47
Scalable and flat controls for reliable power grid operation with high renewable penetration April 2011 Annual Report Research Institutions University of Tennessee (lead) University of Illinois Northeastern/Tufts University Rensselaer Polytechnic Institute

Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

Scalable and flat controls for reliable power grid operation with high renewable

penetration

April 2011 Annual Report

Research Institutions

University of Tennessee (lead) University of Illinois

Northeastern/Tufts University Rensselaer Polytechnic Institute

Page 2: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

2

Investigators

University of Tennessee • Fran Li, Asst. Professor, Electrical Engineering and Computer Science • Leon Tolbert, Professor, Electrical Engineering and Computer Science • Kevin Tomsovic (Lead PI), Professor, Electrical Engineering and Computer Science • Guodong Liu, Ph.D. student, Electrical Engineering and Computer Science • Alex Melhorn, M.S. student, Electrical Engineering and Computer Science • Maryam Variani, Ph.D. student, Electrical Engineering and Computer Science • Bailu Xiao, Ph.D. student, Electrical Engineering and Computer Science • Yao Xu, Ph.D. student, Electrical Engineering and Computer Science University of Illinois • Alejandro Dominguez-Garcia, Asst. Professor, Electrical and Computer Engineering • George Gross, Professor, Electrical and Computer Engineering • Philip Krein, Professor, Electrical and Computer Engineering • Thomas Overbye (UI lead PI), Professor, Electrical and Computer Engineering • Pete Sauer, Professor, Electrical and Computer Engineering • Dimitra Apostolopoulou, Ph.D. student, Electrical and Computer Engineering • Yannick Degeilh, Ph.D. student, Electrical and Computer Engineering • McDavis Fasugba, Ph.D. student, Electrical and Computer Engineering • Justin Hughes, Ph.D. student, Electrical and Computer Engineering

Northeastern University • Ali Abur, Professor, Electrical and Computer Engineering • Hanoch Lev-Ari, Professor (NEU lead PI), Electrical and Computer Engineering • Aleksandar M. Stankovic (now at Tufts University), Professor, Electrical and

Computer Engineering • Paraskevas Argyropoulos, Ph.D. student, Electrical and Computer Engineering • Mert Korkali, Ph.D. student, Electrical and Computer Engineering • Ronald Hernandez, Ph.D. student, Electrical and Computer Engineering • Bei Yan, Ph.D. student, Electrical and Computer Engineering Rensselaer Polytechnic University • Joe Chow (RPI lead PI), Professor, Electrical, Computer and Systems Engineering • Daniel Shawhan, Asst. Professor, Economics • Jian Sun, Assoc. Professor, Electrical, Computer and Systems Engineering • Scott Ghiocel, PhD student, Electrical Computer and Systems Engineering • Andrew Kindle, PhD student, Economics • Hanchao Liu, PhD student, Electrical Computer and Systems Engineering

Page 3: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

3

Abstract The main challenges of operating a power grid with a high proportion of generation

based on renewable resources include that these resources: (1) are less predictable than traditional fuel-based power plants, (2) may be far from load centers so power may have to flow through congested transmission paths, (3) do not generally match the daily cycle of load variation, (4) suffer from unusual operating constraints, such as, rapid variation or complicated weather dependence, and (5) need to be tightly coupled to storage, which may be mobile. To respond to this challenge, this work envisions a fundamental shift in the approach to the electric power infrastructure with both a broadening of the electric grid to consider overall end energy use and a “flattening” of the control structure at all levels of the power grid the traditional control strategies.

The proposed project focuses on the grid control and communication structure to facilitate coordination. Coordination is critical to ensuring that the future grid can enable efficient, low cost and reliable integration of renewables. As such, the work is a system development investigating several areas of control and communications, device technologies as well as electricity market structures. Commonalities arising across these diverse research tasks include the importance of new measurement technologies, increased functionality at the device level and managing uncertainty in both control systems and markets. More specifically, new phasor measurements are being used in this work to enable wide area control of the power grid and understand system limits more precisely. New power electronic functionality, both at the source and load, allow improved stability and voltage control. These functions mean that alternative sources can provide services to the grid that will support their costs. Investigations into incorporating reliability and risk considerations into market structures will properly allocate costs and better define contributions of renewables and controllable load to system performance. Managing uncertainty in the control systems, as for example we do with the proposed delay-cancelling approach, improves reliability and thus, allows greater penetration of renewables.

1. Introduction Frequently overlooked in discussions on energy problems is the central role that the

electric power system infrastructure must play in any viable solution. Power generation plants are among the largest sources of greenhouse gas (GHG) emissions and in addition, many of the proposed solutions for minimizing emission – wind farms, solar roof-tops, plug-in hybrid cars, even the “hydrogen” economy – must rely heavily on the grid. Historically, energy systems have been engineered according to the separate industry sectors, i.e., transportation, heating, electric delivery, and thus, represent “frozen accidents.” Today, a comprehensive solution to the reduction of GHG requires a more general approach. This is not only to avoid shifting problems between sectors but also to take advantage of efficiencies that can only be realized through interaction among the subsystems. The electric power grid must function centrally to this system of systems. Global warming concerns, rising fossil fuel costs, and management of a carbon-constrained economy will require the development of a different type of electric power system infrastructure while electric energy resources based on renewable resources and storage are expected to be pervasive. Overall, energy delivery by electricity has great

Page 4: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

4

advantages in terms of ease of energy transformation, precise control capability and flexibility for end use – i.e., heating, cooling, lighting, consumer electronics, heavy industry, and so on. The modern electric power grid is extremely reliable and efficient in delivering bulk energy from large-scale sources to load distribution centers. At a high level, the interconnected power grid is reliable because system operators can depend on controllable equipment, e.g., generators, to supply power to meet relatively predictable loads. Unfortunately, many of the renewable technologies pose great operational difficulties because the present system is a centralized control structure with a limited amount of storage and control options that requires a precise balance between load and generation to be maintained at all times.

The main challenges of operating a power grid with a high proportion of generation based on renewable resources include that these resources: (1) are less predictable than traditional fuel-based power plants, (2) may be far from load centers so power may have to flow through congested transmission paths, (3) do not generally match the daily cycle of load variation, (4) suffer from unusual operating constraints, such as, rapid variation or complicated weather dependence, and (5) need to be tightly coupled to storage, which may be mobile. To respond to this challenge, this research envisions two fundamental shifts in the approach to the electric power infrastructure, namely

• A broadening of the electric grid to consider overall end energy use, so that electric power generation and delivery does not merely respond to load demand but actively controls energy delivery for plug-in vehicles, the production of fuels (e.g., hydrogen), production of power versus commercially sold steam at thermal plants, energy storage, and end demand as needed.

• A “flattening” of the control structure that fully changes, at all levels of the power grid, the traditional control strategies. Existing energy systems today are characterized by multiple, largely autarchic control systems, including such systems as transient stability control, load frequency control, voltage control, power quality control, and distribution protection. These need to be replaced by a simpler, flatter structure with a local control operating within a more global context for the system.

1.1 A systems approach centered on the electric grid

As illustrated in Figure 1, the PIs believe that a broad integrated energy systems approach is crucial to achieving goals of reduced GHG, adequate performance and low economic cost. Some researchers have suggested a highly distributed approach with, for example at one extreme, extensive roof-top solar and wind units with local storage [1]. This concept is attractive in that it does not rely on the existing infrastructure and allows innovations to be driven at the consumer level. Still, it is not clear that this approach can achieve desired reliability or low economic costs without major technological breakthroughs. The viewpoint taken in this work does not preclude such an eventuality, but does not assume these breakthroughs will materialize. A more pragmatic version of the highly distributed system would rely on some networking and sharing of resources in the distribution system, so-called microgrids, or variations of the different Smart Grid

Page 5: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

5

ideas [e.g., 2]. Again, it is not clear that one can capture the needed reliability and benefits of source diversity by such a structure. At the other extreme, one can envision an extension of the traditional centralized power system operation with say, massive wind farms requiring major new transmission infrastructure, or perhaps large clean coal plants with CO2 sequestration. The uncertainty of the wind output would likely require over building of transmission to take advantage of high power output time periods. Some large scale generation will certainly be built but the economies of scale tend not to hold well for alternative energy units where some smaller installations will certainly be built. Clean technologies for burning fuels are still unavailable. Moreover, the costs and difficulty of siting major new transmission hinder such an approach. Again, this work does not preclude new transmission, and in fact the PIs suggest strongly that new transmission must be added, but depending entirely on extensive new transmission is risky and costly. Finally, while there are certainly potential efficiency gains within the electric power grid to be obtained, these are not as large, and more difficult to achieve, as those from the broader energy system and delivery of services related to overall energy consumption (electric, thermal, HVAC, transportation). Thus, our vision of an expanded electric delivery system is one with greater load and expanded control tools available to operators.

Figure 1: Power system of the future with large penetration of renewable energy and

highly responsive distribution

Underlying this new framework for reliable power system operation is our proposed concept of flat control. Existing energy systems today are characterized by multiple, largely autarchic control systems, including such systems for control of transient stability, load frequency, voltage, power quality, and protection. Within each control system, coordination is achieved through a multi-layered hierarchy at substations, power plants, independent system operators (ISOs), and regional power pools. Such control systems

Page 6: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

6

are often myopic with regard to system needs and emphasize protection of individual components rather than protection of energy delivery and are already stretched to their practical limits. We envision a simpler, flatter structure that consists of only two levels at each scale:

• Local control in which individual components and individual loads operate in a manner that tends to support the best interests of the overall system, for reliability, speed, and robustness of control actions.

• Contextual control in which larger-scale controllers select one of a finite number of system-level control goals, such as efficiency maximization, cost minimization, stabilization, network recovery, or other goals that best reflect needs based on overall system status at a given moment.

An example might be a plug-in hybrid car, for which the owner has set the controls to allow limited use as a grid storage resource in exchange for preferential electricity rates. Given a contextual controller goal, the car’s local power electronics might charge the batteries at night and deliver energy back to the grid for a short time during system load peaks or wind/solar sags. The vehicle could also provide reactive power to the system for local voltage regulation even while charging the battery. However, this context must change with conditions as they arise. There may be, to continue this simplified example, a lull in winds that creates a shortage of supply. The plug-in vehicle should stop, or limit, charging under these conditions. Price signals will convey this to obtain some response, but a simple pricing signal does not provide sufficient granularity for overall system control. The research issue here is how to provide the proper context signal and constraints on local controls to ensure consumption needs are adequately met without jeopardizing overall system operation.

Flat control approaches would be implemented at many different scales, given the multi-scale nature of the overall energy system. For example, a roof-top solar installation would have a local control that might alter its energy behavior in response to local frequency or voltage variation. A shopping center would have a contextual controller to serve the many local controllers within its domain. Each version requires support through information exchange and a communication layer that support this exchange. Flat control supports concepts of aggregation, in which a new type of business offers sophisticated contextual control that serves the power grid operator while supporting local control and its economic benefits down to the customer level.

