DescriptionThe air handling units VUT H EC ECO and VUT EH EC ECO are the fully-featured ventilation units that ensure air filtration, fresh air supply and stale air extract.During operation the extract air heat is transferred to the supply air stream by the highly efficient counter-flow plate heat exchanger.The units are used in ventilation and air conditioning systems installed in various premises.Due to high-efficient EC motors and expanded coun-terflow heat exchanger surface the energy saving pa-rameters of the ECO series units are the best on the market.All models are designed for connection to ø160, 200 and 250 mm round air ducts.
ModificationsVUT H EC ECO – model with a counterflow heat ex-changer, a bypass and EC motors.VUT EH EC ECO – model with a counterflow heat ex-changer, a bypass, EC motors and an electric heater.
CasingMade of aluzinc, internally filled with 25 mm mineral wool heat- and sound-insulating layer.
FilterThe built-in panel G4 filters are used for extract and supply air filtration.
FansThe units are equipped with high-efficient EC motors with an external rotor.These state-of-the-art motors offer the very best in en-ergy efficiency today.EC motors are characterised with high performance and optimum control across the entire speed range.The high efficiency (up to 90 %) is a definite advantage of EC motors.The 300 and 400 size units are equipped with constant flow fans with forward curved blades.These fans provide constant set air flow even in case of variable air resistance in the ventilation system, i.e. in case of clogged filters.The 900 size units are equipped with fans with back-ward curved blades.
Heat exchangerThe VUT H/EH EC units are equipped with a coun-terflow polystyrene heat exchanger.In the cold season the exhaust air heat is captured and transferred to the supply air stream which reduces the ventilation-generated heat losses.This can lead to formation of condensate that is col-lected in a special drain pan and discharged into the sewage system.In the warm season the ambient air heat is transferred to the exhaust air stream.This allows for a considerable reduction of the supply air temperature which, in turn, reduces the air condi-tioning load.
The VUE H/EH EC units are equipped with a counter-flow heat exchanger with an enthalpy membrane at the core.In the cold season the exhaust air heat and moisture are transferred to the supply air stream through the enthalpy membrane reducing the heat losses from ventilation.Consequently, it is the ambient air heat and moisture transferred to the exhaust air stream through the en-thalpy membrane in the warm season.
This allows for a considerable reduction of the supply air temperature and humidity which, in turn, reduces the air conditioning load.
HeaterThe VUT EH EC ECO units are equipped with an electric heater for additional supply air heating downstream of the heat exchanger.The VUT H EC ECO have no built-in electric heater but it can be ordered separately and integrated into the unit if necessary.
BypassThe unit is equipped with a bypass damper which is opened automatically in summer time to cool down a room with cool outside air.For the models with an electric heater the bypass damp-er is also used for the heat exchanger freezing protec-tion.
Control and automationThe unit incorporates an integrated control system with a multifunctional control panel with a sensor display.The scope of delivery contains a 10 m cable for connec-tion of the unit to the control panel.One of the two freeze protection algorithms can be se-lected to prevent the heat exchanger freezing:If the unit is equipped with an electric heater the by-pass damper is opened according to temperature sen-sor readings and the cold intake air passes by the heat exchanger and is warmed up to set temperature in the heater.Synchronously, the heat exchanger surface is warmed up with extract air flow. After a freezing danger is over the bypass damper closes and the unit reverts to the normal operation mode. If the unit is not equipped with an electric heater the supply fan is turned off to let warm air heat up the heat exchangers. After that the supply fan is turned on and the unit re-verts to normal operation.
Series VENTS VUT/VUE H EC ECO
VENTS VUT/VUE EH EC ECO
AIR HANDLING UNITS WITH HEAT RECOVERY
The air handling units in heat- and sound-insulated casing. Air capacity up to 940 m3/h. Heat recovery efficiency
up to 98 %.
