13 www.swegon.com We reserve the right to alter specifications. Sky Wing Power Roof Ventilator 20060501 Sky Wing Quick Guide ....................................................................................................................... 14 General, Advantages of the Sky Wing .......................................................................... 15 Specification ...................................................................................................................... 16 Technical Description of the Sky Wing ............................................................................ 17 LTSA Roof duct .................................................................................................................. 19 Electrical and Control Equipment, Control Functions..................................................... 21 Sizing, Acoustic Data, Motor Data................................................................................... 30 Dimensions ........................................................................................................................ 33 Contents

Sky Wing - Swegon

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Sky Wing - Swegon

13www.swegon.comWe reserve the right to alter specifications.

Sky WingPower Roof Ventilator

20060501

Sky Win

g

Quick Guide ....................................................................................................................... 14General, Advantages of the Sky Wing .......................................................................... 15Specification ...................................................................................................................... 16Technical Description of the Sky Wing ............................................................................ 17LTSA Roof duct .................................................................................................................. 19Electrical and Control Equipment, Control Functions..................................................... 21Sizing, Acoustic Data, Motor Data ................................................................................... 30Dimensions ........................................................................................................................ 33

Contents

Page 2: Sky Wing - Swegon

14

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

0,1 0,2 0,3 0,4 0,5 1 2 3 4 5

1 500

1 000

400

300

200

100

40

040-1

040-2

060-1

060-2

090-1

090-2

090-3

400 1 000 2 000 3 000 4 000 10 000

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/s

Airflow, m3/h

General Survey Diagram

*) Refers to a fan with 4-pole motorr

Quick Guide

Size Length Width Height Max. Weight*

LTCW040 495 495 430 46kg

LTCW060 695 695 600 85kg

LTCW090 995 995 850 200kg

Size Fan Motor Max. Available impeller poles kW flow pressure, m3/s Pa

LTCW040 1 4 0,25 0,22 150 LTCW040 2 4 0,25 0,45 240

LTCW060 1 4 1,1 1,1 420 LTCW060 1 6 0,75 0,75 180

LTCW060 2 4 1,5 1,8 580 LTCW060 2 6 0,75 1,2 260

LTCW090 1 4 2,2 3,1 820 LTCW090 1 6 1,5 2,1 370 LTCW090 1 8 0,75 1,6 210

LTCW090 2 4 3 3,6 910 LTCW090 2 6 1,5 2,5 410 LTCW090 2 8 1,1 1,8 230

LTCW090 3 4 7,5 5,4 1200 LTCW090 3 6 3 3,5 520 LTCW090 3 8 2,2 2,7 300

Design DataDimensions and Weights

Length

Width

Hei

ght

*) Equipped with the largest impeller and heaviest motor.

Page 3: Sky Wing - Swegon

15www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Duringthemiddleofthe1990sSwegonintroducedthenewWingaxi-centrifugalfanintotheGOLDairhandlingsystem.Sincethen,thistypeoffan,ofpatenteddesign,hasundergonefurtherdevelopmentandhasbeenusedtoaneverincreasingextentinourproductmix.

Swegonhasnowalsoreneweditsrooffanseries.Byin-troducingthenewSkyWing,alltheadvantagestheWingfanshavetoofferareutilizedinthissectorofourproductmixaswell,offeringmaximumbenefittoclients.Wingfeaturesincludelowfan-generatednoiselevel–especiallyinthelowerfrequencies,whicharemostdifficulttoat-tenuateinventilationsystems.

Thefaniswell-suitedforspeedcontrolandthereforeconformstomarketdemandsonadjustingtheairflowtomeetpresentneeds.

Advantages of the Sky WingThe Wing fan impeller offers quiet and energy-saving performance.

Its high discharge capacity allows for large duct systems and connected functional sections.

Enables demand-controlled ventilation by con-trolling the fan speed, keeping the air pressure constant and compensating variations in outdoor air temperature.

Service-friendly – the fan can be raised on hinges and has a removable upper section as well as removable side panels.

Measurement tappings for pressure/airflow read-ings enable correct commissioning and periodic performance checks.

Its modest design fits well in a variety of environ-ments.

Operates quietly and saves on energy

Tips!ThankstoitshighdischargecapacitytheSkyWingcanbeusedasanextractairfaninventilationsystemswithheatrecovery–eitherwithcoilheatexchangersinaliquid-coupledheatrecov-erysystemorinventilationsystemswithanextractairheatpump.