Individual aspects of flat control have been broached in recent work [3, 4], but the overall system-level issues and methods are a key issue for this research. Suitable economic incentives for local control of individual loads do not exist at present. Together, these needs suggest research across several levels to form an appropriate framework. An electric power system is an extremely complex dynamic system that relies on regular patterns of operation. Even though system characteristics cannot be completely understood, high performance can be assured as long as system limits are respected. A power system with strong renewable energy penetration would be far more dynamic and subject to greater uncertainties than the present system. Successful

Page 7: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

7

operation cannot be realized following current design and decision-making paradigms. The control system and communication methodologies to realize a flat control framework have not been established in a large-scale practical system. Once a framework is established, with published rules and standards, all participants can contribute to the overall goal of employing high levels of renewables. Moreover, this work seeks to establish a structure where capabilities can be added incrementally at various levels and by different technologies, players, and localities. The remainder of the report breaks down the results to date and plans for the current year by the different research tasks.

2. Research Developments and Plans This project consists of the following primary five research thrusts:

1. Flat control and communication framework

2. Intelligent device interfaces

3. Optimization with multi-scale energy sources and demands

4. Transmission grid management and operation

5. Test and verification

Work and plans on each of these areas will be addressed in sequence.

2.1 Flat control and information system methodologies This task seeks to develop the fundamental theories and methodologies to establish

the foundation for system wide flat controls. The key issues relate to identifying the measured variables that must be monitored for effective control and integrating communication systems (and their inherent delays) into the control structure. In this vein, we have developed: a new control approach for load balancing using phase angle measurements, a concept for delay canceling to improve estimation and control over communication networks, sensitivity methods to understand power flow limits and improved grid models based on phase measurements. A common thread through these developments is the importance of new measurement technology using synchronized time stamping to allow coordinated operation over wide areas.

AGC based on a flat control framework

Automatic generation control (AGC) is the name given to a control system having three major objectives: 1. hold system frequency at or very close to a specified nominal value (e.g., 60Hz); 2. maintain correct value of interchange real power between control areas.; and 3. dispatch each unit's generation at the most economic value [5]. In conventional AGC, these objectives are achieved through primary and secondary control actions. Primary control is fast and automatically occurs within the seconds following a disturbance to stabilize the interconnection. Secondary control takes place in the “minute” time frame and manages the deployment of resources to ensure reliable and economic generation. Wind power plants presently installed in the USA are not

Page 8: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

8

responsive to grid frequency or to load frequency control commands, therefore the presence of wind power plants in the system narrows the range of choice available to the system operator in assigning primary and secondary control duty and we need to consider the effect of these units on AGC to allow a high penetration of wind energy [6].

Primary Control relates to the governor and load response that stabilizes interconnection frequency whenever there is a change in load-resource balance. This control is provided in the first few seconds following a frequency change and is maintained until it is replaced by AGC action. Frequency Response (or Beta) is the more common term for Primary Control. Frequency response depends on the combined effect of the droop of all generator speed governors and the frequency characteristics of all the loads in the system. If the generators start to slow with the frequency decline, their governors supply more energy to the generators' prime mover; On the other hand, a given portion of interconnection demand is composed of motor load, which draws less energy when the motors slow down due to the lower frequency. Figure 2 illustrates the effects of governor speed droop and the frequency sensitivity of load on the net frequency change. In this diagram D is the load-damping constant which characterizes the load response to frequency deviation and R is referred to as speed regulation or droop [7]. We investigated this basic frequency control loop using flat control concepts.

 

Figure 2: Composite governor and load characteristic

When a system is flat it is an indication that the nonlinear structure of the system is well characterized and one can exploit that structure in designing control algorithms for motion planning, trajectory generation, and stabilization. Flatness was first defined by Fliess [8] using the formalism of differential algebra. The system is said to be flat if one can find a set of variables, called the flat outputs, such that the system is algebraic over the differential field generated by the set of flat outputs. Roughly speaking, a system is flat if we can find a set of flat outputs (equal in number to the number of inputs) such that all states and inputs can be determined from these outputs without integration. One major property of differential flatness is that, the state and input variables can be directly expressed, without integrating any differential equation, in terms of the flat output and a finite number of its derivatives [9].

Page 9: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

9

We have these derived necessary conditions on a third order generator model in a multi-area system, which satisfy the flat-based control method criteria and uses standard control design to set the parameters [10]. In this formulation, the bus voltage phase angles [δ1, ..., δi, ..., δn] as the flat outputs, the algebraic relationships between the state variables of the generators and [δ1, ..., δi, ..., δn] with its derivatives can be found. The resulting control logic is depicted in Figure 3. The importance of the structure is the simplicity of the primary control loop given the phase angles as the outputs and the introduction of trajectories for each generator to track.

 Figure 3: Flatness-based control block diagram for AGC

 

Figure 4: Wind generation in areas one and two

Details can be found in [10] but here we present a few simulation results on a three-area system [11] for the proposed control. The simulation investigates the impact of wind generation on frequency response and performance of the flatness-based control strategy relative to conventional AGC. Figure 4 shows the wind generation in areas one and two. As observed in Figure 5 and Figure 6, the flatness-based control tracks frequency as does the conventional AGC but with some reduced variation. Moreover, this control strategy is significantly easier to implement compared to conventional AGC given the phase angle measurement and requires only the coordination of the trajectory

Page 10: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

10

planning. Finally a NERC Balancing Standard, CPS1, is calculated for the system under flatness-based control as well as the conventional AGC. The results shows that this value is about 200 for both cases, which means that frequency is on schedule or ACE is zero [12].

 

Figure 5: Frequency deviations (pu)

 

Figure 6: Mechanical power deviations (pu)

Page 11: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

11

Estimation and control over networks Communication delay is one of the unavoidable side-effects of using a computer

network to interconnect sensors, actuators and control centers/nodes. In general, increased delay in a feedback control system often results in instability or reduced performance [13]. In [14], we have proposed a delay compensation approach based on time-stamping of transmitted signals, which can successfully mitigate the destabilizing effects of delay. By “time-stamping” we mean that every signal sample x(t) is transmitted over the network as an ordered triplet (x, t, k), consisting of the sample value “x,” the corresponding sampling time instant “t,” and the identity of the source of the signal x(t) (e.g., which sensor). Time stamping is enabled by the availability of precise time signals derived from the Global Positioning System (GPS) in various nodes of the power system. Such signals are part of Phasor Measurement Units (PMUs) that are increasingly being deployed as a key ingredient of system-wide monitoring and control.

For illustration, we show the performance of our robust estimation scheme for the case of a 2.5 kW induction motor with an uncertain model. Figure 7 shows the signal to estimation error ratio as a function of the network delay for the accurate model (top trace) and for two models with parametric uncertainties (1% and 5%, two lower traces). In comparison, we note that the system without delay compensation becomes unstable for a 50 ms delay.

 Figure 7: Networked estimation/control configuration

Time-stamping of transmitted information can also be used to overcome random, time-variant, delays in the observation path between sensors and estimation/control centers. It can be used with any state-estimation method and any feedback-control strategy, not just Kalman filtering and LQG state-feedback control. In particular, robust

Page 12: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

12

estimation and control methods (see, e.g., [15]) may be required to accommodate significant uncertainty in system parameters (and models). Endowing such robust estimation and control techniques with delay mitigation capability will be the key to successful implementation in spatially-extended power systems.

Previous analysis of the effects of observation intermittency have mostly addressed the problem of dropped communication packets [16], which result in an irregular (random) inter-sample interval with a Bernoulli (i.e., geometric) probability distribution. We have recently extended these results to the case of arbitrary (non-Bernoulli) sensor sampling patterns [17]. In contrast to the formulation in [18], our results do not rely on coordination between the individual sensors, since we assume the cyber-physical power system to be geographically-distributed over a wide area. Uncoordinated (i.e., statistically independent) sampling and transmission of sensor observations result in enhanced resilience to communication packet loss and cyber-security attacks. In particular, we have demonstrated that staggered sampling - i.e., displacing the sampling instants of individual sensors with respect to each other so as to reduce the variation of the combined multi-sensor inter-sample intervals - results in a reduction of the average estimation error covariance [19].

We established a necessary condition for stability of a continuous-discrete Kalman filter with irregularly sampled observations [17]. Our stability condition extends [18] and relates the location of system poles to the region of convergence of the characteristic function (a.k.a. moment generating function) associated with the random inter-sample interval. We have also shown that estimation performance depends primarily on the average length of the sampling interval, with a very minor dependence on the variance and a negligible dependence on higher order moments of the (time-varying) sampling interval (see Figure 8, where ξ is the normalized variance of the random sampling interval and λ controls kurtosis). These observations lead to a simple design rule: the average sampling interval Tav can be adjusted to achieve an acceptable level of state estimation error. Further research is needed to extend these findings to the multi-sensor case, with special focus on estimator stability conditions and on the explicit relation between the average and variance of the signal-to-estimation-error-ratio (SEER) and the average sampling rates of the individual sensors.

Page 13: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

13

Figure 8: Effect of statistics of sampling interval on SEER (top) and zoom-in (bottom)

PMU measurements for voltage sensitivities at transfer interface

Voltage stability analysis is normally based on analytical models and data and requires a significant amount of computation [20], [21], [22] using complex analysis tools. In addition to steady-state analysis, some longer term simulation programs would also provide information on various system component responses as the power system evolves through a voltage stability scenario [23]. Recently the US Department of Energy (DOE) has provided awards to install a large number of phasor measurement units (PMUs), to supplement those PMUs that are already operational [24]. These measured data from these PMUs will be synchronized via GPS signal, allowing wide-area dynamic analysis. With a good coverage of PMUs in some operating regions, it is of interest to develop on-line tools using synchrophasor data to assess voltage stability along power

Page 14: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

14

transfer paths. An investigation of using PMU data for voltage stability analysis is found in [25]. In [25], the disturbance event data of a loss of generation were used to develop a Thevenin equivalent circuit model [26]. There is, however, quite a bit of complexity in the load area because it is supplied by several in-feed paths. Hence the Thevenin equivalent parameters are highly dependent on the load model used. In addition, no analytical model analysis using system model data was performed to support the PMU data analysis.

