36
Sidel Therm & CO 2 Counter Instruction & Installation Manual

Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

  • Upload
    others

  • View
    13

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Sidel Therm & CO2Counter

Instruction & InstallationManual

Page 2: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

P.O. Box 1868Atascadero, CA 93423

800-668-5003Fax: 805-464-0504

Sid Abma, President

www.sidelsystems.com

Page 3: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 3

Table Of Contents System Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Theory Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Monitoring The Heat Recovered. . . . . . . . . . . . . . . . . . 5

Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Mounting The Control Box . . . . . . . . . . . . . . . . . . . . . . 8

Thermocouples Installation . . . . . . . . . . . . . . . . . . . . . 9

Flow Meter Installation And Operation . . . . . . . . . . . 11

Controller Settings And Calibration . . . . . . . . . . . . . . 26

Accessing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 26

Temperature Settings . . . . . . . . . . . . . . . . . . . . . . . . . 28

Flow Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Controller Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Change Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Setting The Date And The Time . . . . . . . . . . . . . . . . . 30

Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Page 4: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 4

System OverviewTheory of operation

The Sidel SRU fl ue gas recovery unit is designed to recover almost all of the waste exhaust heat and turn it into usable heat.

The waste fl ue gases from the boiler are redirected to the SRU recovery unit, which is placed beside the boiler or alongside the chimney. The Sidel SRU fl ue gas condenser unit cools the fl ue gasses to the point where the sensible as well as the latent heat is recovered. The Sidel SRU series is designed so that fl ue gas temperatures can be lowered well below the dew point temperature of 58 C or 136 F. When the temperature of the waste fl ue gas is lowered beyond 133 F, condensation starts to occur. Naturally the lower the fl ue gases can be cooled, the higher the performing effi ciency of the waster heat recovery unit. The waste heat recovery unit is designed for natural gas or propane fi red equipment only. The vertical construction of the SRU waste heat recovery unit provides for the best possible use of available space.

Installation alongside a 110,000 lb/hr boiler

Page 5: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 5

Monitoring the Heat Recovered

In order to quantify the amount of heat recovered, Sidel Systems in conjunction with Helman Automation, has created the Sidel Therm and CO2 Counter. This is an industrial PLC capable of continuously storing data which shows how much energy is being saved by the SRU Flue Gas Condenser. The Therm and CO2 Counter control unit has two major components: the HMI (human machine interface), and the PLC (programmable logic units).

The HMI displays all the important information, is the gateway to change parameters, and can communicate collected data to other terminals via the internet.

One of the greatest advantages of the system is its capability to be adapted to the monitoring needs of the customer. The system can be programmed to perform all the automation control, data acquisition, and data storage.

Page 6: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 6

The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in response to any occurring hazard that may occur.

The display screen shows the amount of energy being recovered as well as other vital information such as the temperature at several critical points, water fl ow, chimney valve position, and with it monitor any other information required to protect the SRU from damage. Any data that registers out of normal range will set off an alarm.

The HMI used in the Sidel Therm and CO2 Counter has all the latest technology, such as: a high resolution touchscreen, Ethernet, USB and serial port connections. This allows the data collected to be displayed on any computer in the company.

The HMI can be customized to display in either Metric units or British units and also can be programmed for Multi languages.

This feature is very useful to see graphically how the changes of each parameter affect the heat recovery process

Page 7: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 7

History Screen

Trending Screen

Page 8: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 8

How the monitor works:From 4 sensors that are inserted

into the pipes connected to the Sidel SRU Flue Gas Heat recovery Unit, the Therm and CO2 Counter takes the temperature of:

• Water fl owing into the SRU unit.• Water fl owing out of the SRU unit.• Flue gas fl owing into the SRU unit.• Flue gas fl owing out of the SRU

unit.• From the water fl ow sensor

inserted into the water intake pipe, the PLC receives the rate of water fl owing through the SRU in Gallons per minute (GPM).

This data is received by the PLC in 5 second intervals and is displayed on the screen.

The PLC calculates the Delta T in BTU’s, and the fl ow rate in GPM and displayes the resulting calculation as BTU’s saved every 5 seconds.

From these fi gures it is possible to see, in real time, exactly how the SRU is performing.

This information is also saved as history in the PLC memory and can be displayed on the History Screen.

By using the touch screen the operator can open and close the Chimney Valve, control the alarm function, set the system, and navigate between the displays.

The displayed calculations also can be sent over the internet or intranet to be displayed on any computer within

the company.This gives the Sidel SRU a unique

advantage in providing real time cost savings analysis that can be used by managers to prove that their company is reducing greenhouse gas emissions and using their energy effi ciently.

InstallationMounting the Control BoxThe control box is a NEMA 12 with

dimension of 14”x16”x8”. The box can be fl ush mounted to a wall or a post with 4 screws of ¼” diameter. The control box will require power of 120 V ac. To comply with NEC the power shall be supplied with 2 #12 wires and a #14 ground green wire

This picture shows the power 120 VAC point of connection.

