LAKELAND ELECTRIC

MAINTENANCE AND

SERVICES ENGINEEERING

863.834.8868

REVISED 06/09/2016

-

RESIDENTIAL ELECTRIC SERVICE

QUICK REFERENCE GUIDE

Page 2: RESIDENTIAL ELECTRIC SERVICE - KUBRA

Table Of Contents

Overhead Temporary Service Pole ..................................................... Pg. 1

Underground Temporary Service Pole. .. .......... . .... .... . .... .. ... .. .. ..Pg. 2

Overhead Mobile Home Service Pole.... .... . ....... ...... .. . ... .. .. .. .. ....Pg. 3

Overhead Residential Service.. ..... ... ..... ...... .... .. ... .... . .. .. ..... ... ..Pg. 4

Underground Residential Service Applications... ... .......... ...... .. .. .Pg. 5

Underground Residential Single Family Home...........................Pg.6

Underground Mobile Home Service Pole... ... .. ....... . ... .... ... .. .......Pg. 7

Underground Secondary/Service Riser Pole.. .. .... .. .... ...... .. ... . .. ...Pg. 8-9

Overhead/Underground Single Phase,

Three-Wire Meter Connections .... ... .... ...... .... ... ....... ... ... .. ..... .Pg.10

LE Equipment/Driveway Clearance Requirements.....................Pg. 11

Approved Meter Can List.. .. ....... .. ...... . .... ... .... .. ..... .. ..... ... .....Pg.12

Contact List... ... .. .... ... ..... ... .. .... .. .. .. ..... .. .... .... ... .. ...... .. ... .. ..Pg.13

Page 3: RESIDENTIAL ELECTRIC SERVICE - KUBRA

Forward

It is Lakeland Electric's goal to provide our customers with the best quality

electrical service at the most efficient cost. In order to achieve this goal, the

Maintenance & Services Engineering group created this quick reference guide

to answer frequently asked questions concerning common residential temporary

and permanent service connections.

This brochure should be used as a reference only. It is the sole responsibility of

the person or party requesting service to apply for appropriate permits and

comply with all codes and regulations of all concerned agencies.

Lakeland Electric will energize the service when the following (but not limited too) requirements are met:

1) All easements requested by Lakeland Electric have been executed.

2) All invoices are paid in full.

3) An electric account has been set up for each individual service requested.

Blanket deposits do not satisfy this requirement. It is a requirement to

provide Lakeland Electric with the permit number when setting up the

electric account. Contact Lakeland Electric's customer service department

at 834-9535 for assistance to set up your account.

4) Lakeland Electric must receive a "Clearance" from the appropriate permitting agency.

5) House numbers are permanently attached to a residence.

6) All specifications of Lakeland Electric have been complied with.

7) An approved meter can has been installed, see page 12 for approved meter cans.

Contact Maintenance and Services Engineering prior to work commencing

to spot electric meter location.

Contact Maintenance and Services Engineering prior to any work

commencing at locations that may require any extensive line work such as

additional poles, primary lines, transformers or any other extenuating

circumstances that could delay or extend the time to receive service.

All comments and references are subject to change without notice. It is not

the intent of this brochure to address any costs or charges that may be

applied to the customer at time of publication or in the future.

Please call Maintenance and Services Engineering at 834-8868 if you have

any questions.

Page 4: RESIDENTIAL ELECTRIC SERVICE - KUBRA

OVERHEAD TEMPORARY SERVICE POLE

4 " x4 " x16 ' MIN PRESSURE TREATED POST

3 ' MIN LEAD NEUTRAL CLEARLY 6 "

WITH WHITE VINYL 1'· 0"

45' 45'

100' MAX ll ' MIN

16' MIN

2 " x4 " x14 ' BRACE

NOTE 5

5 ' - 6 " MAX 4 ' - 0 " MIN

SECURE GROUNDING

CONDUCTOR EVERY

LE POWER/ POLE

FINAL

4'·0 " MIN

NOTES: l 1. LOCATION OF POL E WIL L BE DESIGNATED BY LE. IF

REQUIRED, POLE HEIGHT MAY BE INCREASED FOR & "ACORN" CLAMP CLEARANCES OVER DRIVEWAYS, ETC.

RECOMMENDED

2. IF DISTANCE FROM POWER POLE TO TEMPORARY POLE EXCEEDS B' 100'; PLEASE CONT ACT L AKEL AND ELECTRIC FOR FURTHER INSTRUCTIONS.

3. TEMPORARY POLE SHALL BE A MINIMUM 4" x 4" x 16' PRESSURE TREATED POST. ALL 4" x 4" x 16' POL ES MUST BE BRACED REGARDLESS OF DISTANCE FROM

L.E. POINT OF DELIV ERY. TEMPORARY POLE SHALL BE SET AT A MINIMUM DEPTH OF 4-FEET BELOW GRADE.

