84
RTU Installation & Operating Packaged Air Conditioning Unit .............................................................................................................................................. ..............................................................................................................................................

RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

  • Upload
    lambao

  • View
    327

  • Download
    6

Embed Size (px)

Citation preview

Page 1: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

RTU Installation & OperatingPackaged Air Conditioning Unit

..............................................................................................................................................

..............................................................................................................................................

Page 2: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

2

Index

1. SECURITY

2. NOMENCLATURE AND CHARACTERISTICS PLATE

3. DOCUMENT FOR COMMISSIONING

4. COMMISSIONING AND TESTING

5. LIFTING AND HANDLING

6. DIMENSIONAL DRAWINGS

7. PLACEMENT AND NSTALLATION

8. VENTILATION

9. TECHNICAL SPECIFICATIONS

10. CLIMANAGER ELECTRONIC CONTROL

11. ELECTRICAL DRAWINGS

12. CERTIFICATES

Page 3: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

3

SAFETY RECOMMENDATIONS

Use PPE for intervention in the unit. Goggles, gloves, boots, clothing

and helmet if necessary.

It is mandatory to follow the recommendations and

guidelines contained within the maintenance manuals,

labels and specific instructions. It is necessary to obey rules

and regulations in force.

Before of manipulating the equipment, check that the unit general

supply is cut to prevent electric shock.

To prevent accidents during installation, implementation or maintenance, is required to take into

consideration the following specifications. The implementation of the equipment as well as repair and

maintenance must be carried out by qualified personnel.

Always use the provided cooling connections for measuring pressure, vacuum or make charging

refrigerant. Before working on the refrigerant lines to remove any component or desoldering, it

should be empty. Welds must be performed by a qualified welder. rod to use 30% silver content at

least in all brazings.

Wear goggles and safety gloves for work. Always avoid skin contact

with the refrigerant and beware of parts or cutting elements of the unit.

Always ensure proper ventilation in the work area

Refrigerant leaks can cause:

Asphyxiation due to displacement of oxygen in the air in confined work areas and narcotic

effect or cardiac arrhythmia by inhalation of refrigerant.

Eye irritation and burns from splashing or skin contact:

In case of accident by inhalation of refrigerant act according to the following instructions:

Remove victim to fresh air. Keep the victim lying down and if the victim is unconscious, place him on

the side with the head facing sideways.

When in doubt or symptoms persist, seek medical attention

In certain circumstances, the scroll compressors the top of the housing and

the compressor discharge line may reach temperatures above 160 ° C.

In case of contact with eyes:

Page 4: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

4

If substance has got into eyes, immediately wash out with plenty of water for at least 15 minutes.

Never rub your eyes or skin if you have come in contact with refrigerant and do not allow the patient

to tightly shut the eyes. If contact lenses are used, they must be removed.

It is important to get the person to a doctor immediately.

In case of burn by refrigerant skin contact:

Immediately flush skin with plenty of water for at least 15 minutes, take off all contaminated

clothing immediately.

Do not cover the affected area with clothes, oil, bandages

Always use original spare parts to ensure proper operation of the unit.

You should only use the coolant shown on the nameplate of the unit. Always use refrigerants

premium. Never use other unapproved products. (Mixture of refrigerants, hydrocarbons, etc.). Use oils

recommended by the manufacturer, respecting the specifications of the oils.

If you install the indoor units it is necessary to pay attention to the

safety recommendations of working at heights, and as appropriate

restraint harnesses out.

Pay attention to the prevailing wind in the area. Removing the panels

with excessive wind may incur danger of injury from falling, keep in

mind that the panels can throw you off the working area due to wind

force effect

Page 5: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

5

NOMENCLATURE

R T U 1 045 I N S 4 W SSF

RTU: Rooftop Unit

1: Construction size

042: Nominal Power (refrigeration if there would be several values) In ARI conditions..

I: Application type (I: Reversible; Q: Only Heating; R: Only Cooling; S: Cooling & Gas Fired)

N: Compressors type (N: Standard; D: Digital Scroll; V: Inverter; O: Others)

P: Version: (S: Standard; F: Free Cooling; R: Recovery)

3: Electrical Voltage: (1: 230V/I/50Hz, 2: 230V/III/50Hz, 3: 400/III/50Hz non neutral, 4:

400/III/50Hz + neutral, 5: 230V/I/60Hz, 6: 230V/III/60Hz, 7: 400/III/60Hz non neutral, 8:

400/III/60Hz + neutral, 9: 440/III/60Hz + neutral, E: Special

W: Refrigerant: (F: R404A; W: R410A; Z: R407C; U: R407F; Y: R134A; L: R407A; E: R1234ze; H:

Water; N: None, nitrogen loading)

In addition to this coding, the equipment is defined by an assembly code. These codes are

three digits behind the letter A (Assembly).

Page 6: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

6

CHARACTERISTICS PLATE

All Roof Top Units have a characteristics plate with the following information:

The voltage on the plate should be respected, within the limits -10% / + 10%. It is your responsibility

to have proper mains voltage within limits. It is important to check that the voltage of the plate

matches the mains voltage.

The plate indicates the correct type of refrigerant. always use the refrigerant indicated on the plate at

its best. Avoid using refrigerant blends or other substances.

Note: For all communication with the

manufacturer is necessary to indicate the

machine's serial number. The first two

digits of the serial number indicate the

year of manufacture.

Page 7: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

7

COMMISSIONING AND TEST REPORT

CUSTOMER AND PROJECT SITE DATA

Customer:

Contact person:

Telephone contact:

Site Address:

models:

Serial number:

Date:

Dates for implementation:

GENERAL CONDITIONS:

- The following preparatory work must be performed prior to commissioning:

• Connect the power supply.

• Check the phase sequence.

• Differential protection of line power supply.

• Power supply equipment for 12 hours prior to commissioning.

• Connecting the air ducts and checking filters (air-air equipment).

• Hydraulic piping connected to the computer, filter the water entering the equipment and filling and

purging the hydraulic circuit (air-water equipment).

- It shall check thermal load demand for the launch of the team.

- The equipment should be placed in its final position. If access to the equipment should be

performed by auxiliary means, these are borne by the customer.

- Teams have adjusted load refrigerant from factory. Therefore, if required additional refrigerant

charge must be provided by the customer.

- The supply voltage of the equipment shall be final. The teams are exempt from warranty if the

implementation is not done with final tension.

- By sending the document for start-up documentation shall communicate safety and PPE required

for access to the facility.

- The document application startup should be sent at least 5 working days before the date of

implementation required.

- From sending the document to launch the availability of dates in the next 24 hours will be

confirmed.

Delays or subsequent treatment due to non-compliance of the points made in the document to be

billed.

Page 8: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

8

TECHNICIAN DATA

Made by:

Date of commissioning:

Unit ID

Model: RTU

Serial No.:

Refrigerant:

Electronic Control:

Version parameters:

ELECTRIC SECURITY TEST

1- General Check operation of switch:

- Cut off voltage properly

- Give all the thermal voltage / differential ON

2.- Check magnetic switches operation:

- Cut voltage properly in OFF

- Provides voltage properly when ON

3.- Check thermal relays to requested values

4.-Check earth continuity

5.- Check that access logs turbines and box stickers carry risk

Page 9: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

9

HEATING MODE TESTING REPORT

1- Check rotation direction of fans / pumps / compressors

2- Check sensors are working correctly:

3-

B1: Return air

B2: Supply air

B3: Air Ambient

4- Check cooling values on the technical sheet.

GROUP 1

GROUP 2

Refrigerant charge = gr Refrigerant charge = gr

Temperature Evaporation = ºC Temperature Evaporation = ºC

Superheating = ºC Superheating = ºC

Temperature

Condensation =

ºC

Temperature

Condensation =

ºC

Sub-cooling = ºC Sub-cooling = ºC

GROUP 3

GROUP 4

Refrigerant charge = gr Refrigerant charge = gr

Temperature Evaporación = ºC Temperature Evaporación = ºC

Superheating = ºC Superheating = ºC

Temperature

Condensation =

ºC

Temperature

Condensation =

ºC

Sub-cooling = ºC Sub-cooling = ºC

5- Check air sensor measurements :

Supply air flow = m3/hr

Temperature Ambient = ºC

Air Exhaust Temperature =

ºC

Temperature Difference = ºC

6- Check Electric Supply data:

Voltage = V

Frequency =

Hz

Cos Phi (0.8) =

Electric Power. =

kW

Intensity = A

Page 10: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

10

7- Make Freecooling operation heating the return air sensor and check the right

operation order of the components

(Outdoor Temperature/Enthalpy > Temperature/Return Enthalpy – Differential

Freecooling)

Outdoor air register / air damper 0-100% / mixed air 100-0%

Exhaust fans ON mixing damper 50-100%

Compressor 1

Compressor 2

8- Verify a defrosting cycle, and verify the standard operation

9- Verify that when turning off the machine and defrosting cycle is active, it turns

on in standard mode

Page 11: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

11

COOLING MODE OPERATION

10- Check thermal data of the cooling circuit in the testing sheet

GROUP 1

GROUP 2

Refrigerant charge = gr Refrigerant charge = gr

Evaporation Temperature = ºC Evaporation Temperature = ºC

Superheating = ºC Superheating = ºC

Condensation

Temperature =

ºC

Condensation

Temperature =

ºC

Sub-cooling = ºC Sub-cooling = ºC

GROUP 3

GROUP 4

Refrigerant charge = gr Refrigerant charge = gr

Evaporation Temperature = ºC Evaporation Temperature = ºC

Superheating = ºC Superheating = ºC

Temperature

Condensation =

ºC

Temperature

Condensation =

ºC

Sub-cooling = ºC Sub-cooling = ºC

11- Check sensors

Supply Air Flow = m3/hr

Temperature Ambient = ºC

Temperature Outdoor Air =

ºC

Temperature difference = ºC

12- Check the electric supply values:

Voltage = V

Frequency =

Hz

Cos Phi (0.8) =

Electric Power. =

kW

Intensity = A

13.- Produce a Free Cooling heating return sensor and check the correct order of

input components:

(Outdoor temperature / Enthalpy > Temperature / Enthalpy Return - Differential

Freecooling) fresh air dampers 0-100% / 100-0% mixing

Outdoor Exhaust Fans ON with mixing damper at 50-100%

Compressor 1

Compressor 2

13- Produce a high pressure switch failure circuit 1 / 2 / 3 / 4

14- Produce a low pressure switch failure circuit 1 / 2 / 3 / 4

Page 12: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

12

FINISHING AND PACKING INSPECTION

15.- Cleaning machine, check that there is no defect in appearance

16.- Check stickers and plate

17.- Check packing and handling parts

Page 13: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

13

SAFETY, TRANSPORT AND OFF LOADING RECOMMENDATIONS

HANDLING AND TRANSPORT

The unit must be handled carefully to prevent damage during transport. Please note the following

instructions:

Always carry and operate the equipment in its vertical position.

Never stack the equipment during transport.

To move the unit uses a forklift or hand pallet.

Do not remove the pallet until the machine is in its final location.

Before moving the unit, make sure that if it takes skies for container. The skies or skates for

containers should be used to get the equipment for transport in containers, but must be

removed after this operation.

