Upload
others
View
15
Download
0
Embed Size (px)
Citation preview
ROBOTICS
Application manualPROFINET Controller/Device
Trace back information:Workspace R18-1 version a16Checked in 2018-04-18Skribenta version 5.2.025
Application manualPROFINET Controller/Device
RobotWare 6.07
Document ID: 3HAC050969-001Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
The information in this manual is subject to change without notice and should notbe construed as a commitment by ABB. ABB assumes no responsibility for any errorsthat may appear in this manual.Except as may be expressly stated anywhere in this manual, nothing herein shall beconstrued as any kind of guarantee or warranty by ABB for losses, damages topersons or property, fitness for a specific purpose or the like.In no event shall ABB be liable for incidental or consequential damages arising fromuse of this manual and products described herein.This manual and parts thereof must not be reproduced or copied without ABB'swritten permission.Keep for future reference.Additional copies of this manual may be obtained from ABB.
Original instructions.
© Copyright 2015-2018 ABB. All rights reserved.ABB AB, Robotics
Robotics and MotionSe-721 68 Västerås
Sweden
Table of contents7Overview of this manual ...................................................................................................................
10Product documentation ....................................................................................................................12Safety ................................................................................................................................................13Network security ...............................................................................................................................14Terminology ......................................................................................................................................
151 Introduction151.1 What is PROFINET? ..........................................................................................161.2 PROFINET for IRC5 ...........................................................................................
192 Hardware overview192.1 Main computer ..................................................................................................262.2 Ethernet switches ..............................................................................................272.3 I/O devices .......................................................................................................
293 Software overview293.1 Information about the internal device ....................................................................313.2 Information about the internal controller ................................................................323.3 Software for configuring a device .........................................................................333.4 Software for configuring a controller .....................................................................
354 Configuring the internal device and external controller354.1 Recommended working procedure .......................................................................364.2 Configuring the PROFINET network settings ..........................................................384.3 Configuring the internal device ............................................................................394.4 Configuring the external controller ........................................................................
415 Configuring the internal controller and external device415.1 Recommended working procedure .......................................................................425.2 Creating the PROFINET configuration file ..............................................................435.3 Configuring the IRC5 controller ............................................................................445.4 Using Fast Device Startup ...................................................................................465.5 Using Shared Device .........................................................................................465.5.1 About Shared Device ...............................................................................
496 System parameters496.1 Introduction ......................................................................................................526.2 Type Industrial Network ......................................................................................526.2.1 Connection ............................................................................................536.2.2 Configuration File ....................................................................................546.2.3 PROFINET Station Name ..........................................................................556.2.4 Nested Diagnosis ....................................................................................566.3 Type PROFINET Device .....................................................................................566.3.1 PROFINET Station Name ..........................................................................576.3.2 Fast Device Startup .................................................................................586.3.3 Port 1 ....................................................................................................596.3.4 Port 2 ....................................................................................................606.3.5 Port 3 ....................................................................................................616.3.6 Port 4 ....................................................................................................626.3.7 Energy Saving ........................................................................................636.4 Type Signal ......................................................................................................636.4.1 Transfer To Device ..................................................................................646.4.2 Output Offset on Destination Device ...........................................................656.4.3 Transfer From Device ..............................................................................666.4.4 Input Offset on Source Device ...................................................................
Application manual - PROFINET Controller/Device 53HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Table of contents
676.5 Type PROFINET Internal Device ..........................................................................676.5.1 Input Size ..............................................................................................686.5.2 Output Size ............................................................................................
697 Troubleshooting697.1 Scenarios ........................................................................................................
71A About the third party tool information
75B Using Siemens Step 7 PC tool
79C Using PROFINET Configurator Express
85Index
6 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Table of contents
Overview of this manualAbout this manual
This manual describes the following options and contains instructions on how toconfigure them in an IRC5 system.
• PROFINET Controller/Device, option number 888-2• PROFINET Device, option number 888-3
UsageThis manual should be used during installation and configuration of the PROFINEToptions.
Who should read this manual?This manual is intended for:
• Personnel that are responsible for installations and configurations of industrialnetwork hardware/software.
• Personnel that make the configurations of the I/O system.• System integrators.
PrerequisitesThe reader should have the required knowledge of:
• PROFINET network• I/O system configuration• IRC5 controller• RobotStudio
References
ABB documents
Document IDReference
3HAC050948-001Technical reference manual - System parameters
3HAC047136-001Product manual - IRC5
3HAC050941-001Operating manual - IRC5 with FlexPendant
3HAC032104-001Operating manual - RobotStudio
3HAC050968-001Application manual - PROFINET Anybus Device
3HAC050967-001Application manual - PROFIenergy Device
Other references
DescriptionReference
The PROFINET industrial network standardis described in the international standards.
International standard IEC 61158 Type 3 In-ternational standard IEC 61784
Installation Guideline for PROFINET (Version2.00, September 1998)
PROFINET Cabling and InterconnectionTechnology
Continues on next pageApplication manual - PROFINET Controller/Device 73HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Overview of this manual
DescriptionReference
Release 12/2006 C79000-G8976-C156-08Commissioning PC Stations - Manual andQuick Start
Manual from SiemensET200S Distributed I/O System
The web site of PROFINET Internationalwww.profinet.com
Revisions
DescriptionRevision
First edition.-Released with RobotWare 6.0.
Released with RobotWare 6.01.• Added information about different ways to connect to networks in
section Main computer on page 19.• System parameters Address, Subnet Mask, and Gateway removed
from Industrial Network.• Added a note that it is advisable to avoid multiple master networks
installation to ensure proper system performance in section Softwareoverview on page 29.
A
Released with RobotWare 6.02.• Updated the path to the template files, see Template I/O configuration
file on page 29.• Added shared device functionality and configuration, seeUsing Shared
Device on page 46.• Added new parameter Nested Diagnosis, see Nested Diagnosis on
page 55.• Added new parameter Energy Saving, see Energy Saving on page62.• Added PROFINET Station Name under Type PROFINET Device, see
PROFINET Station Name on page 56.• The PROFINET internal device has been extended from 128 bytes
(1024 signals) to 256 bytes (2048 signals). See Input Size on page 67and Output Size on page 68.
B
Released with RobotWare 6.03.CAdded information about configuration of AC500 with an IRC5 device inAutomation Builder (Control Builder Plus). See Troubleshooting on page 69section.
Released with RobotWare 6.04.• The information about third party tools is moved to an appendix.• Added new parameters in Type Signal in System Parameters section.
See Transfer To Device on page 63, Output Offset on DestinationDevice on page64, Transfer FromDevice on page65, and Input Offseton Source Device on page 66.
D
Released with RobotWare 6.05.EAdded new allowed value Support in parameter Fast Device Startup onpage 57.
Released with RobotWare 6.06.• Minor correction.• Added information about default gateway only for PROFINET traffic
using LAN3. See Default gateway on page 17.• Added information about device replacement feature. See Device re-
placement on page 18
F
Continues on next page8 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
Overview of this manualContinued
DescriptionRevision
Released with RobotWare 6.07.• Clarified the limitations for Isolated Lan 3 in the section Isolated LAN
3 or LAN 3 as part of the private network on page 20.• PC WORX is not a recommended tool, so it is removed from the
manual.• Added section Link Layer Discovery Protocol (LLDP) on page 17.
G
Application manual - PROFINET Controller/Device 93HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Overview of this manualContinued
Product documentationCategories for user documentation from ABB Robotics
The user documentation from ABB Robotics is divided into a number of categories.This listing is based on the type of information in the documents, regardless ofwhether the products are standard or optional.All documents can be found via myABB Business Portal, www.myportal.abb.com.
Product manualsManipulators, controllers, DressPack/SpotPack, and most other hardware isdelivered with a Product manual that generally contains:
• Safety information.• Installation and commissioning (descriptions of mechanical installation or
electrical connections).• Maintenance (descriptions of all required preventive maintenance procedures
including intervals and expected life time of parts).• Repair (descriptions of all recommended repair procedures including spare
parts).• Calibration.• Decommissioning.• Reference information (safety standards, unit conversions, screw joints, lists
of tools).• Spare parts list with corresponding figures (or references to separate spare
parts lists).• Circuit diagrams (or references to circuit diagrams).
Technical reference manualsThe technical reference manuals describe reference information for roboticsproducts, for example lubrication, the RAPID language, and system parameters.
Application manualsSpecific applications (for example software or hardware options) are described inApplication manuals. An application manual can describe one or severalapplications.An application manual generally contains information about:
• The purpose of the application (what it does and when it is useful).• What is included (for example cables, I/O boards, RAPID instructions, system
parameters, software).• How to install included or required hardware.• How to use the application.• Examples of how to use the application.
Continues on next page10 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
Product documentation
Operating manualsThe operating manuals describe hands-on handling of the products. The manualsare aimed at those having first-hand operational contact with the product, that isproduction cell operators, programmers, and troubleshooters.
Application manual - PROFINET Controller/Device 113HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Product documentationContinued
SafetySafety of personnel
When working inside the robot controller it is necessary to be aware ofvoltage-related risks.A danger of high voltage is associated with the following parts:
• Devices inside the controller, for example I/O devices, can be supplied withpower from an external source.
• The mains supply/mains switch.• The power unit.• The power supply unit for the computer system (230 VAC).• The rectifier unit (400-480 VAC and 700 VDC). Capacitors!• The drive unit (700 VDC).• The service outlets (115/230 VAC).• The power supply unit for tools, or special power supply units for the
machining process.• The external voltage connected to the controller remains live even when the
robot is disconnected from the mains.• Additional connections.
