14
Split System Heat Pump Product & Performance Data XL16i 4TWX6024,036,048 & 060A 2,3,4 & 5 Tons PUB. NO. 22-1754-05 SS-PRC007-EN

Split System Heat Pump Product & Performance Data · 2012. 3. 9. · Split System Heat Pump Product & Performance Data XL16i 4TWX6024,036,048 & 060A 2,3,4 & 5 Tons PUB. NO. 22-1754-05

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • Split SystemHeat Pump Product& Performance Data

    XL16i4TWX6024,036,048 & 060A

    2,3,4 & 5 Tons

    PUB. NO. 22-1754-05

    SS-PRC007-EN

  • © 2008 Trane 2 22-1754-05

    GeneralFeatures

    Split System Heat Pump Units . . .The Evolution ContinuesXL to XLi

    technology, and customer research todevelop the next generation of leadershipproducts.

    Couple the Trane reputation for reliabilityand durability with the above mentionedmission and accomplishments and youcontinue to have systems that prove“It’s Hard to Stop a Trane®. ”

    4TWX6 split systems represent a productthat is not only an engineer’s dream, it'salso a customer’s dream. The designteam’s mission and accomplishment isenhanced performance and efficiency,improved reliability and durability, andimproved installability and serviceability.

    Trane’s experienced design team applied“six sigma principles”, the latest computer

  • 22-1754-05 3

    Contents

    General Features 2

    Features and Benefits 4Optional Equipment 5Low Outdoor Ambient Cooling 5A.R.I. Standard Capacity Rating Conditions 5

    Selection Procedure 6Model Number Nomenclature 6

    General Data 74TWX6024A1000A 74TWX6036A1000A 84TWX6048A1000A 94TWX6060A1000A 10

    Electrical Data 11

    Dimensions 13

    Mechanical Specification Options 14

  • 4 22-1754-05

    Features andBenefits

    • Climatuff® staged scroll compressor

    • Efficiency up to 17.0 SEER and9.85 HSPF

    • All aluminum Spine Fin™ coil

    • WeatherGuard™ II top shields unit

    • DuraTuff™ base, fast complete drain,weather proof

    • WeatherGuard™ fasteners

    • XL Seacoast shield

    • Industry leading appearance

    • Tarpaulin gray cabinet withanthracite gray top

    • Low sound ratings

    • Compresssor sound insulator

    • Multi-stage fan for quiet operation

    • Quick-Sess™ cabinet, service accessand refrigerant connections with full coilprotection

    • Demand Defrost Control withDiagnostics

    • Glossy corrosion resistant finish

    • Internal high/low pressure &temperature protection

    • High pressure switch

    • All models have designed startability

    • 060 ship with start kit

    • Liquid line filter-drier

    • Comfort “R”™ mode approved

    • Easy single side service

    • Multi-use liquid and suction line servicevalves

    • Easy top & fan removal

    • Full length control and service valvecover

    • R-410A refrigerant

    • Compresssor sump heat

    • 10-year limited warranty oncompressor, coil, and internalfunctional parts (Residential only)

    • Extended warranties available

    • S.E.E.T. design testing

    • 100% line run test

    • Low ambient cooling to 40° F. withAY28X084, 30° F. with TXV

  • 22-1754-05 5

    Features andBenefits

    A.R.I. Standard Capacity Rating Conditions

    A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. airentering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoorcoil. (C) Low Temperature Heating 17°F. D.B., 15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Ratedindoor airflow for heating is the same as for cooling.

    A.R.I. STANDARD 270 RATING CONDITIONS — (Noise rating numbers are determined with the unit in cooling operation.)Standard Noise Rating number is at 95°F. outdoor air.

    Low Outdoor Ambient Cooling

    Low Ambient As EvaporatorCooling Manufactured Defrost ControlThermal Expansion Valve (TXV) 55°F 30°F

    Optional Equipment

    OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [✓✓✓✓✓] indicates accessories included).Indoor Thermostats — Elec. Setback Thermostat .................................................................................................. TAYSTAT500C [ ]