If you move the machine using a pallet jack or forklift. Be careful not to damage the lower

parts of the machine to move the machine with a forklift or pallet jack. Check that the forks

can not damage the machine bottoms.

To facilitate the equipment rising by crane, the unit has two holes in each of the four lower corners for

the anchoring with slings. It must be used fabric slings with rings, separated by a brace to prevent

deterioration of the unit body.

Units are shipped on a wooden pallet under request. All machines are shipped properly packed and

protected. Accessories and technical documentation are inside of the units.

Page 14: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

14

The following checks should be taken into account upon receipt of the unit:

- The packaging is in perfect condition

- The outside of the machine is not damaged

- The equipment supplied is in accordance with the order placed.

- Hydraulic, refrigeration and sewage connections are not damaged (check condensate removable

tray).

- The accessories are inside the unit. Check that they have been delivered in accordance with relative

job.

Left: Hole in the corners to anchor slings. Right: Removable condensate tray.

If the product is damaged, it should be noted on the delivery note signed, a copy will be sent to the

factory in the shortest possible time. It is your responsibility to ensure that the goods have arrived in

perfect condition. Failure to indicate the damage and the absence of communication of the same

invalidate any claim. In the event that the product conforms to thereafter transport and maintenance

is your responsibility.

If units are going to remain stored until placement need to verify that they are located in a clean, dry

place. Avoid leaving the equipment packaged with protective film to the sun for long. The direct

sunlight over a period of prolonged exposure on the protective film may deteriorate paint equipment.

Check that all panels and the electrical panel are closed. Check inside remains protected circuits.

The units may be accompanied by matching structure or curb for placement. In the event that it is

included in the order, check the adjustment curb meets the specifications. If a rooftop curbe for

special adaptation to a pre-existing installation is going to be used, prior to manufacture the

customer approval is required to a drawing prepared by the technical office of Nortek Global HVAC, to

verify that the design meets the curbs need for installation. It is your responsibility to ensure that the

curb corresponds to the design shown in the drawings when material has arrived on site

INSTALLATION AND SET-UP

The final location of the unit will determine largely the proper functioning of equipment. For the best

performance use the following guidelines:

Upon receiving your unit, please inspect your machine and its components for damage during

shipping. Install the unit outdoors and away from heat sources. Before to install the equipment it is

important to check that the selected surface has sufficient strength to support the weight of the

Page 15: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

15

machine, vibrations and effort that it can transmit. Ensuring the integrity and security of the

installation.

Do not obstruct air inlet or outlet spaces of the unit to facilitate the air intake and exhaust flow and

avoid as far as possible recirculation of air into the unit.

To ensure proper operation of the equipment and allow access for maintenance, respect the

minimum distances recommended.

Install in their location on type silentblock shock absorbers

Make sure the electric panel is in good condition before making the electrical connection, and please

follow the guidelines:

Follow the wiring diagram provided by the manufacturer.

Note that models to 400V/III/50Hz have a supply connection to 5 wires, being always the grounding

in colour green-yelow.

Install appropriate protective device on the undertaken line, thermomagnetic or thermomagnetic

differential. In cases where it is installed more than a machine it must be provided of its own system

of protection to each line.

To calculate the section of wires of the supply connection it should be considered electrical data

provided in the unit´s nameplate and other factors such as the length of the supply connection, the

type of wiring used, etc.; always respecting current regulations for electrical installations.

START-UP

Before starting/using the unit, please make sure all screws are tightened securely and the electrical

connections are properly installed. If you have worked inside the machine check that you have not left

extraneous objects or tools inside, make sure there are no gas leaks and that both assembly units and

hydraulic connections have been made properly.

Before initial startup of the gear unit or after a prolonged standstill period it is recommended to

activate the sump resistor twelve hours in advance. If the resistor cannot be enabled early enough, the

compressor must be heated otherwise to separate the oil from the refrigerant. This operation is

important, especially at low ambient temperatures start-ups.

Connect the power supply and turn on the system following the instructions given in annex of

regulation. Check subcooling and overheating to verify that the refrigerant charge is appropriate to

the operating conditions. After having been working several hours, key system parameter should be

verified to be sure that the system is working properly or it is needed to make some adjustment.

Compare temperatures of evaporation and condensation with the design conditions. Check security

features.

Page 16: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

16

DIMENSION PLANS

SERIES 0000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

SERIES 0000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan includes transport pallet. Plan with short side supply.

Page 17: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

17

SERIES 1000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan includes transport pallet. Plan with short side supply.

Page 18: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

18

SERIES 1000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT

(SF)

Note. Plan includes transport pallet. Plan with short side supply.

Page 19: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

19

SERIES 2000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side supply, lateral return.

Page 20: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

20

SERIES 2000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT

(SF)

Note. Plan not includes transport pallet. Plan with long side supply.

Page 21: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

21

SERIES 3000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, upper return.

Page 22: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

22

SERIES 3000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side radial supply, lateral return.

Page 23: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

23

SERIES 3000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT (SF)

Note. Plan not includes transport pallet. Plan with long side radial supply, lateral return.

Page 24: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

24

SERIES 4000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, upper return.

Page 25: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

25

SERIES 4000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT (SF)

Note. Plan not includes transport pallet. Plan with long side radial supply, lateral return.

Page 26: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

26

SERIES 5000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, lateral return.

Page 27: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

27

SERIES 5000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT (SF)

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, lateral return.

Page 28: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

28

SERIES 6000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, lateral return.

Page 29: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

29

SERIES 6000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT (SF)

Note. Plan not includes transport pallet. Plan with long side centrifugal supply, lateral return.

Page 30: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

30

SERIES 7000, STANDARD ASSEMBLY WITHOUT UPPER RETURN UNIT

SERIES 7000, STANDARD ASSEMBLY WITH UPPER RETURN UNIT (SF)

Page 31: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

31

INSTALLATION AND COMMISSIONING

The air conditioning units are autonomous Reznor RTU compact air conditioning units. The following

diagrams indicate the outer dimensions of the equipment:

The final location of the unit will determine largely the proper functioning of equipment. Install the

condensing unit outdoors or a place with good air exchange and away from heat sources.

For installation of the equipment will be necessary to check that

the selected surface has sufficient strength to support its weight

and vibrations and efforts that can transmit, ensuring the integrity

and security of the facility.

Minimum distances for commissioning and maintenance

It is necessary to maintain the minimum clearances for maintenance and security. Clear the air intake

areas of the unit for easy intake and exhaust air, and avoid as far as possible the recirculation of air

into the unit.

To ensure reliable operation of the equipment and allow access for

maintenance, observe the minimum distances recommended.

In the case of installing multiple units next, avoid installing units too

close, so that it can restrict airflow to the condenser. Not respecting the

minimum distances can lead to malfunction of the unit.

Please check minimal distances drawings

In the case of installing indoor units it is necessary to pay attention to

the prevailing wind in the area. In areas of excessive wind you need to

check the placement of the registers and dampers covering parts, and

that they do their task properly

Before installing the equipment, make sure that they are to be installed on a clean surface free of

obstacles. Avoid non-horizontal surfaces.

When installing the equipment on the rooftop deck or on the bed, check that all lines are connected

correctly to take the unit, and properly seal ducts and intakes to prevent any air leakage during

operation of the unit.

For bench mounting adaptation, ensure that the unit is correctly placed over the curb and the

tightness of the whole rooftop unit and bench remains after assembly. A bad installation can lead to

air leaks. In some areas, a bad installation can mean that the rules of local regulations heating systems

Page 32: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

32

and fire protection are not met. The assembly of the rooftop unit and the curb is responsibility of the

customer.

Electrical installation

Check that the electrical installation of the work to local regulations

apply. Do not connect the units to provisional light work. The units must

be connected up in the final wiring. Check that the section of the wires

complies with current regulations under the conditions of operation. If

the unit is three-phase with neutral and ground, verify that the

installation is equipped with three-phase network with neutral and

ground. The unit must be connected to the network correctly. Otherwise

it may not make the launch.

Make sure that all connections are properly made machine before

putting the unit on. Check with the wiring diagram that all components

are properly seated and connected, especially the security features, such

as circuit breakers and the main switch.

To start the unit, check that all circuit breakers are open, and turn the

main switch. To start the unit you must have a thermostat control unit or

connect the remote maintenance CLIMANAGER regulation.

After opening the general cut-off switch if the contactor coils are turned all the elements will start.

Check the direction of rotation of the elements. Compressors and fan motors are equipped in header

with a phase control relay. The (standard) Basic model has only phase failure and direction of rotation.

The sophisticated model (optional) also detects phase unbalance, undervoltage and overvoltage. If all

parameters are correct, the compressors will properly rotate.

A compressor runs backwards makes an abnormal noise. The

compressor will turn upside down for a while until it fails completely.

Avoid rotating compressors backwards long

If any of the elements counter-rotating to the right, cut off the main supply voltage bycutting off the

main switch and reverse the two phases, until all elements rotate in right direction.

Page 33: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

33

CLEARANCES

Clearances must be respected according to below drawing. The safety distance must be respected in

order to access maintenance or replacement of items in case you need to install spare parts.

Units series 1000 to 3000.

It is recommended not to place any element in the discharge path

of axial fans or exhaust fans. If necessary, the minimum height to

respect for axial fans of the unit is 2500 mm. The same

consideration should be present in the equipment mounting

exhaust fans in option.

Page 34: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

34

Units series 4000 to 7000.

Series 4000; A = 2000. Series 5000 & 6000; A =2500. Series 7000; A = 3000

It is recommended not to place any element in the discharge path

of axial fans or exhaust fans. If necessary, the minimum height to

respect for axial fans of the unit is 2500 mm. The same

consideration should be present in the equipment mounting

exhaust fans in option.

Page 35: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

35

VENTILATION

Once it has been verified that all elements revolve right direction, connecting the gauges to measure

pressure and start the computers in cooling mode. Check readings of the manometers. The value of

the readings depend on weather conditions.

It must be checked the operation of all elements of the ventilation system. If the computer is

equipped with belt drive and pulleys, ensure correct installation of these elements. It is necessary to

check the operation of the dirty filter pressure switch, pressure switch air flow sensing probes, when

the units carry these items. Disconnect the circuit breakers of the fans and blowing units, and check

the high pressure reading gauges must be verified.

If the equipment is mounted with radial fans with electronic EC motors, it should be connected to the

computer with the right software and the set-point of the fan flow should be introduced into the

system.

Centrifugal fans are made of galvanized steel. EC radial fans can be of high strength polymers or

aluminum, depending on sizes.

The fans are suitable for outdoor air transport, free of particulate or corrosive vapors and gases. For

high humidity or excessive closeness to the sea should be consulted installing epoxy painted fans.

The fans are all mechanically balanced at the factory. When replacing a fan and

have to be transported and elevated, take special care to use separators chains

or slings to avoid damage to the fan.

The operating temperature limits of centrifugal fans are -20 ... + 45 ° C.

Page 36: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

36

Characteristics of the radial fans with EC motors.

The teams riding EC centrifugal fans backward curved blades series assembled a group of one or

more fans R3G500RA2501. Reference 0M002C001. For heavy duty facilities, this fans can be changed

by other references that withstand heavier flow and pressure operation. The following tables show the

characteristics of the standard EC fans.