Page 4: Sky Wing - Swegon

16

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Roof duct for ventilator LTSA-1-aaa

Size 040 060 090

Mounting frame LTSZ-A-aaaJointing duct LTSZ-B-aaaBottom duct LTSZ-C-aaaBlank cover LTSZ-E-aaaAutomatic shutter LTSZ-F-aaaLouvre damper, type 3 LTSZ-J-aaa-3 Size 040 060 090

Mechanical Accessories

Sky Wing power roof ventilator LTCW-1-aaa-b-c-d-e-f

Size 040 =040 060 =060 090 =090

Fan impeller 1 =1 2 =2 3(foraaa=090only) =3

No. of poles 4 =4 6(notforaaa=090) =6 8(foraaa=090only) =8

Voltage 3x230/400V =1 3x400/690 =2 3x500V =3 3x230/400VThermostatic =8 contacts(notrequiredifTBCW controlsystemisfitted)

Motor Standard =1 Fire-proofversion =2

Pressure tappings, fitted Without =0 With =1

Control System

Protective motor contactor, enclosed (Q1) TBCW-101-aaaForconstantspeed

Ratedcurrent 0,63-1,0A =010 1,0-1,6A =016 1,6-2,5A =025 2,5-4,0A =040 4,0-6,3A =063 6,3-9,0A =090 9,0-12,5A =125 12,5-16,0A =160 20,0-25,0A =250

Control Equipment TBCW-12-a-bb-c-ddForcontrollingthefanspeed

Controlfunction Q2 =2 Q3 =3 Q4 =4 Q5 =5

Max.permissiblemotoroutput 0.75kW=07 1.1kW=11 1.5kW=15 2.2kW=22 3.0kW=30 7.5kW=75

Frequencyinverter unmounted =0 mounted =1 (notapplicabletoLTCW-040-2)

PressureControl Nopressurecontrol =00 (Q2andQ3only) 0-300Pa =03 0-500Pa =05 0--1000Pa =10 0--1600Pa =16

Frequencyinverter,0.37-1.5kW,1x230Vin,3x230VoutFrequencyinverter2.2-7.5kW,3x400V

Control panel KPA-1-200

Timer, 0-2 hours TBLZ-1-406-a

Surface-mounted=1 Flush-mounted=2Safety switch ELQZ-1-401-01

Control System Accessories

Specification

Page 5: Sky Wing - Swegon

17www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Range of ApplicationTheSkyWingisanextractairfan,designedforuseinmostextractairsystems,inwhichtheairhasalowcon-tentofimpurities.

ThefanshouldpreferablybemountedonanLTSAroofduct.Thisprovidesafire-resistantandsound-absorbentextractionpassagethroughtheroofandatightconnec-tiontotheextractairduct.

DesignTheSkyWingismadeofaluminium-zincplatedsheetsteelandhasandexternalcasingmadeofblackPrelacpaintedsheetmetal.Othercoloursareavailabletospecialorder.Fromananti-corrosionaspect,theSkyWingcom-plieswiththeprovisionsofEnvironmentalClassC4inac-cordancewithBSK99andSS-EN-ISO12944-2Standards.

ThefanimpellerisofSwegon’spatentedWingtypewithaxi-centrifugalthroughput.Characteristicsareextremelylownoiselevelandinsignificantsystemlosses.Thedesignofthefanandthewayitissuspendedinthecasingalsoenableanextremelylowlevelofvibration.

Thefancanberaisedonhingesforthebestpossibleac-cessforcleaningtheductsystemorcleaningtheimpeller,forexample.Theupperpartofthehoodcaneasilyberemovedforaccesstothemotor.

Ondelivery,thefanisequippedwithliftinglugs,thatshouldberemovedafterlifting.

MotorsThemotorsinstalledintheSkyWingareflangemotorswithspecificationstoIECStandard.TheyconformtodegreeofprotectionIP55.

Themotorisfittedoutsidetheairflowandiseasilyac-cessibleforwiring,cleaningandservicing.Thehighestpermissibleambienttemperatureforstandardmotorsis+40°C.Thetechnicaldetailsspecifiedareapplicabletotheratedvoltageandratedfrequency.Themotorsarenormallysuppliedfora3-phase230/400Vpowersupplywithoutthermostaticcontacts;howevertheycanalsobesuppliedwithsuch,aswellasfora3-phase500Vpowersupply.

SizesTheSkyWingpowerroofventilatorisfabricatedinthreephysicalsizes:040,060and090.Bycombiningvarioussizesofimpellerandmotor,apressure/flowrangeof0.1–5.0m3/scanbeachieved.

