28
SABROE packaged ammonia heat pump

SABROE packaged ammonia heat pump · 2020. 9. 3. · Sabroe packaged ammonia heat pumps: Advantages • Compact design • Small ammonia charge • Evaporator and condenser in suitable

  • Upload
    others

  • View
    24

  • Download
    0

Embed Size (px)

Citation preview

  • SABROE packaged ammonia heat pump

  • Ammonia - the natural choiceAmmonia has a number of characteristics which make it the ideal refrigerant for future refrigeration purposes:

    • Ammonia is the only refrigerant with no negative impact on the environment

    • No ozone depleting potential (ODP)

    • No global warming potential (GWP)

    • A well-known and acknowledged refrigerant which has been used safely in refrigeration for more than 100 years

    • Ammonia has the best thermodynamic efficiency

    • A natural refrigerant which easily breaks down into nitrogen

    • If refrigerant leaks should occur they will be easy to detect, as the distinct smell of ammonia serves as a natural built-in alarm

    • It is inexpensive and significantly cheaper than other refrigerants

  • • Known technology and plant design• Better energy efficiency (COP)• Better heat transfer coefficient• Available and low-priced all over the

    world• Non-mixable with oil• Less sensitive to humidity in the plant• Smaller compressor - same capacity• Smaller heat exchangers - same

    capacity• Smaller circulated quantity

    Why choose ammonia?What are the advantages?

  • SABROE Ammonia heat pump compressorThe natural choice

  • The natural choiceSabroe ammonia 40 bar heat pump compressors

    Types HPO and HPC

    Features:

    • Ammonia is an ozone-friendly refrigerant• Heat pump systems reduce the CO2 emission• The series covers the entire water temperature range

    up to 70°C.• Compared with CFC, HCFC and HFC systems you will

    gain the following advantages:- higher efficiency (COP)- reduced compressor size- smaller evaporators- smaller condensers- smaller pipe and valve dimensions

    • Capacity range: 100-1500 kW (one compressor)• Multiple applications

    HPC104-106-108S

    HPO 24-26-28

  • Sabroe packaged ammonia heat pumps: Advantages• Compact design• Small ammonia charge• Evaporator and condenser in suitable materials • Efficient closed oil and oil recovery system • High COP and energy optimal solution even at part load• First charge of PAO5(P100) full synthetic oil• Unisab II - a complete control and monitoring system with

    external communication facilities• Flooded system with ammonia gives an optimum thermal

    solution and secures an optimum operating economy• Tested with ammonia before dispatch

  • EOL - End Of Line Test centre

    All units are tested with ammonia

    A capacity test is available as an option

    Specified performance is confirmedTrouble-free on-site start-up and operationShorter and safer start-up and commissioning periods

  • Sabroe packaged ammonia heat pump: Application areas

    Dairies Airports

    Process IndustriesPoultry industries

    Ice rinks

    SlaughterhousesBreweries

    District heating

  • ApplicationsSabroe ammonia heat pump compressors are perfectly suited for a large number of applications, such as:

    • Heat reclaim for hot/warm water production in ammonia refrigeration plants within the food industry (abattoirs, dairies, ice cream factories, fish processing, freeze drying, breweries, slaughter houses etc.)

    • Condenser heat reclaim from refrigeration systems

    • Upgrading of industrial waste heat for use in industrial processes, district heating, individual buildings, etc.

    • Heat pump systems based on natural heat sources such as sea water, air and geothermal energy

    • Special applications such as wood seasoning, fish drying, exhaust gas cooling in power plants, etc.

    • Heating in ice rinks or other sports arenas.

    • Hot water for baths and swimming pools.

  • One-stage heat pump unit:Example: Brewery/district heating

    Performance:Heating capacity 2131 kW Evaporating temperature +30ºCSink temperature in/out 60/70ºC Condensing temperature 73.5 ºCFlow 187 m3/h COP 5.6Shaft power 381 kW

  • 65ºC

    55ºC

    Two-stage heat pump unit:Combined chiller - heat pump unit

    Performance:Cooling capacity 210 kW Sink temp. in/out 55/65ºCWater temp. in/out 15/8ºC Flow 25.5 m3/hChilled water flow 26.1 m3/h Shaft power LP compressor 29 kWHeating capacity 290 kW Shaft power HP compressor 53 kW

  • Sabroe packaged ammonia heat pump:Cascade or water / one- or two-stage

    One-stage HPO26 Twin

    Two stage HPC108/SMC116 Twin

    One-stage HPO28 Twin

  • Sabroe packaged two-stage ammonia heat pump unit

    Technical informationProduct-type : Heat pumpCompressor type : Reciprocating compressors Electrical options:Heat exchangers : Plate heat exchangers / Terminal box

    shell & tube Control panel Refrigerant : R717, flooded Starter panel Capacity-range : 200 – 4000 kW (Low/high voltage, 50/60 Hz) Temperature range : 72oC water temperature Variable speed control

    on condenser Softstarter Secondary media : Water Approval : PED, others on requestDesign-pressure : 40 Bar A

    Two stage HPC108/SMC116 Twin

  • Sabroe packaged two-stage ammonia heat pump unit

    Technical information

    Duty (Condenser) : 4000 kW / 72 OC

    Media : Water

    Number ofcompressors : 4

    Power : 2x 250 kW / 2x 400 kWVoltage : 400 V

    Two stage HPC108/SMC116 Twin

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • Sabroe packaged ammonia heat pump: Application areas

  • NSPAC HPC108STraditional design of heat pump unit

  • Safe use of ammonia plants

    SABROE & YORK will support the use of natural refrigerants - invest and develop products for the purpose only!

    SABROE & YORK will support the use of R717 for many years to come - and is therefore reluctant to see this unique refrigerant fall into discredit due to lack of knowledge.

    Ammonia - the natural choiceWhy choose ammonia?�What are the advantages?SABROE �Ammonia heat pump compressor�The natural choiceThe natural choice�Sabroe ammonia 40 bar heat pump compressorsEOL - End Of Line Test centre ��ApplicationsOne-stage heat pump unit:�Example: Brewery/district heatingTwo-stage heat pump unit:�Combined chiller - heat pump unitNSPAC HPC108S�Traditional design of heat pump unit�Safe use of ammonia plants