39
Report on Spectral IP/Resistivity and Magnetic Surveys Tyko Property – 2011 Grid Manitouwadge Area, Ontario Tyko Resources Inc. Ref. 11-99 February, 2012

Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Report on

Spectral IP/Resistivity and Magnetic Surveys

Tyko Property – 2011 Grid

Manitouwadge Area, Ontario

Tyko Resources Inc.

Ref. 11-99 February, 2012

Page 2: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 2

Report on

Spectral IP/Resistivity and Magnetic Surveys

Tyko Property – 2011 Grid

Manitouwadge Area, Ontario

For : Tyko Resources Inc. 123 Robinson Drive Thunder Bay, ON, P7A 6G5

Tel : 807.767.1862 Contact :

Alan Aubut [email protected]

By : JVX Ltd. 60 West Wilmot Street, Unit 22 Richmond Hill, Ontario L4B 1M6

Tel: 905.731.0972 Fax: 905.731.9312 www.jvx.ca

Ref. 11-99

February, 2011

Summary

Spectral IP/resistivity and magnetic surveys were done on the Tyko property –

2011 grid 29 km southeast of Manitouwadge, Ontario. The field work was done from

November 22, 2011 to January 18, 2012. Total production was 29,775 m IP/resistivity

and 56,385 m magnetics. The results have been presented on 5 maps at 1:5,000 and

20 stacked pseudosections at 1:2,500. One of the maps shows IP anomaly centers

over the magnetics with drill holes.

The Tyko and RJ Ni-Cu-PGE occurrences are well marked by moderate to strong

IP anomalies that suggest the occurrences are depth limited. The Tyko occurrence has

no clear resistivity or magnetic expression. The larger RJ occurrence is associated with

a resistivity low and high magnetic relief. The 2D IP inversion results suggest the RJ

occurrence continues to the east-southeast at depth.

Cover page : total magnetic intensity

Page 3: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 3

Table of Contents

1. Presentation 2. Background 3. Survey Results – Overall Statistics 4. IP Anomalies 5. Compilation Map 6. Discussion 7. Conclusions Figures

Figure 1 : Regional location map

Figure 2 : Magnetics

Figure 3 : n=1 Mx chargeability

Figure 4 : Drill holes

Figure 5 : AeroTEM magnetics

Figure 6 : Distribution of n=1 apparent resistivities

Figure 7 : IP anomalies over magnetics – RJ occurrence

Figure 8 : 2D Mx chargeability inversions – lines 5300W to 4700W (top to bottom)

Attachments

Certificates of Qualifications

Appendix 1 : Production, GPS control points, Instrumentation and Data Processing

Appendix 2 : Weekly field production reports

Appendix 3 : IP anomalies

Instrument specification sheets

Maps

The results are presented in 5 maps at 1:5,000 and 20 stacked pseudosections at

1:2,500. The 5 maps are

total magnetic intensity

n=2 Mx chargeability

n=2 apparent resistivity

compilation (IP anomaly centers and drill holes over magnetics)

compilation (IP anomaly centers and drill holes over n=1 apparent resistivity)

The stacked pseudosections include 2D inversions of Mx chargeability and apparent

resistivity.

Paper copies of these 5 maps and the 20 stacked pseudosections are folded and bound

with this report.

Page 4: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 1

Spectral IP/Resistivity and Magnetic Surveys Tyko Property – 2011 Grid, Manitouwadge Area, Ontario

Tyko Resources Inc. Spectral IP/resistivity and magnetic surveys were done on the Tyko property – 2011 grid,

centered 29 km southeast of Manitouwadge or 63 km east northeast of Marathon, Ontario. The work was done for Tyko Resources Inc. by JVX Ltd. under JVX job number 11-99. The field work was done from November 22, 2011 to January 18, 2012. Total production was 29,775 m IP/resistivity and 56,385 m magnetics.

Figure 1. Regional location map

The grid covers all or parts of claims 3012936, 3012937, 3012938, 4203376, 4203377, 4203385 and 4203397 registered to Tyko Resources Inc. The grid is made up of 22 north northeast lines at 100 m spacing (3300W to 5400W) and one tie line at 10000N. The maximum station range is 9225N to 12000N. The grid is bounded by Pickle Lake on the northwest and Peanut Lake to the southeast. Tyko Lake is just south of the property. Magnetic readings were taken every 5 m. IP/resistivity surveys were done in time domain with a pole-dipole combination array. The moving current electrode was advanced in 25 m steps. In general, 8 receiver dipoles were set out at each current electrode position. The first 2 or 3 dipoles were 25 m long. The last 5 or 6 dipoles were 50 m long. The moving current electrode was always grid north of the potential electrodes.

The results are presented on maps at 1:5,000 and stacked pseudosections at 1:2,500. The maps include total magnetic intensity, n=1 Mx chargeability, n=1 apparent resistivity and 2 compilation maps - IP anomaly centers over magnetics and IP anomalies over n=1 resistivities. Compilation maps show 2006 and 2007 drill holes provided by Tyko Resources. The stacked pseudosections include 2D inversion results for Mx chargeability and apparent resistivity.

Production summaries, grid registration, instrumentation and data processing are described in appendix 1. Weekly field production reports are reproduced in appendix 2. IP anomaly listings are in appendix 3. Instrument specification sheets are attached. The results of the survey are discussed below. 1. Presentation The results of the surveys are presented in 5 maps at 1:5,000 and 20 stacked pseudosections at 1:2,500. All maps show land tenure from the MNDMF claimap3 website and drainage from NRCAN geogratis.ca. A UTM grid (NAD83, Z16N) and latitude / longitude co-ordinates have been added. The 1:5,000 map sheet area is 3.25 x 3.6 km (603660 to 606910 e, 5419840 to 5423445 n, NAD83, Z16N). Map types are

Page 5: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 2

- total magnetic intensity - n=1 Mx chargeability - n=1 apparent resistivity - compilation (IP anomalies and drill holes over magnetics) - compilation (IP anomalies and drill holes over n=1 apparent resistivity)

The total magnetic intensity map is shown in figure 2. The n=1 Mx chargeability map is shown in figure 3. Part of the compilation map with IP anomalies and drill holes over the magnetics is shown in figure 7. Paper copies of the 5 maps and 20 stacked pseudo sections are folded and bound with this report. Stacked pseudosections show colour contoured pseudosections of Mx chargeability, 2D inverted Mx chargeability, apparent resistivity, 2D inverted apparent resistivity, spectral chargeability amplitude (MIP) and spectral IP time constant (tau) plus the ground magnetic profile. There is one stacked pseudosection for each of the 20 lines surveyed with IP (3500W to 5400W). Digital results (this report, raw and processed ASCII data files, Geosoft database and map files) are archived on CD.

Figure 2. Magnetics

2. Background Alan Aubut’s 43-101 ICI report indicates that, prospecting resulted in the discovery of the Tyko

Cu-Ni-PGE showing in 1999. Freewest Resources optioned the property, flew an Aeroquest AeroTEM survey and did two sets of ground IP surveys. Prospecting resulted in the discovery of the nearby RJ Cu-Ni-PGE showing in 2005. IP surveys and diamond drilling (13 holes, total 2230 m) by North American Palladium of the Tyko and RJ occurrences followed. The best intersection was 1.2% Ni and 0.506% Cu over 2 m in hole TK06-004.

Page 6: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 3

The 2006 report from the North American Palladium states that:

“The Tyko property sits within an area that has seen very little government mapping or historic exploration. Regional-scale mapping indicated that the rocks in the area were predominantly granitic. Prospecting and mapping indicated that the granites contain numerous mafic to ultramafic xenoliths or fragments, some of which are mineralized.

Sulphide mineralization within these ultramafic fragments varies from fine-grained disseminated to coarse grained blebby. Macroscopically, the sulphides consist mostly of pyrrhotite and chalcopyrite with lesser pyrite. A second group of xenoliths are referred to simply as amphibolites. These rocks are usually barren except for minor amounts of pyrite. The mafic-ultramafic body intersected at the RJ showing is quite large and may be considered an intrusive body as opposed to a large “raft” in the granites.”

