    Slide Rack Mount KitInstallation Procedure

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    2/34

    2 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Copyright 2002-2004, Brocade Communications Systems, Incorporated.

    ALL RIGHTS RESERVED. Publication Number: 53-0001625-06

    Brocade, the Brocade B weave logo, Secure Fabric OS, and SilkWorm are registered trademarks of Brocade Communications Systems,

    Inc., or its subsidiaries in the United States and/or in other countries. FICON is a registered trademark of IBM Corporation in the United

    States and other countries. All other brands, products, or service names are or may be trademarks or service marks of, and are used toidentify, products or services of their respective owners.

    Notice: The information in this document is provided AS IS, without warranty of any kind, including, without limitation, any implied

    warranty of merchantability, noninfringement or fitness for a particular purpose. Disclosure of information in this material in no way

    grants a recipient any rights under Brocade's patents, copyrights, trade secrets or other intellectual property rights. Brocade reserves the

    right to make changes to this document at any time, without notice, and assumes no responsibility for its use.

    The authors and Brocade Communications Systems, Inc., shall have no liability or responsibility to any person or entity with respect to

    any loss, cost, liability, or damages arising from the information contained in this book or the computer programs that accompany it.

    Notice: The product described by this document may contain open source software covered by the GNU General Public License or

    other open source license agreements. To find out which open source software is included in Brocade products, view the licensing terms

    applicable to the open source software, and obtain a copy of the programming source code, please visit http://www.brocade.com/

    support/oscd.

    Export of technical data contained in this document may require an export license from the United States government.

    Brocade Communications Systems, Incorporated

    Corporate Headquarters

    1745 Technology Drive

    San Jose, CA 95110

    T: (408) 333-8000

    F: (408) 333-8101

    Email: [email protected]

    Asia-Pacific Headquarters

    Shiroyama JT Trust Tower 36th Floor

    4-3-1 Toranomon, Minato-ku

    Tokyo, Japan 105-6036

    T: +81 35402 5300

    F: +81 35402 5399

    Email: [email protected]

    European Headquarters

    29, route de lAeroportCase Postale 105

    CH-1211 Geneva 15,

    Switzerland

    T: +41 22 799 56 40

    F: +41 22 799 56 41

    Email: [email protected]

    Latin America Headquarters

    5201 Blue Lagoon DriveMiami, FL 33126

    T: (305) 716-4165

    Email: [email protected]

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    3/34

    Slide Rack Mount Kit Installation Procedure 3 of 34

    Publication Number: 53-0001625-06

    Document History

    The following table lists revision history of the Slide Rack Mount Kit Installation Procedure.

    Overview

    You can use the slide rack mount kit to install a 1U, 1.5U, or 2U SilkWorm switch in a standard 19-inch EIA rack. The

    installation methods are listed in Table 1 on page 4.

    Refer to the following sections to install the slide rack mount kit:

    "Installation Requirements" on page 4

    "Planning the Switch Installation" on page 7

    "Preparing Slide Assemblies" on page 8

    "Installing the Switch to Slide Out Port Side" on page 8

    "Installing the Switch to Slide Out Nonport Side" on page 21

    Document Title Publication Number Summary of Changes Publication Date

    Slide Rack Mount Kit

    Installation Procedure

    53-0001625-01 First release (new book) March 2002

    Slide Rack Mount Kit

    Installation Procedure

    53-0001625-02 n.a. November 2002

    Slide Rack Mount Kit

    Installation Procedure

    53-0001625-03 Internal review only. August 2003

    Slide Rack Mount Kit

    Installation Procedure

    53-0001625-04 Added 2U switch installation procedures to

    support SilkWorm AP7420 switches.

    September 2003

    Slide Rack Mount Kit

    Installation Procedure

    53-0001625-05 Revised publication number. September 2003

    Slide Rack Mount KitInstallation Procedure

    53-0001625-06 Complete reformat (including alteringprocedures), provided new illustrations, and

    added SilkWorm 3250/3850 support.

    December 2003

    Note

    U represents a rack unit of space in a standard EIA cabinet. 1U equals 1.75 inches (4.44 cm).

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    4/34

    4 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Installation RequirementsAllow 15 to 30 minutes to complete this procedure.

    Slide rack mount kit installation requirements include:

    Electrical requirements:

    - Use a primary AC input 100-240 VAC, 47-63 Hz, correctly wired with the circuit protected by a circuit breaker

    and grounded in accordance with local electrical codes.

    - Use an adequate supply circuit, line fusing, and wire size, as specified by electrical rating on the switch

    nameplate.

