    SAG582121901System Application Guide

    Spec. No. 582121901 (Model 1231V1)Issue AH, January 26, 2009

    SYSTEM OVERVIEW

    Preface: This document provides systemapplication information on VPSDistribution Bay Model 1231V1, Spec.

    No. 582121901. The following is ageneral description of the completesystem which includes distribution baysand power bays.

    Description: A -48VDC @ up to 10,000 amperespower system (eight power bays plus amain and supplemental distribution bay,the system may contain up to threeadditional supplemental distributionbays).

    The Vortex

    product line is a complete

    integrated power system containingpower conversion, intelligent monitoring,and distribution. This Vortex

    Power

    System (VPS) typically consists of ...

    VPS Power Bays

    The VPS Power Bays (Spec. No.582121100, 582121300, 582121700,or 582122100) house the PowerConversion Units (PCUs). Thissystem can consist of one (1) toeight (8) power bays, each of whouses up to seven (7) PCUs. This

    document does not describe the VPSPower Bay. Refer to VPS PowerBay System Application GuSAG582121100, SAG582121300,SAG582121700, or SAG582122100.

    hich

    ide

    SAG582122100).

    VPS Power Conversion Units(PCUs)

    The PCUs provide load power,battery float current, and batteryrecharge current during normaloperating conditions. This documentdoes not describe the PCUs. The

    PCUs are described in the VPSPower Bay System ApplicationGuide (SAG582121100,SAG582121300, SAG582121700, or Main Bay

    Home

    Page 1 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    2/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Application

    G582121700,).

    VPS Meter-Control -Alarm(MCA) Panel

    Houses the MCA. The MCAcontrols the operation of up to fifty-six (56) PCUs and providessystem metering, control, andalarm functions. The MCA islocated in the main VPSDistribution Bay. This documentdoes not describe the MCA. TheMCA is described in the VPSPower Bay SystemGuide (SAG582121100,SAG582121300, SAor SAG582122100

    VPS Distribution Bays

    The VPS Distribution Bay providesDC distribution through fusesand/or circuit breakers. Thesystem can consist of one (1) tofive (5) VPS Distribution Bays.

    The VPS Distribution Bays aredesigned to accept VPSdistribution bus modules and VPSbattery disconnect modules. Thedistribution bus modules provide achoice of fuse and circuit breakertypes and sizes. The batterydisconnect module provides aconnection point for a battery

    string and a battery disconnectcontactor for that battery string. Aswitch is provided to manuallyconnect or disconnect the batterystring from the system. Provisionis made for connection of anemergency shutdown and firealarm disconnect switch. Refer tothe LIST DESCRIPTIONS sectionof this document for illustrations ofthe available VPS distribution busmodules and VPS batterydisconnect module.

    This power system can consist ofup to five (5) VPS DistributionBays. One (1) main bay and up tofour (4) supplemental bays. Themain bay accepts up to six (6)modules (distribution and/orbattery disconnect). Eachsupplemental bay accepts up toeight (8) modules (distribution

    Supplemental Bay

    Home

    Page 2 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    3/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    and/or battery disconnect). The bays are split in a Side A and Side Bconfiguration. Distribution and battery disconnect modules cannot be installedon the same side of a bay. Each type may be installed on separate sides of a bay.

    Integrated LMS1000Monitoring System

    The distribution bays contain an integrated LMS1000 Monitoring System. The LMS1000Monitoring System consists of an LMS1000 Main Cabinet, optional Expansion Cabinet,and Expansion Assemblies. The LMS1000 Main Cabinet is always mounted in the mainDistribution Bay. Each distribution bay (main and supplemental) always contain twoLMS1000 Expansion Assemblies. The Expansion Assemblies are factory wired tomonitor the left and right sides of the distribution bays (all distribution shuntmeasurements, CB/FA alarms, and control fuse alarms). The LMS1000 Main Cabinet isfactory wired to the LMS1000 Expansion Assemblies in the main bay. Simple LMS1000network cable connections interconnect the supplemental bays' Expansion Assembliesback to the LMS1000 Main Cabinet. In addition, the LMS1000 Main Cabinet accepts upto ten input/output (I/O) cards of various types to monitor external points. An optionalLMS1000 Expansion Cabinet can be provided which also accepts up to ten I/O cards foradditional monitoring points. Refer to the LMS1000 System Application Guide

    (SAG586505000) for additional information.

    Family: Vortex

    Spec. No.: 582121901

    Model: 1231V1

    Output Voltage: -48 Volts DC

    Output Capacity: 5000 Amperes, maximum, per Bay(2500 Amperes, maximum, per side)

    Agency Approval: Listed UL Subject 1801 ("c UL")

    Framework Type: Seismic Rated (Zone 4) Box Framework

    Mounting Width: 31.375 Inches

    Mounting Depth: 24 Inches

    Access: Front and Rear for Installation, Front for Operation and Maintenance

    Supplemental Bay(s) Available: Four

    Control: Microprocessor

    Color: Off-White (Lorain Spec. M500-117)

    Options: Main Distribution Bay (w/o internal shunt), Supplemental DistributionBay (w/o internal shunt), Main Distribution Bay (w/ internal shunts),Supplemental Distribution Bay (w/ internal shunts), MCA Panel,Special Application MCA Panel List 25, Special Application MCAPanel List 26, LMS1000 Expansion Cabinet, Capacitor PrechargeUnit, Side Cover Panel, Blank Panel for Empty Module Position,Battery Disconnect Module, Distribution Modules,AC CourtesyPanel

    Home

    Page 3 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    4/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Accessories: Distribution Bay Overhead Busbars, Power Bay OverheadBusbars, Overhead Busbar Termination Kits, OverheadBusbar Safety Covers, Power Bays, Distribution Devices, Lugs,56-PCU Conversion Kit

    Environment: 40C

    Home

    Page 4 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    5/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Main Distribution Bay

    Distribution

    Module

    Position

    7

    Distribution

    Module

    Position

    8

    Distribution

    Module

    Position

    5

    Distribution

    Module

    Position

    6

    Distribution

    Module

    Position

    1

    Distribution

    Module

    Position

    2

    FRONT VIEWMAIN DISTRIBUTION BAY

    See "Main DistributionBay Spare FuseHolders"

    Configuration Options

    List 1: Main Distribution Bay(w/o internal shunt)

    List 11: Main Distribution Bay(w/ internal shunts)

    See "Main DistributionBay Spare Fuse

    Holders"

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    See "Main Distribution Bay19-Inch AccessoryEquipment Mounting"

    Distribution Bus

    Module (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Distribution BusModule (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Home

    Page 5 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    6/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Main Distribution Bay 19-Inch Accessory Equipment Mounting

    MCA Panel (List 21, 25,or26) (equipped withMCA RS-485 InterfaceOption, P/O List 1 or11)

    Blank Panelor

    AC Courtesy Panel(ListAC)

    GMT Fuse Panel andAudible Alarm

    PANEL LAYOUT

    (Assemblies to be mountedin positions shown, unless

    otherwise specified.)

