Page 1: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen Draft1 © Nokia Siemens Networks

SiteStar CabinetTechnical slides

Marko P. Komulainen

June 11th, 2009

Page 2: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft2 © Nokia Siemens Networks

Introduction

• Background and Challenges– Battery lifetime is strongly affected by operating ambient temperature

with cycles Rule of thumb is that every 10C increase on operating temperature will halve

battery lifetime

– Standard power system cooling solutions are always not the most optimal in cost and energy efficiency Cost optimization and energy efficiency benefits lost due to heat load inside

the cabinets

– Traditional cabinet structure not the most optimal in thermal conductivity Single wall, single wall w/ thermal insulation, double wall w/ air gap Sun load impact noticeable at high operational temperatures

Page 3: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft3 © Nokia Siemens Networks

System Overview

FPRA Flexi Power Rectifier

Cable entry

Mains connections

Climate Control Unit

Batteries

Page 4: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft4 © Nokia Siemens Networks

Cabinet Overview

• Cabinet installation on top of the plinth• HE compressor cooling• Operating temperature range -40C to +50C• Cabinet internal temperature

• Constant +20C • With ’ECO mode’ between +15C…+25C

• Ingress protection class IP55• Power consumption <40W (typical @ +35C)• Dual skin construction with foam insulation• Cable entry at bottom on side wall• AC connection at cabinet bottom• Single alarm output from Climate Control Unit• Primarily used with FPRA Flexi Power Rectifier• Door locked with two screws and screw openings

covered with lock cylinders• Right or Left door handedness

Page 5: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft5 © Nokia Siemens Networks

Cabinet (1.8m)

1500mm

588mm

585mm

345mm

• Empty cabinet weight ~95kg

• Battery capacity up to 4 strings of 170Ah

• Cabinet dimensions (WxDxH)– External dimensions

660x780x1794mm (excl. plinth)

– Internal dimensions 588x585x1500mm

– Individual battery shelf space 588x585x345mm

660mm

780mm

1794mm

Page 6: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft6 © Nokia Siemens Networks

Cabinet (1.1m)

TBCmm

588mm

585mm

345mm

• Empty cabinet weight TBCkg

• Battery capacity up to 2 strings of 170Ah

• Two cabinets stackable

• Cabinet dimensions (WxDxH)– External dimensions

660x780x1094mm (excl. plinth)

– Internal dimensions 588x585xTBCmm

– Individual battery shelf space 588x585x345mm

660mm780mm

1094mm

Page 7: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft7 © Nokia Siemens Networks

Cabinet Plinth

• Cabinet must always be mounted on top of the plinth

• Cabinet must always be lifted plinth mounted– Plinth is delivered as a part of cabinet (pre-installed)

• Plinth is made from hot dip galvanized steel

• Dimensions 660 x 573 x 50mm (W x D x H)

• Weight 6.5kg

Page 8: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft8 © Nokia Siemens Networks

Cabinet Construction

• Dual skin construction and special manufacturing process with thermal insulation between the walls– 37mm polyurethane foam

insulation Thermal conductivity 0,02W/mK

– Minimized ambient temperature impact to cabinet interior

• Cabinet material– Outer liner galvanized powder

painted steel

– Inner liner unpainted Alu Zink steel

Outer liner

Inner liner

Condenser

Compressor compartment

PUR insulation

Page 9: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft9 © Nokia Siemens Networks

Cabinet Climate Management

• SiteStar cabinet climate units are placed in the cabinet door

• Internal and external airflows mechanically separated

• Cabinet interior fully closed looped

• The cooling air generated is distributed by means of fan

• The high performance climate system combined with the high performance cabinet structure will enable to keep a +15…+25C internal temperature even up to +50C ambient

Page 10: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft10 © Nokia Siemens Networks

Climate Control Unit

• Climate control unit locates at bottom on a cabinet door

• Unit have four LED’s for information – ‘Eco’ to indicate ECO mode status; enabled (GREEN) / disabled (LED OFF)

– ‘Operational’ to indicate cooling system is running (GREEN)

– ‘Test’ to indicate self-test ongoing (YELLOW) and self-test completed (LED OFF)

– ‘Fault’ to indicate any fault or alarm on climate control unit (RED)

• CCU alarms are combined into a one common alarm output send via the D9 Ext alarm connector – External alarm is triggered by compressor/heater/fan/controller fail, high/low internal

temperature, high external temperature, door open and mains failure

– Alarm cable one end is unterminated allowing either NC or NO connection inside FPRA Pin1 – NO, Pin2 – NC, Pin3 – Common

Door switch

Power inlet

Door inner surface

Page 11: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft11 © Nokia Siemens Networks

Cable Entry

• Cabinet cable entry space locates at bottom on side wall– Cable entry plate assembly delivered separately inside the cabinet

• Cable entry can be installed either left or right sides

• Multigate is metal reinforced plate made from various types of polymers– Ingress protection IP55

– Flame resistance UL94; V-0

• Cable diameters supported– 8 x 10-30mm

– 2 x 7-12mm

Page 12: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft12 © Nokia Siemens Networks

SiteStar – Electrical Specification

• SiteStar cabinet have a different version for nominal voltages of 230VAC and 115VAC