Rated air capacity [m3/h]
300; 400; 900
Heater
_ – without heater
E – electrical heater
Spigot orientation
H – horizontal
Motor type
ЕС – synchronous electronically
commutated motor
Extra designation
ECO
Series
VENTS VUT VENTS VUE
Service side
L – left R – right
A11 control panel
Designation key
WWW.VENTILATION-SYSTEM.COM
VENT
S VUT
H/
EH EC
ECO
AIR
HAND
LING
UNIT
S WIT
H HE
AT R
ECOV
ERY
Technical data:
Control and protection functions From the control panel: turning the unit on/off, speed selection, timer, day- and week-scheduled operation, errors
maintaining pre-set room or duct temperature
control by the HV1 duct humidity sensor (available separately) or the sensor built into the air duct
three fan speed control integrated or optional electric heater control filter clogging control by motor hours
MountingThe unit is designed for suspended or floor moun-ting. Service access to the unit is on the front panel side.
VUT/VUE 300 H EC ECO
VUT/VUE 300 EH EC ECO
VUT/VUE 400 H EC ECO
VUT/VUE 400 EH EC ECO
VUT/VUE 900 H EC ECO
VUT/VUE 900 EH EC ECO
Voltage [V / Hz] 1~ 230Maximum unit power without a heater [W] 138 306 340
Maximum unit current without a heater [A] 0,9 2 2,2
Integrated electric heater power [kW] – 3,0 – 3,0 – 3,0
Integrated electric heater current [A] – 13,0 – 13,0 – 13,0Optional electric heater power [kW] 3,0 – 3,0 – 3,0 –Optional electric heater current [A] 13,0 – 13,0 – 13,0 –
Maximum air capacity [m3/h] 300 450 940RPM [min-1] 1380 2600 1740
Sound pressure level at 3 m distance [dB(A)] 24-45 28-47 28-47Max. transported air temperature [°C] from -25 up to +60
Casing material aluzincInsulation 25 mm mineral wool
Extract filter G4Intake filter G4
Connected air duct diameter [mm] Ø160 Ø200 Ø250Weight [kg] 40 42 45 47 77 80
Heat recovery efficiency from 86 up to 98 %/from 83 up to 93 %
from 85 up to 98 %/from 75 up to 95 %
from 81 up to 98 %/from 74 up to 94 %
Energy efficiency class AHeat exchanger type counterflow
Heat exchanger material polystyrene/enthalpy membrane
polystyrene/enthalpy membrane
polystyrene/enthalpy membrane
B2
H
B3 B1
B
H1
H2
L
L1
D
Model Dimensions [mm]
Ø D B B1 B2 B3 H H1 H2 L L1
VUT/VUE 300 H/EH EC ECO 159 566 125 391 186 475 202 118 1081 1187
VUT/VUE 400 H/EH EC ECO 199 687 255 588 220 514 235 139 1092 1174
VUT/VUE 900 H/EH EC ECO 249 940 250 837 345 620 262 156 1200 1282
Overall dimensions:
AIR HANDLING UNITS WITH HEAT RECOVERY
0
100
200
300
400
500
600
700
800
0,8 W/l/s
1,0 W/l/s
1,2 W/l/s
LOW MED HIGH
1
2
3
4
6
7
8
591011
12
VUT 400 H EC ECOVUT 400 EH EC ECO
60
70
80
90
100
VUE 400 H EC ECOVUE 400 EH EC ECO
VUT/VUE 400 H EC ECOVUT/VUE 400 EH EC ECO
Air capacity [l/s]
Stat
ic p
ress
ure
[Pa]
H
eat r
ecov
ery
effic
ienc
y [%
]H
eat r
ecov
ery
effic
ienc
y [%
]
Air capacity [m3/h]
VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO
0
100
200
300
400
500
VUT 300 H EC ECOVUT 300 EH EC ECO
0,8 W/l/s
1,0 W/l/s
1,2 W/l/s
9101112
HIGH
LOW
MED
1
2
3
4
56
7
8
60
70
80
90
100
VUE 300 H EC ECOVUE 300 EH EC ECO
Stat
ic p
ress
ure
[Pa]
Air capacity [l/s]
Air capacity [m3/h]
Hea
t rec
over
yef
ficie
ncy
[%]
Hea
t rec
over
yef
ficie
ncy
[%]
VUT/VUE 300 H EC ECOVUT/VUE 300 EH EC ECO
