10
2-wire programmable transmitter 5331A RTD, TC, Ohm, or mV input Extremely high measurement accuracy 1.5 kVAC galvanic isolation Programmable sensor error value For DIN form B sensor head mounting Applications Application Linearized temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or TC sensor. Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors. Amplification of a bipolar mV signal to a standard 4...20 mA current signal. Technical characteristics Within a few seconds the user can program PR5331A to measure temperatures within all ranges defined by the norms. The RTD and resistance inputs have cable compensation for 2-, 3- and 4-wire connection. Continuous check of vital stored data for safety reasons. Mounting / installation For DIN form B sensor head or DIN rail mounting with the PR fitting type 8421. This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

2-wire programmable transmitter

5331ARTD, TC, Ohm, or mV input–Extremely high measurement accuracy–1.5 kVAC galvanic isolation–Programmable sensor error value–For DIN form B sensor head mounting–

ApplicationsApplication

Linearized temperature measurement with Pt100...Pt1000,Ni100...Ni1000, or TC sensor.

Conversion of linear resistance variation to a standard analogcurrent signal, for instance from valves or Ohmic levelsensors.

Amplification of a bipolar mV signal to a standard 4...20 mAcurrent signal.

Technical characteristicsWithin a few seconds the user can program PR5331A tomeasure temperatures within all ranges defined by the norms.

The RTD and resistance inputs have cable compensation for2-, 3- and 4-wire connection.

Continuous check of vital stored data for safety reasons.•

Mounting / installationFor DIN form B sensor head or DIN rail mounting with the PRfitting type 8421.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Page 2: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

5331A-032218

Environmental ConditionsOperating temperature................................... -40°C to +85°CCalibration temperature................................. 20...28°CRelative humidity............................................ < 95% RH (non-cond.)Protection degree (encl./terminal).................. IP68 / IP00

Mechanical specificationsDimensions.................................................... Ø 44 x 20.2 mmWeight approx................................................ 50 gWire size........................................................ 1 x 1.5 mm2 stranded wireScrew terminal torque.................................... 0.4 NmVibration......................................................... IEC 60068-2-62...25 Hz......................................................... ±1.6 mm25...100 Hz..................................................... ±4 g

Common specificationsSupplySupply voltage............................................... 7.2...35 VDCInternal power dissipation.............................. 25 mW…0.8 W

Isolation voltageIsolation voltage, test /working........................................................... 1.5 kVAC / 50 VAC

Response timeResponse time (programmable).................... 1...60 s

Voltage drop................................................... 7.2 VDCWarm-up time................................................. 5 min.Programming................................................. Loop LinkSignal / noise ratio......................................... Min. 60 dBEEprom error check....................................... < 3.5 sAccuracy........................................................ Better than 0.05% of selected

rangeSignal dynamics, input................................... 20 bitSignal dynamics, output................................. 16 bitEffect of supply voltage change..................... < 0.005% of span / VDCEMC immunity influence................................ < ±0.5% of spanExtended EMC immunity: NAMURNE21, A criterion, burst.................................. < ±1% of span

Input specificationsCommon input specificationsMax. offset...................................................... 50% of selected max. value

RTD inputRTD type........................................................ Pt100, Ni100, lin. RCable resistance per wire.............................. 5 Ω (max.)Sensor current............................................... Nom. 0.2 mAEffect of sensor cable resistance(3-/4-wire)....................................................... < 0.002 Ω / ΩSensor error detection................................... Yes

Linear resistance inputLinear resistance min....max.......................... 0 Ω...5000 Ω

TC inputThermocouple type........................................ B, E, J, K, L, N, R, S, T, U,

W3, W5, LRCold junction compensation(CJC).............................................................. < ±1.0°CSensor error detection................................... YesSensor error current: Whendetecting / else............................................... Nom. 33 μA / 0 μA

Voltage inputMeasurement range....................................... -12...800 mV

Min. measurement range (span).................... 5 mVInput resistance.............................................. 10 MΩ

Output specificationsCurrent outputSignal range................................................... 4…20 mAMin. signal range............................................ 16 mALoad (@ current output)................................. ≤ (Vsupply - 7.2) / 0.023 [Ω]Load stability.................................................. ≤ 0.01% of span / 100 ΩSensor error indication................................... Programmable 3.5…23 mANAMUR NE43 Upscale/Downscale............... 23 mA / 3.5 mA

