    CONLIT 150 STRUCTURAL STEEL FIRE PROTECTION

    TECHNICAL SPECIFICATION

    DESCRIPTION The Conlit 150 supplied by Wilhams Insulation Far East Sdn Bhd, must have a proven track record of use for a minimum of 5 years. It shall be manufactured from a non combustible mineral fibre and formed into a slab, the outer face being foiled, acting as fire, thermal and acoustic insulation. All joints must be jointed in accordance with the manufacturers installation instructions and conform to the specifications below:- REFERENCE DOCUMENTATION

    1. The use of structural steel in buildings. Part 2. Metric units. British Standard 449 : Part 2 : 1969. British Standards Institution, London, 1969.

    2. Fire tests on building materials and structures. Part 8. Test methods and

    criteria for the fire resistance of elements of construction. British Standard 476: Part 8 : 1972. British Standards Institution, London, 1972.

    3. Fire protection of structural steel in buildings (2nd Edition - revised).

    Association of Specialist Fire Protection Contractors and Manufacturers Limited, 1992.

    4. Loss Prevention Standard LPS 1107. Requirements, Tests and Methods

    of Assessment of Passive Fire Protection Systems for Structural Steelwork. Loss Prevention Council, 1987.

    5. Fire tests on building materials and structures. Part 21. Method for

    determination of the fire resistance of load bearing elements of construction. British Standard 476 : Part 21 : 1987. British Standards Institution, London, 1987.

    6. Structural use of steelwork in buildings. Part 8. Code of practice for fire

    resistant design. British Standard 5950 : Part 8 : 1990. British Standards Institution, London, 1990.

    FIRE TEST PERFORMANCE The structural steel fire protection system shall comply with all applicable life safety, building, and fire ratings of Thailands Fire Authority and be tested and assessed to the following:-

  • WILHAMS INSULATION FAR EAST SDN BHD (340166M)

    Page2 Wilhams Insulation Far East Sdn Bhd tel.00-6-03-78466728 15 & 17 Jalan U5/23, Seksyen U5 fax.00-6-03-78466540 Mah Sing Integrated Industrial Park E-mail : [email protected] 40150 Shah Alam, Selangor D.E, Malaysia Website: www.wilhams.com.my

    CONLIT 150 STRUCTURAL STEEL FIRE PROTECTION TECHNICAL SPECIFICATION

    1. The structural steel shall be constructed in accordance with The use of

    structural steel in buildings. Part 2. Metric units. British Standard 449 : Part 2 : 1969 and The Structural use of steelwork in building. Part 8. Code of practice for fire resistant design. British Standard 5950 : Part 8 : 1990.

    2. Structural steel fire protection shall have been tested in accordance with

    British Standard 476 : Part 21 : 1987 or British Standard 476: Part 8 : 1972 and installed at the locations shown on the drawings according to the thickness shall be in accordance with the following table using a critical temperatures of 450C ;-

    Fire Resistance

    Period 2 Hours Fire Resistance Period 2 Hours Steel columns protected in 1 or 2 layers

    Steel beams and similar sections protected in 1 or 2 layers

    Item Hp/A Thicknes

    s Item Hp/A Thickness 1 1 to 34 15mm 1 1 to 49 15mm2 35 to 48 20mm 2 50 to 71 20mm3 49 to 64 25mm 3 72 to 95 25mm4 65 to 82 30mm 4 96 to 129 30mm5 83 to 103 35mm 5 130 to 167 35mm6 104 to 127 40mm 6 168 to 215 40mm7 128 to 154 45mm 7 215 to 260 45mm8 155 to 186 50mm 9 187 to 260 60mm

    3. Where no fire insulation period is stated the minimum acceptable period is

    2 hours when tested to BS 476 Part 21: 1987. 4. The fire protection system shall be mineral wool based with a minimum

    density of 165kg/m3. The outside surface of the fire rated ductwork shall be coated with a aluminium foil that has been tested to BS 476: Part 6 & 7 achieving Class O surface spread of flame.

    5. Mineral wool fire protection material must be certified by The LUL Code of

    Practice for Fire Safety; August 1990 as non toxic.

  • WILHAMS INSULATION FAR EAST SDN BHD (340166M)

    Page3 Wilhams Insulation Far East Sdn Bhd tel.00-6-03-78466728 15 & 17 Jalan U5/23, Seksyen U5 fax.00-6-03-78466540 Mah Sing Integrated Industrial Park E-mail : [email protected] 40150 Shah Alam, Selangor D.E, Malaysia Website: www.wilhams.com.my

    CONLIT 150 STRUCTURAL STEEL FIRE PROTECTION TECHNICAL SPECIFICATION

    6. The mineral wool fire protection material shall have achieved Euro Class A1 when tested by an independent testing authority BS EN 13501: 2002.

    7. All fixings are to be provided by the manufacturer or manufacturers

    representative.

    8. Any materials used for the construction of penetrations shall provide fire ratings equal to or better than the adjacent construction.

    INSTALLATION Conform to the material manufacturers installations and fire ratings accepted under the fire and building codes / laws, coordinating the installation with other works. All surfaces to be covered by fire rated insulation is to be clean, dry and in proper condition to receive the insulation. Install the 2 hour fire rated Conlit150 Structural Steel Fire Protection System in all areas and surface shown on the drawings. The 2 hour fire rated Conlit150 Structural Steel Fire Protection System slabs shall be attached to steel work using either of the following methods:

    1. Conlit150 applied in a single layer, with butt joints glued and nailed or stapled, and Conlit Glue and nailed or stapled to noggings 120mm wide at 1000mm centres, the noggins of Conlit150 formed from the same thickness as the casing board.The length of the screws or nails is at least twice the thickness of the Conlit150. Spiral screws or nails are located approximately 50mm from the top and bottom of the of the noggin, with additional screws at 100mm maximum centres, or nails at 200mm maximum centres.

    2. Conlit150 applied in two layers, with butt joints glued and nailed or stapled,

    and Conlit Glue and nailed or stapled to noggings 120mm wide at 1000mm centres, the noggins of Conlit150 formed from the same thickness as the casing board. The length of the screws or nails is at least twice the thickness of the Conlit150. Spiral screws or nails are located approximately 50mm from the top and bottom of the of the noggin, with additional screws at 100mm maximum centres, or nails at 200mm maximum centres.

  • WILHAMS INSULATION FAR EAST SDN BHD (340166M)

    Page4 Wilhams Insulation Far East Sdn Bhd tel.00-6-03-78466728 15 & 17 Jalan U5/23, Seksyen U5 fax.00-6-03-78466540 Mah Sing Integrated Industrial Park E-mail : [email protected] 40150 Shah Alam, Selangor D.E, Malaysia Website: www.wilhams.com.my

    CONLIT 150 STRUCTURAL STEEL FIRE PROTECTION TECHNICAL SPECIFICATION

    3. Conlit Clips or spot welded steel pins of minimum 2.67mm diameter and

    locking washers. Conlit Glue must be installed at all transverse joints and spiral screws, at longitudinal joints..

    The fire protection material should be fitted securely into position against the steel work without leaving a void and tightly butted to the adjacent Conlit 150 Slabs . Where a vapour barrier is required all exposed Conlit edges and penetrations through the foil must be sealed using foil tape.