    - Ground all equipment in the cabinet through a reliable branch circuit connection, and maintain ground at all

    times. Do not rely on a secondary connection to a branch circuit such as a power strip.

    Thermal requirements:

    - Plan the installation so that the nonport side of the switch faces the cool-air aisle. This allows the switch fans to

    pull in cool air.

    - Verify that the air flow available to the air intake vents meets the minimum requirements specified for the switch

    being installed.

    - Verify that the ambient air temperature at the nonport side of the switch does not exceed 40 Celsius (104

    Fahrenheit) while the switch is operating.

    Table 1 Switch Installation Methods Using the Slide Rack Mount Kit

    Switch

    Height

    Switch Type Slide Direction and Positioning Cabinet

    Rail Type

    1U SilkWorm 2000-series,3200-series, and 3800-

    series

    Switch slides out ofportside of cabinet (exhaust-air side).

    Port side of switch isflush with edge of cabinet.

    Round-hole

    Square-hole

    Switch slides out ofnonportside of cabinet (air-intake

    side).

    Port side of switch isset 3 inches backfrom edge of

    cabinet (allows a more gradual bend in cables).

    Round-hole

    Square-hole

    1.5U SilkWorm 3900 Switch slides out of portside of cabinet (exhaust-air side).

    Port side of switch isflush with edge of cabinet.

    Round-hole

    Square-hole

    Switch slides out ofnonportside of cabinet (air-intakeside).

    Port side of switch isset 3 inches backfrom edge of

    cabinet (allows a more gradual bend in cables).

    Round-hole

    Square-hole

    2U SilkWorm AP7420 Switch slides out of portside of cabinet (exhaust-air side).

    Port side of switch isflush with edge of cabinet.

    Note: Nonport-side installation is not supported.

    Round-hole

    Square-hole

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    5/34

    Slide Rack Mount Kit Installation Procedure 5 of 34

    Publication Number: 53-0001625-06

    Cabinet specifications:

    - Use a standard EIA cabinet.

    - Plan a cabinet space that is up to 2 rack units (2U) high and 11 to 30 inches deep, depending on the switch being

    installed.

    - Verify that the additional weight of the switch does not exceed the weight limits of the cabinet or unbalance thecabinet in any way.

    - Secure the cabinet to ensure stability in case of unexpected movement, such as an earthquake.

    Tool Requirements and Parts List

    The following tools are required to perform this procedure:

    Phillips #2 screwdriver with torque capability

    1/4-inch slotted-blade screwdriver with torque capability

    Ensure all of the items listed in Table 2 are included in your kit. See Figure 1 on page 6 for an illustration of each item.Table 2 Items Included in the Slide Rack Mount Kit

    Item Description Total Qty.

    A Slide assembly, containing one inner and one outer slide rail, with Items B, C, and D installed on

    the outer slide rail (each slide assembly is bagged separately)

    2

    B Three-hole slide mount L-bracket 4

    C Locking hex nut, 8-32 (for Item D) 12

    D Slotted screw, 8-32 x 3/8 inch, zinc 12

    E Power cord clip 6

    F Phillips screw, 10-32 x 3/8 inch, black 12

    G Three-hole rack nut bar, 8-32 (for Item F) 4

    H Alignment washer 12

    I Retainer nut, 10-32 (for Item F) 12

    J Left rack mount bracket (unexpected movement safety bracket for port side) 1

    K Right rack mount bracket (unexpected movement safety bracket for port side) 1

    L Left mount bracket (unexpected movement safety bracket for port side) 1

    M Right mount bracket (unexpected movement safety bracket for port side) 1

    N Phillips screw, 8-32 x 1/4 inch, black 4

    O Back rack mount bracket (unexpected movement safety bracket for nonport side) 2

    P Phillips screw, 8-32 x 3/16 inch, zinc 12

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    6/34

    6 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 1 Items Included in the Slide Rack Mount Kit

    scale: 1/2" = 1"scale: 1/2" = 1"

    LL

    B (4x)

    Note: Scale is 1/2" = 1"

    unless otherwise noted.

    Note:

    Heavy box outlines

    indicates separate

    packages of

    components

    Item A(2x)

    N (4x)

    F (12x) H (12x)

    E(6x)

    D (6x)

    scale: 1/2" = 1"

    C (8x)

    O (2x) C (4x) D (4x) P (12x)

    J(1x)

    K(1x)

    L(1x)

    M(1x)

    I (12x)G(4x)

    scale: 3/16" = 1"

    scale: 5/16" = 1"

    3.001

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    7/34

    Slide Rack Mount Kit Installation Procedure 7 of 34

    Publication Number: 53-0001625-06

    Planning the Switch Installation

    This section helps you plan how to install the switch in a cabinet.

