9/30/2020 VER 1.0 S-16 Introduction

S-16 Route Setting type Relay Interlocking

SURESH HELCHEL Instructor (Signal),IRISET/SC

Page 2: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 2

Siemens PI

Siemens RRI

Usually preferred for smaller yards. Used for major yards or busy sections.

Points in the route, overlap and isolation are operated individually prior to Signal clearance.

Points in the route overlap and isolation are operated automatically with the setting of route.

Minor Point group is used. Major Point group is used.

NWKR/RWKR are normally pickup. NWKR/RWKR are normally dropped, pick-up only when Sub Route and Overlap are set.

Difference between P.I & RRI

Page 3: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

3

Siemens PI

Siemens RRI

Before setting any point individually,

it shall be ensured that all relevant

U(R)S and OVZ2U(R)R are normal.

Point setting is done by concerned U(R)S,

OVZ2U(R)R. Locking provided at various

stages takes care of the same

Points in the route, overlap and isolation are operated individually before signal operation.

Setting of points in route, overlap, isolation and also clearing the signal is achieved by single operation of pressing the GN & UN buttons together.

Point chain group not used. Point chain group is used for auto operation of

point.

Difference between P.I & RRI

Page 4: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

4

Siemens PI

Siemens RRI

After individual setting of points,

locking of points for the route is

achieved through U(R)S and

OVZ2U(R)R

U(R)S and OVZ2U(R)R are meant for

operation of points; W(R)LR locks the point.

NWKR/RWKR required for AU(R)S

& BU(R)S Route section setting. Route Section A U(R)S and B U(R)S are used for operation of point, NWKR and RWKR proved in DUCR of Sub Route.

Difference between P.I & RRI

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 5: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

5

Point Major Group

Z1WR1 Z1NWR Z1RWR Z1WR WLR WKR1

W(R)R

W(N)R

(R)WLR1

(N)WLR1

(R)WLR2

(N)WLR2

(R)WLR3

(N)WLR3

W(R)LR

W(N)LR

WKR2

WR WJR Z2WR1 Z2WR2

TP1R TP2R WKR3

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 6: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

6

Point Major Group

Relay Purpose

Z1WR Point Group control Initiation Relay with Route setting.

Z1WR1 Point Group Control Initiation relay.

WLR Checks track locking and helps in sequential operation of point.

Z1RWR Normal to Reverse Control

Z1NWR Reverse to Normal Control

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 7: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

7

Relay Purpose

W(R/N)R

Used for point operation and detection mode circuit.

WR Point Contactor Relay (Heavy duty contact)

WJR Point Timer(10 Seconds)

WKR3 Checks the complete operation of point.

WKR2 Point Out of Correspondence Checking Relay.

Point Major Group

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 8: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

8

Relay Purpose

WKR1

Point Detection Relay

(R/N)WLR 1,2,3 Closes point operation circuit (locks point for operation)

Z2WR1 Panel indication control relay for Pt. track on running portion of line (Pt. track in route or OV set to main line)

Z2WR2 Panel indication control relay for Pt. track on OV set to sand hump

W(R/N)LR Point group locking relay

Point Major Group

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 9: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

9

Control Table S 1 to ML

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

1 S1 to ML 1GN ML

UN

4A,

1/9

4B OV10/2 OV2 5B OV3/2 4N 5N -

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

1T,9T,

10/11T,

4AT,

MLT

5AT,

2/3T

CH in S-2

RG,HG,DG

- A1T 1T 1T, 9T,

10/11T, 4AT

LC Closed

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 10: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

10

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

2 CO1 to

ML

1GN,

COG

GN

ML

UN

4A,

1/9

4B OV10/2 OV2 5B OV3/2 4N 5N -

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

- - CH in - - A1T - 1T, 9T,

10/11T, 4AT

120 sec. after 1AT

occupied;

LC Closed

Control Table S 1 C-ON to ML

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 11: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

11

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

3 S1 to LL

With

OV3/1

1GN LL

UN

4B,

1/9

4A OV11,

OV10/1

OV3/1 6A,

5B

OV3/2 4R 5N 6N

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

1T,9T,

10/11T,

4AT,

4BT,

LLT

5BT

CH in S-3

RG

Left A1T 1T 1T, 9T,

10/11T, 4AT,

4BT

LC Closed

Control Table S 1 C-ON to LL

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 12: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

