© 2006 Rosemount Inc. All rights reserved For more information: www.rosemount.com TECHNICAL NOTE Specify the Right Solution for Vacuum Applications KEY POINTS Specify a high temperature fill fluid (DC704) Specify All-Welded Vacuum Construction for vacuums below 6 psia (300 mmHgA) Mount transmitter at or below the lower tap (3 feet or 1 meter is rule of thumb) Use Instrument Toolkit ® software to validate system in your application OVERVIEW When a vessel is under a vacuum pressure, it is important to specify the correct transmitter remote seal system to measure level accurately and reliably. Failure to do so will result in output drift or complete system failure. The combination of high process temperature and vacuum process pressure conditions creates additional requirements when specifying the transmitter remote seal system. APPLICATION There are three primary transmitter-seal system components necessary to successfully specify vacuum application solutions: Mounting Position Fill Fluid Selection Seal System Construction Mounting Position Mounting the pressure transmitter at or below the bottom vessel tap is an important factor to ensure a stable measurement with vacuum applications. The static pressure limit for a differential pressure transmitter is 0.5 psia (25 mmHgA), which ensures the transmitter sensor module fill fluid typically (DC200) remains within the liquid phase of the vapor pressure curve. If the vessel static limit is below 0.5 psia, mounting the transmitter below the bottom tap provides a capillary fill fluid head pressure on the module. A general rule of thumb is to always mount the transmitter approximately 3 feet (1 meter) below the bottom tap of the vessel. The actual head pressure can be calculated by multiplying the vertical distance between the bottom tap and transmitter by the specific gravity of the fill fluid. Finally, validate the system in your application using Instrument Toolkit Software to ensure the system will perform under your operating conditions.

Specify the Right Solution for Vacuum Applications

Embed Size (px)

DESCRIPTION

Specify the Right Solution for Vacuum Applications

Citation preview

TECHNICAL NOTE

Specify the Right Solution for Vacuum Applications

KEY POINTS

• Specify a high temperature fill fluid (DC704)

• Specify All-Welded Vacuum Construction for vacuums below 6 psia (300 mmHgA)

• Mount transmitter at or below the lower tap (3 feet or 1 meter is rule of thumb)

• Use Instrument Toolkit® software to validate system in your application

OVERVIEWWhen a vessel is under a vacuum pressure, it is important to specify the correct transmitter remote seal system to measure level accurately and reliably. Failure to do so will result in output drift or complete system failure. The combination of high process temperature and vacuum process pressure conditions creates additional requirements when specifying the transmitter remote seal system.

APPLICATIONThere are three primary transmitter-seal system components necessary to successfully specify vacuum application solutions:

• Mounting Position

• Fill Fluid Selection

• Seal System Construction

Mounting PositionMounting the pressure transmitter at or below the bottom vessel tap is an important factor to ensure a stable measurement with vacuum applications. The static pressure limit for a differential pressure transmitter is 0.5 psia (25 mmHgA), which ensures the transmitter sensor module fill fluid typically (DC200) remains within the liquid phase of the vapor pressure curve.

If the vessel static limit is below 0.5 psia, mounting the transmitter below the bottom tap provides a capillary fill fluid head pressure on the module. A general rule of thumb is to always mount the transmitter approximately 3 feet (1 meter) below the bottom tap of the vessel. The actual head pressure can be calculated by multiplying the vertical distance between the bottom tap and transmitter by the specific gravity of the fill fluid. Finally, validate the system in your application using Instrument Toolkit Software to ensure the system will perform under your operating conditions.

© 2006 Rosemount Inc. All rights reserved

For more information: www.rosemount.com

TECHNICAL NOTE

l Fluid Specifications Technical Note, document

um Temperature at ATM Pressure

49°F (–45°C) to 400°F (205°C)

32°F (0°C) to 600°F (315°C)

68°F (20°C) to 662°F (350°C)

Fill Fluid SelectionWhen the process is under vacuum conditions, the fill fluid will vaporize under a lower temperature than when it is under normal atmospheric or greater pressure. Emerson Process Management offers over 16 different types of fill fluids for filled systems. Each fill fluid has a specific Vapor-Pressure curve. The Vapor-Pressure curve indicates the pressure and temperature relationship where the fluid is in a liquid or a vapor state. Proper seal operation requires the fill fluid to remain in a liquid state. For vacuum applications, specify fluids with a premium combination of vapor-pressure curve and high temperature limits like DC704 or DC705.