    To plan the position of the switch in the cabinet:

    1. Plan the orientation of the switch so that the nonport side faces the air-intake aisle.

    2. Plan 1U, 1.5U, or 2U of rack space for your specific switch.

    The slide rack mount kit supports the following switch sizes:

    1U SilkWorm 2000-series, 3200-series, and 3800-series

    1.5U SilkWorm 3900

    2U SilkWorm AP7420

    3. For 1.5U switches only, determine whether you want the additional 0.5U or 1U of the switch to be above or below the

    brackets.

    The L-brackets cover three holes (1U) on each cabinet rail (see Figure 2).

    Figure 2 1.5U Switch Installed with 0.5U Above the L-bracket

    4. Determine the direction in which you want the switch to slide: Toward the exhaust-air aisle (port side; see Figure 14 on page 19)

    Toward the air-intake aisle (nonport side; see Figure 25 on page 30)

    Note

    When replacing the rack mount hardware of a previously installed switch, first power down the switch and

    remove all attached cables and power cords; then, remove the switch from the cabinet and uninstall all rack

    mount hardware.

    Note

    U represents a rack unit of space in a standard EIA cabinet. 1U equals 1.75 inches (4.44 cm).

    Caution

    SilkWorm AP7420 only supports port-side installation due to the length of the switch.

    scale: 1/4" = 1"

    Cabinet Rail(round hole)

    1.5USwitch

    L-bracket

    0.5U

    1U8 9 10 110 1 2 3

    23222120 31302928

    12 13 14 154 5 6 7

    19181716 27262524

    IOIOI

    IP

    3.002

    B ASlide Rail Assembly

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    8/34

    8 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Preparing Slide Assemblies

    To prepare both slide assemblies for installation:

    1. Locate the slide assembly (Item A) in the kit (see Figure 1 on page 6).

    2. Pull the inner slide rail out until the lock engages (see Figure 3).

    Figure 3 Pulling the Slide Rails Apart

    3. Press the lock-release lever located inside the inner slide rail and pull the inner rail away from the outer rail.

    4. Repeat step 1 through step 3with the second slide assembly.

    Proceed to "Installing the Switch to Slide Out Port Side", next, or"Installing the Switch to Slide Out Nonport Side" on

    page 21.

    Installing the Switch to Slide Out Port Side

    This section provides the following information:

    "Attaching Inner Slide Rails" on page 9

    "Attaching Rack Mount Brackets" on page 10

    "Attaching L-brackets to Cabinet Rails" on page 11

    "Inserting the Switch in the Cabinet" on page 17

    Inner SlideRail

    Lock-releaseLever

    SlideAssembly

    scale:5/16" = 1"

    scale:1/8" = 1"M 3

    .003

    Lock-releaseLever

    Push to release

    A

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    9/34

    Slide Rack Mount Kit Installation Procedure 9 of 34

    Publication Number: 53-0001625-06

    Attaching Inner Slide Rails

    To attach the inner slide rails:

    1. Position an inner slide rail with the flat side against the switch and the end containing the lock-release lever toward

    the nonport side of the switch.

    2. Align the rail holes with the holes drilled in the side of the switch (see Figure 4).

    Figure 4 Installing Inner Rail in the Lower Holes to Allow a 1.5U Switch to Slide Out of Port Side

    3. Attach the rail using three Phillips 8-32 x 3/16-inch screws (Item P).

    For 1.5U switches, choose from the upper or lower rail holes to determine vertical positioning. 1U and 2U switches

    only have a single row of holes for mounting brackets.

    4. Tighten the screws to a torque of 15 inch-pounds (17 cm-kgs).

    5. Repeat step 1 through step 4for the inner slide rail on the other side of the switch.

    Caution

    Using screws longer than the specified length can damage the switch. Use only the screws provided with

    the kit.

    scale:3/16" = 1"

    3.004

    3

    2

    3

    1 2

    31

    30

    29

    13

    14

    15

    IP

    Lock-release

    Lever

    Lower Holes Inner

    Slide Rail1.5U

    Switch

    P (3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    10/34

    10 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Attaching Rack Mount Brackets

    Installing the rack mount brackets prevents unexpected movement, such as from an earthquake.

    To attach rack mount brackets:

    1. Position the right mount bracket (Item M) next to the right side of the switch (see Figure 5).

    If you used the lower holes for the inner side rails, install the rack mount brackets using the lower two of the rack

    mount bracket holes. If you used the upper holes for the inner side rails, install the rack mount brackets using the

    upper two of the rack mount bracket holes.