Figure 3. n=1 Mx chargeability

The 13 North American Palladium drill holes are listed in table 1 and plotted with the 2011 grid in figure 4. The Tyko occurrence is in the extreme south part of the grid and in the area of holes TK06-001 and TK06-002. The RJ occurrence is in the west central part of the grid and in the area of holes TK06-003 to TK06-005, TK07-001, TK07-002, TK07-003, TK07-005 and TK07-006. Some prominent sulphide intersections are listed in table 1. Drill log descriptions of the sulphides include disseminated, blebby, net-textured, stringer and semi-massive net-textured. The section of interest is named mineralized hornblendite. In the drill log, the northing for hole TK07-010 is listed as 5422155. From maps provided by Tyko Resources, this should be 5421155.

Page 7: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 4

Hole ID UTM e UTM n azimuth dip length mineralized intersections TK06-001 605366 5420361 135 -45 132.8 10-15% diss. sulphides, 17.4 – 20.8 m TK06-002 605446 5420429 135 -45 125 35% diss. sulphides over .25 m at 30.8 m TK06-003 604523 5421692 195 -45 200 5 to 50% sulphides, 56 to 73.7 m TK06-004 604499 5421608 17 -45 143 .5 to 10% sulphides, 24.3 to 92.0 m TK06-005 604466 5421616 15 -45 110 7 to 8 % sulphides, 18.4 to 44.1 m TK07-001 604321 5421688 12 -45 164 diss. sulphides, 39.4 to 47.3 m, 53.7 to 79.7 m TK07-002 604362 5421656 12 -45 170 up to 7% diss. Sulphides at 161 m TK07-003 604400 5421634 12 -45 179 4 to 5% sulphides, 94.3 to 97.4 m, 105.5 to 107 m TK07-005 604644 5421651 192 -45 194 - TK07-006 604457 5421576 12 -60 251 blebs sulphides 81.2 to 83.0 m TK07-008 604790 5421433 12 -45 155 - TK07-009 604942 5421661 192 -45 167 - TK07-010 604889 5421155 192 -55 239 -

Table 1. Drill holes – North American Palladium, 2006 and 2007

Figure 4. Drill holes

The 2011 grid is within an area flown for Tyko Resources in early 2011 with AeroTEM with 100 m lines at 350°. Total coverage was 751 km. The results were presented on maps of TMI, Zoff channel 0 at .0384 msec and Zoff offset profiles at 1:20,000. The magnetics map is shown in figure 5. All maps show EM anomaly centers. All EM anomaly centers represent surficial conductors - lake bottom sediments. No bedrock conductors were detected. This is consistent with results from earlier airborne surveys.

In order to better highlight any magnetic highs associated with the Tyko and RJ occurrences, Aeroquest was asked to remove the effects of the northeast trending mafic dikes from the TMI grid. The results were partially successful. Part of the problem in any 2D filtering of the airborne magnetics is the loss of resolution that comes with an average sensor terrain clearance more than 80 m. Short wavelength features seen in the ground survey become blurred at the higher terrain clearance.

Page 8: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 5

Figure 5. AeroTEM magnetics

References

Jason Rickard, 2006, Prospecting – geology – geophysics – drilling report, Tyko property, for North American Palladium Ltd.,

Paul Nielsen, 2007, Geology – geophysics – drilling report, Tyko property, for North American Palladium Ltd.

Alan Aubut – Sibley Basin Group, 2011, 43-101 Technical Report, Tyko Nickel-Copper Occurrence, White Lake area, Ontario, prepared for Tyko Resources Inc.

3. Survey Results – Overall Statistics The average of all 11,250 total magnetic intensity readings is 56,872 nT. Range is 56,580 to 58,113. The reference geomagnetic field for this place (48.94° north, 85.56° west, 368 m amsl) and time is given by amplitude 57,023 nT, inclination 74.5° and declination 7.3° west of north.

Overall statistics for all Mx chargeabilities, apparent resistivities and for those from the first dipole only are listed in table 2. Also shown are the percentages of chargeabilities in 4 ranges. Units are mV/V for chargeability and ohm.m for apparent resistivity. A total of 7,794 dipoles were read.

quantity # average median min max >5 5- 10 10 – 20 >20 Mx all 7755 4.2 4.2 -2.0 25.2 74.5% 24.3% 1% 0.2%

n=1 1043 4.0 4.1 -0.1 25.2 72.2% 26.1% 1.2% 0.5% rhoa all 7754 11812 11048 340 64244

n=1 1044 9524 8528 340 64244 Table 2. IP/resistivity statistics

Page 9: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 6

As with most surveys in this type of terrain, background levels for Mx are ≤ 5 mV/V. 24% of all Mx values are in the range of 5 to 10 mV/V, the conventional range for ‘weak’ IP anomalies. A moderate IP anomaly normally means peak Mx values of 10 to 20 mV/V and strong means peak Mx values more than 20 mV/V. Under these criteria, less than 2 % of all chargeabilities are moderately or strongly anomalous. In the absence of bedrock conductors, most crystalline rock has a resistivity of more than 50,000 ohm.m. Sea water has a resistivity of around 1 ohm.m. Overburden resistivities in the Canadian Shield are commonly in the range of 50 to 200 ohm.m. In the absence of bedrock conductors, most variations in apparent resistivity are due to variations in the conductivity and thickness of the overburden. Most soil and bedrock conductivities are determined by water content and ground water conductivity. The distribution of n=1 apparent resistivities is shown in figure 6.

Figure 6. Distribution of n=1 apparent resistivities

n=1 resistivities more than 10,000 ohm.m (45%) usually means some outcrop and a prospecting history. n=1 resistivities in the range of 2,000 to 10,000 ohm.m (29%) often means access to bedrock may be possible by back hoe stripping. In the absence of bedrock conductors, n=1 resistivities less than 1,000 ohm.m (16%) usually mean no outcrop, some thickness of overburden and some reduction in the amplitude of IP anomalies from any underlying chargeable bodies.

More than 96% of the measured IP decays are of sufficient amplitude and quality to generate spectral parameters with a fit value of less than 5%. 80% is considered a good performance number for most surveys. Anything more than 90% is excellent. 4. IP anomalies IP anomalies that are thought to represent a discrete body of chargeable material have been picked from the pseudosections. The location and extent of the anomaly centre-top, IP anomaly amplitude, dipole number of the centre-top, spectral IP features and the resistivity setting and expression are taken from the measured pseudosections. IP anomalies are classed as weak, moderate or strong. IP anomaly listings are in appendix 3.

A total of 17 IP anomalies have been picked. 7 are classed as weak. 5 are moderate and 5 are strong.

all IP anomalies have centre-tops in the first dipole. These are all shallow chargeable bodies with estimated depths to top less than 20 m. No IP anomalies are seen in the measured sections at depth.

only 2 IP anomalies have an associated resistivity high. 8 have an associated resistivity low. 7 have no clear resistivity expression.

050

100150200250300350400

< 500 500 -1000

1000 -2000

2000 -5000

5000 -10000

10000 -20000

> 20000

Page 10: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 7

In areas of little or no overburden, Mx chargeabilities are often in the range of 5 to 7 mV/V. These are considered background values and characteristic of bedrock with little or no sulphides. These areas are not identified as weak IP anomalies unless they appear in a confined IP anomaly form. 5. Compilation Map

The 1:5,000 compilation maps shows IP anomalies and the 13 North American Palladium drill holes. There are 2 compilation maps – one with IP anomalies over the magnetics and one with IP anomalies over the n=1 apparent resistivity. The IP anomalies are shown as coloured squares. They are red for strong, orange for moderate and yellow weak. The anomaly ID is shown on the left side of the coloured squares.

6. Discussion The Tyko and RJ occurrences are well marked by moderate to strong IP anomalies with centre-tops in the first dipole. Most of the IP anomalies are consistent with depth limited chargeable bodies with depth extents from 50 to 200 m. The relationship between the low resistivities over the RJ occurrence and the mineralization is unclear. The strongest / shallowest parts of the Tyko and RJ IP anomaly sets are well sampled by the North American Palladium drill holes. Two weak IP anomalies away from the Tyko and RJ occurrences have been picked. Both are poorly defined, shallow features of little geophysical interest. They may be no more than high background chargeabilities isolated by overburden variations.