Page 9: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 9

Thermocouples installation Thermocouple probes are the

preferred temperature sensor used for the Sidel Therm and CO2 Counter, because they provide a large temperature range and are durable. The probe tip is composed of two alloys welded together which makes them almost indestructible.

The Sidel SRU unit provides ½” NPT threaded couplings for therm couple installation. One, for each water inlet and outlet, and one for each fl ue gas exhaust inlet and outlet. The sensors provided with the unit are made of stainless steel. Make sure to use Tefl on tape or pipe sealant for sealing the fi tting, especially for the water pipe.

In most cases we will provide the NB4 with a sub-miniature aluminum head and a SS ½” NPT thread bushing. It has an internal terminal block for probe connection. The “J” type thermocouple is composed of two wires; the White wire is the (+) and the Red wire is the (-). Sidel provides 250 ft. of cable to connect the 5 sensors to the controller. This 2 wire shielded cable has one black wire

run with EMT, or liquid tite conduit. If the unit is equipped with a chimney valve control, the box will require also the installation of a compressed air valve of 80 PSI or more, or wiring to the chimney valve as per actuator requirements.

and one red wire. The black wire is to be connected to the white (+) in the probe terminal and the red to the red (-) in the probe terminal. The length of the cable has little effect in the accuracy of the temperature but it is very important to isolate the routing of the cables to the control box from electrical noises to diminish fl uctuation on the temperature readings. The probe comes pre-calibrated. Each probe will be delivered labeled for the port where it will be installed. The following picture depicts the connection to the probe terminal:

Page 10: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 10

Notice the black wire is connected to the white wire of the thermocouple.

The connection to the control box is marked clearly with color terminals.

Each thermocouple has red and white terminals.

The terminal connections are organized from right to left; the fi rst is the water inlet, the second is the water outlet, the third is the exhaust inlet and the fourth is the exhaust outlet as shown in the picture. This is for the standard Sidel SRU unit. (The installation of a Sidel SRU Combi will be described in a separate manual.)

Notice the white terminal is connected to the black wire of the thermocouple probe cable.

Page 11: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 11

Operation:The paddle wheel sensor

measures the fl ow at of water in the pipe. Fluid moving in a pipe does not all fl ow at the same velocity. Toward the center of the pipe, fl uid moves faster than at the wall and the relationship between the two changes as the overall fl ow rate increases. The recommended depth settings have been carefully chosen to minimize this source of error, and should be followed, especially in the smaller pipe sizes.

Installation of the sensor:The fl ow meter IP100/200 series

are adjustable depth insertion paddle-wheels. These models are designed to fi t 2” to 48” pipe. Installation fi ttings are standard 1-1/2” or 2” NPT.

Ruby bearings and a non-drag hall-effect sensor give these meters the widest fl ow range of any of the paddle wheel types. A sensor detects the passage of miniature magnets in the six rotor blades. The resulting square wave signal can be sent for hundreds of feet over unshielded cable without the addition of a transmitter. This cable can be connected directly to the PLC (programmable logic controller) for the fl ow measurement.

The “hot-tap” models (IP115/215) can be installed or serviced without shutting down the line by means of a 2” full-port isolation valve that comes with a nipple for installation on the pipe fi tting. In most circumstances, no special tool is required.

Flow Meter Installation and Operation

Cold Water Inlet #1

Heated Water Outlet #2

Flue Gas Exhaust Inlet #3

Flue Gas Exhaust Outlet #4

Page 12: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 12

The picture bellow depicts the IP115/215 equipped with the service ball valve.

Page 13: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 13

Specifi cations:

Piping:For best results, the IP sensor should be installed with at least ten

diameters of straight pipe upstream and fi ve downstream. If the installation allows obtaining greater distances, then the result should be optimum.

Page 14: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 14

See Straight Pipe Recommendations:

Page 15: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 15

Horizontal is the preferred installation orientation, since it improves low-fl ow performance and avoids problems with trapped air. Bottom, top, and vertical pipe installation are all acceptable.

Page 16: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 16

See Full Pipe Recommendations:

These are several types of Full Pipe Recommendations:

Page 17: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 17

Fitting and Meter Installation:

The sensor comes with a 1-1/2” male NPT pipe thread adapter fi tting.

Loosen the compression nut so the adapter slides freely. Pull the meter fully upward and fi nger-tighten the compression nut. Do not over tighten. Now loosen the compression nut,

lower the meter to the appropriate depth setting. The depth setting parameters are given by the combination of the preceding Tables. Be sure fl ow is in the direction of the arrow on the housing, then tighten compression nut fully.

Page 18: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 18

Sensor without the

service ball valve:

Sensor with the service

ball valve:

Page 19: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 19

Sensor Depth Setting:It is important for accuracy that the

sensor be inserted to the correct fl ow direction and depth into the pipe.

