32
Single Duct Terminal Units

Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

Single Duct Terminal Units

Page 2: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

On the coverIntegrated professional services designed for your unique business need.

We care about your business and understand that each business has its unique requirements. Our all-encompassing maintenance package is tailor-made to fit your every financial and technical need. It covers from planned routine equipment inspections and predictive maintenance routines to system performance checks and annual shutdowns.

Page 3: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

3

A VAV Controller System Preview............................................................................................................................................... 4

1 Benefit from The Johnson Controls VAV Unit ............................................................................................................................ 4

1.1 For the Property Owner................................................................................................................................................................ 4

1.2 For the Architect ......................................................................................................................................................................... 4

1.3 For the Consulting Engineer......................................................................................................................................................... 4

1.4 For the Mechanical Contractor .................................................................................................................................................... 4

2 Johnson Controls Synergy ........................................................................................................................................................... 5

3 Johnson Controls DDC controllers ............................................................................................................................................. 6

B Product ........................................................................................................................................................................................ 12

1 Single Duct Terminal Unit Assemblies & Accessories................................................................................................................... 12

2 Combinations of Basic Assemblies and Accessory Modules ....................................................................................................... 13

3 Selection Procedure..................................................................................................................................................................... 14

4 Basic Box Dimensions & Flow Ranges ......................................................................................................................................... 15

4.1 SDx Series Product Dimensions .................................................................................................................................................. 15

5 Accessories’ Dimension & Basic Box Leakage Data..................................................................................................................... 16

5.1 ATT Attenuator Section................................................................................................................................................................ 16

5.2 Basic Box Casing and Damper Leakage........................................................................................................................................ 16

5.3 Standard Outlet Arrangements ................................................................................................................................................... 17

5.4 Water Coil ................................................................................................................................................................................... 18

5.5 Electric Heater.............................................................................................................................................................................. 18

C Single Duct Terminal Units – Performance Data.................................................................................................................... 19

1 Typical Selection Guide................................................................................................................................................................ 19

2 Discharge Sound Power Levels, Basic Assembly.......................................................................................................................... 20

3 Discharge Sound Power Levels with Attenuator ......................................................................................................................... 21

4 Radiated Sound Power Levels ..................................................................................................................................................... 22

D Heater Selection Guides and Performances............................................................................................................................ 23

1 1 & 2 Row Hot Water Coil Data (Metric Units).............................................................................................................................. 23

2 1 & 2 Row Hot Water Coil Data (SI Units) .................................................................................................................................... 25

E Acoustical Engineering Guidelines........................................................................................................................................... 27

1 Engineering Guide / Terminal Units............................................................................................................................................... 27

1.1 Estimating Sound Levels – Noise Criteria .................................................................................................................................... 27

1.1.1 Noise Criteria – NC ...................................................................................................................................................................... 27

1.2 Estimating Sound Levels............................................................................................................................................................... 28

1.2.1 Radiated Sound.......................................................................................................................................................................... 28

1.2.2 Discharge Sound........................................................................................................................................................................ 28

1.2.3 Environmental Adjustment Factors............................................................................................................................................. 29

F Single Duct Terminal Units – Suggested Specification........................................................................................................... 30

1 General ....................................................................................................................................................................................... 30

2 Digital Control SDV ..................................................................................................................................................................... 30

Table of Content

Page 4: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

4

A. VAV Controller System Preview

1. Benefit from The Johnson Controls VAV UnitThe Johnson Controls professional team has designed a whole new VAV range with the professional property owner, architect, consulting

engineer and mechanical contractor in mind. The result is a dramatic step forward ensuring building owner economies through air control

systems based on the latest direct digital control technology. For the first time, systems have been designed by professionals with an aim to

produce flexibility and simplicity at an economical cost with a single source responsibility.

1.1 For the Property OwnerA Savings in energy costs by supplying accurately measured quantity

of air to achieve occupant comfort.

A Simple installation for either new or retrofit projects.

A Ideal for new tenancy and partitioning changes.

A Revision and resetting of maximum and minimum air quantities to

suit changed zone loads is done in minutes, at the thermostat. It is

no longer necessary to inconvenient tenants by having to access

the ceiling space to reset air quantities.

A The DDC unit can be added for a retrofit as a complete unit using

existing ceiling source power supply.

A The property owner’s own maintenance staff can monitor and

maintain VAV performance with one simple instrument.

A REMOTE MONITOR AND CONTROL

The Johnson Controls system provided both local or remote

monitoring and control through the BMS. Maintenance staffs can

read zone temperature and actual airflow from the central control

station and reset control parameters without entering the tenant’s

premises.

A Single source responsibility.

1.2 For the ArchitectA In most commercial buildings the architect has to design to a

modular grid with wide flexibility to change, since at design stage

he rarely knows what tenancies and partitioning will be required.

A JOHNSON CONTROLS VAV units, having reset and recalibration of

maximum and minimum air quantities, allow him to partition to

suit almost any tenancy needs and move air around the building

to provide correct air quantities in each location. Having this reset

capability at the thermostat enables such shifts to be made without

accessing the ceiling space with its attendant risk of damaging and

soiling tiles.

1.3 For the Consulting EngineerA He can design with confidence knowing the Johnson Controls

systems will perform in accordance with catalogue data. The

JOHNSON CONTROLS PROFESSIONAL TEAM, many of whom are

exconsultants, understand the need for the designer to know he

can rely on published data.

A Our laboratory provide us the capability of simulating and demonstrating

the operation of VAV units and air distribution equipment under

variable volume conditions. All these assist the consultants who

have special or difficult applications which require witness testing

and performance assurance.

A The Johnson Controls systems offer a wide range of options and

auxiliary control functions giving the consultant enormous flexibility

in the selection of features to provide the control his project

demands whether it is stand alone or integrated to BMS.

A Single source responsibility.

1.4 For the Mechanical ContractorA The JOHNSON CONTROLS VAV unit is compact and easy to install,

with all control gear externally mounted for easy access and

service.

A Johnson Controls control components are protected from site

damage by a steel shroud. In the event of damage or malfunction,

control components are interchangeable and be removed and

replaced without breaking the ductwork.

A The contractors provide Johnson Controls with a TAG list for

his ordering. Each terminal unit is then computer selected and

calibration points indicated and printed on TAGS that are placed

on the carton and components indicating installation location,

calibration details, and air volumes.

NOTE: ALL JOHNSON CONTROLS VAV ARE

PRECALIBRATED AT THE FACTORY UNLESS OTHERWISE

REQUESTED.

A When the mechanical contractor comes to commissioning, the

Johnson Controls unit is simplicity itself. Each terminal is an

accurate flow measuring station. With one simple instrument,

calibration and volume settings can be checked in minutes.

Demonstration of performance of terminals to the consultant is

visually and graphically, thus accelerating the approval process.

Page 5: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

5

2. Johnson Controls SynergyThe VAV market in Asia has been developing very fast over the

past 30 years. From the pneumatic controls in the seventies to

the electronic controls in the early eighties, it has made a vast

improvement. As technology continues to advance, the direct digital

control technology has changed the whole concept of VAV system.

Instead of just providing room comfort independently and energy

saving through pressure changes in the main air duct, the VAV system

is now networked to a central workstation and provide on-line

control. Energy saving on air-side & water-side can be realized more

effectively by on-line feedback from all the VAV boxes in the building.

Changing of control parameters is performed at workstation instead

of disturbing occupants while meeting is in progress. The concept

of intelligent building is inherented from the VAV controls and the

flexibility of control strategy is up to the imagination of the designers.

But, one big problem continues to haunt contractors, designers/

consultants & owners. Contractors have problem in identifying

who is/are responsible for the VAV failure-whether it is the control

suppliers’ or VAV box manufacturer’s responsibility. Consultant

faces the dilemma of whether to put VAV control onto HVAC or BAS

specification and owner similarly does not know who to turn to after

taking over the building when it comes to VAV problems.

To address this marketing need for clear responsibility for VAV boxes.

Johnson Controls INC. has responded by supplying turn key VAV

systems. Now customer can count on JOHNSON CONTROLS as a

single source responsibility for the VAV boxes.

Single Source Responsibilityfor VAV Systems

ControlsTerminal Units

Johnson Controls

Page 6: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

6

3. Johnson Controls DDC Controllers

As powerful as the VAV Controller is by itself, your facility will benefit even more when VAV Controllers are part of a larger Metasys Network.

Each VAV Controller can connect to the Metasys N2, or BACnet MS/TP network. Either a Network Control Unit or Companion system can be

programmed to provide additional energy management and supervisory control capabilities, including optimal start, demand limiting, load rolling,

runtime totalization, and more.

NAE

VAV ControllerVMA 1400 Series

VAV ControllerVMA 1632 Series

VAV ControllerVMA 1617 Series

AHU ControllerFEC Series

AHU ControllerFEC Series

AHU ControllerFX Series

NAE NAE

BACnet IPWeb Service

BACnet IPWeb Service

Server ADXClient

Page 7: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

7

VMA1617/1632 Series Controllers

Description VMA16s (32-bit) are programmable digital controllers tailored for VAV

applications that communicate via the BACnet Master-Slave/Token-

Passing (MS/TP) protocol. The VMA16 (32-bit) controllers feature an

integral digital pressure sensor, an integral damper actuator, and a 32-bit

microprocessor. The controllers' small package size facilitates quick field

installation and efficient use of space, while not compromising high-tech

control performance. The VMA16 (32-bit) controllers connect easily to the

NS Series Network Sensors for zone and discharge air temperature sensing.

These features make the VMA16 (32-bit) the product of choice for VAV

systems. The wide variety of network sensor models provides options

for measuring and displaying zone temperature, occupancy detection,

duct temperature, zone humidity and dewpoint determination, carbon

dioxide (CO2) level, setpoint adjustments, VAV box fan speed control, and

discharge air temperatures.

FeaturesStandard BACnet® Protocol - Provides interoperability with other

Building Automation System (BAS) products that use the widely

accepted BACnet standard.

Standard Hardware and Software Platform - Uses a common hardware

design throughout the family line to support standardized wiring

practices and installation workflows. Also uses a common software

design to support use of a single tool for control applications,

commissioning, and troubleshooting to minimize technical training.

ZigBeeTM Wireless Field Controller (FC)/Sensor/Actuator (SA) Bus

Interface - Provides a wireless alternative to hard-wired Metasys@

system counterparts, providing application flexibility and mobility with

minimal disruption to building occupants.

Bluetooth® Wireless Commissioning Interface - Provides an easy-to-

use connection to the configuration and commissioning tool.

Auto Tuned Control Loops - Reduce commissioning time, eliminate

change-of-season re-commissioning, and reduce wear and tear on

mechanical devices.

Universal Inputs, Configurable Outputs, and Point Expansion Modules -

Allow multiple signal options to provide input/output flexibility.

Optional Local User Interface Display - Allows convenient monitoring

and adjusting capabilities at the local device.

BACnet Testing Laboratories™ (BTL) Listing - Ensures interoperability

with other BTL-listed devices. BTL is a third-party agency which

validates that BAS vendor products to meet the BACnet industry-

standard protocol.

32-bit microprocessor ensures optimum performance and meets

industry specifications.

BACnet Automatic Discovery support enables easy controller

integration into Metasys BAS.

Integral End-of-Line (EOL) switch enables field controller as a

terminating device on the communications bus.

Pluggable communications bus and supply power terminal blocks

expedite installation and troubleshooting.

Wireless capabilities via a ZFR1800 Series Wireless Field Bus System

enable wireless mesh connectivity between Metasys field controllers

to WRZ Series Wireless Room Temperature Sensors and to

supervisory controllers, facilitating easy initial location and relocation.

Patented proportional adaptive control (P-Adaptive) and Pattern

Recognition Adaptive Control (PRAC) technologies provide continuous

loop tuning.

Writable flash memory allows standard or customized applications to

be downloaded from the Controller Configuration Tool (CCT) and

enables persistent application data.

Large product family provides a wide range of point mix to meet

application requirements and allows the addition of one or more nput/

Output Module (IOM)s and/or Network Sensors to provide even more

I/O capacity.

A state-of-art digital non-flow pressure sensor to provide 14-bit

resolution with bidirectional flow operation that supports automatic

correction for polarity on high- and low-pressure DP tube connections;

this pressure sensor eliminates high- and low-pressure connection

mistakes.

Two additional Universal Inputs that provide more low-cost sensor

options

A 33 percent smaller package than the VMA16s (16-bit)

The phone jack-style connector on the FC Bus and SA Bus of the

VMA1615 and VMA1630 to support quick connection to the BTCVT

Wireless Commissioning Converter, ZFR1811 wireless router, and

network sensors.

A fast response actuator that drives the damper from full open to full

closed (90°) in 60 seconds to reduce commissioning time.