Common output specificationsUpdating time................................................. 440 ms

of span........................................................... = of the presently selectedrange

I.S. / Ex markingATEX.............................................................. II 3 G Ex nA [ic] IIC T4...T6

Gc, II 3 G Ex ic IIC T4...T6 Gc,II 3 D Ex ic IIIC Dc

IECEx............................................................. Ex nA [ic] IIC T4...T6 Gc, Ex icIIC T4...T6 Gc, Ex ic IIIC Dc

Observed authority requirementsEMC............................................................... 2014/30/EURoHS.............................................................. 2011/65/EUEAC................................................................ TR-CU 020/2011

ApprovalsDNV-GL Marine............................................. Stand. f. Certific. No. 2.4ATEX 2014/34/EU.......................................... KEMA 10ATEX0002 XIECEx............................................................. DEK 13.0035XINMETRO....................................................... DEKRA 13.0001 XCCOE............................................................. P337392/1

Page 3: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

2-wire programmable transmitter

5333ARTD or Ohm input–High measurement accuracy–3-wire connection–Programmable sensor error value–For DIN form B sensor head mounting–

ApplicationsApplication

Linearized temperature measurement with Pt100...Pt1000 orNi100...Ni1000 sensor.

Conversion of linear resistance variation to a standard analogcurrent signal, for instance from valves or Ohmic levelsensors.

Technical characteristicsWithin a few seconds the user can program PR5333A tomeasure temperatures within all RTD ranges defined by thenorms.

The RTD and resistance inputs have cable compensation for3-wire connection.

Mounting / installationFor DIN form B sensor head or DIN rail mounting with the PRfitting type 8421.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Page 4: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

5333A-100318

Environmental ConditionsOperating temperature................................... -40°C to +85°CCalibration temperature................................. 20...28°CRelative humidity............................................ < 95% RH (non-cond.)Protection degree (encl./terminal).................. IP68 / IP00

Mechanical specificationsDimensions.................................................... Ø 44 x 20.2 mmWeight approx................................................ 50 gWire size........................................................ 1 x 1.5 mm2 stranded wireScrew terminal torque.................................... 0.4 NmVibration......................................................... IEC 60068-2-62...25 Hz......................................................... ±1.6 mm25...100 Hz..................................................... ±4 g

Common specificationsSupplySupply voltage............................................... 8.0...35 VDCInternal power dissipation.............................. 25 mW…0.8 W

Response timeResponse time (programmable).................... 0.33...60 s

Voltage drop................................................... 8.0 VDCWarm-up time................................................. 5 min.Programming................................................. Loop LinkSignal / noise ratio......................................... Min. 60 dBAccuracy........................................................ Better than 0.1% of sel. rangeSignal dynamics, input................................... 19 bitSignal dynamics, output................................. 16 bitEffect of supply voltage change..................... < 0.005% of span / VDCEMC immunity influence................................ < ±0.5% of span

Input specificationsCommon input specificationsMax. offset...................................................... 50% of selected max. value

RTD inputRTD type........................................................ Pt100, Ni100, lin. RCable resistance per wire.............................. 10 Ω (max.)Sensor current............................................... > 0.2 mA, < 0.4 mAEffect of sensor cable resistance(3-wire)........................................................... < 0.002 Ω / ΩSensor error detection................................... Yes

Linear resistance inputLinear resistance min....max.......................... 0 Ω...10000 Ω

Output specificationsCurrent outputSignal range................................................... 4…20 mAMin. signal range............................................ 16 mALoad (@ current output)................................. ≤ (Vsupply - 8) / 0.023 [Ω]Load stability.................................................. ≤ 0.01% of span / 100 ΩSensor error indication................................... Programmable 3.5…23 mANAMUR NE43 Upscale/Downscale............... 23 mA / 3.5 mA

Common output specificationsUpdating time................................................. 135 ms

of span........................................................... = of the presently selectedrange

Observed authority requirementsEMC............................................................... 2014/30/EUEAC................................................................ TR-CU 020/2011

ApprovalsATEX 2014/34/EU.......................................... KEMA 10ATEX0003 XIECEx............................................................. DEK 13.0036XINMETRO....................................................... DEKRA 13.0002 XCCOE............................................................. P337392/3DNV-GL Marine............................................. Stand. f. Certific. No. 2.4

Page 5: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

2-wire transmitter with HART protocol

5335ARTD, TC, Ohm, or mV input–Extremely high measurement accuracy–HART 5 protocol–Programmable sensor error value–For DIN form B sensor head mounting–

ApplicationsApplication

Linearized temperature measurement with Pt100...Pt1000,Ni100...Ni1000, or TC sensor.