• Mains AC connection support different connection options– Single phase

– Three phase

– Between the phases

Nominal input voltage (AC)

Voltage tolerance

Frequency (Hz)

Frequency tolerance

Input fuse rating (A)

230VAC ± 15% 50Hz -5%...+10% 2.5A

115VAC ± 15% 60Hz -5%...+10% 5A

Page 13: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft13 © Nokia Siemens Networks

SiteStar – Power Consumptions

Power ConsumptionsBattery system on float charge

Ambient temp. 20C/20C inside’ECO’ OFF

25C/15C inside’ECO’ ON

+55 C 158 W 132 W

+45 C 96 W 74 W

+35 C 50 W 39 W

+25 C 16 W 16 W

+20 C 16 W 16 W

+10 C 28 W 16 W

0 C 63 W 47 W

-10 C 99 W 79 W

-20 C 133 W 110 W

-30 C 169 W 142 W

-40 C 206 W 174 W

Typical

Page 14: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft14 © Nokia Siemens Networks

Optional HW Installation Kits

• There are two different optional HW installation kits provided– Roof rail kit (2 rails on top and one side wall rail)

Allowing FPRA Flexi Power Rectifier installation on top of the cabinet• FMFA Flexi plinth is needed as an installation base

Includes a lone ong side wall rail for cable support

– Side wall rail kit (4 rails, 2 rails for both sides) Allowing Flexi BTS module installation to cabinet

side walls• Max up to 6 modules / side

• FMFA Flexi plinth is needed as an installation base

Page 15: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft15 © Nokia Siemens Networks

SiteStar & FPRA Flexi Power Rectifier

• FPRA Flexi Power Rectifier is a primary power system to be used with SiteStar

• FPRA can be installed on top of the cabinet or together with Flexi BTS modules into a separate stack/cabinet etc outside the SiteStar cabinet

• FPRA distance to SiteStar is limited by temperature sensor length of 3m to have battery thermal control in place

• Battery cables will be fed directly from FPRA into the individual battery strings inside SideStar– Cables must be provided locally due to multiple mounting

locations of FPRA

• SiteStar alarms are connected and forwarded via FPRA

• SiteStar mains connection point at cabinet bottom can be used to share mains feed to FPRA if both not fed separately from site main distribution board

Page 16: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft16 © Nokia Siemens Networks

Battery Cabling Principle

• Up to 3 battery strings can be fed directly from FPRA to the individual strings

• In case of 4th battery string is required an additional DCCU plate is needed– DCCU plate will provide bigger fuses

allowing chaining of 3rd and 4th strings

• DCCU plate will be installed at cabinet bottom next to mains AC terminals– DCCU plate comes with 3 x 100A fuses

• Battery outputs from FPRA will be connected to DCCU fuses and Common and further to battery strings

From FPRA

DCCU plate

Mains terminals

Page 17: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft17 © Nokia Siemens Networks

FPRA Flexi Power Rectifier – Overview

• FPRA has the same conceptual approach like any Flexi BTS platform products– 3U high chassis build up from IP54 building blocks (rectifier and controller)

– Final IP55 protection achieved with front and rear covers (same covers as used with FlexiBTS)

– Same FPRA unit used both indoor and outdoor environments Indoor and any outdoor cabinet installations without front/rear covers Outdoor stand alone installations (wall/pole/stack) with front/rear covers mounted

– Back to Front airflow like on FlexiBTS modules

• No air filters => reduced maintenance needs => lower OPEX

• No special system specific SW needed– Only web browser needed for local connection to make the commissioning

• Output power scaleable from 2kW to 6kW (3 x 2kW)

• No space for batteries inside like on FPMA

Page 18: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft18 © Nokia Siemens Networks

FPRA Flexi Power RectifierCase with integrated DC distribution for rectifiers (provides IP55 protection to controller and rectifier modules when fitted with Flexi front/rear covers)

IP54 Rectifier Module

IP54 PDA unit incl. controller and distribution (delivered with case)

FPRA with/without Flexi Covers (FMCA)

Page 19: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen Draft19 © Nokia Siemens Networks

Configuration and Site Examples

Page 20: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft20 © Nokia Siemens Networks

SiteStar Cabinet Configuration Examples

Small cooled battery cabinetwith FPRA

Small cooled battery cabinetsstacked with FPRA

Tall cooled battery cabinet with FPRA

FPRA

FPRA

FPRA

Page 21: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft21 © Nokia Siemens Networks

Site Configuration Examples #1

Small cooled battery cabinetwith FPRA and FCOA cabinet

Tall cooled battery cabinet withFCOA cabinet including FPRA

Small cooled battery cabinet withFCOA cabinet including FPRA

Tall cooled battery cabinetwith FPRA and FCOA cabinet

FPRA

FPRA

FPRA

FPRA

Page 22: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen / Draft22 © Nokia Siemens Networks

Site Configuration Examples #2

Small or tall cooled battery cabinet with FPRA and stacked Flexi BTS Tall cooled battery cabinet with FPRA

and side mounted with Flexi BTS

FPRA

FPRA

Page 23: SiteStar Technical Slides

Soc Classification level Marko P. Komulainen Draft23 © Nokia Siemens Networks

Thank You