Therefore, it is important that all safety regulations are followed when doingmechanical and electrical installation work.
Safety regulationsBefore beginning mechanical and/or electrical installations, ensure you are familiarwith the safety regulations described in Operating manual - General safetyinformation1 .
1 This manual contains all safety instructions from the product manuals for the manipulators and the controllers.
12 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Safety
Network securityNetwork security
This product is designed to be connected to and to communicate information anddata via a network interface, It is your sole responsibility to provide and continuouslyensure a secure connection between the product and to your network or any othernetwork (as the case may be). You shall establish and maintain any appropriatemeasures (such as but not limited to the installation of firewalls, application ofauthentication measures, encryption of data, installation of anti-virus programs,etc) to protect the product, the network, its system and the interface against anykind of security breaches, unauthorized access, interference, intrusion, leakageand/or theft of data or information. ABB Ltd and its entities are not liable fordamages and/or losses related to such security breaches, any unauthorized access,interference, intrusion, leakage and/or theft of data or information.
Application manual - PROFINET Controller/Device 133HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Network security
TerminologyTerms
ExplanationTerm
The PROFINET master is referred to as PROFINETcontroller.
Controller
In this manual the term device is used to describe aphysical unit.
Device
The term external is used to describe a controller ordevice on the PROFINET network connected to theIRC5 controller.
External slave or master
A third party PC software to configure the PROFINETcontroller.
External PROFINET configurationtool
Recommended softwares are:• PROFINET-IO Configurator Express• PROFINET-IO Configurator Professional
See Configuration programs on page 16.
Functionality for shortening the connection time withan I/O device.
Fast Device Startup
Other manufacturers refer to this functionality as FastStart Up (FSU) or Prioritized Startup.
A GSDML file contains information about a PROFINETdevice.
GSDML file
(Generic Station Description Markup Language)
A built-in device in the robot controllerInternal Device
The term internal is used to describe when the IRC5controller acts as a controller or device on thePROFINET network.
Internal slave or master
Port/connector for Local Area Network.LAN
The nested diagnosis functionality is used for diagnos-is in hierarchial plants and enables the user to evaluatethe status of the PROFINET network from a centralPLC or external tool.
Nested Diagnosis
XML file created using an external PROFINET config-uration tool
PROFINET configuration file
Poll rateReduction ratio
A device that is controlled by two controllers via aPROFINET interface.
Shared Device
See term DeviceSlave
Port/connector for Wide Area Network.WAN
14 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Terminology
1 Introduction1.1 What is PROFINET?
GeneralPROFINET is an open standard for Industrial Ethernet. PROFINET satisfiesrequirements for automation technology. PROFINET solutions can be implementedfor factory and process automation, for safety applications, and for the entire rangeof drive technology right up to clock-synchronized motion control.
StandardizationThe use of open standards, simple operation, and the integration of existing systemsegments have driven the definition of PROFINET from the beginning. PROFINETis standardized in IEC 61158 and IEC 61784. The continual further developmentof PROFINET offers users a long term perspective for the implementation of theirautomation tasks.
Communication profilesPROFINET has a modular design and different PROFINET communication profilesare all combinations of modular elements from the groups transmission technology,communication protocol, and application profiles.Here are some examples of PROFINET communication profiles:
• PROFINET-IO - Distributed I/O (Remote I/O). Here, the familiar I/O view ofPROFIBUS is retained, in which the user data from the field devices areperiodically transmitted into the process model of the control system.
• PROFINET-CBA - Based on the object-oriented modelling of technologicalmodules. Based on the object model, machines and installations arestructured in PROFINET in the form of technological modules.
• PROFIsafe - Defines how safety-oriented devices (emergency shutoffswitches, light grids, overfill protection systems, etc.) can communicatesafety control information over a network securely enough that they can beused in safety-oriented automation tasks up to EN954's KAT4, AK6, or SIL3(Safety Integrity Level).
• PROFIdrive - The PROFIdrive profile covers application scenarios from simplefrequency converters to highly dynamic servo drivers.
• PROFIenergy - A profile of the PROFINET communications protocol thatallows the power consumption of automation equipment in manufacturing(such as robot assembly cells, laser cutters and sub-systems such as paintlines) to be managed over a PROFINET network. It offers an open andstandardized means of controlling energy usage during planned andunplanned breaks in production. See alsoApplicationmanual - PROFIenergyDevice.
Application manual - PROFINET Controller/Device 153HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
1 Introduction1.1 What is PROFINET?
1.2 PROFINET for IRC5
GeneralThe PROFINET network is running on the IRC5 main computer and does not requireany additional hardware. PROFINET as described in this manual requires the maincomputer DSQC1000.
OptionsWith optionPROFINETController/Device, the IRC5 controller can act as a controller,device, or both on the PROFINET network.With option PROFINET Device, the IRC5 controller can only act as a device.
Tip
If only PROFINET device functionality is required, then the option PROFINETAnybus Device can also be used.For more information, see Application manual - PROFINET Anybus Device.
Note
Note that the network settings are set for the Connection, i.e. the physicalconnector on the main computer used for the PROFINET network.This means that the network settings are shared between the internal device andthe internal controller if the IRC5 controller acts as both on the PROFINETnetwork.
CompatibilityFor RobotWare 6.06 and later, the PROFINET device is certified by PROFIBUS &PROFINET International (PI) with conformance class B/ NetLoad Class II and thedevice profiles; PROFIenergy and PROFIsafe.PROFINET device is certified for the PROFINET version 2.33.
Configuration programsTo be able to configure the PROFINET controller, an external PROFINETconfiguration tool is needed. There are two different versions available:PROFINET-IO Configurator Express and PROFINET-IO Configurator Professional.Supplied in the RobotWare distribution package is the Express version, see Aboutthe third party tool information on page 71. The Professional version have someadditional features and can be bought separately.The PROFINET internal device does not require any external configuration tool forthe IRC5 controller. A connecting PLC or other controller needs to use the providedGSDML file and its vendor specific configuration tool to be able to connect to thePROFINET internal device.
Continues on next page16 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
1 Introduction1.2 PROFINET for IRC5
Specification overview, internal controller
SpecificationItem
Maximum 50 I/O devicesNumber of I/O devices connected to control-ler
Maximum 256 input bytes and 256 outputbytes per device.
Connection size
Specification overview, internal device
SpecificationItem
See GSDML file on page 29.GSDML file
2.33PROFINET Version
Slot 1-2: Digital input or output modules ofvariable size
Slot configuration
Maximum 256 input bytes and 256 outputbytes per device.
Connection size
Default gatewayThere are multiple default gateways in the system. And hence, it is possible tohave two different default gateways in the system, one for the non-PROFINETtraffic and one that only manages the PROFINET interface and its traffic. So whileusing optionPROFINETController/Device the LAN 3 port is used only for PROFINETtraffic.
Link Layer Discovery Protocol (LLDP)The IRC5 controller supports LLDP, but only on one port at a time. PreferrablyLLDP should be used on the PROFINET network. Any network connected to anotherport must have LLDP disabled (or use equipment not supporting LLDP).
Factory Network
Not using LLDP
WANLAN 2 LAN 3
Robot Controller
LAN 1Service
Private PROFINET network
Using LLDP
xx1800000140
Continues on next pageApplication manual - PROFINET Controller/Device 173HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
1 Introduction1.2 PROFINET for IRC5
Continued
Device replacementPROFINET controller supports the device replacement mechanism. When a devicefails, a new, identical device can replace the failed one if plugged in the sametopology location. And this does not need any engineering tool. The new deviceis automatically assigned the same parameters and name as the previous one.The conditions for device replacement to work are:
• You must replace a previously connected device by an identical device withan empty station name at the same topology location. For example, the newdevice is plugged in the same port as previously in a switch.
• This feature requires all switches and devices to support Link Layer DiscoveryProtocol (LLDP). The easiest way to achieve this is to only use ConformanceClass B devices and switches in the PROFINET network.
18 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
1 Introduction1.2 PROFINET for IRC5Continued
2 Hardware overview2.1 Main computer
ConnectionsThe I/O network can be connected to one of the the Ethernet ports WAN, LAN 2,or LAN 3 on the main computer.The following figure illustrates where the Ethernet port connectors, are placed onthe main computer.
xx1500000391
DescriptionLabelConnector
Port to the robot's private network. Intended to be left emptyso that service personnel can use it to connect to the com-puter unit.
ServiceX2
Port to the robot's private network. Normally used to connectthe FlexPendant.
LAN 1X3
Port to the robot's private network.LAN 2X4
By default LAN 3 is configured for an isolated LAN3 network.Can be reconfigured to be a part of the private network.
LAN 3X5
Wide Area Network that can host a public industrial network.WANX6
Note
It is not supported to connect multiple ports of the main computer (X2 - X6) tothe same external switch, unless static VLAN isolation is applied on the externalswitch.
Continues on next pageApplication manual - PROFINET Controller/Device 193HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computer
Intended use of WAN and LAN portsThe WAN port is a public network interface to the controller, typically connectedto the factory network with a public IP address provided by the networkadministrator.The LAN ports are intended for connecting network based process equipment tothe controller, for example industrial networks, cameras, and welding equipment.LAN 2 can only be used as a private network to the IRC5 controller.
Isolated LAN 3 or LAN 3 as part of the private networkThe default configuration is that LAN 3 is configured as an isolated network. Thisallows several robot controller to be connected to the same network, seePROFINETon dedicated industrial network on page 23.