    Electronic, 3 Htg./2 Clg. (Non Prog.) ..................................................................................... TAYSTAT575 [ ]3/2 HP Stat Electro Mech. ........................................................................................................................................BAY28X153A [ ]Outdoor Thermostats 46°F. to – 10°F. (Adjustable) ................................................................................................. TAYSTAT250B [ ]Evaporator Defrost Control Kit ..................................................................................................................................... AY28X084 [ ]5 Minute Delay Relay 1 ........................................................................................................................................TAYASCT501A [ ]Outdoor Temperature Sensor (TAYSTAT500C) ...................................................................................................... TAYSENS100A [ ]Snow Legs – Base and Cap 4" High ....................................................................................................................... BAYLEGS002 [ ]Snow Legs – addition 4" extension (used with BAYLEGS002) ................................................................................ BAYLEGS003 [ ]Start Kit (2.5-4 ton models) ..................................................................................................................................... BAYKSKT260 [ ]Extreme Conditions Mounting Kit ........................................................................................................................... BAYECMT001 [ ]1 Do not use with programmable thermostats

    BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)1/2" ODM (90° bend, one end), 1/2" and 1/4" tubing ............................................................................................ TAYREFLN5__* [ ]5/8" ODM (90° bend, one end), 5/8" and 5/16" tubing .......................................................................................... TAYREFLN6__* [ ]3/4" ODM (90° bend, one end), 3/4" and 3/8" tubing ............................................................................................ TAYREFLN7__* [ ]3/4" ODM (90° bend, one end), 3/4" and 5/16" tubing .......................................................................................... TAYREFLN2__* [ ]7/8" ODM (90° bend, one end), 7/8" and 3/8" tubing ............................................................................................ TAYREFLN3__* [ ]* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.

    Example: TAYREFLN220

  • 6 22-1754-05

    Refrigerant Type2 = R-224 = R-410A

    TRANE

    Product TypeW = Split Heat PumpT = Split Cooling

    Product FamilyZ = LEADERSHIP - 2 STAGEX = LEADERSHIPR = REPLACEMENT / RETAILB = BASICA = LIGHT COMMERCIAL

    Family SEER0 =̃ 10 2 =̃ 12 4 =̃ 141 =̃ 11 3 =̃ 13 6 =̃ 16 8 =̃ 18

    Unit PartsIdentifier

    Minor DesignModifications

    SecondaryFunction

    Power Supply1 = 200 - 230 / 1 / 60 or 208 - 230 / 1 / 603 = 200 - 230 / 3 / 604 = 460 / 3 / 60

    Major Design Modifications

    Nominal Capacity in 000’s of BTU’s

    Split System Connections 1 - 6 Tons0 = Brazed

    1 2 3 4 5 6 7 8 9 1 0 11 1 2 1 3 1 4 1 5

    4 T W X 6 0 3 6 A 1 0 0 0 A A

    SelectionProcedure

    Model Number Nomenclature

  • 22-1754-05 7

    OUTDOOR UNIT 12 4TWX6024A1000ASOUND RATING (DECIBELS) 2 77POWER CONNS. — V/PH/HZ 3 230/1/60MIN. BRCH. CIR. AMPACITY 13BR. CIR. MAX. (AMPS) 20PROT. RTG. } MIN. (AMPS) 20COMPRESSOR CLIMATUFF® - SCROLLNO. USED - NO. SPEEDS 1 - 2VOLTS/PH/HZ 230/1/60R.L. AMPS 7 - L.R. AMPS 10.3 - 52FACTORY INSTALLED

    START COMPONENTS 8 NOINSULATION/SOUND BLANKET YESCOMPRESSOR HEAT YES

    OUTDOOR FAN — TYPE PROPELLERDIA. (IN.) - NO. USED 23 - 1TYPE DRIVE - NO. SPEEDS DIRECT - 2CFM @ 0.0 IN. W.G. 4 2700NO. MOTORS - HP. 1 - 1/15MOTOR SPEED R.P.M. 825VOLTS/PH/HZ 200/230/1/60F.L. AMPS 0.60OUTDOOR COIL — TYPE SPINE FIN™ROWS - F.P.I. 1 - 24FACE AREA (SQ. FT.) 21.20TUBE SIZE (IN.) 5/16REFRIGERANT CONTROL EXPANSION VALVEREFRIGERANT R-410A(O.D. UNIT) NP CHRG. 5 5/12-LB/OZFACTORY SUPPLIED YESLINE SIZE - IN. O.D. GAS 6 5/8LINE SIZE - IN. O.D. LIQ. 6 5/16FCCVRESTRICTOR ORIFICE SIZE N/ADIMENSIONS H X W X DOUTDOOR UNIT CRATED (IN.) 47.6 X 30.1 X 33UNCRATED SEE OUTLINE DWG.WEIGHTSHIPPING (LBS.) 266NET (LBS.) 229

    GeneralData 4TWX6024A1000A

    1 CERTIFIED IN ACCORDANCE WITH THE AIR-SOURCE UNITARYHEAT PUMP EQUIPMENT CERTIFICATION PROGRAM, WHICH ISBASED ON A.R.I. STANDARD 210/240.