4. AN OPTIONAL 16' x 6" DIAMETER PRESSURE TREATED ROUND POLE MAY BE USED IF

DESIRED. THIS P OL E DOES NOT REQUIRE BRACING.

5. POLE BRACES SHALL CONSIST OF TWO - 2 " x 4" x 14' LENGTHS OF LUMBER FIRMLY ATT ACHED TO A

2" x 4" x 4' S TAKE DRIVEN TO A DEPTH OF 3' INTO THE GROUND. PRESSURE - TREATED LUMBER IS OPTIONAL FOR BRACES.

6. . ALL TEMPORARY POLES SHALL DISPLAY A PERMANENT MARKING TAG WITH CONTRACTOR'S NAME,

ADDRESS, AND TELEPHONE NUMBER.

7. GROUNDING - ATTACH A •4 SOLID SOF T- DRAWN COPPER WIRE TO THE GROUND TERMINAL IN THE ME TER

CAN AND RUN TO A SINGLE ¾" 8' COPPER-CLAD GROUND ROD. AN ACORN- TYPE GROUND CL AMP IS RECOMMENDED FOR CONNECTION TO GROUND ROD. ABOVE 200 AMPS REFER TO NEC FOR WIRE SIZE.

8 . CONT ACT L AKELAND ELECTRIC AT (863) 834-8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 1

Page 5: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND TEMPORARY SERVICE POLE.

CUSTOMERS' PANEL - - - - 1

ELECTRICAL CONTRACTOR SHALL

PROVIDE BUSINESS NAME AND

PHONE NUMBER ON POLE,

PANEL OR METER HOUSING.

LE TRANSFORMER

OR PEDESTAL.

FRONT

6' MAX

48" MIN

8 ' MIN

ACORN

TYPE

CLAMP

FINAL

GRADE

NOTES:

SEE NOTE 8

24" MIN

GROUND ROD <SEE NOTE

1. TEMPORARY POLE SHALL BE A MINIMUM 4 " X 4 " X 8 ' LENGTH OF PRESSURE TREA TED

LUMBER INSTAL LED AT A MINIMUM DEPTH OF 24" BELOW FINAL GRADE.

2. CONTRACTOR WILL MAINTAIN A MINIMUM OF 12" AND A MAXIMUM OF 24" OF SEPARATION

BETWEEN EDGE OF TEMPORARY POLE AND THE NE AREST EDGE OF TRANSFORMER OR

PEDESTAL.

3. METER CAN SHALL BE MOUNTED ON THE TEMPORARY POLE AT A MINIMUM HEIGHT OF

48" ABOVE FINAL GRADE MEASURED TO THE CENTERLINE OF THE ME TER.

4. THE RISER CONDUIT FROM THE BASE OF THE METER CAN TO SUB- GRADE SHALL BE

ALUMINUM, RIGID STEEL OR SCHEDULE 80 P VC.

5. GROUNDING - ATTACH A •4 SOLID SOFT-DRAWN COPPER WIRE TO THE GROUND TERMINAL IN THE METER

CAN AND RUN TO A SINGLE ¾" 8' COPP ER- CL AD GROUND ROD. AN ACORN-TYPE GROUND CLAMP IS

RECOMMENDED FOR CONNECTION TO GROUND ROD. ABOVE 200 AMPS REFER TO NEC FOR WIRE SIZE.

6. MINIMUM CONDUCTOR SIZE SHALL BE •2 STRANDED ALUMINUM OR 0 4 STRANDED COPPER WIRE.

7. MARK THE NEUTRAL WITH WHITE VINYL TAPE INSIDE THE METER CAN AND AT THE EXPOSED END OF THE

CONDUCTOR.

8. A MINIMUM OF 48" OF CONDUCTOR SHALL BE LEFT COILED ABOVE GRADE TO COMPLETE THE CONNECTIONS

INTO THE TRANSFORMER OR PEDESTAL.

9. CONT ACT LAKELAND ELECTRIC AT (863) 834-8868 FOR FURTH ER INFORMATION..

LAKELAND ELECTRIC PAGE 2

Page 6: RESIDENTIAL ELECTRIC SERVICE - KUBRA

OVERHEAD MOBILE HOME SERVICE POLE

NOTES 7, 8

t 6" MIN

10" MAX

%" HOLE

3/4" HOLE

NOTES 4, 5

DETAIL A

, • ""'-NOTE 9

5'-6"

"ACORN"

l

TYPE 8'

CLAMP

NOTES: "'--NOTE 6

- - - 6'MIN ------------------ --.I

1. CALL MAINTENANCE ANO SERVICES ENGINEERING TO SPOT MOBILE HOME POLE.

2. INSTALL ONLY LAKELAND ELECTRIC APPROVED METER CAN (PAGE 12) AT 5'6 " FROM CENTERLINE OF METER

TO FINAL GRADE. USE OF LAKELAND ELECTRIC NON-APPROVED METER SOCKETS IS PROHIBITED.