12

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

4 Co1 to

LL

With

OV3/1

1GN,

COG

GN

LL

UN

4B,

1/9

4A OV11,

OV10/1

OV3/1 6A,

5B

OV3/2 4R 5N 6N

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

- - CH in - - A1T - 1T, 9T,

10/11T, 4AT,

4BT

120 sec. after 1AT

occupied;

LC Closed

Control Table S 1 C-ON to LL

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 13: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

13

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

5 S1 to LL

With

OV3/2

1GN LL

UN

4B,

1/9

4A OV11,

OV10/1

OV3/2 6A,

5A

OV3/1

,

OV2

4R 5R 6N

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

1T,9T,

10/11T,

4AT,

4BT,

LLT

5BT,5

AT,2/

3T

CH in S-3

RG,HG

Left A1T 1T 1T, 9T,

10/11T, 4AT,

4BT

LC Closed

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Control Table S 1 C-ON to LL

Page 14: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

14

S.

No.

Sig.

Route

Push

Buttons

In the route In the OV Points set

GN UN RS

Set

Eliminated OV

Set

Eliminated RT OV Iso

RS OV RS OV

6 Co11 to

LL

With

OV3/2

1GN,

COG

GN

LL

UN

4B,

1/9

4A OV11,

OV10/1

OV3/2 6A,

5A

OV3/1

,

OV2

4R 5R 6N

TC Clear Y/

LC/

CH

Signal

ahead

proved

RI

App.

Lock

TC

Sig.

ON

TC

Back lock

TC

Remarks

RT OV

- - CH in - - A1T - 1T, 9T,

10/11T, 4AT,

4BT

120 sec. after 1AT

occupied;

LC Closed

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Control Table S 1 C-ON to LL

Page 15: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

15

Signal Clearance Route initiation to signal clearance

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 16: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

16

Signal Clearance Route initiation to signal clearance

GNR Signal Button Relay

UNR Route Button Relay

Sh G(R/N)R Shunt Signal /Main Signal selection relay.

ZU(R/N)R Direction determining relay

Z1UR Sub Route Initiating Relay

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 17: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

17

Z1UR1 Diversion Selection relay, Normally drop for main line movement and picks up for diversion movement.

Sh GZR Shunt Signal Route Initiating Relay.

Mn GZR Main Signal Route Initiating Relay.

ZDUCR Zonal Route permissibility Checking Relay, depends upon number of zones.

Signal Clearance Route initiation to signal clearance

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 18: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

18

Z1UR1: Diversion Selection Relay

In case of RRI, NWKR and RWKR relays are normally drop. Hence to know the movement is initiated for Main line or For a diversion line Z1UR1 relay is used. o Z1UR1 is a Normally drop Relay.

o Front contact of this relay is for diversion line. o Back contact of this relay is used for straight line.

o Z1UR1 is named after the point number.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 19: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

19

S1

S10

S11 S12

S3

S2

4

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Z1UR1: Diversion Selection Relay

GNPR Loop Line

UNR

Loop Line

GNPR UNR

Z1UR1

OR

217

Mn Line

Loop Line

5

Page 20: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

20

Mn GZR and Sh GZR

Purpose: o Differentiate the path for initiation circuit of main and shunt signal. o Main signal and Shunt signal is initiated in two different path to

pick up ZDUCR relay

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Mn Signal Initiation (Selection) Relay. Sh Signal Initiation (Selection )Relay.

Page 21: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Sh

GNPR

Mn

GNPR

UNCR

GNCR

Mn

GZR

Sh

GZR

Mn

GZR

Sh

GZR

Sh

GZR ZDUCR

CO

GGNR

Mn

GZR Mn

GZR

Sh

GZR

1 2 3 4 5

Mn GZR: Main Signal Initiation Relay.

Sh GZR : Shunt Signal Initiation relay.

In the Route In the Overlap

1 Main Signal Initiation

2.Shunt Signal Initiation

3.Mn GZR

4.Sh GZR.