    2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.

    ONLY USE HACR CIRCUIT BREAKERS OR FUSES.4 STANDARD AIR - DRY COIL - OUTDOOR5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT

    NAMEPLATE AND SERVICE INSTRUCTION.6 MAX. LINEAR LENGTH: 80 FT. MAX. LIFT - SUCTION 25 FT; MAX LIFT -

    LIQUID 25 FT. FOR GREATER LENGTH REFER TO REFRIGERANTPIPING SOFTWARE PUB. NO. 32-3312-01.

    7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNITNAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TOCOMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUMFUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUITSELECTION CURRENT.

    8 NO MEANS NO START COMPONENTSYES MEANS QUICK START KIT COMPONENTSPTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

    SPLIT SYSTEM

  • 8 22-1754-05

    OUTDOOR UNIT 12 4TWX6036A1000ASOUND RATING (DECIBELS) 2 77POWER CONNS. — V/PH/HZ 3 230/1/60MIN. BRCH. CIR. AMPACITY 24BR. CIR. MAX. (AMPS) 40PROT. RTG. } MIN. (AMPS) 40COMPRESSOR CLIMATUFF® - SCROLLNO. USED - NO. SPEEDS 1 - 2VOLTS/PH/HZ 230/1/60R.L. AMPS 7 - L.R. AMPS 16.7 - 82FACTORY INSTALLED

    START COMPONENTS 8 NOINSULATION/SOUND BLANKET YESCOMPRESSOR HEAT YES

    OUTDOOR FAN — TYPE PROPELLERDIA. (IN.) - NO. USED 27.6 - 1TYPE DRIVE - NO. SPEEDS DIRECT - 2CFM @ 0.0 IN. W.G. 4 3975NO. MOTORS - HP. 1 - 1/3MOTOR SPEED R.P.M. 660VOLTS/PH/HZ 200/230/1/60F.L. AMPS 2.80OUTDOOR COIL — TYPE SPINE FIN™ROWS - F.P.I. 1 - 24FACE AREA (SQ. FT.) 24.88TUBE SIZE (IN.) 5/16REFRIGERANT CONTROL EXPANSION VALVEREFRIGERANT R-410A(O.D. UNIT) NP CHRG. 5 8/04-LB/OZFACTORY SUPPLIED YESLINE SIZE - IN. O.D. GAS 6 3/4LINE SIZE - IN. O.D. LIQ. 6 3/8FCCVRESTRICTOR ORIFICE SIZE N/ADIMENSIONS H X W X DOUTDOOR UNIT CRATED (IN.) 46.4 X 35.1 X 38.7UNCRATED SEE OUTLINE DWG.WEIGHTSHIPPING (LBS.) 300NET (LBS.) 253

    4TWX6036A1000AGeneralData

    1 CERTIFIED IN ACCORDANCE WITH THE AIR-SOURCE UNITARYHEAT PUMP EQUIPMENT CERTIFICATION PROGRAM, WHICH ISBASED ON A.R.I. STANDARD 210/240.

    2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.

    ONLY USE HACR CIRCUIT BREAKERS OR FUSES.4 STANDARD AIR - DRY COIL - OUTDOOR5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT

    NAMEPLATE AND SERVICE INSTRUCTION.6 MAX. LINEAR LENGTH: 80 FT. MAX. LIFT - SUCTION 25 FT; MAX LIFT -

    LIQUID 25 FT. FOR GREATER LENGTH REFER TO REFRIGERANTPIPING SOFTWARE PUB. NO. 32-3312-01.

    7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNITNAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TOCOMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUMFUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUITSELECTION CURRENT.