Reference 0M002C001

Motor M3G150-FF

Supply Phases 3~

Nominal Voltage 400 (VAC)

Nominal Voltage range 380 … 480 (VAC)

Frequency 50/60 Hz

Nominal velocity 1700 rpm

Max. Absorbed Power 2680 (W)

Intensity Absorbed 4.2 (A)

Min. Temperature in ambient -25ºC

Máx. Temperatue in ambient 60ºC

Page 37: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

37

These fans have three phase motors and have speed regulation by electronic switching. The units

comprise a pressure transducer for control that is located on suction plenum fans.

Page 38: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

38

Page 39: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

39

Page 40: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

40

Radia EC fan curve / 0M002C001( R3G500RA2501)

Commisioning the radial fan

The configuration of the electronic radial fan is only necessary to do it in connection differential

pressure transducer air. In case of several fans, the fan configured will act as Master mode and the

other assembled radial fans will act in Slave mode. It is therefore necessary to make settings for these

fans.

For fan configuration should be used "EC CONTROL" software. Connection with an electronic radial

fan with potentiometer.

CONNECTING TWO RADIAL FANS WITH POTENTIOMETER

Page 41: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

41

Page 42: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

42

SCHEME OF POSITION AND CONNECTION OF PRESSURE SENSOR.

The sensor is connected by a ¼ " flexible hose, affirmative decision is connected to the suction side

(the outlet must be perpendicular to the direction of air)

Page 43: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

43

Centrifugal fan units with belts and pulleys

For equipment with motor driven centrifugal fans with coupling pulleys and belts, is necessary to

check at receiving equipment the belts are positioned correctly and stressed. All equipment is tested

at the factory, so that the belts have operated for testing at least 10 hours. However during transport

they may slacken. Is necessary to check the belt tension, the axle alignment and positioning of the

boss or tappers. Normally if the belts are not positioned correctly produce abnormal noise.

To tighten the belts, using the motor mount screw. To measure

the belt tension can be used the method of force - deflection.

Applying a force perpendicular to the belt, you should check that

the recommended deflection is 15.7 mm per meter from center to

center.

The belts must be replaced when they fail to properly stress or when show visible damage. Excessively

loose belt can slide and this generates heat and may result in premature deterioration of the strap

and its ruling. On the other hand if the belts are too tight, it can cause failure of the same or becomes

excessively suffer bearings fans and motors, which can in turn fail. Typically fails fan shaft bearing.

The most appropriate method to control and measure the tension is to use a suitable gauge, usually

supplied by the suppliers of belts. There are also electronic meters that are more accurate. In case you

need to change the belts for wear and tear over time, it is always recommended to check the original

specification and use original belts or the same quality as the original. Poor selection of the belt can

lead to a serious failure of other components such as the fan or motor.

Pulleys

The fans are equipped with bearings designed with a rated average life 40,000 hours of operation.

(L10 according to ISO 281-1), provided they do not exceed the load limit. Not to exceed the limit load

is recommended not to install smaller diameter pulleys to the minimum diameter. Minimum pulley

diameters are applicable provided that the straps are tensioned according to specifications. Excessive

belt tension can lead to premature deterioration of bearings or even fan shaft breakage.

The following table shows the minimum diameters of the pulleys to be installed in the AT fans voltage

conditions suitable belts, depending on engine power. The maximum recommended number of belts

is two. Only under certain conditions it supports up to three belts.

Page 44: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

44

To proceed to change pulleys, unscrew the screws (3), tighten the Allen head screw (4), press the hub

and remove the pulley.

To proceed to fix the pulley, pull the pulley and the hub and place the allen head screw (3) connecting

the two parts. Align the motor pulley and the fan, exactar way, using an aligner, and place and tension

the belt according to instructions.

Axles and bearings

The fan shafts are made of carbon steel C40. The axes are equipped with a

keyway. The axes are protected against corrosion. The bearings are maintenance-

free, and use grease lubrication high performance and high durability. In case of

continuous use at high temperatures or has exceeded the hours of operation, can

be relubricated using recommended fat

A IWN 01 - Standard grease, Gadus S2 V100 3

A IWN 11 - Klüber-Staburags NBU12/300KP

Page 45: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

45

FAN AT 15-11 PERFORMANCE

FAN AT 15-15 PERFORMANCE

Page 46: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

46

FAN PERFORMANCE AT 18-13

FAN PERFORMANCE AT 18-18

Page 47: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

47

FAN PERFORMANCE RDH 355

FAN PERFORMANCE RDH 400

Page 48: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

48

The following table lists the fan models and pressure drops in the various elements of equipment as

standard construction. For dimensioning the transmission has to take into account the fan model, the

available pressure and flow required in the installation required.

The capacity of the equipment can vary generally ± 20% from the nominal values, except models 200

and 230, the maximum flow rate is 15%, without application of the mist eliminator. The optional stop-

drop can be used to exceed the value of flow rate up to 5% more than the maximum, or for

applications where moisture conditions are very high and the production of excessive condensation,

to protect facilities crawl drops.

Model

Standard

Centrifugal

Fan

Standard

Fan

Number

Indoor

Air

flow

(m3/h)

options

Indoor

coil

press.

drop

(Pa)

Indoor

.coil Rec. Unit

pressure

drop (Pa)

Prefilter

pressure

drop PPI

15 (Pa)

Filter

pressu

re

drop

G4

(Pa)

FIlter

pressu

re

drop

F6

(Pa)

Filter

pressu

re

drop

F7

(Pa)

Filter

pressu

re

drop

F8

(Pa)

Filter

pressu

re

drop

F9

(Pa)

Water

heating

coil

Mist

elimin

ator

(Pa)

Availa

ble

pressu

re (Pa)

(Pa)

(Pa)

1039 AT 15-15 S 1 6800 45 15 20 38 109 160 179 208 212 30.15 32 100

1041 AT 15-15 S 1 6800 45 15 20 19 96 146 160 180 184 30.15 19 100

1044 AT 15-15 S 1 7400 50 17 20 23 99 149 164 186 190 33.5 22 100

1045 AT 15-15 S 1 7400 50 17 20 23 99 149 164 186 190 33.5 22 100

2050 AT 15-15 S 1 8900 40 13 25 33 106 157 175 201 206 26.8 29 120

2060 AT 15-15 S 1 10300 50 17 25 22 98 148 163 184 188 33.5 21 120

3070 AT 15-15 S 1 12000 50 17 25 30 104 154 171 196 201 33.5 26 120

3080 AT 15-15 S 1 13300 55 18 25 25 101 151 167 190 194 36.85 23 120

4090 AT 18-18 S 1 15400 50 17 25 22 98 148 163 184 188 33.5 21 150

4095 AT 18-18 S 1 15400 50 17 25 22 98 148 163 184 188 33.5 21 150

4100 AT 15-15 S 2 17700 60 20 30 29 103 154 170 195 199 40.2 25 150

5120 AT 15-15 S 2 19800 46 15 30 20 96 147 160 181 184 30.82 19 150

5135 AT 15-15 S 2 22700 43 14 30 18 94 145 158 177 181 28.81 18 150

5140 AT 15-15 S 2 23500 46 15 30 19 96 146 160 180 183 30.82 19 150

5150 AT 15-15 S 2 24900 50 17 30 21 97 148 162 184 187 33.5 20 150

6170 AT 18-18 S 2 28600 80 20 30 28 103 153 170 194 198 40 25 150

6200 AT 18-18 S 2 31900 70 18 30 35 107 158 176 204 208 35 30 150

7230 AT 18-18 S 3 37800 75 19 30 32 105 156 173 199 203 37.5 27 150

7260 AT 18-18 S 2 39000 75 19 30 32 105 156 173 199 203 37.5 27 150

7300 AT 18-18 S 3 42500 75 19 30 32 105 156 173 199 203 37.5 27 150

For the purpose of calculating the transmission must be added losses of standard features, indoor

coil, indoor air channel, the losses of the corresponding filters of the unit, and the available pressure.

The sum of these values gives the total static pressure for selection of the fan.

Page 49: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

49

If the airflow is not the nominal value, it must be corrected by a factor equal to the ratio of the flow

squared. With the value of the pressure and flow rate, it is entered in the chart of the fan, and

electrical power consumption and speed of the fan is obtained. The motors are fitted as standard IE2

high efficiency, so that the value of the power required to be increased inversely with the engine

efficiency. The engine speed is used to select transmission. The ratio of the diameter of the smallest

and largest pulley must be equal to the ratio between the recommended regimen of graphic rotation

and the rate of nominal rotation of the electric motor. Conventional engines used on rooftops, unless

specific constructs are four poles. You should always check that the size of the pulleys are eligible for

motor shafts and fan to avoid mechanical failure.

In any case, it is recommended to consult Reznor technical department with plant data for selecting

items that best suits the particular application.

In special applications are available centrifugal fans with backward curved blades or reaction, for

working with higher pressures available than standard fans action.

Page 50: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

50

EXTERNAL FANS OPTIONS

Equipped with axial AC as standard construction HyBlade® outdoor fans, which are designed and

manufactured with the highest quality standards, built with an innovative and unique support

structure coated aluminum blades constructed reinforced plastic fiberglass. Its aerodynamic shape

results in a huge reduction of noise while also increases the efficiency compared to conventional

blades.

Groups of serial axial fan assembly motors two speed motors class F, IP54 protection and internal

thermal protection, low noise and low weight, factory balanced for less vibration and external

protection grille lacquered with polyester.

Rooftop Low noise High Efficiency +

Low noise

Standard

Fan AC

High Energy

Efficiency Powered fan

1039 Axitop Axitop + EC 800-6 AC 800 EC -

1041 Axitop Axitop + EC 800-6 AC 800 EC -

1044 Axitop Axitop + EC 800-6 AC 800 EC -

1045 Axitop Axitop + EC 800-6 AC 800 EC -

2050 Axitop Axitop + EC 2x800-8 AC 2x800 EC 2x800-6

2060 Axitop Axitop + EC 2x800-8 AC 2x800 EC 2x800-6

3070 Axitop Axitop + EC 2x800-8 AC 2x800 EC 2x800-6

3080 Axitop Axitop + EC 2x800-8 AC 2x800 EC 2x800-6

4090 Axitop Axitop + EC 2x800-6 AC 2x800 EC -

4095 Axitop Axitop + EC 2x800-6 AC 2x800 EC -

4100 Axitop Axitop + EC 2x800-6 AC 2x800 EC -

5120 Axitop Axitop + EC 2x800-6 AC 2x800 EC -

5135 Axitop Axitop + EC 2x800-6 AC 2x800 EC -

5140 Axitop Axitop + EC 4x800-8 AC 4x800 EC 4X800-6

5150 Axitop Axitop + EC 4x800-8 AC 4x800 EC 4X800-6

6170 Axitop Axitop + EC 4x800-8 AC 4x800 EC 4X800-6

6200 Axitop Axitop + EC 4x800-6 AC 4x800 EC -

7230 Axitop Axitop + EC 4x800-6 AC 4x800 EC -

7260 Axitop Axitop + EC 6x800-6 AC 6x800 EC

7300 Axitop Axitop + EC 6x800-6 AC 6x800 EC -

Ventilation options for the condensing unit of rooftops we contemplate the option of High Energy

Efficiency with axial fans with EC technology and electronic control of condensation (High Energy

Efficiency), Low Sound, enhanced axial and radial centrifugal fans with available pressure for indoor

installation with ducted air condensation, all available with AC or EC motors. Units are prepared in

standard with condensate tray in the outdoor unit for indoor installation technical rooms.