Difference or average temperature measurement of 2resistance or TC sensors.

Conversion of linear resistance variation to a standard analogcurrent signal, for instance from valves or Ohmic levelsensors.

Amplification of a bipolar mV signal to a standard 4...20 mAcurrent signal.

Connection of up to 15 transmitters to a digital 2-wire signalwith HART communication.

Technical characteristicsWithin a few seconds the user can program PR5335A tomeasure temperatures within all ranges defined by the norms.

The RTD and resistance inputs have cable compensation for2-, 3- and 4-wire connection.

The 5335A has been designed according to strict safetyrequirements and is therefore suitable for application in SIL 2installations.

Continuous check of vital stored data for safety reasons.•Sensor error detection according to the guidelines in NAMURNE89.

Mounting / installationFor DIN form B sensor head or DIN rail mounting with the PRfitting type 8421.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Page 6: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

5335A-102618

Environmental ConditionsOperating temperature................................... -40°C to +85°CCalibration temperature................................. 20...28°CRelative humidity............................................ < 95% RH (non-cond.)Protection degree (encl./terminal).................. IP68 / IP00

Mechanical specificationsDimensions.................................................... Ø 44 x 20.2 mmWeight approx................................................ 50 gWire size........................................................ 1 x 1.5 mm2 stranded wireScrew terminal torque.................................... 0.4 NmVibration......................................................... IEC 60068-2-62...25 Hz......................................................... ±1.6 mm25...100 Hz..................................................... ±4 g

Common specificationsSupplySupply voltage............................................... 8.0...35 VDC

Isolation voltageIsolation voltage, test /working........................................................... 1.5 kVAC / 50 VAC

Response timeResponse time (programmable).................... 1...60 s

Warm-up time................................................. 30 sProgramming................................................. Loop Link & HARTSignal / noise ratio......................................... Min. 60 dBAccuracy........................................................ Better than 0.05% of selected

rangeSignal dynamics, input................................... 22 bitSignal dynamics, output................................. 16 bitEffect of supply voltage change..................... < 0.005% of span / VDCEMC immunity influence................................ < ±0.1% of spanExtended EMC immunity: NAMURNE21, A criterion, burst.................................. < ±1% of span

Input specificationsCommon input specificationsMax. offset...................................................... 50% of selected max. value

RTD inputRTD type........................................................ Pt100, Ni100, lin. RCable resistance per wire.............................. 5 Ω (up to 50 Ω per wire is

possible with reducedmeasurement accuracy)

Sensor current............................................... Nom. 0.2 mAEffect of sensor cable resistance(3-/4-wire)....................................................... < 0.002 Ω / ΩSensor error detection................................... Yes

TC inputThermocouple type........................................ B, E, J, K, L, N, R, S, T, U,

W3, W5Cold junction compensation(CJC).............................................................. < ±1.0°CSensor error detection................................... YesSensor error current: Whendetecting / else............................................... Nom. 33 μA / 0 μA

Voltage inputMeasurement range....................................... -800...+800 mVMin. measurement range (span).................... 2.5 mVInput resistance.............................................. 10 MΩ

Output specificationsCurrent outputSignal range................................................... 4…20 mAMin. signal range............................................ 16 mALoad (@ current output)................................. ≤ (Vsupply - 8) / 0.023 [Ω]Load stability.................................................. ≤ 0.01% of span / 100 ΩSensor error indication................................... Programmable 3.5…23 mANAMUR NE43 Upscale/Downscale............... 23 mA / 3.5 mA

of span........................................................... = of the presently selectedrange

Observed authority requirementsEMC............................................................... 2014/30/EUEAC................................................................ TR-CU 020/2011

ApprovalsATEX 2014/34/EU.......................................... KEMA 03ATEX1508 XIECEx............................................................. KEM 10.0083XINMETRO....................................................... DEKRA 18.0002XDNV-GL Marine............................................. Stand. f. Certific. No. 2.4SIL.................................................................. Hardware assessed for use in

SIL applications

Page 7: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

2-wire HART 7 temperature transmitter

5437ARTD, TC, potentiometer, linear resistance and bipolar mV input–Single or true dual inputs with sensor redundancy and drift detection–Wide ambient operating temperature of -50 to +85°C–Total accuracy from 0.014%*, long-term stability <0.05% per year–2.5 kVAC galvanic isolation–Full assessment to IEC61508 : 2010 for use in SIL 2/3 applications–

ApplicationsApplication

Temperature measurement of a wide range of TC and RTDtypes.