    LMS1000 MonitoringSystem (Main Cabinet)(P/O List 1 or11)

    LMS1000 MonitoringSystem (ExpansionCabinet) (List 34)

    or Blank Panel

    Home

    Page 6 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    7/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Main Distribut ion Bay Spare Fuse Holders

    SPARE

    FUSE

    HOLDERS

    SPARE

    FUSE

    HOLDERS

    SPARE FUSEHOLDERS

    Home

    Page 7 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    8/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Supplemental Distribut ion Bay

    Distribution

    Module

    Position

    7

    Distribution

    Module

    Position

    8

    Distribution

    ModulePosition

    5

    Distribution

    ModulePosition

    6

    Distribution

    ModulePosition

    3

    Distribution

    ModulePosition

    4

    Distribution

    Module

    Position

    1

    Distribution

    Module

    Position

    2

    Home

    FRONT VIEWSUPPLEMENTAL

    DISTRIBUTION BAY

    Configuration Options

    List 2: SupplementalDistribution Bay(w/o internal shunt)

    List 12: SupplementalDistribution Bay(w/ internal shunts)

    Distribution Bus

    Module (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), or

    Blank Panel (List 72)

    Distribution BusModule (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Distribution BusModule (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Distribution BusModule (ListA, B, C,

    E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Distribution BusModule (ListA, B, C,E, F, G, H, J, orN), orBattery DisconnectModule (List 85), orBlank Panel (List 72)

    Page 8 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    9/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Main and Supplemental Distribution Bays Side Cover PanelHome

    OPTIONAL SIDECOVER PANEL

    Optional SideCover Panel(List 71)

    SEE ALSO

    System OverviewTable of Contents

    List InformationAccessory InformationList of PartsSpecificationsPhysical Size InformationRelated Documentation

    Page 9 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    10/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    TABLE OF CONTENTS

    SystemOverview

    PictureList

    InformationAccessoryInformation

    List ofParts

    SpecificationsPhysical SizeInformation

    RelatedDocumentation

    SYSTEM OVERVIEW.................................................................................................................................................1Main Distr ibut ion Bay ...........................................................................................................................................5Main Dis tri bution Bay 19-Inch Accessory Equipment Mounting .....................................................................6Main Distr ibut ion Bay Spare Fuse Holders ........................................................................................................7Supplemental Distribution Bay............................................................................................................................8Main and Supplemental Dist ribution Bays Side Cover Panel ..........................................................................9

    TABLE OF CONTENTS...........................................................................................................................................10LIST INFORMATION................................................................................................................................................12

    List Structure.......................................................................................................................................................12See also the following located in this document ...............................................................................................14

    List Descript ions .................................................................................................................................................15List 1: Main Distribution Bay (Common Equipment) ........................................................................................15

    List 2: Supplemental Distribution Bay (Common Equipment) ..........................................................................16List 11: Main Distribution Bay (Common Equipment) ......................................................................................16List 12: Supplemental Distribution Bay (Common Equipment) ........................................................................17List 21: MCA Panel (Standard Application)......................................................................................................18List 25: MCA Panel (Special Application).........................................................................................................18List 26: MCA Panel (Special Application).........................................................................................................18List 34: LMS1000 Monitoring System Expansion Cabinet ...............................................................................19List 64: Optional Capacitor Precharge Unit......................................................................................................19List 71: Side Cover Panel .................................................................................................................................20List 72: Module Blank Panel.............................................................................................................................20List 85: Battery Disconnect Module (Part No. 501524) ....................................................................................20List AC: AC Courtesy Panel (Part No. 514606)

    (1) Duplex 20A Ground-Fault Circuit-Interrupter Protected Receptacle .............................................23List A: Distribution Bus Module (Part No. 431850900)

    (16) Distribution TPA/LEL1 Fuse/Circuit Breaker Positions..................................................................24List B: Distribution Bus Module (Part No. 431851000)

    (12) Distribution TPS Fuse Positions ....................................................................................................27List C: Distribution Bus Module (Part No. 431654100)

    (6) Distribution TPJ Fuse Positions.......................................................................................................30List E: Distribution Bus Module (Part No. 508636)

    (1) Distribution TPL Fuse Position ........................................................................................................33List F: Distribution Bus Module (Part No. 505872)

    (3) Distribution TPL Fuse Positions.......................................................................................................36List G: Distribution Bus Module (Part No. 505865)

    (5) 1-Pole Distribution GJ/218 Circuit Breaker Positions .....................................................................39List H: Distribution Bus Module (Part No. 505866)

    (4) 2-Pole Distribution GJ/218 Circuit Breaker Positions ......................................................................42List J: Distribution Bus Module (Part No. 505867)(3) 3-Pole Distribution GJ/218 Circuit Breaker Positions ......................................................................45

    List N: Distribution Bus Module (Part No. 514602)(2) 4-Pole Distribution GJ/218 Circuit Breaker Positions ......................................................................48

    ACCESSORY INFORMATION ................................................................................................................................5110000 Ampere Overhead Busbar Assemblies .................................................................................................51Companion VPS Power Bay Overhead Busbar Assembl ies ..........................................................................54Overhead Busbar Termination Kits ..................................................................................................................54

    Page 10 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    11/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Overhead Busbar Safety Covers .......................................................................................................................56VPS Power Bays..................................................................................................................................................56Distr ibut ion Devices ...........................................................................................................................................57

    Replacement Alarm-Type Fuses.......................................................................................................................57TPA-Type Fuses ...............................................................................................................................................58LEL1-Type Circuit Breakers ..............................................................................................................................59TPS-Type Fuses ...............................................................................................................................................60TPJ-Type Fuses ................................................................................................................................................61TPL-Type Fuses................................................................................................................................................62GJ/218-Type Circuit Breakers...........................................................................................................................63

    Lugs......................................................................................................................................................................64 Distribution (Load) Lugs ....................................................................................................................................64Input Lugs..........................................................................................................................................................64Standard Crimp Lugs ........................................................................................................................................65Special Application Crimp Lug / Strap Combination .........................................................................................66

    Fifty-Six (56) PCU Conversion Ki t .....................................................................................................................67Accessory Cables ...............................................................................................................................................67

    582121901 Supplemental Bay to 582121900 Main or Supplemental Bay FA/CBA and Shunt PODInterconnect Cable ............................................................................................................................................67