Page 8: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

8

VMA16 (32-bit) Series Point Type Counts per Model

VMA16 (32-bit) Series Ordering Information

Technical Specifications

Point Types Signals Accepted VMA1617 VMA1632

Modular Jacks "8-pin SA Bus supports analog non-communicating sensor"

Universal Input (UI)

"Analog Input, Voltage Mode, 3 3 3 3 0–10 VDC" 3 3"Analog Input, Resistive Mode, 0–2k ohm, RTD (1k NI [Johnson

Controls], 1k PT, A998 SI), NTC (10k Type L, 2.252k Type 2)""Binary Input, Dry Contact Maintained Mode"

Binary Output (BO) 24 VAC Triac 2 3

Configurable Output (CO)"Analog Output, Voltage Mode, 220–10 VDC"

2Binary Output Mode, 24 VAC Triac

Integrated Actuator Internal 1 1

Integrated Flow Sensor Internal 1 1

Zone Sensor Input On SA Bus1

Up to 4 NS Series Network Zone Sensors

Up to 9 WRZ sensors when using the ZFR1811 wireless router configuration and up to 5 WRZ sensors when using the one-to-one WRZ-78xx wireless configuration

Product Code Number Description

MS-VMA1617-0

32-bit, Integrated VAV Controller/Actuator/Pressure Sensor,

3 UI and 2 BO; 24 VAC;

Field Controller (FC) Bus, and Sensor/Actuator (SA) Bus

8-pin TSTAT Port for use with TE-7xx Series Non-Communicating Sensors

MS-VMA1632-0

32-bit, Integrated VAV Controller/Actuator/Pressure Sensor,

3 UI, 3 BO, and 2 CO; 24 VAC;

Field Controller (FC) Bus, and Sensor/Actuator (SA) Bus

8-pin TSTAT Port for use with TE-7xx Series Non-Communicating Sensors

Product Code Numbers

MS-VMA1617-0: 32-bit, Integrated VAV Controller/Actuator/Pressure Sensor,

3 UI and 2 BO; 24 VAC;

FC and SA Bus;

8-pin TSTAT Port for use with TE-7xx Series Non-Communicating Sensors

MS-VMA1632-0: 32-bit, Integrated VAV Controller/Actuator/Pressure Sensor,

3UI,3BO, 2CO, 24VAC,

FC and SA Bus;

8-pin TSTAT Port for use with TE-7xx Series Non-Communicating Sensors

Supply Voltage24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption 10 VA typical, 14 VA maximum

Ambient ConditionsOperating: 0 to 50°C (32 to 122°F)

Storage: -40 to 70°C (-40 to 158°F)

Terminations

Inputs/Outputs, SA Bus, and Supply Power: 6.3 mm (1/4 in.) Spade Lugs

FC Bus Pluggable Screw Terminal Block

TSTAT Modular Port: RJ-45 8-Pin Modular Jack

Controller AddressingDIP switch set; valid field controller device addresses 4–127

(Device addresses 0–3 and 128–255 are reserved and not valid field controller addresses.)

Communications Bus2

BACnet MS/TP, RS-485:

3-wire FC Bus between the supervisory controller and field controllers

4-wire SA Bus from the VMA controller, network sensors, and other sensor/actuator devices, includes a terminal to source 15 VDC supply power from VMA to SA Bus devices.

Processor RX630 32-bit Renesas® microcontroller

Memory 1 MB Flash Memory and 512 KB Random Access Memory (RAM)

Actuator Rating 4 N•m (35 lb•in.)

Dimensions (Height x Width x Depth): 165 x 125 x 73 mm (6.5 x 4.92 x 2.9 in.)

Weight 0.65kg (1.45lb)

1. A total of 10 MS/TP master addresses (IOMs), not including sensor addresses (MS/TP slaves), can be used in a single VMA controller.

1. This model is currently available only in Asia; contact your local Johnson Controls

Page 9: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

9

Selection Chart

Technical Specifications

Product Code Number Temperature Sensor Type Temperature Setpoint

Adjustment DialIntegral Manual Occupancy

Override Push Button Connection "Enclosure Dimensions (Height x Width x Depth)"

TE730-29C-0 Platinum 1k ohm Thin Film Resistive Yes No Modular Jack "3-1/4 x 3-1/4 x 1-7/16 in.[80*80*36mm]"

TE730-39C-0 Platinum 1k ohm Thin Film Resistive Yes Yes Modular Jack "3-1/4 x 3-1/4 x 1-7/16 in.[80*80*36mm]"

Temperature Sensor Type Platinum 1k ohm Thin Film Resistive

Temperature Sensor Coefficient Approximately 3.9 ohms per C° (2 ohms per oF)

Temperature Sensor 1k ohms at 0 oC (32 oF)

Temperature Sensor Accuracy ±0.56Co/±1.0Fo at 21° C (70 oF)

Temperature Setpoint Range Adjustable 15 to 29 oC (59 to 84 oF)

Temperature Sensor Response Time 8-Pin Modular Jack Connector

SA Bus Access 6-Pin Modular Jack Connector with Bottom Access for a Wireless Commissioning Converter or VAV Balancing Tool

Ambient Operating Conditions 0 to 40 oC (32 to 104 oF); 10 to 90% RH, Noncondensing; 30° C (86 oF) Maximum Dew Point

Ambient Storage Conditions ‘-40 to 60 oC (-40 to 140 oF); 5 to 95% RH, Noncondensing; 30° C (86 oF) Maximum Dew Point

Materials White Thermoplastic Enclosure

Shipping Weight 0.1 kg (0.3 lb)

TE730 Series Temperature Sensors

DescriptionThe TE730 Series Temperature Sensors provide temperature sensing in

room wall-mount applications. This arrangement allows local temperature

setpoint adjustment and temporary occupancy override.

A setpoint dial is included on all models to adjust the temperature

setpoint. A manual occupancy override push button is available on one

model to allow the user to request a time-of-day scheduling override,

when the space is occupied outside the normal occupied hours schedule.

The wires connecting the temperature sensor to the controller are

terminated with a modular jack connection. All models include a Sensor

Actuator (SA) Bus access port (6-pin modular jack) for connecting

accessories. This feature allows a technician to commission or service the

controller via the temperature sensor.

Features large setpoint dial — provides ease of temperature setpoint

adjustment by the user

occupancy override push button (TE730-39C-0 model) — allows

the user to request a time-of-day scheduling override when the

space is occupied outside the normal occupied hours schedule

compact and easy to install design — interfaces directly with the

field controller via modular jack connections

6-pin modular jack SA Bus access port — allows a technician

to commission or service the field controller via the TE730 Series

Temperature Sensor

Page 10: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

10

.

NS Series Network Sensors

DescriptionThe NS Series Network Sensors are electronic zone sensors designed

to function directly with Metasys® system BACnet® protocol Field

Equipment Controllers (FECs), Input/Output Modules (IOMs), and the

Variable Air Volume (VAV) Modular Assembly (VMA) 1600.

All models of network sensors monitor room temperature. Options

are available to also monitor zone humidity, local temperature setpoint

adjustments, and other variables identified in the following sections. This

data is transmitted to a field controller on the Sensor-Actuator (SA) Bus.

The line of network sensors includes models with a temperature setpoint

dial and Liquid Crystal Display (LCD) that allows occupants to view the

Product Code Numbe

Size (mm), Height x Width

Vertical Wallbox- Mounted (WB), or

Surface-Mounted (SM)

LCD Display

HumidityTemperature Adjustment: Setpoint (Set), or Warmer/

Cooler Dial (W/C)

Occupancy Override

F/C Scale Toggle

Screw Terminals (ST), or Modular

Jack (MJ)

NS-APA7001-0 80 x 80 SM Yes 2% Set Yes MJ

NS-APA7002-0 80 x 80 SM Yes 2% Set Yes ST

NS-APB7001-0 80 x 80 SM Yes 2% Set Yes Yes MJ

NS-APB7002-0 80 x 80 SM Yes 2% Set Yes Yes ST

NS-BPB7001-0 120 x 80 WB,SM Yes 2% Set Yes Yes MJ

NS-BPB7002-0 120 x 80 WB,SM Yes 2% Set Yes Yes ST

NS-AHA7001-0 80 x 80 SM Yes 3% Set Yes MJ

NS-AHA7002-0 80 x 80 SM Yes 3% Set Yes ST

NS-AHB7001-0 80 x 80 SM Yes 3% Set Yes Yes MJ

NS-AHB7002-0 80 x 80 SM Yes 3% Set Yes Yes ST

NS-BHB7001-0 120 x 80 WB,SM Yes 3% Set Yes Yes MJ

NS-BHB7002-0 120 x 80 WB,SM Yes 3% Set Yes Yes ST

zone temperature, and view and adjust the zone setpoint. A fan mode

push button is included to set the desired fan speed (Auto-Off-Low-

Med-High).

An occupancy override function allows the user to signal the controller

that the zone is occupied to override the scheduled mode. For

communication wiring flexibility, the wires connecting the sensor to a

controller can be terminated using a modular jack or screw terminals.

Each network sensor includes an SA Bus access port to allow accessories

to access the SA Bus. This plug allows accessories to service or

commission the connected controller or gain access to any other

controller on the same FC Bus. Refer to the Metasys System BACnet

Protocol Field Controllers, Network Sensors, and Related Products

Product Bulletin (LIT-12011042) for product application details.

Features BACnet Master-Slave/Token-Passing protocol communication

provides compatibility with Metasys system Field Controllers in a

proven communication network.

Backlit LCD (available on some models) provides realtime status of

the environment in easy-to-read, plain text messages with

backlighting activated during user interaction.

Simple setpoint adjustment enables user to change the setpoint

with the turn of a dial.

Temporary occupancy (available on some models) provides a timed

override command, which temporarily initiates an alternate mode.

Fahrenheit/Celsius (F/C) button toggles the display temperature

between degrees Celsius and degrees Fahrenheit.

Selection ChartsNetwork Sensor Ordering Information — Temperature and Humidity Models

Page 11: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

11

Network Sensor Ordering Information — Temperature and Humidity Models

Product Code Numbe

Size (mm), Height x Width

Vertical Wallbox- Mounted (WB), or

Surface-Mounted (SM)

LCD Display

Temperature Adjustment: Setpoint (Set), or Warmer/

Cooler Dial (W/C)

Occupancy Override

F/C Scale Toggle

Fan Control

Screw Terminals (ST), or Modular

Jack (MJ)

Address Switches

VAV Balancing Feature

NS-ATA7001-0 80 x 80 Yes Set Yes MJ

NS-ATA7002-0 80 x 80 Yes Set Yes ST

NS-ATB7001-0 80 x 80 SM Yes Set Yes Yes MJ

NS-ATB7002-0 80 x 80 SM Yes Set Yes Yes ST

NS-ATC7001-0 80 x 80 SM Yes Set Yes Yes MJ

NS-ATC7002-0 80 x 80 SM Set Yes Yes ST

NS-ATD7001-0 80 x 80 SM Set Yes Yes Yes MJ

NS-ATD7002-0 80 x 80 SM Set Yes Yes Yes ST

NS-ATN7001-0 80 x 80 SM MJ

NS-ATN7003-0 80 x 80 SM ST Yes

NS-ATP7001-0 80 x 80 SM W/C Yes MJ

NS-ATP7002-0 80 x 80 SM W/C Yes ST

NS-ATV7001-0 80 x 80 SM Yes Set Yes Yes No1 MJ Yes

NS-ATV7002-0 80 x 80 SM Yes Set Yes Yes No1 ST Yes

NS-BTB7001-0 120 x 80 WB,SM Yes Set Yes Yes MJ

NS-BTB7002-0 120 x 80 WB,SM Yes Set Yes Yes ST

NS-BTN7001-0 120 x 80 WB,SM MJ

NS-BTN7002-0 120 x 80 WB,SM ST Yes

NS-BTP7001-0 120 x 80 WB,SM W/C Yes MJ

NS-BTP7002-0 120 x 80 WB,SM W/C Yes ST

NS-BTV7001-0 120 x 80 WB,SM Yes Set Yes Yes No1 MJ Yes

NS-BTV7002-0 120 x 80 WB,SM Yes Set Yes Yes No1 ST Yes

1. In the VAV Balancing models, the Fan Control button is replaced by a light bulb button used in the VAV Balancing Process.

