referring to the installation manual. Incomplete installationcouldcausefire,electricshock, injuryduetothe
unitfalling,orleakageofwater.n When installing the unit, use appropriate protective equipment and
tools for safety. Failure to do so could cause injury.n Install the unit securely in a place which can bear the weight of the
unit. Iftheinstallationlocationcannotbeartheweightoftheunit,theunitcould
fall causing injury.n Electrical work should be performed by a qualified, experienced electri-
cian, according to the installation manual. Be sure to use an exclusive circuit. Do not connect other electrical appliances to the circuit.
If the capacity of thepower circuit is insufficient or there is incompleteelectricalwork,itcouldresultinafireoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts or screws.
Damagedwirescouldcausefireorelectricshock.n Be sure to cut off the main power in case of setting up the indoor P.C.
board or wiring works. Failuretodosocouldcauseelectricshock.n Use the specified wires to connect the indoor and outdoor units
securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections. Do not extend the wires, or use intermediate connection.
Incompleteconnectingandsecuringcouldcausefire.n Do not install the unit in a place where inflammable gas may leak. Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcausean
explosion.n Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet. Itcouldcauseafireoranelectricshockduetodefectivecontact,defective
insulation,exceedingthepermissiblecurrent,etc.n Be sure to use the parts provided or specified parts for the installation
work. Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterdue
toafire,anelectricshock,theunitfalling,etc.n When plugging the power supply plug into the outlet, make sure that
there is no dust, clogging, or loose parts in both the outlet and the plug. Make sure that the power supply plug is pushed completely into the outlet.
Ifthereisdust,clogging,orloosepartsonthepowersupplyplugortheoutlet,itcouldcauseelectricshockorfire.Ifloosepartsarefoundonthepowersupplyplug,replaceit.
n Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely.
Iftheelectricalcoveroftheindoorunitand/ortheservicepaneloftheoutdoorunitarenotattachedsecurely,itcouldresultinafireoranelectricshockduetodust,water,etc.
n When installing, relocating, or servicing the unit, make sure that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
Anypresenceofforeignsubstancesuchasaircancauseabnormalpres-sureriseandmayresultinexplosionorinjury.Theuseofanyrefrigerantother than thatspecified for thesystemwillcausemechanical failure,systemmalfunction,orunitbreakdown.Intheworstcase,thiscouldleadtoaseriousimpedimenttosecuringproductsafety.
n Do not discharge the refrigerant into the atmosphere. If refrigerant leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithafire,harmfulgascouldbegenerated.n Check that the refrigerant gas does not leak after installation has
been completed. Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeflameofa
fanheater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.n Use appropriate tools and piping materials for installation. ThepressureofR410Ais1.6timesmorethanR22.Notusingappropriate
toolsormaterialsandincompleteinstallationcouldcausethepipestoburst or injury.
n When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunningandthestopvalveisopen,aircouldbedrawninandthepressureintherefrigeration cycle could become abnormally high. This could cause the pipestoburstorinjury.
n When installing the unit, securely connect the refrigerant pipes before starting the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnectedandwhenthestopvalveisopen,aircouldbedrawninandthepressurein the refrigeration cycle could become abnormally high. This could cause thepipestoburstorinjury.
n Fasten a flare nut with a torque wrench as specified in this manual. Iffastenedtootight,aflarenutmaybreakafteralongperiodandcause
refrigerantleakage.n The unit shall be installed in accordance with national wiring regula-
tions.n Earth the unit correctly. Donotconnecttheearthtoagaspipe,waterpipe,lightningrodortel-
ephoneearth.Defectiveearthingcouldcauseelectricshock.n Be sure to install an earth leakage breaker. Failuretoinstallanearthleakagebreakermayresultinelectricshockorfire.
n Perform the drainage/piping work securely according to the installation manual.