    Replacement Cables ...........................................................................................................................................68LIST OF PARTS.......................................................................................................................................................69SPECIFICATIONS....................................................................................................................................................76

    DC Distr ibut ion....................................................................................................................................................76Standard Features ..............................................................................................................................................76Environmental Ratings .......................................................................................................................................77Compl iance Informat ion .....................................................................................................................................77

    PHYSICAL SIZE INFORMATION............................................................................................................................79Overall Dimensions ............................................................................................................................................79

    Notes, Floor Drilling, and Bus Modules.............................................................................................................79Main Distribution Bay ........................................................................................................................................80Supplemental Distribution Bay ..........................................................................................................................81Input Busbars ....................................................................................................................................................82

    RELATED DOCUMENTATION................................................................................................................................83REVSION RECORD.................................................................................................................................................84

    Page 11 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    12/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    LIST INFORMATION

    List Structure

    More detailed information is available for each option by clicking on the desired number in the column entitledList # from the table below.

    List#

    Part Number Description

    1 58212190101

    Common Equipment for 5000 Ampere Main Distribution Bay Mounted in a 7'0"H x31.375"W x 24"D Seismic Box Framework.

    Does Not Include Internal Main Shunts (External System Shunt Must Be Provided).

    Distribution Modules NotIncluded.

    Includes LMS1000 Monitoring System (Main Cabinet) (3.5" x 19" Mounting)

    2 58212190102

    Common Equipment for 5000 Ampere Supplemental Distribution Bay Mounted in a7'0"H x 31.375"W x 24"D Seismic Box Framework.

    Does Not Include Internal Main Shunts (External System Shunt Must Be Provided).

    Distribution Modules NotIncluded.

    11 58212190111

    Common Equipment for 5000 Ampere Main Distribution Bay Mounted in a 7'0"H x31.375"W x 24"D Seismic Box Framework.

    Includes Internal Main Shunts.

    Distribution Modules NotIncluded.

    Includes LMS1000 Monitoring System (Main Cabinet) (3.5" x 19" Mounting)

    12 58212190112

    Common Equipment for 5000 Ampere Supplemental Distribution Bay Mounted in a7'0"H x 31.375"W x 24"D Seismic Box Framework.

    Includes Internal Main Shunts.

    Distribution Modules Not Included.

    21 58212190121 MCA Panel (3.5" x 19" Mounting) with Standard Alarms

    25 58212190125 MCA Panel (3.5" x 19" Mounting) with Modified Alarms

    26 58212190126 MCA Panel (3.5" x 19" Mounting) with Modified Alarms

    34 58212190034 LMS1000 Monitoring System Expansion Cabinet

    64 58212190164Hand Held Capacitor Pre-Charge Unitfor Use with List's B, C, F, G, H, and J

    71 58212190171 Side Cover Panel (for one side)

    72 58212190172 Module Blank Panel

    AC 582121901AC AC Courtesy Panel

    Home

    Page 12 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    13/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List#

    Part Number Description

    BATTERY DISCONNECT AND DISTRIBUTION MODULES

    85 58212190185 Battery Disconnect Module - 1200 Ampere Contactor Controlled

    A 5821219010ADistribution Module - (16) PositionTPA / LEL1 Fuse / Circuit Breaker Module (w/ shunts)

    B 5821219010B Distribution Module - (12) Position TPS Fuse Module (w/ shunts)

    C 5821219010C Distribution Module - (6) Position TPJ Fuse Module (w/ shunts)

    E 5821219010E Distribution Module - (1) Position TPL Fuse Module (w/ shunts)

    F 5821219010F Distribution Module - (3) Position TPL Fuse Module (w/ shunts)

    G 5821219010GDistribution Module - GJ/218 Breaker Module Arranged forFive (5) 100-250A 1-Pole Breakers and Load Shunts (w/ shunts)

    H 5821219010HDistribution Module - GJ/218 Breaker Module Arranged forFour (4) 300A and 400A 2-Pole Breakers and Load Shunts (w/ shunts)

    J 5821219010J

    Distribution Module - GJ/218 Breaker Module Arranged for

    Three (3) 600A 3-Pole Breakers and Load Shunts (w/ shunts)

    N 5821219010NDistribution Module - GJ/218 Breaker Module Arranged forTwo (2) 800A 4-Pole Breakers and Load Shunts (w/ shunts)

    ACCESSORIES

    --Order by

    Part NumberDistribution Bay Overhead Busbars and Power Bay Overhead Busbars

    --Order by

    Part NumberOverhead Busbar Termination Kits

    --Order by

    Part NumberOverhead Busbar Safety Covers

    --

    Order per

    VPSPower Bay

    Documentation

    VPS Power Bays

    --Order by

    Part NumberDistribution Devices

    --Order by

    Part NumberLugs

    --Order by

    Part NumberFifty-Six (56) PCU Conversion Kit

    Home

    Page 13 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    14/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    See also the follow ing located in this document

    System Overview

    Table of Contents

    Accessory Information

    List of Parts

    Specifications

    Physical Size Information

    Related Documentation

    Home

    Page 14 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    15/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List Descriptions

    List 1: Main Distribution Bay (Common Equipment)

    Provides common equipment for one (1) main Distribution Bay rated for up to 5000 amperes of distribution,without internal main shunts (customer to provide external system shunt). One Shunt POD is providedconnected to a terminal block for customer shunt lead connections.

    Features

    Six (6) distribution bus module mounting positions.

    One (1) Shunt POD circuit card (514027) is provided to allow current monitoring of an external load shunt.The Shunt POD interfaces with the VPS's MCA for remote shunt monitoring.

    Two (2) (one per side) LMS1000 Expansion Assemblies provided. Provides analog and binary points tothe LMS1000 Main Cabinet for Distribution Module Shunt and FA/CBA monitoring.

    Provides an LMS1000, Spec. No. 58650500001, Main Cabinet and CPU circuit card. Refer toSAG586505000 for further information.

    MCA RS-485 Interface: Also supplied is an MCA RS-485 Communications Interface circuit card, Spec.No. 486781400; plus associated MCA Panel RJ-45 connector, cable, and hardware. The RS-485 circuit

    card plugs onto the MCA circuit card, and the RJ-45 connector attaches to the back of the MCA Panel.

    Allows VPS (MCA) interface to the LMS1000, via an RS-485 port.

    Also provided is an interface cable that interconnects the MCA and the LMS1000.

    Restrictions

    DO NOT order Vortex WinLink Hardware and Software via the Power Bay SAG (System Application Guide).These cannot be used when the MCA RS-485 Interface is installed on the MCA.