NS Series Network Sensor

Sensor Type With Setpoint Adjustment Without Setpoint Adjustment

Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal

Current Consumption 25 mA Maximum (Non-Transmitting) 13 mA Maximum (Non-Transmitting)

Terminations Modular Jack or Screw Terminal Block

Sensor Addressing on the SA BusNA DIP Switch Set (200 to 203)

Fixed Address of 199 Fixed Address of 199

Wire Size26 AWG (0.4 mm Diameter) Recommended; Three Twisted Pair (6 conductors)

18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended

Communication Rate Auto-Detect: 9600, 19.2k, 38.4k, or 76.8k bps

Mounting Surface-Mounted (80 x 80) Surface-Mounted or Vertical Wallbox-Mounted (120 x 80)

Temperature Measurement Range 0.0 oC/ 32.0 oF to 40.0 oC/104.0 oF

Sensor Type Local Platinum Resistance Temperature Detector (RTD)

Resolution ±0.5 oC/±0.5 oF

Sensor Accuracy ±0.6 oC/±1.0 oF

Resolution ±0.5 oC/±0.5 oF NA

Sensor Accuracy ±0.6 oC/±1.0 oF

Time Constant 10 Minutes Nominal at 10 fpm Airflow

Default Setpoint Adjustment Range 10.0 oC/50.0 oF to 30.0 oC/86.0 oF in 0.5 o Increments ±3.0 oC/±5.0 oF

Ambient Conditions0 to 40 oC (32 to 104 oF); 10 to 95% RH, Non-condensing; 29 oC (85 oF) Maximum Dew Point

-20 to 60 oC (-4 to 140 oF); 5 to 95% RH, Non-condensing -40 to 70 oC (-40 to 158 oF); 5 to 95% RH, Non-condensing

Compliance

UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A

UL Listed, File E107041, CCN PAZX7, Under CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003"

CE Mark, EMC Directive 89/336/EEC EN61000-6-3 (2001) Generic Emission Standard for Residential and Light Industry EN61000-6-2 (2001) Generic Immunity Standard for Heavy Industrial Environment

C-Tick Mark, Australia/NZ Emissions Compliant

Shipping Weight 0.09 kg (0.20 lb) - NS-Axx7xxx-0 0.11 kg (0.25 lb) - NS-Bxx7xxx-0

Technical Specifications

Page 12: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

12

B. Product

1. Single Duct Terminal Unit Assemblies & Accessories

VAV Basic Box

Electric Heater

Sound Attenuator

Hot Water Coil

Multi-Outlet Attenuator

Select a Basic Control Assembly, Add Accessory Modules To Suit The Design.

Page 13: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

13

Basic Box Open End

Attenuator Multi-Outlet Attenuator

Hot Water Heating Coil + Multi-Outlet Attenuator Electrical Heater

Hot Water Heating Coil Round Discharge Collar

a All diagrams are plan views.

a It is usually preferable to assure airflow through a heating coil above a controlled minimum. Therefore coils are listed only with the

pressure independent Series 8000.

a All models are shipped assembled as shown in diagrams.

a Shown are 2 row coil / 2 stage heater designations.

2. Combinations of Basic Assemblies and Accessory Modules

Page 14: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

14

3. Selection Procedure

System CodeC: Constant Air VolumeV: Variable Air Volume

Controller Code5: No Controller6: MS-VMA1632/1620-0 Controller7: MS-VMA1617/1610-0 Controller8: AP-VMA1420-0 Controller9: AP-VMA1415-0 Controller

Thermostat Code0: No ThermostatA: NS-ATA7001-0 ThermostatB: TE67-NP-2B00 ThermostatC: TE700-29C-0 ThermostatD: NS-ATD7001-0 ThermostatN: TE67-NP-2N00 ThermostatP: NS-ATP7001-0 ThermostatT: TE730-29C-0 ThermostatZ: AP-TMZ1600-0 Thermostat

Discharge Section Code0: No Discharge Section1: Attenuator2: Round Discharge CollarA~Z: Multi-outlet attenuator

Outlet Size for Multi-outlet Attenuator00: No Multi-outlet Attenuator06: 6"07: 7"08: 8"09: 9"10: 10"12: 12"14: 14"

SD V - 8 C - 2 06 - E 1 -08-010- R - 0

Heating Section Code0: No Heating SectionE: Electric HeaterW: Water Heating Coil

Special Requirement Code0: No Special Requiremnt D: Double SkinP: Perforated LinerF: Discharge FlangeL: Low-temperature UnitS: Other Special Requirement

Unit Handing CodeR: Right HandingL: Left Handing

Electric Heater Capacity Code000:No Electric Heater005: 0.5kw007: 0.75kw010: 1.0kw015: 1.5kw020: 2.0kw025: 2.5kw

Unit Size04: 4"05: 5"06: 6"07: 7"08: 8"09: 9"10: 10"12: 12"14: 14"16: 16"

Heating Stage Code0: No Heating Section1: One Stage Electric Heater or One Row Coil2: Two Stage Electric Heater or Two Rows Coil

Page 15: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

15

Note for Basic Box:1. Internal insulation 25mm (1”), 48kg/m3 density coated to prevent air erosion. Passed Fire Test BS476 Part 6 & 7 to meet Class “0”.

2. Mechanically sealed leak resistant construction.

3. Right hand control location standard, as shown above.

4. Basic Box Dimensions & Flow Ranges

4.1 SDx Series Product Dimensions

UnitSize

SI Units in mm IMPERIAL Units in inchesB C D d E B C D d E

4 305 203 149 99 394 12 8 5.875 3.875 15.5315 305 203 149 124 394 12 8 5.875 4.875 15.5316 305 203 149 N/A 394 12 8 5.875 N/A 15.5317 305 254 175 N/A 394 12 10 6.875 N/A 15.5318 305 254 200 N/A 394 12 10 7.875 N/A 15.5319 356 318 225 N/A 394 14 12.5 8.875 N/A 15.53110 356 318 251 N/A 394 14 12.5 9.875 N/A 15.53112 406 381 302 N/A 394 16 15 11.875 N/A 15.53114 508 445 352 N/A 496 20 17.5 13.875 N/A 19.53116 610 457 403 N/A 496 24 18 15.875 N/A 19.531

Basic Box Dimensions and Flow Ranges

Adaptor for Sizes 4 & 5

End View Side ViewB

D

E

d

6.25” (159)6.375”(162)

AirFlow

2”(51)

SDx includes: DDC Controller, factory mounted

a Damper actuator, factory mounted

a Room temperature sensor (Supplied loose)

a 20 VA Transformer, 240/24 VAC, factory mounted (*)

a Velocity sensor, factory mounted

a Transducer, factory mounted.

UnitSize

I/s Min – Max

CFM Min – Max

CMH Min – Max

4 12-106 26-225 44-382

5 20-165 42-350 71-595

6 29-212 62-450 105-765

7 40-307 85-650 145-1105

8 52-378 110-800 187-1360

9 66-496 140-1050 238-1785

10 85-637 180-1350 306-2295

12 127-991 270-2100 460-3570

14 189-1510 400-3200 680-5440

16 269-1888 570-4000 970-6800

Air Volume Ranges Notes for Flow RangesJohnson Controls units are pressure independent at any flow rate within the

minimum and maximum flow range limits. For a given unit size, the minimum

flow setting and the maximum flow setting must be within the range limits for

each based on the controller selected. Tables of the minimum and maximum

flow setting range limits are included on this page. Please specify the

controller model selected.

A minimum value of zero is also available.

When an auxiliary setting is specified, the value must be greater than the

minimum setting and within the range limits.

Page 16: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

16

5. Accessories’ Dimension & Basic Box Leakage Data

5.1 ATT Attenuator Section

5.2 Basic Box Casing Leakage

Unit Size SI Units in mm Imperial Units in Inches

B C RDC Outlets B C RDC Outlets

4, 5, 6 305 203 102, 127, 152 12 8 4, 5, 6

7, 8 305 254 178, 203 12 10 7, 8

9, 10 356 318 229, 254 14 12.5 9, 10

12 406 381 308 16 15 12

14 508 445 355 20 17.5 14

16 610 457 406 24 18 16

* All metric conversions are soft conversion. Imperial dimensions are converted to metric and round to the nearest millimeter

Notes:1. Only one outlet size to be specified per MOA, no mixing of outlet sizes on the same unit.2. All round outlets c/w manual dampers.3. Denotes air flow direction.4. For special outlet sizes & arrangement, consult your Johnson Controls sales representative office.

The casing leakage is less than 1% at the standard rating condition of 3 inches inlet static pressure

3.625"(84)

3.625"(84)36" (914) B

NormalSize

B 4" (102)

3.625"(84)36" (914)

Attenuator Section – ATT Round Discharge Collar Section – RDC

C

Side View

Side View

C

End View

End View

Side View

Multi-Outlet Attenuator Section – MOA

C

Page 17: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

17

Size MOA Outlets

4、5、6 3 @ 6” (152)

7、84 @ 8” (203)

5 @ 6” (152)

9、 10、123 @ 10” (254)

5 @ 8” (203)

5.3 Standard Outlet Arrangements

MOA OutletRecommended no. & size of outlets on MOA shall not exceed the limits listed below.

Both max quantity of outlets and max size of outlets.

Note:

Turbulent flow approaching the terminal will create additional noise and

pressure drop. It is therefore recommended for optimum performance there

should be a minimum of 4 duct diameters of straight inlet duct, same size as

inlet, between the inlet and any transition, tap off or fitting.

Page 18: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

18

29.5”(750)

Heater Element Compartment

Heater Control Compartment

Overlook View End View

100

100

298/308

200/

181

70

50 127 10.5”(267)

143

B

C

C

B

245

3”4

5.4 Water Coil

5.5 Electric Heater

Notes:a Copper tube size: 9.53×0.33

a The inlet/outlet pipe connections use 3/4" threads copper joint.

Notes: A minimum air flow of 70 CFM per kW across the heater must be maintained.

Page 19: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

19

C. Single Duct Terminal Units – Performance Data

1. Typical Selection Guide

UnitSize

Airflow Minimum Ps Across Unit (static pressure) Discharge NC Basic Assembly∆Ps Across Unit

Discharge NC c/w 36"Attenuator∆Ps Across Unit

Radiated NC Basic Assembly∆Ps Across Unit

Basic Unit with Atten 1-Row Coil 2-Row Coil 0.5 In W.G. 1.5 In W.G. 3.0 In W.G. 0.5 In W.G. 1.5 In W.G. 3.0 In W.G. 0.5 In W.G. 1.5 In W.G. 3.0 In W.G.

CFM CMH L/s In.W.G. Pa In.W.G. Pa In.W.G. Pa In.W.G. Pa Min 125 Pa 375 Pa 750 Pa Min 125 Pa 375 Pa 750 Pa Min 125 Pa 375 Pa 750 Pa

4

100 170 47 0.01 2 0.01 2 0.03 7 0.07 17 -- -- -- -- -- -- -- -- -- -- -- --113 192 53 0.01 2 0.01 2 0.03 7 0.07 17 -- -- -- -- -- -- -- -- -- -- -- 15150 255 71 0.01 2 0.01 2 0.06 15 0.16 40 -- -- 16 19 -- -- -- 15 -- -- 15 19200 340 94 0.01 2 0.01 2 0.11 27 0.28 70 -- 15 20 23 -- -- 17 23 -- -- 19 23225 383 106 0.01 2 0.01 2 0.15 37 0.35 87 -- 17 23 25 -- -- 20 25 -- 15 21 24

5

100 170 47 0.01 2 0.01 2 0.01 2 0.03 7 -- -- -- 28 -- -- -- -- -- -- 20 25175 298 83 0.01 2 0.01 2 0.04 9 0.06 15 -- -- 20 25 -- -- -- 18 -- -- 21 30200 340 94 0.01 2 0.01 2 0.04 10 0.10 25 -- -- 22 26 -- -- 15 20 -- -- 23 30250 425 118 0.01 2 0.01 2 0.06 15 0.16 40 -- 17 25 31 -- -- 18 23 -- 15 25 27300 510 142 0.01 2 0.01 2 0.09 22 0.23 57 -- 17 26 32 -- 15 21 26 -- 16 27 28350 595 165 0.01 2 0.01 2 0.12 30 0.32 80 -- 21 30 33 -- 17 23 28 -- 19 28 29

6

200 340 94 0.01 2 0.01 2 0.04 10 0.1 25 -- -- 21 25 -- -- -- -- -- -- 22 28225 383 106 0.01 2 0.01 2 0.06 15 0.16 40 -- -- 22 27 -- -- -- -- -- -- 23 31300 510 142 0.01 2 0.01 2 0.09 22 0.23 57 -- -- 23 31 -- -- -- 15 -- -- 24 32350 595 165 0.01 2 0.01 2 0.12 30 0.3 75 -- 15 25 32 -- -- -- 17 -- 15 25 33400 680 189 0.01 2 0.01 2 0.16 40 0.31 77 -- 18 27 35 -- -- -- 19 -- 21 25 34450 765 212 0.01 2 0.01 2 0.18 45 0.35 87 -- 21 28 36 -- -- 15 20 -- 31 28 35

7

250 425 118 0.01 2 0.01 2 0.04 10 0.07 17 -- -- 20 25 -- -- -- 20 -- -- 20 25325 553 153 0.01 2 0.01 2 0.06 15 0.16 40 -- -- 23 28 -- -- 18 24 -- 15 25 30450 765 212 0.01 2 0.01 2 0.11 27 0.21 52 -- -- 29 32 -- -- 21 27 -- 16 27 35550 935 260 0.01 2 0.01 2 0.31 45 0.31 77 -- 16 29 35 -- -- 23 31 -- 16 28 37650 1105 307 0.01 2 0.01 2 0.31 47 0.35 88 -- 18 30 36 -- 16 26 33 -- 20 29 39