In this work, we extended the method proposed in [25] to a transfer path in the EI, where the PMU data of a loss- of-generation event at a nearby location is available. This particular transfer path is one of several possible paths to supply generation to the affected areas. Results are reported in [27]

Dynamic data source measurements

Dynamic data source measurements, such as PMUs and digital fault recorders (DFRs), are needed to improve power system dynamic models. In particular, research over the last decade or two has made it clear that the load models used in a transient stability study can have a significant impact on the results, particularly with respect to voltage stability. As a result, transient stability packages such as PSS/E, GE, and PowerWorld include dynamic load models that include a mix of loads including induction motors, discharge lighting, and electronic load. Also, the current draft of NERC Standard TPL-001-2 (Transmission System Planning Performance Requirements) requires that dynamic load models, which include the behavior of induction motor models, be used in system studies. Hence the focus on our initial work has been to determine the most appropriate load models for use in positive sequence transient stability studies (that is, studies with a time frame on the order of several to several dozen seconds). Of course, for many locations on a power system the load composition has a substantial time variation, with factors such as time-of-day and weather conditions having a significant impact. For example, during a hot summer afternoon the load in residential locations would have a high percentage of single-phase air-conditioners, whereas during a winter evening it would have more lighting and resistive heating. However, regardless of the time of day, a significant percentage of the load will need to be modeled using dynamic induction machine models. The goal of this work is to use actual system measurements to determine the appropriate load models, recognizing that this might require several different models to represent different operating conditions.

We plan continue to focus on the application of dynamic data source measurements, for the development of improved power system dynamic models. We are in the process of getting NDAs in place with utilities in order to get access to actual system information. Work will continue on developing appropriate load models, and will also expand to the development of better models for wind turbines.

Modeling and control via dynamic phasors Dynamic phasors are finding increasing use in analysis and control of electric energy

components and systems. Applications of the dynamic phasor framework are numerous, and include power systems (analysis of unbalanced faults and protection), electric drives

Page 15: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

15

(analysis of unbalanced electric machines and of position-dependent loads, torque ripple minimization) and power electronics (model reduction in DC/DC converters, analysis of resonant and high-power converters, control of active filters). While dynamic phasors are intended for near-to-periodic operation, they have a number of useful features: (i) models are time-invariant (autonomous); (ii) inputs and consequently states tend to vary slowly compared to the driving frequencies; (iii) they achieve "simultaneous demodulation" in that all variables are constant (``dc") in a steady state; (iv) they are very effective in revealing dynamic couplings between various quantities, as shown in derivation of novel equivalent circuits for unbalanced ac machines [28].

Recently we have shown that such dynamic phasor expressions are a special case of a broader family of customizable signal transforms that we called Phasor Banks [29]. The need for compact dynamic phasor representations that can be efficiently communicated across a spatially distributed cyber-physical energy system mandates customization that focuses on frequency selectivity. Similarly, dynamic phasors for fault detection and location applications require a customization focused on time selectivity. In this project, we will explore advantages of matching the phasor bank to different applications such as fault detection and location, power decomposition, adaptive compensation and networked estimation. We will also explore the use of such descriptions in model-based detection and neutralization of cyber intrusions [30].

Dynamic power analysis and control

One well-known approach to dynamic characterization of power, proposed in [31], relies on the observed instantaneous (polyphase) voltage and current. Instantaneous quantities are convenient in real-time control implementations, especially when minimization of memory requirements and online calculations is of key importance. This is much less important for modern discrete controllers whose memory and computational capabilities are often driven by very demanding applications (such as video), and typically much surpass control requirements in electronic and electromechanical systems. Instantaneous quantities are extremely sensitive to noise and processing delays, and thus are often filtered in an ad-hoc way in implementations. They are often used in straightforward control schemes that rely on integral action (at an appropriate frequency) to drive the error signals (e.g., the instantaneous reactive power as defined by Akagi-Nabae [31]) to acceptably low levels.

We propose an alternative approach, motivated by our steady-state decomposition, to construct a novel dynamic (i.e., time-variant) 7-component power decomposition [32]. Our approach is based on dynamic phasors, and offers an interesting alternative. It relies on the fundamental, cyclic mode of operation of all energy conversion systems (periodic in the idealized steady-state) and applies naturally to any number of phases. It includes explicit models of components, and reduces to well-known quantities (such as harmonics) in steady state. Such quantities are often the subject of binding regulations (e.g., the power factor or the harmonic content). The quantities that we define dynamically can be used both in simple integral controllers and in more ambitious model-based control schemes. In addition, dynamic phasors can be customized to optimize specific properties

Page 16: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

16

in transients (e.g., frequency separation), as shown in [29]. Our dynamic power decomposition, viz.,

S2(t) = P2(t) + Ns

2(t) + Nu2(t) + QB

2(t) + Qs2(t) + Qu

2(t) + S┴2(t))

captures transient behavior, while reducing to the standard (constant phasor) characterization in steady-state [31]. Here, P denotes the real (active) power, QB is the reactive (Budeanu) power, Ns (respectively Qs) is the co-active (resp. co-reactive) power due to the spread of (incremental) conductances (resp. susceptances) in various phases over frequency, Nu (respectively Qu) is the co-active (resp. co-reactive) power due to the spread of (incremental) conductances (resp. susceptances) in various phases across phases, and S┴ denotes a component due to system responses (typically currents) at frequencies or phases when there is no driving term (caused by circuit nonlinearity).

For instance, Figure 9 shows the time-evolution of our seven power components, determined from data recorded in a paper plant during an outage described in [33] (the data was graciously provided to us by the authors).

 Figure 9: Dynamic power components

Notice the dramatic change in the Nu(·) and Qu(·) components, which captures the

effect of load imbalance during the onset of the fault. Also notice that our dynamic power components assume their classical (steady-state) values away from the fault. The

Page 17: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

17

use of dynamic phasors makes it possible to enforce P(t) = S(t) (with negligible line impedance) even during transients, by employing the adaptive compensator of [34], which we describe below.

The role of compensation in controlling power flow in cyber-physical energy systems is to reduce the power consumption of the Thevenin equivalent source (or "line") impedance, so that most of the generated power is delivered to the load. This impedance represents the combined effect of all power sources, loads and transmission/distribution lines in a power network. With the dispersion of energy sources to lower-voltage networks, the line impedances are bound to increase. They will also vary much more, as the topology changes are much more frequent is such networks. In addition, many renewable sources are inherently single phase (e.g., small rooftop photovoltaics), and their intermittency will lead to increased unbalances in polyphase networks. Together with increased injection of harmonics by new loads and sources, this will result in modes of operation that are qualitatively very different from the ones assumed traditionally for network compensators such as active and passive filters and shunt capacitors.

Traditional compensation methods, such as Fryze compensation, lose their effectiveness when the equivalent line impedance is no longer negligible in comparison with the load impedance. Moreover, constantly changing network conditions require continuous readjustment of the compensator current in order to ensure continuing efficient operation of the power system. Recently, we have introduced an adaptive near-optimal compensation scheme that relies only on measurements of the load voltage and current or, equivalently, on the phasor description of these waveforms [34]. Our compensator tracks variations in both network and load conditions, continuously adjusting the polyphase compensator current so as to reduce the power dissipated in the source impedance, for both linear and nonlinear loads.

We show in Figure 10 an example of the performance of our adaptive near-optimal compensation method: Pline are the line losses, Pcload is the power supplied to the compensated load, and Pcomp is the (real) power supplied by the compensator (which is zero on the upper parabolic cross-section curve). The nonlinear (electrical) load to be compensated is an induction machine rated at 25 kW, connected to a mechanical load with a quadratic torque-speed characteristic, and supplied over a long, unbalanced line [34]. The solid line in the figure connects the points obtained by our iterative algorithm. We use the cross-section curve, which indicates the theoretical optimum (dash-dot line in Figure 10) achievable with exact knowledge of network and load characteristics, as a benchmark for comparison. Due to the near-optimal characteristic of our compensator it is observed that the steady-state points (white circle markers in Fig. 10) lie very nearly on the optimum cross section curve.

Page 18: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

18

Figure 10: Convergence trajectory of the adaptive compensator.

Future research is needed to validate our approach with a wide variety of nonlinear loads, to establish the boundaries of stable operation, both in steady-state and in the presence of network transients, and to develop safeguards against loss of stability even under the most compromising conditions. Our ultimate goal is to develop a methodology of collaborative adaptive networked power flow control that can use network status information, extracted from the information layer of a cyber-physical energy system, to improve overall energy delivery efficiency beyond what can be achieved with stand-alone (i.e., network-blind) adaptive compensators. In particular, network information can be used to speed up the convergence of our adaptive compensation scheme, as well as expand the region of its stable operation.

The sensing, communication, and processing resources available in each hub can also be used to detect and locate faults in power lines, using the technique proposed by [35] and [36]. In this work, arrival time differences of signals from the fault point to the synchronized monitoring instruments are used for accurate fault location. When a fault occurs, electromagnetic waves which originated at the fault point travel along neighboring transmission lines. Since these traveling waves follow different paths, they arrive at distant recorder locations with distinct time delays. Referring to these wave-arrival delays of a certain fault transient at various locations in the network, the fault location can be determined. The previously proposed methods assumed either a single recorder at one end of the faulted line, or a pair of synchronized recorders at both ends of the faulted line. In this work we take advantage of sparsely distributed available synchronized recorders throughout the network. The captured waveforms are processed together in order to identify the exact location of the fault under study.

Page 19: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

19

2.2 Intelligent device interfaces Under the concept of flat control, a key property for development of an inclusive

power grid infrastructure is effective local control. In general, the objective is to seek control approaches at each level of hierarchy that acts in accordance with limited information, but in such a way that the overall system performance in enhanced. This implies requirements for communications and device interfaces. An implication of the local control approach is that many types of electrical loads will participate as active entities at the lowest level of grid control. This task will identify, analyze, and implement examples of useful communication and device interfaces to establish the concepts. We have developed an information infrastructure for vehicle to grid generation that provides benefits to the owners and regulation services for the utility. We also investigate how the PV interface can be used to enhance power quality providing dual functionality for the PV system. We have developed new wind turbine models and power electronic interface for improved control. Finally, a control system that allows “plug-and-play” capability for a STATCOM is described.

Vehicle-to-grid informational infrastructure

Initial work has focused on the informational aspects associated with the integration of electric vehicles in the grid. In particular, vehicle-to-grid emphasizes bidirectional power flow as a means of providing V2G benefits to the utility, but the work suggests that bidirectional flow may not be necessary to gain nearly all of the benefits. These benefits include ancillary services such as reactive power support, active power regulation, and storage support as well as revenue generation or discounted rates for vehicle owners. The goal of this work is to establish the principles of a unidirectional charge scheduling algorithm that can provide cost benefits to EV owners and regulation services to the power system while guaranteeing the desired charge energy. Basic principles have been established that suggest the use of low-rate communications and a unidirectional charger for V2G control. Figure 11 shows an example of this charging. These results are reported in detail in [37, 38].

Page 20: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

20

 

Figure 11: Unidirectional EV Charger Performing Regulation Services.