A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m
dB(A)LpA, 1 m
dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000
LwA to supply air inlet 51 30 48 46 37 42 36 32 21
LwA to supply air outlet dB(A) 61 41 54 57 55 44 46 35 24
LwA to exhaust air inlet dB(A) 51 30 47 46 38 43 35 31 22
LwA to exhaust air outlet dB(A) 61 40 52 58 56 43 46 34 22
LwA surrounding dB(A) 34 23 23 32 27 19 15 19 18 24 34
A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m
dB(A)LpA, 1 m
dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000
LwA to supply air inlet 32 50 51 40 43 40 37 25 29
LwA to supply air outlet dB(A) 44 57 58 54 51 48 38 27 35
LwA to exhaust air inlet dB(A) 32 49 51 41 44 39 36 26 29
LwA to exhaust air outlet dB(A) 43 55 59 55 50 48 37 25 32
LwA surrounding dB(A) 27 28 32 29 22 19 21 23 22 24 34
Accessories for air handling units:
Model
Panel filter G4Outdoor humidity
sensor
Electric heater Silencer Backdraft
damper Air damper Clamps Electric actuator
VUT/VUE 300 H EC ECO SF VUT 300 H/
EH EC ECO G4
HV1 NK-VUT 300 EH EC ECO SR 160
600/900/1200SRF 160
600/900/1200 KOM 160 KRV 160 C 160
LF230 TF230
VUT/VUE 300 EH EC ECO -
VUT/VUE 400 H EC ECO SF VUT 400 H/
EH EC ECO G4
HV1 NK-VUT 400 EH EC ECO SR 200
600/900/1200SRF 200
600/900/1200 KOM 200 KRV 200 C 200VUT/VUE 400 EH EC ECO -
VUT/VUE 900 H EC ECO SF VUT 900 H/
EH EC ECO G4
HV1 NK-VUT 900 EH EC ECO SR 250
600/900/1200SRF 250
600/900/1200 KOM 250 KRV 250 C 250VUT/VUE 900 EH EC ECO -
WWW.VENTILATION-SYSTEM.COM
supply filter
heat exchanger
bypass
condensate drain pipe
exhaust fan
TF2 freeze protection temperature sensor
HV1 duct humidity sensor (accessory)
extract filter
duct temperature sensor TES
control unit
supply fan
electric heater*
drain pan
VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO
0
100
200
300
400
500
600
700
0,8 W/l/s1,0 W/l/s1,2 W/l/s1,4 W/l/s
15
7
8
910
1112
2
3
4
6
15
7
8
910
1112
2
3
4
6LOW
MED
HIGHVUT/VUE 900 H EC ECO
VUT/VUE 900 EH EC ECO
VUT 900 H EC ECOVUT 900 EH EC ECO
60
70
80
90
100
VUE 900 H EC ECOVUE 900 EH EC ECO
Air capacity [l/s]
Stat
ic p
ress
ure
[Pa]
H
eat r
ecov
ery
effic
ienc
y [%
]H
eat r
ecov
ery
effic
ienc
y [%
]
Air capacity [m3/h]
pointUnit single power [W]
VUT/VUE 300 H EC ECO / VUT/VUE 300 EH EC ECO
VUT/VUE 400 H EC ECO / VUT/VUE 400 EH EC ECO
VUT/VUE 900 H EC ECO / VUT/VUE 900 EH EC ECO
1 83 87 340
2 96 145 340
3 124 247 336
4 134 299 300
5 45 79 138
6 48 103 140
7 60 143 120
8 73 217 110
9 20 28 33
10 22 32 32
11 25 41 32
12 27 56 28
Application options:
Unit design:
Disk valve
Ventilation hood
VENTS VUT EH EC ECO
* included in the scope of delivery of the VUT EH EC ECO model. Is available separately for the VUT H EC ECO model.
A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m
dB(A)LpA, 1 m
dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000
LwA to supply air inlet 36 55 51 41 47 42 38 28 29
LwA to supply air outlet dB(A) 47 62 62 59 53 52 42 29 35
LwA to exhaust air inlet dB(A) 36 54 51 42 48 41 37 29 29
LwA to exhaust air outlet dB(A) 46 60 63 60 52 52 41 27 32
LwA surrounding dB(A) 26 29 36 32 24 22 26 26 22 24 34 VENT
S VUT
H/
EH EC
ECO
AIR
HAND
LING
UNIT
S WIT
H HE
AT R
ECOV
ERY