Description The air handling units VUT H EC ECO and VUT EH EC ECO are the fully-featured ventilation units that ensure air filtration, fresh air supply and stale air extract. During operation the extract air heat is transferred to the supply air stream by the highly efficient counter- flow plate heat exchanger. The units are used in ventilation and air conditioning systems installed in various premises. Due to high-efficient EC motors and expanded coun- terflow heat exchanger surface the energy saving pa- rameters of the ECO series units are the best on the market. All models are designed for connection to ø160, 200 and 250 mm round air ducts. Modifications VUT H EC ECO – model with a counterflow heat ex- changer, a bypass and EC motors. VUT EH EC ECO – model with a counterflow heat ex- changer, a bypass, EC motors and an electric heater. Casing Made of aluzinc, internally filled with 25 mm mineral wool heat- and sound-insulating layer. Filter The built-in panel G4 filters are used for extract and supply air filtration. Fans The units are equipped with high-efficient EC motors with an external rotor. These state-of-the-art motors offer the very best in en- ergy efficiency today. EC motors are characterised with high performance and optimum control across the entire speed range. The high efficiency (up to 90 %) is a definite advantage of EC motors. The 300 and 400 size units are equipped with constant flow fans with forward curved blades. These fans provide constant set air flow even in case of variable air resistance in the ventilation system, i.e. in case of clogged filters. The 900 size units are equipped with fans with back- ward curved blades. Heat exchanger The VUT H/EH EC units are equipped with a coun- terflow polystyrene heat exchanger. In the cold season the exhaust air heat is captured and transferred to the supply air stream which reduces the ventilation-generated heat losses. This can lead to formation of condensate that is col- lected in a special drain pan and discharged into the sewage system. In the warm season the ambient air heat is transferred to the exhaust air stream. This allows for a considerable reduction of the supply air temperature which, in turn, reduces the air condi- tioning load. The VUE H/EH EC units are equipped with a counter- flow heat exchanger with an enthalpy membrane at the core. In the cold season the exhaust air heat and moisture are transferred to the supply air stream through the enthalpy membrane reducing the heat losses from ventilation. Consequently, it is the ambient air heat and moisture transferred to the exhaust air stream through the en- thalpy membrane in the warm season. This allows for a considerable reduction of the supply air temperature and humidity which, in turn, reduces the air conditioning load. Heater The VUT EH EC ECO units are equipped with an electric heater for additional supply air heating downstream of the heat exchanger. The VUT H EC ECO have no built-in electric heater but it can be ordered separately and integrated into the unit if necessary. Bypass The unit is equipped with a bypass damper which is opened automatically in summer time to cool down a room with cool outside air. For the models with an electric heater the bypass damp- er is also used for the heat exchanger freezing protec- tion. Control and automation The unit incorporates an integrated control system with a multifunctional control panel with a sensor display. The scope of delivery contains a 10 m cable for connec- tion of the unit to the control panel. One of the two freeze protection algorithms can be se- lected to prevent the heat exchanger freezing: If the unit is equipped with an electric heater the by- pass damper is opened according to temperature sen- sor readings and the cold intake air passes by the heat exchanger and is warmed up to set temperature in the heater. Synchronously, the heat exchanger surface is warmed up with extract air flow. After a freezing danger is over the bypass damper closes and the unit reverts to the normal operation mode. If the unit is not equipped with an electric heater the supply fan is turned off to let warm air heat up the heat exchangers. After that the supply fan is turned on and the unit re- verts to normal operation. Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECO AIR HANDLING UNITS WITH HEAT RECOVERY The air handling units in heat- and sound-insulated casing. Air capacity up to 940 m 3 /h. Heat recovery efficiency up to 98 %. Rated air capacity [m 3 /h] 300; 400; 900 Heater _ – without heater E – electrical heater Spigot orientation H horizontal Motor type ЕС synchronous electronically commutated motor Extra designation ECO Series VENTS VUT VENTS VUE Service side L – left R – right A11 control panel Designation key

Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECOold.ventilation-system.com/images/cat/714_2418_cat_file... · 2017. 5. 17. · Casing Made of aluzinc, internally filled with

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECOold.ventilation-system.com/images/cat/714_2418_cat_file... · 2017. 5. 17. · Casing Made of aluzinc, internally filled with

DescriptionThe air handling units VUT H EC ECO and VUT EH EC ECO are the fully-featured ventilation units that ensure air filtration, fresh air supply and stale air extract.During operation the extract air heat is transferred to the supply air stream by the highly efficient counter-flow plate heat exchanger.The units are used in ventilation and air conditioning systems installed in various premises.Due to high-efficient EC motors and expanded coun-terflow heat exchanger surface the energy saving pa-rameters of the ECO series units are the best on the market.All models are designed for connection to ø160, 200 and 250 mm round air ducts.