5.C-ON

S 15 Panel Interlocking (Siemens) IRISET Ver 1.0

Page 22: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

ZDUCR

Zonal Route Permissibility Check

S1

S5

Mn

GNPR

UNCR

GNCR

1 2

Z1UR1

Z1UR1

4B

U(R)PS

4A

U(R)PS

ZU(N)R

ZU(N)R

ML

UNR LL

UNR

4

Z1UR

S1

GNR

4

1.Main Signal Initiation Path

2.Shunt Signal Initiation Path Sh

GNPR

4

Z1UR

ML

LL

ZU(N)R

ZU(R)R

Page 23: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

23

o First relay to pick up in Signal Clearances. Checks the

permissibility for route initiation, it checks ……

o SH G(R/N)R Conflicting Signal.

o ZU(R/N)R Conflicting Movement.

o ZDUCPR After operation are dropped.

o EUYR & EUUYR DROPS no cancellation is in progress.

Checks that relays involved in stage ii is dropped

Conditions:

Signal button and Route button to be kept in pressed condition.

ZDUCR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 24: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

GZR & ZDUCR CIRCUIT

EUUYNCR

ZDUCPR

MN

GZR

SH

GZR COGGNR

ZDUCR

ZDUCR

2

MN GZR

3

SH GZR

SH GNPR

EUYR

EUUYR

4

SH GZR

MN GNPR

MN GZR

COGGNR

SH GZR

EUUYNR

EUYNR

EUUYNR

OUT IN

Between OUT and IN checks GN & UN button are pressed and the overlap s are not set

OV

Page 25: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Sequence : Route Permissibility to Sub-route lock

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

ZDUCR

U(R)PS U(R)PS RS With Point RS Without Point

OVZ2U(R)R

U(R)S

Point Group Control

Initiates,Z1WR

If point is not in

required position

Point Group Control

Initiates,Z1WR

If point is not in

required position

NWKR/RWKR

DUCR

U(R)LR

TPR

UDKR

U(R)S

NWKR/RWKR

GLSR

GN & UN Buttons are Released

Page 26: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

26

U(R)S and U(R)PS

Conditions to pick up U(R)S: oRoute is initiated i.e. Z1UR & ZDUCR are up. o Sub route is unlocked i.e. U(N)LR is up. o Conflicting Overlap is normal. o Conflicting Route section is normal.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 27: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

27

4 Z1UR

ZDUCR

4 B Z1UR1

OV 10/2 Z2U(R)R

4 A U(R)S 4 A U(R)PS

4 A U(N)PS

Sub Route initiation Relay

Checks Route is initiated.

Diversion selection Relay.

Conflicting Overlap is Normal.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 28: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

28

Point Group Control Initiation Z1WR

U(R)S OVZ2U(R)R

Z1WR

WLR

WWR

TPR ZDUCR Z1UR

Point Operation with Route Setting o U(R)S or OVZ2U(R) is pickup. o Z1WR Pikes up . o WLR Checks Route Initiation o WLR Checks Track Locking.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 29: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

29

Z1WR (Major Group only) o First relay to pick up in the point group under route initiation to operate the point in the route, overlap and in isolation. CONDITION o Route sections are set U(R)S o Overlap are set OVZ2U(R)R o Point is detected….. WKR1 Purpose: o To by pass the individual point operation button contact for auto operation of point.

Point Group Control Initiation Z1WR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 30: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

30

Point Group Control Initiation Z1WR

S1

S10

S11 S12

S3

S2

4

W(N)R

WR

WKR1

4 A

U(R)S 4 B

U(R)S OV-10

Z2U(R)R

OV-10/2

Z2U(R)R OV-11

Z2U(R)R

1 Z1WR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 31: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

31

Point Group Control Initiation WLR

WLR (Double Coil Relay) Point Locking Relay o It checks the conditions for Z1WR Point Group is initiated due to route setting Z1UR & ZDUCR is UP. o Point track locking condition (TP1P2R) o Helps in sequential operation of points (Z3WR)

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 32: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

32 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Point Group Control Initiation WLR

Page 33: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

33 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Point Chain Group Initating Relay Z3WR

Z3WR: Point Chain group Initiating Relay. o Normally dropped Relay. o Slow to release for smooth chain operation. Conditions: I. Z1WR up II. WLR up.

Page 34: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

34

Point Chain Group Initiating Relay Z3WR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 35: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

35 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Point Chain Group Relay WWR

WWR:Point Chain Group Relay I. Consist of 8 Neutral Relay. II. 8 Major groups can be arranged in one Rack. III. Each WWR correspond to one Major Group.