Note
The isolated LAN 3 cannot be used to connect to any HMI device (RobotStudio,Robot Web Services, or PC SDK client) since it does not support the protocolneeded for communication.
WANLAN 2 LAN 3
Private
Robot Controller
LAN 1Service
PublicIsolated
LAN 3
xx1500000393
An alternative configuration is that LAN 3 is part of the private network. The portsService, LAN 1, LAN 2, and LAN 3 then belong to the same network and act justas different ports on the same switch. This is configured by changing the systemparameter Interface, in topic Communication and type Static VLAN, from "LAN 3"to "LAN". See Technical reference manual - System parameters.
WANLAN 2 LAN 3
Private
LAN 1Service
Public
Robot Controller
xx1500000394
Continues on next page20 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computerContinued
One PROFINET network connected to the robot controllerIf PROFINET is used on the public network (WAN port) without an Anybus adapter,PROFINET cannot be used on the private network. Equipment not using PROFINET(for example a camera) can be connected to the private network. To use PROFINETon both the public and private network, an Anybus adapter must be used. SeeUsing Anybus adapter to connect two PROFINET networks on page 24.
PROFINET on factory networkWhen the WAN port is used for connecting to an industrial network, the trafficshares the same media as the factory network and will share bandwidth with othernon industrial network traffic.The following figure illustrates the network when connecting a controller and adevice to the WAN port of the main computer:
WANLAN 2 LAN 3
Private
LAN 1Service
Public
WAN
Factory Network & Industrial Network
LAN 2 LAN 3
Private
Robot Controller 1
LAN 1Service
Robot Controller 2
PLC
Camera
Public
Cell I/O
I/OI/O
PROFINET
xx1500000472
Continues on next pageApplication manual - PROFINET Controller/Device 213HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computer
Continued
PROFINET on private networkThe private network can contain I/O, sensors, etc. for the robot controller. However,it is not possible to connect several robot controllers to the same private network.The following illustration shows two robot controllers with PROFINET (and otherIP traffic) on each private network. The factory network cannot communicate withthe robot controller using PROFINET.
Factory Network
Robot I/O
I/O
Switch
Robot I/O
I/O
I/O
I/O
Switch
Sensor
Camera
WANLAN 2 LAN 3
Private
Robot Controller 1
LAN 1Service
Public
WANLAN 2 LAN 3
Private
Robot Controller 1
LAN 1Service
Public
PLC
PROFINET PROFINET
xx1500000473
Continues on next page22 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computerContinued
PROFINET on dedicated industrial networkBy connecting to the isolated LAN 3 port it is possible to connect several robotcontrollers to a dedicated industrial network.
WAN
Factory Network
LAN 2 LAN 3
Private
Robot Controller 1
LAN 1Service WANLAN 2 LAN 3
Robot Controller 2
LAN 1Service
PLC
Sensor
Cell I/O
I/OI/O
Industrial Network
Isolated
LAN 3Public Private
Isolated
LAN 3Public
Camera
PROFINET
xx1500000474
Continues on next pageApplication manual - PROFINET Controller/Device 233HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computer
Continued
Using Anybus adapter to connect two PROFINET networks
PROFINET on shared factory network and private networkTo be able to use PROFINET on both the public and the private network, an Anybusadapter must be used. If the same factory network is used both for PROFINETcommunication and other communication, both the Anybus adapter and the WANport must be connected to the factory network. For information about the PROFINETAnybus adapter, see Application manual - PROFINET Anybus Device.
WAN
Factory Network
Private
Robot Controller 1
LAN 1Service
PLC
Robot I/O
LAN 2 LAN 3
I/O I/O
Anybus
adapter
WAN
Private
Robot Controller 1
LAN 1Service
Robot I/O
LAN 2 LAN 3
I/O I/O
Public Public
Anybus
adapter
PROFINET PROFINET
PROFINET PROFINET
xx1500000475
PROFINET on dedicated industrial networkIf the PROFINET communication is separated from other communication, an Anybusadapter must be connected to the PROFINET industrial network and the WAN portmust be connected to the factory network.If the PROFINET communication shall be separated from other Ethernetcommunication, an Anybus adapter must be installed and connected to the publicPROFINET industrial network and the WAN port connected to the factory network.
Continues on next page24 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computerContinued
For information about the PROFINET Anybus adapter, see Applicationmanual - PROFINET Anybus Device.
WAN
Factory Network
Private
Robot Controller 1
LAN 1Service
PLC
Robot I/O
LAN 2 LAN 3
I/O I/O
FBA
WAN
Private
Robot Controller 1
LAN 1Service
Robot I/O
LAN 2 LAN 3
I/O I/O
Public Public
Industrial Network
FBA
PROFINET
PROFINET PROFINET
xx1500000476
Application manual - PROFINET Controller/Device 253HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.1 Main computer
Continued
2.2 Ethernet switches
PrerequisitesIt is recommended that switches used in the I/O network support Quality of Service(QoS).I/O devices mark their packets with a priority value. The priority value is used inorder to get better I/O data throughput and shorter delays on the network.Switches and routers are then able to differentiate the device's critical from theother non-critical traffic. To do this, the switches and routers must support Qualityof Service.
26 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.2 Ethernet switches
2.3 I/O devices
LimitationsIt is possible to connect any type of PROFINET-IO compliant I/O device on thePROFINET controller network. All I/O devices should comply with the PROFINETstandard and be conformance tested by PROFINET international. I/O devices maybe mounted inside the IRC5 controller.
Safety I/O devicesPROFINET network supports safety module. It is possible to configure safety I/Odevices and create safety signals to the I/O devices. For more information, referto Application manual - Functional safety and SafeMove2 and Applicationmanual - I/O Configurator.
Application manual - PROFINET Controller/Device 273HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
2 Hardware overview2.3 I/O devices
This page is intentionally left blank
3 Software overview3.1 Information about the internal device
GeneralTo use the PROFINET internal device, the IRC5 controller must be installed witheither the option 888-2 PROFINET Controller/Device or 888-3 PROFINET Device.The PROFINET internal device can be used to:
• connect a PLC to the IRC5 controller.• connect the IRC5 controller to another IRC5 controller which acts as a master.
Predefined networkWhen the robot system is installed with thePROFINET option, a predefined networkwith the name PROFINET is created at system startup.Use RobotStudio or other recommended tool to configure the PROFINET networkfor initial use. For example, by setting the correct network name and IP settings.
Predefined internal deviceWhen the robot system is installed with the PROFINET option, a predefined internaldevice with the name PN_Internal_Device is created at system startup.It is used to define the internal device in the IRC5 controller, which will enable aPLC to connect to the IRC5 controller. There can only be one internal device definedin the IRC5 controller.
GSDML fileIn order to configure a PROFINET network with an external PROFINET configurationtool, a GSDML file for each I/O device needs to be imported into the tool. Thesefiles contains vital information about the PROFINET I/O devices and they shall besupplied by the vendor/manufacturer of the specific PROFINET module.For information on where to find the GSDML file for the IRC5 controller, see Locationof GSDML files on page 32.
Template I/O configuration fileA template I/O configuration file is available for the internal device. The file containspreconfigured names for all available inputs and outputs. The file can be loadedto the controller, using RobotStudio or the FlexPendant, to facilitate and speed upthe configuration.The I/O template configuration file, PN_Internal_Device.cfg, can be obtained fromRobotStudio or the IRC5 controller.
• In the RobotWare installation folder in RobotStudio: ...\RobotPackages\RobotWare_RPK_<version>\utility\service\ioconfig\PROFINET\
• On the IRC5 Controller: <SystemName>\PRODUCTS\<RobotWare_xx.xx.xxxx>\utility\service\ioconfig\PROFINET\
Continues on next pageApplication manual - PROFINET Controller/Device 293HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
3 Software overview3.1 Information about the internal device
Note
Navigate to the RobotWare installation folder from the RobotStudio Add-Ins tab,by right-clicking on the installed RobotWare version in the Add-Ins browser andselecting Open Package Folder.
Input and output sizePROFINET has an internal device with maximum 2048 digital input signals andmaximum 2048 digital output signals. Similarly, for safe PROFINET internal device,you can add safety digital input signals and safety digital output signals.The internal device PN_Internal_Device has two system parameters, Input Sizeand Output Size. Input Size is used to configure the input size of the internal deviceand Output Size configures the output size. A connecting PLC needs to have aslot configuration created in the external PROFINET configuration tool that matchesthe configuration of the internal device.The following table shows a few examples of how the Input Size and Output Sizeparameters can be used to create different slot configurations of a connecting PLC:
Step 7 ConfigurationOutput SizeInput Size
Slot 1: DI 8 bytes8 bytes8 bytesSlot 2: DO 8 bytes
Slot 1: DI 16 bytes16 bytes8 bytesSlot 2: DO 8 bytes
Slot 1: DI 32 bytes32 bytes64 byteSlot 2: DO 64 bytes
Tip
If a configuration mismatch between the connecting PLC and the internal deviceoccurs, an event message is generated on the FlexPendant. This event messageinforms the user of the present slot configuration of the internal device.
Note
The Input Size sets the size on digital outputs and Output size sets the size ondigital inputs, seen from the PLC’s point of view.
30 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
3 Software overview3.1 Information about the internal deviceContinued
3.2 Information about the internal controller
GeneralTo use the PROFINET internal controller, the IRC5 controller must be installed withthe option PROFINET Controller/Device.The PROFINET internal controller can be used to:
• connect PROFINET devices to the IRC5 controller.• connect the IRC5 controller to another IRC5 controller which acts as a device.