Ifthereisdefectinthedrainage/pipingwork,watercoulddropfromtheunit,soakinganddamaginghouseholdgoods.
n Do not touch the air inlet or the aluminum fins of the outdoor unit. This could cause injury.
n Do not install the outdoor unit where small animals may live. Ifsmallanimalsenterandtouchtheelectricpartsinsidetheunit,itcould
causeamalfunction,smokeemission,orfire.Also,adviseusertokeepthe area around the unit clean.
WARNING (Couldleadtodeath,seriousinjury,etc.)
1. BEFORE INSTALLATION
BH79A274H01_en.indd 1 2016/03/23 10:42:15
En-2
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTSIfthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable.
Portsizeofoutdoorunit Optionaldifferent-diameterjoints(portsizeofoutdoorunit→diameterofconnectionpipe)
MXZ-6E Liquid/Gas 6.35(1/4)→9.52(3/8):PAC-493PI9.52(3/8)→12.7(1/2):MAC-A454JP9.52(3/8)→15.88(5/8):PAC-SG76RJ12.7(1/2)→9.52(3/8):MAC-A455JP12.7(1/2)→15.88(5/8):MAC-A456JP
Refertotheinstallationmanualofindoorunitforthediameterofconnectionpipeofindoorunit.
AUNIT 6.35(1/4)/12.7(1/2)
B-FUNIT 6.35(1/4)/9.52(3/8)
1-4. SELECTING THE INSTALLATION LOCATION• Whereitisnotexposedtostrongwind.• Whereairflowisgoodanddustless.• Whererainordirectsunshinecanbeavoidedasmuchaspossible.• Whereneighboursarenotannoyedbyoperationsoundorhotair.• Whererigidwallorsupportisavailabletopreventtheincreaseofopera-
tionsoundorvibration.• Wherethereisnoriskofcombustiblegasleakage.• Wheninstallingtheunit,besuretosecuretheunitlegs.• Whereitisatleast3mawayfromtheantennaofTVsetorradio.Opera-
tionoftheairconditionermayinterferewithradioorTVreceptioninareaswherereceptionisweak.Anamplifiermayberequiredfortheaffecteddevice.
• Installtheunithorizontally.• Pleaseinstallitinanareanotaffectedbysnowfallorblowingsnow.In
areaswithheavysnow,pleaseinstallacanopy,apedestaland/orsomebaffleboards.
Note:It isadvisable tomakeapiping loopnearoutdoorunitsoas to reducevibrationtransmittedfromthere.
Note: Whenoperatingtheairconditionerinlowoutsidetemperature,besuretofollowtheinstructionsdescribedbelow.• Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside
maybeexposeddirectlytowind.• Topreventexposuretowind,installtheoutdoorunitwithitsairinlet
sidefacingthewall.• Topreventexposuretowind,itisrecommendedtoinstallabaffleboard
on the air outlet side of the outdoor unit.Avoidthefollowingplacesforinstallationwhereairconditionertroubleis liable to occur.• Whereflammablegascouldleak.• Wherethereismuchmachineoil.• Saltyplacessuchastheseaside.• Wheresulfidegasisgeneratedsuchashotspring,sewage,waste
water.• Wherethereishigh-frequencyorwirelessequipment.• WherethereisemissionofhighlevelsofVOCs,includingphthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
(Unit:mm(inch))
3. Obstacles in front (blowing) onlyWhen there is an obstacle in front of theunitasshowninthefigure,openspaceabove,behind,andonthesidesoftheunitisrequired.
2. Front (blowing) side openAs long as space indicatedin the figure is provided, itis allowed to install the unitwhere obstacles are behindand on the sides of the unit. (Noobstacleabovetheunit)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
500ormore
200ormore
350ormore100ormore
1. Obstacles aboveWhen there is no obstacle in front and onthesidesof theunit, it isallowedtoinstalltheunitwhereanobstacleisabovetheunitonlyifthespaceshowninthefigureisprovided.
100ormore
500ormore
100ormore
Servicespace
350ormore350ormore
6. Service spaceProvidespaceforserviceandmaintenanceasshowninthefigure.
500ormore
100ormore
• Wheninstallingtheunitinanareathatisenclosedwithwallssuchasaverandah,besuretohaveenoughspaceasshownbelow.