ModificationsVUT H EC ECO – model with a counterflow heat ex-changer, a bypass and EC motors.VUT EH EC ECO – model with a counterflow heat ex-changer, a bypass, EC motors and an electric heater.

CasingMade of aluzinc, internally filled with 25 mm mineral wool heat- and sound-insulating layer.

FilterThe built-in panel G4 filters are used for extract and supply air filtration.

FansThe units are equipped with high-efficient EC motors with an external rotor.These state-of-the-art motors offer the very best in en-ergy efficiency today.EC motors are characterised with high performance and optimum control across the entire speed range.The high efficiency (up to 90 %) is a definite advantage of EC motors.The 300 and 400 size units are equipped with constant flow fans with forward curved blades.These fans provide constant set air flow even in case of variable air resistance in the ventilation system, i.e. in case of clogged filters.The 900 size units are equipped with fans with back-ward curved blades.

Heat exchangerThe VUT H/EH EC units are equipped with a coun-terflow polystyrene heat exchanger.In the cold season the exhaust air heat is captured and transferred to the supply air stream which reduces the ventilation-generated heat losses.This can lead to formation of condensate that is col-lected in a special drain pan and discharged into the sewage system.In the warm season the ambient air heat is transferred to the exhaust air stream.This allows for a considerable reduction of the supply air temperature which, in turn, reduces the air condi-tioning load.

The VUE H/EH EC units are equipped with a counter-flow heat exchanger with an enthalpy membrane at the core.In the cold season the exhaust air heat and moisture are transferred to the supply air stream through the enthalpy membrane reducing the heat losses from ventilation.Consequently, it is the ambient air heat and moisture transferred to the exhaust air stream through the en-thalpy membrane in the warm season.

This allows for a considerable reduction of the supply air temperature and humidity which, in turn, reduces the air conditioning load.

HeaterThe VUT EH EC ECO units are equipped with an electric heater for additional supply air heating downstream of the heat exchanger.The VUT H EC ECO have no built-in electric heater but it can be ordered separately and integrated into the unit if necessary.

BypassThe unit is equipped with a bypass damper which is opened automatically in summer time to cool down a room with cool outside air.For the models with an electric heater the bypass damp-er is also used for the heat exchanger freezing protec-tion.

Control and automationThe unit incorporates an integrated control system with a multifunctional control panel with a sensor display.The scope of delivery contains a 10 m cable for connec-tion of the unit to the control panel.One of the two freeze protection algorithms can be se-lected to prevent the heat exchanger freezing:If the unit is equipped with an electric heater the by-pass damper is opened according to temperature sen-sor readings and the cold intake air passes by the heat exchanger and is warmed up to set temperature in the heater.Synchronously, the heat exchanger surface is warmed up with extract air flow. After a freezing danger is over the bypass damper closes and the unit reverts to the normal operation mode. If the unit is not equipped with an electric heater the supply fan is turned off to let warm air heat up the heat exchangers. After that the supply fan is turned on and the unit re-verts to normal operation.

Series VENTS VUT/VUE H EC ECO

VENTS VUT/VUE EH EC ECO

AIR HANDLING UNITS WITH HEAT RECOVERY

The air handling units in heat- and sound-insulated casing. Air capacity up to 940 m3/h. Heat recovery efficiency

up to 98 %.

Rated air capacity [m3/h]

300; 400; 900

Heater

_ – without heater

E – electrical heater

Spigot orientation

H – horizontal

Motor type

ЕС – synchronous electronically

commutated motor

Extra designation

ECO

Series

VENTS VUT VENTS VUE

Service side

L – left R – right

A11 control panel

Designation key

Page 2: Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECOold.ventilation-system.com/images/cat/714_2418_cat_file... · 2017. 5. 17. · Casing Made of aluzinc, internally filled with

WWW.VENTILATION-SYSTEM.COM

VENT

S VUT

H/

EH EC

ECO

AIR

HAND

LING

UNIT

S WIT

H HE

AT R

ECOV

ERY

Technical data:

Control and protection functions From the control panel: turning the unit on/off, speed selection, timer, day- and week-scheduled operation, errors

maintaining pre-set room or duct temperature

control by the HV1 duct humidity sensor (available separately) or the sensor built into the air duct

three fan speed control integrated or optional electric heater control filter clogging control by motor hours

MountingThe unit is designed for suspended or floor moun-ting. Service access to the unit is on the front panel side.