    8 NO MEANS NO START COMPONENTSYES MEANS QUICK START KIT COMPONENTSPTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

    SPLIT SYSTEM

  • 22-1754-05 9

    GeneralData 4TWX6048A1000A

    OUTDOOR UNIT 12 4TWX6048A1000ASOUND RATING (DECIBELS) 2 78POWER CONNS. — V/PH/HZ 3 230/1/60MIN. BRCH. CIR. AMPACITY 29BR. CIR. MAX. (AMPS) 50PROT. RTG. } MIN. (AMPS) 50COMPRESSOR CLIMATUFF® - SCROLLNO. USED - NO. SPEEDS 1 - 2VOLTS/PH/HZ 230/1/60R.L. AMPS 7 - L.R. AMPS 21.2 - 96FACTORY INSTALLED

    START COMPONENTS 8 NOINSULATION/SOUND BLANKET YESCOMPRESSOR HEAT YES

    OUTDOOR FAN — TYPE PROPELLERDIA. (IN.) - NO. USED 27.6 - 1TYPE DRIVE - NO. SPEEDS DIRECT - 2CFM @ 0.0 IN. W.G. 4 4200NO. MOTORS - HP. 1 - 1/3MOTOR SPEED R.P.M. 660VOLTS/PH/HZ 200/230/1/60F.L. AMPS 2.80OUTDOOR COIL — TYPE SPINE FIN™ROWS - F.P.I. 1 - 24FACE AREA (SQ. FT.) 27.81TUBE SIZE (IN.) 5/16REFRIGERANT CONTROL EXPANSION VALVEREFRIGERANT R-410A(O.D. UNIT) NP CHRG. 5 9/01-LB/OZFACTORY SUPPLIED YESLINE SIZE - IN. O.D. GAS 6 7/8LINE SIZE - IN. O.D. LIQ. 6 3/8FCCVRESTRICTOR ORIFICE SIZE N/ADIMENSIONS H X W X DOUTDOOR UNIT CRATED (IN.) 53.4 X 35.1 X 38.7UNCRATED SEE OUTLINE DWG.WEIGHTSHIPPING (LBS.) 322NET (LBS.) 274

    1 CERTIFIED IN ACCORDANCE WITH THE AIR-SOURCE UNITARYHEAT PUMP EQUIPMENT CERTIFICATION PROGRAM, WHICH ISBASED ON A.R.I. STANDARD 210/240.

    2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.

    ONLY USE HACR CIRCUIT BREAKERS OR FUSES.4 STANDARD AIR - DRY COIL - OUTDOOR5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT

    NAMEPLATE AND SERVICE INSTRUCTION.6 MAX. LINEAR LENGTH: 80 FT. MAX. LIFT - SUCTION 25 FT; MAX LIFT -

    LIQUID 25 FT. FOR GREATER LENGTH REFER TO REFRIGERANTPIPING SOFTWARE PUB. NO. 32-3312-01.

    7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNITNAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TOCOMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUMFUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUITSELECTION CURRENT.

    8 NO MEANS NO START COMPONENTSYES MEANS QUICK START KIT COMPONENTSPTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

    SPLIT SYSTEM

  • 10 22-1754-05

    GeneralData 4TWX6060A1000A

    OUTDOOR UNIT 12 4TWX6060A1000ASOUND RATING (DECIBELS) 2 79POWER CONNS. — V/PH/HZ 3 230/1/60MIN. BRCH. CIR. AMPACITY 35BR. CIR. MAX. (AMPS) 60PROT. RTG. } MIN. (AMPS) 60COMPRESSOR CLIMATUFF® - SCROLLNO. USED - NO. SPEEDS 1 - 2VOLTS/PH/HZ 230/1/60R.L. AMPS 7 - L.R. AMPS 25.6 - 118FACTORY INSTALLED

    START COMPONENTS 8 YESINSULATION/SOUND BLANKET YESCOMPRESSOR HEAT YES

    OUTDOOR FAN — TYPE PROPELLERDIA. (IN.) - NO. USED 27.6 - 1TYPE DRIVE - NO. SPEEDS DIRECT - 2CFM @ 0.0 IN. W.G. 4 4400NO. MOTORS - HP. 1 - 1/3MOTOR SPEED R.P.M. 660VOLTS/PH/HZ 200/230/1/60F.L. AMPS 2.80OUTDOOR COIL — TYPE SPINE FIN™ROWS - F.P.I. 2 - 24FACE AREA (SQ. FT.) 26.32TUBE SIZE (IN.) 5/16REFRIGERANT CONTROL EXPANSION VALVEREFRIGERANT R-410A(O.D. UNIT) NP CHRG. 5 11/03-LB/OZFACTORY SUPPLIED YESLINE SIZE - IN. O.D. GAS 6 7/8LINE SIZE - IN. O.D. LIQ. 6 3/8FCCVRESTRICTOR ORIFICE SIZE N/ADIMENSIONS H X W X DOUTDOOR UNIT CRATED (IN.) 53.4 X 35.1 X 38.7UNCRATED SEE OUTLINE DWG.WEIGHTSHIPPING (LBS.) 360NET (LBS.) 312