Page 51: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

51

Axitop is a diffuser which is placed directly over the fence of axial fans diameters 800 and

910, and that reduces the noise level of acoustic pressure directly up to 7.2 dB (A). It can also

be used to enhance the fan, giving a 9% performance.

Before beginning assembly, make sure the engine model corresponds to the model supplied AXITOP. Several types of AXITOP depending on the engine and the diameter of the nozzle. To do so check the label (see diagram above). Check that you have the support rings (A) and the terminal box (E).

Example

Page 52: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

52

Position the fan with the support ring, making sure the press screwed into the final assembly position

pointing downward (this only applies to vertical mounting). Insert and tighten the screws. Then

proceed to the connection of the terminal box, being careful to follow the same order of wiring was

observed when removing the connection. In the case of engines 150 (of size 910 fans), install the

cooling tube (see picture)

Finally, mounting the diffuser as shown in Fig. If the diffuser is removed, it must be mounted to be

placed on the fan.

Page 53: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

53

Left: diffuser mounted. Right: dismantled internal diffuser placed on the EC motor.

Left: assembling outer diffuser. Right: outer diffuser placement on the EC motor

Left: Mount protection grid. Right: placing external connection box

Page 54: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

54

Assembly and filter replacement

The access panel of the indoor unit provides access to maintenance of filters and motorized

dampers. The graph on the left shows the position of the main elements of the indoor unit

mounted active recovery.

The image shows a unit with EC radial fans in drive, mounting free cooling and three registers, and

return centrifugal fan mounted filters before the coil. The photo on the right shows a detail of the F7

compact filters in its rails. The rail allows the extraction of the filters easily for replacement and

cleaning. The rails are removable and are completely painted with epoxy-polyester paint thermally

oven-cured.

Standard equipment incorporate a pre-filtration stage and up to two stages of filtration. The filters are

mounted in a self-supporting structure made of galvanized sheet steel painted with epoxy-polyester

paint oven cured, removable rating and air leakage L2 according to the EN1886 standard.

Optionally, depending on the type of installation, the equipment can also manufacture:

- Only the prefiltration step

- With the prefiltration step and a filtration step

The pre-filtration stage can be set from the following types.

- Prefilter very low pressure drop, washable 15 mm thick.

- Prefilter efficiency G2, G3 or G4 extractable metallic rail painted galvanized steel 25 mm wide,

cleanable.

The electronic control allows EC radial fans by keeping the air flow, which will regulate according to

the fouling of filters.

Page 55: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

55

Hot water coils for heating

The hot water coil is an optional recommended in applications where the outdoor temperature drops

below 5 ° C a high number of hours during the year. The backup coil is a tube and fins heat exchanger

for hot water with two rows. The hydraulic connections are located inside the supply air module.

The backup coil optionally assembles hot water valve three-way on / off or proportional valve

actuator.

The use of glycol for freeze protection for all applications is recommended. In low temperature

conditions the use of glycol is mandatory, as it is the only protection against freezing. When the

installation is left unused for a long time, you should check that the facility is clean, drained and

empty water. It is important to remember that the mixture of monoethylene in the presence of air can

cause corrosive agents. Check that the circuit has drain valves at a low point to allow emptying of the

installation.

It should be checked that the hydraulic system has traps in the highest point of the pipe to allow the

purging of air.

Use glycol to protect the coil from freezing. The warranty does not

cover damage caused by freezing the coil.

Electric heaters for heating

Electric coils are built to support independent modules which are mounted on brackets inside the unit

module, next to the cooling coil.

Electric coils are formed by modules of finned steel tube 1, 2 and 3 kW. The resistors feature a

thermistor high temperature safety.

Model RoofTop Low Power Medium Power High Power

Serie 1000 12 kW 18 kW 27 kW

Serie 2000 y 3000 27 kW 36 kW 45 kW

Serie 4000 y 5000 36 kW 45 kW 54 kW

Serie 6000 y 7000 54 kW 72 kW 90 kW

Page 56: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

OPERATION LIMITS

The specially designed frigorific circuit equipment "CR" allows efficient and reliable operation in

all weather conditions refrigerated between -8 ° C and + 48 ° C as standard and up to + 52 ° C in its

Tropicalized option without changing coolant. In heating mode, the "CR" units allow operation in

wet conditions environmental temperature between -10 and + 18 ° C.

AIR TEMPERATURE OUTDOOR CONDITIONS INSIDE UNIT CONDITIONS

STANDAR MINIMUM MAXIMUM MINIMUM MAXIMUM

COOLING - 8ºC +48 ºC 14ºC BH 22ºC BH

HEATING -10 ºC BH +18 ºC BH 10 ºC 27 ºC

TROPICALIZED MINIMUM MAXIMUM MINIMUM MAXIMUM

COOLING - 8ºC +52 ºC 14ºC BH 22ºC BH

HIGH TEMPERATURE R134A MINIMUM MAXIMUM MINIMUM MAXIMUM

COOLING - 8ºC +55 ºC 14ºC BH 22ºC BH

Page 57: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

57

TECHNICAL SPECIFICATIONS

The Reznor RTU roof top units are manufactured in steel sheetmetal structure of high mechanical

strength and corrosion resistance.

Main features

- Optimized design for HCF-410A refrigerant.

- High energy efficiency with full load and partial load which reduces operating costs.

- Low noise level through the high performance fans, as well as the anti-vibration silent-blocks

assembled for compressors and refrigerant circuits.

- Centrifugal fans, or optionally radial plug-fan with EC motor in impulsion and return.

- High performance electronic control until four phases.

- Easily integrated with communication systems.

- All components and the control are checked and tested in the factory..

- Designed and conceived for maintenance. All components are near to the machine’s perimeter

for a better maintenance and ease of service.

Developed with the HFC410A a non-ozone depleting refrigerant with high performance latest

generation scroll compressors developed by top brands, control by advanced microprocessor and

high performance fans made of a composite material.

All these options are designed to simplify installation to simple operations such as refrigeration and

electrical connection. The design of the units is also conceived for maximum access for maintenance

and service, saving money and time throughout its operational life.

The Reznor rooftops include the latest technologies into its components and they have been

laboratory tested under extreme conditions, proving that they are capable of operating in a wide

range of climatic conditions of functioning. Our laboratories are continuously working on

performance and durability tests in permanently monitored conditions, this allows our teams of

technical specialists develop new solutions that are tailored to the needs of our customers.

Page 58: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

58

Structure

The Reznor rooftops are manufactured as standard with self-supporting chassis of galvanized steel

high zinc content. Some non-structural elements are made of aluminum for weight reduction. All

machine parts are coated with oven cured polyester paint treatment.

The stainless steel condensate pan is removable for an easy cleaning.

Structure finishing details: On the top left, stainless removable isolated pan; on the top right, F7 filtering section, structure

completely painted with thermally treated powder paint; at the bottom left, corner detail totally painted inside and out; at the

bottom in the middle, motorized gate made of aluminium and completely painted inside; at the botton right, air tightness

draught excluder and completely painted inside.

Optionally, it is posible to produce the series AL 5000 equipments with galvanized steel self-

supporting frame and non-structural aluminium panels with high corrosion resistence.

Page 59: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

59

Frigorific Circuit

High efficiency designed in staggered rows coils of copper tubes and high performance aluminium fins.

The condensate pan is incorporated in the external coils of reversible models standard chassis,

allowing the assembly of the equipment in an indoor technical room or designated áreas, maintaining

the floors clean.

Hermetic compressors scroll technology,

with acoustic insulation as standard,

mounted on anti vibration supports. It

includes check valve in all compressors

discharge, either internal or external

mounted and discharge temperature

sensor.

Full charge of refrigerant from factory.

Thermally isolated in all cold metallic lines

of refrigerant or water.

Electrical board with compressor protection

relay with detection of phase loss, phase

equilibrium control and rotation.

Carter resistance electric heater for heat

pump design.

Thermostatic expansion valve with external

equalisation specifically seleted for each

heat exchanger that can be used as

evaporator. Heat pump systems are

equipped with two expansion valves, one

of them for de internal exchanger and the

other for the external one.

Anti acid dehydrating filter, accumulator

tank of refrigerant liquid in the heat pump

systems and refrigerant liquid viewfinder.

Four ways cycle reversing valve for heat

pump systems. Defrost cycle through cycle

reversing by four ways valve.

Droplet separator in aspiration of

compressor standard in heat pump version.

Protections

The following protections are included as standard:

- Pressure switch of low and high pressure, and thermostat of high temperature of compressor

discharge

- Differential pressure switch of dirty filter as standard, optionally for F filters.

- Thermal protection of compressor, thermomagnetic and protection relay of phases.

Differential switches as optional.

- Thermomagnetic switch for the supply line of fans

Page 60: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

60

- General switch in electric panel.

- Transport packaging for maximum protection, with pallet of reinforced wood and

phytosanitary treatment according to international transport regulations.

- Design of enhanced evaporator in only-cooling systems

External and internal ventilation

Internal fans are equipped in centrifugal supply and return version as standard, and optionally in

radial backward curved fins with EC motor incorporated.

The machines are equipped with HyBlade® axial external fans as standard, constructed with an

innovative and unique support structure of aluminum coated fins made of reinforced plastic with

fiberglass. Its aerodynamic shape results in a huge noise reduction while as well increases its efficiency

comparing with other traditional fins.

Axial motor-fan units of two speeds as standard, with motor class F, protection IP54 and thermal

internal protection, of low noise level and reduced weight, they have been balanced in factory for less

vibration with external protection grid lacquered with polyester.

Among the options of the condensing ventilation there is the high energy efficiency option

with axial fans with EC technology and electronic control of condensation (XEE), low noise level (LNA),

axial enhanced fans and centrifuge radials with available pressure for indoor installation with

condensation driven air, all of them available with motor AC or EC. The standards units are prepared

with condensate pan in the internal unit for its installation in indoor technical rooms.

Electronic control

The Reznor RTU rooftop equipment integrates the electronic control platform CLIMANAGER that

allows the air-to-air heat pump system complete control. It also allows the following elements

connection:

- Other platforms CLIMANAGER or PCO

- Temperature and/up humidity probes (up to maximum 6 units)

- Network analyzer (energy analyzer)

- Electronic EBM fans

- Gates servomotors.

- Electronic Expansion Valves driver modules

- Inverter Compressor driver modules

- Digital-Scroll Compressor driver modules

The CLIMANAGER platform can use three different types of connectivity systems:

1- By BMS platform it can be connected to a technical management system centralized in RS485

or Ethernet connection and using the communication protocols Carel, Modbus, LonWorks,

BACnet, Ethernet or Konnex.

2- By Field-Bus platform it allows the communication with probes and other equipments in

RS485 connection and MODBUS protocol.

3- By pLAN platform it allows the with PDG1 / remote PLD PRO (up to 2 units) and other

CLIMANAGER platforms.