The Tyko occurrence and its host has no clear magnetic expression. Magnetic relief over the RJ occurrence is often high but the relationship between the occurrence and the magnetics is not clear (figure 7). Dighem and AeroTEM surveys have not identified any bedrock conductors on the property.

Figure 7. IP anomalies over magnetics – RJ occurrence

Page 11: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 8

Figure 8. 2D Mx chargeability inversions – lines 5300W to 4700W (top to bottom).

Page 12: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

J V X

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 9

Stacked 2D Mx chargeability inversions for lines 5300W to 4700W in the area of the RJ occurrence (10000N to 15000N) are shown in figure 8. These affirm the strongest / shallowest IP anomaly is at 10200N to 10300N on line 5000W. There are 3 NAP drill holes in this line segment. They also confirm the depth limited nature of the IP zone.

New information from these sections is the implication that mineralization may be found at depths of 75 m under station 10175N on line 4700W. The inversion results suggest the RJ zone continues at depth east and south of its shallowest parts. More drilling into the inverted IP highs on lines 4800W and 4700W might be considered – with due regard for all of the uncertainties that accompany ‘inversion’.

NAP drilling focussed on the strongest IP anomalies and these are almost always the shallowest parts of the target. Inversion should correct the reduction in IP anomaly amplitude from targets at depth. Inverted IP highs at depth may or may not be real – they are best judged in parallel with the measured IP results.

7. Conclusions Spectral IP/resistivity and magnetic surveys were done on the Tyko property – 2011 grid,

Total production was 29,775 m IP/resistivity and 56,385 m magnetics. The results have been presented on 5 maps at 1:5,000 and 20 stacked pseudo sections at 1:2,500. Compilation maps show IP anomalies and drill holes over the magnetics and over n=1 apparent resistivity.

The Tyko and RJ occurrences are well marked by moderate to strong shallow IP anomalies of limited depth extent. Inversion suggests the RJ showing continues at depth east and south of its shallowest parts. Parts of these inverted IP highs are untested and may be drill targets. Allowance should be made for the possibility that some of these inverted IP highs are not real. Ian Johnson, Ph.D., P.Eng. Blaine Webster, B.Sc., P. Geo. February 24, 2012

Page 13: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 1

Certificate of Qualifications

Blaine Webster President - JVX Ltd.,

60 West Wilmot Street, Unit 22 Richmond Hill, Ontario L4B 1M6

Tel : (905) 731-0972 Email : [email protected]

I, Blaine Webster, B. Sc., P. Geo., do hereby certify that

1. I graduated with a Bachelor of Science degree in Geophysics from the University of British Columbia in 1970.

2. I am a member of the Association of Professional Geoscientists of

Ontario.

3. I have worked as a geophysicist for a total of 40 years since my graduation from university and have been involved in minerals exploration for base, precious and noble metals and uranium throughout much of the world.

4. I am partly responsible for the preparation of this report. Most of the

technical information in this report is derived from geophysical surveys conducted by JVX Ltd. for Tyko Resources Inc. and information provided by Tyko Resources Inc.

______________________ Blaine Webster, B. Sc., P. Geo.

Page 14: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 2

Certificate of Qualifications

Ian Johnson R R 2 Aylmer, Ontario N5H 2R2

Tel : (519) 773-2932 Email : [email protected]

I, Ian Johnson, Ph. D., P. Eng., do hereby certify that

1. I graduated with a Bachelor of Science degree in Geophysics from the University of Western Ontario in 1968 and a Doctorate degree in Geophysics from the University of British Columbia in 1972.

2. I am a member of the Association of Professional Engineers of Ontario.

3. I have worked as a geophysicist for a total of 35 years since my

graduation from university and have been involved in minerals exploration for base, precious and noble metals and uranium throughout much of the world.

4. I am partly responsible for the overall preparation of this report. Most of

the technical information in this report is derived from geophysical surveys conducted by JVX Ltd. for Tyko Resources Inc. and information provided by Tyko Resources Inc.

______________________ Ian Johnson, Ph.D., P.Eng.

Page 15: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 1

Appendix 1 Production, GPS control points, Instrumentation and Data Processing

Spectral IP/resistivity and magnetic surveys were done on the Tyko property – 2011 grid, centered 29 km southeast of Manitouwadge or 63 km east-northeast of Marathon, Ontario. White Lake is just south of the property. The work was done for Tyko Resources Inc. by JVX Ltd. under JVX job number 11-99. The field work was done from November 22, 2011 to January 18, 2012. Total production was 29,775 m IP/resistivity (table 1) and 56,385 m magnetics (table 2).

Line IP-From IP-To Separation Date 5400W 10025N 9525N 500 December 12, 2011 5300W 10775N 9475N 1300 December 12, 2011 5200W 10775N 9475N 1300 December 11, 2011 5100W 10825N 9475N 1350 December 10, 2011 5000W 10875N 9525N 1350 December 8, 2011 4900W 11025N 9475N 1550 December 7, 2011 4800W 10775N 9475N 1300 December 5/6, 2011 4700W 11125N 9500N 1625 December 3/4, 2011 4600W 11125N 9475N 1650 December 2/3, 2011 4500W 11125N 9500N 1625 December 1/2, 2011 4400W 11125N 9475N 1650 December 13/15, 2011 4300W 11125N 9525N 1600 December 15/16, 2011 4100W 11025N 9525N 1500 December 17, 2011 4200W 11025N 9475N 1550 December 18, 2011 4000W 11025N 9450N 1575 January 10/11, 2012 3900W 10925N 9450N 1475 January 11/12, 2012 3800W 10925N 9375N 1550 January 12/14, 2012 3700W 11025N 9325N 1700 January 15, 2012 3600W 11075N 9275N 1800 January 16/17, 2012 3500W 11125N 9300N 1825 January 18, 2012

Total 29,775 m Table 1. Production summary, IP/resistivity survey

Line Mag-From Mag-To Separation Date 3900W 12025N 9475N 2550 22-Nov-11 3800W 12000N 9425N 2575 22-Nov-11 3700W 12000N 9365N 2635 22-Nov-11 3600W 12000N 9325N 2675 22-Nov-11 4100W 12000N 9475N 2525 23-Nov-11 4000W 12000N 9475N 2525 23-Nov-11 3500W 12000N 9300N 2700 23-Nov-11 3400W 12025N 9300N 2725 23-Nov-11 4300W 12000N 9475N 2525 24-Nov-11 4200W 12000N 9500N 2500 24-Nov-11 3300W 11975N 9225N 2750 24-Nov-11 T10000 5400W 3300W 2100 24-Nov-11 4700W 12000N 9500N 2500 25-Nov-11 4600W 12000N 9500N 2500 25-Nov-11 4500W 12000N 9500N 2500 25-Nov-11 4400W 12000N 9500N 2500 25-Nov-11 5100W 12000N 9500N 2500 27-Nov-11 5000W 12000N 9500N 2500 27-Nov-11 4900W 12000N 9475N 2525 27-Nov-11 4800W 12000N 9475N 2525 27-Nov-11 5400W 10000N 9475N 525 28-Nov-11 5300W 12000N 9475N 2525 28-Nov-11 5200W 11975N 9475N 2500 28-Nov-11

Total: 56,385 m Table 2. Production summary, magnetic survey

Page 16: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

2

For the IP/resistivity survey, coverage is measured from the station of the first moving current electrode to the station of the last potential electrode (ideal grid). For the magnetic survey, coverage is measured from the first to last station (ideal grid). Magnetic readings were taken every 5 m. IP/resistivity surveys were done in time domain with a pole-dipole combination array with the first 2 or 3 dipoles 25 m long and the last 6 or 5 dipoles 50 m long. Psuedosection plot point depths are from 19 to 175 m. The moving current electrode was always grid north of the potential electrodes. Grid registration was through 99 GPS control points at an average station separation of 705 m.

