Series Hybrid Converter (SHC) System

Embed Size (px)

Citation preview

  • 8/7/2019 Series Hybrid Converter (SHC) System

    1/15

    Series Hybrid Converter (SHC)

    HVDC System

    Adlan B Pradana

    2010EEP3791

  • 8/7/2019 Series Hybrid Converter (SHC) System

    2/15

    SCC (Self Commutated Converter vs. LCC

    (Line Commutated Converter)

    SCC

    Immune to the strength ofnetwork (+)

    Controllable power factor (+)

    Can be used in a voltagesupport role (+)

    Permit the elimination oflower order harmonic filters

    (+) Excessive cost (-)

    Smaller ratings compare toLCC (-)

    LCC

    Extensively used (+)

    Require reactive power

    source (-)

    Difficult to operate in weak

    system (-)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    3/15

    SCC + LCC = Hybrid HVDC System

    There are 2 arrangements :

    Back 2 back (B2B)

    Series Hybrid Converter (SHC)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    4/15

    Back to Back (B2B)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    5/15

    Series Hybrid Converter (SHC)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    6/15

    B2B vs. SHC

    Hybrid HVDC

    SCC only in one side, so its

    advantages also only in one

    side (inverter/rectifier)

    Only for a new built system

    SHC

    SCC can be installed on both

    side, so its advantages also

    for both side (inverter &rectifier)

    Can be used both for a new

    built system or add on

    (upgrade)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    7/15

    SHC

    Combination of LCC and VSC in one bus

    LCC provides part of the required real power, VSCadd the remainder

    VSC controls reactive power necessary for theLCC

    2 types :

    VSC as add on of existing LCC HVD VSC + LCC for a new system

    SVSC = [PVSC2+QVSC

    2] 1/2

    = [(Pnom PLCC )2 + (0.6 *PLCC Qfilt )

    2] 1/2

  • 8/7/2019 Series Hybrid Converter (SHC) System

    8/15

    Control

  • 8/7/2019 Series Hybrid Converter (SHC) System

    9/15

    Control (LCC)

    Current order is generated using external PIpower regulator

    Angle orders is based on :

    Terminal power mismatch Current in HVDC circuit

    Measured extinction angle at rectifier and

    inverter

  • 8/7/2019 Series Hybrid Converter (SHC) System

    10/15

    Control (SCC)

    VSC Control block P & Q orders are derived from external regulators for

    dc & ac side voltages respectively

    Magnitude and angle driving signals are issued based

    on : Capacitor voltage (Vdc) mismatch generates P

    Terminal voltage (Et) mismatch generates Q

    Terminals d & q axis components of voltage (Et,Eq)

  • 8/7/2019 Series Hybrid Converter (SHC) System

    11/15

    Start Up Comparison

    LCC Only SHC

  • 8/7/2019 Series Hybrid Converter (SHC) System

    12/15

    Step Response Comparison

    LCC Only SHC

  • 8/7/2019 Series Hybrid Converter (SHC) System

    13/15

    Conclusion

    SHC system combining advantages of LCC andVSC

    SHC can be applied both as add on or as a new

    system Response of SHC is better than LCC alone :

    Excellent start up

    Terminal voltage support

    Superior step response Acceptable fault recoveries

    The disadvantages is more complexity in control

  • 8/7/2019 Series Hybrid Converter (SHC) System

    14/15

    References

    B. Qahraman (IEEE student member), A. Gole (IEEEmember), A VSC Based Series Hybrid Converter forHVDC Transmission, Canadian Conference Electricaland Computer Engineering on 1-4 May 2005

    Li Guangkai, Li Gengyin (Member IEEE), Liang Haifeng,Zhao Chengyong, Yin Ming Research on HybridHVDC, Power System Technology - POWERCON 2004

    Y Iwata, S Tanaka, K Sakamoto H Konishi, H Kawazoe,Simulation Study of a Hybrid HVDC System Composedof a Self-commutated Converter and a Line-commutated Converter