RO LE so lech mbt 87

Embed Size (px)

Citation preview

  • 7/28/2019 RO LE so lech mbt 87

    1/4

    HCMC PC SPECIFICATION

    DIFFERENTIAL POWER TRANSFORMER RELAY (87)

    I. SCOPE :

    This specification should be applicable to differential relay intended forprotecting the power three coil transformer.

    II. STANDARD OF MANUFACTURE AND TEST :IEC 255 : Electric relays.

    III. DESCRIPTION :

    1. Construction :- The relay should operate on the basis of numeral measuring principle.- Display : LCD.- Terminals: Plug - in screw type.- The relay consists of a case used for flush mounting and should be

    supplied with all accessories for installation and operation.

    2. Technical data :- The protective function :

    + Biased different protection for three phase power three coilstransformer (one high voltage winding, two medium voltagewindings). The relay should have the individual contacts per phase.

    + Restricted earth fault protection.+ Over fluxing protection.+ Measurement of phase, differential and bias currents.+ Comprehensive self-checking and alarms.

    + Integral event recorder accessible from PC.+ Flexible operating logic options via software function links.+ Numerical display of setting values, measured values, recorded fault

    values, ...

    - DC supply : 90 240 Vdc.

    Tenderer may quote the relay with operating voltage of 110Vdc10%and the voltage divider to be able to supply the operating voltage of220Vdc to the relay.

    - Rated current (In) : 1A- Rated frequency : 50 Hz- Thermal withstand capability in current circuit :

    + Continuous : 04 x In+ for 3s : 10 x In+ for 1s :100 x In

    - Dynamic over load : 250 x In

    - Minimum operating time : 25 ms

    - Reset time : 30 ms

    - Accuracy :

    + 3% set current value.

    + 1% of the time value.

    -Environment :+ Ambient temperature : 0 to 55oC+ Humidity : 0 - 95%.

    /var/www/apps/conversion/tmp/scratch_5/137134858.doc 1/5

  • 7/28/2019 RO LE so lech mbt 87

    2/4

    HCMC PC SPECIFICATION

    DIFFERENTIAL POWER TRANSFORMER RELAY (87)

    3. Accessory :- 01 test block 14 circuits, 10A-240VDC

    + Test block offers facilities for monitoring and secondary injectiontesting and power system protection scheme when used with test

    plug.+ Test block can be fixed to relay without addition any equipment.

    - 01 test plug 14 circuits, 10A-240VDC- All other accessories for the installation and operation.

    IV/. TESTING REQUIREMENT :

    - The relay is subject to inspection during manufacturing. Routine andtype tests of each relay including operational test at minimum,accuracy tests will be performed according to IEC 255 standard.

    - In order to ensure the quality of supplied goods , in case of bid winning

    , the Tenderer shall supply routine test and copies of type test reportmet the following requirements:a. Routine test shall be performed for each equipment.b. Type test report shall meet the followings :

    - Testing sample : The same as the supplied item (manufacturer,original country, manufactures code as specified in tender document).

    - Testing items : Including testing items according to IEC 255.- Testing values shall be corresponding values as stated in Section III

    of this specification. If in section III, there are no corresponding values,testing values will be selected according to the standard specified insection II of this specification.

    V/. REQUIREMENT OF TECHNICAL TENDER DOCUMENT :- Technical description, data sheets, catalogues and other material

    submitted with the quotation must enable the buyer's engineers tothoroughly evaluate the proposals as to its compliance with the inquiryspecifications.

    - Minimum requirements :+ Detailed summary of deviations to inquiry specification.+ Completed inquiry data sheet expressed at clause VI.+ Brochures and catalogues containing outline dimensions, main

    electrical dataand installation details.

    + Certificate of quality management.- The proposal bidding has Type Test Report which meets the

    requirements as specified in item IV 2.b will be preferable.VI/. DATA SHEET :

    No DESCRIPTION REQUIREMENTS TENDERED

    1. Item No.2. Manufacturer3. Country4. Manufactures code

    5. Standards of factory andtest

    IEC 255

    6. Standards of quality

    /var/www/apps/conversion/tmp/scratch_5/137134858.doc 2/5

  • 7/28/2019 RO LE so lech mbt 87

    3/4

    HCMC PC SPECIFICATION

    DIFFERENTIAL POWER TRANSFORMER RELAY (87)

    management7. Member approve of

    certificate ofmanagement

    8. In case of bid winning ,the Tenderer shall supplyroutine test and copies oftype test report met therequirements of sectionIV .

    Yes

    9. Type microprocessor10. Display LCD11. Terminals Plug-in screw type12. Case flush mounting

    13. Function + Biased differentprotection for three phase

    power three coilstransformer (one high

    voltage winding and twomedium voltage

    windings). The relayshould have the individual

    contacts per phase.+ Restricted earth fault

    protection.+ Over fluxing protection.+ Measurement of phase,

    differential and biascurrents.

    + Comprehensive self-checking and alarms.

    + Integral event recorderaccessible from PC.

    + Flexible operating logicoptions via software

    function links.+ Numerical display ofsetting values, measured

    values, recorded faultvalues, ...

    14. Contacts Individual contacts perphase.

    15. DC supply 90 - 240 VDCNote :

    Tenderer may quote therelay with operating

    voltage of 110Vdc10%and the voltage dividerto be able to supply the

    /var/www/apps/conversion/tmp/scratch_5/137134858.doc 3/5

  • 7/28/2019 RO LE so lech mbt 87

    4/4

    HCMC PC SPECIFICATION

    DIFFERENTIAL POWER TRANSFORMER RELAY (87)

    operating voltage of220Vdc to the relay.

    16. Input circuit :+ Rated current+ Rated frequency

    1A50 Hz

    17. Thermal withstandability in current circuit :

    + Continuous 4 x In+ For 3s 10 x In+ For 1s 100 x In

    18. Dynamic currentwithstand

    250 x In

    19. Minimum operating time 25 ms

    20. Reset time 30 ms

    21. Accuracy of current value 3% of set current value22. Accuracy of time value 1% of set value

    23. Ambient temperature 0-55C

    24. Humidity 0-95%25. Accessories :

    - 01 test block 14circuits, 10A-240VDC

    - 01 test plug 14circuits, 10A-240VDC

    - All other accessoriesfor the installation andoperation.

    Yes

    + Test block offersfacilities for monitoringand secondary injectiontesting and power

    system protectionscheme when used withtest plug.+ Test block can befixed to relay withoutaddition any equipment.

    Yes

    Yes

    /var/www/apps/conversion/tmp/scratch_5/137134858.doc 4/5