IF SERVICE IS GREATER THAN 225 AMPS LAKELAND ELECTRIC WILL PROVIDE METER CAN.

3. THE MINIMUM MOBILE HOME SERVICE POLE SHALL BE 20 ' X 6" X 6" PRESSURE TREATED LUMBER. THE POLE

SHALL BE BURIED AT A MINIMUM DEPTH OF 5 '. OPTIONAL 20' X 8" DIA. ROUND POLE MAY BE USED.

4. IF THE SERVICE POLE IS LOCATED ON THE SAME SIDE OF THE STREET AS POWER POLE ANO WITH IN 75 ' OF THE

POWER POLE, GUYING OF THE SERVICE POLE IS NOT REQUIRED.

5. THE POINT OF ATTACHMENT FOR OVERHEAD SERVICE CABLE SHALL BE INSTALL ED TO PROVIDE A MINIMUM VERTICAL

CLEARANCE OF 14'-6" ABOVE FINAL GRADE. IF NECESSARY, LAKELAND ELECTRIC MAY REQUIRE THE POLE HEIGHT TO BE INCREASED FOR CLEARANCE ISSUES.

6. ATTACH •4 SOLID SOFT -DRAWN COPPER WIRE TO GROUNDING TERMINAL IN METER CAN. SECURE GROUND WIRE TO POLE

USING "J" TYPE WIRE CLAMPS EVERY 24". ABOVE 200 AMPS REFER TO NEC FOR WIRE SIZE.

7. INSTALL TWO %" X 8' COPPER-CLAD GROUND ROOS WITH MINIMUM 6' SEPARATION BETWEEN EACH ROD ANO ATTACH

GROUND WIRE WITH BRASS "ACORN" TYPE GROUND CLAMP ONLY. ADDITIONAL GROUNDING MAY BE REQUIRED BY LOCAL REGULATION.

8. SIZE NEUTRAL PER N.E.C. CODE. THE NEUTRAL CONDUCTORS INSIDE THE METER CAN ANO AT THE WEATHER HEAD

SHALL BE MARKED WITH WHITE VINYL TAPE.

9 . CUSTOMER SHALL PROVIDE A MINIMUM OF 36" EXCESS CONDUCTOR PROJECTING FROM WEATHERHEAD.

10.CONTACT LAKELAND ELECTRIC AT (863) 834-8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 3

Page 7: RESIDENTIAL ELECTRIC SERVICE - KUBRA

OVERHEAD RESIDENTIAL SERVICE

12' MIN

NOTE 6

llllDII UICIIIC NOTE 2 Q)l-$1.

-.s.'111l•4MI

5' -6 "

NOTE 3

NOTE 1

FINAL

GRADE

i+------6'MIN ------ 4

8'

NOTES:

1. METER HOUSING AND LOCATION MUST BE APPROVED BY LAKELAND ELECTRIC. ELECTRICAL

CONTRACTOR SHALL PROVIDE BUSINESS NAME, ADDRESS ANO PHONE NUMBER

INSIDE PANEL OR METER HOUSING.

2. INSTALL ONLY L AKELAND ELECTRIC APPROVED METER CAN (PAGE 12) AT 5'6" FROM CENTERLINE OF

METER TO FINAL GRADE. USE OF LAKELAND ELECTRIC NON-APPROVED METER SOCKETS IS PROHIBITED.

IF SERVICE IS GREATER THAN 225 AMPS LAKELAND ELECTRIC WILL PROVIDE METER CAN.

3. ATTACH •4 SOLID, SOFT-DRAWN COPPER WIRE TO GROUNDING TERMINAL IN METER CAN. SECURE

GROUND WIRE TO WALL/POLE USING "J" TYPE WIRE CLAMPS EVERY 24". ABOVE 200 AMPS REFER

TO NEC FOR WIRE SIZE.

4. INSTALL TWO o/a" X 8' COPPER-CLAD GROUND ROOS WITH MINIMUM 6' SEPARATION BETWEEN EACH ROD

AND ATTACH GROUND WIRE USING BRASS "ACORN" TYPE GROUND CLAMP ONLY. ADDITIONAL GROUNDING

ATTACHMENT POINTS MAY BE REQUIRED BY LOCAL REGULATION.

5. SERVICE RISER PIPE SHALL EXTEND A MINIMUM OF 36" ABOVE ROOF ELEVATION. ALL OVERHEAD SERVICE RISER PIPES

SHALL MEET A MINIMUM OVERALL HEIGHT OF 12' ABOVE FINAL GRADE.