VUT/VUE 300 H EC ECO

VUT/VUE 300 EH EC ECO

VUT/VUE 400 H EC ECO

VUT/VUE 400 EH EC ECO

VUT/VUE 900 H EC ECO

VUT/VUE 900 EH EC ECO

Voltage [V / Hz] 1~ 230Maximum unit power without a heater [W] 138 306 340

Maximum unit current without a heater [A] 0,9 2 2,2

Integrated electric heater power [kW] – 3,0 – 3,0 – 3,0

Integrated electric heater current [A] – 13,0 – 13,0 – 13,0Optional electric heater power [kW] 3,0 – 3,0 – 3,0 –Optional electric heater current [A] 13,0 – 13,0 – 13,0 –

Maximum air capacity [m3/h] 300 450 940RPM [min-1] 1380 2600 1740

Sound pressure level at 3 m distance [dB(A)] 24-45 28-47 28-47Max. transported air temperature [°C] from -25 up to +60

Casing material aluzincInsulation 25 mm mineral wool

Extract filter G4Intake filter G4

Connected air duct diameter [mm] Ø160 Ø200 Ø250Weight [kg] 40 42 45 47 77 80

Heat recovery efficiency from 86 up to 98 %/from 83 up to 93 %

from 85 up to 98 %/from 75 up to 95 %

from 81 up to 98 %/from 74 up to 94 %

Energy efficiency class AHeat exchanger type counterflow

Heat exchanger material polystyrene/enthalpy membrane

polystyrene/enthalpy membrane

polystyrene/enthalpy membrane

B2

H

B3 B1

B

H1

H2

L

L1

D

Model Dimensions [mm]

Ø D B B1 B2 B3 H H1 H2 L L1

VUT/VUE 300 H/EH EC ECO 159 566 125 391 186 475 202 118 1081 1187

VUT/VUE 400 H/EH EC ECO 199 687 255 588 220 514 235 139 1092 1174

VUT/VUE 900 H/EH EC ECO 249 940 250 837 345 620 262 156 1200 1282

Overall dimensions:

Page 3: Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECOold.ventilation-system.com/images/cat/714_2418_cat_file... · 2017. 5. 17. · Casing Made of aluzinc, internally filled with

AIR HANDLING UNITS WITH HEAT RECOVERY

0

100

200

300

400

500

600

700

800

0,8 W/l/s

1,0 W/l/s

1,2 W/l/s

LOW MED HIGH

1

2

3

4

6

7

8

591011

12

VUT 400 H EC ECOVUT 400 EH EC ECO

60

70

80

90

100

VUE 400 H EC ECOVUE 400 EH EC ECO

VUT/VUE 400 H EC ECOVUT/VUE 400 EH EC ECO

Air capacity [l/s]

Stat

ic p

ress

ure

[Pa]

H

eat r

ecov

ery

effic

ienc

y [%

]H

eat r

ecov

ery

effic

ienc

y [%

]

Air capacity [m3/h]

VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO

0

100

200

300

400

500

VUT 300 H EC ECOVUT 300 EH EC ECO

0,8 W/l/s

1,0 W/l/s

1,2 W/l/s

9101112

HIGH

LOW

MED

1

2

3

4

56

7

8

60

70

80

90

100

VUE 300 H EC ECOVUE 300 EH EC ECO

Stat

ic p

ress

ure

[Pa]

Air capacity [l/s]

Air capacity [m3/h]

Hea

t rec

over

yef

ficie

ncy

[%]

Hea

t rec

over

yef

ficie

ncy

[%]

VUT/VUE 300 H EC ECOVUT/VUE 300 EH EC ECO

A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m

dB(A)LpA, 1 m

dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000

LwA to supply air inlet 51 30 48 46 37 42 36 32 21

LwA to supply air outlet dB(A) 61 41 54 57 55 44 46 35 24

LwA to exhaust air inlet dB(A) 51 30 47 46 38 43 35 31 22

LwA to exhaust air outlet dB(A) 61 40 52 58 56 43 46 34 22

LwA surrounding dB(A) 34 23 23 32 27 19 15 19 18 24 34

A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m

dB(A)LpA, 1 m

dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000

LwA to supply air inlet 32 50 51 40 43 40 37 25 29

LwA to supply air outlet dB(A) 44 57 58 54 51 48 38 27 35

LwA to exhaust air inlet dB(A) 32 49 51 41 44 39 36 26 29

LwA to exhaust air outlet dB(A) 43 55 59 55 50 48 37 25 32

LwA surrounding dB(A) 27 28 32 29 22 19 21 23 22 24 34

Accessories for air handling units:

