Sept 2007 Labday Safety Presentation

Embed Size (px)

Citation preview

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    1/29

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    2/29

    Outline

    Background

    InsulationComponent Selection

    Labeling

    Documentation

    Wiring

    Resistance to Fire

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    3/29

    Product Safety Requirements

    US/Canada:NRTL Listing (cULus, cTUVus, cCSAus)

    Legal requirement, customer requirement, or to limit liability

    Europe:CE Mark

    Legal requirement

    Others:CB Report

    To facilitate International Approvals.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    4/29

    Product Safety Hazards Electric Shock Hazards: Accessible parts over 30Vrms,

    42.4Pk, or 60VDC.

    Energy Hazards: Energy level over 240VA or 8A

    Fire Hazards: Materials, Enclosure, Abnormal conditions

    Mechanical Hazards: Moving parts, Sharp edges,Tipping, Handles

    Radiation Hazards: Lasers, UV, Sonic

    Thermal Hazards: External temps, component temps

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    5/29

    Product SafetyDesign Guidelines

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    6/29

    Design Requirements

    Protection against electric shock andenergy hazards:

    The OPERATORcan not touch bare or inadequatelyinsulated parts at hazardous voltage or energy levels.

    Hazardous Voltage Level is typically >30Vrms,42.4Vpeak, or 60VDC.

    Hazardous energy is typically >240VA or 8A

    Protection may be provided via insulation, guarding orinterlocking.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    7/29

    What is Insulation? Physical barrier between two parts

    (tape, plastic shield, wire insulation,

    enclosure, etc)

    Separation between two parts through

    air or along a surface (creepage orclearance distance)

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    8/29

    Insulation Types

    Functional / Operational Insulation (DC

    input to ground)

    Basic Insulation (Primary to Ground,TNV to Ground, TNV to SELV)

    Reinforced Insulation (Primary toSecondary)

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    9/29

    Reinforced Insulation Example

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    10/29

    Spacings (Creepage / Clearance)

    Based on the required insulation for your circuit.

    Based on the maximum working voltage for yourcircuit.

    Based on the environment the product will be used in

    (Pollution Degree)

    Based on the PCB material: Material Group -

    Comparitive Tracking Index (CTI)

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    11/29

    Creepage / Clearance

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    12/29

    Creepage / Clearance

    Creepage Creepage = distance between two points along the

    surface

    Creepage is measured on 1:1 artwork or on a blank board

    Locations of circuits determined by reviewing schematics

    Clearance Clearance = distance between two points through the air

    Clearance is measured on a populated sample

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    13/29

    Component Selection

    Safety Critical Components must have theappropriate approvals or additional evaluationwill be required.

    Safety Critical Components: Devices in the AC path (inlets, fuses, switches, power

    supplies, transformers, etc.) Motors, fans Power conversion components (AC-DC or DC-DC

    Converters)

    Any isolation component (Transformer, BridgingCapacitors, MOVs,) Wiring Batteries Others depending on their application.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    14/29

    Component Selection For NRTL approvals, all components must be UL approved.

    For CE Mark approvals, all components must have aEuropean approval such as CE, TUV, VDE, etc. (exception:fuses and wiring can be UL approved)

    For GS or CB Scheme approvals, all components musthave a TUV, VDE, or other official European approval. CE

    Mark is not acceptable for these approvals.

    Approval certificates required (TUV or VDE Cert, CEDeclaration of Conformity, UL File number, etc.)

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    15/29

    Labeling and Marking

    Rated voltage, current or power, frequency

    Manufacturers name or registered

    trademark. Model or type number.

    Fuse replacement info (if applicable).

    IEC symbols wherever possible. Warnings and Cautions appropriate for the

    particular equipment.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    16/29

    User Instructions

    Installation Instructions - information regardingmounting, connection to the supply, ventilation, inputratings, etc.

    All information regarding use, cleaning, maintenance(if necessary).

    All safety warnings and cautions.

    Rack Mount instructions.

    Safety-related information to be in appropriate

    language of the country you are exporting to. Some standards have entire sections of specific info

    that must be in manual.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    17/29

    Wiring and connection to the supply

    Protective Earth - PE conductor must be green/yellow or bare insulation

    conductor

    PE connections must be double secured so that both

    the wire and insulation are crimped

    IEC PE symbol shall be marked adjacent to PE stud

    PE conductor shall connect to chassis directly from

    input (inlet, terminal block, etc).

    PE conductor must be secured with washer and

    locknut.