The board is prepared to be able to remotely connect with another devices (up to maximum 15 units)

by a PGD1 control without any optional element (TCONN card only).

Page 61: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

61

COOLING SCHEMES

COOLING ONLY UNIT

HEAT PUMP UNIT

Page 62: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

62

NOMINAL POWER TABLE

Model 0017 0020 0022 0026 0030 0035 0039 0044 1039 1041

Size 0 0 0 0 0 0 0 0 1 1

Indoor air flow (m3/h) 3300 3700 4000 4600 5100 6000 6800 7800 6800 6800

Only cooling rooftop

Refrigeration capacity (kW) Gross 17.8 20.7 23.1 25.8 30.5 34.2 37.5 43.3 41.3 42.5

Refrigeration capacity (kW) Net 17.5 20.3 22.7 25.2 29.7 33.3 36.5 41.9 40.4 41.6

Refrigeration sensitive capacity (kW) 13.3 15.6 17.3 19.3 22.5 25.6 28.4 32.7 28.8 29.2

Sensitive Heat Factor 0.7 0.8 0.7 0.7 0.7 0.7 0.8 0.8 0.71 0.70

Compressor Absorbed Power (kW) (1) 4.9 5.8 6.4 7.0 8.5 9.3 10.3 12.7 10.9 10.6

Compressor nominal current (A) 8.9 10.5 11.6 12.6 15.4 16.8 18.6 23.0 19.1 24.3

Total absorbed power (kW) 5.7 6.6 7.6 8.4 10.1 12.1 13.2 15.9 13.5 13.2

EER Gross 3.6 3.6 3.6 3.7 3.6 3.7 3.6 3.4 3.2 3.4

EER Net 3.2 3.1 3.1 3.1 3.0 2.8 2.9 2.7 3.1 3.3

Clasification A A A A A B B C A A

Heat pump unit reversible rooftop

Cooling mode

Refrigeration capacity (kW) Gross 17.7 20.6 23.0 25.6 30.3 33.9 37.1 42.9 40.6 41.6

Refrigeration capacity (kW) Net 17.4 20.2 22.6 25.0 29.5 33.1 36.1 41.4 39.7 40.7

Refrigeration sensitive capacity (kW) 13.2 15.5 17.2 19.2 22.4 25.4 28.2 32.5 28.4 28.8

Sensitive Heat Factor 0.76 0.77 0.76 0.77 0.76 0.77 0.78 0.79 0.71 0.71

Compressor Absorbed Power (kW) (1) 4.9 5.8 6.4 7.0 8.5 9.3 10.3 12.7 11.3 11.58

Compressor nominal current (A) 8.9 10.5 11.6 12.6 15.4 16.8 18.6 23.0 19.6 25.4

Total absorbed power (kW) 5.7 6.6 7.6 8.4 10.1 12.1 13.2 15.9 13.9 14.2

EER Gross 3.60 3.60 3.60 3.70 3.60 3.70 3.60 3.40 3.15 3.16

EER Net 3.20 3.10 3.10 3.10 3.00 2.80 2.90 2.70 2.98 3.00

Clasification A A A A A B B C B A

Heating mode

Heating Power (kW) 18.8 21.6 24.4 27.1 32.2 37.3 41.3 46.7 40.4 42.0

Compressor Absorbed Power (kW) (1) 4.5 5.1 6.2 6.4 7.7 9.0 10.1 11.8 10.07 11.3

Compressor nominal current (A) 8.1 9.2 11.1 11.6 13.9 16.3 18.2 21.3 18.5 24.4

Total absorbed power (kW) 5.3 5.9 7.3 7.8 9.3 11.8 13.0 15.0 14.3 15.5

COP Gross 4.1 4.2 3.9 4.1 4.1 4.0 4.0 3.8 3.46 3.26

COP Net 3.5 3.5 3.3 3.4 3.4 3.1 3.1 3.0 3.42 3.23

Clasification A A B A A C C C A B

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(4) Nominal absorbed power (compressor motors, external and internal standar fan)

Page 63: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

63

Model 0017 0020 0022 0026 0030 0035 0039 0044 1039 1041

Size 0 0 0 0 0 0 0 0 1 1

Internal air flow (m3/h) 3300 3700 4000 4600 5100 6000 6800 7800 6800 6800

No. Compressors 1 1 1 1 1 1 1 1 1 2

No. Refrigerant circuits 1 1 1 1 1 1 1 1 1 1

No. Control Stages 1 1 1 1 1 1 1 1 1 2

Max. Absorbed Current (A) 14,9 17,7 19,5 21,3 25,9 28,3 31,4 38,8 45,1 45,2

Length (mm) 2205 2205 2205 2205 2205 2205 2205 2205 2755 2755

Width (mm) 1370 1370 1370 1370 1370 1370 1370 1370 2100 2100

Height (mm) 1600 1600 1600 1600 1600 1600 1600 1600 1175 1175

Standar unladen weight (kg) 489 495 504 521 538 561 587 621 641 660

SSF assembly unladen weight (kg) 611 619 630 651 673 701 734 776 913 940

Noise pressure level Lw (db(A)) 77 78 78 80 83 85 88 90 85 84

Noise pressure level Lp at 10 m (dbA) (4) 49 50 50 52 55 57 60 62 57 56

Only cooling rooftop

Refrigerant power (kW) Net (2) 17.5 20.3 22.7 25.2 29.7 33.3 36.5 41.9 40.4 41.6

Heat pump unit reversible rooftop

Cooling mode

Refrigerant power (kW) Net (2) 17.4 20.2 22.6 25.0 29.5 33.1 36.1 41.4 39.7 40.7

Heating mode

Heating power (kW) (3) 18.8 21.6 24.4 27.1 32.2 37.3 41.3 46.7 40.4 42.0

External Circuit Battery

External air flow (m3/h) 14400 14400 14000 14000 14000 20000 20000 20000 20000 20000

No. fans 1 1 1 1 1 1 1 1 1 1

Diameter 800 800 800 800 800 800 800 800 800 800

Poles 8 8 8 8 8 6 6 6 6 6

Fan Absorbed Power (kW) 0.7 0.7 0.7 0.7 0.7 1.6 1.6 1.6 1.58 1.58

Internal Circuit Battery

Internal air flow (m3/h) 3300 3700 4000 4600 5100 6000 6800 7800 6800 6800

Available nominal pressure (Pa) 80 80 100 100 100 100 100 100 100 100

Maximun available pressure (Pa) 750 750 750 750 750 700 700 700 680 680

No. Plugfan Units 1 1 1 1 1 1 1 1 1 1

Standar Centrifugal fan motor (5) 0,75 0,75 0,75 1,0 1,0 1,5 2,2 2,2 2,2 2,2

Standar Centrifugal fan Absorbed Power (5) 0,50 0,55 0,55 0,80 0,90 1,15 1,30 1,50 1,45 1,55

Plugfan absorbed power (kW) (5) 0.40 0.50 0.60 0.70 0.80 0.90 1.0 1.1 1.0 1.0

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(1) Noise pressure level at 10 m distance, in free field, directivity 2 and 1,5 meters above the floor, according to standard ISO3744

(4) Absorbed power data for standard nominal point without filtering optionals.

Page 64: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

64

Model 1044 1045 2050 2060 3070 3080 4090 4095 4100

Size 1 1 2 2 3 3 4 4 4

Internal Air Flow (m3/h) 7400 7400 8900 10300 12000 13300 15400 15400 17700

Only cooling rooftop

Refrigerant power (kW) Gross 46.2 47.1 52.6 66.4 74.3 80.8 95.5 95.3 105.8

Refrigerant power (kW) Net 45.0 45.9 51.2 64.9 72.6 78.7 92.6 91.3 102.0

Sentivie refrigerant power (kW) 33.0 33.0 38.7 47.2 51.1 55.8 65.6 65.4 73.2

Sensitive heat factor 0.73 0.72 0.76 0.73 0.70 0.71 0.71 0.72 0.73

Compressor absorbed power (kW) (1) 11.67 11.8 15.4 17.2 19.3 21.9 24.4 24.2 28.0

Compressor nominal current (A) 22.8 22.6 36.1 34.8 35.4 38.2 47.4 42.6 49.3

Total absorbed power (kW) 14.3 14.4 18.1 19.9 22.3 25.2 29.7 32.0 35.3

EER Gross 3.40 3.43 3.06 3.51 3.50 3.36 3.35 3.34 3.27

EER Net 3.26 3.30 2.93 3.35 3.34 3.19 3.17 3.26 3.21

Clasification A A B A A A A A A

Heat pump unit reversible rooftop

Cooling mode

Refrigerant power (kW) Gross 46.0 45.9 52.2 60.1 71.3 77.1 91.4 90.4 99.8

Refrigerant power (kW) Net 44.8 44.9 50.8 58.6 69.6 75.0 88.5 87.4 96.8

Sensitive refrigerant power (kW) 31.5 31.7 36.9 44.1 49.9 54.3 63.9 63.78 73.8

Sensitive heat factor 0.70 0.71 0.73 0.75 0.72 0.72 0.72 0.74 0.78

Compressor Absorbed power (kW) (1) 12.29 13 16.2 18.2 20.7 23.7 26.0 26.28 29.2

Compressor nominal current (A) 23.7 23.8 28 36 37 40.6 49.4 50.8 55.6

Total absorbed power (kW) 14.9 15.6 18.9 20.9 23.7 27.0 31.3 31.4 33.9

EER Gross 3.31 3.31 2.97 3.08 3.22 3.06 3.13 3.07 3.08

EER Net 2.99 3.10 2.75 2.87 2.99 2.80 2.81 2.91 2.94

Clasification B A C B B B B B B

Heating mode

Heating power (kW) 47.0 47.6 54.2 62.1 73.4 79.6 92.4 93.7 103.0

Compressor Absorbed power (kW) (1) 12.24 13.2 13.6 16.6 19.1 21.5 23.8 25.7 27.8

Compressor nominal current (A) 23.6 24.6 33 34 35.2 37.6 46.2 47.2 52.0

Potencia absorbida total (kW) 16.6 17.6 17.7 20.8 23.8 30.1 32.8 32.9 35.2

COP Gross 3.40 3.22 3.48 3.47 3.56 3.46 3.42 3.24 3.32

COP Net 3.34 3.16 3.39 3.34 3.39 3.25 3.29 3.22 3.30

Clasification B C B B B B B B B

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(4) Nominal absorbed power (compressor motors, external and internal standar fan)