8

400 680 189 0.01 2 0.01 2 0.07 17 0.12 30 -- -- 19 26 -- -- -- 20 -- -- 24 31500 850 236 0.01 2 0.01 2 0.10 25 0.18 45 -- -- 22 30 -- -- 16 23 -- -- 29 35600 1020 283 0.01 2 0.01 2 0.15 37 0.26 65 -- -- 24 32 -- -- 19 25 -- -- 29 37700 1190 330 0.01 2 0.01 2 0.20 50 0.36 90 -- 15 24 34 -- -- 20 27 -- 16 30 37800 1360 378 0.01 2 0.01 2 0.27 67 0.60 149 -- 16 25 34 -- -- 22 28 -- 17 30 39

9

450 765 212 0.01 2 0.01 2 0.05 12 0.10 25 -- - 26 34 -- -- -- 19 -- -- 19 30525 893 248 0.01 2 0.01 2 0.07 17 0.12 30 -- 15 27 34 -- -- -- 21 -- -- 19 30650 1105 307 0.01 2 0.01 2 0.11 27 0.21 52 -- 15 28 36 -- -- 16 23 -- -- 21 29850 1445 401 0.01 2 0.01 2 0.18 45 0.35 87 -- 15 28 36 -- -- 18 24 -- 15 23 30950 1615 448 0.01 2 0.01 2 0.26 65 0.42 105 -- 16 29 37 -- -- 19 25 -- 16 24 301050 1785 496 0.01 2 0.01 2 0.28 70 0.54 134 -- 17 30 39 -- -- 20 26 15 20 26 31

10

550 935 260 0.01 2 0.01 2 0.04 10 0.99 22 -- -- -- 17 -- -- -- 17 -- -- 35 48675 1148 319 0.01 2 0.01 2 0.10 25 0.19 47 -- -- -- 18 -- -- -- 18 -- 16 34 45750 1275 354 0.01 2 0.01 2 0.08 20 0.17 42 -- -- -- 19 -- -- -- 19 -- 17 36 45950 1615 448 0.01 2 0.01 2 0.13 32 0.27 67 -- -- -- 18 -- -- 16 22 -- 25 33 451150 1955 543 0.01 2 0.01 2 0.19 47 0.40 100 -- -- -- 19 -- -- 18 24 23 30 37 471350 2295 637 0.01 2 0.01 2 0.27 67 0.55 137 -- -- -- 19 -- -- 19 25 27 32 38 47

12

900 1530 425 0.01 2 0.01 2 0.05 12 0.12 30 -- -- 25 29 -- -- 15 21 -- -- 23 341050 1785 496 0.01 2 0.01 2 0.12 30 0.23 57 -- -- 25 30 -- -- 16 22 -- -- 23 351300 2210 614 0.01 2 0.01 2 0.11 27 0.25 62 -- -- 25 31 -- -- 18 24 -- -- 25 361500 2550 708 0.01 2 0.01 2 0.22 55 0.42 105 -- -- 26 32 -- -- 19 25 -- -- 25 361700 2890 802 0.01 2 0.01 2 0.19 47 0.43 107 -- 17 27 32 -- -- 20 26 -- 16 27 352100 3570 991 0.01 2 0.01 2 0.29 72 0.65 162 15 21 28 35 -- -- 22 28 21 22 29 37

14

1200 2040 566 0.01 2 0.01 2 0.07 17 0.13 32 -- -- 29 36 -- -- 15 21 -- -- 23 341600 2720 755 0.01 2 0.01 2 0.13 32 0.25 62 -- 19 30 37 -- -- 18 24 -- 15 25 342200 3740 1038 0.01 2 0.01 2 0.23 57 0.44 109 -- 21 31 37 -- -- 21 27 -- 20 30 362700 4590 1274 0.01 2 0.01 2 0.35 87 0.66 164 15 24 32 38 -- -- 23 30 23 26 32 373200 5440 1510 0.01 2 0.01 2 0.48 119 0.91 226 21 26 33 39 -- 15 25 32 32 33 37 40

16

1500 2550 708 0.01 2 0.01 2 0.07 17 0.13 32 -- -- 25 31 -- -- 15 21 -- -- 29 342000 3400 944 0.01 2 0.01 2 0.12 30 0.23 57 -- -- 25 31 -- -- 18 24 -- -- 29 362500 4250 1180 0.01 2 0.01 2 0.19 47 0.36 90 -- -- 26 32 -- -- 20 26 19 19 29 373000 5100 1416 0.01 2 0.01 2 0.27 67 0.52 129 -- 17 27 33 -- -- 22 28 29 29 31 373500 5950 1652 0.01 2 0.01 2 0.37 92 0.70 174 16 20 28 34 -- -- 23 29 35 35 36 404000 6800 1888 0.01 2 0.01 2 0.49 122 0.91 226 21 21 28 35 -- 15 24 30 36 36 37 43

Performance Notes:1. NC derived from Sound Power Levels obtained in accordance with AHRI Standard 880-98.

2. Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).

3. Blank Spaces indicate NC's less than 15.

4. Minimum ΔPs across the unit is lowest inlet to discharge Static Pressure Differential at which controls are pressure independent.

5. ΔPs is the difference in Static Pressure from Inlet to Discharge of the unit.

6. Pressure is given in Pascals (Pa) and Inches of Water Guage (In. W.G).

Page 20: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

20

34

1 Test data obtained in accordance with ARI Standard 880-98.2 Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).3 Blank Spaces Indicate Sound Power Levels less than 20.4 Minimum ∆Ps - Minimum Operating Pressure.5 Pressure is given in Pascals (Pa) and Inches of Water Guage (In. W.G).* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.

Actual levels are less than or equal to the levels indicated.

Performance Notes:

2. Discharge Sound Power Levels, Basic Assembly

100 17 0 47 45 31 22 20 -- -- 49 47 40 38 34 30 52 52 48 47 44 40 55 55 52 52 50 4711 3 192 53 46 33 25 23 -- -- 51 49 42 40 36 32 55 55 51 59 46 42 56 56 54 53 51 4815 0 255 71 47 39 32 32 25 21 54 53 45 43 38 34 58 58 52 51 48 44 60 60 57 56 54 51200 340 94 49 44 39 40 35 31 58 57 49 46 41 37 61 61 56 54 50 47 64 64 60 59 57 54225 383 106 .2 50 47 42 44 39 36 60 59 50 47 42 38 64 64 58 55 51 48 65 66 62 60 58 55100 17 0 47 42* 34* 24* 20* 21 * 21 * 49 49 43 38 34 32 53 54 52 47 44 42 56 59 62 57 52 5017 5 298 83 42* 38 34 23 21 21 * 54 55 48 43 39 36 60 61 58 53 49 46 62 66 67 62 56 53200 340 94 43* 40 36 27 23 21 * 56 56 49 45 41 37 61 63 59 54 51 48 63 68 68 64 58 54250 425 11 8 47 46 42 35 31 27 59 59 51 47 43 41 64 66 62 57 53 50 67 71 71 65 60 56300 51 0 141 .6 50 50 45 39 36 33 60 60 53 49 45 44 66 68 64 59 54 51 69 73 73 67 62 58350 595 165 .2 53 54 49 44 41 38 62 63 55 51 47 46 68 70 65 60 56 53 71 74 74 68 63 59200 340 94 42* 37* 33 20* 21 * 21 * 52 54 48 43 40 35 59 62 58 53 49 46 62 66 66 61 56 53225 383 106 .2 42* 38 36 20* 21 * 21 * 53 55 48 43 40 36 61 63 60 54 50 47 64 68 68 63 58 54300 51 0 141 .6 43* 42 40 30 25 22* 56 57 50 45 42 45 63 65 62 56 52 49 66 71 70 65 60 56350 595 165 .2 44* 44 41 34 29 27 57 58 51 45 41 42 66 67 63 58 54 51 68 73 72 67 62 58400 680 188 .8 47 48 44 39 35 36 60 61 54 48 43 43 67 68 64 59 55 51 70 74 72 68 63 58450 765 212 .4 48 50 46 41 38 38 61 63 56 49 46 46 69 69 65 60 56 53 71 75 72 69 64 59250 425 11 8 44* 35* 24* 20* 20* 22* 51 54 48 42 38 35 58 59 59 55 51 48 60 62 62 61 58 57325 55 3 153 .4 44* 37 31 25 20* 22* 57 56 50 45 41 37 63 65 64 59 54 50 64 67 66 66 61 58450 765 212 .4 46* 44 39 35 27 23* 59 57 50 47 42 41 67 69 63 60 56 52 68 73 70 70 64 6055 0 935 259 .6 48 49 44 41 34 33 61 59 52 49 44 42 67 69 65 62 56 52 69 76 71 72 65 61650 110 5 306.8 54 53 48 47 39 38 63 61 54 50 46 45 69 70 64 61 57 53 71 77 72 72 66 62400 680 188 .8 45* 38* 31 28 20* 20* 54 52 46 43 39 37 62 61 59 55 51 49 64 65 64 62 59 56500 850 236 45* 41 36 34 24 20* 56 54 48 45 42 39 65 64 61 56 52 50 68 70 67 66 62 59600 1020 283 .2 46* 44 39 40 29 24* 57 56 49 46 43 41 67 66 62 58 54 52 70 72 68 67 63 60700 119 0 330.4 49 48 43 44 34 30 59 58 51 48 44 42 68 67 62 58 54 52 72 75 69 68 63 61800 136 0 377 .6 52 51 47 49 39 36 61 60 54 49 45 43 69 67 62 58 54 52 74 76 70 68 63 61450 765 212 .4 42* 35* 25 24 19* 21 * 53 50 46 47 47 44 58 62 57 56 57 56 61 69 70 66 66 65525 893 247 .8 42* 35* 31 31 21 * 21 * 54 52 48 48 49 45 62 63 57 57 58 57 62 68 69 66 66 65650 110 5 306.8 42* 39 37 39 30 25 57 54 49 49 48 45 62 63 58 57 58 58 64 68 67 67 67 67850 1445 401.2 48 45 45 48 39 34 60 58 53 52 50 47 65 65 60 59 60 60 68 70 68 70 70 69950 161 5 448.3 51 48 48 51 42 38 61 59 54 53 51 48 66 67 61 61 62 62 69 70 68 70 71 70105 0 178 5 495 .5 53 50 50 54 45 41 62 60 55 54 52 49 68 68 63 63 64 64 70 71 69 71 72 7255 0 935 259 .6 43* 35* 22* 19* 20* 23* 44* 38 32 25 21 * 23* 54 53 49 40 35 31 57 59 60 51 45 39675 114 8 318 .6 43* 35* 24 19* 20* 23* 46 41 34 27 22* 23* 56 53 48 40 34 29 59 61 60 51 46 39750 127 5 354 43* 35* 26 21 * 20* 23* 48 42 34 27 22* 23* 58 54 50 42 36 31 60 61 60 51 46 39950 161 5 448.3 43* 36* 32 25 20* 23* 51 44 36 29 24 23* 58 54 49 42 35 31 63 61 59 51 45 38115 0 195 5 542 .7 45* 39 37 31 22 23* 55 48 40 32 27 23* 60 55 49 42 36 32 65 62 58 52 46 38135 0 229 5 637 .1 49 43 41 35 26 24* 58 51 43 36 30 25* 62 56 50 42 37 32 67 62 59 54 47 39900 153 0 424.8 48* 37* 38 29 23* 22* 54 52 48 47 48 45 66 64 59 57 56 57 70 70 68 66 64 62105 0 178 5 495 .5 49* 39* 42 33 28 22* 55 53 49 48 48 45 66 65 60 57 57 57 72 71 68 66 64 63130 0 221 0 613 .5 50* 43 48 40 35 28 58 56 52 49 48 46 67 66 62 59 58 57 73 72 69 67 65 64150 0 255 0 707 .9 53* 47 52 44 40 34 60 58 55 51 50 48 68 66 64 61 60 58 75 73 70 68 66 65170 0 2890 802.3 54* 49 56 48 43 39 62 59 57 53 51 49 68 67 64 62 61 59 75 74 71 69 67 652100 357 0 991 .1 59 55 63 54 50 45 66 63 63 57 55 53 71 69 67 64 63 61 76 75 74 72 70 681200 2040 566 .3 47* 35 38 27 21 * 21 * 56 52 50 51 50 49 65 64 61 61 61 62 70 71 70 68 68 691600 272 0 755 .1 48* 41 47 37 32 24* 58 55 53 53 52 51 70 67 64 62 63 63 72 72 74 69 69 702200 3740 1038 51 * 47 56 47 43 38 62 59 57 55 54 53 70 68 65 63 63 64 75 73 71 70 70 702700 4590 127 4 55 52 63 53 49 44 66 63 62 58 57 56 72 70 67 65 65 65 77 75 73 71 71 713200 5440 151 0 60 57 68 59 55 50 69 66 68 61 59 58 74 71 70 67 67 66 79 77 75 73 73 72150 0 255 0 707 .9 48* 36* 37 25 21 * 21 * 54 52 48 48 48 44 67 65 59 56 57 57 73 71 69 66 66 642000 3400 943.9 48* 39 45 34 31 24 56 53 50 49 49 45 68 66 60 58 58 57 75 73 70 67 66 642500 4250 118 0 50* 44 52 41 38 31 59 56 53 51 50 48 69 66 62 60 60 58 77 75 71 68 67 653000 510 0 141 6 51 * 47 59 47 44 38 62 58 57 53 51 49 71 67 64 62 61 59 79 75 72 69 68 663500 595 0 165 2 53* 51 64 52 49 43 65 61 62 56 54 52 73 69 66 63 62 60 80 76 72 70 69 674000 6800 188 8 56 54 67 56 53 48 66 63 67 58 56 53 75 70 68 64 63 60 82 77 74 71 70 67

6

7

4

5

14

16

8

9

10

12

CFM CMH L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

Minimum Ps 125 Pa (0.5 In W.G.) 375 Pa (1.5 In W.G.) 750 Pa (3.0 In W.G.)UnitSize

Minimum Ps Plus

Octave BandAirflow

Octave Band Octave Band Octave Band

Sound Power Levels Lw dB RE 10-12 Watts

Performance Notes:1. Test data obtained in accordance with ARI Standard 880-98.

2. Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).

3. Blank Spaces Indicate Sound Power Levels less than 20.

4. Minimum ∆Ps - Minimum Operating Pressure.

5. Pressure is given in Pascals (Pa) and Inches of Water Gauge (In. W.G).

* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.

Actual levels are less than or equal to the levels indicated.

2. Discharge Sound Power Levels, Basic Assembly

Page 21: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

21

35

CFM CMH L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

Minimum Ps 125 Pa (0.5 In W.G.) 375 Pa (1.5 In W.G.) 750 Pa (3.0 In W.G.)UnitSize

Minimum Ps Plus

Octave BandAirflow

Octave Band Octave Band Octave Band

Sound Power Levels Lw dB RE 10-12 Watts3. Discharge Sound Power Levels with Attenuator

1 Test data obtained in accordance with ARI Standard 880-98.2 Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).3 Blank Spaces Indicate Sound Power Levels less than 20.4 Minimum ∆Ps - Minimum Operating Pressure.5 Pressure is given in Pascals (Pa) and Inches of Water Guage (In. W.G).* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.Actual levels are less than or equal to the levels indicated.

Performance Notes:

100 170 47 45 36 23 -- -- -- 42 37 29 24 20 22 48 44 38 31 24 25 52 48 44 36 26 2711 3 192 53 46 38 26 -- -- -- 44 39 31 25 20 22 50 46 40 33 24 25 54 51 46 38 26 2715 0 255 71 48 43 32 -- -- -- 49 45 36 28 21 22 55 52 45 36 25 26 59 56 51 41 27 28200 340 94 5 48 38 28 -- -- 53 51 41 32 22 23 59 58 50 40 25 26 63 62 56 45 28 28225 383 106 .2 51 50 40 31 -- -- 55 53 43 33 22 23 61 60 52 41 26 26 65 64 58 46 28 29100 170 47 43 28 -- -- -- -- 46 38 32 21 -- -- 50 44 39 29 -- 21 53 48 43 35 25 2717 5 298 83 46 36 28 24 -- -- 50 44 38 26 -- -- 55 50 45 35 21 22 58 54 49 40 28 29200 340 94 47 38 30 25 -- -- 52 46 39 27 -- -- 56 51 46 36 22 23 59 55 51 41 28 30250 425 118 48 41 35 28 -- -- 53 48 42 29 -- -- 58 54 49 38 23 24 61 58 53 44 29 30300 510 141 .6 49 43 39 29 -- -- 55 50 44 31 -- -- 59 56 51 40 24 24 62 60 56 45 30 31350 595 165 .2 50 46 42 31 -- -- 56 52 46 33 -- -- 61 58 53 41 24 25 63 61 57 47 31 32200 340 94 45 35 26 -- -- -- 51 45 37 25 -- -- 55 51 45 34 20 23 58 55 51 41 28 30225 383 106 .2 46 36 28 -- -- -- 52 46 38 26 -- -- 56 52 47 36 21 23 59 56 52 42 28 31300 510 141 .6 48 40 33 20 -- -- 54 49 41 28 -- -- 58 55 50 38 23 24 61 59 55 44 30 31350 595 165 .2 49 42 36 23 -- -- 55 50 43 30 -- -- 60 56 51 40 23 24 62 60 57 46 31 31400 680 188 .8 50 44 38 26 -- -- 56 51 44 31 -- -- 61 58 53 41 24 25 64 61 58 47 31 32450 765 212 .4 50 45 41 28 -- -- 57 52 46 32 -- -- 62 59 54 42 25 25 65 63 60 48 32 32250 425 118 44 33 28 -- -- -- 48 44 41 30 -- -- 53 52 47 38 25 29 57 58 53 43 31 36325 553 153 .4 45 37 32 24 -- -- 50 48 43 32 -- -- 55 55 49 40 27 30 59 60 55 45 33 38450 765 212 .4 48 42 37 30 -- -- 52 50 44 35 20 20 58 59 52 43 29 32 61 64 58 48 36 3955 0 935 259 .6 49 46 41 34 -- -- 53 52 46 36 21 21 59 61 54 44 31 33 62 66 59 49 37 40650 1105 306.8 50 48 43 37 -- -- 55 53 47 38 22 22 60 63 55 46 32 34 63 68 61 51 38 41400 680 188 .8 45 36 29 20 -- -- 50 46 41 33 23 -- 56 54 50 42 31 29 59 60 56 47 35 36500 850 236 47 40 34 25 -- -- 52 48 43 34 25 -- 57 57 52 43 33 30 61 62 58 49 37 37600 1020 283 .2 49 43 38 30 -- -- 53 50 44 36 27 20 59 59 54 45 34 31 62 64 60 51 39 38700 1190 330.4 50 45 41 33 -- -- 55 52 46 37 28 21 60 60 55 46 35 32 63 65 61 52 40 39800 1360 377 .6 51 47 44 36 -- -- 56 53 47 38 29 22 61 62 56 47 36 33 56 67 62 53 41 40450 765 212 .4 45 35 29 20 -- -- 51 47 43 34 22 23 56 56 54 44 33 35 59 61 61 50 40 42525 893 247 .8 47 37 32 23 -- -- 53 48 44 35 23 24 58 57 55 45 34 36 61 63 61 51 41 43650 1105 306.8 50 41 36 29 -- -- 55 49 45 36 24 25 60 58 56 46 35 37 63 64 62 53 43 44850 1445 401.2 53 45 42 35 -- -- 58 51 46 38 26 26 63 60 57 48 37 38 66 66 64 54 44 45950 1615 448.3 55 47 44 38 -- -- 59 52 47 39 26 27 64 61 57 49 38 38 67 66 64 55 45 461050 1785 495 .5 56 49 46 40 -- -- 60 54 47 39 27 27 65 61 58 49 38 39 68 67 65 55 45 4655 0 935 259 .6 46 36 30 -- -- -- 51 46 41 33 23 23 56 55 51 43 33 33 60 60 57 49 39 40675 1148 318 .6 48 39 34 23 -- -- 53 48 43 34 24 25 58 56 52 44 34 35 62 62 58 51 41 41750 1275 354 49 41 36 25 -- -- 54 49 43 35 25 26 59 57 53 45 35 36 63 63 59 51 41 42950 1615 448.3 51 44 40 31 -- -- 56 51 45 37 27 28 62 59 55 47 37 38 65 65 61 53 43 4411 50 1955 542 .7 53 47 43 35 21 -- 58 52 47 38 28 29 64 61 56 48 38 39 67 66 62 54 45 4513 50 2295 637 .1 54 49 46 39 23 24 60 54 48 39 29 30 65 62 57 49 39 40 69 67 64 55 46 47900 1530 424.8 45 38 33 23 -- -- 53 51 47 37 29 28 60 59 57 48 40 39 64 65 63 54 47 451050 1785 495 .5 47 41 37 26 -- -- 55 52 48 38 30 30 62 60 58 49 41 40 66 66 64 55 48 4713 00 221 0 613 .5 51 45 42 31 21 20 57 54 49 40 32 31 64 62 59 50 43 42 68 67 65 57 49 4815 00 255 0 707 .9 53 48 45 34 24 24 59 55 50 41 33 33 66 63 60 51 44 43 70 68 66 58 50 4917 00 2890 802.3 55 50 48 37 27 28 60 55 51 42 34 34 67 64 61 52 45 44 71 69 67 58 51 5021 00 3570 991 .1 59 54 53 42 32 34 62 57 52 43 35 35 69 65 62 53 46 46 74 70 68 60 53 5212 00 2040 566 .3 46 40 33 23 -- -- 55 52 48 39 33 29 62 61 56 49 43 39 66 66 62 56 49 461600 2720 755 .1 52 46 41 29 23 -- 58 55 50 40 35 32 65 63 59 51 45 42 70 68 64 58 52 482200 3740 1038 57 53 50 37 31 28 62 58 53 42 37 35 69 66 62 53 48 45 74 71 67 60 54 512700 4590 1274 61 57 56 41 37 34 64 59 55 44 39 37 71 68 64 54 49 47 76 73 69 61 56 533200 5440 151 0 64 61 60 45 41 39 66 61 57 45 40 38 73 69 65 55 51 49 78 74 70 62 57 5515 00 255 0 707 .9 45 40 35 25 -- -- 56 54 50 41 36 32 64 62 58 51 47 42 68 67 63 57 53 492000 3400 943.9 51 46 43 31 24 21 59 57 52 43 39 34 67 64 61 53 49 45 72 69 66 59 55 512500 4250 1180 56 51 49 36 31 27 62 58 54 44 40 36 69 66 63 54 50 47 74 71 68 60 57 533000 5100 1416 59 55 54 40 36 32 63 60 56 45 42 38 71 67 64 55 52 48 76 72 69 61 58 553500 5950 1652 63 58 59 43 40 37 65 61 57 46 43 39 73 68 65 56 53 50 78 73 71 62 59 564000 6800 1888 65 61 63 46 44 40 67 62 58 47 44 40 74 69 67 57 54 51 79 74 72 63 60 57

10

12

14

16

6

7

8

9

4

5

Performance Notes:1. Test data obtained in accordance with ARI Standard 880-98.

2. Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).

3. Blank Spaces Indicate Sound Power Levels less than 20.

4. Minimum ∆Ps - Minimum Operating Pressure.

5. Pressure is given in Pascals (Pa) and Inches of Water Gauge (In. W.G).

* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.

Actual levels are less than or equal to the levels indicated.

3. Discharge Sound Power Levels with Attenuator

Page 22: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

22

36

4. Radiated Sound Power Levels

1 Test data obtained in accordance with ARI Standard 880-98.2 Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).3 Blank Spaces Indicate Sound Power Levels less than 20.4 Minimum ∆Ps - Minimum Operating Pressure.5 Pressure is given in Pascals (Pa) and Inches of Water Guage (In. W.G).* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.

Actual levels are less than or equal to the levels indicated.

Performance Notes:

Sound Power Levels Lw dB RE 10-12 Watts

CFM CMH L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

Minimum P 125 Pa (0.5 In W.G.) 375 Pa (1.5 In W.G.) 750 Pa (3.0 In W.G.)UnitSize

Minimum Ps Plus

Octave BandAirflow

Octave Band Octave Band Octave Band

100 170 47 44 29 -- -- -- -- 46 38 31 25 21 -- 49 41 37 31 29 25 50 43 40 36 34 30113 192 53 44 30 21 -- -- -- 47 39 33 26 22 -- 50 43 40 34 29 25 51 44 42 37 35 31150 255 71 46 34 27 24 -- -- 50 43 36 29 24 20 52 46 42 36 32 27 53 48 45 40 37 32200 340 94 47 37 33 30 -- -- 52 47 40 33 26 22 54 50 45 39 33 29 56 52 49 43 38 33225 383 106.2 47 39 35 33 24 -- 53 48 41 34 26 22 57 52 47 41 34 29 57 53 50 45 39 34100 170 47 44* 33* 22* 18* 19* 21* 47 38 29 24 20 21 * 50 47 42 37 34 32 52 51 51 46 42 41175 298 83 45* 33* 22* 18* 19* 21* 50 44 34 28 25 22* 56 53 44 40 36 34 58 57 55 49 44 42200 340 94 46 34* 23 18* 19* 21* 51 45 35 29 25 23* 58 55 45 40 36 34 59 59 55 50 45 43250 425 11 8 47 37 28 20* 19* 21* 53 48 38 32 29 26 61 57 47 42 38 36 62 62 57 51 46 43300 510 141.6 49 41 32 25 21 21* 54 49 39 34 30 28 62 58 49 43 39 37 64 64 58 52 47 44350 595 165 .2 50 44 35 29 25 23* 57 51 41 36 33 30 64 59 51 44 41 38 67 65 59 53 48 45200 340 94 40* 33* 23* 18* 20* 22* 48 43 34 30 26 22* 55 54 45 40 36 30 56 57 54 50 47 45225 383 106.2 40* 33* 23* 18* 20* 22* 48 43 35 30 27 22* 56 55 47 42 38 31 58 60 56 52 48 46300 510 141.6 40* 35* 28 22 20* 22* 51 46 37 34 30 27 59 56 48 44 39 33 61 62 57 53 49 46350 595 165 .2 41* 36 31 25 21 * 22* 52 48 39 35 31 27 61 57 49 44 41 36 62 64 58 54 50 47400 680 188.8 41* 38 33 28 24 22* 65 61 42 36 33 27 63 57 50 46 42 38 63 65 59 55 51 48450 765 212 .4 42* 41 37 32 28 23* 56 53 43 37 34 29 64 59 51 48 43 40 65 66 60 56 52 49250 425 11 8 44* 34* 24* 20* 21 * 23* 52 46 39 34 29 23* 52 50 46 40 35 27 55 52 51 46 40 35325 553 153 .4 44* 34* 24* 20* 21 * 23* 52 48 39 35 30 23* 54 56 51 46 42 31 56 57 55 50 45 37450 765 212 .4 44* 38 29 23 21 * 23* 53 49 40 34 29 23* 56 58 53 48 44 34 59 63 60 56 51 40550 935 259 .6 48 41 34 28 21 * 23* 54 49 41 34 29 24* 57 59 54 49 45 34 61 65 62 58 54 42650 1105 306.8 50 45 39 33 23 23* 55 52 44 36 30 24* 60 60 55 49 45 34 62 67 64 60 55 43400 680 188.8 44* 38* 21* 19* 20* 23* 50 45 38 30 23 23* 57 56 51 44 38 35 58 59 56 50 44 40500 850 236 44* 38* 23 21 * 20* 23* 51 45 38 30 23 23* 60 59 53 46 39 37 62 64 60 54 48 44600 1020 283.2 44* 39* 27 24 20* 23* 53 46 39 31 25 24* 61 59 54 45 38 35 64 66 62 55 49 46700 1190 330.4 44* 39* 31 28 20* 23* 55 48 41 33 27 24* 62 60 55 45 39 35 66 68 62 56 49 47800 1360 377 .6 45* 41* 34 33 23 23* 56 50 42 35 29 24* 64 60 55 46 39 35 68 69 63 56 49 46450 765 212 .4 41* 33* 23 18* 19* 21* 44 40 33 29 27 22* 50 51 44 39 37 33 53 57 55 47 43 40525 893 247.8 41* 33* 27 20* 19* 21* 45 41 35 31 29 25 52 51 45 39 37 33 55 57 55 47 44 41650 1105 306.8 41* 34* 32 27 19* 21* 49 44 38 34 31 27 54 53 46 40 38 34 57 57 54 47 44 42850 1445 401.2 44 39 37 34 27 21* 52 48 41 32 34 30 57 55 47 42 40 37 61 59 55 49 45 43950 1615 448.3 47 41 40 37 31 23 54 49 43 39 35 31 59 56 48 43 41 38 62 60 55 49 45 441050 1785 495 .5 50 44 42 40 34 25 56 52 44 40 37 31 60 58 49 45 42 39 63 61 56 49 46 44550 935 259 .6 49* 37* 29* 26* 25* 22* 52* 50 45 44 43 40 64 63 60 55 53 52 67 69 72 70 64 61675 1148 318 .6 49* 38* 34 31 25* 22* 53* 52 47 45 45 41 65 64 59 55 54 53 69 71 69 67 63 61750 1275 354 49* 38* 37 35 25* 22* 55 53 48 46 45 42 65 64 58 56 54 53 71 72 69 67 63 62950 1615 448.3 49* 43 43 42 31 24* 58 56 51 48 46 43 65 64 61 58 56 54 72 73 69 66 64 6211 50 1955 542.7 51 * 48 49 48 37 32 62 60 55 52 48 46 67 65 62 59 57 55 74 73 69 67 65 6313 50 2295 637 .1 55 52 53 53 43 38 64 61 57 54 49 47 69 67 63 60 57 56 74 73 71 70 66 64900 1530 424.8 40* 32* 23 17 * 19* 21* 46 41 35 32 29 25 57 55 49 46 41 35 61 63 61 56 52 431050 1785 495 .5 40* 32* 28 19* 19* 21* 47 42 36 33 30 25 58 55 49 46 41 36 63 63 60 56 51 4313 00 221 0 613 .5 41* 37 34 25 19* 21* 51 45 38 34 30 26 60 56 51 47 42 37 65 63 59 55 51 4315 00 255 0 707.9 44 40 38 30 23 22* 52 47 41 37 32 28 60 56 51 47 43 38 67 64 59 55 51 4417 00 2890 802.3 47 43 41 33 26 23 54 49 43 38 34 29 62 57 53 48 44 40 68 64 60 55 51 4521 00 3570 991 .1 53 47 47 39 32 27 58 53 48 42 37 33 64 59 54 49 45 41 70 65 62 57 52 4712 00 2040 566.3 42* 32* 23* 17 * 19* 21* 48 42 38 38 33 24 57 55 49 46 48 37 61 62 59 55 55 471600 2720 755 .1 43* 33* 30 20 19* 21* 52 46 42 40 37 31 60 56 51 47 49 39 64 63 59 54 55 482200 3740 1038 43* 39 40 28 23 21* 55 50 46 41 37 31 63 60 55 49 50 43 68 65 61 55 55 492700 4590 1274 48 44 49 35 29 23* 58 53 52 43 39 32 66 62 58 51 51 46 71 67 62 56 56 513200 5440 1510 51 48 57 42 35 29 60 56 58 46 41 35 69 64 62 54 53 47 73 69 65 58 58 5315 00 255 0 707.9 45* 34 30 19* 19* 21* 50 44 36 33 27 24 62 59 49 41 35 31 66 65 58 51 45 382000 3400 943.9 46* 39 36 25 21 * 21* 51 46 39 35 30 26 63 59 49 42 36 33 69 67 59 52 45 402500 4250 1180 46* 45 45 33 26 21* 54 49 45 38 32 27 64 59 51 45 39 34 71 68 60 53 46 413000 5100 1416 49 49 54 38 31 24 57 53 54 41 35 29 66 60 56 47 41 36 73 68 61 53 47 423500 5950 1652 53 54 60 42 37 29 61 56 60 44 38 32 68 62 61 50 44 39 75 69 63 55 48 434000 6800 1888 57 57 61 46 41 33 64 60 61 48 42 36 71 64 62 52 46 40 77 70 64 56 51 46

14

16

8

9

10

12

4

5

6

7

Performance Notes:1. Test data obtained in accordance with ARI Standard 880-98.

2. Air Flow given in Liters/Second (L/s), Cubic Feet/Minute (CFM) and Cubic Meter/Hour (CMH).

3. Blank Spaces Indicate Sound Power Levels less than 20.

4. Minimum ∆Ps - Minimum Operating Pressure.

5. Pressure is given in Pascals (Pa) and Inches of Water Gauge (In. W.G).

* Sound Power Level Data has reached ambient levels in the test room or is determined by instrument limitations.

Actual levels are less than or equal to the levels indicated.

4. Radiated Sound Power Levels

Page 23: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

23

D. Heater Selection Guides and Performances

Coil Air Flow Rate (L/s)Rows L/s HD Loss 59 71 83 94 106 118 142 165 189

1-RowSingleCircuit

0.03 0.24 1.99 2.14 2.29 2.40 2.49 2.58 2.73 2.87 2.99

0.06 0.84 2.23 2.43 2.61 2.75 2.9 3.02 3.22 3.43 3.58

0.13 2.85 2.4 2.61 2.81 2.99 3.17 3.31 3.53 3.81 4.02

0.25 9.60 2.49 2.75 2.96 3.14 3.34 3.49 3.73 4.04 4.28

2-RowMulti-Circuit

0.06 0.24 3.58 3.96 4.28 4.54 4.81 5.04 5.42 5.77 6.07

0.13 0.84 3.90 3.90 3.78 5.13 5.45 5.74 6.27 6.71 7.12

0.25 2.85 4.10 4.10 5.07 5.48 5.83 6.21 6.83 7.39 7.85

0.32 4.20 4.13 4.13 5.13 5.54 5.95 6.30 6.95 7.53 8.03

Coil Air Flow Rate (L/s)Rows L/s HD Loss 94 118 142 165 189 236 283 330 378

1-RowSingleCircuit

0.03 0.33 2.75 2.96 3.17 3.31 3.46 3.66 3.84 3.99 4.13

0.06 1.14 3.17 3.49 3.75 3.99 4.19 4.51 4.81 5.04 5.25

0.13 3.87 3.36 3.84 4.16 4.45 4.69 5.13 5.48 5.80 6.07

0.25 13.02 3.63 4.04 4.40 4.72 5.01 5.51 5.92 6.30 6.65

2-RowMulti-Circuit

0.06 0.33 5.07 5.66 6.13 6.54 6.89 7.47 7.94 8.32 8.65

0.13 1.14 5.71 6.45 7.09 7.65 8.15 8.97 9.67 10.26 10.79

0.32 5.73 6.18 7.06 7.85 8.56 9.17 10.26 11.20 11.99 12.72

0.63 19.23 6.36 7.30 8.15 8.91 9.58 10.79 11.8 4 12.75 13.57

Coil Air Flow Rate (L/s)Rows L/s HD Loss 142 189 236 283 330 378 425 472 566

1-RowSingleCircuit

0.06 0.24 4.25 4.72 5.10 5.39 5.66 5.86 6.07 6.24 6.54

0.13 0.78 4.81 5.45 5.95 6.36 6.74 7.06 7.36 7.59 8.06

0.25 2.58 5.19 5.92 6.54 7.06 7.50 7.88 8.26 8.59 9.17

0.50 8.73 5.42 6.21 6.89 7.47 7.97 8.44 8.85 9.23 9.91

2-RowMulti-Circuit

0.13 0.54 7.97 9.23 10.23 11.05 11.75 12.37 12.90 13.36 14.18

0.19 1.08 8.47 9.91 11.08 12.07 12.92 13.66 14.30 14.92 15.94

0.32 2.61 8.94 10.52 11.87 13.01 14.01 14.92 15.71 16.44 17.73

0.63 8.79 9.32 11.08 12.57 13.89 15.03 16.06 17.03 17.88 19.40

Coil Air Flow Rate (L/s)Rows L/s HD Loss 189 236 283 330 378 472 566 661 755

1-RowSingleCircuit

0.06 0.30 5.48 5.95 6.33 6.62 6.89 7.36 7.7 1 8.00 8.26

0.13 1.02 6.36 6.98 7.50 7.97 8.35 9.03 9.58 10.08 10.49

0.25 3.45 6.92 7.68 8.32 8.88 9.38 10.23 10.96 11.61 12.16

0.50 11.61 7.27 8.09 8.82 9.47 10.02 11.02 11.87 12.63 13.28

2-RowMulti-Circuit

0.13 0.69 10.37 11.58 12.31 13.45 14.18 15.4 2 16.38 17.23 17.94

0.19 1.38 11.14 12.57 13.75 14.8 15.71 17.2 6 18.52 19.61 20.54

0.32 3.39 11.84 13.45 14.86 16.09 17.17 19.08 20.66 22.04 23.24

0.63 11.43 12.43 14.24 15.86 17.26 18.52 20.75 22.65 24.32 25.82

Inlet Size 4", 5"&6"

Inlet Size 7"&8"

Inlet Size 9"&10"

Inlet Size 12"

* Table based on high temperature water (99oC)

* Table based on high temperature water (99oC)

* Table based on high temperature water (99oC)

* Table based on high temperature water (99oC)

1. 1 & 2 Row Hot Water Coil Data (Metric Units)

1 & 2 Row Hot Water Coil Data – Metric Units

Page 24: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

24

* Table based on high temperature water (99oC)

* Table based on high temperature water (99oC)

1 & 2 Row Hot Water Coil Data – Metric Units – cont.