    1 CERTIFIED IN ACCORDANCE WITH THE AIR-SOURCE UNITARYHEAT PUMP EQUIPMENT CERTIFICATION PROGRAM, WHICH ISBASED ON A.R.I. STANDARD 210/240.

    2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270/SECTION 5.3.6.3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.

    ONLY USE HACR CIRCUIT BREAKERS OR FUSES.4 STANDARD AIR - DRY COIL - OUTDOOR5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT

    NAMEPLATE AND SERVICE INSTRUCTION.6 MAX. LINEAR LENGTH: 80 FT. MAX. LIFT - SUCTION 25 FT; MAX LIFT -

    LIQUID 25 FT. FOR GREATER LENGTH REFER TO REFRIGERANTPIPING SOFTWARE PUB. NO. 32-3312-01.

    7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNITNAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TOCOMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUMFUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUITSELECTION CURRENT.

    8 NO MEANS NO START COMPONENTSYES MEANS QUICK START KIT COMPONENTSPTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

    SPLIT SYSTEM

  • 22-1754-05 11

    4TWX6024A 4TWX6036A

    ElectricalData

    Schematic Diagrams(SEE LEGEND)

  • 12 22-1754-05

    ElectricalData

    4TWX6048A

    Schematic Diagrams

    4TWX6060A

  • 22-1754-05 13

    Dimensions

    4TWX6 Outline DrawingNOTE: ALL DIMENSIONS ARE IN MM (INCHES)

    From Dwg. 21D152635 Rev. 10

    MODELS BASE A B C D E F G H J K

    4TWX6024A 3 1118 (44) 829 (32-5/8) 756 (29-3/4) 5/8 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 692 (27-1/4)

    4TWX6036A 4 1165 (45-7/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)

    4TWX6048A 4 1267 (49-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)

    4TWX6060A 4 1267 (49-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)

    LEGEND

    SYMBOLS

  • Literature Order Number

    File Number

    Supersedes

    Stocking Location 06/08

    Trane has a policy of continuous product and product data improvement and it reserves the right to changedesign and specifications without notice.

    Tranewww.trane.com

    MechanicalSpecification Options

    GeneralThe 4TWX60 is fully charged from thefactory for up to 15 feet of piping. Thisunit is designed to operate at outdoorambient temperatures as high as 115°F.Cooling capacities are matched with awide selection of air handlers andfurnace coils that are A.R.I. certified. Theunit is UL listed. Exterior is designed foroutdoor application.

    CasingUnit casing is constructed of heavygauge, G90 galvanized steel and paintedwith a weather-resistant powder painton all louvered panels, prepaint on allother panels. Corrosion and weather-proof CMBP-G30 Duratuff™ base.

    Refrigerant ControlsRefrigeration system controls includecondenser fan, compressor contactorand high pressure switch. High and lowpressure controls are inherent to thecompressor. A factory installed liquid linedrier is standard.

    CompressorThe Climatuff® compressor features a10 year limited warranty, internal overtemperature and pressure protectionand total dipped hermetic motor. Otherfeatures include: roto lock suction anddischarge refrigerant connections,centrifugal oil pump and low vibrationand noise.

    Condenser CoilThe outdoor coil provides low airflowresistance and efficient heat transfer.The coil is protected on all four sides bylouvered panels and has a 10 yearlimited warranty.

    Low Ambient CoolingAs manufactured, this unit has a coolingcapability to 55°F. The addition of anevaporator defrost control permitsoperation to 40° F. The addition of anevaporator defrost control with TXVpermits low ambient cooling to 30° F.

    AccessoriesThermostats — Cooling only andheat/cooling (manual and automaticchangeover). Sub-base to match thermo-stat and locking thermostat cover.

    Evaporator Defrost Control — See LowAmbient Cooling.