Page 36: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

36 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Point Group Control Initiation Z1WR1

Page 37: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

37 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Signal Clearance

Page 38: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

38 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Signal Lock Stick Relay GLSR

o This relay creates the condition for Signal Clearance. o Drops before signal clearance, to ensure One train One

Signal. o Slow to release to pickup G(R)LR.

Page 39: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

39

GR2

GLSR GLSR GLSR

G(R)LR GR1

1 2 3

Purpose of GLSR: 1. Creates condition for signal clearance GR1

up. 2. Slow to release to pickup G(R)LR. 3.GLSR drop use in signal clearance i.e.GR2. 4.After picking up of G(R)LR ,GLSR drops.

Signal Lock Stick Relay GLSR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 40: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

40

Conditions required to pickup GLSR: I. Route is initiated

o GZR o ZDUCR.

2. GN & UN buttons are in pressed condition. 3. Concerned Route Sections & Overlaps are set. 4. Holds through first Route Section.

Signal Lock Stick Relay GLSR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 41: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

11.8

S-2

GNR

EGNR

S-2

GLSR

GLSR

GPR1

GLSR

COULR2

S 2

U(R)S

S

OV1-4

Z2U(R)R

Mn

GZR

ZDUCR

OV-3

Z2U(R)R

OV2-4

Z2U(R)R

DM

UNPR

102 A

U(R)S

DL

UNPR

102 B

U(R)S

101 A

U(R)S

S-2

U(R)PS

Signal Lock Stick Relay GLSR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 42: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

42 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Signal Controlling Relay

GR1

Signal Controlling Relay No 1 o Made slow to release to prevents signal going

to danger, in case of track circuit flickering.

Conditions to pickup : o GLSR is pickup. o Signal Buttons are released. o Signal in advance is not blank. o OV is set and point is detected. o Track Circuits are free. o Points in the Route is checked by DUCR.

Page 43: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

S 20

S 18

S 19

OV- 18

OV- 19, OV2-18

UL

UP Main S 20 U(R)S 113 A

113 B

S 19

HECR

S 19

RECR

S 19

HECR

OV Tracks

OVZ2U(R)R

OV Point

N/RWKR

Berthing Track

113 A DUCR

113 U(R)LR

Track Circuits

in the run

S 20

UDKR

11.9

S-20

GNR

GLSR

GR1

EGNR

100 Ohms

5 Watt

500 Mfd

27

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

GR1

Page 44: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

44 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Signal locking Relay G(R)LR

Circuit Source of supply

GLSR Separate fuse.

GR1 Signal in advance

G(R)LR Same Group Supply

o Picks up through slow to release timing of GLSR(500-700 mile seconds

G(R)LR: o Provided for every main signal. o Locks the action done by the GLSR.

Page 45: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

45

Signal locking Relay G(R)LR

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 46: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

46 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Point Major Group

Page 47: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Super Imposed Operation and Detection. o Series mode of Operation. Criteria: o Left hand and Right hand cross over. o Right Hand Machine1 operates then Machine 2. o Left Hand Machine2 operates then Machine 1. Length of Operation: o 400Volts ACI up to 1.2 KM. o More Than 1.2 KM Point Switching Group is used. Groups Used: o RRI Installation Major RRI Group. o Chain Group for Route Setting type only.

Point Operation

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 48: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Position Of Point

Left Hand Cross Over

Right Hand Cross Over

NORMAL 1-1 A & 4-4A 2-2A & 3-3A

REVERSE 2-2A & 3-3A

1-1 A & 4-4A

Relays Normally pickup in the group:

Point at Normal W(N)R,WKR1,(N)WLR1,2,3,W(N)LR

Point at Reverse W(N)R,WKR1,(R)WLR1,2,3,W(N)LR

1-1a NC,3-3a ND,2-2a RC,4-4a RD

Field and group details

Page 49: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Points Control Initiation, Operation, Locking & Detection Sequence

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 50: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Point Control Initiation Sequence

TPR WWNR WNR EWNR

U(R)S OVZ2U(R)R

Z1WR1(1)

WKR3

WKR1

Z1WR

WJR

WKR1

Z1WR

W(R)R W(R)R

TPR

‘R’ Operation intended ‘N’ Operation intended

Z1RWR WKR3 Z1WR1(1) Z1WR1(2) Z1NWR Z1WR1(1) Z1WR1(2)

Control initiated Control initiated

Z1WR TPR

WLR

WWR

ZDUCR Z1UR

W(N)R

Page 51: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Point Operation Sequence

(R )WLR3

Z1RWR Z1NWR

WR

Z1WR1 Motor.