Inthiscase,theairconditioningcapacityandpowerconsumptionmight deteriorate.
• Whenthereisalackofairfloworthereisapossibilityofbecomingshortcycle,installanoutletguideandmakesurethereisenoughspacebehindoftheunit.
• Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontorbehind each other.
100ormore
200ormore
350ormore
500ormore 500ormore
(Unit:mm)
5. Obstacles in front, behind and on side(s)
4. Obstacles in front and behindThe unit can be used by at-tachinganoptionaloutdoorblowingguide(PAC-SH96SG-E)(butbothsidesandtopareopen).
100ormore
500ormore
Blowingguide(PAC-SH96SG-E)
Heightoftheobstacleis1200orless
BH79A274H01_en.indd 2 2016/03/23 10:42:15
En-3
1-5. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.
After the leak test, apply insulat-ing material tightly so that there isnogap.
ACCESSORIESCheckthefollowingpartsbeforeinstallation.(1) Drainsocket 1(2) Draincap 5
PARTS TO BE PROVIDED AT YOUR SITE(A) Powersupplycord* 1(B) Indoor/outdoorunitconnectingwire* 1(C) Extensionpipe 1(D) Wallholecover 1(E) Pipingtape 1
(F)Extension drain hose (orsoftPVChose,15mminnerdiameterorhardPVCpipeVP16)
1
(G) Refrigeration oil Little amount
(H) Putty 1(I) Pipefixingband 2to7(J) Fixingscrewfor(I) 2to7(K) Wallholesleeve 1
(L)SoftPVChose,15mminnerdiameterorhardPVCpipeVP16fordrainsocket(1)
1
* Note:Place indoor/outdoor unit connectingwire (B) andpowersupplycord(A)at least1maway fromtheTVantennawire.
The“Q’ty”for(B)to(K)intheabovetableisquantitytobeusedperindoorunit.
More than 100mm
OpenasaruleMorethan500mmif the front and both sidesareopen
Morethan100mmMorethan200mmifthereareobstacles to both sides
OpenasaruleMorethan500mmiftheback,bothsidesandtopareopen
Morethan350mm
Outdoor unit installation
Air inlet
Air outlet
Air inlet
950mm
600mm175mm
2-U-shapenotchedholes(BaseboltM10)
330mm
2-12mm×36mm ovalholes(BaseboltM10)
370mm
417mm
Whenthepipingistobeattachedtoawallcontainingmetals(tinplated)or metal netting, use a chemically treatedwooden piece 20mm orthicker between thewall and thepipingorwrap7to8turnsofinsula-tionvinyltapearoundthepiping.To use existing piping, performCOOL operation for 30minutesandpumpdownbefore removingtheoldairconditioner.Remakeflareaccordingtothedimensionfornewrefrigerant.
1-6. DRAIN PIPING FOR OUTDOOR UNIT1) Performthedrainpipingworkonlywhendrainingfromoneplace.2) Providedrainpipingbeforeindoorandoutdoorpipingconnection.3) Attachthedrainsockettooneoftheseveraldrainholes. Fixthedrainsocketintothedrainholeofthebaseusingthecatchestosecureitin
place.4) ConnectthesoftPVChoseI.D.15mmasshownintheillustration.5) Makesuretoprovidedrainpipingwithadownhillgradeforeasydrainflow.6) Gluethedraincapstoclosealltheotherunnecessaryholeswiththeglue(Prepare
inthefield).
Note:Applythegluesecurely,astheglue(Prepareinthefield)willworkassealtopreventwaterfromleaking.Usetheadhesivefortherubberandmetal.
AttentionTheoutdoorunit is providedwith several holes for drainageat thebottom tomakedrainage easier. Thedrainsocketisusedtoclosetheunnecessaryholesandcentralizethedrainagewhenusingthedraintubeattheinstallationplace.Donottousethedrainsocketincoldregion.Thedraintubecanbefrozen.