    Figure 5 Attaching a Rack Mount Bracket

    2. Attach the right rack mount bracket to the switch using two Phillips 8-32 x 1/4 inch screws (Item N).

    3. Tighten the screws to a torque of 15 inch-pounds (17 cm-kgs).

    4. Repeat step 1 through step 3for the left rack mount bracket (Item L).

    Note

    For a 1U switch, use Item O instead of Item M.

    Note

    For upper-hole installation, use Item M on the left and Item L on the right of the switch.

    Caution

    Using screws longer than the specified length can damage the switch. Use only the screws provided with

    the kit.

    Note

    For a 1U switch, use Item O instead of Item L.

    3.005

    scale: 5/16" = 1"

    31

    30

    29

    13

    14

    15

    IP

    (Item L on left side)

    N

    M

    (2x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    11/34

    Slide Rack Mount Kit Installation Procedure 11 of 34

    Publication Number: 53-0001625-06

    Attaching L-brackets to Cabinet Rails

    Each slide assembly (Item A) includes two L-brackets (Item B) that attach to the cabinet rails (either round-hole or

    square-hole). The slide rack mount kit includes hardware compatible with both cabinet rail types.

    The following sections provide installation instructions for each type of cabinet rail:

    "Round-hole Cabinet Rails"

    "Square-hole Cabinet Rails (Method A)" on page 13

    "Square-hole Cabinet Rails (Method B)" on page 15

    Round-hole Cabinet Rails

    To install the round-hole hardware:

    1. On the port side of the outer slide rail, loosen the nuts (Item C) securing the L-bracket (Item B) and extend the end of

    the bracket beyond the end of the slide rail by 5/8 inch (see Figure 6).

    Repositioning allows the rack mount brackets to align with the cabinet rails.

    Figure 6 Repositioning the L-brackets

    2. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the nonport side of the

    cabinet (see Figure 7 on page 12).

    3. Loosen and adjust the position of the nonport side L-bracket as necessary.

    Note

    Two methods are available for square-hole cabinet rails.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the

    nonport side, and adjust the bracket position until the total rail length matches the cabinet depth.

    3.006

    5/8"

    5/8"

    Outer

    Slide

    Rail

    Loosen

    Item C

    (2x)

    scale: 3/8" = 1"

    B

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    12/34

    12 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    4. Attach the L-brackets (Item B) to the cabinet rails using five 10-32 x 3/8 inch screws (Item F) and two of the three-

    hole nut bars (Item G).

    Figure 7 Attaching Outer Slide Rails to Round-hole Cabinet Rails

    5. Tighten the screws to 15 inch-pounds (17 cm-kgs).

    6. Repeat step 1 through step 5for the other rail.

    Note

    Leave the middle hole empty on the port side for securing the rack mount bracket (Item O or M) later (refer

    to "Inserting the Switch in the Cabinet" on page 17).

    3.007

    scale: 3/8" = 1"

    Cabinet

    Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Outer Slide Rail

    (closed end on non-port side)

    G

    G

    BB

    F (3x)

    F (2x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    13/34

    Slide Rack Mount Kit Installation Procedure 13 of 34

    Publication Number: 53-0001625-06

    Square-hole Cabinet Rails (Method A)

    To install the square-hole hardware using method A:

    1. On the port side of the outer slide rail, loosen the nuts (Item C) securing the L-bracket (Item B) and extend the end of

    the bracket beyond the end of the slide rail by 5/8 inch (see Figure 8).

    Repositioning allows the rack mount brackets to align with the cabinet rails.

    Figure 8 Repositioning the L-brackets

    2. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the nonport side of the

    cabinet (see Figure 9 on page 14).

    3. Loosen and adjust the position of the nonport side L-bracket as necessary.

    4. Attach the L-brackets (Item B) to the cabinet rails using five 10-32 x 3/8 inch screws (Item F) and five retainer nuts

    (Item I).

    5. Tighten the retainer nuts (Item I) to 15 inch-pounds (17 cm-kgs).

    6. Repeat step 1 through step 5for the other rail.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the nonport

    side, and adjust the bracket position until the total rail length matches the cabinet depth.

    Note

    Leave the middle hole empty on the port side for securing the rack mount bracket (Item O or M) later (refer

    to "Inserting the Switch in the Cabinet" on page 17).