PV to grid integration for improved power quality In grid-connected systems, the panels needed to reach the required power levels are

usually arranged in strings. The cascaded H-bridge multilevel inverter requires a separate DC source for each H-bridge; thus, the high power and/or high voltage from the combination of the multiple modules would favor this topology in grid-connected PV applications [39, 40]. shown in Fig. 12, the cascaded multilevel inverter topology consists of n H-bridge converters connected in series, and each DC link is fed by a short string of PV panels. By different combinations of the four switches in each H-bridge, three output voltage levels can be generated, –vc, 0, or +vc. A cascaded multilevel inverter with n input sources will provide 2n+1 levels to synthesize the AC output waveform. This (2n+1)-level voltage waveform enables the reduction of harmonics in the generated current, reducing the output filters. In addition, the multilevel inverter also presents the advantages of reducing the device voltage stress and being high efficiency [41].

The grid-connected PV systems should provide both the active power and reactive power, especially in a grid system with high renewable penetration. In Figure 12, the photovoltaic cascaded H-bridge multilevel inverter is connected to the grid through an inductor L. A generalized nonactive power theory is applied to generate the nonactive current reference [42]. In addition to providing the active power, the multilevel inverter could also provide the reactive power required by the local load to maintain good power quality in the grid. Simulation is carried out in Matlab/Simulink to validate the proposed ideas. An 11-level cascaded H-bridge inverter is considered. Each H-bridge has its own 195 W PV panel connected as an independent source. The system parameters are shown in Table 1. The PV panel is modeled according to the specification of the commercial

Page 21: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

21

PV panel from Sanyo, HIP-195BA19. The I-V characteristic of the panel obtained by simulation is shown in Figure 13.

 

Figure 12: Topology for grid connection.

Table 1. System parameters

Parameters Value

DC-link capacitor 2200 µF

Connection inductor L

6 mH

Load inductor 20 mH

Load resistor 20 ohm

Grid inductor 5 mH

Grid resistor 0.2 ohm

Grid rated RMS voltage

120 V

Page 22: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

22

The power generated by the solar panel depends on the solar irradiation on the panel, the operating temperature and the operating voltage of the panel. To use all of the available output power, PV systems should be operated at their maximum output power levels for any solar irradiation and any temperature. Thus, tracking the maximum power point of PV panels is an essential part of PV systems. The incremental conductance method is applied, and simulation results are shown in Figure 14-Figure 15. When temperature T=25 ˚C and irradiation S=1000 W/m2, the maximum power point voltage Vmpp of PV panel HIP-195BA19 is 55.3 V. It can be seen that the voltage reference would achieve 55.3 V by maximum power point tracking (MPPT) control no matter what the start voltage reference is, and the output power would be 195 W.

The voltage and current waveforms of the grid and load are shown in Figure 16. It can be seen that the load voltage is tracking the grid voltage. The load current is lagging the voltage, however, even if the grid is sending power to the local load or receiving power from the PV system, the grid current has the same phase as the voltage, which means the grid has unity power factor. Figure 17 shows the THD of the load voltage and grid current when PV operated under irradiance S=1000 W/m2. Due to the cascaded H-bridge multilevel inverter, the THD is low even without any filter. The high order harmonics could be easily eliminated by adding a small capacitor, and the THD can be further reduced.

In a grid system with high renewable penetration, the grid-connected PV systems should provide both the active power and reactive power to improve grid power quality. The cascaded H-bridge multilevel inverter is suitable for grid-connected PV applications, and presents the advantages of reducing the device voltage stress and output filters.

Future plans include experimental tests to validate the proposed ideas and compare with the simulation results. Besides reactive power compensation, other auxiliary functions, like harmonics compensation, will be also considered in grid-connected PV systems. In addition, three-phase grid-connected PV systems will be studied in the future.

 

Figure 13: I-V characteristic under different irradiance.

Page 23: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

23

   

Figure 14: Voltage reference and output power when start voltage reference is 59V (T=25 ˚C, S=1000 W/m2).

   

Figure 15: Voltage reference and output power when start voltage reference is 53V (T=25 ˚C, S=1000 W/m2).

Page 24: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

24

 

(a) S=1000 W/m2, grid receives power from PV

 

(b) S=400 W/m2, local load receives power from grid

Figure 16: Voltage and current waveforms of grid and load (T=25 ˚C).

Page 25: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

25

 

(a) THD of the load voltage

 

(b) THD of the grid current

Figure 17: THD of the load voltage and grid current (S=1000 W/m2, T=25 ˚C).

Wind turbine modeling and controls for grid integration The first year effort has focused on offshore wind turbine modeling and control for

grid integration. A baseline 1,000 MW offshore wind farm with high-voltage direct current (HVDC) transmission connection to onshore ac power grid has been defined and modeled in a circuit simulation program (Saber). The modeled wind farm consists of 400 turbines each rated at 2.5 MW and using a permanent-magnet generator and two back-to-back voltage source converters (VSC). The turbines are connected to a 33 kV local power collection bus, which is stepped up to 211 kV at a central location for interfacing with an offshore HVDC rectifier station. Both line commutated converter (LCC) and VSC-based HVDC technologies have been considered, and an LCC HVDC system was designed. A 300 MVA static synchronous compensator (STATCOM) is used in parallel with the HVDC rectifier to support the stability of the 33 kV ac bus.

To reduce the complexity and simulation time, the 400 wind turbines are lumped into 5 equivalent turbines each rated for 200 MW. Startup and steady-state operation of the system has been simulated to verify the circuit and control design. Currently, small-signal impedance models of the wind turbine system, the STATCOM, and the HVDC rectifier are being developed using harmonic linearization methods. These impedance

Page 26: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

26

models will be used to analyze the voltage stability of the 33 kV local collection bus, and to determine control requirements for the turbine, the STATCOM, and the HVDC rectifier to ensure system voltage stability. The models will also provide a foundation for optimal system control development to minimize the required capacity of the STATCOM, thereby minimizing overall system cost.

The overall objective of this task is to development analytical methods and tools for local control design to ensure system stability and power quality of future power grid. A fundamental challenge for the analysis and control of an ac power system is the time-varying (sinusoidal) operation trajectory, which prevents direct linearization of any nonlinear device models. Existing power system analysis methods overcome this difficulty by using phasor-based models, in which voltages and currents are represented by their amplitudes and phase angles. These phasor quantities become constant once the system reaches a steady-state, thereby permitting the application of traditional small-signal linearization techniques [43]. However, phasor-based models are only meaningful below the grid fundamental frequency and cannot capture the fast dynamics of power electronic circuits and control that are becoming increasingly pervasive due to the proliferation of renewable generation, energy storage, as well as load management and energy-efficiency technologies (such as solid-state lighting and variable-speed drives) that rely on power electronics. New analytical methods and tools are needed for the modeling and control design of such power electronics-enabled sources and loads, as well as for the analysis of power systems incorporating such devices.

One way to overcome the frequency limitations of traditional phasor-based models is to use dynamic phasor models [44]. In this approach, a periodic dynamic variable is represented by its fundamental component as well as a selected number of harmonics, and each such frequency component is represented by its amplitude and phase angle (or real and imaginary parts of the Fourier representation.) Task 1.4 in this project will tackle modeling and control at different time-scales using dynamic phasors. A different method based on harmonic linearization will be used in this task to develop small-signal models particularly suitable for fast dynamic stability and power quality analysis, as well as for local control design that enables autonomous operation of distributed resources, energy storage devices, and actively controlled loads with minimal requirement for communication.

The harmonic linearization method develops a small-signal input and/or output impedance model directly in the frequency-domain. The method works by first injecting a voltage or current perturbation at a particular harmonic frequency, and then using harmonic balance principle to determine the response of the device at the perturbation frequency. Input or output impedance of the device at the perturbation frequency is obtained by the ratio between the input or output voltage to the input or output current. This method has been successfully applied to multi-pulse rectifiers [45] as well as phase-controlled rectifiers [46] used in motor drive systems. One objective of this task is to extend the harmonic linearization method to other power electronic circuits, and to develop system analysis and control design techniques based on the resulting impedance models.

Page 27: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

27

A particular type of system that we want to investigate is offshore wind farm with HVDC connection to onshore power grid. Such a system involves different types of switching power converters, such as PWM rectifiers and inverters, STATCOM, and HVDC converters. Stability is a critical issue at multiple interconnecting points in such a system, including the dc bus within each wind turbine, the local ac collection bus, the HVDC link, and the onshore power grid. The impedance models developed by using the harmonic linearization method can be used in conjunction with impedance-based system stability criterion to determine the stability of these buses [47]. The impedance models also provide a basis for control design of individual converters to ensure system stability and power quality, and to minimize converter size and system cost.

One form of instability in ac power systems involving power electronics is harmonic resonance formed between a converter and the network, or between different converters connected to the system. For example, an inverter interfacing a wind turbine with the grid usually exhibits capacitive output impedance above the grid fundamental frequency. Such capacitive output can form an un-damped or very lightly damped resonance with the typically inductive impedance of the grid, producing high harmonic currents that represent a major power quality problem and can lead to tripping of inverter disconnect switches and other protection devices. The impedance models developed using harmonic linearization techniques were found to be very effective in predicting such system harmonic resonance [48]. The impedance models also provide a basis for converter and system design to mitigate such resonance by means of passive and active damping, as well as inverter control design to purposely reshape its output impedance.

Wind turbines using full-power conversion architecture are typically controlled to act as current sources. The grid must have low enough impedance in order to provide a stable interface for such turbines. In the case of an offshore wind farm with HVDC transmission connection, the “grid” seen by these turbines is formed by the HVDC rectifier. Existing design approaches measure the strength of the grid by its MVA rating, which makes no sense when the turbines are connected to a HVDC rectifier, as the MVA rating at the fundamental frequency has very little correlation to its impedance at other frequencies, particularly above the line fundamental frequency where harmonic resonance is a major concern. Input impedance of the rectifier, as pursued in this project, provides a much more suitable performance measurement of HVDC rectifiers for offshore wind applications.

A STATCOM is required to stabilize the local collection bus when a LCC HVDC rectifier is used [49]. Sizing of the STATCOM is important for system optimization, as it significantly affects overall system cost. The existing design method based on steady-state power ratings of the turbines doesn’t address the high-frequency impedance compatibility issue mentioned above, and often leads to either an overly sized design that drives up system cost, or an inappropriate design that is unable to stabilize the ac bus despite its high MVA rating at the fundamental frequency. A specific objective of this research is to develop system impedance models that can be used to guide the design of the STATCOM and individual turbine control that results in minimal converter size and system cost.