Pressure/flow measurementsThepowerroofventilatorisequippedwithexternaltap-pingsforpressure/airflowmeasurementwithaninaccu-racyof±5%.

The Sky Wing is supplied with lifting lugs/handles. They can be easily removed and refitted.

The Sky Wing is easy to inspect and clean. The upper section is simple to remove and mounted on the roof duct, the power roof ventilator can also be opened by raising it on its hinges.

Technical Description

Page 6: Sky Wing - Swegon

18

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

To the right: Certificate based on fire-resistance test conducted by the Emer-gency (SOS) Service in Finspång, Sweden.Below: Excerpt from the Test Report.

The Sky Wing units are tested for fire resistance.ForapplicationsinwhichtheSkyWingpowerroofventilatormustbecapableoftransportingairwithhigher-than-normaltemperatureforalimitedperiod,theven-tilatorcanbeorderedwithaspecialmotordesignedtooperateunderhightemperatureconditions.Thepurposeofthisversionistoenableoccupantstosafelyevacuateaburningbuilding,byusingtheventilatorforsmokeandcombustiongasextraction.Ventilatorsinthehightemper-atureversionaretestedforfireresistanceandwithstand300°Cforthreehours,providedthattheyarenotoper-atedatspeedshigherthantheirmax.permissiblespeed.SeeTablebelow.

Fan size Max. permissible fan speed 060-1 2000r/min.060-2 1670r/min.090-1 1420r/min.090-2 1420r/min.

090-3 1470r/min.

Important! Does not apply to ventilators with built-in control equipment.

Technical Description

Description of Test with Combustion-gas Fan

Test of an LTCW-1-060-1-4-1 Power roof ventilator, in the combustion-gas version, Order no. 204 825

The test was conducted in the Emergency (SOS) Service container facilities at the Flampunkten (Flash-point) Testing Ground. The fan was mounted on a container that is connected to a fire caisson made of steel surrounded by cement stone. The fan was wired to a three-phase power supply and was started up. Pallets were burned inside the caisson and a type TM-916 temperature gauge was used for continuously measuring the temperature.The fan operated throughout the heating period (see Appendix 1). When the temperature reached 300 degrees Celsius, test events were timed until 120 minutes had elapsed. Throughout the period, we sought to obtain smallest possible differences.(See Appendix 2)

When 120 minutes had elapsed, Test no. 2 started and this involved keeping the temperature at about 400 degrees Celsius for 60 minutes.Maintaining a constant temperature of 400 degrees proved difficult since we obtained substantial differences in temperature.It is quite clear to us that the fan has passed the test, among other factors, because the temperature was up to 475 degrees at the most and because the fan had managed to operate for 120 minutes impelling 300-degree gas during the previous test.(See Appendix 3)In our opinion, the fan managed to operate for 180 minutes impelling 300-degree-Celsius gas during the first test since the temperature was considerably higher during the last 60 minutes.

Date: Oct. 22, 2003

PM-LUFT ABKoppargatan 19602 23 Norrköping, Sweden

For the attention of: Keit Ohlsson

CERTIFICATE

The combustion-gas resistant power roof ventilator was tested on Oct. 7, 2003Model LTCW-1-060-1-4-1, Order no. 204 825

The ventilator was able to discharge gas having a temperature of 300 degrees Celsius for 180 minutes without problems.

The ventilator was able to discharge gas having a temperature of 400 degrees Celsius for 60 minutes without problems.

Jan KarlssonAssistant Chief

Address: Emergency (SOS) Service, Bergslagsvägen 21, 612 30 FinspångPhone: Switchboard 0122-850 80, Direct phone: 0122-850 79, Mobile: 070 338 54 14, Fax: 0122-151 33

E-mail: [email protected]

Page 7: Sky Wing - Swegon

19www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

LTSA

LTSZ-B

LTSZ-C

LTSZ-A

Range of ApplicationTheLTSAductisaroofductthatcanbeusedasaventila-tionchimneyfortheLTCWpowerroofventilator.

Theroofductisasimpleandinexpensivealternativetoasite-fabricatedchimneymadeofsomeotherbuildingmaterial.

Itissound-attenuatingandthereforereducesthenoiselevelintheventilationchimney.

Theroofductcanbefittedamongotherfixtureswithajointingductandbottomduct(seeextraaccessories).

DesignTheLTSAroofductconsistsofagalvanizedsheet-steelduct,internallyinsulatedwith50mmthickmineralwoolslabsandlinedwithperforatedsheetsteel.TheinsulationmeetstheprovisionsofFire-resistanceClassEI30.