6. NEUTRAL OF CUSTOMER INST ALLED CONDUCTOR SHALL BE MARKED WITH WHITE VINYL TAPE INSIDE METER CAN AND

OPPOSITE END AT WEATH ERHEAD.

7. CUSTOMER SHALL PROVIDE A MINIMUM OF 36" OF EXCESS CONDUCTOR PROJECTING FROM WEATHERHEAD.

8. CONT ACT LAKELAND ELECTRIC AT (863) 834-8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 4

Page 8: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND RESIDENTIAL SERVICE APPLICATIONS

LE UTILITY POLE <POINT OF OELIVERY>

SERVICE LOCATION

(POINT OF ATTACHMENT>

LAKELANO ELECTRIC APPROVEO METER CAN. 21/," ALUM RISER

2½" ALUM RISER

PROF ILE VIEW

0 SERVICE LOCATION

LE UTILITY POLE, PEDESTAL, OR TRANSFORMER !.,. ...... ..-LOT L I Nt

<POINT OF OELIVERY> 1

/ 2 ,, I

- - - - - - - - = •5 _PVC CONOU1 T= = = = = = = = = =:: - -• "'

LOT LINt c:t:::i:I::, I

PLAN V I E W

1) REFER TO PAGES 6 THROUGH 10 FOR SPECIFIC INFORMATION ABOUT APPLICABLE

UNDERGROUND SPECIFICATIONS.

2) CUSTOMER SHALL PROVIDE AND GRANT UTILITY EASEMENTS REQUESTED BY

LAKELAND ELECTRIC.

3l CUSTOMER IS RESPONSIBLE TO PROVIDE AND INSTALL CONDUIT SYSTEM.

CONDUIT INSTALLED ON PRIVATE PROPERTY SHALL BE INSTALLED AT A MIN.

DEPTH OF 24 " FROM TOP OF CONDUIT TO FINAL GRADE. CONDUIT INST ALLED WITHIN

CITY, COUNTY, OR STATE RIGHTS OF WAY SHALL BE INSTALLED AT A MIN. OF 36" FROM

TOP OF CONDUIT TO FINAL GRADE. CONDUIT SHALL NOT BE INSTALLED UNDER

ANY PERMANENT STRUCTURE EXCEPT FOR DRIVEWAYS.

4) MATERIALS FOR A TYPICAL 200 AMP SERVICE ARE 21/z" SCH.40 GRAY PVC BELOW GRADE,

21/ 2" ALUM. CONDUIT AT THE METER CAN & POLE, 21/2" SCH.40 GRAY PVC ELBO WS (MAX 2 ELBOWS)

WITH A 24" RADIUS & 2'-11" RISER HEIGHT. GALVANIZED ELBOWS WILL BE REQUIRED AND PULL STRING

INST ALLED WHEN TOTAL DISTANCE EXCEEDS 175' AND LAKELAND ELECTRIC IS PULLING CONDUCTOR.

MAXIMUM LENGTH OF CONDUIT RUN SHALL BE 200'.

5) CUSTOMER SHALL PROVIDE 20' OF ALUMINUM CONDUIT' AT THE POLE, WITH THE FIRST 10'

STICK ATTACHED TO THE ELBOW. IF THE POLE IS NOT ACCESSIBLE BY A BUCKET TRUCK,

THE ALUM. CONDUIT MUST BE INSTALLED 6" OFF THE POLE. IF THERE IS AN EXISTING

RISER ON THE POLE, INST ALL THE NEW ALUM CONDUIT ADJACENT TO THE E XISTI NG RISER.

6) FOR SERVICES ABOVE 200 AMPS INCLUDING SUBPANELS, THE CUSTOMER IS RESPONSIBL E

TO PROVIDE CONDUIT AND SERVICE CONDUCTOR PER NEC, LOCAL INSPEC TION AGENC Y AND

LAKELAND ELECTRIC'S SPECIFICATIONS. CUSTOMER/ BUILDER SHALL CONTACT LAKELAND ELECTRIC

PRIOR TO ST ART OF CONSTRUCTION.

7) ELECTRICIAN SHALL PROVIDE LOAD CALCULATIONS ON ANY RESIDENCE WHEN REQUESTED

BY LAKELAND ELECTRIC.

8) CONTACT LAKELAND ELECTRIC AT C863) 834-8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 5

Page 9: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND RESIDENTIAL SINGLE FAMILY HOME

iltaUII.X.I-IC-H,C,T.IIIC

t-ct-..'t "''° •Vq),t,tt

5 ' -6"

FINAL GRADE

RADIUS ELBOW

i.- - - - - - 6 ' MIN- - - - - - -

8 '

"ACORN" TYPE NOTE 5 CLAMP

NOTES:

1. SEE PAGE 5 (UNDERGROUND RESIDENTIAL SERVICE APPLICATIONS>.

2. METER HOUSING AND LOCAT ION MUST BE APPROVED BY LAKELAND ELECTRIC. ELECTRICAL CONTRACTOR SHALL

PROVIDE BUSINESS NAME, ADDRESS AND PHONE NUMBER INSIDE PANEL OR METER HOUSING.