    3.006

    5/8"

    5/8"

    Outer

    SlideRail

    Loosen

    Item C(2x)

    scale: 3/8" = 1"

    B

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    14/34

    14 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 9 Method A for Attaching Outer Slide Rails to Square-hole Cabinet Rails

    3.008

    scale: 3/8" = 1"Square Hole

    Cabinet Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Outer Slide Rail

    (closed end on non-port side)

    I

    BB

    (3x)F (2x)

    I (2x)

    F(3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    15/34

    Slide Rack Mount Kit Installation Procedure 15 of 34

    Publication Number: 53-0001625-06

    Square-hole Cabinet Rails (Method B)

    To install the square-hole hardware using method B:

    1. On the port side of the outer slide rail, loosen the nuts (Item C) securing the L-bracket (Item B) and extend the end of

    the bracket beyond the end of the slide rail by 5/8 inch (see Figure 10).

    Repositioning allows the rack mount brackets to align with the cabinet rails.

    Figure 10 Repositioning the L-brackets

    2. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the nonport side of the

    cabinet (see Figure 11 on page 16).

    3. Loosen and adjust the position of the nonport side L-bracket as necessary.

    4. Attach the L-brackets (Item B) to the cabinet rails using five 10-32 x 3/8 inch screws (Item F), six alignment washers

    (Item H), and two of the three-hole nut bars (Item G).

    5. Tighten the screws to 15 inch-pounds (17 cm-kgs).

    6. Repeat step 1 through step 5for the other rail.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the nonportside, and adjust the bracket position until the total rail length matches the cabinet depth.

    Note

    Leave the middle hole empty on the port side for securing the rack mount bracket (Item O or M) later (refer

    to "Inserting the Switch in the Cabinet" on page 17); however, position an alignment washer (Item H)

    between the L-bracket (Item B) and the cabinet rail.

    3.006

    5/8"

    5/8"

    Outer

    SlideRail

    Loosen

    Item C

    (2x)

    scale: 3/8" = 1"

    B

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    16/34

    16 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 11 Method B for Attaching Outer Slide Rails to Square-hole Cabinet Rails

    3.009

    scale: 3/8" = 1"

    Cabinet

    Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Outer Slide Rail

    (closed end on non-port side)

    H

    G

    G

    B

    B

    (3x)

    F (3x)

    F (2x)

    H (3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    17/34

    Slide Rack Mount Kit Installation Procedure 17 of 34

    Publication Number: 53-0001625-06

    Inserting the Switch in the Cabinet

    To install the switch in the cabinet:

    1. Position the power cord clips (Item E) on the outer surface of both outer slide rails (see Figure 12).

    Ensure that the clips do not interfere with the movement of the rails. Position all the clips either with the tabs above or

    with the tabs below the rail.

    Figure 12 Attaching Power Cord Clips

    2. Insert the power cords into the power cord clips, with the power cord prongs pointing toward the power source (see

    Figure 13 on page 18).

    Allow a minimum service loop of 6 inches at the switch to ensure freedom to plug and unplug the power cords.

    Ensure the power cords route completely outside of the slide rails.

    Caution

    Ensure the power cords align in the clips and do not fall inside the slide rails. To prevent the cords from

    being pulled out of the clips, unplug the cords from the switch before moving the switch on the slide rails.

    3.010

    CabinetRail

    (port side)

    3/16" = 1"

    .1875" = 1"

    Cabinet

    Rail

    (non-port side)

    E

    A

    (3x)

    B (2x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    18/34

    18 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 13 Inserting Power Cords in Clips

    3. Position the switch next to the cabinet; align and insert the inner rails inside the outer rails (see Figure 14 on page 19).

    4. Gently slide the switch into the cabinet; check rail alignment by sliding the switch out and back into the cabinet.

    If there is any resistance, pull the switch out of the cabinet and realign the slide rails.

    3.011

    Power

    Cord

    3/16" = 1"

    Cabinet

    Rail

    (non-port side)

    Cabinet Rail

    (port side)

    E (3x)

    A

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    19/34

    Slide Rack Mount Kit Installation Procedure 19 of 34

    Publication Number: 53-0001625-06

    Figure 14 Inserting the Switch

    5. Secure the rack mount brackets to the cabinet rails using one Phillips 10-32 x 3/8 inch screw (Item F) per bracket and

    tighten the screws to a torque of 25 inch-pounds (29 cm-kgs).

    For square-hole cabinet rail method A installations, use the remaining retainer nut (Item I) to secure the screw.

    See Figure 15 on page 20 for a round-hole cabinet rail; see Figure 16 on page 20 (Method A) orFigure 17 on page 21

    (Method B) for a square-hole cabinet rail.