Theductisequippedwithpivotablemountingbracketsontwosides.Theanglebracketscanbepositionedtosuittheslopeoftheroof.

Theductisequippedwithacableconduit.

Extra AccessoriesMountingframe LTSZ-AJointingduct LTSZ-BBottomduct LTSZ-CBlankcover LTSZ-E (fortheLTSZ-Cbottomduct)Automaticshutter LTSZ-FLouvredamper,type3 LTSZ-J

LTSA Roof duct

Page 8: Sky Wing - Swegon

20

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Installation Examples1. 50mmthickinsulationconformingto Fire-resistanceClassEI30,internallylinedwithperforatedsheetsteel.

2. Conduitforelectriccable.

3. Structuralpanel(notsuppliedbySwegon).

4. Roofingfelt,sheetsheelorsimilarweather-proofroofingmaterial(notsuppliedbySwegon).

5. Pivotablemountingbrackets.

6. Existingroofingmaterial (notsuppliedbySwegon).

7. LTSZ-FAutomaticshutterthatautomaticallyopenswhenthefanisoperating. Automaticallyshutsifthefanstopstopreventcolddown-flowaircurrents.8. LTSZ-BJointingduct,LTSZ-BBottomduct,LTSZ-JLouvredamperorExtractairduct.

LTSA Roof duct

Page 9: Sky Wing - Swegon

21www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

KPA-1-200 Control panel

Several different control equipment options are available. The frequency inverter can be mounted inside the fan casing of the size 060 and 090

roof ventilators.

Electrical and Control EquipmentTheventilatorisproducedasstandardwithasingle-speedmotor.Ifspeedcontrolisnotdesirable,theventilatorshouldbewiredacrossanenclosedTBCW-101protectivemotorcontactor,(Q1starter).

Fan-speedcontrolfunctionsQ2,Q3,Q4andQ5areavail-ableforadjustingtheairflowtomeetcurrentneeds.

TheKPA-1-200controlpanelisusedforsettingallthesetpointsandparameters.Sincethispanelisonlyusedforprogramminginconjunctionwithcommissioningandiftheoperatingconditionschange,onlyoneisrequiredforeachventilationsystem.

Ifanotheritemofequipmentisusedforspeedcontrol,theventilatorcanbesuppliedwithbuilt-inthermostaticcontactsinthemotorwindingsformaximalprotection,ifrequired.

Control EquipmentAnumberofalternativesolutionsareavailableforcontrol-lingtheSkyWingpowerroofventilator.Thealternativesaresummarizedbelow.Aoredetaileddescriptionisgiveninthenextsectionentitled:ControlEquipment.

Equipment variant Q1Inthesimplestapplications,theventilatorcanbewiredtothepowersupplyacrossanenclosedprotectivemotorcontactor.

Equipment variant Q2Thecontrolsystemwithfrequencyinverter,programmedforoneconstantspeedortwoconstantspeeds(high-speedorlow-speedfanperformance).

Equipment variant Q3Thecontrolsystemwithfrequencyinverter,programmedforvariablespeedinresponsetoa0–10Vsignalorviaanexternalpotentiometer.

Equipment variant Q4Controlsystemwithfrequencyinverter,programmedforpressurecontrol.

Equipment variant Q5Controlsystemwithfrequencyinverter,programmedforoutdoorairtemperaturecompensatedpressurecontrol.

Thefrequencyinvertercaneitherbesuppliedfittedinsidetheroofventilatorcasing(sizes060and090only)orlooseforinstallationatanoptionallocationinthebuild-ing.Anextraprotectiveroofisalwayssuppliedwiththeroofventilatortoupgradethedesigntodegreeofprotec-tionIP21.Thefrequencyinverterpermitsuseunderambi-enttemperatureconditionsrangingfrom-20to+50°C.

Important! Wiring to a 230 V mains supplyIftheunitiswiredtoa230Vmainssupply,controlequip-mentvariantsQ2,Q3,Q4orQ5canbeusedonlyifthefanmotoroutputis1.5kWorlower.Ifthemotoroutputishigher,adifferentexternalfrequencyinverter,oranexternaltransformermustbeused.

Electrical and Control Equipment

Page 10: Sky Wing - Swegon

22

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Control functionsQ1: Direct power roof ventilator connection via enclosed protective motor contactor

Electric Power Connections

G1

Q

FunctionG1=ExtractairfanQ=Starter

Start/stopviaexternaltimerorselectorswitch.Constantspeed.Alarmintheeventofexcesscurrent.