Figure 1. Grid layout – line segments with IP/resistivity in black

Personnel The field work was done by JVX personnel Scott Mortson (party chief), senior geophysicist Dennis Palos and assistants Jeff Spiers, Jeff Boettcher, Yaroslav Kubacek, Michel Begin, Dan Kelly, Claude Robert and Brad Jackson. Data processing was handled by Hasnein Jeraj at the JVX office in Richmond Hill, Ontario. Grid The grid covers all or parts of claims 3012936, 3012937, 3012938, 4203376, 4203377, 4203385 and 4203397 registered to Tyko Resources Inc. The grid is made up of 22 north northwest lines at 100 m and one tie line at 10000N. The maximum station range is 9225N to 12000N. Grid registration is based on UTM coordinates collected with a hand held GPS receiver at 99 points at various locations on the grid, including line ends. The average separation between GPS control points is 705 m. The full set of GPS control points is listed in table 1. The grid is drawn by interpolation or extrapolation from these control points. The full grid is shown in grey in figure 1. Line segments with IP/resistivity are shown in black. Lake names in figure 1 are Pickle (northwest), Peanut (southeast) and Tyko (south).

Page 17: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

3

Line Station UTM e UTM n elevation 3300W 9225N 605487 5419951 339

10000N 605850 5420630 343 11500N 606569 5421931 410 11975N 606803 5422360 361

3400W 9300N 605421 5420049 337 10000N 605764 5420690 344 11500N 606507 5421973 400 12025N 606751 5422423 368

3500W 9300N 605346 5420122 346 10000N 605687 5420746 354 11500N 606416 5422023 400 12000N 606658 5422452 365

3600W 9325N 605264 5420186 340 10000N 605587 5420779 337 12000N 606543 5422512 358

3700W 9365N 605198 5420261 345 10000N 605499 5420831 351 11500N 606220 5422128 391 11900N 606410 5422469 377 12000N 606453 5422553 363

3800W 9425N 605137 5420377 10000N 605405 5420866 352 10875N 605831 5421627 358 11500N 606145 5422172 396 11600N 606184 5422244 385 11725N 606245 5422350 384 12000N 606293 5422495

3900W 9475N 605074 5420468 352 10000N 605318 5420924 357 10750N 605631 5421483 363 11500N 606036 5422232 427 11975N 606212 5422544 393 12125N 606277 5422666 380

4000W 9475N 604982 5420512 338 10000N 605230 5420965 359 10125N 605292 5421077 362 10375N 605411 5421295 371 11500N 605957 5422284 437 11900N 606152 5422600 384

4100W 9475N 604890 5420564 345 10000N 605148 5421001 360 11500N 605858 5422341 452 12000N 606078 5422745 396

4200W 9500N 604814 5420634 363 10000N 605060 5421067 371 10500N 605313 5421547 412 11500N 605787 5422361 408 12000N 606024 5422786 370

4300W 9475N 604720 5420639 352 10000N 604969 5421104 383 11000N 605451 5421958 398 11500N 605697 5422411 409 12000N 605918 5422847 383

4400W 9500N 604647 5420722 377 10000N 604894 5421150 393 11500N 605600 5422467 407 12000N 605851 5422902 390

4500W 9500N 604560 5420765 368 10000N 604795 5421208 386 12000N 605747 5422967 381

Page 18: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

4

Line Station UTM e UTM n elevation 4600W 9500N 604485 5420825 307

10000N 604710 5421236 361 11000N 605196 5422115 421 11500N 605431 5422564 382 12000N 605663 5422994 369

4700W 9500N 604376 5420875 336 10000N 604625 5421303 361 11000N 605121 5422215 413 11500N 605346 5422626 357 12000N 605582 5423053 347

4800W 9475N 604271 5420900 378 10000N 604543 5421346 388 11500N 605296 5422639 364 12000N 605538 5423066 349

4900W 9475N 604198 5420936 379 10000N 604456 5421385 390 11500N 605190 5422701 370 12000N 605426 5423136 353

5000W 9500N 604135 5420997 364 10000N 604365 5421435 389 11000N 604845 5422332 373 11500N 605070 5422759 356 12000N 605317 5423201 355

5100W 9500N 604038 5421057 379 10000N 604280 5421485 408 11000N 604771 5422364 368 11500N 605017 5422793 351 12000N 605248 5423240 372

5200W 9475N 603929 5421090 356 10000N 604193 5421534 383 11025N 604711 5422469 367 11975N 605163 5423311 364

5300W 9475N 603859 5421132 354 10000N 604111 5421586 354 11000N 604605 5422455 331 11500N 604841 5422899 352 12000N 605096 5423335 351

5400W 9475N 603774 5421177 353 10000N 604027 5421642 359 Table 1. GPS control points (NA83, Z16N)

Instrumentation Magnetometer

Gem Systems GSM-19, SN 6072060, 7052356 and 7082476

When set up for mobile readings, the GSM-19 magnetometer records line, station, total magnetic intensity and time. When operating as a base station, it records total magnetic intensity and time. Total magnetic intensity is measured to 0.01 nT. The base station was set to take a reading every 10 seconds. Specification sheets are attached. IP/resistivity

Scintrex IPR-12 time domain IP/resistivity receiver, SN 950248 GDD TXII – 1800W-2400V time domain transmitter, SN TX#258 Honda 3000 watt MG set. SN 1900-827-0000

For each potential electrode pair, the IPR12 measures the primary voltage (Vp) and the ratio of secondary to primary voltages (Vs/Vp) at 11 points on the IP decay (2 second current pulse). These 11 points are labeled M4 to M14. There is the option for an additional user defined slice (Mx). Units are

Page 19: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

5

millivolts for Vp and milliVolts/Volt for M4 to M14 and Mx. Settings are

Vp : 200 to 1600 msec M4 centered at 60 msec (50 to 70) M5 centered at 90 msec (70 to 110) M6 centered at 130 msec (110 to 150) M7 centered at 190 msec (150 to 230) M8 centered at 270 msec (230 to 310) M9 centered at 380 msec (310 to 450) M10 centered at 520 msec (450 to 590) M11 centered at 705 msec (590 to 820) M12 centered at 935 msec (820 to 1050) M13 centered at 1230 msec (1050 to 1410) M14 centered at 1590 msec (1410 to 1770) Mx centered at 870 msec (690 to 1050)

The apparent resistivity is calculated from Vp, the transmitted current and the appropriate geometric or K factors. M4 to M14 define the IP decay curve. The Mx slice is commonly presented in pseudosections and maps.

JVX has chosen the above settings for Mx in order to better reflect an IP measurement from the older Scintrex IPR11 time domain receiver. In IPR11 surveys from the 1980s, this chargeability window was most often plotted and experience gained is based in part on this measurement.

The IPR12 also calculates the theoretical decay that best fits the measured decay. The theoretical decay is based on the Cole-Cole impedance model applied in the 1970s. The fit is based on a set of theoretical master curves with restrictions that limit the value of the calculation. JVX uses a different method to calculate impedance parameters (see below).

The Instrumentation GDD Inc. GDD TXII 1800 time domain IP transmitter operates off 120V output from a 3000 watt motor generator. Output is current stabilized from 150 to 2400 volt taps. The maximum current is 10 amps. Current and circuit resistance are displayed in digital form.

Data Processing and Presentation Grid The grid is drawn by interpolation or extrapolation from a set of 99 GPS control points – 99 widely separated line/stations with UTM coordinates from a hand held GPS receiver.

Base Map Land tenure has been downloaded as *.shp files from the MNDMF claimap3 website. Lakes,

rivers and roads have been downloaded as 1:50,000 *.shp files from geogratis.ca (Earth Sciences Sector of Natural Resources Canada). There are minor differences in topographic elements from federal and provincial sources.

Magnetics At the end of every survey day, data from the mobile and base station magnetometers are dumped to a PC. Output from both magnetometers are text files labelled by date and the operator’s name or ‘base’. Data dumps from the mobile unit show line/station, total magnetic intensity (nT) and time (decimal hours). Data dumps for the base unit show time and total magnetic intensity. Subsequent processing steps normally are

1. Apply base station corrections to the mobile data. Corrected total magnetic intensity values are appended to the mobile files and renamed as *_corr files. Bad data or repeat values are removed.