GSDML filesIn order to configure a PROFINET network with an external PROFINET configurationtool, GSDML files need to be imported into the tool. These files contains vitalinformation about the PROFINET I/O devices and they shall be supplied by thevendor/manufacturer of the specific PROFINET module.
Configuration programsSee Configuration programs on page 16 and About the third party tool informationon page 71.
Application manual - PROFINET Controller/Device 313HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
3 Software overview3.2 Information about the internal controller
3.3 Software for configuring a device
GeneralThe PROFINET internal device does not need any type of PC software to beactivated, but the connecting PLC / PROFINET controller might need a PC softwaretool to configure all connection parameters used to connect to the IRC5 system.
Location of GSDML filesThe provided GSDML file for the IRC5 PROFINET device is used to inform theconnecting PLC / PROFINET controller of supported connection parameters.The GSDML file,GSDML-V2.xx-ABB-Robotics-PNSW-Device-YYYYMMDD.xml, forthe internal device can be obtained from the RobotStudio or the IRC5 controller.
• In the RobotWare installation folder in RobotStudio: ...\RobotPackages\RobotWare_RPK_<version>\utility\service\GSDML\
• On the IRC5 Controller: <SystemName>\PRODUCTS\<RobotWare_xx.xx.xxxx>\utility\service\GSDML\
Note
Navigate to the RobotWare installation folder from the RobotStudio Add-Ins tab,by right-clicking on the installed RobotWare version in the Add-Ins browser andselecting Open Package Folder.
32 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
3 Software overview3.3 Software for configuring a device
3.4 Software for configuring a controller
PC SoftwareTo configure the PROFINET network in the IRC5 controller, a PROFINETconfiguration file needs to be created and downloaded to the IRC5 controller. ThisPROFINET configuration file has to be created using a third party configurationsoftware. See About the third party tool information on page 71.NetNames+ is a PC software that is used for diagnostics mainly, like setting thename, IP address, Subnet Mask, etc of the internal device. For more information,see NetNames+ on page 72.The following third party software PC tools can be used to create PROFINETconfiguration files:
• PROFINET -IO Configurator Express• PROFINET -IO Configurator Professional
Note
The software PROFINET-IO Configurator Express, together with NetNames+, isfree to use and is included in the RobotWare distribution package.
Note
PROFINET -IO Configurator Professional provides some added functionalitycompared to the PROFINET-IO Configurator Express. For example, functionalityto scan a network and import devices.
Application manual - PROFINET Controller/Device 333HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
3 Software overview3.4 Software for configuring a controller
This page is intentionally left blank
4 Configuring the internal device and external controller4.1 Recommended working procedure
GeneralThis section describes the recommended working procedure when installing andconfiguring a PROFINET internal device. The working procedure helps tounderstand the dependencies between the different steps.When the IRC5 controller is connected to an external master, the IRC5 controlleracts as an ordinary slave device on the PROFINET network.
Do not configure parameters while exchanging I/O dataIt is important to make sure that the PROFINET network is not involved in any I/Odata exchange before configuring the parameters.If for example the PROFINET internal device is exchanging I/O data with a PLC, itis not possible to change the IP address or any other settings of the PROFINETnetwork.
Basic stepsUse this procedure to install and configure a PROFINET device.
SeeAction
Technical referencemanual - System paramet-ers
Use RobotStudio to configure the topicCommunication.
1
Configuring the PROFINET network settingson page 36
Use RobotStudio, or an externalPROFINET network browser tool, toconfigure the PROFINET network set-tings.
2
Configuring the internal device on page 38Create and configure the internal devicein the IRC5 controller using RobotStu-dio or the FlexPendant.
3
Configuring the external controller on page39Configure the external controller usingthe vendor specific configuration tool.
4
Application manual - PROFINET Controller/Device 353HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller4.1 Recommended working procedure
4.2 Configuring the PROFINET network settings
GeneralThe following procedure describes how to change the PROFINET network settingsusing RobotStudio.
External toolsThese settings, except Connection, can also be configured using an externalPROFINET network browser tool.Many external PROFINET tools have overlapping functionality when it comes tochanging the network settings. This means that for example a network addressset in RobotStudio can be overwritten by an external tool in a subsequent step.The overwritten settings will not be applied immediately but after the next restartof the IRC5 controller. Therefore, it is important to have a good working procedureto avoid that parameters are overwritten.
Note
Note that the network settings are set for the Connection, i.e. the physicalconnector on the main computer used for the PROFINET network.This means that the network settings are shared between the internal device andthe internal controller if the IRC5 controller acts as both on the PROFINETnetwork.
Network configurationUse this procedure to configure the PROFINET network settings in the IRC5controller, using RobotStudio.
NoteAction
Start RobotStudio and connect to theIRC5 controller. Request write access.
1
For more information about the paramet-ers, see System parameters on page 49.
Open theConfiguration Editor and selectI/O System.
2
xx1400002055
In the Type list click Industrial Networkand edit the parameter PROFINET.Edit the parameter values, if applicable.
• Connection, the physical connect-or on the main computer.
• ConfigurationFile, empty for intern-al device.
• PROFINET Station Name, userdefined.
• Simulated, user defined.Click OK.
3
Configuring the internal device on page38Restart the controller, or continue with thenext step of the configuration.
4
Continues on next page36 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller4.2 Configuring the PROFINET network settings
Note
Gateway is chosen from one of the configured instances of IP Route (seeTechnical referencemanual - System parameters). The gateway is matched withthe configured IP Setting pointed out by the Connection parameter for theIndustrial Network (see Connection on page 52). If the gateway is found to beon the same network as defined by the IP Setting for the Industrial Network, itis chosen.
Application manual - PROFINET Controller/Device 373HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller4.2 Configuring the PROFINET network settings
Continued
4.3 Configuring the internal device
GeneralThe internal device is pre-installed at the system startup. However, the input andoutput size of the device can be changed. The size of the internal device determineshow many signals that can be attached, see Input and output size on page 30.This section describes the recommended working procedure of configuring ainternal device. The working procedure helps to understand the dependenciesbetween the different steps.
Note
It is only possible to have one internal device.
Internal device configurationUse this procedure to create and configure the internal device in the IRC5 controller,using RobotStudio.
NoteAction
Start RobotStudio and connect to theIRC5 controller. Request write access.
1
For more information about the paramet-ers, see System parameters on page 49.
Open theConfiguration Editor and selectI/O System.
2
xx1400002056
In the Type list, click PROFINET InternalDevice, right-click in the workspace andselect PROFINET Internal Device.Edit the parameter values for the internaldevice, if applicable.
• Change the default values for InputSize and Output Size to the de-sired size.
Note
This step is optional, for more in-formation see Input and output sizeon page 30.
Click OK.
3
In the Type list click Signal.4Add I/O signals for the internal device.
Restart the controller.5
38 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller4.3 Configuring the internal device
4.4 Configuring the external controller
GeneralThe external controller is configured using the vendor specific configuration toolthat is delivered, or bought, together with the controller.The tool is used to specify all the devices in the PROFINET network. One of thedevices is the internal device of the IRC5 controller. To create such a device, theGSDML file describing the internal device has to be imported into the vendorspecific configuration tool, see Location of GSDML files on page 32.All other I/O devices used in the network also has to have its GSDML file imported.
ExampleAs an example, a Siemens PLC is used to configure an external controller. Theprocedure to configure an external controller using Siemens Step 7 PC tool isdescribed in the Appendices. See Using Siemens Step 7 PC tool on page 75.
External controller configurationThis procedure describes the general steps that needs to be performed whenconfiguring an external controller, independent of which tool is used.
Action
Use the external controller configuration tool to:• Specify the IP address range that the external PROFINET controller operates
within.• Import the GSDML files for the internal device and all other types of I/O devices
in the network.• Add the IRC5 controller I/O device and set the same IP address as the
PROFINET industrial network.• Add any other I/O devices.• Set the properties of the I/O devices to reflect the device's properties on the
PROFINET network.
1
Application manual - PROFINET Controller/Device 393HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller4.4 Configuring the external controller
This page is intentionally left blank
5 Configuring the internal controller and external device5.1 Recommended working procedure
GeneralThis section describes the recommended working procedure when installing andconfiguring a PROFINET controller. The working procedure helps to understandthe dependencies between the different steps.
Basic stepsUse this procedure to install and configure a PROFINET controller.
SeeAction
Technical referencemanual - System paramet-ers
Use RobotStudio to configure the topicCommunication.
1
Configuring the PROFINET network settingson page 36
Use a PROFINET network browser toolto configure the PROFINET networksettings.
2
Creating the PROFINET configuration file onpage 42
Use an external PROFINET configura-tion tool to create a project that con-tains the configuration of thePROFINET network.
3
Configuring the IRC5 controller on page 43Download the PROFINET configurationfile to the controller.
4
Configure the I/O devices connected tothe PROFINET network using RobotStu-dio or FlexPendant.
5
Additional configuration
SeeAction
Using Fast Device Startup on page 44Configuring Fast Device Startup.
Using Shared Device on page 46Configuring Shared Device.
Examples
SeeAction
Using PROFINET Configurator Express onpage 79
Creating master network configuration fileusing PROFINET-IO Configurator Express.
Application manual - PROFINET Controller/Device 413HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.1 Recommended working procedure
5.2 Creating the PROFINET configuration file
GeneralThe PROFINET configuration file can be created with the help of an externalPROFINET configuration tool. This section describes the basic steps that needsto be performed independent of which tool is used.
ExamplesAs an example, PROFINET Configurator Express is used to create a configurationfile. The procedure is described in the Appendices. See Using PROFINETConfigurator Express on page 79 .