3. . INSTALL ONLY LAKELAND ELECTRIC APPROVED METER CAN <PAGE 12> AT 5'6" FROM CENTERLINE OF

METER TO FINAL GRADE. USE OF LAKELAND ELECTRIC NON- APPROVED METER SOCKETS IS PROHIBITED. IF

SERVICE IS GREATER THAN 225 AMPS LAKELAND ELECTRIC WILL PROVIDE METER CAN.

4. ATT ACH •4 SOLID, SOFT-DRAWN COPPER WIRE TO THE GROUNDING TERMINAL IN METER CAN. RUN THE

GROUND WIRE THROUGH THE RISER GROUNDING BUSHING AND THE BASE OF THE METER C AN. SECURE

GROUND WIRE TO WALL/POLE USING " J " TYPE WIRE CLAMPS EVERY 2 4" . ABOVE 200 AMPS REFER

TO NEC FOR WIRE SIZE .

5. INSTALL TWO ¾" X 8' COPPER-CLAD GROUND RODS WITH MINIMUM 6' SEPARATION BETWEEN EACH ROD

AND ATTACH GROUND WIRE USING BRASS " ACORN" TYPE GROUND CLAMP ONLY. ADDITIONAL GROUNDING

ATTACHMENT POINTS MAY BE REQUIRED BY LOCAL REGULATION.

6. ALL CONDUIT INSTALLED ABOVE GRADE SHALL BE ALUMINUM. NO PVC CONDUIT SHALL BE VISIBLE ABOVE GRADE WHEN

LAKELAND ELECTRIC PULLS IN THE SERVICE. IF CUSTOMER PULLS IN THE SERVICE, PVC RISER CAN BE INSTALLED PER

NEC AND LOCAL REGULATION

7. SERVICE CONDUIT SHALL NOT BE INST ALLED UNDER ANY PERMANENT

STRUCTURE EXCEPT FOR DRIVEWAYS.

8. CONT ACT LAKELAND ELECTRIC AT (863> 834-8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 6

Page 10: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND MOBILE HOME SERVICE POLE

CUSTOMER'S 2.5" ALUMINUM SERVICE PANEL

CONDU

6IT

; 5·

NOTE

0::: 2. 5 " ALUMINUM 4' MIN 0

w CONDUIT 5 ' - 6" MAX LL Vl Vl

NO TE 6 :::>

0::: 0

I I-

ACORN X 0

0 0

TYPE f!;I I- I-

•4 COPPER WIRE I-

CLAMP

I NOTE 5

24"" MIN

3•

, _ _ _ _ _ _ 6"M I N- - - - - - - 24" RADIUS /

PVC ELBOW

SIDE NOTE 5 FRONT VIEW VIEW

NOTES:

1. SEE PAGE 5 (UNDERGROUND RESIDENTI AL SERVICE APPLICATIONS).

2. SERVICE POLE SHALL BE A 6" X 6" X 8' STEEL REINFORCED CONCRETE POST BURIED 3' BEL OW FINAL GRADE.

3. MOUNT A LAKELAND ELECTRIC APPROVED METER CAN (PAGE 12) ON POST SO THAT TOP EDGE IS F LUSH WIT H

THE TOP OF THE POST . NO UNITARY METER CANS WILL BE ACCEP TED.

4. MOUNT LIGHTING MAIN DISCONNECT OR PANEL ON THE OPPOSITE SIDE OF POST FRO_M THE METER CAN. NIPPLE

OUT THE BACK OF THE METER CAN INTO THE P ANEL. CUSTOMER P ANEL DOES NOT HAVE TO BE FLUSH WITH

TOP OF POST.

5 . GROUNDING - ATTACH A •4 SOLID SOF T -DRAWN C OPPER WIRE TO THE GROUND TERMINAL IN THE METER CAN.

RUN THE GROUND WIRE THROUGH THE RISER GROUNDING BUSHING AND THE BASE OF THE METER CAN

AND SECURE IT TO THE POST WITH WIRE J-CLIPS OR TO THE RISER CONDUIT WITH ZIP TIES. TERMINATE

THE GROUND WIRE TO TWO ¾" X 8 ' COPPER CLAD GROUND RODS USING "ACORN" TYPE CLAMP ONLY .

GROUND RODS MUST BE SPACED A MINIMUM OF 6 ' APAR T. ABOVE 200 AMPS REFER TO NEC FOR WIRE SIZ E.

