SPIDERS Phase II Technical Report

Dave Barr, P.E. Eric Putnam, P.E.

Page 2: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Definition

The U.S. Department of Energy’s official definition of a microgrid is “a group of

interconnected loads and distributed energy resources within clearly defined electrical

boundaries that acts as a single controllable entity with respect to the grid [and can] connect and disconnect from the grid to

enable it to operate in both grid-connected or island-mode.”

Page 3: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Definition

The U.S. Department of Energy’s official definition of a microgrid is “a group of

interconnected loads and distributed energy resources within clearly defined electrical

boundaries that acts as a single controllable entity with respect to the grid [and can] connect and disconnect from the grid to

enable it to operate in both grid-connected or island-mode.”

Page 4: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

One Name but Many Forms

• Centralized Generation • Distributed Generation • Highly Renewable Focused / Net Zero

Page 5: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Common Features

• Decoupling of Generators from Loads • Seamless Transitions to/from Utility • Increased Redundancy of Generation

Page 6: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Common Benefits

• Increased Situational Awareness for Operators

• Increased Automation of Distribution • Integration of Renewable Resources for

Backup Power • Multiple Modes of Operation Both Islanded

and Grid-Tied

Page 7: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

What Microgrids are Not

• Uninterruptible Power Supplies (UPS) • Controls Only Solutions • Out-of-the-box Solutions • Sources of Revenue (by themselves)

Page 8: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Page 9: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Distributed Approach

• Any Power Source Can be a SPIDERS Generator

• Controls are Distributed to Match Generators and Loads

• Dynamic Electrical Topology Responds to System Events

Page 10: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS JCTD Objectives

Provide a Cyber-Secure Microgrid for Enhanced Mission Assurance

• Increase reliability of backup generation • Reduce fossil fuel consumption of

generators through renewable integration • Increase efficiency of generators • Reduce operational risk through cyber

secure control systems

Page 11: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS Multiphase Approach

CAMP SMITH ENERGY ISLAND

• Entire Installation

Smart Micro-Grid • Distributed

Renewables • Blinkless Transfer of

Buildings on Loss of Utility

• Load Curtailment • ROI-Focused

Approach

PEARL-HICKAM CIRCUIT LVL DEMO

• Single, 15kV Distribution

Circuit • Two Critical Loads • Renewable Power Island

FT CARSON MICRO-GRID

• Three, 15kV Distribution Circuits

• Relatively Large PV Source

• Bi-Directional EV Charging Stations

• Peak Shaving • PF Correction

HIGHLY SENSITIVE CRITICAL LOADS

TRANSITION • Template for DoD-

wide implementation • New Uniform Facility

Criteria (UFC) • CONOPS • TTPs • Training Plans • Transition to Electric

Utility Sector • Transition Cyber-

Security

Phase 1

Phase 2

Phase 3

UTILITY ANCILLARY SERVICES

Page 12: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Purpose of SPIDERS • More Efficient Operation of Diesel Generators

– Supply critical load using fewer generators – Online generators operate at more efficient point

• Ability to Integrate Renewable Resources – Microgrid provides a “grid source” to allow UL compliant equipment to

operate – Power from renewables further reduces consumption of diesel fuel

• Increased Redundancy for Critical Systems – Generators can serve any load in microgrid

• Implement Cyber Security for Microgrid Command and Control – Microgrids must be less vulnerable than the utility grid to cyber attacks – Control network must be responsive to rapidly changing electrical

system • Minimize Changes to Existing Infrastructure

– In order to maximize effectiveness of SPIDERS program, it must be implemented at existing facilities – not just new ones

– Utilizing existing infrastructure increases reliability and maintainability of systems

INCREASE RELIABILITY

& REDUCE DIESEL FUEL

CONSUMPTION

Page 13: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Performance Optimization

0.2

0.4

0.6

0.8

1

1.2

1.4

0

100

200

300

400

500

600

Fuel

Con

sum

ptio

n (g

al/m

)

Pow

er (k

W)

Typical Microgrid Power and Fuel Consumption

PV Output

WWTP Total Load

Traditional FuelConsumptionSPIDERS FuelConsumption

Fuel savings due to generator optimization

Fuel savings due to PV integration

Page 14: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Repurpose Existing Assets • Reduced Cost • Utilize Otherwise Stranded Assets • Minimize Downtime of Existing Facilities

Flexibility in Usage

• Fully Functional Fail Safe Mode (Do No Harm) • Satisfy Life Safety Codes • Facilitate Improved Testing and Maintenance

SPIDERS Value Proposition

Page 15: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Cyber Secure Controls • Dramatically Increase Situational Awareness • Isolated Network with Multiple Enclaves • Distributed Controls Philosophy

COTS-Based Solution

• Adaptable to Each Site’s Unique Requirements • Facilitate Maintenance

SPIDERS Value Proposition

Page 16: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS Breaker

• Existing 15kV Distribution System Used for Connecting Generators and Loads

• Generators Directly Connected to the 480V Side of the Building Transformers Using Bypass Breakers

• Automatic Synchronizers Permit Paralleled Operation to Other Generators or Utility

Page 17: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS Phase II

Page 18: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS Phase II

• Three Microgrid Diesel Generators (3MW total)

• 1MW Segment of PV Array • Five Bi-Directional Hi-Speed Electric

Vehicle Charging Stations (300kW / 400kWh total)

Page 19: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

15kV Synchronizing Breaker

• Allows Seamless Transition to Utility • New Sectionalizing Point within Circuit • Seamless Transitions are Critical During

Testing of System

Page 20: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

15kV Sectionalizing Switch

• Replaced Existing Manual Switches with Motor Operated Models

• Workhorse of Microgrid • Allows for Dynamic Electrical Topology

Page 21: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

SPIDERS Breaker

• Provides Pathway for Generator to Feed Microgrid

• Switchboard Design for Compactness • Schweitzer Relay Backing Up Typical

Electronic Trip Unit

Page 22: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

PV Array

• 2MW Array with Four, 500kW Inverters • Electrically Divided in Half • Third-Party Owned & Operated

Page 23: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

EV Charging Stations

• Five, 100kVA Stations • Four Quadrant Control Permits VAR

Support of Utility or Microgrid Even Without Vehicles

• Aggregator Allows Smart Charging of Fleet Based on Utility and Functional Requirements

Page 24: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

PV Array

Distribution Line

Phase II Microgrid

Page 25: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Normal Operation

D

G

G PV

B C

B C

D E F

A

Page 26: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Utility Failure

D

G

G PV

B C

B C

D E F

A

Page 27: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Microgrid Forms

D

G

G PV

B C

B C

D E F

A

Page 28: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Microgrid Forms (Step 2)

D

G

G PV

B C

B C

D E F

A

Page 29: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Microgrid Forms (Step 3)

D

G

G PV

B C

B C

D E F

A

Page 30: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Microgrid Fully Formed

D

G

G PV

B C

B C

D E F

A

Page 31: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Generator Optimization

D

G

G PV

B C

B C

D E F

A

Page 32: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Seamless Return to Utility

D

G

G PV

B C

B C

D E F

A

Page 33: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Normal Operation

D

G

G PV

B C

B C

D E F

A

Page 34: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Microgrid Differences

D

G

G PV

B C

B C

D E F

A

Increased Redundancy Power Without Local Generator Increased Redundancy and Full Building Power Generator Shut Down in Microgrid Mode Renewable Power Available

Page 35: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Page 36: SPIDERS Phase II Technical Report - Energy.gov...SPIDERS Phase II Technical Report Subject This presentation includes information on Phase II of SPIDERS and DOD involvement with microgrids

®

Questions?