2. Move the contents of the files containing the corrected total magnetic intensity into a Geosoft database (*.gob).

Colour + line contour maps of the corrected total magnetic intensity are generated from the database using Geosoft Montaj. Random gridding with a 7.5 m grid cell is used.

Page 20: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

6

In this job, the base station was not set up properly. The base station record could not be synchronized with the mobile records and could not be used for the diurnal correction. A low pass filter of the uncorrected total magnetic intensity grid was used as a substitute.

Because orientation is close to the survey grid, north/south magnetic features were poorly represented in the TMI grid. A further process of trend reinforcement was used to better show these features.

IP/Resistivity At the end of every survey day, the IP/resistivity data are dumped from the IPR12 to a PC.

Output is a text file with the date as the file name. Raw data from each survey line are collected in text files with the line number as the file name. The data are checked for quality and quantity. The data are archived for transfer to JVX Ltd. in Richmond Hill.

Office data processing is based largely on Geosoft Oasis Montaj v6.3 (www.geosoft.com). Impedance modeling is based on a suite of programs developed by JVX for the IPR11 and IPR12.

The collated text files for each survey line are taken into a Geosoft database. UTM coordinates for each line/station of the interpolated grid are added. The IP decays are analyzed for spectral content (see below) – the results are added back into the database.

The results are presented as plan maps of the n=1 Mx chargeability and n=1 apparent resistivity and stacked pseudosections. Stacked pseudosections show the Mx chargeability, 2D inverted Mx chargeability, apparent resistivity, 2D inverted resistivity, spectral IP time constant (tau) and spectral IP amplitude (MIP). All are prepared with Geosoft Oasis Montaj. Pseudosections assume an ideal survey line. Plan maps show the IP survey grid, station numbers, the colour grid and line contours. Random gridding with a 16 m grid cell is used.

Impedance Modelling The Cole-Cole impedance model was developed in the 1970s after it became clear that

chargeability is a complex property determined by amplitude (volume percent electronic conductors), grain size and grain size uniformity. In this model, the low frequency electrical impedance Z(ω) of rocks and soils is defined by 4 parameters. They are

r0 : DC resistivity in ohm.m m : true chargeability amplitude in V/V (also called MIP) τ : tau - time constant in seconds c : exponent

The form of the model is Z(ω) = r0 1 – m 1 - (1+(iωτ)c)-1 ohm.m where ω is the angular frequency (2πf).

The true chargeability (m or MIP) is a better measure of the volume percent electronic conductors - primarily pyrrhotite, pyrite and graphite. The time constant is a measure of the square of the average grain size. The exponent is a measure of the uniformity of the grain size. Common or possible ranges are 0 to 1 V/V (m), .01 to 100 seconds (tau) and .1 to .5 (c). In time domain IP surveys, impedance model parameters may be estimated using a best fit between theoretical and measured decays. The simplest approach is to use a set of master decay curves, pre-calculated for selected values of time constant and exponent. For a 2 second current pulse, the master curve set used here is for time constant values of .01, .03, .1, .3, 1, 3, 10, 30 and 100 seconds and exponent values of 0.1, 0.2, 0.3, 0.4 and 0.5. This gives a total of 45 master curves. All decays that give an RMS fit between measured and master decay of less than 5% are judged to be of sufficient quality to yield spectral IP parameters. Under ideal conditions, more than 90 % of the IP decays in any survey are of sufficient amplitude and quality to yield spectral parameters. 80 % is probably average for most surveys. The most common reason for the lack of spectral parameters is very low decay amplitudes – often seen in areas of thick and/or conductive overburden. Instrumentation and/or noise problems can occur over long sections of outcrop or at an abrupt boundary between outcrop and conductive ground.

Page 21: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 1: Production, GPS control points, Instrumentation and Data Processing

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99

7

Impedance Modelling The 2D IP/resistivity inversion results are from DCIP2D, a program library from the UBC Geophysical Inversion Facility for the forward modelling and inversion of DC resistivity and induced polarization data in 2 dimensions. The main steps in any inversion are

1. Model the area under the survey line into a mesh of rectangles. Mesh cells are usually a/2 m wide and a/4 m thick. There must be several cells of increasing size on all 3 sides outside the region where current has been injected.

2. Assign initial chargeability and resistivity values to each mesh cell. The default settings commonly are 0 and 10000 for all mesh cells (half space model).

3. Calculate what would be the measured chargeability and apparent resistivity from the model.

4. Compare the calculated and measured chargeability and apparent resistivity. Use these comparisons to make intelligent changes in the chargeability and resistivity of each mesh cell. Re-calculate what would be the measured chargeability and apparent resistivity from the revised model. Repeat this forward – compare – model change cycle until there is a reasonable fit between the calculated and measured chargeability and apparent resistivity.

The inversion results are not unique – any number of earth models will fit the measured chargeability and apparent resistivity. When properly applied, inversion may correct the IP results for overburden masking, terrain effects and physical attenuation due to depth of burial. When not properly applied, inversion can generate wildly unrealistic IP sections, including false IP anomalies. Inversion results are best viewed in parallel with the measured results. Chargeability highs seen only in the inversion are suspect.

Pseudosections Pseudosections are plotted using standard depth and position conventions. For fixed ‘a’ surveys, the plot point for any measured quantity for the nth potential dipole pair is (n+½)a/2 m forward of and below the current electrode. For combination surveys where the ‘a’ spacing changes from 25 to 50 m, the plot point for any receiver dipole is ‘x’ m forward of and below the current electrode where ‘x’ is half the distance between the current electrode and the centre points of the Rx dipole. Pole-dipole anomaly shapes depend on array orientation. The array sketch shown with each pseudo section shows the correct array orientation.

These plot forms have been found to give a reasonable image of target-top location, width and depth where 1) the anomalously chargeable and/or resistive body is an isolated, tabular body with a dip that is within ± 45° of vertical, 2) where background chargeabilities and resistivities (overburden and host rock) are uniform and 3) where the terrain is relatively flat. They are more difficult to interpret for irregular, nearby or shallow dipping chargeable bodies and where there is any amount of conductive cover or topographic relief. Forward or inverse modelling may be useful in such cases. For Mx, MIP and apparent resistivity, colour contour intervals in the pseudosections are taken from equal area distribution for the whole grid. Colour assignments for the spectral time constant are fixed.

Archives The results of the survey are archived on CD. Included on the CD is the Oasis Montaj viewer. File types include

*.txt or *.dat or *.xyz or *.xls – text and Excel files, instrument data dumps, collated line files *.gdb - Geosoft databases (magnetics, IP/resistivity) *.map – Geosoft maps and pseudo sections *.doc and *.pdf – this report

Page 22: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 1

Appendix 2 Weekly Field Production Reports

JVX Ltd.

Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: November 26, 2011

Day Description of Work (Survey Details, Location, etc.)

Line From

To Length, m

Sun. November

20

Mobilization. Travel Thunder Bay to Manitouwadge

Mon. November

21

Located grid and cut trees for access. 30 minute drive and 40 minute quad

ride to get to the grid

Tue. November

22 Mag survey

3600W 3700W 3800W 3900W

9325N 9360N 9425N 9475N

12000N 12000N 12000N 12025N

2675 2640 2575 2550

Wed. November

23 Mag survey. Had some icing

problems with the quad

4100W 4000W 3500W 3400W

9475N 9475N 9300N 9300N

12000N 12000N 12000N 12025N

2525 2525 2700 2725

Thu. November

24

Mag survey. Had trouble starting quad at end of day. Also checked for southern road access – Twist

Lake road no good

4200W 4300W 3300W 10000N

9500N 9475N 9225N 3300W

12000N 12000N 11975N 4200W

2500 2525 2750 1900

Fri. November

25 Mag survey

4700W 4600W 4500W 4400W

9500N 9500N 9500N 9500N

12000N 12000N 12000N 12000N

2500 2500 2500 2500

Sat. November

26 Day off

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6101 6101 6205 6205 6205 6205 off

