2
IPS109-2 January 1997 MTL ICC300 SERIES * Three-port isolation between inputs, outputs and power supply * Provides two outputs from one 4 to 20mA transmitter * Line-fault detection feature provides alarm facilities * Transfer accuracy better than 0.1% of span * 20 to 35V dc power supplies T- or G-section DIN-rail mounting ICC312 repeater power supply, 4 to 20mA, for 2-wire transmitters with dual outputs The ICC312 is an independently powered isolator which provides both a fully isolated dc supply for energising a two-wire transmitter (or other 4 to 20mA current source) while also transferring the transmitter current to two separate isolated output circuits driving loads up to 1k. Line-fault detection facilities (also isolated) are provided by an open collector which can be used to activate an alarm. When the input cable is broken, no current flows into terminal 8 and the line-fault detection (LFD) output is OFF. When a current greater than 1mA flows in the input, then LFD output is ON. Power supply required is 20 to 35V dc. SPECIFICATION Number of input channels One (either terminals 7&8 or 8&9) Input channel (terminals 7 & 8) 2-wire transmitter supply: 4 to 20mA Input channel (terminals 8 & 9) 4 to 20mA current source Number of output channels Two Input signal 4 to 20mA Isolation between input, output 1, output 2 and power supply 1500V dc/ac Power supply 20 to 35V dc Voltage available for transmitter 20V minimum at 20mA Voltage drop across input from current source (terminals 8 & 9) 2.4V maximum Power requirements (supplying a transmitter) 150mA maximum at 20V dc with a 20mA signal 120mA maximum at 35V dc with a 20mA signal Power requirements (from a current source) 110mA maximum at 20V dc with a 20mA signal 90mA maximum at 35V dc with a 20mA signal Load resistance 0 to 1k Transfer accuracy at 25 ° C for both outputs Better than 20 μA Line-fault detection (LFD) output Transistor open collector output Circuit diagram ICC312 Load Load 20 to 35V dc 4 to 20mA 4 to 20mA 2k24V 4 to 20mA 4 to 20mA Current source 1 2 3 4 5 6 7 8 9 10 11 12 + - LFD *

Signal Multiplier Icc312

Embed Size (px)

DESCRIPTION

Signal Multiplier Icc312

Citation preview

Page 1: Signal Multiplier Icc312

IPS109-2

January 1997

MTL ICC300 SERIES

* Three-port isolationbetween inputs, outputsand power supply

* Provides two outputs fromone 4 to 20mA transmitter

* Line-fault detectionfeature provides alarmfacilities

* Transfer accuracy betterthan 0.1% of span

* 20 to 35V dc powersuppliesT- or G-section DIN-railmounting

ICC312 repeaterpower supply,4 to 20mA,for 2-wiretransmitterswith dual outputs

The ICC312 is an independently powered isolator which provides both a fully isolated dcsupply for energising a two-wire transmitter (or other 4 to 20mA current source) while alsotransferring the transmitter current to two separate isolated output circuits driving loads up to1kΩ. Line-fault detection facilities (also isolated) are provided by an open collector which canbe used to activate an alarm. When the input cable is broken, no current flows into terminal 8and the line-fault detection (LFD) output is OFF. When a current greater than 1mA flows in theinput, then LFD output is ON. Power supply required is 20 to 35V dc.

SPECIFICATION

Number of input channelsOne (either terminals 7&8 or 8&9)

Input channel (terminals 7 & 8)2-wire transmitter supply: 4 to 20mA

Input channel (terminals 8 & 9)4 to 20mA current source

Number of output channelsTwo

Input signal4 to 20mA

Isolation between input, output 1,output 2 and power supply

1500V dc/ac

Power supply20 to 35V dc

Voltage available for transmitter20V minimum at 20mA

Voltage drop across input fromcurrent source (terminals 8 & 9)

2.4V maximum

Power requirements (supplying atransmitter)

150mA maximum at 20V dc with a 20mA signal120mA maximum at 35V dc with a 20mA signal

Power requirements (from a currentsource) 110mA maximum at 20V dc with a

20mA signal 90mA maximum at 35V dc with a

20mA signal

Load resistance0 to 1kΩ

Transfer accuracy at 25°C for bothoutputs

Better than 20µA

Line-fault detection (LFD) outputTransistor open collector output

Circuit diagram

ICC312

Load

Load

20 to 35V dc4 to 20mA

4 to 20mA

2kΩ24V

4 to 20mA

4 to 20mA

Current source

1

2

3

4

5

6

7

8

9

10

11

12

+

-

LFD

*

Page 2: Signal Multiplier Icc312

Dimensions and mounting (in mm)

LFD characteristicsInput current <0.2mA Transistor OFF

Maximum permitted voltage: 26V dcMaximum OFF leakage current: 150µA

Input current >1mA: Transistor ONMaximum permitted input current: 50mAMaximum ON voltage: 1V

Temperature drift<1µA/ °C

Common mode rejection ratio150dB typical

Ambient temperature limits-20°C to +55 °C (operating)-40°C to +80 °C (storage)

Humidity5 to 95% RH, non-condensing

TerminalsAccommodate 2.5mm2 conductors

Casing40mm width polyamide casing

MountingDirectly onto T- or G-section DIN-rail to DIN46277

TO ORDER:-

ICC312 Repeater power supply, 4 to 20mA, with dual outputs

Response timeTo reach 90% of span: 80msTo reach 99.9% of span: 280ms

A member of The MTL Instruments Group plc

MTL Instruments Pvt LtdNo 3 Old Mahabalipuram Road, Sholinganallur, Chennai 600119Tel: 91 44 2450 1552 , 91 44 2450 2477 Fax: 91 44 2450 1657Email:[email protected]

Insert screwdriver torelease box T-section rail

(DIN 46277)

G-section rail(DIN 46277)

79

Terminals7, 8, 9, 10, 11, 12

Terminals1, 2, 3, 4, 5, 6

40

15= =