Page 28: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

28

A 1,000 MW offshore wind farm with high-voltage direct current (HVDC) transmission connection to onshore ac power grid has been defined and modeled in Saber. The wind farm consists of 400 turbines each rated at 2.5 MW and using a permanent-magnet generator and two back-to-back voltage source converters (VSC). Each turbine is equipped with a step-up transformer for interfacing with a 33 kV power collection bus, and includes several control loops that affect its behavior at the grid interface, including dc bus voltage control, grid current control, remote bus voltage control, and a phase-locked loop for grid synchronization. To reduce the model complexity, the 400 turbines are lumped into 5 equivalent turbines each rated at 200 MW. These turbines are connected to a 33 kV local collection bus, which is stepped up to 211 kV at a central location for interfacing with an offshore HVDC rectifier station. Both line commutated converter (LCC) and VSC-based HVDC technologies have been considered, and an LCC HVDC system has been designed.

To stabilize the 33 kV local collection bus, a 300 MVA static synchronous compensator (STATCOM) is placed in parallel with the LCC HVDC rectifier. A 7 km medium voltage submarine cable is assumed between each lumped wind turbine model and the HVDC rectifier station. The nominal voltage of the HVDC link is set at 500 kV. Filters are placed at both the input of the HVDC rectifier and the output of the onshore HVDC inverter to attenuate the large 11th and 13th harmonic. The onshore power network is assumed to be a weak grid with high impedance. The grid voltage can also be modulated by a control signal to simulate various operation conditions. Figure 18 shows the overall schematic of the system including all components and major connections. Figure 19 gives additional details for the five lumped turbine models, where each model consists of a permanent-magnet generator, a PWM rectifier and a PWM inverter connected back to back, a step-up transformer that converters the 690 V ac output of the inverter to 33 kV, and an impedance circuit represents a 7 km submarine cable.

Figure 18: Overall schematic of the simulated offshore wind system as implemented in Saber.

Page 29: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

29

 

Figure 19: Details of a lumped wind turbine model with a step-up transformer and 7 km cable.

While the control of the system is still being revised, preliminary simulation results have been obtained for the system during startup and steady-state operation. Figure 20 shows the simulated startup transient response of the HVDC link current settling at 2 kA rated current, as well as the STATCOM dc bus voltage, which has a steady-state value of 37 kV. Overshoot of the dc bus voltage is critical for the design of the STATCOM and is limited by incorporating a feedforward signal into the HVDC rectifier current control loop to minimize the transient power imbalance between the wind turbines and the HVDC rectifier that otherwise has to be absorbed by the STATCOM dc bus capacitor. Responses of the system to gust wind conditions have also been simulated.

Figure 20: Startup transient responses of HVDC link current (left) and STATCOM dc bus voltage (right).

Small-signal modeling of the wind inverter, the STATCOM, and the HVDC converters has been pursed in parallel with numerical simulation of the system. The inverter output impedance is modeled by the harmonic linearization method. A particular issue studied is the coupling between positive-sequence and negative-sequence output impedance of the inverter. Through analytical modeling and numerical simulation, it was concluded that, although the phase-locked look creates cross coupling between the two sequence component subsystems, the coupling term can be ignored for small-signal analysis, thereby permitting the stability of each sequence subsystem to be studied independently. Figure 21 illustrates the calculated (solid lines) and simulated (dots) inverter output admittance in the positive and negative-sequence domain.

Page 30: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

30

1 Hz 10 Hz 102 Hz 103 Hz

1 Hz 10 Hz 102 Hz 103 Hz

Figure 21: Positive- and negative-sequence output admittance (in dB) of one wind turbine inverter.

Preliminary modeling results have also been obtained for the LCC HVDC rectifier input impedance. The following equations give the input impedance of an N-phase rectifier in the positive and negative sequence domain (Zp and Zn) as a function of the dc link impedance, Zdc, as measured between the dc output terminals of the rectifier, where α0 is the phase control angle of the rectifier at the given steady-state operation point, Hc(s) is the transfer function of the HVDC rectifier dc link current controller, V1 is the amplitude of grid phase voltage, and f1 is the grid fundamental frequency (60 Hz). The infinite summation over m can be truncated to include only the first few terms without significantly affecting the accuracy of the model. In addition to dc link cable impedance, Zdc is also affected by the onshore grid impedance and control of the onshore HVDC inverter, and can be determined using similar impedance mapping functions. Application of these basic impedance models to develop a complete input impedance model for the 12-pulse HVDC rectifier will be pursued in the 2nd year of the project along with system small-signal analysis.

Page 31: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

31

The impedance-based system stability analysis method has also been applied to determine harmonic resonance between a wind inverter and a traditional ac grid in a related project. An experimental setup (distributed generation test-bed) at RPI allows the grid impedance as seen by the wind inverter to be varied to simulate different grid conditions. Figure 22 shows the measured grid voltage and wind inverter output current under two different grid conditions. Harmonic resonance was found to occur in the second case when the grid impedance is high. To find the origin of such harmonic resonance, the grid impedance and the inverter output impedance were measured and their responses are plotted in Figure 23. In the case of high grid impedance, the inverter output impedance intersects with the grid impedance at about 400 Hz where the phase difference between the two impedance approaches 180o, indicating a highly under-damped resonance between the inverter and the grid at about 400 Hz. Spectrum analysis of the grid current, shown in Figure 24, indicates that the dominant components are the 5th and 7th harmonics, which correlate closely with the predicted system resonant frequency.

Page 32: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

32

Figure 22: A wind inverter output voltage (upper traces) and current (lower traces) under different grid conditions: Left: Strong grid with low grid impedance; right: weak grid

with high grid impedance.

Figure 23: Inverter output impedance (blue) vs. grid impedance under two different grid conditions. a) Low grid impedance (dashed lines); b) high grid impedance (solid lines).

 

Figure 24: Measured grid current harmonics.

Page 33: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

33

Plans for further development of this work include:

• Design of the wind turbine, STATCOM, and HVDC converter control will be tuned and finalized based on preliminary simulation results.

• Small-signal impedance models will be developed for the wind inverter, the STATCOM, and the HVDC rectifier using harmonic linearization and impedance mapping techniques.

• Voltage stability of the 33 kV local power collection bus will be studied using the developed impedance models. Possible modes of high-frequency interactions and system harmonic resonance will be identified.

• Control of the wind turbine, the STATCOM, and the HVDC rectifier will be optimized based on system impedance characteristics and stability requirement to minimize the required STATCOM power rating. General guidelines for the development of such offshore wind power systems will also be developed to minimize the system cost.

• A similar approach will be used to study the interactions between the HVDC inverter and the onshore power grid. Stability and control of the onshore grid will be studied in conjunction with Task 4.

• VSC-based HVDC converters will be designed as possible replacement for the LCC HVDC converters. Control and stability characteristics of both offshore and onshore power system will be investigated and compared with that using LCC HVDC.

• Effects of local energy storage devices and loads on system stability and control will be studied, and autonomous control techniques will be developed for such devices to enhance system stability.

Adaptive control for STATCOM to enhance voltage stability A STATCOM can provide fast and efficient reactive power support to maintain

power system voltage stability. In the literature, various STATCOM control methods have been discussed including many applications of PI controllers. However, these previous efforts obtain the PI gains via a trial and error approach or extensive studies with a tradeoff between performance and efficiency. Control parameters for the optimal performance at a given operating point may not be effective at a different operating point. This paper proposes a new control model based on adaptive PI control, which can self-adjust the control gains during a disturbance. The control gains are dynamically adjusted such that the performance matches a pre-defined desired response, regardless of the change of operating condition. Since the adjustment is autonomous, this gives a “plug and play” capability for STATCOM operation. Simulation tests demonstrate consistent performance under a variety of operating conditions, including different load levels and topology changes. As a comparison, the conventional STATCOM control with tuned,

Page 34: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

34

fixed PI gains is shown to suffer significant problems when there is a change of the system conditions. This work is reported in [50].

3.3 Optimization with multi-scale energy sources and demands The highly random variability of wind speeds results in major challenges in scheduling. As the penetration of wind increases, the variability issue becomes more pronounced. This has a direct impact on electricity prices as can be seen today with price spikes occurring during fast ramp up or ramp down time periods. When the effects of wind speed forecasting errors are also considered, the combined effects of the various sources of uncertainty create major challenges for unit commitment and dispatch. Without sufficient controls and storage, the operators can only manage the uncertainty by increasing the level of reserves -- spinning and stand-by -- to have the appropriate “insurance” in place. This insurance policy incurs costs for running the increased reserves and the associated start-up costs with the reserves. This task will develop optimization methods to schedule loads, generation, and storage dynamically while respecting system limits and considering a broadening of the system to these new loads, such as, might exist for hydrogen production. A significant challenge is developing computationally tractable methods for optimization under these uncertainties. Initial efforts have focused on quantifying the reserves needed to allow reliable operation without sacrificing reliability or imposing high costs on producers. We are also developing modeling tools to allow studies of longer term impact on the system. Finally, in these and other efforts, the importance of establishing market incentives for integration of renewables is emphasized.

Quantifying spinning reserve for systems with high penetration of wind

Currently, there are two basic methods of quantifying spinning reserve. One is deterministic method, which usually requires spinning reserve equal to the capacity of the largest generator in the system [5, 51]. By this method, the system is able to continue operate following the loss of any single unit. While simple to implement, this method cannot guarantee uniform reliability of the system at all time. More importantly, the concept is difficult to apply to the forecast errors associated with wind power. The other approach to setting reserves is probabilistic, which attempts to take load forecast error and generators' outages into consideration by calculating some reliability index, such as loss of load probability (LOLP) or Expected of Energy Not served (EENS). In [52], the commitment risks of generators are used to determine the spinning reserve in unit commitment. This approach is generally not used to dispatch generators but for planning or operations planning purposes.

In [54], the conventional hydro-thermal model is extended to take into account load and wind speed forecast errors. The reserve levels are determined by setting the possibility of unacceptable frequency deviations due to load and wind fluctuations. However, the Swedish system has a reserve pool for frequency control separate to the reserve allocated for generator trips and extensive hydro. Persaud et al [54] analyze the impact of wind power capacity on system reserve availability and conclude that large amounts of spinning reserve will be needed to maintain the system security when wind power penetration is integrated. Ronan et al [55] use the number of load shedding events per year as the reliability criterion to quantify the spinning reserve in a system with large

Page 35: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

35

wind power penetration. The net load forecast error is modeled as normal distribution. However, this criterion does not consider the extent that supply fails to meet the demand. In [56], Bouffard and Galiana use both EENS and LOLP as constraints in market clearing scheme, which is then solved by mixed integer linear programming. The wind power penetration is considered in [58] with a discrete normal distribution of the net load forecast error. In addition, a scenario tree is introduced to simulate the intro-period transitions. However, the model requires a heavy computational burden when all possible scenarios are considered. Ortega-Vazquez et al [58] use a cost/benefit analysis to determine the optimal spinning level for each time interval, which is used in later reserve constrained unit commitment. The iterated grid search with three-point search is taken to find the optimal spinning reserve. In [59], they add the uncertainty of wind power generation into the model. The Gaussian distribution of net forecast demand error is approximated by seven intervals. A capacity outage probability table (COPT) [60] is used to calculate the EENS of system. This method is suitable for unit commitment. However, in advanced dispatch, which is typically one hour ahead, the COPT is not applicable due to the ramping rates of generators.