Basic stepsThis procedure describes the general steps that needs to be performed whencreating a controller network configuration file, independent of which tool is used.
Action
Use the PROFINET configuration tool to:• Specify the IP address range that the PROFINET internal controller operates
within.• Set the same IP address for the PROFINET industrial network as specified
in the system parameter IP Address in the IRC5 controller.• Import the GSDML files for all types of I/O devices in the network.• Add the I/O devices into the network structure.• Set the properties of the I/O devices to reflect the device's properties on the
PROFINET network.
1
Build the project and create the PROFINET configuration file, ippnio.xml.2
The next step is to download the ippnio.xml file to the HOME directory of thecurrently used RobotWare system, seeConfiguring the IRC5 controller on page43.
42 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.2 Creating the PROFINET configuration file
5.3 Configuring the IRC5 controller
DescriptionThis configuration example uses the PROFINET configuration file, ippnio.xml,created in section Creating the PROFINET configuration file on page 42. It showshow to use the PROFINET configuration file and how to add the configurationdefinitions to the system parameters.
Internal controller configurationUse this procedure to configure the PROFINET controller in the IRC5 controller,using the Configuration Editor in RobotStudio.
NoteAction
Start RobotStudio and connect to the IRC5controller. Request write access.
1
Use the File Transfer tool in RobotStudio,or an external FTP client.
Download the ippnio.xml configuration fileto theHOME directory of the currently usedRobotWare system.
2
Click Configuration Editor and select I/OSystem.
3
For more information about the parameters,see System parameters on page 49.
In the type list, click Industrial Networkand then right-click in the workspace onthe PROFINET item and select Edit Indus-trial Network.
4
xx1500000937
Enter the parameter values for the industri-al network.
• Connection, select the used Ether-net connector.
Note
The Connection value is configuredin Communication topic. A defaultconnection is created forPROFINET. For information aboutIP address configuration, see Tech-nical reference manual - Systemparameters, section 2.2 Communic-ation, Use case 2: isolated LAN 3.
• Configuration File, the path to theippnio.xml file.
• PROFINET Station name, the ro-bot's PROFINET name id on thePROFINET network.
Click OK.
5
Restart the IRC5 controller.6In this example, the et200_test device(found in the example file ippnio.xml) isadded.
If needed, change the signal names on theadded I/O device.
7
Restart the IRC5 controller to connect tothe configured I/O device.
8
Application manual - PROFINET Controller/Device 433HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.3 Configuring the IRC5 controller
5.4 Using Fast Device Startup
About Fast Device StartupThe Fast Device Startup functionality is used in tool changing applications toshorten the connection time between the PROFINET controller and an I/O device.To be able to use this functionality, the I/O device needs to support this functionality.All devices must support fast startup in the communication chain. Devices suchas switches or other intermediate hardware that could affect the PROFINETcommunication. For more information, see Poor performance using fast startupon page 69.Some manufacturers also call this functionality Fast Start Up (FSU) or PrioritizedStartup.To activate Fast Device Startup against an I/O device, activate the system parameterFast Device Startup and select the corresponding port(s) to be configured. SeeFast Device Startup on page 57.
Note
The I/O device with FSU functionality is connected with the IRC5 controller. Whenthe power of the I/O device is switched off and switched on again, the IRC5controller establishes contact with the I/O device using the fast startup sequence.
Three alternative connections
I/O device connected via a switch
xx1100000093
IRC5 controller acting as PROFINET controllerA
SwitchB
Connection pointC
I/O deviceD
Port 1 on the deviceF
Port 2 on the deviceG
In this alternative the PROFINET controller connects to the I/O device via a switch.Enable fast device startup and select 100 MBit (full duplex) on port 1. The portnumber is usually displayed upon the I/O device itself.
Continues on next page44 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.4 Using Fast Device Startup
Two I/O devices connected in serial via a switch
xx1100000094
IRC5 controller acting as PROFINET controllerA
SwitchB
Connection pointC
I/O deviceD
I/O deviceE
In this alternative, both I/O devices are disconnected at the connection point. Bothport 1 and port 2 on the first device (D) and port 1 on the second device (E) needsto be configured to support Fast Device Startup.
I/O device connected without a switch
A
C
D
xx1100000095
IRC5 controller acting as PROFINET controllerA
Connection pointC
I/O deviceD
In this alternative there is a direct cable between the PROFINET controller and theI/O device. Enable fast device startup and select 100 MBit (full duplex) on the port.A crossed Ethernet cable needs to be used.
Application manual - PROFINET Controller/Device 453HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.4 Using Fast Device Startup
Continued
5.5 Using Shared Device
5.5.1 About Shared Device
IntroductionShared device functionality is when two controllers are sharing a device. Eachcontroller has the ownership over different modules on the device.
Note
The internal device itself cannot be configured to be a shared device.
I/O device modules
Controller 1 Controller 2
xx1400002064
Configuring PROFINET controller with shared device functionality
Basic steps
SeeAction
Using PROFINET Configurator Ex-press on page 79
Use the external PROFINET configuration tool tocreate a project that contains the configuration ofthe PROFINET network.
1
Updating configuration file to sup-port shared device functionality onpage 83.
Update the project in PROFINET configurationtool to create shared device functionality.
2
Download the PROFINET configuration file to theIRC5 controller.
3
Configuring the IRC5 controller onpage 43
Configure the I/O devices connected to thePROFINET network using RobotStudio or theFlexPendant.
4
Continues on next page46 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.5.1 About Shared Device
SeeAction
Technical reference manual - Sys-tem parameters
Configure the I/O signals.5
Restart the IRC5 controller.6
Updating PROFINET configuration file for shared deviceThis section describes how to update the configuration file with the shared devicefunctionality, where the configuration file is created by using the PROFINETConfigurator Express tool.For details on installing the PROFINET Configurator Express, see PROFINET-IOConfigurator Express on page71 andUpdating configuration file to support shareddevice functionality on page 83.
Application manual - PROFINET Controller/Device 473HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device5.5.1 About Shared Device
Continued
This page is intentionally left blank
6 System parameters6.1 Introduction
About the system parametersThere are both PROFINET specific parameters and more general parameters. Thischapter describes all PROFINET specific system parameters. The parameters aredivided into the type they belong to. For information about other parameters, seeTechnical reference manual - System parameters.
PROFINET system parameters
Industrial NetworkThese parameters belong to the type Industrial Network in the topic I/O System.
For more information, see ...Parameter
Technical reference manual - System parametersName
Technical reference manual - System parametersIdentification Label
Connection on page 52Connection
Configuration File on page 53Configuration File
PROFINET Station Name on page 54PROFINET Station Name
Nested Diagnosis on page 55Nested Diagnosis
PROFINET DeviceThese parameters belong to the type PROFINET Device in the topic I/O System.
For more information, see ...Parameter
Technical reference manual - System parametersName
PROFINET Station Name on page 56PROFINET Station Name
Technical reference manual - System parametersConnected to IndustrialNetwork
Technical reference manual - System parametersState at System Restart
Technical reference manual - System parametersIdentification Label
Technical reference manual - System parametersTrust Level
Technical reference manual - System parametersSimulated
Technical reference manual - System parametersVendor Name
Technical reference manual - System parametersRecovery Time
Fast Device Startup on page 57Fast Device Startup
Fast Device Startup on page 57Port1, 2, 3, 4
Energy Saving on page 62Energy Saving
Continues on next pageApplication manual - PROFINET Controller/Device 493HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.1 Introduction
SignalThese parameters belong to the type Signal in the topic I/O System.
For more information, see ...Parameter
Technical reference manual - System parametersName
PROFINET Station Name on page 56Type of Signal
Technical reference manual - System parametersAssigned to Device
Technical reference manual - System parametersSignal Identification Label
Technical reference manual - System parametersDevice Mapping
Technical reference manual - System parametersCategory
Technical reference manual - System parametersAccess Level
Technical reference manual - System parametersDefault Value
Technical reference manual - System parametersFilter Time Passive (ms)
Fast Device Startup on page 57Filter Time Active (ms)
Fast Device Startup on page 57Invert Physical Value
Energy Saving on page 62Analog Encoding Type
Technical reference manual - System parametersMaximum Logical Value
Technical reference manual - System parametersMaximum Physical Value
Technical reference manual - System parametersMaximum Physical ValueLimit
Technical reference manual - System parametersMaximum Bit Value
Technical reference manual - System parametersMinimum Logical Value
Technical reference manual - System parametersMinimum Physical Value
Technical reference manual - System parametersMinimum Physical ValueLimit
Technical reference manual - System parametersMinimum Bit Value
Transfer To Device on page 63Transfer To Device
Output Offset on Destination Device on page 64Output Offset On Destina-tion Device
Transfer From Device on page 65Transfer From Device
Input Offset on Source Device on page 66Input Offset On SourceDevice
PROFINET Internal DeviceThese parameters belong to the type PROFINET Internal Device in the topic I/OSystem.
For more information, see ...Parameter
Technical reference manual - System parametersName
Technical reference manual - System parametersConnected to IndustrialNetwork
Technical reference manual - System parametersSimulated
Technical reference manual - System parametersVendor Name
Continues on next page50 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.1 IntroductionContinued
For more information, see ...Parameter
Technical reference manual - System parametersProduct Name
Technical reference manual - System parametersIdentification Label
Input Size on page 67Input Size
Output Size on page 68Output Size
Application manual - PROFINET Controller/Device 513HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.1 Introduction
Continued
6.2 Type Industrial Network
6.2.1 Connection
ParentConnection belongs to the type Industrial Network, in the topic I/O System.