    The LMS1000 mounts in the 19"W mounting space provided in the main Distribution Bay.

    Ordering Notes

    1) Order up to six (6) Distribution Bus Modules per ListsA, B, C, E, F, G, H, J, N, and 85.

    2) Order blank cover panels as required for any unused Distribution Bus Module mounting position perList72.

    3) Order distribution fuses and/or circuit breakers as required per ListsA, B, C, E, F, G, H, J, and N.

    4) Order load distribution lugs as required per ListsA, B, C, E, F, G, H, J, and N.

    5) Order input lugs as required per Tables 10 and 12 (under INPUT LUGS).

    6) Order MCA Panel as required per List 21, 25, or26. This locates the MCA Panel (which displays systemvoltage and system current) in the main VPS Distribution Bay, above to the LMS1000.

    7) Order LMS1000 Expansion Cabinet, as required, perList 34.

    8) Order LMS1000 options as required per SAG586505000 (example; input/output cards to monitor pointsexternal to the power system).

    9) Order Capacitor Precharge Unit as required perList 64.

    10) Order Side Cover Panels as required perList 71.

    11) Order AC Courtesy Panel as required perList AC.

    12) OrderOverhead Busbars, Termination Kits, and Safety Covers as required. See ACCESSORYINFORMATION.

    13) Order VPS Power Bays as required per the Power Bay's SAG (System Application Guide).

    List of Parts

    Home

    Page 15 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    16/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List 2: Supplemental Distribu tion Bay (Common Equipment)

    Provides common equipment for one (1) supplemental Distribution Bay rated for up to 5000 amperes ofdistribution, without internal main shunts.

    Features

    Eight (8) distribution bus module mounting positions.

    Ordering Notes

    1) Order up to eight (8) Distribution Bus Modules per ListsA, B, C, E, F, G, H, J, N, and 85.

    2) Order blank cover panels as required for any unused Distribution Bus Module mounting position perList72.

    3) Order distribution fuses and/or circuit breakers as required per ListsA, B, C, E, F, G, H, J, and N.

    4) Order load distribution lugs as required per ListsA, B, C, E, F, G, H, J, and N.

    5) Order input lugs as required per Tables 10 and 12 (under INPUT LUGS).

    6) Order Side Cover Panels as required perList 71.

    7) OrderOverhead Busbars, Termination Kits, and Safety Covers as required. See ACCESSORYINFORMATION.

    List 11: Main Distribution Bay (Common Equipment)

    Provides common equipment for one (1) main Distribution Bay rated for up to 5000 amperes of distribution,with two internal main shunts and two Shunt PODs.

    Features

    Six (6) distribution bus module mounting positions.

    Two (2) Shunt POD circuit cards (433800164) are provided (one for each side). The Shunt PODsinterface with the VPS's MCA for system and subsystem current monitoring. Load and battery distributionper VPS Distribution Bay is supplied in a split bus configuration. Load and battery distribution is dividedinto left side and right side distribution. Each VPS Distribution Bay (Lists 11 and 12 only) is providedwith two shunts and two Shunt PODs to monitor left and right side distribution.

    VPS distribution and/or battery disconnect modules may be installed in the VPS Distribution Bay. Forsides that have VPS distribution modules installed, the Shunt POD monitors left side or right side loaddistribution. The MCA displays load distribution as system current. For sides that have VPS batterydisconnect modules installed, the shunt POD monitors left side or right side battery current. The MCAdisplays battery current as subsystem current.

    Two (2) (one per side) LMS1000 Expansion Assemblies provided. Provides analog and binary points tothe LMS1000 Main Cabinet for Distribution Module Shunt and FA/CBA monitoring.

    Provides an LMS1000, Spec. No. 58650500001, Main Cabinet and CPU circuit card. Refer toSAG586505000 for further information.

    MCA RS-485 Interface: Also supplied is an MCA RS-485 Communications Interface circuit card, Spec.No. 486781400; plus associated MCA Panel RJ-45 connector, cable, and hardware. The RS-485 circuitcard plugs onto the MCA circuit card, and the RJ-45 connector attaches to the back of the MCA Panel.

    Allows VPS (MCA) interface to the LMS1000, via an RS-485 port.

    Also provided is an interface cable that interconnects the MCA and the LMS1000.

    List of Parts

    List of Parts

    Home

    Page 16 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    17/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Restrictions

    DO NOT order Vortex WinLink Hardware and Software via the Power Bay SAG (System Application Guide).These cannot be used when the MCA RS-485 Interface is installed on the MCA.

    The LMS1000 mounts in the 19"W mounting space provided in the main Distribution Bay.

    Ordering Notes

    1) Order up to six (6) Distribution Bus Modules per ListsA, B, C, E, F, G, H, J, N, and 85.

    2) Order blank cover panels as required for any unused Distribution Bus Module mounting position perList72.

    3) Order distribution fuses and/or circuit breakers as required per ListsA, B, C, E, F, G, H, J, and N.

    4) Order load distribution lugs as required per ListsA, B, C, E, F, G, H, J, and N.

    5) Order input lugs as required per Tables 10 and 12 (under INPUT LUGS).

    6) Order MCA Panel as required per List 21, 25, or26. This locates the MCA Panel (which displays systemvoltage and system current) in the main VPS Distribution Bay, next to the LMS1000.

    7) Order LMS1000 Expansion Cabinet, as required, perList 34.

    8) Order LMS1000 options as required per SAG586505000 (example; input/output cards to monitor pointsexternal to the power system).

    9) Order Capacitor Precharge Unit as required perList 64.

    10) Order Side Cover Panels as required perList 71.

    11) Order AC Courtesy Panel as required perList AC.

    12) OrderOverhead Busbars, Termination Kits, and Safety Covers as required. See ACCESSORYINFORMATION.

    13) Order VPS Power Bays as required per the Power Bay's SAG (System Application Guide).

    List 12: Supplemental Distribution Bay (Common Equipment)

    Provides common equipment for one (1) supplemental Distribution Bay rated for up to 5000 amperes ofdistribution, with two internal main shunts and two Shunt PODs.

    Features

    Eight (8) distribution bus module mounting positions.

    Two (2) shunt POD circuit cards (433800164) are provided (one for each side). The Shunt PODsinterface with the VPS's MCA for system and subsystem current monitoring. Load and battery distributionper VPS Distribution Bay is supplied in a split bus configuration. Load and battery distribution is dividedinto left side and right side distribution. Each VPS Distribution Bay (Lists 11 and 12 only) is providedwith two shunts and two shunt PODs to monitor left and right side distribution.