    Caution

    Do not connect the switch to the network until the IP address is correctly set. For power-on and

    configuration instructions, refer to the hardware manual for your specific switch.

    Port side installation

    scale: .10" = 1"

    L

    8

    9

    10

    11

    0

    1

    2

    3

    23

    22

    21

    20

    31

    30

    29

    28

    12

    13

    14

    15

    4

    5

    6

    7

    19

    18

    17

    16

    27

    26

    25

    24

    IOIOI

    IP

    1

    3

    2

    3

    1 2

    3.012

    Switch(Slides in/out on Port Side)

    Outer

    Slide

    Rail

    Cabinet Rail

    Inner

    Slide

    Rail

    Slide Rail

    Open End

    Slide RailClosed End

    Lock-releaseLever

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    20/34

    20 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 15 Securing Rack Mount Brackets for Round-hole Cabinet Rails

    Figure 16 Method A for Securing Rack Mount Brackets for Square-hole Cabinet Rails

    31

    30

    29

    13

    14

    15

    IP

    3.013

    scale: 3/8" = 1"

    Round HoleCabinet Rail

    (port side)

    (exploded for clarity)

    M

    F

    G

    31

    30

    29

    13

    14

    15

    IP

    3.014

    scale: 3/8" = 1" Square HoleCabinet Rail

    (port side)

    For attachingItem M

    (exploded for clarity)

    (2x)

    For attachingSlide Rail Bracket

    (Item B)

    I

    I

    M

    B

    F

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    21/34

    Slide Rack Mount Kit Installation Procedure 21 of 34

    Publication Number: 53-0001625-06

    Figure 17 Method B for Securing Rack Mount Brackets for Square-hole Cabinet Rails

    Installing the Switch to Slide Out Nonport Side

    This section provides the following information:

    "Attaching Inner Slide Rails" on page 22

    "Attaching Rack Mount Brackets" on page 23

    "Attaching L-brackets to Cabinet Rails" on page 24

    "Inserting the Switch in the Cabinet" on page 28

    Caution

    SilkWorm AP7420 only supports port-side installation due to the length of the switch.

    31

    30

    29

    13

    14

    15

    IP

    3.015

    scale: 3/8" = 1" Square HoleCabinet Rail

    (port side)

    Alignment Washer(installed when

    attaching Slide "L"Bracket)

    (exploded for clarity)

    G

    H (3x)

    F

    M

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    22/34

    22 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Attaching Inner Slide Rails

    To attach inner slide rails:

    1. Position an inner slide rail with the flat side against the switch, facing the end containing the lock-release lever

    toward the port side of the switch.

    2. Align the rail holes with the holes drilled in the side of the switch (see Figure 18).

    Figure 18 Installing Inner Rail in the Lower Holes to Allow a 1.5U Switch to Slide Out of Nonport Side

    3. Attach the rail using two Phillips 8-32 x 3/16-inch screws (Item P).

    For 1.5U switches, choose from the upper or lower rail holes to determine vertical positioning. 1U and 2U switches

    only have a single row of holes for mounting brackets.

    4. Tighten the screws to a torque of 15 inch-pounds (17 cm-kgs).

    5. Repeat step 1 through step 4for the inner slide rail on the other side of the switch.

    Caution

    Using screws longer than the specified length can damage the switch. Use only the screws provided with

    the kit.

    Lock-release

    Lever

    scale:3/16" = 1"

    3.016

    31

    30

    29

    13

    14

    15

    IP

    3

    2

    3

    1 2

    Lower Holes

    Inner

    Slide Rail

    1.5U

    Switch

    P (3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    23/34

    Slide Rack Mount Kit Installation Procedure 23 of 34

    Publication Number: 53-0001625-06

    Attaching Rack Mount Brackets

    Installing the rack mount brackets prevents unexpected movement, such as from an earthquake.

    To attach rack mount brackets:

    1. Position a back rack mount bracket (Item O) at the end of an inner slide rail (see Figure 19).

    Position the bracket opposite to the end with the lock-release lever.

    Figure 19 Attaching the Rack Mount Brackets

    2. Attach the brackets to the slide rail using two slotted-head 8-32 x 3/8 inch screws (Item D); add lock nuts (Item C) to

    the end of each screw.

    3. Tighten the screws to a torque of 15 inch-pounds (17 cm-kgs).

    4. Repeat step 1 through step 3for the rack mount bracket on the other side of the switch.

    Inner

    Slide Rail

    scale:3/16" = 1"

    3.017

    31

    30

    29

    13

    14

    15

    IP

    3

    2

    3

    1 2

    D (2x)

    C(2x)

    O

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    24/34

    24 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Attaching L-brackets to Cabinet Rails

    Each slide assembly (Item A) includes two L-brackets (Item B) that attach to the cabinet rails (either round-hole or

    square-hole). The slide rack mount kit includes hardware compatible with both cabinet rail types.