Field Assistant Jeff Spiers 6101 6101 6205 6205 6205 6205 off

Page 23: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 2

JVX Ltd. Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: December 3, 2011

Day Description of Work

(Survey Details, Location, etc.) Line From

To Length, m

Sun. November

27

Mag survey 4800W 4900W 5000W 5100W

9475N 9475N 9500N 9500N

12000N 12000N 12000N 12000N

2525 2525 2500 2500

Mon. November

28

Mag survey 5200W 5300W 5400W

9475N 9475N 9475N

11975N 12000N 10000N

2500 2525 525

Tue. November

29

Took quad from bush. Picked Jeff up in White River. Worked on IP equipment

Wed. November

30

Laid infinity and access wire. Put tent up

Thu. December

1

IP survey. Had some trouble with access wire in pm. Some wire was

put on the spool but not spliced

4500W 11125N 10000N 1125

Fri. December

2

IP survey. Short-handed crew of 4. Combo array, 2x25 + 6x50, alternating with 3x25 + 5x50

4500W 4600W

10000N 11125N

9500N 10925N

500 200

Sat. December

3

IP survey. Short-handed crew of 4. 4600W 10925N 9475N 1450

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6205 6205 6101 6207 6207 6101 off Assistant Jeff Spiers 6205 6205 6101 6207 6207 6101 off Manager Dennis Palos 6101 6207 6207 6207 6207 Assistant Jeff Boettcher 6101 6207 6207 6207 6207 Assistant Yaroslav Kubacek 6207 6207 6207 6207

Tx Operator Michel Begin

Page 24: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 3

JVX Ltd. Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: December 10, 2011

Day Description of Work

(Survey Details, Location, etc.) Line From

To Length, m

Sun. December

4

IP survey. Also fixed broken infinite wire (moose), replaced drive belt, changed reel with broken take out

4700W 11125N 10200N 925

Mon. December

5

IP Survey 4700W 4800W

10200N 11000N

9550N 10800N

650 200

Tue. December

6

IP Survey 4800W 10800N 9475N 1325

Wed. December

7

IP Survey 4900W 11025N 9475N 1550

Thur. December

8

IP Survey 5000W 10875N 9500N 1375

Fri. December

9

Day off

Sat. December

10

IP Survey 5100W 10825N 9450N 1375

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6101 6207 6207 6201 6207 Assistant Jeff Speirs 6101 6207 6207 6201 6207 Manager Dennis Palos 6207 6207 6207 6101 6101 Assistant Jeff Boettcher 6207 6207 6207 6207 6207 6201 6207 Assistant Yaroslav Kubacek 6207 6207 6207 6207 6207 6201 6207 Assistant Mitch Begin 6207 6207 6207 6207 6207 6201 6207 Assistant Dan Kelly 6207 6207 6201

Geophysicist Estifanos Ghared 6101 6101 6101

Page 25: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 4

JVX Ltd. Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: December 17, 2011

Day Description of Work

(Survey Details, Location, etc.) Line

From To Length, m

Sun. December

11

IP survey. Line 5200W and set up on line 5300W

5200W 10775N 9475N 1300

Mon. December

12

IP survey 5300W 5400W

10775N 10025N

9475N 9525N

1300 500

Tue. December

13

IP survey. Picked up wire. Laid new access wire. Cut firewood

4400W 11125N 10225N 950

Wed. December

14

Day off. Waited for truck. Helped unload snow machine and generator

Thur. December

15

IP survey 4400W 4300W

10225N 11125N

9475N 10450N

750 675

Fri. December

16

IP survey. Snake broke. Solder on Rx leads and wires started breaking off

4300W 10425N 9950N 875

Sat. December

17

IP survey 4100W 11025N 9525N 1500

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6207 6207 6207 off 6207 6207 6207 Assistant Jeff Speirs 6207 6207 6207 off 6207 6207 6207 Assistant Jeff Boettcher 6207 6207 6207 off 6207 6207 6207 Assistant Yaroslav Kubacek 6207 6207 6207 off 6207 6207 6207 Assistant Mitch Begin 6207 6207 6207 off 6207 6207 6207

Page 26: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 5

JVX Ltd. Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: December 24, 2011

Day Description of Work

(Survey Details, Location, etc.) Line From

To Length, m

Sun. December

18

IP survey 4200W 11025N 9475N 1550

Mon. December

19

Picked up all equipment from grid.

Tue. December

20

Demob. Loaded trucks. Travel to Thunder Bay. Stored truck and expensive equipment.

Wed. December

21

Thur. December

22

Fri. December

23

Sat. December

24

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6207 6101 6101 Assistant Jeff Speirs 6207 6101 6101 Assistant Jeff Boettcher 6207 6101 6101 Assistant Yaroslav Kubacek 6207 6101 6101 Assistant Mitch Begin 6207 6101

Page 27: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 6

JVX Ltd. Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: January 14, 2012

Day Description of Work

(Survey Details, Location, etc.) Line From

To Length, m

Sun. January

8

Laid out infinity. Had problems – no 300 m snake.

Mon. January

9

Laid access wire. Put up tent. Broke ski-doo trail. Cut firewood.

Tue. January

10

IP survey 4000W 11025N 10125N 900

Wed. January

11

IP survey. Note 100 m chaining error on this line.

4000W 3900W

10125N 10900N

9450N 10400N

675 500

Thur. January

12

IP survey. Note 100 m chaining error on this line.

3900W 3800W

10400N 10900N

9450N 10525N

950 375

Friday January

13

Sat. January

14

IP survey. Had trouble starting generator.

3800W 10525N 9375N 1150

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6101 6101 6207 6207 6207 6207 6207 Assistant Jeff Speirs 6101 6101 6207 6207 6207 6207 6207 Assistant Yaroslav Kubacek 6101 6101 6207 6207 6207 6207 6207 Assistant Claude Robert 6101 6101 6207 6207 6207 6207 6207 Assistant Mitch Begin 6101 6207 6207 6207 6207 6207 Assistant Brad Jackson 6207 6207 6207 6207 6207

Page 28: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 2: Weekly Field Production Reports

Tyko Resources - Tyko Property - 2011 Grid JVX 11-99 7

JVX Ltd.

Weekly Field Production Report

Project No 11-99 Client : Tyko Resources Area : Tyko Property - 2011 Grid Week Ending: January 21, 2012

Day Description of Work (Survey Details, Location, etc.)

Line From

To Length, m

Sun. January

15

IP survey 3700W 11025N 9325N 1700

Mon. January

16

IP Survey 3600W 11075N 9725N 1350

Tue. January

17

IP survey. Generator quit so we packed last 3 lines. Picked up wire. Cut firewood. Heated generator and changed plus, oil and gas.

3600W 9725N 9275N 500

Wed. January

18

IP survey 3500W 11125N 9300N 1825

Thur. January

19

Picked up wire and equipment from the field

Fri. January

20

Day off

Sat. January

21

Day off. Jeff and Jaroslav went and picked up snow machines from the grid.

Field Day Off : 6201, Weather and Standby : 6210, Mobilization/Demobilization : 6101

DHIP : 6202, GPS : 6203, Gravity : 6204, Mag : 6205, MaxMin : 6206, Surface IP : 6207, TDEM : 6208, VLF : 6209

Position Name S M T W T F S Crew Chief Scott Mortson 6207 6207 6207 6207 6101 6201 6101 Assistant Jeff Boettcher 6207 6207 6207 6207 6101 6201 6101 Assistant Yaroslav Kubacek 6207 6207 6207 6207 6101 6201 6101 Assistant Claude Robert 6207 6207 6207 6207 6101 6201 6101 Assistant Mitch Begin 6207 6207 6207 6207 6101 6201 6101 Assistant Brad Jackson 6207 6207 6207 6207 6101 6201 6101

Page 29: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 1

Appendix 3 - IP Anomalies IP anomalies have been picked from pseudosections of Mx chargeability. The spectral chargeability amplitude MIP may be consulted where the anomaly is poorly defined. IP anomalies are identified by the line and station of the centre-top of the IP anomaly. Additions are an identifying letter, the chargeability peak amplitude in mV/V (Mx), the class (C : weak, Moderate or Strong), the dipole number of the anomaly centre-top (n), the spectral IP amplitude (MIP) in mV/V, the time constant range (TC), the n=1 resistivity at or over the centre-top (rho1) and the resistivity expression, if any, of the IP anomaly (resis). The time constant range is shown as S - short (< 0.1 sec), M - moderate or mixed (0.1 to 10 seconds) and L - long (> 10 seconds). A blank entry means the results were incomplete, inconclusive or unavailable. For an IP anomaly to be classified as weak, the peak Mx chargeability is normally in the range of 5 to 10 mV/V. Moderate strength IP anomalies have a peak Mx chargeability of 10 to 20 mV/V. Strong IP anomalies have a peak Mx chargeability of more than 20 mV/V.