Page 20: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 20

To fi nd the distance “D” fi rst, fi nd the Dimension “C” from

Table 1 corresponding to the model of sensor and the size of

pipe. Then subtract the wall thickness of your corresponding

size and type of pipe you use from Table 2.

“D” is the distance measuring from the outside of the pipe to the joint in the housing, as shown in the diagram above. Adjust the sensor to Dimension “D” and hand-tighten compression

nut. Align the strain relief housing with the center line of the pipe where the arrow on the housing points in the direction of the fl ow as shown in the diagram above.

Page 21: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 21

Electrical connection:The sensor connection is very

simple and straight forward. The IP115/215 come equipped with 18 ft.

of cable. The 3 wires cable comes with color coded wires as shown in the picture below:

Page 22: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 22

Flow Calibration:In order to properly process

pulses from the fl ow sensor, a number must be enter in the Operator Interface Terminal. This number, is called the “K” factor, and is the number of pulses the sensor puts out per unit of fl uid

The picture above shows the terminal numbers to which each of the fl ow meter cables needs to be connected:

passing through the pipe. For the sake of practicality the “K” factor given on Table 3 will be Pulses per Gallons. To set the “K” factor in the controller follow direction provided in Table 3.

Page 23: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 23

For example, if 4” copper tubing (type L) is been used, then the “K” factor to be set is: 17.85 pulse per gallon. This value has to be entered

in the “Flow Adjustment Menu”. The value to be entered should be “1785” without the decimal point.

Page 24: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 24

Repair and Parts of

Sensor:The fl ow sensor has only

one moving part, the rotor. If this is turning properly and there is no signal, the Hall-effect sensor is not operating properly. In order to test the sensor for signal, once the sensor is removed from the pipe for service, gently rotate the paddlewheel. Observe if the input signal “X0” in the PLC fl icked or goes from turning on and off to see if the Hall Effect changes state. If “X0” changes state then the sensor is operating properly.

Parts Explosion:

Page 25: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 25

Page 26: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 26

Accessing ParametersTo enter the “K” factor the user

should press the “Settings” button from the main screen. This will access the fl ow parameters. Once you press the “Settings” button the user is required to entered the security Password. This password can be set

Main screen Setting button

Controller Settings and Calibration

or changed by the user at any time. Warning!!! any changes made on any category of the setting menu will have a drastic effect in the way the Therm and CO2 Counter will control or monitor the Sidel Flue Gas Condenser. Only authorized personnel should be accessing this feature of the Therm and CO2 Counter.

Page 27: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 27

The following is the Password screen where the user will enter the password by touching the green window.

After the cursor is active in the Green window the keypad becomes active and a number can be entered. To save the password the “ENT” key

When the correct password is entered the “Setting Menu” screen opens as shown in the picture

needs to be pressed. To clear press the “CR” key.

The password can be any number between 1111 to 99999999 as shown in the picture below.

Page 28: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 28

Temperature SettingsIt is important to calibrate all the

temperature probes before installation. Since the probes are not perfectly the same when they are shipped from the

The adjustment instructions are shown on the screen for convenience. Generally the slope for the “J” type thermocouples are almost identical, so the only parameters to be calibrated are the Offsets because they might differ a couple of degrees. To accomplish this calibration, the probes must be placed in a container with water at room temperature. This will allow a uniform temperature

factory, it is necessary to adjust the temperature offsets of each probe.

Helman Automation will calibrate all sensors for all new installations so that recalabration is not required.

among the probes. At this point a well calibrated thermometer needs to be used as a reference. Once the temperature is stabilized, then enter the temperature of the reference thermometer in the “green window”. As the fi nal step press the “SINCRONIZE” button. Now the program will set all of the probes to the same temperature.

Page 29: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 29

Flow SettingsOnce the “K” factor is obtained from

Table 3, enter this number as shown below.

In this example the “K” factor used is for a 4” type L copper pipe which is “17.85” pulse per gallon. The number entered must not have decimal point as shown in the picture.

Controller SettingThe Therm Counter comes pre-

programmed to perform energy monitoring and to automatically control the opening and closing of the chimney valve as well all the safety

alarms. This feature must be activated as shown in the picture.

After pressing the green button, the message will indicate the Chimney Valve Control is activated.

Page 30: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 30

Change PasswordTo set a new password the user

needs to enter a number that is easy to remember and should be at least 4 digits between 1111 to 99999999.

Setting the Date and the TimeIf the Date and Time shown in the main screen are not correct then

they need to be corrected. To correct them select the “Setting Date/Time” button to access the following screen.

Touch any green window to change any parameter and the input keypad will popup then press the appropriate value and press enter.

Page 31: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 31

Page 32: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 32

Page 33: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 33

Schematics This system shows an optional diagram

with a recirculation pump.

Page 34: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 34

Notes

Page 35: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 35

Page 36: Sidel Therm & CO · 2010. 9. 18. · The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in

Page 36