In this work, dispatch considering the reliability index EDNS and the uncertainties of wind speed, load and generators is formulated. The overall optimization scheme is shown in Figure 25. Some results are presented here based on the IEEE Reliability Test System. We solve the deterministic model while maintaining a fixed spinning reserve as the capacity of the largest generator in the system, which is 400MW. Then, we calculate the EDNS using a deterministic method. By setting the maximum EDNS of it as the constraint of probabilistic method, we calculate the new dispatch result of our probabilistic method. The EDNS of deterministic method and standard deviation of net demand forecast error are shown in Figure 26. The results demonstrate the validity of the model and the relationships of various uncertainties with the system spinning reserve. The objective here is take advantage of wind resources without a decrease in reliability.

Future work includes adding a more complete set of constraints to the unit commitment problem, increasing the speed and efficiency of the algorithm, and modifying the new reserve constraint so that the new system will have the same reliability while lowering cost.

Page 36: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

36

 Figure 25: Iterative scheme to determine spinning reserve requirements.

0 1 2 3 4 5 65

6

7x 10 3

t timeinterval=10mins

EDN

S U

nder

Det

erm

inis

tic M

etho

d

0 1 2 3 4 5 640

45

50

Stan

dard

Dev

iatio

n of

For

ecas

ting

Erro

rEDNSStandard Deviation of Forecasting Error

 Figure 26: EDNS variation with forecasting error

Page 37: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

37

Long term simulation for systems with high penetration of renewables Work has begun on the development of a simulation tool to emulate the behavior over

longer-term periods of the power system with deep penetration of renewable energy, storage and demand resources. The deepening penetration of renewable resources, together with the renewed emphasis on the active participation of the demand side in attaining the needed supply-demand balance, are creating an acute need for practical planning and operations tools to study the effects of the integration of wind resources into the grid. The high variability in wind speeds and insolation patterns, as well as their intermittency effects in the output of wind and solar generation resources, pose major difficulties in power system planning and operations. Indeed, the highly variable and intermittent wind and solar generation outputs are not controllable by the operator. The wind speed and insolation patterns present a key challenge to integration of wind resources since the wind may not blow and the sun may be covered by a cloud when the system most needs the output of these resources. Moreover, often the wind may blow at appropriate speeds for generation in the low-load hours while the wind speeds are too low for generation during the peak-load hours. The lack of controllability over such wind speed patterns and cloud cover events implies that the integration of wind and solar resources into the grid may be unable to realize their full potential. There are also concerns about “spilling” of wind energy at night due to the insufficiency of the load demand, not providing to the system, in such cases, the benefits from this energy to meet the demand. The basic tool operators use to manage the wind variability is the raising of the reserve levels, which, typically, results in increasing the overall production costs, notwithstanding the zero fuel costs of the wind resources. Such situations create excellent applications for utility-scale storage to facilitate the improved harnessing of the wind resources by storing renewable energy for release during peak-load hours so as to displace the costly energy from polluting generating units.

Growing environmental concerns and increasing electricity prices have led to the wider implementation of demand response programs and created a new class of players – the so-called demand response resources (DRRs). These DRRs modify their electricity consumption in response to the signals from the energy service providers (ESPs) or the independent grid operators (IGOs) to provide the services requested of them. The market and policy developments in the U.S. over the last decade have led to a significant increase in the nationwide DRR capacity. The 41 GW peak load reduction potential recorded in 2008 represented a 26 % increase in the DRR capacity from that in 2006 and nearly 5.8 % of the 2008 U.S. peak load. The DRRs actively participate in the electricity markets as both buyers of electricity and sellers of load curtailment services and, thus, affect the market outcomes and the utilization of the generation and transmission resources. In many U.S. jurisdictions, mechanisms have been developed which allow DRRs to actively participate in the IGO-operated electricity. The market rules allow DRR participation for certain hours of the day, during which DRRs may reduce their demands to provide load curtailment services. In this way, DRRs compete directly against the supply-side resources that sell their generation outputs and provide the IGO with additional degrees of freedom in maintaining the supply-demand balance. Clearly, the ability to exploit the enhanced flexibility in the system operations provided by the DRRs is heavily influenced by the market structure and the operating policies in force.

Page 38: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

38

Although there is wide agreement that the DRRs are important to fully harness the benefits of competition, there is considerable debate as to the best way to integrate them into the system and market clearing operations.

To address these issues in the systems with the deeper penetration of renewable resources, appropriate tools, which quantify the impacts of integrated renewable, storage and demand response resources on the market performance, generation dispatch, transmission usage and congestion, emissions and system reliability are required. We are laying the foundation for a unified framework aimed at the quantification of wind, solar, storage and DRR impacts. The framework represents, with the appropriate level of detail, the supply- and demand-side resources, the transmission grid, the market clearing operations, the market structure and operating policies, as well as the various sources of uncertainty. Our efforts are focused on the incorporation of the renewable, storage and DRR modeling in a probabilistic methodology so as to explicitly account for the impacts of the DRRs on the conventional supply side resources and the utilization of the transmission grid. This is a key step in the establishment of an analytical basis for a comprehensive simulation methodology for power system planning, policy analysis and economic/reliability evaluation for longer-term studies. Such a basis provides the means to construct a probabilistic simulation approach of systems with integrated wind, solar, storage and DRRs over longer-term periods. The methodology may be used to quantify the variable effects over longer-term periods of large-scale power systems with storage and intermittent solar and wind, and time dependent demand response resources operating in a market environment.

To date we have completed the initial steps to construct probabilistic models for wind and solar resources, with the uncertainty in the variability/intermittency effects of wind and solar generation at multiple sites together with the other sources of uncertainty explicitly represented. The modeling approach is based on the identification of the prevailing wind speed and solar output regimes in the regions where the resources are located. The regimes-based approach effectively captures both the seasonal and the diurnal variations of renewable resources and their correlation with the load seasonal and diurnal changes.

Incentives and mechanism for intermittent resources to be in the day-ahead market Optimal prices would help the power system respond to fluctuating generation from

renewable energy sources, thereby facilitating much greater penetration by such sources. Many prices in electricity markets continue to be the same across time and space within a system. Such constant prices include not just generation charges but also distribution charges, taxes, system benefit charges, stranded cost charges, a portion of transmission charges, some ancillary services, most environmental cap-and-trade permit requirements, and other nonbypassable charges. In many cases, these prices should instead vary by time and location to optimally reflect current marginal operation and maintenance cost, discourage congestion, improve reliability, reduce capacity and reserve needs, guide investment, and reduce environmental damages. In some cases, this is already possible. In other cases, it will be made possible by the expansion of real-time metering and system monitoring equipment such as phasor measurement units. The design of optimal pricing

Page 39: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

39

in other industries is a major activity of economists. We plan to develop and propose methods for computing and charging prices that vary approximately optimally over time and space, to replace current constant prices of some of the kinds mentioned above. This research constitutes optimal aggregation of load and generators (Task 3.1 in proposal) and design of market rules and pricing structures (Task 3.3 in proposal), and it potentially may encompass incentives and mechanisms for intermittent resources to be in the day-ahead market (Task 3.4 in proposal). We also plan to begin adapting a large-scale power system simulation model to be able to illustrate and estimate the effect of adopting these prices on costs and on renewable energy penetration.

We plan to continue with the incorporation of the probabilistic renewable resource models into a probabilistic simulation methodology. We will also develop the appropriate models for the time-dependent DRR and integrate into the probabilistic simulation approach. A key challenge in the development of the simulation methodology is to represent the impacts of the time varying transmission constraints on the deliverability of the electricity to the loads. Another is the effective representation of the storage plant operations with the integrated renewable and demand response resources.

3.4 Transmission grid management and operation To meet the 50% renewable penetration challenge, the transmission system of the future requires significant conceptual rethinking and physical reinforcement. Although a 10% wind penetration from scattered locations can be accommodated readily by the present transmission infrastructure, grid operators view the transmission system as being the major obstacle to further wind resource installations. In this task, we are investigating solutions to make the transmission system adaptive to new renewable generation. One objective of the transmission grid management and operation task is to assess the current grid’s ability to manage large amount of concentrated or distributed renewable resources with large amount of storages under normal daily operations and under sudden changes in the power flow associated with intermittent resources, such as shifting wind and isolation conditions. An important issue is the impact of intermittent renewables on the dynamic performance of the system. As the system changes, violations of operating constraints must be quickly assessed. We are developing methods that address modeling issues as well as the use of phasor measurements to track grid topology changes. Another important concern with this variability is the need for improved methods of visualizing the state of the transmission grid for the operators. Initial work is investigating disturbances in power systems that cause oscillations and which can be observed in measured signals throughout the network. The objective is to extract event information that can be easily understood and presented to the operator.

Wind integration impact on system dynamic performance

We have focused on investigating the impact of wind penetration on system dynamic performance. In particular, we address how system variables may deviate from prescribed values imposed by operational requirements due to the uncontrolled variability of the wind resource. In this regard, we provide an analytically tractable method, amenable for computer implementation, to assess whether certain variables of interest,

Page 40: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

40

such as system frequency and bus voltages, remain within acceptable ranges while the system is subjected to uncontrolled disturbances caused by the variability of the wind resource. This method can be used to evaluate the impact of wind power generation location and different levels of wind penetration. We have also begun modeling studies using the existing WECC transmission system.

Our future work in this vein will include a formal analysis of the limits of small-signal reachability analysis for power systems, i.e., how large can the deviations on the uncontrolled disturbance be so that the approximation of the true reach set by the reach set of the linearized model is valid. Another aspect to be investigated is whether or not the small-signal reach set upper bounds the exact reach set or on the contrary, it is not possible to make any general statements on this matter. The scalability of the proposed method to analyze larger systems also needs to be further investigated. More accurate models of the wind-based power injections will also be proposed. In this regard, wind-based power injections, instead of assuming they are an unknown-but-bounded quantity or a first order differential equation, we assume the power injected into the system from the renewable-based generation can be modeled as the output of a process, dynamic or static. In other words, this process can be governed by higher-order differential equations or algebraic equations or a combination thereof. This could allow us to also include limits on the time derivatives on wind-based power injections. We will also continue work in applying increased renewable generation scenarios to existing power grids, with work on the WECC system planned.