Conversion of wide span linear resistance and potentiometerinputs.

Conversion of bipolar mV signals to 4...20 mA.•Integration into asset management schemes.•Critical applications requiring superior accuracy and/or sensorredundancy and drift detection.

Technical characteristicsTrue dual input transmitter. High density 7-terminal designaccepts the widest range of dual input combinations.

Sensor redundancy - output automatically switches tosecondary sensor in event of primary sensor failure,maintaining uptime.

Sensor drift detection - alerts when sensor differentialexceeds user-defined limits, for maintenance optimization.

Dynamic variable mapping for process data in addition to theprimary variable e.g. dual input features such as average,differential and min./max. tracking.

Groundbreaking digital and analog signal accuracy over fullinput span and ambient conditions.

Extensive sensor matching including Callendar Van Dusenand custom linearizations.

Programmable input limits and runtime metering ensuremaximum process traceability and sensor out of rangeprotection.

IEC 61508 : 2010 full certification up to SIL 3 together withenhanced EMC Functional Safety testing to IEC 61236-3-1.

Meets NAMUR NE21, NE43, NE44, NE89 and NE107compliant diagnostics information.

Mounting / installationFor DIN form B sensor head mounting.•Configuration via standard HART communication interfaces orby PR 5909 Loop Link.

The 5437A can be mounted in zone 2 and 22 / Class I,Division 2, Groups A, B, C, D.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Page 8: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

5437A-111418

Environmental ConditionsOperating temperature................................... -50°C to +85°C (standard)Operating temperature................................... -40°C to +80°C (SIL)Storage temperature...................................... -50°C to +85°CCalibration temperature................................. 23...25°CRelative humidity............................................ < 99% RH (non-cond.)Protection degree (encl./terminal).................. IP68 / IP00

Mechanical specificationsDimensions.................................................... Ø 44 x 20.2 mmCenter hole diameter..................................... Ø 6.35 mm / ¼ inWeight approx................................................ 50 gWire size........................................................ 1 x 1.5 mm2 stranded wireScrew terminal torque.................................... 0.4 NmVibration......................................................... IEC 60068-2-62...25 Hz......................................................... ±1.6 mm25...100 Hz..................................................... ±4 g

Common specificationsSupplySupply voltage............................................... 7.5*...48** VDCInternal power dissipation.............................. ≤ 850 mWAdditional min. supply voltagewhen using test terminals.............................. 0.8 VMin. load resistance at >37V supply......................................................... (Vsupply – 37) / 23 mA

Isolation voltageIsolation voltage, test /working........................................................... 2.5 kVAC / 55 VAC

Response timeResponse time............................................... 70 msProgrammable damping................................. 0...60 s

Polarity protection.......................................... All inputs and outputsWrite protection.............................................. Jumper or softwareWarm-up time................................................. < 5 min.Start-up time................................................... < 2.75 sProgramming................................................. Loop Link & HARTSignal / noise ratio......................................... > 60 dBLong-term stability, betterthan................................................................ ±0.05% of span / year

(±0.18% of span / 5 years)Signal dynamics, input................................... 24 bitSignal dynamics, output................................. 18 bitEffect of supply voltage change..................... < 0.005% of span / VDCAccuracy........................................................ See manual for detailsEMC immunity influence................................ < ±0.1% of spanExtended EMC immunity: NAMURNE21, A criterion, burst.................................. < ±1%

Input specificationsRTD inputRTD type........................................................ Pt10...10000, Ni10...10000,

Cu5...1000Cable resistance per wire.............................. 50 Ω (max.)Effect of sensor cable resistance(3-/4-wire)....................................................... < 0.002 Ω / ΩSensor current............................................... < 0.15 mASensor error detection................................... None, Shorted, Broken,