    VPS distribution and/or battery disconnect modules may be installed in the VPS Distribution Bay. For

    sides that have VPS distribution modules installed, the shunt POD monitors left side or right side loaddistribution. The MCA displays load distribution as system current. For sides that have VPS batterydisconnect modules installed, the shunt POD monitors left side or right side battery current. The MCAdisplays battery current as subsystem current.

    Restrictions

    Supplemental Distribution Bay and Power Bay cabinets must expand all to the left or all to the right of MainDistribution Bay, not in both directions. Interbay network cable provided will not accommodate systemexpansion in both directions.

    List of Parts

    Home

    Page 17 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    18/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Ordering Notes

    14) Order up to eight (8) Distribution Bus Modules per ListsA, B, C, E, F, G, H, J, N, and 85.

    15) Order blank cover panels as required for any unused Distribution Bus Module mounting position perList72.

    16) Order distribution fuses and/or circuit breakers as required per ListsA, B, C, E, F, G, H, J, and N.

    17) Order load distribution lugs as required per ListsA, B, C, E, F, G, H, J, and N.

    18) Order input lugs as required per Tables 10 and 12 (under INPUT LUGS).

    19) Order Side Cover Panels as required perList 71.

    20) OrderOverhead Busbars, Termination Kits, and Safety Covers as required. See ACCESSORYINFORMATION.

    List 21: MCA Panel (Standard Appl ication)

    Features

    Provides the standard 19" MCA Panel (Part No. 500732 e/w MCA circuit card 507572 programmed with

    MCA configuration 507472), mounted in the main VPS Distribution Bay.

    Alarms: Major, Minor, High Voltage #1, High Voltage #2, 50% Battery On Discharge, AC Fail, Battery OnDischarge, MCA Audible, Test/Equalize Mode.

    Restrictions

    1) DO NOT order via the Power Bay SAG (System Application Guide). The MCA Panel must be mounted inthe main Distribution Bay for easy cable connection to LMS1000.

    List 25: MCA Panel (Special Application)

    Features

    Provides special application 19" MCA Panel (Part No. 501911 e/w MCA circuit card 507572 programmedwith MCA configuration 507476) in lieu of the standard MCA Panel, mounted in the main VPS DistributionBay.

    Alarms: Major, Minor, High Voltage #1, Very Low Voltage, Battery On Discharge, AC Fail, MCA Fail,Fuse/Circuit Breaker, PCU Fail.

    Restrictions

    1) DO NOT order via the Power Bay SAG (System Application Guide). The MCA Panel must be mounted inthe main Distribution Bay for easy cable connection to LMS1000.

    List 26: MCA Panel (Special Application)

    Features

    Provides special application 19" MCA Panel (Part No. 505111 e/w MCA circuit card 507572 programmedwith MCA configuration 507474) in lieu of the standard MCA Panel, mounted in the main VPS DistributionBay.

    Alarms: Major, Minor, High Voltage #1, PCU Fail Major, PCU Fail Minor, AC Fail, Battery On Discharge,MCA Audible, Fuse/Circuit Breaker.

    List of Parts

    List of Parts

    List of Parts

    Home

    Page 18 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    19/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    Restrictions

    1) DO NOT order via the Power Bay SAG (System Application Guide). The MCA Panel must be mounted inthe main Distribution Bay for easy cable connection to LMS1000.

    List 34: LMS1000 Monitoring System Expansion Cabinet

    Features

    Provides an LMS1000, Spec. No. 58650500006,Expansion Cabinet. Refer to SAG586505000 forfurther information.

    Allows additional input/output (I/O) circuit cardmounting positions to increase number of externalpoints that can be monitored.

    Restrictions

    The LMS1000 Expansion Cabinet mounts in the 19"W mounting space provided in the main Distribution Bay.

    Ordering Notes

    1) Order one (1) LMS1000 Expansion Cabinet as required to monitor additional points external to thesystem.

    2) Order LMS1000 options as required per SAG586505000 (example; input/output cards to monitor pointsexternal to the power system).

    List 64: Optional Capacitor Precharge Unit

    Features

    Provides a portable hand-held capacitor precharge unit.

    Allows capacitors of a DC load to be initially chargedbefore a TPS, TPJ, or TPL distribution fuse isinserted, or a GJ/218 distribution circuit breaker isclosed. This prevents the fuse from possiblyblowing open or the breaker from possibly trippingopen as it is inserted or closed due to high capacitorcharging

    current.

    Designed to plug directly into a TPS type fuseholdercase.

    Adapter cable furnished for use with distribution busmodules utilizing TPJ or TPL type fuses, or GJ/218type circuit breakers. Cable plugs into J1 ofPrecharge unit.

    Restrictions

    For Use with Lists B, C, E, F, G, H, J, and N.

    Ordering Notes

    1) Order one List 64 for each system, as required.

    List of Parts

    Home

    List of Parts

    Home

    J1

    J1

    Page 19 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    20/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List 71: Side Cover Panel

    Features

    Provides a cover panel to enclose one side of a VPS main or supplemental Distribution Bay.

    Restrictions

    Side cover panels are only needed on side of bays that are exposed. Panels are not required between bays.

    Ordering Notes

    1) Order as required. Each List 71 provides a cover panel for one (1) side. Cover panel can be used oneither side.

    List 72: Module Blank Panel

    Features

    Provides one (1) blank panel to cover an unused VPS distribution bus module mounting position.

    Restrictions

    A blank panel must be provided for each unused module position.Ordering Notes

    1) Order one (1) List 72 for each unused module position.

    List 85: Battery Disconnect Module (Part No. 501524)

    Features

    Provides a 1200 ampere contactor controlled battery disconnect module, Part No. 501524.

    Local switch provided to connect and disconnect the battery string.

    1200A maximum capacity.

    Restrictions

    Must be used with overhead busbar assemblies (see 10000 AMPERE OVERHEAD BUSBAR ASSEMBLIES).

    VPS distribution bus modules and VPS battery disconnect modules fit into the same mounting space, butmust not be mixed on the same vertical bus. DO NOT install a VPS distribution bus module if a VPS batterydisconnect module is already installed on the same side of the bay.

    Unless otherwise specified, the Battery Disconnect Module will be mounted on the left vertical bus starting atthe lowest position.

    Ordering Notes

    1) Order as required for each battery string.

    2) Order battery lugs as required per Tables 10 and 12 (under INPUT LUGS).

    3) Order Overhead Busbars per10000 AMPERE OVERHEAD BUSBAR ASSEMBLIES.

    List of Parts

    List of Parts

    List of Parts

    Home

    Page 20 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    21/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List 85 (Part No. 501524)

    BATTERYCONNECTIONS

    BATTERY RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Shown as

    Mounted in Left

    Side of Bay.