Coil Air Flow Rate (L/s)Rows L/s HD Loss 283 378 472 566 661 755 850 1033 1227

1-RowSingleCircuit

0.13 0.48 8.73 9.73 10.52 11.17 11.72 12.19 12.63 13.3 3 13.95

0.19 0.96 9.41 10.61 11.58 12.37 13.04 13.66 14.13 15.09 15.88

0.32 2.31 10.05 11.46 12.57 13.54 14.36 15.09 15.74 16.91 17.88

0.63 7.77 10.64 12.22 13.51 14.62 15.59 16.47 17.23 18.64 19.84

2-RowMulti-Circuit

0.13 0.42 14.13 16.00 17.44 18.58 19.55 20.34 21.04 22.19 23.09

0.19 0.87 15.53 17.88 19.72 21.25 22.54 23.65 24.59 26.23 27.58

0.32 2.10 16.88 19.72 22.04 23.97 25.64 27.11 28.40 30.36 32.53

0.63 7.05 18.08 21.39 24.18 26.55 28.63 30.51 32.18 35.11 37.51

Coil Air Flow Rate (L/s)Rows L/s HD Loss 378 472 566 661 755 849 944 1038 1133 1321 1510

1-RowSingleCircuit

0.13 0.54 10.61 11.52 12.22 12.84 13.36 13.84 14.27 14.63 14.98 15.59 16.09

0.19 1.09 11.61 12.66 13.57 14.33 15.01 15.60 16.15 16.63 17.09 17.88 18.55

0.32 2.64 12.51 13.80 14.89 15.80 16.65 17.39 18.05 18.68 19.25 20.28 21.19

0.63 8.94 13.36 14.33 16.09 17.20 18.17 19.09 19.90 20.64 21.34 22.63 23.77

2-RowMulti-Circuit

0.19 0.33 18.55 20.46 22.04 23.36 24.5 25.48 26.35 27.12 27.81 29.04 30.07

0.25 0.54 19.81 22.04 23.89 25.47 26.85 28.03 29.10 30.08 30.95 32.47 33.79

0.32 0.78 20.63 23.09 25.15 26.90 28.46 29.82 31.04 32.17 33.18 34.90 36.49

0.63 2.64 22.60 25.59 28.16 30.42 32.44 34.25 35.90 37.42 38.80 41.29 43.52

∆T℃ 22 28 33 39 44 56 67 78 83 89 100 111

Factor 0.27 0.33 0.40 0.47 0.53 0.67 0.80 0.93 1.00 1.07 1.20 1.33

Inlet Size 14"

Inlet Size 16"

Correction Factors - 1 & 2 Row Hot Water Coils

Performance Notes - 1 & 2 Row Hot Water Coils:1. Tabulated values are in kW

2. Tables on pages 47 & 48 are based on temperature difference of 83oC between entering air (16oC) and entering water (99oC).

For other temperature differences, multiply kW values by factor as listed above.

3. Minimum air and water flow values are based on ASHRAE recommendations for coil selection.

For selections below these tabulated water or airflow values, please consult your local JC sales representatives.

4. HD (Head) loss is in kilopascals.

5. Air temperature rise = ATR; ATR( oC) = 829 x kW / L/s (Air Flow)

6. Water temperature drop = WTD; WTD ( oC) = 0.244 x kW / L/s (Water Flow)

7. Connections: Single Circuit is 13mm OD male solder.

Multi-Circuit is 22mm OD male solder.

Page 25: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

25

Coil Air Flow Rate (CFM)Rows GPM HD Loss 125.01 150.44 175.87 199.17 224.6 250.03 300.88 349.62 400.47

1-RowSingleCircuit

0.5 0.08 6.8 7.3 7.8 8.2 8.5 8.8 9.3 9.8 10.2

1.0 0.28 7.6 8.3 8.9 9.4 9.9 10.3 11.0 11.7 12.2

2.1 0.95 8.2 8.9 9.6 10.2 10.8 11.3 12.0 13.0 13.7

4.0 3.20 8.5 9.4 10.1 10.7 11.4 11.9 12.7 13.8 14.6

2-RowMulti-Circuit

1.0 0.08 12.2 13.5 14.6 15.5 16.4 17.2 18.5 19.7 20.7

2.1 0.28 13.3 13.3 12.9 17.5 18.6 19.6 21.4 22.9 24.3

4.0 0.95 14.0 14.0 17.3 18.7 19.9 21.2 23.3 25.2 26.8

5.1 1.40 14.1 14.1 17.5 18.9 20.3 21.5 23.7 25.7 27.4

Coil Air Flow Rate (CFM)Rows GPM HD Loss 199.17 250.03 300.88 349.62 400.47 500.06 599.64 699.23 800.94

1-RowSingleCircuit

0.5 0.11 9.4 10.1 10.8 11.3 11.8 12.5 13.1 13.6 14.1

1.0 0.38 10.8 11.9 12.8 13.6 14.3 15.4 16.4 17.2 17.9

2.1 1.29 11.5 13.1 14.2 15.2 16.0 17.5 18.7 19.8 20.7

4.0 4.34 12.4 13.8 15.0 16.1 17.1 18.8 20.2 21.5 22.7

2-RowMulti-Circuit

1.0 0.11 17.3 19.3 20.9 22.3 23.5 25.5 27.1 28.4 29.5

2.1 0.38 19.5 22.0 24.2 26.1 27.8 30.6 33.0 35.0 36.8

5.1 1.91 21.1 24.1 26.8 29.2 31.3 35.0 38.2 40.9 43.4

10 6.41 21.7 24.9 27.8 30.4 32.7 36.8 40.4 43.5 46.3

Coil Air Flow Rate (CFM)Rows GPM HD Loss 300.88 400.47 500.06 599.64 699.23 800.94 900.52 1000.1 1199.3

1-RowSingleCircuit

1.0 0.08 14.5 16 .1 17.4 18.4 19.3 20.0 20.7 21.3 22.3

2.1 0.26 16.4 18.6 20.3 21.7 23.0 24.1 25.1 25.9 27.5

4.0 0.86 17.7 20.2 22.3 24.1 25.6 26.9 28.2 29.3 31.3

7.9 2.91 18.5 21.2 23.5 25.5 27.2 28.8 30.2 31.5 33.8

2-RowMulti-Circuit

2.1 0.18 27.2 31.5 34.9 37.7 40.1 42.2 44.0 45.6 48.4

3.0 0.36 28.9 33.8 37.8 41.2 44.1 46.6 48.8 50.9 54.4

5.1 0.87 30.5 35.9 40.5 44.4 47.8 50.9 53.6 56.1 60.5

10.0 2.93 31.8 37.8 42.9 47.4 51.3 54.8 58.1 61.0 66.2

Coil Air Flow Rate (CFM)Rows GPM HD Loss 400.47 500.06 599.64 699.23 800.94 1000.1 1199.3 1400.6 1599.8

1-RowSingleCircuit

1.0 0.10 18.7 20.3 21.6 22.6 23.5 25.1 26.3 27.3 28.2

2.1 0.34 21.7 23.8 25.6 27.2 28.5 30.8 32.7 34.4 35.8

4.0 1.15 23.6 26.2 28.4 30.3 32.0 34.9 37.4 39.6 41.5

7.9 3.87 24.8 27.6 30.1 32.3 34.2 37.6 40.5 43.1 45.3

2-RowMulti-Circuit

2.1 0.23 35.4 39.5 42.0 45.9 48.4 52.6 55.9 58.8 61.2

3.0 0.46 38.0 42.9 46.9 50.5 53.6 58.9 63.2 66.9 70.1

5.1 1.13 40.4 45.9 50.7 54.9 58.6 65.1 70.5 75.2 79.3

10.0 3.81 42.4 48.6 54.1 58.9 63.2 70.8 77.3 83.0 88.1

Inlet Size 4", 5"&6"

Inlet Size 7"&8"

Inlet Size 9"&10"

Inlet Size 12"

* Table based on high temperature water (210oF)

* Table based on high temperature water (210oF)

* Table based on high temperature water (210oF)

* Table based on high temperature water (210oF)

2. 1 & 2 Row Hot Water Coil Data (SI Units)

1 & 2 Row Hot Water Coil Data – Metric Units

Page 26: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

26

* Table based on high temperature water (210oF)

* Table based on high temperature water (210oF)

1 & 2 Row Hot Water Coil Data – Metric Units – cont.

Coil Air Flow Rate (CFM)Rows GPM HD Loss 599.64 800.94 1000.1 1199.3 1400.6 1599.8 1801 2188.8 2599.9

1-RowSingleCircuit

2.1 0.16 29.8 33.2 35.9 38.1 40.0 41.6 43.1 45.5 47.6

3.0 0.32 32.1 36.2 39.5 42.2 44.5 46.6 48.2 51.5 54.2

5.1 0.77 34.3 39.1 42.9 46.2 49.0 51.5 53.7 57.7 61.0

10.0 2.59 36.3 41.7 46.1 49.9 53.2 56.2 58.8 63.6 67.7

2-RowMulti-Circuit

2.1 0.14 48.2 54.6 59.5 63.4 66.7 69.4 71.8 75.7 78.8

3.0 0.29 53.0 61.0 67.3 72.5 76.9 80.7 83.9 89.5 94.1

5.1 0.70 57.6 67.3 75.2 81.8 87.5 92.5 96.9 103.6 111.0

10.0 2.35 61.7 73.0 82.5 90.6 97.7 104.1 109.8 119.8 128.0

Coil Air Flow Rate (CFM)Rows GPM HD Loss 800.94 1000.1 1199.3 1400.6 1599.8 1798.9 2000.2 2199.4 2400.7 2799 3199.5

1-RowSingleCircuit

2.1 0.18 36.2 39.3 41.7 43.8 45.6 47.2 48.7 49.9 51.1 53.2 54.9

3.0 0.36 39.6 43.2 46.3 48.9 51.2 53.2 55.1 56.7 58.3 61.0 63.3

5.1 0.88 42.7 47.1 50.8 53.9 56.8 59.3 61.6 63.7 65.7 69.2 72.3

10 2.98 45.6 48.9 54.9 58.7 62.0 65.1 67.9 70.4 72.8 77.2 81.1

2-RowMulti-Circuit

3.0 0.11 63.3 69.8 75.2 79.7 83.6 86.9 89.9 92.5 94.9 99.1 102.6

4.0 0.18 67.6 75.2 81.5 86.9 91.6 95.6 99.3 102.6 105.6 110.8 115.3

5.1 0.26 70.4 78.8 85.8 91.8 97.1 101.8 105.9 109.8 113.2 119.1 124.5

10.0 0.88 77.1 87.3 96.1 103.8 110.7 116.9 122.5 127.7 132.4 140.9 148.5

∆T℃ 40 50 59 70 79 101 121 140 149 160 180 200

Factor 0.27 0.33 0.40 0.47 0.53 0.67 0.80 0.93 1.00 1.07 1.20 1.33

Inlet Size 14"

Inlet Size寸16"

Correction Factors - 1 & 2 Row Hot Water Coils

Performance Notes - 1 & 2 Row Hot Water Coils:1. Tabulated values are in MBH, 1MBH = 1000BTU/Hr.

2. Tables on pages 49 & 50 are based on temperature difference of 150oF between entering air (60oF)and entering water (210 oF).

For other temperature differences, multiply kW values by factor as listed above.

3. Minimum air and water flow values are based on ASHRAE recommendations for coil selection.

For selections below these tabulated water or airflow values, please consult your local JC sales representatives.

4. HD (Head) loss is in In. W.G.

5. Air temperature rise = ATR; ATR( oF) = 927 x MBH / CFM (Air Flow)

6. Water temperature drop = WTD; WTD (oF) = 2.04 x MBH / GPM (Water Flow)

7. Connections: Single Circuit is 1/2" OD male solder.

: Multi-Circuit is 7/8" OD male solder.

Page 27: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

27

E. Acoustical Engineering Guidelines

1. Engineering Guide / Terminal Units

1.1 Estimating Sound Levels – Noise Criteria

1.1.1 Noise Criteria – NCNoise Criteria or NC level values have become widely accepted as a

measure of room noise levels and as a rating scale for equipment that is

expected to stay within those levels.

When deriving NC levels for terminal units, the sound pressure level of

octave bands 2 through 7 should be considered. These pressure levels

are plotted on a standard NC curve form (Figure 1).

The highest pressure level when measured against the NC curves,

regardless of frequency, determines the NC of the unit.

Table 1 illustrates the ASHRAE recommended space NC values for many

commercial air conditioning applications. Terminal units should be

selected so that the tabulated NC levels are within these design goals.

Most manufacturers' catalogue data for terminal units lists the sound

power levels at various operating conditions. To determine the actual

sound pressure level in the space, we must evaluate what attenuation

factors are presented in the system and subtract these values form the

manufacturers sound power levels.

The Air Conditioning and Refrigeration Institute (AHRI) has published

"A Procedure for Estimating Occupied Space Sound Levels in the

Application of Air Terminals and Air Outlets" , known as Standard 885-

90. This standard forms the basis for the sound estimation guidelines

presented on the following pages. These guidelines are offered for typical

conditions. For a more detailed analysis, refer to AHRI Standard 885-90

and the 1991 ASHRAE HVAV Applications Handbook, Chapter 42.

63 125 250 500 1000 2000 4000 8000Band Centre Frequencies, Hz*

*(American Standard S 1.6 1960)

Figure 1: Noise Criteria Curves

PWL,

Oct

ave

Band

Sou

nd P

ower

Lev

el, d

B, re

10-1

2 Wat

tsSP

L, O

ctav

e Ba

nd S

ound

Pre

ssur

e Le

vel,

dB, r

e 0.