    The following sections provide installation instructions for each type of cabinet rail:

    "Round-hole Cabinet Rails"

    "Square-hole Cabinet Rails (Method A)" on page 26

    "Square-hole Cabinet Rails (Method B)" on page 27

    Round-hole Cabinet Rails

    To install the round-hole hardware:

    1. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the port side of the

    cabinet.

    2. Loosen and adjust the position of the nonport side L-bracket (Item B) as necessary.

    3. Attach the L-brackets to the cabinet rails using five 10-32 x 3/8 inch screws (Item F) and two of the three-hole nut

    bars (Item G) (see Figure 20 on page 25).

    Note

    Two methods are available for square-hole cabinet rails.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the nonport

    side, and adjust the bracket position until the total rail length matches the cabinet depth.

    NoteLeave the middle hole empty on the nonport side for securing the rack mount bracket (Item O) later (refer

    to "Inserting the Switch in the Cabinet" on page 28).

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    25/34

    Slide Rack Mount Kit Installation Procedure 25 of 34

    Publication Number: 53-0001625-06

    Figure 20 Attaching Outer Slide Rails to Round-hole Cabinet Rails

    4. Tighten the screws to 15 inch-pounds (17 cm-kgs).

    5. Repeat step 1 through step 4for the other rail.

    3.018

    scale: 3/8" = 1"

    Cabinet

    Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Closed End

    on Outer

    Slide Rail

    Outer Slide Rail

    (closed end on port side)

    F

    B

    G

    G

    B

    (2x)

    F (3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    26/34

    26 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Square-hole Cabinet Rails (Method A)

    To install the square-hole hardware using method A:

    1. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the port side of the

    cabinet.

    2. Loosen and adjust the position of the nonport side L-bracket (Item B) as necessary.

    3. Attach the L-brackets to the cabinet rails using five 10-32 x 3/8 inch screws (Item F) and five retainer nuts (Item I)

    (see Figure 21).

    Figure 21 Method A for Attaching Outer Slide Rails to Square-hole Cabinet Rails

    4. Tighten the retainer nuts (Item I) to 15 inch-pounds (17 cm-kgs).

    5. Repeat step 1 through step 4for the other rail.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the

    nonport side, and adjust the bracket position until the total rail length matches the cabinet depth.

    Note

    Leave the middle hole empty on the nonport side for securing the rack mount bracket (Item O) later (refer

    to "Inserting the Switch in the Cabinet" on page 28).

    3.019

    Cabinet

    Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Outer Slide Rail

    (closed end on port side)

    scale: 3/8" = 1"

    Closed Endon Outer

    Slide Rail

    I (3x)

    F (3x)I

    B

    B

    (2x)

    F (2x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    27/34

    Slide Rack Mount Kit Installation Procedure 27 of 34

    Publication Number: 53-0001625-06

    Square-hole Cabinet Rails (Method B)

    To install the square-hole hardware using method B:

    1. Position the outer slide rail inside the cabinet rails with the closed ends of the slide rail toward the port side of the

    cabinet.

    2. Loosen and adjust the position of the nonport side L-bracket (Item B) as necessary.

    3. Attach the L-brackets to the cabinet rails using five 10-32 x 3/8 inch screws (Item F), six alignment washers (Item H),

    and two of the three-hole nut bars (Item G) (see Figure 22).

    Figure 22 Method B for Attaching Outer Slide Rails to Square-hole Cabinet Rails

    4. Tighten the screws to 15 inch-pounds (17 cm-kgs).

    5. Repeat step 1 through step 4for the other rail.

    Note

    If side cabinet access is not available, measure the depth of the cabinet, loosen the L-bracket on the

    nonport side, and adjust the bracket position until the total rail length matches the cabinet depth.

    Note

    Leave the middle hole empty on the nonport side for attaching a rack mount bracket (Item O) later (refer to

    "Inserting the Switch in the Cabinet" on page 28); however, position an alignment washer (Item H)

    between the L-bracket and the cabinet rail.

    3.020

    Cabinet

    Rail

    (port side)

    Cabinet

    Rail

    (non-port side)

    Outer Slide Rail

    (closed end on port side)

    scale: 3/8" = 1"

    H (3x)

    H(3x)

    F(3x)

    B

    G

    G

    B

    F (2x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    28/34

    28 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Inserting the Switch in the Cabinet

    To install the switch in the cabinet:

    1. Position the power cord clips (Item E) on the outer surface of both outer slide rails (see Figure 23).

    Ensure that the clips do not interfere with the movement of the rails. Position all the clips either with the tabs above or

    with the tabs below the rail.