6. ALL CONDUIT INSTALLED ABOVE GRADE SHALL BE ALUMINUM. NO PVC CONDUIT SHALL BE VISIBLE ABOVE GRADE WHEN

LAKELAND ELECTRIC PULLS IN THE SERVICE . IF CUSTOMER PULL S IN THE SERVICE, PVC RISER CAN BE INST

ALLED PER NEC AND LOCAL REGULATION.

7. ELECTRICAL CONTRACTOR SHALL PROVIDE NAME, ADDRESS AND PHONE NUMBER INSIDE P ANEL OR ON POST.

8. CONTACT LAKELAND ELECTRIC AT (863) 834-8868 FOR FUR THER INFORMATION.

LAKELAND ELECTRIC PAGE 7

Page 11: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND SECONDARY /SERVICE RISER POLE <FOR ALL COMMERCIAL, AND RESIDENTIAL SERVICES REQUIRING CUSTOMER INSTALLING SERVICE CONDUCTOR>

POINT OF DELIVERY ---

POINT OF ATTACHMENT

- - - - - - 6' MIN ------------------------------------------ t

NOTE 5

NOTES 11, 12

FINAL

GRADE

24"

NOTE 36"

2. 5" PVC SERVICE

\ 2 4 " RADIUS_/ PVCELBOW 2.5" PVC SECONDARY

\_ SECONDARY CONDUIT

NOTES 7, 8, 9

LAK ELAND ELECTRIC PAGE 8

Page 12: RESIDENTIAL ELECTRIC SERVICE - KUBRA

UNDERGROUND SECONDARY /SERVICE RISER POLE <FOR ALL COMMERCIAL, AND RESIDENTIAL SERVICES REQUIRING CUSTOMER INSTALLING SERVICE CONDUCTOR>

NOTES=

1. THE CUSTOMER SHALL BE CHARGED A FEE FOR SINGLE ANO THREE PHASE SERVICES

<THREE PHASE SERVICE IS NOT AVAILABLE FOR RESIDENTIAL SERVICE) WHEN A POINT OF

ATTACHMENT IS REQUIRED FOR AN UNDERGROUND SERVICE FROM AN OVERHEAD UTILITY POLE.

CONTACT 863-834·8868 FOR CURRENT FEES.

2. CUSTOMER SHALL BE CHARGED FOR ANY PERMITING FEES ASSOCIATED WITH

OBTAINING PERMITS WITHIN ANY RIGHTS OF WAY.

3. CUSTOMER SHALL PROVIDE AND GRANT UITILI TY EASEMENTS REQUESTED BY

LAKELAND ELECTRIC.

4. PRIOR TO ANY WORK COMMENCING THE CUSTOMER SHALL CONT ACT LAKELAND ELECTRIC

TO OBTAIN INFORMATION ABOUT METERING AND CONDUIT LAYOUT.

5. CUSTOMER SHALL PROVIDE ANO INST ALL CONDUIT AND CONDUCTOR FROM POINT OF

ATTACHMENT BACK TO METER CAN OR SERVICE PANEL IN ACCORDANCE WITH

LAKELAND ELEC TRIC' S, NEC'S AND LOCAL AGENCY SPECIFICATIONS.

6. ALL SERVICE CONDUIT INSTALLED ON PRIVATE PROPERTY SHALL BE INSTALLED AT A MINIMUM DEPTH

OF 24" FROM TOP OF CONDUIT TO FINAL GRADE. ALL CONDUIT LOCATED WITHIN CIT Y, COUNTY OR

STATE RIGHT-OF-WAY SHALL BE INSTALLEDAT 36" MINIMUM DEPTH FROM TOP OF CONDUIT TO

FINAL GRADE.

7. SIZE OF SECONDARY CONDUIT TO BE DETERMINED BY LAKELAND ELECTRIC. SECONDARY CONDUIT

SHALL BE PROVIDED AND INST ALLED BY CUSTOMER AS SPECIFIED IN LAKELAND ELECTRIC 'S "STANDARD

ELECTRICAL SERVICE REQUIREMENTS" AND "SPECIFICATIONS FOR SUBDIVISIONS ANO COMMERCIAL

DEVELOPMENTS" POLICIES.

8. ALL SECONDARY CONDUIT SHALL BE INSTALLED AT A MINIMUM DEPTH OF 36" FROM TOP

OF CONDUIT TO FINAL GRADE.

9. ELBOWS FOR SECONDARY CONDUIT SHALL HAVE A MINUMUM RADIUS OF 24"

10. DIRT BACKFI LL MUST BE CLEAN AND ROCK-FREE.

11. CUSTOMER SHALL PROVIDE 20' OF ALUMINUM CONDUIT PER RUN AT POLE

WITH FIRST 10' STICK ATTACHED TO ELBOW OF EACH RUN.