Shorted or Broken

TC inputThermocouple type........................................ B, E, J, K, L, N, R, S, T, U,

W3, W5, LR

Cold junction compensation(CJC).............................................................. Constant, internal or external

via a Pt100 or Ni100 sensorSensor error detection................................... None, Shorted, Broken,

Shorted or Broken

Linear resistance inputMeasurement range / min. range(span)............................................................. 0 Ω...100 kΩ / 25 ΩCable resistance per wire(max.)............................................................. 50 ΩSensor current............................................... < 0.15 mASensor error detection................................... None, Broken

Potentiometer inputPotentiometer min....max............................... 10 Ω...100 kΩMeasurement range / min. range(span)............................................................. 0...100% / 10%Cable resistance per wire(max.)............................................................. 50 ΩSensor current............................................... < 0.15 mASensor error detection................................... None, Shorted, Broken,

Shorted or Broken

mV inputMeasurement range....................................... -800...+800 mV (bipolar)Measurement range....................................... -100 to 1700 mVMin. measurement range (span).................... 2.5 mVInput resistance.............................................. 10 MΩSensor error detection................................... None, Broken

Output specificationsCommon output specificationsNormal range, programmable........................ 3.8...20.5 / 20.5...3.8 mAExtended range (output limits),programmable................................................ 3.5...23 / 23...3.5 mAUpdating time................................................. 10 msLoad (@ current output)................................. ≤ (Vsupply -7.5)/0.023 [Ω]Load stability.................................................. < 0.01% of span / 100 ΩSensor error indication................................... Programmable 3.5…23 mANAMUR NE 43 Upscale/Downscale.............. > 21 mA / < 3.6 mA

HART protocol revisions................................ HART 7 and HART 5

Observed authority requirementsEMC............................................................... 2014/30/EURoHS.............................................................. 2011/65/EUEAC................................................................ TR-CU 020/2011

ApprovalsATEX 2014/34/EU.......................................... DEKRA 16ATEX0047XIECEx............................................................. IECEx DEK. 16.0029XCSA................................................................ 70066266FM.................................................................. FM16US0287X /

FM16CA0146XINMETRO....................................................... DEKRA 16.0008XNEPSI............................................................ GYJ18.1054XEAC Ex TR-CU 012/2011.............................. RU C-DK.GB.98.V.00192SIL.................................................................. SIL 2 / SIL 3 certified & fully

assessed acc. to IEC 61508

NB* / **................................................................ See manual for details

Page 9: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

Field mounted HART temperature transmitter

7501RTD, TC, Ohm, and bipolar mV input and analog output–High definition local operator interface (LOI) with 3 optical buttons–Selectable red or white backlight–Ex d explosion proof / flame proof in aluminum or 316 stainless steelversion

HART 7 functionality with HART 5 compatibility–

ApplicationsHigh defintion display

0, 90, 180, & 270 degree position adjustments.•Monitoring, programming and diagnostics view.•Extensive diagnostics with flashing red or white backlight•Supports 7 languages.•

Local operator interface (LOI)3 optical buttons; up, down and enter.•Dynamically adaptive to wear or accumulation of dirt.•Immune to interference from ambient light sources.•Useable with or without gloves.•

ConfigurationFrom the LOI through PR guided menu.•PReset and HART modem.•HHC, DCS or AMS via HART.•

Mounting / installationFor installation in zone 0, 1, 2 and zone 20, 21, 22 and inClass 1, Division 1 and 2 applications.

Hardware assessed for use in SIL 2 applications.•Mounting on 1.5”–2” pipe bracket or on wall / bulkhead.•

ApplicationLinearized temperature measurement with TC and RTDsensors e.g. Pt100 and Ni100.

HART communication and 4...20 mA analog PV output forindividual, difference or average temperature measurement ofup to two RTD or TC input sensors.

Conversion of linear resistance to a standard analog currentsignal, e.g from valves or Ohmic level sensors.

Amplification of bipolar mV signals to standard 4...20 mAcurrent signals.

Up to 63 transmitters (HART 7) can be connected in amultidrop communication setup.