Line ID Centre-Top Mx C n MIP TC Rho1 Resis

3500W A 9587.5 10.9 M 1 359 L 10368 high

B 9637.5 10.7 M 1 199 L 5319 -

3600W A 9525 12.6 M 1 375 L 894 low B 9587.5 6.0 w 1 138 S 2060 -

3700W A 10512.5 5.3 w 1 213 S 12023 high

3800W

3900W

4000W

4100W

4200W

4300W

4400W

4500W

4600W A 10412.5 7.2 w 1 255 L 9277 - B 10962.5 7.5 w 1 263 M 10481 -

4700W A 10312.5 6.0 w 1 233 S 10479 -

4800W A 10312.5 7.9 w 1 274 L 11725 - B 10362.5 9.6 w 1 329 L 10601 -

4900W A 10225 16.0 M 1 477 L 4540 low B 10262.5 22.4 S 1 361 L 3433 low

5000W A 10225 25.1 S 1 414 L 1468 low B 10262.5 24.9 S 1 397 L 1316 low C 10300 25.2 S 1 401 L 1398 low

5100W A 10250 20.2 S 1 340 L 2908 low

Page 30: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Appendix 3 : IP Anomalies

Tyko Resources – Tyko Property – 2011 Grid JVX 11-99 2

Line ID Centre-Top Mx C n MIP TC Rho1 Resis

5200W A 10225 14.5 M 1 421 L 7204 low

5300W

5400W

Page 31: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Introduction The GSM-19 v7.0 Overhauser instrument is the total field magnetometer / gradiometer of choice in today’s earth science environment -representing a unique blend of physics, data quality, operational efficiency, system design and options that clearly differentiate it from other quantum magnetometers.

With data quality exceeding standard proton precession and comparable to costlier optically pumped cesium units, the GSM-19 is a standard (or emerging standard) in many fields, including:

* Mineral exploration (ground and airborne base station)

* Environmental and engineering * Pipeline mapping * Unexploded Ordenance Detencion

* Archeology * Magnetic observatory measurements * Volcanology and earthquake

prediction

Taking Advantage of the Overhauser Effect

GSM-19 v7.0Overhauser

Magnetometer / Gradiometer / VLF

Overhauser effect magnetometers are essentially proton precession devices except that they produce an order-of magnitude greater sensitivity. These "supercharged" quantum magnetometers also deliver high absolute accuracy, rapid cycling (up to 5 readings / second), and exceptionally low power consumption. The Overhauser effect occurs when a special liquid (with unpaired electrons) is combined with hydrogen atoms and then exposed to secondary polarization from a radio frequency (RF) magnetic field. The unpaired electrons transfer their stronger polarization to hydrogen atoms, thereby generating a strong precession signal-- that is ideal for very high-sensitivity total field measurement.

In comparison with proton precession methods, RF signal generation also keeps power consumption to an absolute minimum and reduces noise (i.e. generating RF frequencies are well out of the bandwidth of the precession signal).

In addition, polarization and signal measurement can occur simultaneously - which enables faster, sequential measurements. This, in turn, facilitates advanced statistical averaging over the sampling period and/or increased cycling rates (i.e. sampling speeds).

The unique Overhauser unit blends physics, data quality, operational efficiency, system design and options into an instrumentation package that ... exceeds proton precession and matches costlier optically pumped cesium capabilities. And the latest v7.0 technology up-grades provide even more value, including: - Data export in standard XYZ (i.e. line-oriented) format for easy use in standard commercial software programs - Programmable export format for full control over output

- GPS elevation values provide input for geophysical modeling

- <1.5m standard GPS for high- resolution surveying

- <1.0 OmniStar GPS

- <0.7m for Newly introduced CDGPS

- Multi-sensor capability for advanced surveys to resolve target geometry

- Picket marketing / annotation for capturing related surveying information on the go.

And all of these technologies come complete with the most attractive prices and warranty in the business!

Terraplus Inc. 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9

Tel: 905-764-5505 Fax: 905-764-8093

Email: [email protected] Website: www.terraplus.ca

Page 32: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

MAGNETOMETERS

Maximizing Your Data Quality with the GSM-19

Data quality is a function of five key param­eters that have been taken into considera­tion carefully in the design of the GSM-19. These include sensitivity, resolution, absolute accuracy, sampling rates and gradient tolerance.

Sensitivity is a measure of the signal-to noise ratio of the measuring device and reflects both the underlying physics and electronic design. The physics of the Overhauser effect improves sensitivity by an order of magnitude over conventional proton precession devices. Electronic enhancements, such as high-precision precession frequency counters enhance sensitivity by 25% over previous versions.

The result is high quality data with sensitivi­ties of 0.022 nT / vHz. This sensitivity is alsothe same order-of magnitude as costieroptically pumped cesium systems.

Resolution is a measure of the small­est number that can be displayed on the instrument (or transmitted via the download process). The GSM-19 has unmatched resolution (0.01mT)

This level of resolution translates into well-defined, characteristic anomalies; im­proved visual display; and enhanced numerical data for processing and modeling.

Absolute accuracy reflects the closeness to the "real value" of the mag­netic field -- represented by repeatability of readings either at stations or between different sensors. With an absolute accu­racy of +/- 0.1 nT, the GSM-19 delivers repeatable station-to-station results that are reflected in high quality total field results.

Similarly, the system is ideal for gradient installations (readings between different sensors do not differ by more than +/- 0.1 nT) -- maintaining the same high standard

of repeatability.

Data from Kalahari Desert kimberlites. Courtesy of MPH Consulting (project managers), IGS c. c. (geophysical contractor) and Aegis Instruments (Pty) Ltd., Botswana.

The GSM-19 gradiometer data are consistently low in noise and representative of the geologic environment under investigation.

Sampling rates are defined as the fastest speed at which the system can acquire data. This is a particularly important parameter because high sampling rates ensure accurate spatial resolution of anomalies and increase survey efficiency.

The GSM-19 Overhauser system is configured for two "measurement modes" or maximum sampling rates --"Standard" (3 seconds / reading), and"Walking" (0.2 seconds / reading)These sampling rates make the GSM-19 a truly versatile system forall ground applications (including vehicle-borne applications).

Gradient tolerance represents the ability to obtain reliable measure­ments in the presence of extreme magnetic field variations. GSM-19 gradient tolerance is maintained through internal signal counting algorithms, sensor design and Overhauser physics. For example, the Overhauser effect produces high amplitude, long-duration signals that facilitate measurement in high gradi­ents.

The system's tolerance (10,000 nT / meter) makes it ideal for many chal­lenging environments -- such as highly magnetic rocks in mineral exploration applications, or near cultural objects in environmental, UXO or archeological applications.

Total Field and Stationary Vertical Gradient showing the gradient largely

unaffected by diurnal variation. Absolute accuracy is also shown to be

very high (0.2 nT/meter).

Much like an airborne acquisition system, the GSM­19 “Walking” magnetometer option delivers very

highly-sampled, high sensitivity results that enable very accurate target location and / or earth science

decision-making.

Terraplus Inc. Tel: 905-764-5505 Email: [email protected] 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9 Fax: 905-764-8093 Website: www.terraplus.ca

Page 33: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Increasing Your Operational Efficiency Many organizations have standardized their magnetic geophysical acquisition on the GSM-19 based on high performance and operator preference. This preference reflects performance enhancements such as memory capacity; portability character­istics; GPS and navigation; and dumping and processing. Memory capacity controls the efficient daily acquisition of data, acquisition of positioning results from GPS, and the ability to acquire high resolution results (particularly in GSM-19’s "Walking" mode). V7.0 upgrades have established the GSM­19 as the commercial standard for memory with over 1,465,623 readings (based on a basic configuration of 32Mbytes of memory and a survey with time, coordinate, and field values).