(1)Drainsocket(L)SoftPVChose
(2)Draincap
BH79A274H01_en.indd 3 2016/03/23 10:42:15
En-4
A B C
D E F
A B C
D E F
A B C
E F
A B C
D E F
A B C
D D E F
DRDRDRDRDRP P P P P
2-1. INSTALLING THE UNIT
FixherewithM10bolts.
Makethesettingdepthdeeper.
Makewidthwider.
Anchor leg
25orless
Anchor bolt length Anchorboltpitch
(Unit:mm)
2-2. CONNECTING WIRES FOR OUTDOOR UNIT Terminalblock forpowersupply
• Besuretofixtheunit’slegswithboltswheninstallingit.• Besuretoinstalltheunitfirmlytoensurethatitdoesnotfallbyanearthquakeoragust.• Refertothefigureintherightforconcretefoundation.• Donotusethedrainsocketandthedraincapsinthecoldregion. Drainmayfreezeanditmakesthefanstop.• Removethetapeonthepanelwhenopeningthepackage.(DONOTremovetheLABELSonthepanel.)
1)Removetheservicepanel.2)Loosenterminalscrew,andconnectindoor/outdoorunitconnectingwire
(B)fromtheindoorunitcorrectlyontheterminalblock.Becarefulnottomakemis-wiring.Fixthewiretotheterminalblocksecurelysothatnopartofitscoreisappeared,andnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock.
3)Firmlytightentheterminalscrewstopreventthemfromloosening.Aftertightening,pullthewireslightlytoconfirmthattheydonotmove.
4)Perform2)and3)foreachindoorunit.5)Connectpowersupplycord(A).6)Fixindoor/outdoorunitconnectingwire(B)andpowersupplycord(A)
withthecableclamps.7)Closetheservicepanelsecurely.Makesurethat3-2.PIPECONNEC-
TIONiscompleted.• Aftermakingconnectionsbetweenbothpowersupplycord(A)andindoor/outdoorunitconnectingwire(B),besuretofixbothcableandwirewithcableclamps.
Connectingorder• Connect the terminal block in
followingorder. A→B→C→D→E→F→P→DR
Terminalblockforindoor/outdoorunit
Cableclamps
600
370
Servicepanel Screws
Note:• Removingthehandleincreasestheeffectivenessofthewiringoperation.• Besuretoreinstallthehandle.
2. OUTDOOR UNIT INSTALLATION
Terminalblock forDREDInterface
DREDInterfacePowersupply
35mm15mm
Leadwire
• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthecordand/orthewiretotheterminalblock.
• Makeearthwirealittlelongerthanothers.(Morethan35mm)• Forfutureservicing,giveextralengthtothecon-
nectingwires.
1 2 3 C
<OUTDOORUNIT>
Indoor/outdoorunitconnectingwire
<INDOORUNIT>
Terminalblock
Terminalblock Terminalblock
TerminalblockforpowersupplyTerminalblock
<INDOORUNIT>
POWERSUPPLY~/N230V50Hz
ThisunithasdemandresponsecapabilitywhichiscompliantwithAS/NZS4755.3.1.Toactivatethisfunction,youneedtomakeacontractwithremoteagentssuchaselectricsupplycompany,thenthisunitshouldbeconnectedtoDemandresponseenablingdevise(DRED).Forfurtherinformation,consultyourdealer.Thisunitsupports3DemandResponseModes(DRMs):DRM1,DRM2andDRM3.
CAUTION
•Topreventmalfunctioncausedbynoise,routethecordconnectingthisunittoDREDandthepowersupplycordasparallelaspossible.•Donotconnectthedemandcontroltransmissioncabletotheterminalblockforpowersupply.•Donotpull,extremelybendorapplystrongpressureonthewiretopreventfailure.•DonotscrewDREDtooutdoorunit.•DonotputDREDinoutdoorunit.•Secureelectricalwiringaboveclamp.•DonotgetDREDwirecaughtintheservicepanel.