Model

Panel filter G4Outdoor humidity

sensor

Electric heater Silencer Backdraft

damper Air damper Clamps Electric actuator

VUT/VUE 300 H EC ECO SF VUT 300 H/

EH EC ECO G4

HV1 NK-VUT 300 EH EC ECO SR 160

600/900/1200SRF 160

600/900/1200 KOM 160 KRV 160 C 160

LF230 TF230

VUT/VUE 300 EH EC ECO -

VUT/VUE 400 H EC ECO SF VUT 400 H/

EH EC ECO G4

HV1 NK-VUT 400 EH EC ECO SR 200

600/900/1200SRF 200

600/900/1200 KOM 200 KRV 200 C 200VUT/VUE 400 EH EC ECO -

VUT/VUE 900 H EC ECO SF VUT 900 H/

EH EC ECO G4

HV1 NK-VUT 900 EH EC ECO SR 250

600/900/1200SRF 250

600/900/1200 KOM 250 KRV 250 C 250VUT/VUE 900 EH EC ECO -

Page 4: Series VENTS VUT/VUE H EC ECO VENTS VUT/VUE EH EC ECOold.ventilation-system.com/images/cat/714_2418_cat_file... · 2017. 5. 17. · Casing Made of aluzinc, internally filled with

WWW.VENTILATION-SYSTEM.COM

supply filter

heat exchanger

bypass

condensate drain pipe

exhaust fan

TF2 freeze protection temperature sensor

HV1 duct humidity sensor (accessory)

extract filter

duct temperature sensor TES

control unit

supply fan

electric heater*

drain pan

VENTS VUT/VUE H EC ECO / VENTS VUT EH EC ECO

0

100

200

300

400

500

600

700

0,8 W/l/s1,0 W/l/s1,2 W/l/s1,4 W/l/s

15

7

8

910

1112

2

3

4

6

15

7

8

910

1112

2

3

4

6LOW

MED

HIGHVUT/VUE 900 H EC ECO

VUT/VUE 900 EH EC ECO

VUT 900 H EC ECOVUT 900 EH EC ECO

60

70

80

90

100

VUE 900 H EC ECOVUE 900 EH EC ECO

Air capacity [l/s]

Stat

ic p

ress

ure

[Pa]

H

eat r

ecov

ery

effic

ienc

y [%

]H

eat r

ecov

ery

effic

ienc

y [%

]

Air capacity [m3/h]

pointUnit single power [W]

VUT/VUE 300 H EC ECO / VUT/VUE 300 EH EC ECO

VUT/VUE 400 H EC ECO / VUT/VUE 400 EH EC ECO

VUT/VUE 900 H EC ECO / VUT/VUE 900 EH EC ECO

1 83 87 340

2 96 145 340

3 124 247 336

4 134 299 300

5 45 79 138

6 48 103 140

7 60 143 120

8 73 217 110

9 20 28 33

10 22 32 32

11 25 41 32

12 27 56 28

Application options:

Unit design:

Disk valve

Ventilation hood

VENTS VUT EH EC ECO

* included in the scope of delivery of the VUT EH EC ECO model. Is available separately for the VUT H EC ECO model.

A-weighted sound power levelGen Octave-frequency band [Hz] LpA, 3 m

dB(A)LpA, 1 m

dB(A)dB(A) 63 125 250 500 1000 2000 4000 8000

LwA to supply air inlet 36 55 51 41 47 42 38 28 29

LwA to supply air outlet dB(A) 47 62 62 59 53 52 42 29 35

LwA to exhaust air inlet dB(A) 36 54 51 42 48 41 37 29 29

LwA to exhaust air outlet dB(A) 46 60 63 60 52 52 41 27 32

LwA surrounding dB(A) 26 29 36 32 24 22 26 26 22 24 34 VENT

S VUT

H/

EH EC

ECO

AIR

HAND

LING

UNIT

S WIT

H HE

AT R

ECOV

ERY