Powersupply:230,400or500V

Controlvoltage

Start

Alarms

In-operation

Indications

The components within the dashed box are included in the enclosed protective motor contactor.

F=OverloadprotectorG1=ExtractairfanP=IndicatinglampQ1=ContactorQ2=SafetyswitchS=Selectorswitch

Designations used are according to EN 61346-2:2000

Electrical and Control Equipment

Page 11: Sky Wing - Swegon

23www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Control functionsQ2: Control system with frequency inverter*, programmed for constant speed.(1- or 2-speed operation)

Electrical ConnectionsPowersupply(wiringterminalX1)

Controlfunctions(wiringterminalX2)

Powersupply,fanmotor

Alternative 1: 1-phaseIncomingpowersupply,1x230V (motors0.25-1.5kW)

Alternative 2: 3-phaseIncomingpowersupply, 3x400V (motors2.2-7.5kW)

Alarm outputActivealarms:closure19-20.

Normal positionNoalarm:closure18-19.

In-opera-tionindications

Max.48V/

1AAC

Earth,digital

24VDC,Imax.=50mA

Earth,digital(14↔ 17)

Start/Stop

Alarmreset,stand-by

24VDC, Imax.=200mA

Earth,analogue

Input2,analogue

Input1,analogue

Referencevoltage:10.5V;5mA

G1

T1*

FunctionG1=ExtractairfanT1=FrequencyinverterTheextractairfanisstartedandstoppedviafrequencyinverterT1*.Thedesiredspeed(s)canbepresetfromtheKP-1-200controlpanel.Oneortwoconstantspeeds.Startviaclosurebetween7-8and7-9.Speed1:7-10open.Speed2:7-10closed.Alarmscanberesetbybrieflyisolatingthepowersupplytotheventilatororbyinterruptingthecircuitatterminals7–8.Provisionisavailableforforwardingalarms.

*Thefrequencyinvertercaneitherbesuppliedmountedinsidethefancasing(size060and090)orlooseforindoorinstallation.Important!Ifitisinstalledindoors,ashieldedcablemustbeusedbetweenT1andG1.Toavoiddamagetothewiringterminalsofthefrequencyinverter,cableconductorsshouldnotbeconnectedifthetemperatureisbelow-10°C.

High/Low

Electrical and Control Equipment

Page 12: Sky Wing - Swegon

24

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Control functionsQ3: The control system with frequency inverter*, programmed for variable speed via 0 – 10 V signal or via an external potentiometer.

Electrical ConnectionsPowersupply(wiringterminalX1) Controlfunctions(wiringterminalX2)

Powersupply,fanmotor

Alternative 1: 1-phaseIncomingpowersupply, 1x230V (motors0.25-1.5kW)

Alternative 2: 3-phaseIncomingpowersupply, 3x400V (motors2.2-7.5kW)

Alarm outputActivealarms:closure19-20.Normal positionNoalarm:closure18-19.

In-opera-tionindications

Max.48V/

1AAC

Earth,digital

24VDC,Imax.=50mA

Earth,digital(14↔ 17)

Start/Stop

Alarmreset,stand-by

24VDC, Imax.=200mA

Earth,analogue

Input2,analogue

Input1,analogue

Referencevoltage:10.5V;5mA

0-10Vsignal

G1

T1*

FunctionG1=ExtractairfanT1=Frequencyinverter

Extractairfan,G1,iscontrolledbetween0andmax.speedviaanexternal0-10Vsignal,connectedG0toterminal4andsignaltoterminal2.

Startviaclosurebetween7-8and7-9.Thealarmcanberesetbyisolatingthepowersupplytotheventilatororbyopeningthecircuitbetween7-8.

Provisionisavailableforforwardingalarms.

*Thefrequencyinvertercaneitherbesuppliedmountedinsidethefancasing(size060and090)orlooseforindoorinstallation.Important!Ifitisinstalledindoors,ashieldedcablemustbeusedbetweenT1andG1.Toavoiddamagetothewiringterminalsofthefrequencyinverter,cableconductorsshouldnotbeconnectedifthetemperatureisbelow-10°C.

Electrical and Control Equipment

Page 13: Sky Wing - Swegon

25www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Control functions

0-10Vcontrol

Alternative 10-10Vcontrolsignal

Earth,analogue

Input2,notactivated

Input1,analogue0-10V

Referencevoltage:10.5V;5mA

Potentiometer,linear10kΩ.

