6
VD.CU.A1.02 Produced by Danfoss Floor Heating Hydronics 06.2008 Room Thermostats Floor Heating

Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

Embed Size (px)

Citation preview

Page 1: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

VD.CU.A1.02 Produced by Danfoss Floor Heating Hydronics 06.2008

Room ThermostatsFloor Heating

Page 2: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

2

Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats

VD.CU.A1.02 Produced by Danfoss Floor Heating Hydronics 06.2008

The room thermostats are available in three versions; two standard room thermostats with respectively dial or with LCD display and a programmable room thermostat with LCD display. All Room Thermostats are used for room temperature control in water based floor heat-

ing systems. By controlling room temperature in accordance with the temperature desired by the user the room thermostats provide optimal energy savings whilst upholding optimal thermal comfort in the room/ apartment.

Floor Heating Room Thermostats

Functions

Application

Room Thermostat, FH-CWT (Dial)By turning the dial to the desired set-point temperature optimal thermal comfort in the room is achieved. In addition to temperature the thermostat setting scale includes frost symbol allowing for minimal energy consumption while keeping the room from freezing. The thermo-stat is equipped with diodes which through the front cover will display a green light while the thermostat is ON but without heat demand and a red light when the thermostat is ON and there is heat demand.

Room Thermostats, FH-CWD (display) and FH-CWP (display and programmable) The thermostats with LCD display can in addi-tion to room temperature control be equipped with floor sensor thus allowing for control of maximum floor temperature and reducing risk of over heated and damaged floors. For specific maximum floor temperatures please refer to recommendations from floor suppliers.

Using the Frost Protection Mode instead of turn-ing the thermostat OFF completely may protect against damages due to low temperatures. The room temperature will be maintained around 5°C.

For the FH-CWP (programmable thermostat) two timer programs are available allowing tempera-ture setback or alternatively complete turning off the heat supply during selected periods without occupants in the room/ apartment.

The ON/ OFF Timer Function allows you to pro-gram the thermostat for one period with heating turned OFF and one period with heating turned ON per day. During the ON period the thermostat will regulate in relation to the set temperature and TIMER ON will be shown in the display. Dur-ing the OFF period, the heating is off, and TIMER OFF is shown in the display.

The Advanced Programmable Timer Function allows you to set a timer controlled program for automatic comfort temperature and energy saving lower setback temperature when standard room comfort temperature is not required.The Advanced Programmable Timer Function allows for 4 different periods / 5+2 days per week.

FH-CWT FH-CWD FH-CWP

Ordering Product Type Supply voltage Output voltage Code no.

Room Thermostat - Dial FH-CWT 230 Vac 230 Vac 088U0601

Room Thermostat - Display FH-CWD 85-250 Vac 85-250 Vac 088U0602

Room Thermostat - Display Programmable FH-CWP 85-250 Vac 85-250 Vac 088U0603

Floor sensor FH-CWF – – 088U0610

Page 3: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

3

Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats

Produced by Danfoss Floor Heating Hydronics 06.2008 VD.CU.A1.02

Data Feature FH-CWT FH-CWD FH-CWP

Approval: CE Marking, EN 60730 CE Marking, EN 60730 CE Marking, EN 60730

Colour White RAL 9016/ Grey RAL 7011

White RAL 9016 White, RAL 9016

Dimensions 86 x 99 x 29 mm 86 × 99 ×19mm 86 × 99 ×19mm

Ambient temperature -10˚C - 60˚C -10˚C - 60˚C -10˚C - 60˚C

Operating rating 0˚C - 40˚C, 5 - 95% RH (Non-condensing)

0˚C - 40˚C, 5 - 95% RH (Non-condensing)

0˚C - 40˚C, 5 - 95% RH (Non-condensing)

Adjustment mode Dial Push buttons Push buttons

Fault indication/ failure mode

If sensor failure, thermo-stat will turn off all output of relays.