Cfg nameConnection
DescriptionThe parameter Connection specifies the IP Setting that the PROFINET industrialnetwork shall use.
Default valuePROFINET Network
Allowed valuesValid instances of IP Setting
Additional informationThe Public Network or the Private Network cannot be edited by external controllersor tool, such as NetNames+.
52 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.2.1 Connection
6.2.2 Configuration File
ParentConfiguration File belongs to the type Industrial Network, in the topic I/O System.
Cfg nameCfgPath
DescriptionConfiguration File specifies the path to an XML file that is located on the IRC5controller. This file is created and edited with the program PROFINET-IOConfigurator Express or PROFINET-IO Configurator Professional, see Creatingthe PROFINET configuration file on page 42.
UsageThe Configuration File system parameter is used to point out where to find thePROFINET controller configuration file. This file is only used by the controller part.If the file is placed in the HOME directory of the installed system on the IRC5controller, it is enough to write the file name.If the PROFINET configuration file is placed in the HOME directory, it will also beincluded in backups.
PrerequisitesThe option PROFINET Controller/Device must be installed.
Default valueThe default value is an empty string.
Allowed valuesA string with maximum 80 characters.
Application manual - PROFINET Controller/Device 533HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.2.2 Configuration File
6.2.3 PROFINET Station Name
ParentPROFINET Station Name belongs to the type Industrial Network, in the topic I/OSystem.
Cfg nameStationName
DescriptionPROFINET Station Name specifies the PROFINET station name on the network ofthe IRC5 controller.
UsageThe parameter PROFINET Station Name is used to identify a PROFINET deviceon the network. The name must be unique on the network.The parameter PROFINET Station Name can also be changed with an externalPROFINET configuration tool or a connecting PROFINET controller.
PrerequisitesThe option PROFINET Controller/Device or PROFINET Device must be installed.
Default valueThe default value is an empty string.
Allowed valuesA string with maximum 80 characters.Allowed characters:
• 0-9 (numerical)• A-Z (uppercase letters)• a-z (lowercase letters)• - (hyphen)• . (full stop)
54 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.2.3 PROFINET Station Name
6.2.4 Nested Diagnosis
ParentNested Diagnosis belongs to the type Industrial Network, in the topic I/O System.
Cfg nameNesteddiagnosis
DescriptionThe parameter Nested Diagnosis specifies diagnosis in hierarchical plants andenables the end-users to evaluate the status of the PROFINET network from acentral PLC or external tool.
UsageIf the parameter Nested Diagnosis is activated, alarms will be forwarded from acontroller if its internal device has a connected controller.
PrerequisitesThe option PROFINET Controller/Device or PROFINET Device must be installed.
Default valueThe default value is Deactivated.
Allowed valuesActivatedDeactivated
Application manual - PROFINET Controller/Device 553HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.2.4 Nested Diagnosis
6.3 Type PROFINET Device
6.3.1 PROFINET Station Name
ParentPROFINET Station Name belongs to the type PROFINET Device, in the topic I/OSystem.
Cfg nameStationName
DescriptionPROFINET Station Name specifies the PROFINET station name on the network ofthe external I/O device.
UsageThe parameter PROFINET Station Name is used to identify a PROFINET deviceon the network. The name must be unique on the network.
PrerequisitesThe option PROFINET Controller/Device or PROFINET Device must be installed.
Default valueThe default value is an empty string.
Allowed valuesThe station name follows the PROFINET naming convention for IO devices.
Note
It is possible to set the PROFINET station name of a device and it does not followthe naming restriction as the CFG name, which still has restrictions of a RAPIDIdentifier.
56 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.1 PROFINET Station Name
6.3.2 Fast Device Startup
ParentFast Device Startup belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameFastDeviceStartup
DescriptionThe parameter Fast Device Startup specifies if the I/O device should use a fasterconnection attempt algorithm or not.
UsageThe parameter Fast Device Startup is used mainly to speed up tool changeapplications. The usual PROFINET connection attempt takes a few seconds tocomplete, but with Fast Device Startup enabled devices, this time is shortened toless than a second. For more information, see Using Fast Device Startup onpage 44.
PrerequisitesThe option PROFINET Controller/Device must be installed.
LimitationsThe Ethernet switches between the IRC5 controller and the I/O device that usesthe Fast Device Startup functionality. It must be configured to disable the autocrossover and automatic speed detection functions on used connectors. The speedrate is set to 100Mbps (full duplex).
Default valueThe default value is Deactivated.
Allowed values• Deactivated• Activated• Support
Note
Select Support to set the desired port speed. For port speed, select 100 Mbpsand the port speed is adjusted to 100Mbps, and auto negotiation is turned offfor the port.Hence, it is possible to change the settings on a built-in switch for a PROFINETI/O device.
Application manual - PROFINET Controller/Device 573HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.2 Fast Device Startup
6.3.3 Port 1
ParentPort 1 belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameFastDeviceStartup_Port1
DescriptionThe parameter Port 1 specifies fast device startup port 1 in the I/O device.
UsageThe parameter Fast Device Startup is configured at port 1 of the I/O device.
PrerequisitesThe parameter Fast Device Startup must be activated.
Default valueThe default value is Deactivated.
Allowed values• Deactivated• 100 Mbps
58 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.3 Port 1
6.3.4 Port 2
ParentPort 2 belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameFastDeviceStartup_Port2
DescriptionThe parameter Port 2 specifies fast device startup port 2 in the I/O device.
UsageThe parameter Fast Device Startup is configured at port 2 of the I/O device.
PrerequisitesThe parameter Fast Device Startup must be activated.
Default valueThe default value is Deactivated.
Allowed values• Deactivated• 100 Mbps
Application manual - PROFINET Controller/Device 593HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.4 Port 2
6.3.5 Port 3
ParentPort 3 belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameFastDeviceStartup_Port3
DescriptionThe parameter Port 3 specifies fast device startup port 3 in the I/O device.
UsageThe parameter Fast Device Startup is configured at port 3 of the I/O device.
PrerequisitesThe parameter Fast Device Startup must be activated.
Default valueThe default value is Deactivated.
Allowed values• Deactivated• 100 Mbps
60 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.5 Port 3
6.3.6 Port 4
ParentPort 4 belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameFastDeviceStartup_Port4
DescriptionThe parameter Port 4 specifies fast device startup port 4 in the I/O device.
UsageThe parameter Fast Device Startup is configured at port 4 of the I/O device.
PrerequisitesThe parameter Fast Device Startup must be activated.
Default valueThe default value is Deactivated.
Allowed values• Deactivated• 100 Mbps
Application manual - PROFINET Controller/Device 613HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.6 Port 4
6.3.7 Energy Saving
ParentEnergy Saving belongs to the type PROFINET Device, in the topic I/O System.
Cfg nameEnergy Saving
DescriptionThe parameter Energy Saving specifies if the I/O device should respond to energysaving command or not.
UsageThe parameter Energy Saving is used mainly to activate energy saving mode.
PrerequisitesThe option PROFINET Controller/Device and PROFIenergy must be installed.
Default valueThe default value is Activated.
Allowed values• Activated• Deactivated
62 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.3.7 Energy Saving
6.4 Type Signal
6.4.1 Transfer To Device
ParentTransfer To Device belongs to the type Signal, in the topic I/O System.
Cfg nameTransferToDevice
DescriptionThe parameter Transfer To Device specifies that the signal shall be transferred tothe internal device starting at the offset specified in the parameter Output OffsetOn Destination Device.
PrerequisitesThe option PROFINET Controller/Device must be installed.
LimitationsOnly signals of type Digital Output/ Digital Input/ Group Output/ Group Input canbe transferred. The destination I/O device can only be the PROFINET internaldevice.
Allowed valuesThe allowed value is the PROFINET internal device.
Application manual - PROFINET Controller/Device 633HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.4.1 Transfer To Device
PROFINET Controller/Device
6.4.2 Output Offset on Destination Device
ParentOutput Offset On Destination Device belongs to the type Signal, in the topic I/OSystem.
Cfg nameTransferOutputOffset
DescriptionThe parameter Output Offset On Destination Device specifies the output start biton the PROFINET internal device set by the transfer signal.
PrerequisitesThe option PROFINET Controller/Device must be installed.
LimitationsThe destination I/O device can only be the PROFINET internal device.
Default valueThe default value is -1. This means that no Output Offset On Destination Deviceis defined.
Allowed valuesThe values are in the range of -1 to 65535.
Additional informationThe parameter Output Offset On Destination Device specifies the start bit on theinternal device. And, for bits specified in a group are transferred starting with thefirst bit.
64 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.4.2 Output Offset on Destination DevicePROFINET Controller/Device
6.4.3 Transfer From Device
ParentTransfer From Device belongs to the type Signal, in the topic I/O System.
Cfg nameTransferFromDevice
DescriptionThe parameter Transfer From Device specifies that the bit value for the internaldevice (starting at the offset specified in the parameter Input Offset On DestinationDevice) shall be transferred to the signal.
PrerequisitesThe option PROFINET Controller/Device must be installed.
LimitationsOnly the input bits from the PROFINET internal device can be transferred to thesignals of type digital output and group output.
Allowed valuesThe allowed value is the PROFINET internal device.
Application manual - PROFINET Controller/Device 653HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.4.3 Transfer From Device
PROFINET Controller/Device
6.4.4 Input Offset on Source Device
ParentInput Offset on Source Device belongs to the type Signal, in the topic I/O System.