(Shieldedcablemustbeused.)

Alternative 2Controlviapotentiometer

Earth,analogue

Input2,notactivated

Input1,analogue0-10V

Referencevoltage:10.5V;5mA

Continued, Q3, Alternatives

Electrical and Control Equipment

Page 14: Sky Wing - Swegon

26

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Control functionsQ4: The control system with frequency inverter*, programmed for pressure control.

Electrical ConnectionsPowersupply(wiringterminalX1) Controlfunctions(wiringterminalX2)

Powersupply,fanmotor

Alternative 1: 1-phaseIncomingpowersupply, 1x230V (motors0.25-1.5kW)

Alternative 2: 3-phaseIncomingpowersupply, 3x400V (motors2.2-7.5kW)

Alarm outputActivealarms:closure19-20.Normal positionNoalarm:closure18-19.

In-operationindications

Max.48V/

1AAC

Earth,digital

24VDC,Imax.=50mA

Earth,digital(14↔ 17)

Start/Stop

Alarmreset,stand-by

24VDC, Imax.=200mA

Earth,analogue

Input2,analogue

Input1,analogue

Referencevoltage:10.5V;5mA

G1

T1*

FunctionG1=ExtractairfanT1=FrequencyinverterBP1=Pressuretransmitter

Thespeedoftheextractairfan,G1,iscontrolledviaa4-10mAsignalfromactivepressuretransmitterBP1,connectedtoterminals6and2.Startviaclosurebetween7-8and7-9.Alarmscanberesetbybrieflyisolatingthepowersupplytotheventilatororbyinterruptingthecircuitattermi-nals7–8.Provisionisavailableforforwardingalarms.

BP1

*Thefrequencyinvertercaneitherbesuppliedmountedinsidethefancasing(size060and090)orlooseforindoorinstallation.Important!Ifitisinstalledindoors,ashieldedcablemustbeusedbetweenT1andG1.Toavoiddamagetothewiringterminalsofthefrequencyinverter,cableconductorsshouldnotbeconnectedifthetemperatureisbelow-10°C.

Electrical and Control Equipment

Page 15: Sky Wing - Swegon

27www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Control functions

Control via external pressure transmitter

Analogueinput1canbereprogrammedwithparameter180to0-10Vor0-20mAforuseofanotherpressuretransmitter.

Continued, Q4, Alternatives

Pressuretransmit-ter,BP1;4-20mAReginDTLa-420

Input1,analoguein4-20mA

Electrical and Control Equipment

Page 16: Sky Wing - Swegon

28

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Control functionsQ5: The control system with frequency inverter*, programmed for outdoor temperature-compensated pressure control.

Electrical ConnectionsPowersupply(wiringterminalX1) Controlfunctions(wiringterminalX2)

Powersupply,fanmotor

Alternative 1: 1-phaseIncomingpowersupply, 1x230V (motors0.25-1.5kW)

Alternative 2: 3-phaseIncomingpowersupply, 3x400V (motors2.2-7.5kW)

Alarm outputActivealarms:closure19-20.Normal positionNoalarm:closure18-19.

In-operationindications

Max.48V/

1AAC

Earth,digital

24VDC,Imax.=50mA

Earth,digital(14↔ 17)

Start/Stop

Alarmreset,stand-by

24VDC, Imax.=200mA

Earth,analogue

Input2,analogue

Input1,analogue

Referencevoltage:10.5V;5mA

G1

T1*

BP1

BT1

FunctionG1=ExtractairfanT1=FrequencyinverterBP1=PressuretransmitterBT1=Outdoortemperaturesensor

Thespeedoftheextractairfan,G1,iscontrolledviaa4-10mAsignalfromactivepressuretransmitterBP1,connectedtoterminals6and2.Thesetpointisoutdoor-temperature-compensatedbe-tweeen-25°Cand+25°C.Connecttheoutdoortemperaturesensor,BT1,conductorstoterminals6,4and3.Startviaclosurebetween7-8and7-9.Alarmscanberesetbybrieflyisolatingthepowersupplytotheventilatororbyinterruptingthecircuitatterminals7–8.Provisionisavailableforforwardingalarms.

*Thefrequencyinvertercaneitherbesuppliedmountedinsidethefancasing(size060and090)orlooseforindoorinstallation.Important!Ifitisinstalledindoors,ashieldedcablemustbeusedbetweenT1andG1.Toavoiddamagetothewiringterminalsofthefrequencyinverter,cableconductorsshouldnotbeconnectedifthetemperatureisbelow-10°C.