WJR

‘R’ Operation ‘N’ Operation

(R )WLR2

(R )WLR1

Z1RWR

WKR2 WKR2

WLR

Z1NWR

(N )WLR3

(N )WLR2

(N )WLR1

WJR WJR

Drops after 10 sec Drops after 10 sec

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 52: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Point Lock & Detection Sequence WR

Z1WR1

WKR3

WJR WKR2

WR

W(N)R

WKR3

WKR1

WKR3

WKR3(1)

W(R)LR

NWKR or RWKR Z2WR1 or Z2WR2

Motor

Page 53: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

53 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Z1WR1

Point Group Control Initiation

Z1WR1: First Relay to pick up, in major point group to initiate controls for point group during individual point operation. Z1WR1 picks up through Z1WR

pick up during route setting Z1WR1 1

WNR

EWNR

TP1P2R

WWNR

Z1WR

WLR

WWR

W(N)R

2 Z1WR1

W(R)R

Z1WR1

(N TO R )

TP1P2R

Page 54: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

54 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

WKR3 (N TO R ) Point Controlling Relay No 3

Normal to Reverse Operation:

WKR3 picks up twice

o With 60 Volts DC for breaking detection.

o With 110 Volts DC after complete operation.

(N)WLR3

W(N)R

Z1WR1

1 WKR3

W(N)R

B End

ND

A End

ND

N 110/60

B110 B 60

Page 55: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

55 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

WKR1 (N TO R ) Point Controlling Relay No 1

W(N)R

WKR2

WKR3

WJR ND

ND

WKR1

o Field controlling relay. o Detect the correct setting of point. o Coil of WKR2 ensures correspondence of

point. o WKR3 contact is proved to break detection for

Normal to Reverse operation. o WJR contact is proved to break detection for

Reverse to Normal operation.

B 60 N 60

Page 56: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

56 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

W(R)R (N TO R )

WNR

EWNR

TP1P2R

WWNR

W(N)R

WKR1

Z1WR1

Z1WR1 1 2

Z1WR1

W(R)R

Z1WR1

W(R)R

TP1P2R

Z1WR

WLR

WWR

o Dropping of WKR1 Causes

W(R)R to pickup.

o Z1WR1(2) to pickup as

Z1WR1(1) was up due to

W(N)R pickup contact.

Page 57: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

57 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

(N)WLR3

W(N)R

Z1WR1

1 WKR3

W(N)R

B End

ND

A End

ND

N 110/60

B110

B 60

WKR3 Drop as W(R)R pickup (N TO R )

Page 58: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

58 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Z1RWR (N TO R ) Reverse Control initiation

WNR

Z1NWR

WWNR

W(R)R

W(R)LR

W(N)R

(N)WLR Z1RWR

Z1RWR

Z1RWR 1

2

o First Coil of Z1WR1 is pickup

with the press contacts of

buttons.

oHence Second coil of Z1WR1

is pickup.

Page 59: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

59

WKR2 picks up.

•Z1RWR UP.

•WR DOWN.

•WKR2 PICKS UP THROUGH 270 Ohms Resistance and then sticks through its own contacts. Because feed to Z1RWR Second Coil will cut off ,When (R)WLR 3 picks up

WKR 2 (N TO R )

WKR3

WKR2

Z1RWR Z1NWR WKR2

WR

270 Ohms

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 60: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

60

WJR (N TO R )

Z1NWR Z1RWR

W(N)R

WKR3

WJR

WKR2

WJR 39 Ohms

250 mfd

(R)

WLR3

Z1WR1

WJR Point Timer Relay picks up…… o Z1RWR(2) is pick up. o WKR2 is pick up as out of correspondence

is established o Holding path is provided as Z1RWR will be

drop due to pickup of (R)WLR3. o WJR sticks through its own contact, and

control the feed for point operation for at least 10 Seconds.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 61: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

11.8 11.9 11.10

(R)WLR1 (R)WLR3 (R)WLR2

¾.19 WR

Z1RWR

(N)WLR1

(N)WLR3

(N)WLR1 (N)WLR2

(R)WLR Reverse control locking

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 62: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