1:DRM12:DRM23:DRM3C:COMMON
AS/NZS4755terminalblock
BH79A274H01_en.indd 4 2016/03/23 10:42:17
En-5
Fig. 1 Fig.2
Fig.3 Fig.4
Fig.5 Fig.6
3-1. FLARING WORK
Pipediameter(mm)
Nut (mm)
A(mm) TighteningtorqueClutchtypetool forR410A
Clutchtypetool forR22
Wing nut typetool forR22
N•m kgf•cm
ø6.35(1/4”) 17
0to0.5 1.0to1.51.5to2.0
13.7to17.7 140to180ø9.52(3/8”) 22 34.3to41.2 350to420ø12.7(1/2”) 26
2.0to2.549.0to56.4 500to575
ø15.88(5/8”) 29 73.5to78.4 750to800
TiltedUnevenBurred
Good No good
Burr CopperpipeSparereamer
Pipecutter
Smooth all around
Evenlengthall around
Inside is shin-ingwithoutanyscratches.
Flare nut
DieCopperpipe
Clutchtype
Flaring tool
Wingnuttype
3-2. PIPE CONNECTION1)Applyathincoatofrefrigerationoil(G)totheflaredendsofthepipes
andthepipeconnectionsoftheoutdoorunit.Donotapplyrefrigerationoilonscrewthreads.Excessivetighteningtorquewillresultindamageonthescrew.
2)Alignthecenterofthepipewiththatofthepipeconnectionsoftheoutdoorunit,thenhandtightentheflarenut3to4turns.
3)Tightentheflarenutwithatorquewrenchasspecifiedinthetable.• Over-tighteningmaycausedamagetotheflarenut,resultinginrefriger-antleakage.
• Besuretowrapinsulationaroundthepiping.Directcontactwiththebarepipingmayresultinburnsorfrostbite.
3-3. INSULATION AND TAPING1)Coverpipingjointswithpipecover.2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoorunit.
• Stoptheendofpipingtape(E)withtape(withadhesiveagentattached).•Whenpipinghavetobearrangedthroughaboveceiling,closetorwherethetemperatureandhumidityarehigh,windadditionalcommerciallysoldinsulationtopreventcondensation.
Copperpipe
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Aimthecopperpipedownwardwhileremovingburrstopreventburrsfromdroppinginthepipe.
3)Removeflarenutsattachedtoindoorandoutdoorunits,thenputthemonpipehavingcompletedburrremoval.(Notpossibletoputthemonafterflaringwork.)
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshownin the table. Select A mm from the table according to the tool selected.
5)Check• ComparetheflaredworkwithFig.6.• Ifflareisnotedtobedefective,cutofftheflaredsectionanddoflaringworkagain.
WARNINGWhen installing the unit, securely connect the refrigerant pipes before starting the compressor.
CAUTIONWhen there are the ports which are not used, make sure their nuts are tightened securely.
4-1. PURGING PROCEDURES AND LEAK TEST1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunit
gaspipe.(Thestopvalvesarefullyclosedandcoveredincapsintheirinitialstate.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportofstopvalveonthegaspipesideoftheoutdoorunit.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)4)Checkthevacuumwithgaugemanifoldvalve,thenclosegaugemanifold
valve,andstopthevacuumpump.5)Leaveasitisforoneortwominutes.Makesurethepointerofgauge
manifoldvalveremainsinthesameposition.Confirmthatpressuregaugeshows-0.101MPa[Gauge](-760mmHg).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.7)Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.8)Referto1-2.,andchargetheprescribedamountofrefrigerantifneeded.
Besuretochargeslowlywithliquidrefrigerant.Otherwise,compositionoftherefrigerantinthesystemmaybechangedandaffectperformanceof the air conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.10)Leaktest
StopvalveforGAS
Gaugemani-foldvalve(forR410A)
Compoundpressuregauge(forR410A)–0.101MPa
(–760mmHg)
HandleLow HandleHigh
Vacuumpump(forR410A)
Chargehose(forR410A)
*Close*Open
Hexagonalwrench
*4to5turns
Stopvalve forLIQUID
Pressuregauge(forR410A)
Precautionswhenus-ingthecontrolvalve
Whenattachingthecontrolvalvetotheserviceport,valvecoremaydeformorloosenifexcesspres-sureisapplied.Thismaycausegasleak.