Page 65: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

65

Model 1044 1045 2050 2060 3070 3080 4090 4095 4100

Size 1 1 2 2 3 3 4 4 4

Internal Air Flow (m3/h) 7400 7400 8900 10300 12000 13300 15400 15400 17700

No. Compressors (5) 1 2 2 2 2 2 2 4 4

No. Refrigerant circuits 1 1 2 2 2 2 2 2 2

No. Control Stages 1 2 2 2 2 2 2 4 4

Maximum Absorbed Current (A) 47,5 47,6 61,9 75,3 83,4 89,3 91,7 105,1 119,1

Length (mm) 2755 2755 2755 2755 2755 2755 3055 3055 3055

Width (mm) 2100 2100 2100 2100 2100 2100 2100 2100 2100

Height (mm) 1175 1175 1555 1555 1810 1810 1810 1810 1810

Standar unladen weight (kg) 682 694 948 1075 1155 1210 1355 1419 1560

SSF assembly unladen weight (kg) 922 938 1282 1453 1562 1572 1699 1702 1872

Noise pressure level Lw (db(A)) 86 85 85 85 86 85 86 86 88

Noise pressure level Lp at 10 m (dbA) (4) 58 57 57 57 58 57 58 58 60

Only cooling rooftop

Refrigerant power (kW) Net (2) 45.0 45.9 51.2 64.9 72.6 78.7 92.6 91.3 102.0

Heat pump unit reversible rooftop

Cooling mode

Refrigerant power (kW) Net (2) 44.8 44.9 50.8 58.6 69.6 75.0 88.5 87.4 96.8

Heating mode

Heating power (kW) (3) 46.9 47.6 52.2 62.1 73.4 79.6 92.4 93.7 103.0

External Circuit Battery

External Air Flow (m3/h) 20000 20000 25000 24000 26000 26000 36000 36000 36000

No. fans 1 1 2 2 2 2 2 2 2

Diameter 800 800 800 800 800 800 800 800 800

Poles 6 6 8 8 8 8 6 6 6

Fan Absorbed Power (kW) 1.58 1.58 1.4 1.3 1.5 1.5 3.2 3.2 3.2

Internal Circuit Battery

Internal Air Flow (m3/h) 7400 7400 8900 10300 12000 13300 15400 15400 17700

Available nominal pressure (Pa) 100 100 120 120 120 120 120 150 150

Maximum available pressure (Pa) 610 610 830 800 760 700 580 580 410

No. Plugfan units (6) 1 1 2 2 2 2 2 2 2

Plugfan Absorbed Power(kW) (6) 1.0 1.0 1.3 1.4 1.5 1.8 2.1 2.5 2.9

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(4) Noise pressure level at 10 m distance, in free field, directivity 2 and 1,5 meters above the floor, according to standard ISO3744

(5) Series 2000 and 3000 equipments available in multiscroll option with tandem compressor, 4 compressors and 2 circuits.

(6) Absorbed power data for standard nominal point without filtering optionals.

Page 66: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

66

Model 5120 5135 5140 5150 5170 6200 6230 7230 7260 7290

Size 5 5 5 5 5 6 6 7A 7B 7B

Internal Air Flow (m3/h) 19800 22700 23500 24900 28600 31900 35500 36000 39000 42500

Only cooling rooftop

Refrigerant power (kW) Gross (2) 123.6 144.0 149.8 159.8 182.1 208.9 230.5 230.5 270.4 299.8

Refrigerant power (kW) Net 118.8 137.8 143.0 152.0 174.5 199.5 221.8 221.8 260.2 287.1

Sensitive refrigerant power (kW) 85.2 99.1 102.7 108.9 132.3 150.2 176.5 176.5 202.4 224.9

Sensitive Heat Factor 0.72 0.72 0.72 0.72 0.76 0.76 0.77 0.77 0.73 0.74

Compressor Absorbed Power (kW) (1) 32.6 38.9 41.0 43.0 50.7 58.5 65.8 65.8 75.1 84.2

Compressor Nominal Current (A) 57.4 68.6 72.3 75.8 89.4 103.0 114.0 114.0 138.9 155.7

Total Absorbed Power 44.1 49.4 52.9 53.9 61.3 70.6 82.5 82.5 94.9 106.6

EER Gross 3.30 3.25 3.27 3.32 3.24 3.06 3.05 3.05 3.07 3.06

EER Net 3.20 3.11 3.09 3.10 3.10 2.90 2.97 2.97 3.02 2.97

Energetic clasification A A A A A B B B A B

Heat pump unit reversible rooftop

Cooling mode

Refrigerant power (kW) Gross (2) 118.9 134.0 144.4 155.1 173.4 200.6 218.7 231.0 261.2 288.6

Refrigerant Power (kW) Net 115.9 131.0 141.4 152.1 169.4 196.6 212.7 227.0 251.0 275.9

Sensitive refrigerant power (kW) 83.4 98.4 100.5 107.2 129.1 146.8 166.9 177.9 192.5 211.4

Sensitive Heat Factor 0.74 0.77 0.73 0.73 0.78 0.76 0.78 0.81 0.74 0.73

Compressor Absorbed Power (kW) (1) 37.4 42.3 46.1 46.7 53.2 58.5 71.6 69.8 79.2 89.9

Compressor Absorbed Current (A) 73.6 75.2 80.0 80.0 98.8 103.1 122.2 119.2 137.9 156.5

Total Absorbed Power 41.7 45.1 47.7 50.8 54.7 69.0 84.5 82.5 99.0 112.3

EER Gross Version 2.92 2.93 2.95 3.13 3.07 3.07 2.89 3.01 2.94 2.90

EER Net Version 2.77 2.75 2.76 2.89 2.89 2.86 2.74 2.89 2.79 2.71

Energetic clasification C C C B B B C B C C

Heating mode

Heating power (kW) (3) 118.9 142.4 149.1 158.7 183.2 210.2 234.1 234.1 286.6 308.3

Compressor Absorbed power (kW) (1) 31.7 38.0 40.9 43.6 46.6 56.9 66.8 66.8 70.2 76.3

Compressor nominal current (A) 62.2 70.0 73.2 76.0 90.4 104.0 112.4 112.4 126.8 137.8

Total absorbed power (kW) (4) 37.4 47.6 50.5 54.2 57.4 73.1 87.5 87.5 90.0 98.7

COP Gross 3.38 3.44 3.42 3.42 3.68 3.30 3.20 3.20 3.59 3.59

COP Net 3.31 3.34 3.30 3.28 3.57 3.20 3.14 3.14 3.56 3.52

Energetic clasification B B B B A B C C A A

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(4) Nominal absorbed power (compressor motors, external and internal standar fan)

Page 67: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

67

Technical Specification

Model 5120 5135 5140 5150 5170 6200 6230 7230 7260 7300

Size 5 5 5 5 5 6 6 7 8 8

Internal air flow (m3/h) 19800 22700 23500 24900 28600 31900 35500 36000 39000 42500

No. Compressors 4 4 4 4 4 4 4 4 6 6

No. Refrigerant circuits 2 2 2 2 4 4 4 4 3 3

No. Control Stages 4 4 4 4 4 4 4 4 6 6

Maximun Absorbed Current (A) 135,1 144,5 153,8 166,8 173,2 217,3 247,5 247,5 248.1 275.5

Length (mm) 4575 4575 4575 4575 4575 4575 4575 5775 6375 6375

Width (mm) 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100

Height (mm) 2200 2200 2200 2200 2200 2475 2475 2200 2200 2200

Standar unladen weight (kg) 2024 2093 2223 2140 2285 2579 2646 2798 3045 3130

SSF assembly unladen weight (kg) 2752 2511 2670 2568 2742 3094 3175 3358 3654 3756

Noise pressure level (db(A)) 89 90 90 89 89 92 93 93 96 97

Noise pressure level Lp at 10 m (dbA) (4) 61 62 62 61 61 64 65 65 68 69

Only cooling rooftop

Refrigerant Power (kW) Net (2) 118.8 137.8 143.0 152.0 174.5 199.5 221.8 221.8 260.2 287.1

Heat pump unit reversible rooftop

Cooling mode

Refrigerant Power (kW) Net (2) 115.9 131.0 141.4 152.1 169.4 196.6 212.7 217.0 251.0 275.9

Heating mode

Heating Power (kW) (3) 118.9 142.4 149.1 158.7 183.2 210.2 234.1 234.1 286.6 308.3

External Circuit Battery

External Air Flow (m3/h) 56000 56000 56000 56000 76000 76000 76000 76000 118000 118000

No. Fans 4 4 4 4 4 4 4 4 6 6

Diameter 800 800 800 800 800 800 800 800 800 800

Poles 8 8 8 8 6 6 6 6 6 6

Fan Absorbed power (kW) (1) 2.8 2.8 2.8 2.8 6.8 6.8 6.9 6.9 9.6 9.6

Internal Circuit Battery

Internal air flow (m3/h) 19800 22700 23500 24900 28600 31900 35500 36000 39000 42500

Available nominal pressure (Pa) 150 150 150 150 150 150 150 150 150 180

Maximum available pressure (Pa) 690 590 570 500 650 550 390 390 450 450

Fan Useful Power (kW) 2.8 3.2 3.3 3.5 4.0 4.4 5.0 5.0 6.0 7.5

No. Plugfan Units (6) 3 3 3 3 4 4 4 4 5 5

Plugfan absorbed power(kW) (6) 3.4 3.7 4.0 4.4 4.9 5.3 5.8 5.8 7.2 7.2

(1) Nominal absorbed Power only for compressors

(2) Refrigeration data for return air 27ºC-50% (77ºF), external temperature 35ºC (95ºF).

(3) Refrigeration data for return air 20ºC – 50%, external temperature 6ºC BH.

(4) Noise pressure level at 10 m distance, in free field, directivity 2 and 1,5 meters above the floor, according to standard ISO3744

Page 68: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

68

OPTIONAL TECHNICAL SPECIFICATIONS

INTERNAL CIRCUIT OPTIONALS

AIR TREATMENT UNIT ASSEMBLY OPTIONALS

Reznor RTU range units are designed to facilitate assembly and installation. For that reason, all

propulsion, return and new air location combinations are possible, indicating outlets position.

The assemblies are defined by three digits behind the letter A (Assembly), that make reference to

supply and return locations and assembly type.

Page 69: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

69

SUPPLY

B: Lower supply, the supply outlet is under the unit.

S: Long side supply (in a perpendicular direction to the unit)

T: Upper supply, the supply outlet is above the unit.

A: Short side supply (longitudinal direction to the unit). This option is available with standard radial

supply fans. This option is not possible with the opcional centrifugal fan.

RETURN

B: Lower return, the return outlet is under the unit.

S: Long side return (in a perpendicular direction to the unit)

T: Upper return, the return outlet is above the unit.

A: Short side return (longitudinal direction to the unit).

ASSEMBLY TYPE

0: Standard. The standard assembly includes centrifugal supply fans with electric IE2 motor with belts

and pulleys coupling. Optionally, a radial plug-fan fan with EC technology, in supply and in return

outlets.

A: Two ways mixing box

B: Axial return and air extraction with three ways mixing box, with mixed aluminium gates

motorized with servomotors. Lower return (B) is required.

C: Centrifugal EC plug-fan return with three ways mixing box, with mixed aluminium gates

motorized with servomotors. Long side return (S) is required.

D: Dinamic energy recovery (by subcooler) and two ways mixing box. Available option for one

compressor units. Lower return (B) is required. Ask for other options.

E: Axial air extraction fan with three ways mixing box, with mixed aluminium motorized gates.

Lower return (B) is required.

F: Radial EC return with three ways mixing box and active refrigerant recovery, includes the

aluminium motorized gates, and refrigerant recovery group with compressor. If lateral return (S), the

unit incorporates an upper return drawer. It allows Active Enery Recovery (AER standard, AERH-

enhanced, AER+Digital Scroll). Centrifugal return fans with IE2 electric motors with belts coupling are

incorporated as standard. Optionally, EC technoly plug-fan fans are available.