Cfg nameTransferInputOffset
DescriptionThe parameter Input Offset on Source Device specifies the input start bit PROFINETinternal device that will be transferred to the defined signal.
PrerequisitesThe option PROFINET Controller/Device must be installed.
LimitationsThe transfer is possible only to the signals of type digital output and group output.For all cases, it is possible to transfer information from the internal device to signalsdefined on other PROFINET I/O devices only.
Default valueThe default value is -1. This means that Input Offset on Source Device is not defined.
Allowed valuesThe values are in the range of -1 to 65535.
Additional informationThe parameter Input Offset On Destination Device specifies the start bit on theinternal device. The bits specified in a group are transferred starting with the firstbit.
66 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.4.4 Input Offset on Source DevicePROFINET Controller/Device
6.5 Type PROFINET Internal Device
6.5.1 Input Size
ParentInput Size belongs to the type PROFINET Internal Device, in the topic I/O System.
Cfg nameInputSize
DescriptionThe parameter Input Size is used to configure the input slot configuration of thePROFINET internal device.
UsageIt will configure the input slot size for the PROFINET internal device. This size mustmatch the connecting PLC’s or other PROFINET controller’s defined output slotsize. For more information, see Input and output size on page 30.
PrerequisitesThe option PROFINET Controller/Device or PROFINET Device must be installed.
Default valueThe default value is 64 bytes (512 signal bits).
Allowed values8, 16, 32, 64, 128 or 256 bytes (64, 128, 512, 1024 or 2048 signal bits).
Application manual - PROFINET Controller/Device 673HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.5.1 Input Size
6.5.2 Output Size
ParentOutput Size belongs to the type PROFINET Internal Device, in the topic I/O System.
Cfg nameOutputSize
DescriptionThe parameter Output Size is used to configure the output slot configuration ofthe PROFINET internal device.
UsageThe parameterOutput Size is only valid for the PN_Internal_Device. It will configurethe output slot size for the PROFINET internal device. This size must match theconnecting PLC’s or other PROFINET controller’s defined input slot size. For moreinformation, see Input and output size on page 30.
PrerequisitesThe option PROFINET Controller/Device or PROFINET Device must be installed.
Default valueThe default value is 64 bytes (512 signal bits).
Allowed values8, 16, 32, 64, 128 or 256 bytes (64, 128, 512, 1024 or 2048 signal bits).
68 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters6.5.2 Output Size
7 Troubleshooting7.1 Scenarios
Problem assigning IP address or station nameIf an external PROFINET configuration tool is used to set IP address or stationname for a controller or device, it may not be possible to perform that operation.In such a case, make sure that the device or PLC is not involved in any I/O dataexchange. If, for example, a device or PLC is exchanging data with another deviceor PLC, it is not possible to change the IP address or station name of those devices.
Unable to connect to a deviceIf all parameters are correct, but it is still not possible to connect to an device usingthe PROFINET controller, make sure that the device does not already have anactive connection with another controller. Most I/O devices do not accept that twocontrollers are connected against the same I/O device at the same time. That is,if the device does not allow shared device functionality.
Connections are lost randomlyLost connections can occur for a number of reasons.
• Bad network• Overloaded Ethernet switches• Ethernet cable problems
Another possible reason is that the IRC5 PROFINET is not able to process all thePROFINET requests within the specified time frame. If, for example, 20 I/O devicesare used with 1 ms reduction ratio (poll rate), the slightest variation of CPU loadon the main computer might cause a protocol disturbance which can lead to aconnection timeout. The maximum possible devices that can be used depends onthe reduction ratios used, CPU load and data lengths transferred at every datacycle.There can be connection loss while configuring PROFINET Master on the samelogical subnet as other applications, on the WAN port. It might cause sporadic lossof communication for the applications as well as for the PROFINET communication.
Poor performance using fast startupIn general the startup time for one I/O device using fast startup is less than asecond, together with the robot controller. This is highly dependent upon the deviceitself. Check with the device vendor for detailed description about I/O devices thatsupport fast startup with corresponding performance figures.
• If there are other intermediate hardware on the connection link that mightinterfere with the PROFINET connection.
• If there is a chained setup containing multiple devices, there is an increasedlatency before all devices are running. Depending upon the number of chaineddevices the total connection time can be more than a second.
Continues on next pageApplication manual - PROFINET Controller/Device 693HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
7 Troubleshooting7.1 Scenarios
• Make sure that the port/ports used for fast startup is selected in the IOconfiguration.
• Check with the device vendor for optimal settings when using the I/O devicewith fast startup. Sometimes device behavior is configurable with a vendorspecific tool or through the network configuration tool. According to theGSDML file.
• Check that the switch settings are correct according to below:- 100 Mbit speed rate with full duplex.- Auto negotiation shall be switched off.- Disable "switch intelligent features" such as flow control and MDIX
(medium dependent interface crossover) that might cause delays duringstartup.
Configuration of AC500 with an IRC5 device in Automation Builder (Control Builder Plus)Use this procedure to configure the AC500 with an IRC5 device in the AutomationBuilder:
NoteAction
In the AC500 project, select the appropri-ate PROFINET controller.
1
xx1500003223
Double-click on the IRC5 device icon toselect the IRC5 device.
2
In the PNIO parameters tab, edit the fieldRT Class to RT Class 2 Data-RTC-PDU.
3
ID mismatch on PROFINET controllerIf the diagnostics from the PROFINET controller say something like "Peer Port IDmismatch" or "Peer Chassis ID mismatch":This can be caused by more than one network connected to the robot controllerusing LLDP. For more information, see Link Layer Discovery Protocol (LLDP) onpage 17.
70 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
7 Troubleshooting7.1 ScenariosContinued
A About the third party tool informationOverview
There are external software tools available to configure the PROFINET controller.This section describes some of the external tools and procedure of configuringthe controller.
Validity of the information for third party toolsThe information is available "as is", and should only be used for reference. Thethird party tools can include functionality that is not supported in IRC5.The information about the third party tools is applicable for specific versions of thethird party tools and RobotWare. Other versions of the tools can also be used butare not tested by ABB.
PROFINET-IO Configurator ExpressPROFINET-IO Configurator Express is a PC software used to create PROFINETconfiguration files.The PROFINET-IO Configurator Express package is available in the RobotWaredistribution package.
InstallationThe installation can be downloaded from the RobotStudio Online Community,where it is included in the RobotWare Tools and Utilities package.Use this procedure to install the PROFINET-IO Configurator Express package,including NetNames+.
Action
Go to the RobotStudio Online Community and click Downloads to open the SoftwareDownloads webpage.
1
In Software Downloads webpage, under Miscellaneous group, click Download Ro-botWare Tools and Utilities.
2
After the package is downloaded, unzip the package.3
Locate the file and run the PROFINET configurator.exe file.
Note
After the download, the folder path is: C:\Users\...\Downloads\RobotWare Tools andUtilities 6.01\Utilities\Fieldbus\Profinet
4
Follow the instructions on the installation window.5
Note
Please refer to www.kw-software.com for information about system requirementsand limitations when running the PROFINET-IO Configurator Express tool.
Continues on next pageApplication manual - PROFINET Controller/Device 713HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
A About the third party tool information
NetNames+NetNames+ is a PC software used to manage the PROFINET network, organizethe PROFINET devices, and avoid duplicated IP addresses and station names.NetNames+ is included in the PROFINET-IO Configurator Express package availablein the RobotWare distribution package.
xx1300002216
InstallationNetNames+ is included in the PROFINET-IO Configurator Express installation, seePROFINET-IO Configurator Express on page 71.Use this procedure to install the NetNames+.
NoteAction
Start NetNames+.1
Select Network Adapter to the Ethernetadapter used on the PC that connects tothe PROFINET network.
2
Click Options and make sure that SaveIP Addresses permanently is selected.This makes sure that a name or IP ad-dress change sent down from NetNames+is saved by the PROFINET device.
3
Now NetNames+ will list all PROFINETdevices that are reachable on the network.Using this view, it is possible to changea device configuration parameters.
Click the Refresh button.4
Note
Gateway cannot be set, see Limitations.
To change a device's parameters, double-click on that device and fill in the valuesthat need to be changed.When done, click the Send button.
5
Continues on next page72 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
A About the third party tool informationContinued
Fault indicationIf there is a problem with a device, like duplicated IP address, the device will bemarked red.
en1100000261
Device identificationSometimes it is difficult to distinguish devices in the network from each other. Auseful function in such a case is the Flashing On functionality. This will send arequest to the selected device to flash its status LEDs.
Action
Select a device from the list and click the Flashing On button.1
The status LED on the selected device will start to flash.2
Click the Flashing On button again to stop the status LED from flashing.3
LimitationsSince the gateway is chosen from IP Route and must be valid to our system it isnot possible to set the gateway externally from DCP request, ie.AddressAssignMode is LOCAL when it comes to the gateway parameter.
Application manual - PROFINET Controller/Device 733HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
A About the third party tool informationContinued
This page is intentionally left blank
B Using Siemens Step 7 PC toolConfiguring an external controller using Siemens Step7 PC tool
DescriptionThis is a configuration example for an internal device with 32 byte input and 32byte output size. The example also shows how to configure a PLC that connectsagainst the internal device.This example uses the Siemens Step7 PC tool. The procedure can be used withother tools as well. See the documentation for your PLC configuration tool.
Configuring the internal deviceUse the procedure described in sections Configuring the PROFINET networksettings on page 36 and Configuring the internal device on page 38. Set the InputSize and Output Size to 32 bytes.
Configuring the external controllerUse this procedure to configure a Siemens PLC to connect to the internal device,using Siemens Step 7.