We plan to develop a test system based on a real power system that is suitable for integration of renewables such as solar PV systems and land-based and offshore wind plants. The test system will be used to develop methodology for investigating transmission system adequacy for renewable integrations. The study of reactive power control using FACTS controllers will continue. We will investigate the use of PMU data for real-time voltage stability analysis and control using flat-control technology. Related to this, we will work on further developing damping and frequency control design for renewable resources. We will also examine improvement in current frequency control strategies by storage components. Finally, we will develop dynamic models for renewable resources.

GPS-synchronized phasor data for power system monitoring, operation and control

The problem of tracking topology changes in the external network model has long been under investigation due to its impact on real time contingency analysis, an important application for maintaining system security. Our preliminary work uses an approach which can track line outages based on the real-time measurements from the internal system and GPS synchronized phasor data from the external system. The formulation of the problem uses the equivalent injection representation of line outages and converts the problem into an equivalent problem of tracking changes in injection pairs in the external system. An optimization problem can be set up in order to identify the most probable pair of injection changes. This is done by minimizing a norm of the difference between the observed and estimated signature of changes in injection pairs from the external system on the internal system real-time model. Simulated scenarios have shown that the

Page 41: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

41

approach may be useful when measurement scan rates are relatively faster than the rate at which the system load changes [61].

Power system visualization We have begun work on the underlying applications necessary to develop the

visualizations. In particular, disturbances in power systems cause oscillations, which can be observed in measured signals throughout the network. Research to-date examines the relationship between events in the system and the measured modal content of the oscillations. Identifying patterns or distinguishing characteristics from oscillation monitoring data is examined in the context of linear system theory and control theory. Our results show that with knowledge of the nominal modes of certain generators, it is often possible to distinguish an event at one of these generators. These results have been accepted for publication at the 2011 PowerTech Conference, which will be held in Stockholm in June 2011 [62]. Future work in this area will focus more on how the results of the other tasks in this project can best be presented to various power system audiences, including operators and engineers. A key research goal will continue to be the development of algorithms that help to extract information for the large amount of power system data.

3.5 Test and verification

The control concepts developed in the tasks 1-4 will be demonstrated in realistic power systems with various characteristics such as mix of renewable and non-renewable generation, locations of renewables, transmission system support, storage, loads, grid dispatch systems, power markets, communication infrastructure, and load management strategies. Scenarios will be developed for each system to test the efficacy of the proposed control methods and strategies. To evaluate the control methods, an integrated set of computer code will be developed; linking grid models to distribution networks to power electronic interfaces and load management systems. In terms of the task time line, these efforts need to follow on the other tasks and more effort will be placed on later years in the contract.

Power system model development We have focused on the broad modeling aspects necessary to achieve the goal of high

wind power penetration. To date the work has addressed a topic, which is extremely important in the planning, development and installation stage of these wind farms, namely collector system design. Collector systems consolidate the power generated by turbine units distributed over the geographical area of the wind farm to a substation from where the generated power is transmitted to the electric grid. The difficulty of a collector system design project is that given the wind turbine locations and the substation location where the aggregated power is transmitted to the grid, depending on the dimension of the wind farm, there may be thousands of feasible layout configurations to choose from. Choosing an optimal design from these choices can be a daunting task.

Three algorithms have been developed to automatically generate an optimal layout design for a collector system. More specifically, the developed algorithms achieve the following three functions: further improve the results of a minimum spanning tree

Page 42: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

42

algorithm by creating external splice locations separate from the wind turbine locations in computing the cable layout configuration; compute the minimum cable length layout configuration under the constraint of a prespecified maximum number of turbines connected to a feeder cable; automatically compute the direction and magnitude of power flow on the different cables and assign cable sizes accordingly. Finally, we have done a preliminary economic study that computes the cost of electricity generated in each configuration in $/kwh. A paper detailing this work is in preparation.

Power system model development

We have begun work on the development of test scenarios. The technical approach has been to start with existing models for the actual grids, and then to create reduced models that capture many of the germane aspects of these systems, but which do not disclose confidential information. We have also begun work on test systems that incorporate newer wind turbine and PV installations for transient stability applications. Associated with the effort, the PI Tom Overbye participated in the November 2010 and February 2011 meetings of the WECC Renewable Energy Modeling Task Force.

We plan to continue the development of appropriately sized power system models that represent the germane issues of the existing power grids, but are sufficiently different from the actual power grids to allow distribution to the wider power community without compromising data confidentiality.

Page 43: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

43

References [1] Energy Information Administration, Electric Power Annual, online at:

http://www.eia.doe.gov/fuelelectric.html. [2] F. Giraud and Z.M. Salemeh, “Steady-state performance of a grid-connected rooftop hybrid wind-

photovoltaic power system with battery storage,” IEEE Transactions on Energy Conversion, Vol. 16, No. 1, pp. 1-7.

[3] K. Tomsovic and M. Venkatasubramanian, “Power System Operation and Control,” Electrical Engineering Handbook, Elsevier Academic Press, 2005, pp. 761-778.

[4] K. Tomsovic, D. Bakken, V. Venkatasubramanian and A. Bose, “Designing the Next Generation of Real-Time Control, Communication and Computations for Large Power Systems,” Proceedings of the IEEE, Vol. 93, No. 5, May 2005, pp. 965- 979.

[5] Allen J. Wood, Bruce F. Wollenberg, “Power Generation Operation and Control,” John Wilely and Sons,Inc. 1996.

[6] John Undrill, “Power and Frequency Control as it Relates to Wind-Powered Generation,” LBNL Report, December 2010.

[7] P. Kundur, “Power System Stability and Control,” McGraw-Hill, Inc. 1993. [8] Michel Fliess, Jean Levine, Philippe Martin, Pierre Rouchon, “Flatness and Defect of Nonlinear

Systems: Introductory Theory and Examples,” CAS Internal Report A-284, January 1994. [9] Ph. Martin, R.M. Murry, P. Rouchon, “Flat systems, equivalence and trajectory generation,” Technical

report, April 2003. [10] M. H. Variani, Kevin Tomsovic, “Flatness-Based Automatic Generation Control with High Penetration

of Wind Energy,” to be submitted to IEEE Transactions on Power Systems. [11] P. M. Anderson, A. A. Fouad, “Power System Control and Stability,” The Iowa State University Press,

1997.  [12] NERC Resources Subcommittee, “Balancing and Frequency Control,” July 5, 2009. [13] R. Sipahi, S.-I. Niculescu, C.T. Abdallah, W. Michiels and K. Gu, “Stability and Stabilization of

Systems with Time Delay - Limitations and Opportunities,” IEEE Control Systems Magazine, Vol. 31, No. 1, Feb. 2011, pp.38-65.

[14] H. Lev-Ari, A.M. Stankovic and B. Yan, “Estimation and Control in Electric Energy Systems Based on Time-Stamped Signals,” European Control Conference (ECC), Budapest, Hungary, Aug. 2009.

[15] H. Lev-Ari, A.M. Stankovic and B. Yan, “Estimation and Control in Electric Energy Systems Based on Time-Stamped Signals,” European Control Conference (ECC), Budapest, Hungary, Aug. 2009.

[16] K. Plarre and F. Bullo, “On Kalman Filtering for Detectable Systems with Intermittent Observations,” IEEE Trans. Autom. Control, 54(2), pp. 386-390, Feb. 2009.

[17] B. Yan, H. Lev-Ari and A.M. Stankovic, “Networked Estimation with Irregularly Sampled Observations,” submitted to the 2011 IEEE Conference on Decision and Control.

[18] B. Sinopoli, L. Schenato, M. Francheschetti, K. Poola, M.I. Jordan and S. Sastry, “Kalman Filtering With Intermittent Observations,” IEEE Trans. Autom. Control, 49(9), pp. 1453-1464, Sept. 2004.

[19] B. Yan, “Estimation and Control under Communication Network Constraints,” M.S. Thesis, Department of Electrical and Computer Engineering, Northeastern University, Boston, May 2010.

[20] C. Taylor, Power System Voltage Stability, ser. Power System Engineer- ing Series. McGraw-Hill, 1994.

[21] V. Ajjarapu, “Computational Techniques for Voltage Stability Assessment and Control,” Springer Science+Business Media, 2006.

[22] T. Van Cutsem and C. Vournas, “Voltage Stability of Electric Power Systems,” Kluwer Academic Publishers, 1998.

[23] A. Kurita, H. Okubo, K. Oki, S. Agematsu, D.B. Klapper, N.W. Miller, W.W. Price, Jr., J.J., Sanchez-Gasca, K.A. Wirgau, and T.D. Younkins, “Multiple time-scale power system dynamic simulation,” IEEE Trans- actions of Power Systems, vol. 8, no. 1, pp. 216–223, February 1993.

[24] North American Synchrophasor Initiative. [Online]. Available: http://www.naspi.org [25] Mostafa Parniani, Joe H. Chow, Luigi Vanfretti, Bharat Bhargava, and Armando Salazar, “Voltage

stability analysis of a multiple-infeed load center using phasor measurement data,” in IEEE PES Power Systems Conference and Exposition, 2006.

Page 44: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

44

[26] D. Julian, R. Schulz, K. Vu, W. Quaintance, N. Bhatt, and D. Novosel, “Quantifying Proximity to Voltage Collapse using the Voltage Instability Predictor (VIP),” in IEEE Power Engineering Society Summer Meeting,, 2000, vol. 2, pp. 931–936.

[27] S. G. Ghiocel, J. H. Chow, G. Stefopoulos, B. Fardanesh, D. B. Bertagnolli, and M. Swider, “A Voltage Sensitivity Study on a Power Transfer Path using Synchrophasor Data,” accepted for presentation at the 2011 IEEE PES GM.

[28] A.M. Stankovic, S.R. Sanders, T. Aydin, “Dynamic Phasors in Analysis of Unbalanced Polyphase AC Machines” IEEE Trans. on Energy Conversion, Vol. 17, No. 1, pp. 107-113, March 2002.

[29] H. Lev-Ari, A.M. Stankovic and A. Ghanavati, “Dynamic Decomposition of Apparent Power in Polyphase Unbalanced Networks with Application to Transients in an Industrial Load,” 40-th North American Power Symposium, Calgary, Canada, Sept. 2008.

[30] A.A. Kardenas, S. Amin, S. Sastry, “Research Challenges in the Security of Control Systems”, Proceedings of the 3rd ACM Conference on hot topics in security, San Jose, CA Article No. 6, 2008.

[31] H. Akagi, Y. Kanazawa and A. Nabae, “Instantaneous Reactive Power Compensators comprising Switching Devices without Energy Storage Components,” IEEE Trans. Ind. Appl., Vol. 20, 2004, pp. 625-630.

[32] H. Lev-Ari and A.M. Stankovic, “Phasor-Banks: Customizable Filter Banks for Robust Dynamic Time-Frequency Analysis,” 40th North American Power Symposium, Calgary, Canada, Sept. 2008.