Electrical and Control Equipment

Page 17: Sky Wing - Swegon

29www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Control functions

Control via external pressure transmitter Outdoor temperature compensation of the pressure set point.

Analogueinput1canbereprogrammedwithparameter180to0-10Vor0-20mAforuseofanotherpressuretransmitter.

Continued, Q5, Alternatives

Pressuretransmit-ter,BP1;4-20mAReginDTLa-420

Input1,analogue4-20mA

BT1outdoortem-peraturesensor0-10V

Electrical and Control Equipment

Page 18: Sky Wing - Swegon

30

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 0,25 1,2/0,69 1400(2930) 65,2 3x230∆/3x400star

*()=Max.speedwithfrequencyinverter.

Correction factor Kok for various sound paths and for calculating the sound pressure level in dB(A) to the surroundings.

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Acoustic CalculationsThesoundpowerlevelemittedtothesurroundingshasbeenobtainedfrommeasurementsinaccordancewiththeISO3741methodandthesoundpowerlevelemittedtotheductinghasbeenobtainedfrommeasurementsinaccordancewiththeISO5136method.

ThetotalThetotalsoundpowerlevelemittedtothesurround-ings,LW,totcanbereadineachfanchart.Thefollowingformulacanbeusedforbreakingdownthetotalsoundpowerlevelintooctavebands:Lw,ok=Lw,tot+Kok.Fromthetablebelow:Kok.

dB(A)correctedsoundpowerleveltothesurroundingscanbecalculatedusingthefollowingformula:LwA=Lw,tot+KA.

4-pole

Max. speed 4-pole = 2930 rpm

Range Octaveband,no./mid-frequency,Hz

Soundpath in 1 2 3 4 5 6 7 8 dB

chart 63 125 250 500 1000 2000 4000 8000 (A)

Tothe 1 -7 -6 -5 -9 -9 -13 -20 -24 -5surroundings 2 -17 -13 -11 -5 -3 -12 -23 -19 -1 Tothe 1 -11 -6 -5 -12 -16 -11 -13 -20theduct 2 -9 -13 -11 -5 -7 -11 -10 -15

Motor Data

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

4-pole

Max. speed 4-pole = 2000 rpm

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 0,25 1,2/0,69 1400(2000) 65,2 3x230∆/3x400star

*()=Max.speedwithfrequencyinverter.

Motor Data

Important! SkyWing,size040,cannotbesuppliedwithbuilt-infrequencyinverter.

Sizing, Size 040

Page 19: Sky Wing - Swegon

31www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

6-pole

4-pole

Max. speed 4-pole = 1670 rpm

Max. speed 6-pole = 1320 rpm

6-pole

4-pole

Max. speed 4-pole = 2000 rpm

Max. speed 6-pole = 1760 rpm

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 1,1 4,35/2,511440(2000) 77 3x230∆/3x400star

6-pole 0,75 3,35/1,95 910(1760) 72 3x230∆/3x400star

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Motor Data

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Motor Data

Octaveband,no./mid-frequency,Hz

Soundpath 1 2 3 4 5 6 7 8dB

63 125 250 500 1000 2000 40008000(A)

Tothesurroundings -7 -6 -5 -9 -9 -13 -20 -24 -5 Totheducting -11 -6 -5 -12 -16 -11 -13 -20

Correction factor Kok for various sound paths and for calculating the sound power level in dB(A) emitted to the surroundings.

Acoustic CalculationsThesoundpowerlevelemittedtothesurroundingshasbeenobtainedfrommeasurementsinaccordancewiththeISO3741methodandthesoundpowerlevelemittedtotheductinghasbeenobtainedfrommeasurementsinaccordancewiththeISO5136method.

ThetotalThetotalsoundpowerlevelemittedtothesurround-ings,LW,totcanbereadineachfanchart.Thefollowingformulacanbeusedforbreakingdownthetotalsoundpowerlevelintooctavebands:Lw,ok=Lw,tot+Kok.Fromthetablebelow:Kok.

dB(A)correctedsoundpowerleveltothesurroundingscanbecalculatedusingthefollowingformula:LwA=Lw,tot+KA.

*()=Max.speedwithfrequencyinverter.

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 1,5 5,51/3,181420(1670) 80,5 3x230∆/3x400star

6-pole 0,75 3,38/1,95 910(1320) 72 3x230∆/3x400star

*()=Max.speedwithfrequencyinverter.