12. IF UTILITY POLE IS NOT ACCESSIBLE BY A BUCKET TRUCK THE CONDUIT AT POLE MUST

BE 6" OFF POLE. IF THERE IS EXISTING CONDUIT ON POLE, NEW CONDUIT

SHAL L BE INSTALL ED ADJACENT TO EXISTING CONDUIT.

13. CONTACT LAKELAND ELECTRIC AT (863) 834-8868 FOR FURTHER INF ORMATION.

LAKELAND ELECTRIC PAGE 9

Page 13: RESIDENTIAL ELECTRIC SERVICE - KUBRA

OVERHEAD/UNDERGROUND SINGLE-PHASE, THREE-WIRE METER CONNECTIONS

SIDE SIDE

--....._ NOTE 5 NOTE 5

UV/jllt-t---1- NOTE 2 11J; I+--+ NOTE 2

NOTE 5 NOTE 5

LOAD SIDE

xxxxxx ELCCTlbC XXXXXX (L(CTRIC

t2J" WAIN ST. GROUNDING 12 MAIN ST. LN<ELMO, fl JJ801 LAKELN«>, rL JJeOI

863112J-,!,67 BUSHING 815J/12J•4 7

NOTE 7 NOTE 4 NOTE 7

OVERHEAD INST ALL ATION UNDERGROUND INSTALLATION

NOTES:

U INSTALL ONLY LAKELAND ELECTRIC APPROVED METER CAN AT 5'6" FROM CENTERLINE OF METER TO FINAL GRADE.

THE USE OF NON-APPROVED METER SOCKETS IS PROHIBITED.

IF SERVICE IS GREATER THAN 225 AMPS LAKELAND ELECTRIC WILL PROVIDE METER CAN.

2.) ATTACH A •4 SOLID SOFT-DRAWN COPPER WIRE TO THE GROUND TERMINAL IN THE METER CAN. RUN THE GROUND

WIRE THROUGH THE RISER GROUNDING BUSHING ANO THE BASE OF THE METER CAN. SECURE THE GROUND WIRE

TO THE WALL/POLE USING "J" TYPE WIRE CLAMPS EVERY 24". ABOVE 200 AMPS REFER TO NEC FOR WIRE SIZ.E

DO NOT LOOP THE GROUND WIRE UP INTO THE LINE SIDE OF THE METER CAN.

3.) INSTALL TWO %" X 8' COPPER-CLAD GROUND RODS WITH MINIMUM 6' SEPARATION BETWEEN EACH ROD AND ATTACH

GROUND WIRE USING BRASS "ACORN" TYPE GROUND CLAMP ONLY. ADDITIONAL GROUNDING ATTACHMENT POINTS

MAY BE REQUIRED BY LOCAL REGULATION.

4.) FOR UNDERGROUND INS TALL ATION,S THE RISER CONDUI T MUST BE 2.5" ALUMINUM AND SHALL BE INSTALLED THROUGH

THE BOTTOM KNOCKOUT ON THE LEFT OR RIGHT SIDE OF THE METER CAN ONLY. DO NOT USE CENTER KNOCKOUT

ON BOTTOM OF METER CAN.

5.) CUSTOMER SHALL MARK THE NEUTRAL CONDUCTORS INSIDE THE METER CAN WI TH WHITE VINYL T APE. FOR OVERHEAD

INSTALLATIONS, CUSTOMER SHALL ALSO MARK THE NEUTRAL CONDUCTOR AT WEATHERHEAD WITH WHITE VINYL TAPE.

6.) FOR OVERHEAD INSTALLATIONS, CUSTOMER MUST PROVIDE A MINIMUM OF 36" OF EXCESS CONDUCTOR PROJECTING

FROM THE WEATHERHEAD.

7 . ) ELECTRIC CONTRACTOR SHALL PROVIDE THEIR BUSINESS NAME, ADDRESS AND PHONE NUMBER INSIDE THE

CUSTOMERS' MAIN PANEL OR IN THE METER C AN.

8.l CONTACT L AKELAND ELECTRIC AT (863) 834- 8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 10

Page 14: RESIDENTIAL ELECTRIC SERVICE - KUBRA

MINIMUM CLEARANCE REQUIREMENTS FOR DRIVEWAYS

PROPERTY LINE

..BACK - OF -EASEMENT

.. AC

.K-

.OF-EASEME

.N

.T

..

DRIVEWA ♦ ♦ DRIVEWA

PADMOUNT

.. .. SEE NOTE 1

.. .. ..

.. .. .. .. ..

.. .. UTILITY

:J .................... EASEMENT

.. ..MIN... ..L:MO.IN..' - - - - --- ----- --- -- -·- --·RIGHT- OF - WA Y - - - - - - --- --- --- -- - - -.R.IGHT - .OF.- WA Y.-.- - - - - - ◆ ♦

J- .. .. ...... .. .. .. .. .. .. ♦..