    Module Rotated

    180 when

    Mounted in Right

    Side of Bay.

    Home

    Page 21 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    22/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    1.000

    BATTERY LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS

    (LUGS INSTALLED FROM REAR OF BAY)

    -BAT conductors and lugs are connected to busbar provided

    on the rear of the VPS Battery Disconnect Module(s). Thisbusbar provides holes for installation of customer providedtwo hole lugs with 1 inch centers and 3/8 inch bolt clearanceholes, and 5/8 inch centers and 1/4 inch bolt clearance holes.Customer must provide lug mounting bolts and additionalhardware. When lugs are secured using 3/8 inch bolts,recommended torque is 180 in-lbs when a Belleville lockwasher is used, and 300 in-lbs when a standard flat washerand lock washer are used. When lugs are secured using 1/4inch bolts, recommended torque is 60 in-lbs when a Bellevillelock washer is used, and 84 in-lbs when a standard flat washerand lock washer are used.

    582121901 List 85 (Part No. 501524)

    1.000

    0.625

    3/8 INCH BOLTCLEARANCE HOLE (12)

    1/4 INCH BOLTCLEARANCE HOLE (12)

    Home

    Page 22 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    23/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List AC: AC Courtesy Panel (Part No. 514606)(1) Duplex 20A Ground-Fault Circuit-Interrupter Protected Receptacle

    Features

    Provides a 2U high panel with a UL Listed ground-fault circuit-interrupter protected receptacle mounted inan outlet box.

    Receptacle rated at 125VAC/20A.

    Restrictions

    Panel mounts in the 19"W mounting space provided in the main Distribution Bay.

    Ordering Notes

    1) Order as required.

    List of Parts

    Home

    Page 23 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    24/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List A: Distribution Bus Module (Part No. 431850900)(16) Distribution TPA/LEL1 Fuse/Circuit Breaker Positions

    Features

    (16) Distribution Fuse/Circuit Breaker Mounting Positions(3 to 50A TPA-Type Fuses / 3 to 100A LEL1-Type Circuit Breakers)

    Equipped with One Shunt for All Distribution Positions

    600A Maximum Capacity

    1/4-20 Studs for Load Lead Connections (accepts double hole lugs on 5/8" centers)

    Distribution Shunt Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Unless otherwise specified circuit breakers are to be mounted from top to bottom in each module starting withthe highest capacity and working down to the lowest capacity.

    Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 gauge.

    Maximum lug width, 0.625 inches.

    Caution: Circuit breaker with a 70 ampere or greater rating SHALL HAVE an empty mounting positionbetween it and any other overcurrent protective device.

    Ordering Notes

    1) Order circuit breakers as required perTable 4 (LEL1-Type Circuit Breakers).

    2) Order fuses as required perTable 3 (TPA-Type Fuses).

    3) Order one (1) Part No. 248817350 fuseholder per fuse ordered in 2) above (see TPA-Type Fuses).

    4) Order load lugs (two hole, 1/4" bolt clearance hole, 5/8" centers) as required for each distribution positionper Table 10 or13 (Lugs).

    5) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 24 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    25/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEW

    L. SIDE VIEW

    TOP VIEW

    582121901 List A (Part No. 431850900)

    Shown as

    Mounted in Left

    Side of Bay.

    Module Rotated

    180 when

    Mounted in Right

    Side of Bay.

    Home

    Page 25 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    26/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    Load conductors and lugs (load side) are connected to the VPSmodular distribution fuse/circuit breaker mounting blocks.The VPS modular distribution fuse/circuit breaker mountingblocks provide 1/4-20 studs and mounting hardware forinstallation of customer provided two hole lugs with 5/8 inchcenters and 1/4 inch bolt clearance holes. Recommendedtorque is 72 in-lbs using the supplied hardware. Maximumsize of wire to be connected to a single position of a VPSmodular fuse/circuit breaker mounting block is 2 gauge.

    582121901 List A (Part No. 431850900)

    FRONT VIEW

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS

    (LUGS INSTALLED FROM FRONT OF BAY)

    LOADCONNECTIONS

    0.625"

    1/4-20 STUD, 32 PLACES(ADDITIONAL HARDWAREPROVIDED)

    LOADCIRCUIT

    BREAKERS/FUSES

    0.765"

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOADCONNECTIONS

    LOADCIRCUIT

    BREAKERS/FUSES

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    0.625"0.765"

    1/4-20 STUD, 32 PLACES(ADDITIONAL HARDWARE

    PROVIDED)

    Home

    Page 26 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    27/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List B: Distribution Bus Module (Part No. 431851000)(12) Distribution TPS Fuse Positions

    Features

    (12) Distribution Fuse Mounting Positions(3 to 70A TPS-Type Fuses)

    Equipped with One Shunt for All Fuse Positions

    600A Maximum Capacity

    1/4-20 Studs for Load Lead Connections (accepts single hole lugs)

    Distribution Shunt Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Maximum size of wire to be connected to a single fuseholder position is 2 gauge.

    Maximum lug width, 0.750 inches.

    Caution: When populating the TPS Distribution Module with 70 ampere fuses, skip every othermounting position to ensure that there is an unused position directly above and directly

    below the fuse position.

    Ordering Notes

    1) Order fuses as required perTable 5 (TPS-Type Fuses).

    2) Order one (1) Part No. 248610301 alarm-type fuse and one (1) Part No. 248898700 safety fuse cover perdistribution fuse ordered in 1) above (see TPS-Type Fuses).

    3) Order load lugs (single hole, 1/4" bolt clearance hole) as required for each distribution position perTable9 (Lugs).

    4) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 27 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    28/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List B (Part No. 431851000)

    Shown as

    Mounted in Left

    Side of Bay.

    Module Rotated

    180 when

    Mounted in Right

    Side of Bay.

    Home

    Page 28 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    29/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEW

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS

    (LUGS INSTALLED FROM FRONT OF BAY)

    582121901 List B (Part No. 431851000)

    1/4-20 STUD, 12 PLACES(ADDITIONAL HARDWARE

    PROVIDED)

    1.156"

    LOADCONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Load conductors and lugs (load side) are connected to theTPS-type fuse blocks. The TPS-type fuse blocks provide a1/4-20 stud and mounting hardware for installation ofcustomer provided single hole lug with a 1/4 inch boltclearance hole. Recommended torque is 72 in-lbs using thesupplied hardware.