NoteAction
en1000001189
Start Simatic Manager and create a newPLC project. Open the HW Config windowfor the PLC hardware configuration.
1
Make sure the PROFINET network connec-ted to the PLC is the same as the networkconnected to the IRC5 controller’sPROFINET network port. Also make surethat they are on the same logical subnet IPaddress range. See Configuring thePROFINET network settings on page 36.
2
Continues on next pageApplication manual - PROFINET Controller/Device 753HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
B Using Siemens Step 7 PC tool
NoteAction
en1000001190
Install the GSDML file for the PROFINETinternal device. The GSDML file is includedin the controller software, see GSDML fileon page 29.
3
en1000001191
Expand PROFINET IO \ Additional FieldDevices \ I/O \ IRC5 PNIO-Device in thecatalog view to the right, to find thePROFINET internal device. Add the IRC5PNIO-Device to the PLC project.
4
en1000001192
Add a DI 32 bytes module on Slot 1 and aDO 32 bytes module on Slot 2.
5
Continues on next page76 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
B Using Siemens Step 7 PC toolContinued
NoteAction
en1000001193
Double-click on the ABB icon to bring upthe Properties window. Make sure thatDevice name is set to the same name asthe IRC5’s PROFINET industrial networkparameter PROFINET Station Name, seePROFINET Station Name on page54. Alsomake sure thatAddress is the same as thesystem parameter IP used by thePROFINET network.
6
Download the configuration to the PLC.7
Application manual - PROFINET Controller/Device 773HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
B Using Siemens Step 7 PC toolContinued
This page is intentionally left blank
C Using PROFINET Configurator ExpressCreating controller network configuration file using PROFINET Configurator Express
DescriptionThe following example is performed using PROFINET Configurator Express.This example demonstrates how to create a PROFINET configuration file for onedevice, a Siemens ET200S with 5 DO 2-bit modules and 1 DI 2-bit module.
Action
Start PROFINET-IO Configurator Express.1
In PROFINET-IO Configurator Express, click File and select New to create a newempty project.
2
Click File and select Save to save the new project. Use the name "TestProject".3
In the Bus Structure window, make sure that the "TestProject" node is selected.4
In the Device Details window, set the PROFINET IP range for this project by settingthe following parameters:
• Last IP Address: 192.168.5.254• First IP Address: 192.168.5.2• Subnetmask: 255.255.255.0
en1100000063
5
In the Device Catalog window, expand the nodes Phoenix Contact Software GmbH,Generic PN and PLC.
• Select the PLC version that corresponds to the current version of the PhoenixContact Software. Currently, it is 3.9 version.
xx1400002205
6
Continues on next pageApplication manual - PROFINET Controller/Device 793HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator Express
Action
Right-click on Phoenix Contact Software PROFINET and select Insert Device intoBus structure.
7
This node now represents the IRC5 controller master.
In the Bus Structure window, select Phoenix Contact Software PROFINET to bringup the Device Details window.
xx1600000030
8
These values does not have any effect on the IRC5 controller settings, but could befilled with data to reflect the settings of the IRC5 controller that is using this configur-ation.
Install the GSDML file for the ET200s Standard device by right-clicking in the DeviceCatalog window and select Import GSD file.
xx1600000031
9
In this example, install the GSDML-V2.2-Siemens-ET200S-20090309.xml file.This version of the PROFINET-IO Configurator Express support V2.2 syntax andearlier versions for the GSDML files.The installation of the GSDML file may take several minutes and the program mightappear to be unresponsive during that time.
Continues on next page80 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator ExpressContinued
Action
Make sure that the PROFINET node is selected in the Bus Structure window.10Add an ET200s ST (standard) head module by expanding the SIEMENS / I/O / ET 200Snode in the Device Catalog window.Right-click in the window and select Edit Catalog Representation. Move the OrderNumber item from Available to Used and click OK. The window will no be sorted withorder numbers as well.Select and right-click the node (for example IM151-3 PN ST V6.0 Rev.) and chooseInsert Device into Bus structure.In this example we use a version 6.0 module with order number 6ES7-151 3AA23-0AB0.
xx1600000032
Continues on next pageApplication manual - PROFINET Controller/Device 813HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator ExpressContinued
Action
Select the added node in the Bus Structure window.11In theDevice Detailswindow, set the device properties to reflect the device's propertieson the PROFINET network, see Configuring the PROFINET network settings onpage 36.In this example we set:
• DNS/PROFINET Device Name: unit1.cell2• IP Address: 192.168.5.65• Reduction ratio: 8 ms
xx1600000033
Note
The DNS/PROFINET Device Name is using a much longer string length and a syntaxthat is not allowed in the IRC5 controller for a device name. The DNS/PROFINETDevice Name is matched against the system parameter Name for a device definitionin the IRC5 controller. Therefore the DNS/PROFINET Device Name must be uniquefor the first 32 letters or up to the first "." (full stop character).In this example the device's name in the Robot controller will be "unit1", but on thePROFINET network it will be displayed with the name "unit1.cell2".
Select the node 0 @IM151-3 PN ST V6.0 in the Bus Structure window.12Now the Module Catalog window displays all possible modules to insert at Slot 1 forthis device. Add the power module. Sort this window as well based on order number.Add a power module with order number 6ES7 138-4CA01-0AA0 by selecting it anddrop it in the Bus Structure window on the text 0 @IM151-3 PN ST V6.0.
Note
It is very important for some devices that the firmware/hardware version on the deviceexactly matches the version used in the configuration (for example V 6.0).
Add the rest of the digital input and output modules by repeating the previous step.Select the node 1 PM-E DC24V. Sort the Module Catalog window on order number.Add a 2-bit DO module with order number 6ES7 132-4BB01-0AA0 by dragging anddropping it on the 1 PM-E DC24V node.
13
Continues on next page82 Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator ExpressContinued
Action
When all modules are added, right-click the node PROFINET in the Bus Structurewindow and select Parameterize to compile the configuration project and create theippnio.xml file.
xx1600000034
14
Download the ippnio.xml file to the HOME directory of the currently used RobotWaresystem using an FTP client.
15
Updating configuration file to support shared device functionalityThe following example is performed using PROFINET Configurator Express. Thisexample demonstrates how two IRC5 controllers are configured when sharing anI/O device, a MURR 5529 with 8 DI and 8 DO modules.
Action
Follow the procedure from steps 1-13 that is explained in section Using PROFINETConfigurator Express on page 79. Name the new project as "TestProject_IRC1". Thisconfiguration uses a MURR 55529 as shared device.
1
The configuration should have the following appearance:
xx1500001663
Continues on next pageApplication manual - PROFINET Controller/Device 833HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator ExpressContinued
Action
After the device has been configured, delete the modules that should be owned byanother controller.
• Right-click on the module > click Delete on the shortcut menu.The configuration should have the following appearance:
xx1500001664
2
Download the ippnio.xml file to the HOME directory of the currently used RobotWaresystem in the IRC5 controller using an FTP client.
3
Configure the second controller the same way as mentioned in the above steps 1-2,except that the other nodes should be deleted. That is, the modules owned by firstcontroller are deleted.
4
The second controller configuration should have the following appearance:
xx1500001665
Download the ippnio.xml file to the HOME directory of the currently used RobotWaresystem in the second IRC5 controller using an FTP client
5
Restart both IRC5 controllers.6
84 Application manual - PROFINET Controller/Device3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
C Using PROFINET Configurator ExpressContinued
Index8888-3, 7888-2, 7
Ccommunication profiles, 15compatibility, 16configuration file, 14Configuration File, 49, 53Connection, 37, 49, 52controller, 17
Ddevice, 14, 17
EEnergy Saving, 62
FFast Device Startup, 8, 44, 49–50, 57Fast Start Up, 14, 44FSU, 14, 44
Ggateway, 37, 73GSDML, 14GSDML file, 29, 31–32
Iindustrial Ethernet, 15Input Size, 8, 30, 51, 67
LLLDP, 9, 17, 70
Mmaster, 14
NNested Diagnosis, 8, 49, 55
network security, 13
OOutput Size, 8, 30, 51, 68
PPrioritized Startup, 14, 44private network, 22PROFINET
configuration tool, 14controller, 17device, 17internal device, 29standardization, 15
PROFINET versionsPROFIdrive, 15PROFIenergy, 15PROFINET-CBA, 15PROFINET-IO, 15–16PROFIsafe, 15
QQoS, 26Quality of Service, 26
Rreduction ratio, 14, 69
Ssafety, 12Shared Device, 46Station Name, 49, 54, 77system parameters, 49
Ttemplate I/O configuration file, 29topic I/O System
Device, 49Industrial Network, 49Internal Device, 50predefined internal device, 29predefined network, 29
Application manual - PROFINET Controller/Device 853HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
Index
ABB AB, RoboticsRobotics and MotionS-721 68 VÄSTERÅS, SwedenTelephone +46 (0) 21 344 400
ABB AS, RoboticsRobotics and MotionNordlysvegen 7, N-4340 BRYNE, NorwayBox 265, N-4349 BRYNE, NorwayTelephone: +47 22 87 2000
ABB Engineering (Shanghai) Ltd.Robotics and MotionNo. 4528 Kangxin HighwayPuDong DistrictSHANGHAI 201319, ChinaTelephone: +86 21 6105 6666
ABB Inc.Robotics and Motion1250 Brown RoadAuburn Hills, MI 48326USATelephone: +1 248 391 9000
abb.com/robotics
3HAC050969-001,Rev
G,en
© Copyright 2015-2018 ABB. All rights reserved.