0002

Micr

obar 90

80

70

60

50

40

30

20

10

85

75

65

55

45

35

25

15

5

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Approximate threshold ofhearing for continuous noise

Table 1: Design Guideline for HVAC System Noise in Unoccupied Spaces

Space RC (N) or NC Level

1 Private residences 25 - 35

2

Hotels / Motels - Individual Rooms or Suites - Meeting / Banquet Rooms - Halls, Corridors, Lobbies - Service / Support Areas

25 - 35 25 - 35 35 - 45 35 - 45

3

Office Buildings - Executive and Private Offices - Conference Rooms - Teleconference Rooms - Open-Plan Offices - Circulation and Public Lobbies

25 - 35 25 - 35

25 (max) 30 - 40 30 - 40

4

Hospitals and Clinics - Private Rooms - Wards - Operating Rooms - Corridors - Public Areas

25 - 35 30 - 40 25 - 35 30 - 40 30 - 40

5

Performing Arts Spaces - Drama Theaters - Concert and Recital Halls - Music Teaching Studios - Music Practice Rooms

25 (max)

b 25 (max) 35 (max)

6

Laboratories (With Fume Hoods - Testing/Research, Minimal Speech Communication - Research, Extensive Telephone use, Speech Communication - Group Teaching

45 - 55 40 - 50 35 - 45

7 Churches, Mosques, Synagogues With Critical Music Programs

25 - 35 b

8

Schools - Classrooms up to 750 ft2 (75 m2) - Classrooms over 750 ft2 (75 m2) - Lecture Rooms for more than 50 (Unamplified Speech

40 (max) 35 (max) 35 (max)

9 Libraries 30 - 40

10Courtrooms - Unamplified Speech - Amplified Speech

25 - 35 30 - 40

11Indoor Stadiums and Gymnasiums -School and College Gymnasiums and natatoriums -Large Seating Capacity Spaces (with Amplified Speech)

40 - 50c 45 - 55c

a. The values and ranges are based on judgement and experience, not on quantitative evaluations of human reactions. They represent general limits of acceptability for typical building occupancies. Higher or lower values may be appropriate and should be based on a careful analysis of economics, space usage, and user needs. They are not intended to serve by themselves as a basis for a contractual requirement.

b. An experience acoustical consultant should be retained for guidance on acoustically critical spaces (below RC30) and for all performing arts spaces.

c. Spectrum levels and sound quality are of lesser importance in these spaces than overall sound levels.

Page 28: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

28

1.2 Estimating Sound Levels

1.2.1 Radiated SoundFigure 2 illustrates the sound path for inlet and casing radiated sound.

The attenuation factors which apply to this sound path are Plenum/Ceiling

Effect and Space Effect.

Plenum/Ceiling Effect The plenum/ceiling effect is the combined attenuation of the plenum

absorption and the transmission loss through the ceiling. Table 2 provides

typical values for plenum/ceiling effect of several ceiling types based on

typical penetration and light fixtures.

Space EffectThis is the attenuation of the room due to absorptive surfaces, furnishings

and room volume. The space effect of a typical room can be estimated

using the Shultz equation: S=10LOG r (Ft³) + 3 LOG f -25

Wheres = space effect attenuation

r = shortest distance in feet from noise source to the receiver occupant

v = room volume in cubic feet

f = octave band centre frequency of interest

UpstreamDuct Breakout

Radiated

Unit Inlet &Casing Radiated

Outlet Discharge/Outlet Generated

Duct BreakoutRadiated

DischargeDuct Breakout

Radiated

Figure 2:Sound Paths

Figure 2:Radiated Sound

Figure 3:Radiated Sound

Table 2 Plenum/Ceiling EffectOctave Band 2 3 4 5 6 7

Fiberglass Tile 17 18 21 25 29 35

Mineral Fiber 16 18 20 26 31 36

Sheet Rock 21 25 25 27 27 28VAV with Attenuator W×H (inch) 2 3 4 5 6 7

0606/0806/0811 29×14 0.6 1.1 3.2 7.8 7.3 5.6

1006/1011/1018/1211/1218/1221 37×17 0.6 1 2.9 7 6.1 4.9

1411/1418/1421/1621 45×19 0.5 0.9 2.7 6.5 5.4 4.5

1424/1624 49×19 0.5 0.8 2.7 6.5 5.3 4.4

1.2.2 Discharge SoundFigure 3 illustrates the sound path for outlet discharge sound. The

attenuation factors which apply to this sound path are:

a Duct Insertion Loss

a Branch Power Division

a Elbow and Tee Loss

a Line Flexible Duct Insertion Loss

a End Reflection Factor

a Space Effect

Duct Insertion LossAcoustically lined ductwork is effective in absorbing sound as it

travels down the duct. Table 3 lists the attenuation in VAV unit with

attenuator.

Table 3 Attenuation in Internally Insulated Ducts

Branch Power Division At branch take-offs the acoustic energy is divided in proportion the

flow division of the take-off. Table 4 lists the attenuation at various

percentages of total flow carried by the branch ductwork.

Page 29: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

29

Table 4 Flow Division

Duct Dia.(Inches) Duct Length (Ft.) 2 3 4 5 6 7

6 3 9 12 28 32 37 23

6 6 5 7 17 22 25 16

8 3 9 18 29 31 32 20

8 6 5 10 18 19 21 12

10 3 8 19 28 30 29 18

10 6 4 11 18 17 18 9

12 3 7 17 27 28 26 15

12 6 3 9 16 15 15 7

16 3 3 7 19 23 20 8

16 6 1 2 11 11 11 5

% Total Flow Division 5 10 15 20 30 40 50 60

dB Attenuation 13 10 8 7 5 4 3 1

Lined Flexible Duct Insertion LossThe insertion loss of lined flexible duct is listed in Table 5.

Table 5 Lined Flexible Duct Insertion Loss

End Reflection When sound passes from a small space such as a duct into a large space

such as a room, a portion of the sound is reflected in the room. Table 6

lists the attenuation values for end reflection. Note that the full attenuation

of end reflection is obtained only when air exits an open duct with at least

3 to 5 diameters of straight duct. Diffusers will reduce the end reflection by

at least 6 db.

Table 6 End Reflection

Duct Dia. (Inches)Octave Band & Center Frequency Hz.

2 3 4 5 6 7

6 12 8 4 1 0 0

8 11 6 2 0 0 0

10 9 5 1 0 0 0

12 8 4 1 0 0 0

16 6 2 0 0 0 0

1.2.3 Environmental Adjustment FactorsAccording to AHRI Standard 885.90, an environmental adjustment

factor must be applied to manufacturer’s data if the sound power

data has been obtained in accordance with AHRI Standard 880.

Sound power levels obtained in accordance with Standard 880 are

based on a free field calibration of the reference sound source.

According to AHRI, real rooms at low frequencies behave acoustically

more like reverberant rooms than open spaces (free field). Therefore

it is necessary to adjust power levels obtained in accordance with

AHRI Standard 880 by the Environmental Adjustment Factor Listed

in Table 7. These factors are subtracted from the manufacturer’s

sound power level data.

JOHNSON CONTROLS tests all terminal units in accordance with AHRI

Standard 880, therefore these corrections should be applied when

estimating the sound power in occupied spaces.

Octave Band 2 3 4 5 6 7

Factor, db 2 1 0 0 0 0

Table 7 Environmental Adjustment Factor

Space Effect The space effect is identical to the Shultz equations as radiated sound

Page 30: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

30

F. Single Duct Terminal Units Suggested Specification

1. GeneralFurnish and install JOHNSON CONTROLS single duct, variable volume

air distribution assemblies of the sizes and capacities as shown on the

plans.

The assemblies shall be pressure independent and shall reset to any air

flow between zero and the maximum catalogued air volume.

At an inlet velocity of 2,000 fpm, the differential static pressure for any

unit with attenuator section, sizes 4 through 16, shall not exceed 0.11”

W.G.

Sound ratings of air distribution assemblies, shall not exceed ___ NC at

___ static pressure.

Pressure shall be AIR Certified.

The terminal unit controller shall be a dedicated, microprocessor-

based, pressure independent VAV controller complete with electronic

flow transducer. The controller shall be capable of stand-alone

operation and have the ability to network with a building automation

system, personal computer or portable operator interface device.

The electric actuator shall be 24 VAC bi-directional, direct coupled to

the damper shaft. The actuator must be capable of operating in the

stalled position without overheating or mechanical damage.

Terminal unit controller, flow transducer and electric actuator shall be

supplied by the terminal unit manufacturer. All components shall be

factory wired, calibrated and pre-tested to ensure a full functional unit.

The zone sensor shall be furnished by the terminal unit manufacturer

and shall include temperature setpoint adjustment and access for

connection of a hand-held operator terminal.

The DDC control package shall be calibrated and factory set for the

maximum and minimum flow rates as scheduled on the drawings.

The air flow sensor shall be of a cross configuration located at the inlet

of the assembly and shall have multiple pickup points, designed to

average the flow across the inlet of the assembly. The air flow sensor

shall amplify the sensed air flow signal.

The assembly casing shall be constructed of 22 gauge zinc coated

steel, internal insulation 25mm (1”) 48kg/m³ (3lb/ft³) lined with double

side aluminum foil to prevent air erosing which complies with Fire Test

BS476 parts 6 & 7 to meet class “O”.

The primary air valve damper shall be heavy gauge metal, with

peripheral gasket, pivoted in self-lubricating bearings. In the full closed

position, air leakage past the closed damper shall not exceed 2% of

the nominal catalogue rating at 3” inlet static pressure, as rated by ARI

Standard 880.

The air terminal unit shall be designed, installed and field adjusted,

if necessary, to maintain controlled pressure independent air flow.

For optimum performance, installed units shall be provided with a

minimum of four duct diameters of straight inlet duct, same size as the

inlet, between the inlet and any takeoff, transition or fitting. When inlet

flow deflections and/or turbulence alter factory calibration by more

than 10%, installers shall field adjust the air volume calibration settings.

To facilitate field adjustments, the terminal unit manufacturer shall

furnish a portable hand-held operator interface. The operator

interface shall have the capability of monitoring and changing all

inputs, setpoints and operating parameters of the VAV controller by

connection to the zone sensor.

All control components shall be mounted inside a protective metal

shroud.

2. Digital Control SDV

Page 31: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers
Page 32: Single Duct Terminal Units - Orientecosystems · 2018. 2. 22. · Server ADX Client. 7 VMA1617/1632 Series Controllers Description VMA16s (32-bit) are programmable digital controllers

PUBL-5342 (1013)© 2013 Johnson Controls, Inc. www.johnsoncontrols.com

Johnson Controls is a global diversified technology and industrial leader serving customers in more

than 150 countries. Our 168,000 employees create quality products, services and solutions to optimize

energy and operational efficiencies of buildings; lead-acid automotive batteries and advanced batteries

for hybrid and electric vehicles; and interior systems for automobiles. Our commitment to sustainability

dates back to our roots in 1885, with the invention of the first electric room thermostat. Through our

growth strategies and by increasing market share we are committed to delivering value to shareholders

and making our customers successful. In 2013, Corporate Responsibility Magazine recognized Johnson

Controls as the #14 company in its annual “100 Best Corporate Citizens” list. For additional information,

please visit http://www.johnsoncontrols.com.

Johnson Controls Building Efficiency delivers products, services and solutions that increase

energy efficiency and lower operating costs in buildings for more than one million customers. Operating

from 500 branch offices in more than 150 countries, we are a leading provider of equipment, controls

and services for heating, ventilating, air-conditioning, refrigeration and security systems. We have been

involved in more than 500 renewable energy projects including solar, wind and geothermal technologies.

Our solutions have reduced carbon dioxide emissions by 16 million metric tons and generated savings

of $7.5 billion since 2000. Many of the world’s largest companies rely on us to manage 1.8 billion square

feet of their commercial real estate.

Asia Engineering Centre: Wuxi, ChinaShanghai Distribution Center: Shanghai, ChinaAsia Centre of Excellence in Engineering (CoEE): Beijing, China · Mumbai & Pune, IndiaManufacturing/Assembly: Guangzhou & Wuxi, China · Pune, India

ThailandTel : +66 (2) 717 1260-80Fax: +66 (2) 717 0861

MalaysiaTel : +60 (3) 7628 4393Fax: +60 (3) 7620 0538

IndonesiaTel : +62 (21) 5366 8500Fax: +62 (21) 5366 8300

AustraliaTel : +61 (2) 9805 8300Fax: +61 (2) 9889 3016

New ZealandTel : +64 (9) 444 6434Fax: +64 (9) 444 2092

JapanTel : +81 (3) 5738 6100Fax: +81 (3) 5738 6298

China (Shanghai)Tel : +86 (21) 6276 6509Fax: +86 (21) 6277 3543

SingaporeTel : +65 6748 0202Fax: +65 6284 3017

KoreaTel : +82 (2) 554 5935Fax: +82 (2) 554 5739

Hong KongTel : +852 2590 0012Fax: +852 2516 5648

TaiwanTel : +886 (2) 2657 5568Fax: +886 (2) 2657 6388

MacauTel : +853 2875 1820Fax: +853 2875 1825

IndiaTel : +91 (22) 3082 2200Fax: +91 (22) 3088 1592

Printed on recycled paper

Information contained herein including but not limited to the product design, specification or appearance is subject to change without notice. This document is for reference only, please refer to the actual product when buying.