    LOADFUSES

    LOADCONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    1.156"

    1/4-20 STUD, 12 PLACES(ADDITIONAL HARDWAREPROVIDED)

    LOADFUSES

    Home

    Page 29 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    30/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List C: Distribution Bus Module (Part No. 431654100)(6) Distribution TPJ Fuse Positions

    Features

    (6) Distribution Fuse Mounting Positions(60 to 150A TPJ-Type Fuses)

    Equipped with Six (6) Shunts - One (1) for Each Fuse Block

    900A Maximum Capacity

    3/8-16 Captive Nut for Load Lead Connections (accepts single hole lugs)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Maximum size of wire to be connected to a single fuseholder position is 2/0 gauge.

    Maximum lug width, 0.875 inches.

    Ordering Notes

    1) Order fuses as required perTable 6 (TPJ-Type Fuses).

    2) Order one (1) Part No. 248610301 alarm-type fuse and one (1) Part No. 248898700 safety fuse cover perdistribution fuse ordered in 1) above (see TPJ-Type Fuses).

    3) Order load lugs (single hole, 3/8" bolt clearance hole) as required for each distribution position perTable11 (Lugs).

    4) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 30 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    31/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEW

    L. SIDE VIEW

    TOP VIEW

    582121901 List C (Part No. 431654100)

    Shown as

    Mounted in Left

    Side of Bay.

    Module Rotated

    180 when

    Mounted in Right

    Side of Bay.

    Home

    Page 31 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    32/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    REAR VIEW

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS

    (LUGS INSTALLED FROM REAR OF BAY)

    582121901 List C (Part No. 431654100)

    3/8-16 CAPTIVE NUT, 6 PLACES(CUSTOMER MUST PROVIDE LUG

    MOUNTING BOLT ANDADDITIONAL HARDWARE)

    LOAD

    FUSES

    2.140"

    LOAD

    CONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Load conductors and lugs (load side) are connected to theTPJ-type fuse blocks. The TPJ-type fuse blocks are providedwith lug adapters. The lug adapters provide a 3/8-16 captivenut for installation of customer provided single hole lug witha 3/8 inch bolt clearance hole. Customer must provide lugmounting bolt and additional hardware. When lugs aresecured using 3/8 inch diameter bolts, recommended torque is180 in-lbs when a Belleville lock washer is used, and 300 in-lbswhen a standard flat washer and lock washer are used.

    LOAD

    FUSES

    LOAD

    CONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    2.140"

    3/8-16 CAPTIVE NUT, 6 PLACES(CUSTOMER MUST PROVIDE LUG

    MOUNTING BOLT ANDADDITIONAL HARDWARE)

    Home

    Page 32 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    33/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List E: Distribution Bus Module (Part No. 508636)(1) Distribution TPL Fuse Position

    Features

    (1) Distribution Fuse Mounting Position(1000 or 1200A TPL-Type Fuse)

    Equipped with One (1) Shunt

    1200A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Maximum size of wire to be connected to a single fuseholder position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order fuses as required perTable 7A (TPL-Type Fuses).

    2) Order one (1) Part No. 248610301 alarm-type fuse and one (1) Part No. 248898700 safety fuse cover perdistribution fuse ordered in 1) above (see TPL-Type Fuses).

    3) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    4) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 33 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    34/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    582121901 List E (Part No. 508636)

    TOP VIEW

    FRONT VIEWL. SIDE VIEW

    Shown asmounted in leftside of bay.Module rotated180 degreeswhen in rightside of bay.

    REAR VIEW

    LOADCONNECTIONS

    LOAD RETURNCONNECTIONSTO OVERHEAD

    GROUND BUSBARLOADCONNECTIONS

    LOAD RETURNCONNECTIONSTO OVERHEAD

    GROUND BUSBARLOADFUSE

    LOADFUSE

    Home

    Page 34 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    35/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    582121901 List E (Part No. 508636)

    Load conductors and lugs (load side) are connected to busbarsprovided on the rear of the VPS Distribution Bus Module.These busbars provide holes and captive nuts for installation ofcustomer provided two hole lugs with 1 inch centers and 3/8inch bolt clearance holes. Customer must provide lug mountingbolts and additional hardware. Recommended torque is 180 in-lbswhen a Belleville lock washer is used, and 300 in-lbs when a standardflat washer and lock washer are used.

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS(LUGS INSTALLED FROM REAR OF BAY)

    2.0002.000

    1.000 (TYP)

    3/8" Bolt Clearance Hole (9)

    3/8-16 Captive Nut (3)

    Home

    Page 35 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    36/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List F: Distribut ion Bus Module (Part No. 505872)(3) Distribution TPL Fuse Positions

    Features

    (3) Distribution Fuse Mounting Positions(70 to 800A TPL-Type Fuses)

    Equipped with Three (3) Shunts - One (1) for Each Fuse Block

    1250A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Maximum size of wire to be connected to a single fuseholder position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order fuses as required perTable 7B (TPL-Type Fuses).

    2) Order one (1) Part No. 248610301 alarm-type fuse and one (1) Part No. 248898700 safety fuse cover perdistribution fuse ordered in 1) above (see TPL-Type Fuses).

    3) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    4) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 36 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    37/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    582121901 List F (Part No. 505872)

    TOP VIEW

    FRONT VIEW

    L. SIDE VIEW

    Shown as

    mounted in left

    side of bay.

    Module rotated

    180 degrees

    when in right

    side of bay.

    REAR VIEW

    LOAD

    CONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOAD

    CONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOAD

    FUSES

    LOAD

    FUSES

    Home

    Page 37 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    38/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    582121901 List F (Part No. 505872)

    Load conductors and lugs (load side) are connected to busbars

    provided on the rear of the VPS Distribution Bus Module.

    These busbars provide holes and captive nuts for installation of

    customer provided two hole lugs with 1 inch centers and 3/8

    inch bolt clearance holes. Customer must provide lug mounting

    bolts and additional hardware. Recommended torque is 180 in-lbs

    when a Belleville lock washer is used, and 300 in-lbs when a standard

    flat washer and lock washer are used.

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS

    (LUGS INSTALLED FROM REAR OF BAY)

    2.0002.000

    1.000 (TYP)

    3/8" Bolt Clearance Hole (9)

    3/8-16 Captive Nut (3)

    Home

    Page 38 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    39/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List G: Distribution Bus Module (Part No. 505865)(5) 1-Pole Distribution GJ/218 Circuit Breaker Positions

    Features

    (5) Distribution Circuit Breaker Mounting Positions(100 to 250A GJ/218-Type) NOTE RESTRICTIONS

    Equipped with Shunts - One (1) for Each Circuit Breaker Installed

    1250A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Provides up to five 1-pole GJ/218-type 100 to 250A circuit breakers.

    Five (5) positions available, single pole breakers require one position with an empty position between it andany other breaker.