Serviceport
Chargehose(forR410A)
Body CloseOpen
ControlvalveA
Whenattachingthecontrolvalvetotheserviceport,makesurethatthevalvecoreisinclosedposition,andthen tightenpartA.Donot tightenpartAor turnthebodywhenvalvecoreisinopenposition.
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Stopvalvecap(Torque24.4to30.4N•m,250to310kgf•cm)
Serviceportcap(Torque10to12N•m,100to120kgf•cm)
Serviceportcap(Torque10to12N•m,100to120kgf•cm)
Stopvalvecap(Torque21.5to27.5N•m,220to280kgf•cm)
3. FLARING WORK AND PIPE CONNECTION
BH79A274H01_en.indd 5 2016/03/23 10:42:18
En-6
4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
4-2. GAS CHARGEPerformgaschargetounit.1)Connectgascylindertotheserviceportofstopvalve.2)Performairpurgeofthepipe(orhose)comingfromrefrigerantgascylinder.3)Replenishspecifiedamountoftherefrigerant,whileoperatingtheairconditioner
for cooling.
Note:Incaseofaddingrefrigerant,complywiththequantityspecifiedfortherefrigerat-ing cycle.
CAUTION:Whenchargingtherefrigerantsystemwithadditionalrefrigerant,besuretouseliquidrefrigerant.Addinggasrefrigerantmaychangethecompositionoftherefriger-antinthesystemandaffectnormaloperationoftheairconditioner.Also,chargetheliquidrefrigerantslowly,otherwisethecompressorwillbelocked.Tomaintain thehighpressureof thegas cylinder,warm thegas cylinderwithwarmwater(under40°C)duringcoldseason.Butneverusenakedfireorsteam.
COOL/DRY HEAT
• Descriptionofthefunction: With this function,once theoperationmode is locked toeitherCOOL/DRYmodeor
HEATmode,theairconditioneroperatesinthatmodeonly.* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunc-
tiontoyourcustomersandaskthemwhethertheywanttouseit.
[How to lock the operation mode]1)Besuretoturnoffthemainpowerfortheairconditionerbeforemakingthesetting.2)Setthe“3”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.3)TolocktheoperationmodeinCOOL/DRYmode,setthe“4”ofSW1ontheoutdoor
controllerboardtoOFF.TolocktheoperationinHEATmode,setthesameswitchtoON.
4)Turnonthemainpowerfortheairconditioner.
• Descriptionofthefunction: Withthisfunction,theoperatingnoiseoftheoutdoorunitcanbeloweredbyreducingtheoperationload,forexample,duringnighttimeinCOOLmode.
However,pleasenotethatthecoolingandheatingcapacitymaylowerifthisfunctionisactivated.* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
Union
Stopvalve
Liquidpipe
Indoor unit
Stopvalvewithserviceport Gas
pipe
Refrigerant gas cylinder operatingvalve(forR410A)
Gaugemanifoldvalve(forR410A)
Chargehose(forR410A)
RefrigerantgascylinderforR410Awithsiphon
Electronic scale for refrigerant charging
Refrigerant(liquid)
Outdoorunit
Union
Union
Union
SW1ON
1 2 3 4 5 6
SW1ON
1 2 3 4 5 6
SW1ON
1 2 3 4 5 6
Lowertheoperatingnoise
[How to lower the operating noise]1)Besure to turnoff themainpower for theairconditionerbeforemaking the
setting.2)Setthe“5”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.3)Turnonthemainpowerfortheairconditioner.
LEDSW1
SW871SW2
Terminalblock forDREDInterface
BH79A274H01_en.indd 6 2016/03/23 10:42:18
En-7
4-5. TEST RUN• Testrunsoftheindoorunitsshouldbeperformedindividually.Seetheinstallationmanualcomingwiththeindoorunit,andmakesurealltheunitsoperate
properly.• Ifthetestrunwithalltheunitsisperformedatonce,possibleerroneousconnectionsoftherefrigerantpipesandtheindoor/outdoorunitconnectingwires
cannotbedetected.Thus,besuretoperformthetestrunonebyone.