62 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Z1RWR N TO R drops

WNR

Z1NWR

WWNR

W(R)R

W(R)LR

W(N)R

(N)WLR Z1RWR

Z1RWR Z1RWR

1

2 (N)WLR3

Z1RWR :

o First Coils up due to Button press contact,

hence second coil is prepared

o Z1RWR drop as (R)WLR3 Picks up

Page 63: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

63 S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Z1RWR drop

WNR

Z1NWR

WWNR

W(R)R

W(R)LR

W(N)R

(N)WLR Z1RWR

Z1RWR

Z1RWR 1

2 (N)WLR3

R2 220 Ohms

o Pick up of (R)WLR3 relay short the supply.

o Hence an resistance of 220Ohms is provided

Page 64: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

64

WR (N to R)

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

WR

W(N)R

Z1NWR

Z1RWR

WKR2

WJR

WR

o Due to high inductance of WR Coil, caused by its initial pick up current surge, back e.m.f is generated causes a high current to be discharge through rectifier across it and to avoid interference of this current with other circuit WR back contact is included.

o WR Once picked up it will remain in pickup condition via R3 resistance, so the current consumption will be reduced.

R3 600 Ohms

Page 65: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

65

Z1WR1 Drops (N to R)

2

WR

W(R)R

Z1WR1

Z1WR1

oFinally pickup of WR relay Cut off the supply of Z1WR1 relay.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 66: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

66

Point is in Normal. o Machine contacts no.2,2a(R.C) & 3,3a(ND) is making. o As a Right Hand Cross over machine no.1 will operate first and through the make contact of machine no.1 machine no.2 will operate.

Point machine operation (N to R)

WR

W(R)R

(R)WLR

RC(1ST M)

RD(1ST M)

RC(2nd M)

W(R)R

WR

W(N)R

B 110 N 110

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 67: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

Point Lock & Detection Sequence WR

Motor Z1WR1

WKR3

WJR WKR2

WR

W(N)R

WKR3

WKR1

WKR3(1)

W(R)LR

NWKR or RWKR Z2WR1 or Z2WR2

Page 68: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

68

WKR3 PICKS UP 110VDC(N to R )

WR

W(R)R

(R)WLR

B 110 N 110

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

RD(1ST M)

RD(2ND M)

W(N)R

W(N)R o WKR3 picks up by 110 V Operation supply to prove the “End of point” Operation. An resistance of 1000 Ohms /1W is provided across the coil of WKR3 relay, to protect the coil of this relay, when its picks up by 110 V.DC supply.

1000

Ohms

WKR3

Page 69: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

69

WKR 2 drops(N to R )

WKR3

WKR2

Z1RWR Z1NWR WKR2

WR

270 Ohms Pick up of WKR3 drops WKR2 relay.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 70: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

70

WJR drop (N to R)

Z1NWR Z1RWR

W(N)R

WKR3

WJR

WKR2

WJR 39 Ohms

250 mfd

(R)

WLR3

Z1WR1 Pick up of WKR3 drops WJR relay.

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 71: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

71

WR Drops (N to R)

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

WR

W(N)R

Z1NWR

Z1RWR

WKR2

WJR

WR

R3 600 Ohms

Page 72: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

72

W(N)R PICK UP(N to R )

WR

WKR2

W(R)R

W(N)R

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 73: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

73

WKR3 Drops(N to R )

WR

W(R)R

(R)WLR

B 110 N 110

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

RD(1ST M)

RD(2ND M)

W(N)R

W(N)R

1000

Ohms

WKR3

Page 74: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

74

WKR1 (Reverse Detection)

WKR2

WKR3

W(R)R

M2

NC

(R)WLR3

WKR1

WKR2

W(R)R RD 1ST MC

RD 2nd MC

(R)WLR3

WJR

W(R)R

S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0

Page 75: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

(R)WLR3 (R)WLR3

W(N)LR

W(N)LR

(N)WLR3

W(N)LR W(N)LR

W(R)LR

Z2 WR1

Z2 WR2

WK

R1

CH

(Y)N

R

B U(R)S A U(R)S

Z1WR

W(N)R

W(R)LR (Point locking)

Page 76: S-16 Route Setting type Relay Interlocking122.252.230.113/content/ppt/sig/S16.pdf · 2020. 9. 30. · S 16 Route Relay Interlocking (Siemens) IRISET Ver 1.0 Control Table S 1 C-ON

THANK YOU