[33] M. Radmehr, S. Farhangi and A. Nasiri, “The Power of Paper,” IEEE Industry Applications Magazine, Sept./Oct. 2007, pp. 38-48.

[34] R.D. Hernandez, H. Lev-Ari, A.M. Stankovic and E.A. Marengo, “Adaptive Near-Optimal Compensation in Lossy Polyphase Power Systems,” 41st North American Power Symposium, Starkville, MS, Oct. 2009.

[35] F.H. Magnano and A. Abur, “Fault Location Using Wavelets,” IEEE Trans. Power Delivery, 13(4), pp. 1475-1480, Oct. 1998.

[36] M. Korkali and A. Abur, “Fault Location in Meshed Power Networks Using Synchronized Measurements,” Proc. 42nd North American Power Symposium (NAPS), Arlington, TX, Sep. 26-28, 2010.

[37] M. Fasugba and P. Krein, "Gaining vehicle to grid benefits with unidirectional electric and plug-in hybrid vehicle chargers," submitted to IEEE Vehicle Power and Propulsion Conference, 2011.

[38] M. Fasugba and P. Krein, "Cost benefits and vehicle-to-grid regulation services of unidirectional charging of electric vehicles," submitted to IEEE Energy Conversion Congress (ECCE), 2011.

[39] L. M. Tolbert, F. Z. Peng, “Multilevel converters as a utility interface for renewable energy systems,” IEEE Power Engineering Society Summer Meeting, Seattle, Washington, Jul. 2000, pp. 1271-1274.

[40] F. Filho, Y. Cao, and L. M. Tolbert, “11-level cascaded H-bridge grid-tied inverter interface with solar panels,” in Proc. 2010 Applied Power Electronics Conference and Exposition (APEC), Feb. 2010, pp. 968-972.

[41] J. Rodriguez, J. S. Lai, and F. Z. Peng, “Multilevel inverters: A survey of topologies, controls, and applications,” IEEE Trans. Ind. Electron., vol. 49, no. 4, pp. 724-738, Aug. 2002.

[42] Y. Xu, L. M. Tolbert, J. N. Chiasson, F. Z. Peng, and J. B. Campbell, “Generalized instantaneous nonactive power theory for STATCOM,” IET Electric Power Applications, vol. 1, no. 6, Nov. 2007, pp. 853-861.

[43] M. Ilic and J. Zaborszky, “Dynamics and Control of Large Electric Power Systems,” John Wiley & Sons, Inc., 2000.

[44] S. R. Sanders, J. M. Noworolski, X. Z. Xu, and G. C. Verghese, “Generalized averaging method for power conversion circuits,” IEEE Trans. Power Electron., vol. 6, pp. 251-259, Apr. 1991.

[45] J. Sun, Z. Bing, and K. Karimi, “Input impedance modeling of multipulse rectifiers by harmonic linearization,” IEEE Trans. Power Electron., vol. 24, no. 12, pp. 2812-2820, December 2009.

[46] Z. Bing and J. Sun, “Modeling and analysis of line-frequency converters by double-Fourier series methods,” in Proceedings of IEEE 2010 Workshop on Control and Modeling for Power Electronics (COMPEL 2010), June 2010.

[47] J. Sun, “Small-signal methods for ac distributed power systems – a review,” IEEE Trans. Power Electron., vol. 24, no. 11, pp. 2545-2554, November 2009.

[48] X. Chen and J. Sun, “A study of renewable energy system harmonic resonance based on a DG test-bed,” in Proceedings of IEEE 2011 Applied Power Electronics Conference, pp. 995-1002, March 2011, Ft. Worth, TX.

Page 45: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

45

[49] S. Bozhko, et al., “STATCOM-controlled HVDC power transmission for large offshore wind farms: engineering issues,” in Proceedings of 2006 IEEE Annual Conference on Industrial Electronics (IECON 2006), pp. 4219-4224.

[50] Y. Xu, F. Li and K. Tomsovic, “Adaptive Control Approach for STATCOM to Enhance Voltage Stability,” submitted to IEEE Transactions on Power Delivery.

[51] W. G. Wood, “Spinning Reserve Constrained Static and Dynamic Economic Dispatch,” Power Apparatus and Systems, IEEE Transactions on , vol.PAS-101, no.2, pp.381-388, Feb. 1982.

[52] L.T. Anstine, R.E. Burke, J.E. Casey, R. Holgate,R.S. John and H.G. Stewart, “Application of Probability Methods to the Determination of Spinning Reserve Requirements for the Pennsylvania-New Jersey-Maryland Interconnection,” Power Apparatus and Systems, IEEE Transactions on , vol.82, no.68, pp.726-735, Oct. 1963.

[53] L. Söder, “Reserve margin planning in a wind-hydro-thermal power system,” Power Systems, IEEE Transactions on , vol.8, no.2, pp.564-571, May 1993

[54] S. Persaud, B. Fox and D. Flynn, “Effects of Large Scale Wind Power on Total System Variability and Operation: Case Study of Northern Ireland,” Wind Eng., vol. 27, pp. 3-20, 2003.

[55] R. Doherty and M. O'Malley, “A new approach to quantify reserve demand in systems with significant installed wind capacity,” Power Systems, IEEE Transactions on , vol.20, no.2, pp. 587- 595, May 2005.

[56] F. Bouffard and F.D. Galiana, “An electricity market with a probabilistic spinning reserve criterion,” Power Systems, IEEE Transactions on , vol.19, no.1, pp. 300- 307, Feb. 2004.

[57] F. Bouffard and F.D. Galiana, “Stochastic Security for Operations Planning With Significant Wind Power Generation,” Power Systems, IEEE Transactions on , vol.23, no.2, pp.306-316, May 2008.

[58] M. Ortega-Vazquez and D. Kirschen, “Optimizing the spinning reserve requirements using a cost/benefit analysis,” Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE , vol., no., pp.1, 20-24 July 2008.

[59] M. Ortega-Vazquez and D. Kirschen, “Estimating the Spinning Reserve Requirements in Systems With Significant Wind Power Generation Penetration,” Power Systems, IEEE Transactions on , vol.24, no.1, pp.114-124, Feb. 2009.

[60] R. Billinton and R. N. Allan, “Reliability Evaluation of Power Systems,” London, U.K.: Plenum, 1996. [61] R. Emami and A. Abur, “Identifying External Network Branch Status Errors Using Synchronized

Phasor Measurements”, submitted to the IEEE PES General Meeting, July 25-29, 2011, Detroit. [62] K. M. Rogers, T. J. Overbye, "Application of Oscillation Monitoring Data for the Detection of Event

Signatures," accepted to PowerTech 2011, Trondheim, Norway, June 2011.

Page 46: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

46

Publications (from this project) [1] B. Yan, H. Lev-Ari and A.M. Stankovic, “Networked Estimation with Irregularly Sampled

Observations,” submitted to the 2011 IEEE Conference on Decision and Control. [2] S. G. Ghiocel, J. H. Chow, G. Stefopoulos, B. Fardanesh, D. B. Bertagnolli, and M. Swider, “A

Voltage Sensitivity Study on a Power Transfer Path using Synchrophasor Data,” has been accepted for presentation at the 2011 IEEE PES GM.

[3] M. Fasugba and P. Krein, "Gaining vehicle to grid benefits with unidirectional electric and plug-in hybrid vehicle chargers," submitted to IEEE Vehicle Power and Propulsion Conference, 2011.

[4] M. Fasugba and P. Krein, "Cost benefits and vehicle-to-grid regulation services of unidirectional charging of electric vehicles," submitted to IEEE Energy Conversion Congress (ECCE), 2011.

[5] R. Hernandez, H. Lev-Ari and A.M. Stankovic, “Adaptive Near-Optimal Compensation Applied to Linear and Nonlinear Loads,” submitted to the 43rd North American Power Symposium, Boston, MA, 2011.

[6] H. Lev-Ari and A.M. Stankovic, “Customized Dynamic Phasors for Power Quality Control in Electric Grids,” submitted to a special session on “Signal Processing Techniques for Smart Grids” in the 4th International Workshop on Computational Advances in Multi-Sensor Adaptive Processing, San Juan, Puerto Rico, 2011.

[7] P. Argyropoulos, and H. Lev-Ari, “Customized Wavelets for Fault Location in Power Systems,” submitted to the 43rd North American Power Symposium, Boston, MA, 2011.

[8] Korkali, M. and Abur, A., “Transmission System Fault Location Using Limited Number of Synchronized Recorders”, submitted to International Conference on Power System Transients, June 11-14, 2011, Delft, Netherlands.

[9] Y. Xu, F. Li and K. Tomsovic, “Adaptive Control Approach for STATCOM to Enhance Voltage Stability,” submitted to IEEE Transactions on Power Delivery.

[10] M. H. Variani and Kevin Tomsovic, “Flatness-Based Automatic Generation Control with High Penetration of Wind Energy”, to be submitted to IEEE Transactions on Power Systems.

[11] K. M. Rogers, T. J. Overbye, "Application of Oscillation Monitoring Data for the Detection of Event Signatures," accepted to PowerTech 2011, Trondheim, Norway, June 2011.

[12] Yanli Wei, Fangxing Li, and Kevin Tomsovic, “Impact to the Volatility of Electricity Price under High-Penetration Wind Power,” IET Renewable Power Generation, under review.

[13] Fangxing Li and Yanli Wei, “A Probability-Driven Multilayer Framework for Scheduling Intermittent Renewable Energy,” IEEE Transactions on Sustainable Energy, under review.

Page 47: Scalable and flat controls for reliable power grid ... · New power electronic functionality, both at the source and load, allow improved stability and voltage control. ... constrained

47

Contact information Faculty

Ali Abur: [email protected] Joe Chow: [email protected] Alejandro Dominguez-Garcia: [email protected] George Gross: [email protected] Philip Krein: [email protected] Hanoch Lev-Ari: [email protected] Fran Li: [email protected] Thomas Overbye: [email protected] Peter W. Sauer: [email protected] Aleksandar Stankovic: [email protected] Daniel Shawhan: [email protected] Jian Sun: [email protected] Leon Tolbert: [email protected] Kevin Tomsovic: [email protected] Students

Dimitra Apostolopoulou: [email protected] Paraskevas Argyropoulos: [email protected] Yannick Degeilh: [email protected] McDavis Fasugba: [email protected] Scott Ghiocel: [email protected] Ronald Hernandez: [email protected] Justin Hughes: [email protected] Mert Korkali: [email protected] Andrew Kindle: [email protected] Guodong Liu: [email protected] Hanchao Liu, [email protected] Alex Melhorn: [email protected] Maryam H Variani: [email protected] Bailu Xiao: [email protected] Yao Xu: [email protected] Bei Yan: [email protected]