    Maximum size of wire to be connected to a single circuit breaker position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order circuit breakers and associated mounting kits as required perTable 8 (GJ/218-Type CircuitBreakers). NOTE RESTRICTIONS

    2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    3) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 39 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    40/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List G (Part No. 505865)

    REAR VIEW

    LOAD

    CIRCUITBREAKERS

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOAD

    CONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Shown asMounted in LeftSide of Bay.Module Rotated180 whenMounted in RightSide of Bay.

    Home

    Page 40 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    41/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    582121901 List G (Part No. 505865)

    Load conductors and lugs (load side) are connected to busbarsprovided on the rear of the VPS Distribution Bus Module.These busbars provide holes and captive nuts for installation ofcustomer provided two hole lugs with 1 inch centers and 3/8inch bolt clearance holes. Customer must provide lug mountingbolts and additional hardware. Recommended torque is 180 in-lbswhen a Belleville lock washer is used, and 300 in-lbs when a standardflat washer and lock washer are used.

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS(LUGS INSTALLED FROM REAR OF BAY)

    2.0002.000

    1.000 (TYP)

    3/8" Bolt Clearance Hole (9)

    3/8-16 Captive Nut (3)

    Home

    Page 41 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    42/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List H: Distribution Bus Module (Part No. 505866)(4) 2-Pole Distribution GJ/218 Circuit Breaker Positions

    Features

    (4) Distribution Circuit Breaker Mounting Positions(100 to 400A GJ/218-Type) NOTE RESTRICTIONS

    Equipped with Shunts - One (1) for Each Circuit Breaker Installed

    1250A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Provides up to four 2-pole GJ/218-type 300 to 400A circuit breakers.

    Maximum size of wire to be connected to a single circuit breaker position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order circuit breakers and associated mounting kits as required perTable 8 (GJ/218-Type CircuitBreakers). NOTE RESTRICTIONS

    2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    3) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 42 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    43/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List H (Part No. 505866)

    REAR VIEW

    LOADCIRCUIT

    BREAKERS

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOADCONNECTIONS

    LOAD RETURNCONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Shown asMounted in Left

    Side of Bay.Module Rotated180 whenMounted in RightSide of Bay.

    Home

    Page 43 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    44/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    582121901 List H (Part No. 505866)

    Load conductors and lugs (load side) are connected to busbarsprovided on the rear of the VPS Distribution Bus Module.These busbars provide holes and captive nuts for installation ofcustomer provided two hole lugs with 1 inch centers and 3/8inch bolt clearance holes. Customer must provide lug mountingbolts and additional hardware. Recommended torque is 180 in-lbswhen a Belleville lock washer is used, and 300 in-lbs when a standardflat washer and lock washer are used.

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS(LUGS INSTALLED FROM REAR OF BAY)

    2.0002.000

    1.000 (TYP)

    3/8" Bolt Clearance Hole (9)

    3/8-16 Captive Nut (3)

    Home

    Page 44 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    45/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    List J: Distribution Bus Module (Part No. 505867)(3) 3-Pole Distribution GJ/218 Circuit Breaker Positions

    Features

    (3) Distribution Load Distribution Circuit Breaker Mounting Positions(100 to 600A GJ/218-Type) NOTE RESTRICTIONS

    Equipped with Shunts - One (1) for Each Circuit Breaker Installed

    1250A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Provides up to three 3-pole GJ/218-type 600A circuit breakers.

    Maximum size of wire to be connected to a single circuit breaker position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order circuit breakers and associated mounting kits as required perTable 8 (GJ/218-Type CircuitBreakers). NOTE RESTRICTIONS

    2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    3) Sales order must specify distribution module location on the order packet.

    List of Parts

    Home

    Page 45 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    46/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List J (Part No. 505867)

    REAR VIEW

    LOAD

    CIRCUITBREAKERS

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEADGROUND BUSBAR

    Shown asMounted in LeftSide of Bay.Module Rotated180 whenMounted in RightSide of Bay.

    Home

    Page 46 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    47/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    582121901 List J (Part No. 505867)

    Load conductors and lugs (load side) are connected to busbarsprovided on the rear of the VPS Distribution Bus Module.These busbars provide holes and captive nuts for installation ofcustomer provided two hole lugs with 1 inch centers and 3/8inch bolt clearance holes. Customer must provide lug mountingbolts and additional hardware. Recommended torque is 180 in-lbswhen a Belleville lock washer is used, and 300 in-lbs when a standardflat washer and lock washer are used.

    LOAD LUG MOUNTING HOLE SIZE AND SPACING DIMENSIONS(LUGS INSTALLED FROM REAR OF BAY)

    2.0002.000

    1.000 (TYP)

    3/8" Bolt Clearance Hole (9)

    3/8-16 Captive Nut (3)

    Home

    Page 47 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    48/84

    SAG582121901 System Application GuideIssue AH, January 26, 2009 Spec. No. 582121901 (Model 1231V1)

    List N: Distribution Bus Module (Part No. 514602)(2) 4-Pole Distribution GJ/218 Circuit Breaker Positions

    Features

    (2) Distribution Load Distribution Circuit Breaker Mounting Positions(800A GJ/218-Type) NOTE RESTRICTIONS

    Equipped with Shunts - One (1) for Each Circuit Breaker Installed

    1280A Maximum Capacity

    3/8" Bolt Clearance Holes and 3/8-16 Captive Nut for Load Lead Connections (accepts double hole lugson 1" centers)

    Distribution Shunts Factory Wired to LMS1000 Expansion Assembly

    Restrictions

    Provides up to two 4-pole GJ/218-type 800A circuit breakers.

    Maximum size of wire to be connected to a single circuit breaker position is 750 MCM.

    Maximum lug width, 1.937 inches.

    Ordering Notes

    1) Order circuit breakers and associated mounting kits as required perTable 8 (GJ/218-Type CircuitBreakers). NOTE RESTRICTIONS

    2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution positionperTable 12 (Lugs).

    3) Sales order must specify distribution module location on the order packet.

    List of PartsHome

    Page 48 of 84

    This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, EnergySystems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

  • 7/27/2019 SAG582121901_AH

    49/84

    System Application Guide SAG582121901Spec. No. 582121901 (Model 1231V1) Issue AH, January 26, 2009

    FRONT VIEWL. SIDE VIEW

    TOP VIEW

    582121901 List N (Part No. 514602)

    REAR VIEW

    LOADCIRCUIT

    BREAKERS

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    LOADCONNECTIONS

    LOAD RETURN

    CONNECTIONS

    TO OVERHEAD

    GROUND BUSBAR

    Shown asMounted in LeftSide of Bay.Module Rotated180 whenMounted in RightSide of Bay.

    Home

    Page 49 of 84