TABLE 1. Temperature Limits(1)

(1) Vapor pressure curve and operating limit details for published fill fluids can be found in the Rosemount 1199 Fil00840-2100-4016.

Fill Fluid Maximum Temperature at Minimum Pressure Maxim

D.C.®

200 Silicone 257°F (125°C) @ 25 mmHgA –

D.C. 704 Silicone(2)

(2) Upper temperature limit is for capillary seal systems mounted away from the transmitter.

See vapor pressure curve

D.C. 705 Silicone(2) See vapor pressure curve

00840-0100-4016, Rev AA

For more information: www.rosemount.com

TECHNICAL NOTE

Seal System ConstructionEmerson offers Rosemount 1199 seals with welded-repairable and All-Welded vacuum system construction methods. In vacuum applications, specify the All-Welded vacuum construction. Threaded or gasket connections allow the potential for vacuum pressure to draw air into the capillary system causing drift or complete system failure. No air in the system eliminates the need to re-zero and thus improves plant availability by preventing unscheduled downtime and instrument repair or replacement.

The all welded vacuum construction was designed specifically for high temperature and vacuum applications. In this construction, the sensor module gaskets are removed and a disk is welded over the sensor isolators. This eliminates the possibility of air being drawn into the seal system in deep vacuum conditions. This premium design is strongly suggested for vacuum pressures below 6 psia (310 mmHga).

Remote seal system construction model codes can be found in the Rosemount 1199 Diaphragm Seal System Product Data Sheet (00813-0100-4016, Tables 4, 5, and 50). Furthermore, Rosemount has improved the manufacturing processes for remote seals used for high temperature/high vacuum applications.

00840-0100-4016, Rev AA

TECHNICAL NOTE

Fill Fluid PreparationThe fill fluids used in remote seal systems were developed for other applications, then adapted for use in seal systems. For example, DC704 was developed to be a heat transfer fluid in diffusion pumps for high vacuum chambers common in semiconductor manufacturing. When applied into a remote seal system, Rosemount has implemented the further preparation to purify the fluid and remove residual entrapped air or water to ensure a stable measurement performance under extreme vacuum conditions.

System Components PreconditionedTo ensure long term reliability, manufacturing process improvements were implemented to prepare the seal system for high temperature and vacuum conditions. System components are preconditioned at high temperatures and vacuum pressures to prepare them for the end use.

Stringent Manufacturing ProcessesThe equipment and procedures used to build remote seal systems for high temperature/high vacuum applications are continuously improved to deliver products for ever increasing application demands. Tight quality control measures like 100% helium leak checking of system welds ensures the reliability of every seal system. The process includes monitoring to detect any station leaks and to confirm the fill quality of the finished seal system.

SummaryImplementing the right combination of seal system construction, fill fluid, and mounting position can ensure long term stable measurement performance for high temperature and vacuum applications. If you have questions on a vacuum installation, contact your local Emerson Process Management representative for application assistance.

Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.All other marks are the property of their respective owners.

Emerson Process Management Heath PlaceBognor RegisWest Sussex PO22 9SHEnglandT 44 (0) 1243 863121F 44 (0) 1243 867554

Emerson Process ManagementEmerson Process Management Asia Pacific Private Limited1 Pandan CrescentSingapore 128461T (65) 6777 8211F (65) 6777 [email protected]

Emerson Process ManagementRosemount Division8200 Market BoulevardChanhassen, MN 55317 USAT (U.S.) 1-800-999-9307T (International) (952) 906-8888F (952) 949-7001www.rosemount.com

00840-0100-4016, Rev AA

For more information: www.rosemount.com