Technical characteristicsNAMUR NE43 and NE89.•HART protocol revision can be changed by user configurationto either HART 5 or HART 7 protocol.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

Page 10: Sandelius Model PR5331 · 2019. 2. 16. · E -148 to 1832°F / -100 to 1000°C 90 / 50 IEC 584 J -148 to 2192°F / -100 to 1200°C 90 / 50 IEC 584 K -292 to 2501°F / -180 to 1372°C

7501-092818

Environmental ConditionsOperating temperature................................... -40°C to +85°C (with silicone

O-ring)Operating temperature................................... -20°C to +85°C (with FKM O-

ring)Storage temperature...................................... -40°C to +85°CCalibration temperature................................. 20...28°CRelative humidity............................................ 0...100% RH (condensing)Protection degree........................................... IP54 / IP66 / IP68 / type 4X

Mechanical specificationsDimensions.................................................... Ø 110 mmDimensions (HxWxD), aluminum................... 109.3 x 145 x 126 mmDimensions (HxWxD), stainlesssteel................................................................ 107.4 x 145 x 124 mmWeight approx., aluminum /stainless steel................................................ 1.3 / 2.8 kgWire size........................................................ 0.13 x1.5 mm2 / AWG 26...16

stranded wireScrew terminal torque.................................... 0.4 NmVibration......................................................... IEC 60068-2-62...25 Hz......................................................... ±1.6 mm25...100 Hz..................................................... ±4 gDisplay resolution........................................... 96 x 64 pixelsNumber of digits............................................. 5Backlight......................................................... Selectable ON/OFFBacklight color................................................ Selectable white or red

Common specificationsSupplySupply voltage, DC: Ex ia,intrinsically safe.............................................. 10 (12 - with backlight)...30

VDCSupply voltage, DC: Other............................. 10 (12 - with backlight)...35

VDC

Isolation voltageIsolation voltage, test /working........................................................... 1.5 kVAC / 50 VAC

Response timeResponse time (programmable).................... 1...60 s

Signal / noise ratio......................................... > 60 dBProgramming................................................. HARTStart-up time, transmitterto display........................................................ Max. 5 sLong-term stability, betterthan................................................................ ±0.1% of span / yearAccuracy........................................................ Better than 0.05% of selected

rangeSignal dynamics, input................................... 22 bitSignal dynamics, output................................. 16 bitEMC immunity influence................................ < ±0.1% of spanExtended EMC immunity: NAMURNE21, A criterion, burst.................................. < ±1% of span

Input specificationsCommon input specificationsMax. offset...................................................... 50% of selected max. value

RTD inputRTD type........................................................ Pt50/100/200/500/1000;

Ni50/100/120/1000Cable resistance per wire.............................. 5 Ω (up to 50 Ω per wire is

possible with reducedmeasurement accuracy)

Sensor current............................................... Nom. 0.2 mA

Linear resistance inputLinear resistance min....max.......................... 0 Ω...7000 Ω

TC inputThermocouple type........................................ B, E, J, K, L, N, R, S, T, U,

W3, W5, LRCold junction compensation(CJC).............................................................. Constant, internal or external

via a Pt100 or Ni100 sensor

Voltage inputMeasurement range....................................... -800...+800 mVMin. measurement range (span).................... 2.5 mVInput resistance.............................................. 10 MΩ

Output specificationsCurrent outputSignal range................................................... 4…20 mAMin. signal range............................................ 16 mALoad (@ current output)................................. ≤ (Vsupply - 10) / 0.023 [Ω]Load resistance, with backlight...................... ≤ (Vsupply - 12) / 0.023 [Ω]Sensor error indication................................... Programmable 3.5…23 mANAMUR NE43 Upscale/Downscale............... 23 mA / 3.5 mA

Common output specificationsUpdating time................................................. 440 ms

HART protocol revisions................................ HART 7 and HART 5

Observed authority requirementsEMC............................................................... 2014/30/EUEAC................................................................ TR-CU 020/2011

ApprovalsEU RO Mutual Recognition TypeApproval......................................................... MRA0000009ATEX 2014/34/EU.......................................... DEKRA 15 ATEX 0058 XIECEx............................................................. IECEx DEK 15.0039 XFM.................................................................. FM16US0009X /

FM16CA0010XCSA................................................................ 70024231EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.01316INMETRO....................................................... DEKRA 15.0014 XNEPSI............................................................ GYJ15.1336X, GYJ15.1337X

and GYJ15.1338XSIL.................................................................. Hardware assessed for use in

SIL applications