R: Active energy recovery and two ways mixing box. Active recovery option without return fan.

Long side (S) return is required. Ask for other needs.

T: External air outlet.

Z: Radial EC plug-fan return with three ways mixing box. It incorporates aluminium motorized

gates and allows lower return without upper drawer. It can be only made with plug-fan, it is not

possible with centrifugal fans and pulleys coupling motor.

Page 70: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

70

VENTILATION OPTIONALS AND FILTERING IN THE INTERNAL UNIT

INTERNAL FLOW OPTION

The unit can work with flows between 20% more and 20% less than the nominal flow, except of 7230

model, that it limited to 12% of nominal flow (maximum flow 40,000 m3/h).

For high rates of flow, it is recommended the incorporation of the stop-drop optional to avoid drop

draging. The load loss in this element must be considered to calculate the available pressure and the

unit consumption.

INTERNAL RADIAL EC FAN OPTION

The standard fan are centrifugal with IE2 motors and pulleys coupling, in supply and in return.

Optionally, it is available radial EC version with backward curved plates.

FILTERING OPTIONALS

The units incorporate one prefiltering stage as standard and, optionally, one or two filtering stages.

The filters are equipped in a galvanized steel self-supporting frame protected with thermally treated

polyester paint, removable with air leaks clasification L2 according to standard EN1886.

Optionally, depending on the installation type,

units can be made with:

- Prefiltering stage only.

- Prefiltering stage and F filter stage.

- Prefiltering stage and two F filtering stages.

Prefiltering stage can be configured as the

following types:

- Very low load loss prefilter,cleanable15-

mm-

thickness.

- Eficience G2, G3 or G4 25-mm-wide

prefilter

made of galvanized steel in methalic

removable rail, cleanable.

Filtrating stages can be configured with compact

eficience F6, F7, F8 and F9 48-mm-thickness filters made of galvanized steell in methalic removable

rail.

Page 71: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

71

Axial removal fans (E assembly)

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

Removal air flow (m3/h) 3400 3400 3700 3700 4450 5150 6000 6650 7700

No. Fans 1 2

Diameter (mm) 450

Power (kW) 0,19 2x0,19

Max. Speed (r.p.m.) 940

Max. Absorbed Current (A) 0,9 1,8

Modelo 4095 4100 5120 5135 5140 5150 6170 6200 6230

Removal air flow (m3/h) 7700 8850 9900 11350 11750 12450 14300 15950 16500

No. Fans 2 3 4

Diameter (mm) 450

Power (kW) 2x0,19 3x0,19 4x0,19

Max. Speed (r.p.m.) 940

Max. Absorbed Current (A) 1,8 2,7 3,6

Axial return fans (B assembly)

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

Return air flow (m3/h) 6800 6800 7400 7400 8900 10300 12000 13300 15400

No. Fans 2 2

Diameter (mm) 450 500

Power (kW) 2x0,19 2x0,72

Max. Speed (r.p.m.) 940 1390

Max. Absorbed Current (A) 1,8 2,82

Modelo 4095 4100 5120 7135 5140 5150 6170 9200 7230

Return air flow (m3/h) 15400 17700 19800 22700 23500 24900 28600 31900 36000

No. Fans 2 4

Diameter (mm) 500

Power (kW) 2x0,72 4x0,72

Max. Speed (r.p.m.) 1390

Max. Absorbed Current (A) 2,82 5,64

Page 72: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

72

Radial EC return fan (Z assembly)

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

Return air flow (m3/h) 6800 6800 7400 7400 8900 10300 12000 13300 15400

Max. Available Static Pressure (Pa) 800 800 730 730 500 230 850 810 680

No. Fans 1 2

Diameter (mm) 500

Power (kW) 2,7 2x2,7

Max. Speed (r.p.m.) 1700

Max Absorbed Current (A) 4,2 8,4

Modelo 4095 4100 5120 7135 5140 5150 6170 9200 7230

Return air flow (m3/h) 15400 17700 19800 22700 23500 24900 28600 31900 36000

Max. Available Static Pressure (Pa) 680 520 310 700 660 600 380 190 120

No. Fans 2 3

Diameter (mm) 500

Power (kW) 2x2,7 3x2,7

Max. Speed (r.p.m.) 1700

Max Absorbed Current (A) 8,4 12,6

Refrigerant recovery unit (F assembly)

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

Total Refrigerant Power (20% A.E.) 50,3 51,6 58,0 57,1 65,8 74,3 90,4 95,0 114,9

Total Heating Power (20% A.E.) 52,2 55,5 62,4 63,2 68,4 81,1 97,6 103,7 121,0

Total Refrigerant Power (60% A.E.) 59,1 59,6 66,7 66,6 74,6 86,5 102,2 112,1 129,9

Total Heating Power (60% A.E.) 61,6 64,1 71,2 72,6 79,7 92,8 111,0 120,4 138,3

Nominal air flow (m3/h) 6800 6800 7400 7400 8900 10300 12000 13300 15400

Max. Available Static Pressure (Pa) 710 710 640 640 410 140 760 720 590

Compressor type Scroll

Nº compressors / circuits 1 / 1

Model 4095 4100 5120 7135 5140 5150 6170 9200 7230

Total Refrigerant Power (20% A.E.) 115,1 126,1 148,2 168,1 183,4 192,8 215,4 254,4 N.A.

Total Heating Power (20% A.E.) 124,2 134,3 157,4 184,8 194,9 211,5 242,5 274,3 N.A.

Total Refrigerant Power (60% A.E.) 130,3 142,0 172,4 191,1 210,1 220,6 247,4 287,3 N.A.

Total Heating Power (60% A.E.) 142,8 155,0 180,5 212,3 225,2 240,7 274,3 315,0 N.A.

Nominal air flow (m3/h) 15400 17700 19800 22700 23500 24900 28600 31900 N.A.

Max. Available Static Pressure (Pa) 590 430 220 610 570 510 290 100 N.A.

Compressor type Scroll N.A.

Nº compressors / circuits 1 / 1 N.A.

N.A. Not Available (under development)

Page 73: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

73

DROPLET SEPARATOR IN INTERNAL AIR COIL

Air flow from which it is recommended the droplet separator installation:

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

Air flow (m3/h) 10190 10190 10190 10190 14570 14570 17480 17480 21920

Model 4095 4100 5120 7135 5140 5150 6170 9200 7230

Air flow (m3/h) 21920 21920 29630 35550 35550 35550 35550 41480 41480

ELECTRICAL POWER OPTIONS

The standard version’s operating voltage is 380-400V/3/50Hz + neutral. Optionally, the systems can

be configured with the following voltages of power supply:

2) 200-220V/3/50Hz

3) 380-400V/3/50Hz + neutral.

4) 380-400V/3/50Hz + neutral. (Standard)

6) 208-230V/3/60Hz

7) 380-400V/3/60Hz + neutral.

8) 380-400V/3/60Hz + neutral.

9) 460V/3/60Hz

Page 74: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

74

OPTIONS FOR THE EXTERNAL CIRCUIT

HIGH ENERGY EFFICIENCY (HEE) OPTION

The High Energy Efficiency [HEE] option includes the following available features:

[HEE] High Energy Efficiency external circuit coil design. Ventilation motors with EC technology.

[EXV] Electronic Expansion Valve in the refrigerant circuits.

[MSC] Multi-scroll. Systems with several scroll compressors, for a better power partialization and a

better seasonal performance.

[FRC] Free-cooling with several control strategies, thermal free-cooling, enthalpy or hybrid, for

maximum energy savings. Depending on the type of strategy, two or three gates are available.

HELICAL ELECTRONIC FAN WITH EC TECHNOLOGY

Model 1039 1041 1044 1045 2050 2060 3070 3080 4090

External Air Flow (m3/h) 20000 20000 20000 20000 25000 24000 26000 26000 36000

Max. Available Static Pressure (Pa) 80 150 170 100

No. fans 1 2

Diameter (mm) 1x800 2x800

Power (kW) 1x2,2 2x2,2

Max. Speed (r.p.m.) 1000

Max. Absorbed Current (A) 3,4 6,8

Model 4095 4100 5120 5135 5140 5150 6170 6200 7230

External Air Flow (m3/h) 36000 36000 39000 44000 56000 56000 56000 76000 76000

Max. Available Static Pressure (Pa) 100 80 170 90

No. Fans 2 4

Diameter (mm) 2x800 4x800

Power (kW) 2x2,2 4x2,2

Max. Speed (r.p.m.) 1000

Max. Absorbed Current (A) 6,8 13,6

Page 75: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

75

UNIT APPLICATIONS UNDER DIFFERENT CLIMATIC CONDITIONS

[High Temperature Resistance] High outdoor temperature (up to 52ºC). It has the following

features:

o Forced ventilation in the electric panel as standard.

o Design of electric equipment as standard for high temperature.

o Enhanced fans in option (check availability depending on the model).

[Low Temperature Resistance] Low outdoor temperature. The following features can be installed in

the unit optionally:

o Antifreeze electrical resistance in electric panel.

o Antifreeze electrical resistance in plate exchanger in case of condensation of water or

plates exchangers of sanitary hot water recovery.

o Electric resistance in external condensate pan for low temperatures.

CLIMATE PROTECTION FOR EXTERNAL BATTERY

o COPPERFINTM: Condensing battery of copper tube and copper fins (coastal

protection) and high resistance aluminium alloy framework.

o ALUCOASTTM: Condensing battery of copper tube and fins of high resistance marine

aluminium (coastal protection), with aluminium alloy framework.

o PAINTCOASTTM: Condensing battery of copper tube and post-lacquered with oven

cured epoxy aluminium fins (chemical protection).

o BLYGOLD®: Condensing battery of copper tube and aluminium fins, coated with

post-lacquered Blygold Polual (coastal protection).

o BLUECOASTTM: Condensing battery of copper tube and aluminium fins, pre-lacquered

with hydrophilic or hydrophobic blue polyurethane (basic protection).

Page 76: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

76

HOT WATER SUPPORT COIL. OPERATION DATA.