    Additional PE conductors can be secured to PE stud

    with a second washer and locknut.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    18/29

    EMI FILTER

    TO OTHER

    GROUNDS

    GROUND: GREEN/YELLOW WIRE

    SAME GAUGE AS OR BIGGER THAN SUPPLY

    CHASSIS

    CONNECTION

    MECHANICALLY SECURED

    PE Stud Example

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    19/29

    Wiring and connection to the supply Primary Wiring -

    All AC wires shall be double secured. Double securement can

    be met by:Double crimp connector or

    Single crimp connector and cable tie or

    Single crimp connector and shrink sleeving.

    AC wiring shall be rated for the maximum working voltage andcurrent.

    AC wiring shall be isolated from low voltage wiring or lowvoltage parts, this can be accomplished by:

    Shrink sleeving the AC conductors or

    By routing the AC conductors away from low voltage wires

    and securing with cable ties or

    By using UL1015 Reinforced Insulation wire.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    20/29

    Resistance to fire and control

    of fire spreading Enclosures, components, and other parts shall be

    constructed such that propagation of fire is limited.Flammability of enclosure, internal, and external parts shallbe adequate for the use of that part.

    Flammability ratings

    5VA Most fire resistant 5VB

    V0

    V1

    V2

    HB40 HB75 - Least fire resistant

    Foamed materials:

    HF-1

    HF-2

    HBF

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    21/29

    Resistance to fire and control of

    spread of fire

    60950-1

    Fire enclosure openings shall be: Top and side openings shall be:

    less than 5mm in any dimension or

    less than 1mm in width regardless of length or

    meet the 5 projection rule.

    There shall be no bottom openings (some exceptions

    allowed but difficult to meet)

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    22/29

    Methods for Meeting FireRequirements in 61010-1 Requirement: There shall be no spread of

    fire outside the equipment in Normal or Single

    Fault Conditions.

    Methods of Compliance:

    A: Testing in single fault conditions

    B: Reducing sources of ignition within theequipment

    C: Containing fire within the equipmentshould it occur

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    23/29

    Requirements for fire enclosure

    - Components in primary circuit

    - Components in secondary circuits that are not supplied by LPS

    - Components in secondary circuits supplied by LPS

    but not on V-1 material

    - Components with unenclosed arcing parts

    - Insulated wiring

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    24/29

    Parts not requiring Fire Enclosure

    - Motors

    - Transformers

    - Wiring and cabling insulated with PVC, TFE, PTFE,

    FEP, neoprene or polymide

    - Connectors in secondary circuits powered by less

    than 15VA or LPS

    - Components in secondary circuits supplied by LPS

    and on V-1 material

    - Components in secondary circuits supply by max

    15VA and on HB785 if 3mm.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    25/29

    Plastic materials used for fireenclosure Movable equipment

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    26/29

    Plastic materials used inside a fireenclosure Inside a fire enclosure:

    V-2 or HF-2 or pass A.2

    Exceptions:

    Electronic components (ICs, optos, etc.) mounted onV-1.

    Wiring and connectors insulated with PVC, TFE,PTFE, FEP, neoprene, or polymide.

    Clamps, cable ties.

    Wire marked VW-1 or FT-1 or better.

    Others.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    27/29

    Plastic materials used outside afire enclosure Material outside fire enclosure:

    HB75 if 3mm or HBF or Glow Wire test at550C

    Connectors:

    V-2 or pass A.2 or mounted on V-1 and be small or be insecondary circuit with max 15VA

    Exceptions: Electronic components (ICs, optos, etc.) mounted on V-1.

    Wiring and connectors insulated with PVC, TFE, PTFE, FEP,neoprene, or polymide.

    Clamps, cable ties.

    Others.

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    28/29

    Washington Laboratories, Ltd.

    Help you select the proper Directives and

    Standards to apply to your product.

    Evaluate and test your product to the

    appropriate Safety Standard and offersolutions for non-compliances.

    Provide product design assistance.

    Obtain cTUVus, cCSAus, cULus, GS Mark,and other approvals.

    WLL is a Partner Test Lab for TUV Rheinland

    for 60950-1, 61010-1, and 60065

  • 7/31/2019 Sept 2007 Labday Safety Presentation

    29/29

    Washington Laboratories, Ltd.

    Give us a call or send us info about your product -were here to help!

    Berri Remenick

    Product Safety Manager

    Phone: 301-473-1255

    Fax: 301-473-1257

    E-mail: [email protected]