Thesize060SkyWingcaneitherbesuppliedwithbuilt-inorloosefrequencyinverter.

Sizing, Size 060

Page 20: Sky Wing - Swegon

32

Sky Wing

www.swegon.comWe reserve the right to alter specifications. 20060501

Max. speed 8-pole = 1020 rpm

Max. speed 6-pole = 1130 rpm

6-pole

8-pole

4-pole

6-pole

8-pole

4-pole

Max. speed 6-pole = 1250 rpm

Max. speed 8-pole = 990 rpm Max. speed 8-pole = 1060 rpm

Max. speed 6-pole = 1170 rpm

6-pole

8-pole

4-pole

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 3 10,3/5,941420(14201) 83,5 3x230∆/3x400star

6-pole 1,5 7,45/4,3 940(1130) 77,5 3x230∆/3x400star

8-pole 1,1 5,7/3,3 700(1020) 74 3x230∆/3x400star

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/s

Airflow, m3/h

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Motor Data

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

Airflow, m3/s

Range Octaveband,no./mid-frequency,Hz

Soundpath in 1 2 3 4 5 6 7 8 dB

chart 63 125 250 500 1000 2000 4000 8000 (A)

Tothe 1 -10 -10 -12 -3 -8 -15 -19 -19 -5surroundings 2 -7 -6 -5 -9 -9 -13 -20 -24 -5 Tothe 1 -8 -8 -10 -8 -13 -15 -19 -14theduct 2 -11 -6 -5 -12 -16 -11 -13 -20

Correction factor Kok for various sound paths and for calculating the sound power level in dB(A) emitted to the surroundings.

Acoustic CalculationsThesoundpowerlevelemittedtothesurroundingshasbeenobtainedfrommeasurementsinaccordancewiththeISO3741methodandthesoundpowerlevelemittedtotheductinghasbeenobtainedfrommeasurementsinaccordancewiththeISO5136method.

ThetotalThetotalsoundpowerlevelemittedtothesurround-ings,LW,totcanbereadineachfanchart.Thefollowingformulacanbeusedforbreakingdownthetotalsoundpowerlevelintooctavebands:Lw,ok=Lw,tot+Kok.Fromthetablebelow:Kok.

dB(A)correctedsoundpowerleveltothesurroundingscanbecalculatedusingthefollowingformula:LwA=Lw,tot+KA.

*()=Max.speedwithfrequencyinverter.1)Max.frequencyfromfrequencyinverteroutto4-polemotor:50Hz.

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 2,2 7,87/4,541420(14201) 83 3x230∆/3x400star

6-pole 1,5 7,45/4,3 940(1250) 77,5 3x230∆/3x400star

8-pole 0,75 4,0/2,33 700(990) 72,6 3x230∆/3x400star

Motor Data

Motor Motor Max. Speed Effi- Voltage option output current - ciency kW A r/min.* % V

4-pole 7,5 14,2 1470(14701) 88,6 3x230∆/3x400star

6-pole 3 12,1/7 935(1170) 82,5 3x230∆/3x400star

8-pole 2,2 9,4/5,4 710(1060) 84 3x230∆/3x400star

Motor Data

*()=Max.speedwithfrequencyinverter.1)Max.frequencyfromfrequencyinverteroutto4-polemotor:50Hz.

*()=Max.speedwithfrequencyinverter.1)Max.frequencyfromfrequencyinverteroutto4-polemotor:50Hz.

Sizing, Size 090

Page 21: Sky Wing - Swegon

33www.swegon.comWe reserve the right to alter specifications.

Sky Wing

20060501

Sky Win

g

Size Length Width Height Maxweight

LTCW040-1 495 495 430 44kgLTCW040-2 495 495 430 46kg

LTCW060-1 695 695 600 80kgLTCW060-2 695 695 600 85kg

LTCW090-1 995 995 850 145kgLTCW090-2 995 995 850 155kgLTCW090-3 995 995 850 200kg

Length

Width

Hei

ght

Accessories

Roof duct

LTSA

Jointing ductLTSZ-B

Bottom ductLTSZ-C

Mounting frameLTSZ-A

Automatic shutterLTSZ-F

Louvre damper, type 3LTSZ-J

Size B B1 B2 C D E Weight LTSA LTSZ-C LTSZ-B

040 400 300 412 167 203 –* 29 12060 600 500 612 167 203 290 46 21

090 900 800 912 167 203 400 63 40

*) Size 040 has 1 connection on each side, centred sideways.

Dimensions

Page 22: Sky Wing - Swegon