    Figure 23 Attaching Power Cord Clips

    3.021

    CabinetRail

    (port side)

    3/16" = 1"

    .1875" = 1"

    Cabinet

    Rail

    (non-port side)

    Closed end on

    Outer Slide Rail

    A

    B(2x)

    E(3x)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    29/34

    Slide Rack Mount Kit Installation Procedure 29 of 34

    Publication Number: 53-0001625-06

    2. Insert the power cords into the power cord clips, with the power cord prongs pointing toward the power source (see

    Figure 24).

    Allow a minimum service loop of 6 inches at the switch to ensure freedom to plug and unplug the power cords.

    Ensure that the power cords route completely outside of the slide rails.

    Figure 24 Inserting Power Cords in Clips

    Caution

    Ensure the power cords align in the clips and do not fall inside the slide rails. To prevent the cords from

    being pulled out of the clips, unplug the cords from the switch before moving the switch on the slide rails.

    3.022

    Cabinet Rail

    (port side)

    Power

    Cord

    3/16" = 1"

    Cabinet

    Rail

    Closed end on

    Outer Slide Rail

    E (3x)

    A

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    30/34

    30 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    3. Position the switch next to the cabinet; align and insert the inner rails inside the outer rails (see Figure 25).

    Figure 25 Inserting the Switch

    4. Gently slide the switch into the cabinet; check rail alignment by sliding the switch out and back into the cabinet.

    If there is any resistance, pull the switch out of the cabinet and realign the slide rails.

    5. Secure the rack mount brackets to the cabinet rails using one Phillips 10-32 x 3/8 inch screw (Item F) per bracket and

    tighten the screws to a torque of 25 inch-pounds (29 cm-kgs).

    For square-hole cabinet rail method A installations, use the remaining retainer nut (Item I) to secure the screw.

    See Figure 26 on page 31 for a round-hole cabinet rail; see Figure 27 on page 32 (Method A) orFigure 28 on page 33

    (Method B) for a square-hole cabinet rail.

    Caution

    Do not connect the switch to the network until the IP address is correctly set. For power-on and

    configuration instructions, refer to the hardware manual for your specific switch.

    Non-Port side installation

    scale: .10" = 1"

    8

    9

    10

    11

    0

    1

    2

    3

    23

    22

    21

    20

    31

    30

    29

    28

    12

    13

    14

    15

    4

    5

    6

    7

    19

    18

    17

    16

    27

    26

    25

    24

    IOIOI

    IP

    1

    3

    2

    3

    1 2

    3.023

    Switch(Slides in/out on Non-Port Side)

    OuterSlideRail

    Cabinet RailSlide Rail

    Closed End

    InnerSlide

    RailLock-release

    Lever

    Slide RailOpen End

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    31/34

    Slide Rack Mount Kit Installation Procedure 31 of 34

    Publication Number: 53-0001625-06

    Figure 26 Securing Rack Mount Brackets for Round-hole Cabinet Rails

    scale: 3/8" = 1"

    Cabinet Rail(non-port side)

    OuterSlide Rail

    (closed end on port side)

    InnerSlide Rail

    Switch

    (non-port side)

    3.024

    F

    I

    O

    (1x)

    I

    F

    (2x)

    (2x)

    (previously installed)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    32/34

    32 of 34 Slide Rack Mount Kit Installation Procedure

    Publication Number: 53-0001625-06

    Figure 27 Method A for Securing Rack Mount Brackets for Square-hole Cabinet Rails

    3.025

    scale: 3/8" = 1"

    Cabinet Rail(non-port side)

    OuterSlide Rail

    (closed end on port side)

    InnerSlide Rail

    Switch(non-port side)

    F

    O

    G

    F(2x)

    (previously installed)

  • 7/30/2019 Slide Rack Mount Kit Installation Procedure 53_0001625_06

    33/34

    Slide Rack Mount Kit Installation Procedure 33 of 34

    Publication Number: 53-0001625-06

    Figure 28 Method B for Securing Rack Mount Brackets for Square-hole Cabinet Rails

    scale: 3/8" = 1"

    Cabinet Rail(non-port side)

    OuterSlide Rail

    (closed end on port side)

    Inner

    Slide Rail

    Switch

    (non-port side)

    3.026

    F

    H

    F

    G

    (3x)

    (2x)

    O

    (previously installed)