Model

Internal

flow

(m3/h)

Air inlet temp. 20 (ºC) Air inlet temp. 20 (ºC) Air inlet temp. 20 (ºC)

Ho

t w

áte

r su

pp

ort

coil

Water (50-40)(ºC) Water (50-30)(ºC) Water (60-40)(ºC)

(Pa) Heating

power (kW)

Water

flow

(m3/h)

Water

load

loss

(mca)

Heating

power (kW)

Water

flow

(m3/h)

Water

load

loss

(mca)

Heating

power (kW)

Water

flow

(m3/h)

Water

load

loss

(mca)

KCR0017 3300 28.5 14.3 1.2 0.4 6.1 0.3 0.1 14.7 0.6 0.1

KCR0020 3700 30.0 16.6 1.4 0.4 7.1 0.3 0.1 17.1 0.7 0.1

KCR0022 4000 31.0 18.1 1.5 0.5 7.7 0.3 0.1 18.5 0.8 0.2

KCR0026 4600 28.0 22.5 1.9 0.4 9.6 0.4 0.1 23.1 1.0 0.1

KCR0030 5100 29.0 24.4 2.0 0.4 10.4 0.4 0.1 25.0 1.1 0.1

KCR0035 6000 29.5 28.0 2.3 0.5 11.9 0.5 0.1 28.7 1.2 0.2

KCR0039 6800 30.5 31.4 2.6 0.6 13.3 0.6 0.1 32.2 1.4 0.2

KCR0044 7800 29.5 31.8 2.6 0.6 13.5 0.6 0.1 32.6 1.4 0.2

KCR1039/41 6800 30.2 32.0 2.7 0.3 13.6 0.6 0.1 32.8 1.4 0.1

KCR1044/45 7400 33.5 33.8 2.8 0.3 14.3 0.6 0.1 34.6 1.5 0.1

KCR2050 8900 26.8 37.8 3.2 0.4 16.1 0.7 0.1 38.8 1.7 0.1

KCR2060 10300 33.5 42.6 3.5 0.5 18.1 0.8 0.1 43.7 1.8 0.1

KCR3070 12000 33.5 51.1 4.3 0.3 21.7 0.9 0.1 52.4 2.3 0.1

KCR3080 13300 36.9 54.5 4.6 0.4 23.2 1.0 0.1 55.9 2.4 0.1

KCR4090 15400 33.5 67.2 5.7 0.6 28.5 1.3 0.1 68.8 3.0 0.2

KCR4095 15400 33.5 67.2 5.7 0.6 28.5 1.3 0.1 68.8 3.0 0.2

KCR4100 17700 40.2 73.0 6.2 0.7 31.0 1.4 0.1 74.8 3.3 0.2

KCR5120 19800 30.8 77.4 6.7 0.5 32.9 1.5 0.1 79.3 3.5 0.1

KCR5135 22700 28.8 93.9 7.8 0.3 39.9 1.7 0.1 96.3 4.1 0.1

KCR5140 23500 30.8 96.8 8.3 0.4 41.1 1.8 0.1 99.3 4.3 0.1

KCR5150 24900 33.5 99.5 8.8 0.4 42.3 1.9 0.1 102.0 4.6 0.1

KCR6170 28600 40.0 108.4 9.2 0.4 46.0 2.0 0.1 111.1 4.9 0.1

KCR6200 31900 35.0 115.8 9.9 0.5 49.2 2.2 0.1 118.7 5.2 0.1

KCR6230 35500 30.8 121.9 10.1 0.4 51.8 2.2 0.1 125.0 5.3 0.1

KCR7230 36000 33.5 124.4 10.3 0.4 52.8 2.3 0.1 127.5 5.4 0.1

KCR7260 39000 36.5 145.9 12.1 0.4 62.0 2.7 0.1 149.5 6.4 0.1

KCR7300 42500 37.5 143.8 12.3 0.8 61.1 2.7 0.1 147.4 6.5 0.2

Page 77: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

77

ELECTRONIC REGULATION

The electronic microprocessor control Reznor CLIMANAGER is specifically developed for the

management of Reznors Rooftop air-to-air equipments. This control serves to the market

requirements in terms of energy management, operation simplicity and installations maintenance, for

which Reznor has developed a management software exclusively dedicated to rooftops on the basis

of the latest electronic microprocessor technology.

Please, read carefully the information in this manual before handling

the control of the unit.

Page 78: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

78

Any parameter modification must be carried out by a qualified technician authorised by Reznor. In

case of improper handling or wrong connection the unit may operate incorrectly ore even suffer

irreversible damage. Reznor is not responsible for the effects of any mishandling or unauthorised

modification of operating parameters, in which case the warranty may be voided.

The main specifications of the electronic board are the following:

- Microprocessor 32 bits 24Mhz

- Programmable Flash Memory 2MB;

- RAM Memory 512kB;

- 3 Serial bus:

o pLAN (PC, pGD, pCO, CLIMANAGER connection)

o BMS with optional card

o Fieldbus for intelligent actuators and THT terminal

- Voltage supply 24 Vac and 230 Vac

- Medium size 13 DIN

- BMS plug-in card

- Real time clock RTC (allows scheduling)

- Operation conditions: -10ºC/+60°C

The interface between the human and the unit can be performed through the following compatible

terminals:

- Connection by termina/pLAN

- Graphic Display PLDPRO (Optional)

- Graphic Display PGD1: remote installation up to 50 m, mayores con 2 tarjetas TCONN y cable

apantallado hasta 200 m y superior meter fuente de alimentación. (Optional)

Connection by MODBUS

- Environment terminal THT. (Standard)

- Tactile display PGD Touch: remote installation up to 500 m and 15 machines. (Optional)

The next figure shows the RS485 output integrated for field actuators, which allows to connect up to

five devices. Through J14 connector it is posible to change from RS485 connection to tLAN and vice

versa.

Management by remote control and kind of probes supported

The board is prepared to support remote control type THT, as well as inputs for external signals of

Start /Stop, Cooling/Heating mode and an alarm output from the machine.

The following list contains each of the active/passive probes for which the board’s hardware and

firmware alike are prepared:

Analog sensors

- NTC probes: passive analog input (resistive).

(AIR/AIR: pumped, return, mix and exterior air in addition to extra-pumping in the event of

gas burner).

- Freon pressure transducers: analog input 0-1VDC. / 0-5VDC.

- Air pressure transducers: analog input 0-1VDC. / 0-5VDC.

- Interior/exterior temperature and/or humidity probes: 4-20 mA / 0-1VDC/ passive resistive /

RS485 Modbus or Carel.

- CO2 sensors: 0-1VDC / 4-20 mA.

Page 79: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

79

- Air quality sensors VOC: 0-1VDC / 4-20 mA

- Combined sensors VOC+CO2: 0-1VDC / 4-20 mA

Digital sensors

- High pressure switch: digital input.

- Low pressure switch: digital input.

Through the Field-Bus card, the communication with probes and with other enabled equipment is

allowed by RS485 transmission and MODBUS protocol.

- Other CLIMANAGER cards

- Temperature and/or Humidity probes.

- Network analyser (energy analyser)

- EBM electronic fans

- Gate servomotors.

- Driver modules for Electronic Expansion Valves

- Driver modules for Inverter Compressors

- Driver modules for Digital-Scroll Compressors

The pLAN card allows the connection with PDG1 / remote PLD PRO and with other CLIMANAGER

cards.

The board is prepared without any optional equipment (no more than TCONN card) to be remotely

connected to other machines or devices (15 units maximum) by means of a PGD1 remote control.

Fan management

CLIMANAGER platform allows the connection of EC technology electronic fans, two External Unit

circuits, Pumping and Return.

Page 80: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

80

- Control through 0-10V signal or PWM without driver or additional module.

- Digital input so that the fan communicates state or alarm.

- Likewise the board allows conmmunication with these equipment through RS-485 in the

event of setting up these fans in a network.

CLIMANAGER platform allows a double Star-Triangle output for the External Unit fans.

The Return and Extraction Fans are simultaneously incompatible, these fans can be Centrifugal, Radial

or Plug-Fan, using analogic or digital outputs.

The extraction fan operates according to the following functioning logic:

- Mixing Gate Completely Closed (0%): speed 100%

(ON in the case of ALL/NOTHING)

- Mixing Gate at 30%: speed 70%

(ON in the case of ALL/NOTHING)

- Mixing Gate at 50% and higher opening: speed 0%

(OFF in the case of ALL/NOTHING)

Electronic Expansion Valve Management

The board enables the control of the electronic expansion valve driver by means of FieldBus

(RS458@MODBUS). For that purpose universal drivers are used to work with electronic valves.

Gate Management

The board enables the control of 0-10 VDC or ON/OFF proportional Servomotors for gates. In the

same way, the board allows conmmunication with these equipment through RS-485 in the event of

setting up these fans in a network.

The 3 gates are controlled by means of 2 signals.

External and Exhaust Air: simultaneous functioning

Mixed Air: with an independent signal from the previous ones, this gate will be 90º out of

phase in relation to such signals with a parametrizable differential depending on the

installation specific needs.

Compressor Management

The board allows the control of the following compressors without an external driver.

ON / OFF

Digital-Scroll Copeland: based on Triac and suitable for the Active + recovery option

Inverter: DC and AC versions

The maxiun number of compressors managed is four in two main circuits +2 of the recovery circuit.

Support accesories management and other options

CLIMANAGER platform allows the communication with a network analyser per machine through

Fieldbus, showing consumption, intensity and cosPhi on screen. Consumption lever alarms may be

enabled.

The platform can control a 0-10VDC three ways proportional valve unit for Hot Water Back-up Battery,

and can control pumping back-up or anti-icing resistances, in two stages on/off. It counts on firmware

and outputs for at least one humidifier type ON/OFF, 0-10Vdc or FieldBus.

Page 81: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

81

It has an output for a one-or-two-stage gas burner unit.

To that end it must have enabled: gas burner alarm signal input, burner discharge probe connection

and ON / OFF output for the two burner stages.

THT TERMINAL

The terminal THT is an user terminal as well as a tool that facilitates the start-up, being compatible

with the connectors commonly used in the market.

The terminal main features are:

- Standard power supply (24Vac/dc...230Vac)

- Valid for tempearature and humidity control

- Compatible with Europe and USA power connections

- Possibility of nocturnal functioning or delay.

- Possibility of joint usage with other PGC terminals

Possibility of installation in every socket available in the market.

Page 82: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

82

3.- PGD TERMINAL

The PGD1 terminal is a device which allows the management and access to the CLIMANAGER control

parameters. PGD1 is a monocromatic LCD graphic terminal with a 132x64 pixel resolution and LED

backlighting. It is available in panel mounting version or in wall version.

The PGD1 display has FSTN graphics,

feedback with green and white LEDs, 132x64

pixel resolution, two text modes, 8 rows x 22

columns (5x7 and 11x15 pixel font

management), or 4 rows x 11 columns (11x15

pixel font), or mixed mode. Character height,

3,5 mm (5x7 pixel font), or 7 mm (11x15 pixel

font). Power supply: Supply from electronic

board via phone jack or by means of a 18/30

Vdc outside source protected by an external

250 mA fuse. Max power: 1,2W.

The following figure shows the PGD terminal

dimensions for panel or wall mounting.

The connection between the terminal and the controller is carried out by using a 6 wire telephone

cable. To make the connection, simply plug the phone jack into the RJ12 socket at the terminal’s back,

and into the corresponding electronic board connector.

Panel mounted Wall mounted

Dimensions

Page 83: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

Nortek Global HVAC J&M Sabbestraat 130/A000

B-8930 Menen Belgium

Page 84: RTU Installation & Operating - reznorhvac.com RTU Installation and Operating... · RTU Installation & Operating ... To prevent accidents during installation, implementation or maintenance,

Company Standards and Services:All products are tested and approved to CE standards. We are assessed to EN ISO 9001 Quality Assurance. We offer a service to our customers; including budget schemes, on site technical support and a comprehensive after-sales package. We reserve the right to change specifications without prior notice. Errors and omissions excepted.

Nortek Global HVAC Belgium nvJ&M Sabbestraat 130/A000B-8930 MenenBelgiumTel. +32 (0)56 52 95 11Fax. +32 (0)56 52 95 [email protected]