If room sensor failure, E1 will be displayed. If floor sensor failor, E2 will be displayed. In any case, thermostat will turn off all output of relays.

If room sensor failure, E1 will be displayed. If floor sensor failor, E2 will be displayed. In any case, thermostat will turn off all output of relays.

Frost protection Yes, put the dial to position (5° C)

Yes, if enabled:<5˚C heating on >7˚C heating off

Yes, if enabled:<5˚C heating on >7˚C heating off

Precision ±1° C ±0.5° C ±0.5° C

Hysteresis 1°C, below the setpoint temperature

1°C, symmetrical around the setpoint temperature

1°C, symmetrical around the setpoint temperature

IP class 30 30 30

LCD backlight/nightlight No Yes Yes

LCD display No Yes Yes

LED indicator Green light: Thermostat ON and no heat demandRed light: Thermostat ON and heat demand

No No

Max load, inductive <1A <1A <1A

Max load, resistive <3A <3A <3A

Mounting Wall mounting Flush Mounting for Euro-pean and Chinese built in sockets

Flush Mounting for Euro-pean and Chineese built in sockets

Network, wire No No No

Network, wireless No No No

Off-set function/ Temp. calibration

No Yes (+/-10°C) Yes (+/-10°C)

Power consumption 7W 2 W 2 W

Power supply, battery No No No

Power supply, net 230Vac±10% 50/60Hz 85-250Vac 50/60Hz 85-250Vac 50/60Hz

Power backup settings Not applicable Retains settings in case of power cut saved on memory chip

Retains settings in case of power cut saved on memory chip

Sensor, floor No Optional, 2 terminals (S1, S2) for external sensor mounting. Sensor type NTC 10K accuracy: ±1%

Optional, 2 terminals (S1, S2) for external sensor mounting. Sensor typeNTC 10K accuracy: ±1%”

Sensor, floor - set range No 20-45°C 20-45°C

Sensor, room NTC 10K accuracy: ±1% NTC 100K accuracy: ±1% NTC 100K accuracy: ±1%

Sensor, room - set range 5-30°C 5-35°C 5-35°C

Shell material/ non inflam-mable

94V0/ Yes 94V0/ Yes 94V0/ Yes

Shell material, type ABS+PC ABS+PC ABS+PC

Static protection Yes Yes Yes

Programmable

No No Two program functions1. ON/ OFF program 2 periods/ day2. Periode program for automatic comfort temperature and setback temperature 4 periods/ 5+2 days

Page 4: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

4

Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats

VD.CU.A1.02 Produced by Danfoss Floor Heating Hydronics 06.2008

Application examples

Wiring connections

Room Thermostat, FH-CWT (Dial)

Individual room temperature control

Reference room temperature control

Reference room temperature control

Room Thermostat, FH-CWD (Display) Room Thermostat, FH-CWProgrammable)

( )

( )

Individual room temperature control

Page 5: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

5

Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats

Produced by Danfoss Floor Heating Hydronics 06.2008 VD.CU.A1.02

Dimensions

60

48

60 48

24,518,5

98,6

86

60

60 48

4824,518,5 86

98,6

60

60

29,5 86

98,6

Room Thermostat, FH-CWT (Dial)

Room Thermostat, FH-CWD (Display)

Room Thermostat, FH-CWP (Programmable)

Page 6: Room Thermostats Floor Heatingheating.danfoss.com/PCMPDF/VDCUA102.pdf · 2 Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats VD.CU.A1.02 Produced by Danfoss Floor Heating

6006

1 00

0 01

6

Data sheet FH-CWT/ CWD/ CWP Floor Heating Room Thermostats

Produced by Danfoss Floor Heating Hydronics 06.2008 VD.CU.A1.02

6001

� 00

0 02

12

Data Sheet CF2 Wireless Floor Heating Control System

VD.UH.J2.02 Produced by Danfoss Floor Heating Hydronics 10.2005