- =- - EDGE -O F - PAVE ME N T - - -=, ..:::::. EDGE-OF-PAVEMENT . ' ' . ' . .

. t:,. . . t:,. . t:,. . t:,. . t:,.

. . t:,. . t:,. .. t:,.

. .• t:,. .. t:,. . t:,. ................ t:,.

l> ·•

l> ·•

l> l> l> ·• l> l> ·• l> · • l> ·• l> · • l> • I>

l> · •

l> • I>

. .

l> ·•

. l> . l> l> l> . l> l> l> • I>

l> .. . l> . l> l> • I>

. l> · •

NOTES:

1. WHEN INSTALLING A DRIVEWAY, A MINIMUM OF FIVE (5) FEETOF CLEARANCE SHALL BE MAINTAINED

BETWEEN THE ABOVE GRADE FACILITIES AND THE OUSIDE EDGE OF THE DRIVEWAY NEAREST THE FACILITY

2. MAINTAIN A MINIMUM 1.0' VERTICAL CLEARANCE WHEN INS TALLING ELECTRIC CONDUIT PERPINDICULAR TO ANY

OTHER UNDERGROUND UTILITY.

3. ALL L AKE L AND ELECTRIC EQUIPMENT SHALL BE PLACED WITHIN THE DESCRIBED EASEMENT AREA.

4. IF COMPLI ANCE WITH ANY OF THESE CONDITIONS CANNOT BE ACHEIVED, LAKELAND ELECTRIC MUST BE

NOTIFIED IMMEDIATEL Y PRIOR TO THE INSTAL L ATION OF THE ELECTRICAL CONDUIT.

5.l CONT ACT LAKELAND ELECTRIC AT (863> 834 - 8868 FOR FURTHER INFORMATION.

LAKELAND ELECTRIC PAGE 11

Page 15: RESIDENTIAL ELECTRIC SERVICE - KUBRA

APPROVED 200 AMP SINGLE-PHASE ELECTRIC METER SOCKETS

The following list identifies the manufacturer and catalog number of the 200 amp-rated

single-phase, three-wire electric meter sockets approved for use within the service

territory of Lakeland Electric. This list applies only to 200 amp-rated single-phase

electric meter sockets intended for permanent service applications. Each of the meter

sockets shown are designed for dual-purpose applications and work equally well for

overhead and underground installations.

It is the customer' s responsibility to obtain the most recent version of this list, as

revisions may occur. Manufacturer and catalog numbers of meter sockets other than

those identified on this list are not approved. Installation of a non-approved meter

socket constitutes grounds for denial of electric service. Unitary electric panel/meter

socket type of equipment is not approved for use on Lakeland Electric's system. For

additional information, please call 863-834-8868.

Manufacturer Catalog Number

1. Milbank U7040-XL-TG-HSP

Hughes Electric Supply 419 N. Ingraham Ave, Lakeland 688-5511

CED Raybro Electric Supply 520 N. Ingraham Ave, Lakeland 688-7951

Home Depot (2 Lakeland Stores)

2. Durham UPT-RS212C Graybar Electric Supply 2100 Crystal Grove Dr., Lakeland 904-1200

3. Anchor URS1394HO-OS City Electric Supply 1131 E. Lime St., Lakeland 616-9302

4. Cutler Hammer UPTRS212-CCH City Electric Supply 1131 E. Lime St., Lakeland 616-9302

5. Square D

6. Talon Meter

UPTRS212-SQD

UAT317-DG

Page 12

Page 16: RESIDENTIAL ELECTRIC SERVICE - KUBRA

CONTACT LIST

CITY OF LAKELAND

Address: 228 S. Massachusetts Ave.

Lakeland , FL 33801

Phone: (863) 834-6000 Permit Office

Phone: (863) 834-6012

Inspection Requests (Electrical)

Phone: (863) 834-6250

Property Information Office

Phone: (863) 834-6084

LAKELAND ELECTRIC

Customer Service Office

Office: Main

Address: 501 East Lemon Street

Lakeland, FL 33801-5050

Phone: (863) 834-9535

Maintenance and Services Engineering

Address: 501 East Lemon Street

Lakeland, FL 33801-5050

Phone: (863) 834-8868

Fax: (863) 834-8475

Contracts and Rights-of-Way

Address: 501 East Lemon Street

Lakeland, FL 33801-5050

Phone: (863) 834-6536

Fax: (863) 834-6501

Consumer Service Programs -

Lighting and Surge Protection

Address: 501 East Lemon Street

Lakeland, FL 33801-5050

Phone: (863) 834-6789

Fax: (863) 834-8450

CITY OF POLK CITY

Address: 132 Commonwealth Ave., NW

Post Office Box 113 Polk City, FL 33868-0113

Permit-Building-Inspection Office

Phone: (863) 984-1375