About the restart protective mechanismOncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner.
Wiring/piping correction functionThisunithasawiring/pipingcorrectionfunctionwhichcorrectswiringandpipingcombination.Whenthereispossibilityofincorrectwiringandpipingcombi-nation,andconfirmingthecombinationisdifficult,usethisfunctiontodetectandcorrectthecombinationbyfollowingtheproceduresbelow.
Makesurethatthefollowingisdone.• Powerissuppliedtotheunit.• Stopvalvesareopen.
Note:Duringdetection,theoperationoftheindoorunitiscontrolledbytheoutdoorunit.Duringdetection,theindoorunitautomaticallystopsoperation.Thisisnota malfunction.
ProcedurePressthepiping/wiringcorrectionswitch(SW871)1minuteormoreafterturningonthepowersupply.
• Correctioncompletesin10to20minutes.Whenthecorrectioniscompleted,itsresultisshownbyLEDindication.Detailsaredescribedinthefollowingtable.
• Tocancelthisfunctionduringitsoperation,pressthepiping/wiringcorrectionswitch(SW871)again.
• Whenthecorrectioncompletedwithouterror,donotpressthepiping/wiringcorrectionswitch(SW871)again.
When the resultwas “cannot be corrected”, press the piping/wiring correction switch(SW871)againtocancelthisfunction.Then,confirmthewiringandpipingcombinationinaconventionalmannerbyoperatingtheindoorunitsonebyone.
• Theoperationisdonewhilethepowerissupplied.Makesurenottocontactpartsotherthantheswitch,includingtheP.C.board.Thismaycauseelectricshockorburnbyhotpartsandlivepartsaroundtheswitch.ContactingthelivepartsmaycauseP.C.boarddamage.
• TopreventelectroniccontrolP.C.boarddamage,makesuretoperformstaticeliminationbeforeoperatingthisfunction.
• Thisfunctiondoesnotoperatewhentheoutsidetemperatureis0°Corbelow.
LED indication during detection:LED1(Red)
LED2(Yellow)
LED3(Green)
Lighted Lighted Once
Result of piping/wiring correction functionLED1(Red)
LED2(Yellow)
LED3(Green) Result
Lighted Not lighted LightedCompleted(Problemcorrectedornormal)
Once Once Once Notcompleted(Detectionfailed)
Otherindications
Referto“SAFETYPRE-CAUTIONSWHENLEDBLINKS”locatedbehindtheservicepanel.
4-6. EXPLANATION TO THE USER• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairfilters,
howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.).• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmosphere.1)Turnoffthebreaker.2)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.3)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.4)Turnonthebreaker.5)StarttheemergencyCOOLoperationonalltheindoorunits.6)Whenthepressuregaugeshows0–0.05MPa[Gauge](approx.0–0.5kgf/cm2),fullyclosethestopvalveonthegaspipesideoftheoutdoorunitand
stoptheoperation.(Refertotheindoorunitinstallationmanualaboutthemethodforstoppingtheoperation.) * Iftoomuchrefrigeranthasbeenaddedtotheairconditionersystem,thepressuremaynotdropto0–0.05MPa[Gauge](approx.0–0.5kgf/cm2),or
theprotectionfunctionmayoperateduetothepressureincreaseinthehigh-pressurerefrigerantcircuit.Ifthisoccurs,usearefrigerantcollectingdevicetocollectalloftherefrigerantinthesystem,andthenrechargethesystemwiththecorrectamountofrefrigerantaftertheindoorandoutdoorunitshavebeen relocated.
7)Turnoffthebreaker.Removethepressuregaugeandtherefrigerantpiping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
WARNING
5. PUMPING DOWN
BH79A274H01_en.indd 7 2016/03/23 10:42:18