Portability characteristics (ruggedness, light weight and power consumption) are essential for operator productivity in both normal and extreme field conditions.

GSM-19 Overhauser magnetometer is established globally as a robust scientific instrument capable of withstanding temperature, humidity and terrain ex­tremes. It also has the reputation as the lightest and lowest power system avail­able -- reflecting Overhauser effect and RF polarization advantages.

In comparison with proton precession and optically pumped cesium systems, the GSM-19 system is the choice of operators as an easy-to-use and robust system.

GPS and navigation options are increasingly critical considerations for earth science professionals.

GPS technologies are revolutionizing data acquisition -- enhancing productiv­ity, increasing spatial resolution, and providing a new level of data quality for informed decision-making.

The GSM-19 is now available with real-time GPS and DGPS options in differ­ent survey resolutions. For more details, see the GPS and DGPS section.

The GSM-19 can also be used in a GPS Navigation option with real-time coordinate transformation to UTM, local X-Y coordinate rotations, automatic end of line flag, guidance to the next line, and survey "lane" guidance with cross-track display and audio indicator.

Other enhancements include way point pre-programming of up to 1000 points. Professionals can now define a complete survey before leaving for the field on their PC and download points to the magnetometer via RS-232 connection.

The operator then simply performs the survey using the way points as their survey guide. This capability decreases survey errors, improves efficiency, and ensures more rapid survey completion.

Dumping and processing effectiveness is also a critical consideration today. Historically, up to 60% of an operator's "free" time can be spent on low-return tasks, such as data dumping.

Data dumping times are now signifi­cantly reduced through GEM’s imple­mentation of high-speed, digital data links (up to 115 kBaud).

MAGNETOMETERS

This functionality is faciliated through a new RISC processor as well as the new GSM-19 data acquisition / display software. This software serves as a bi-directional RS-232 terminal. It also has integrated processing functional­ity to streamline key processing steps, including diurnal data reduction. This software is provided free to all GSM­19 customers and regular updates are available.

Navigation and Lane Guidance

The figure above shows the Automatic Grid (UTM, Local Grid, and Rotated Grid). With the Rotated Grid, you can apply an arbitrary origin of your own definition. Then, the coordinates are always in reference to axes parallel to the grid. In short, your grid determines the map, and not the NS direction.

The Local Grid is a scaled down, local version of the UTM system, and is based on your own defined origin. It allows you to use smaller numbers or ones that are most relevant to your

The figure below shows how programmable-waypoints can be

waypoints and enter them via PC or the keyboard. In the field, the unit guides you to each point.

While walking between waypoints, lane guidance keeps you within a lane of predefined width using arrows (< - or - >) to indicate left or right. Within the lane, the display uses horizontal bars (- -) to show your relative position in the lane. The display also shows the distance (in meters) to the next waypoint.

survey.

used to plan surveys on a point-by-point basis. Initially, you define

Terraplus Inc. Tel: 905-764-5505 Email: [email protected] 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9 Fax: 905-764-8093 Website: www.terraplus.ca

Page 34: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Adding Value through Options

When evaluating the GSM-19 as a solution for your geophysical application, we recommend considering the complete range of options described below. These options can be added at time of original purchase or later to expand capabilities as your needs change or grow.

Our approach with options is to provide you with an expandable set of building blocks:

* Gradiometer * *

Walking- Fast Magnetometer / Gradiometer VLF (3 channel)

* GPS (built-in and external)

GSM-19G Gradiometer Option

The GSM-19 gradiometer is a versatile, entry level system that can be upgraded to a full-featured "Walking" unit (model GSM-19WG) in future.

The GSM-19G configuration comprises two sensors and a "Standard" console that reads data to a maximum of 1 reading every three seconds.

An important GSM-19 design feature is that its gradiometer sensors measure the two magnetic fields concurrently to avoid any temporal variations that could distort gradiometer readings. Other features, such as single-button data recording, are included for operator ease-of-use.

GSM-19W / WG "Walking" Magnetometer / Gradiometer Option

The GSM-19 was the first magnetometer to incorporate the innovative "Walking" option which enables the acquisition of nearly continuous data on survey lines. Since its introduction, the GSM-19W / GSM-19WG have become one of the most popular magnetic instruments in the world.

Similar to an airborne survey in princi­ple, the system records data at discrete time intervals (up to 5 readings per second) as the instrument is carried along the line.

At each survey picket (fiducial), the operator touches a designated key. The system automatically assigns a picket coordinate to the reading and linearly interpolates the coordinates of all intervening readings (following survey completion during post-processing).

A main benefit is that the high sample density improves definition of geologic structures and other targets (UXO, archeological relics, drums, etc.).

It also increases survey efficiency because the operator can record data almost continuously. Another productiv­ity feature is the instantaneous record­ing of data at pickets. This is a basic difference between the “Walking” version and the GSM-19 / GSM-19G (the “Standard” mode version which requires 3 seconds to obtain a reading each time the measurement key is pressed).

GSM-19 "Hands-Free" Backpack Option The "Walking" Magnetometer and Gradiometer can be configured with an optional backpack-supported sensor. The backpack is uniquely constructed -permitting measurement of total field or gradient with both hands free. This option provides greater versatility and flexibility, which is particularly valuable for high-productivity surveys orin rough terrain.

MAGNETOMETERS

GSM-19GV "VLF" Option

With its omnidirectional VLF option, up to 3 stations of VLF data can be ac­quired without orienting. Moreover, the operator is able to record both magnetic and VLF data with a single stroke on the keypad.

3rd Party Software - A One-Stop Solution for Your Po­tential Field Needs

As part of its complete solution ap­proach, Terraplus offers a selection of proven software packages. These packages let you take data from the field and quality control stage right through to final map preparation and modeling.

Choose from the following packages:

* Contouring and 3D Surface Mapping

* Geophysical Data Processing & Analysis

* Semi-Automated Magnetic Modeling

* Visualization and Modeling / Inversion

Geophysical Data Processing and Analysis from Geosoft Inc.

GSM-19 with internal GPS board. Small receiver attaches above sensor

Terraplus Inc. Tel: 905-764-5505 Email: [email protected] 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9 Fax: 905-764-8093 Website: www.terraplus.ca

Page 35: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

Version 7 -- New Milestones in Magnetometer Technology

The recent release of v7.0 of the GSM-19 system provides many examples of the ways in which we continue to advance magnetics technologies for our customers.

Enhanced data quality:

* 25% improvement in sensitivity (new frequency counting algorithm)

* new intelligent spike-free algo rithms (in comparison with other manufacturers, the GSM-19 does not apply smoothing or filtering to achieve high data quality)

Improved operational efficiency:

* Enhanced positioning (GPS engine with optional integrated / external GPS and real-time navigationl)

* 16 times increase in memory to 32 Mbytes

* 1000 times improvement in processing and display speed (RISC microprocessor with 32-bit data bus) 2 times faster digital data link (115 kBaud through RS-232)

Innovative technologies:

* Battery conservation and survey flexibility (base station scheduling option with 3 modes - daily, flexible and immediate start)

* Survey pre-planning (up to 1000 programmable waypoints that can be entered directly or downloaded from PC for greater efficiency)

* Efficient GPS synchronization of field and base units to Universal Time (UTC)

* Cost saving with firmware up grades that deliver new capabilities via Internet

MAGNETOMETERS More About the Overhauser System

In a standard Proton magnetometer, current is passed through a coil wound around a sensor containing a hydrogenrich fluid. The auxiliary field created by the coil (>100 Gauss) polarizes the protons in the liquid to a higher thermal equilib­rium.

When the current, and hence the field, is terminated, polarized protons precess in the Earth's field and decay exponentially until they return to steady state. This process generates precession signals that can be measured as described below.

Overhauser magnetometers use a more efficient method that combines electronproton coupling and an electron-rich liquid (containing unbound electrons in a solvent containing a free radical). An RF magnetic field -- that corresponds to a specific energy level transition -- stimulates the unbound electrons.

Instead of releasing this energy as emitted radiation, the unbound electrons transfer it to the protons in the solvent. The resulting polarization is much larger, leading to stronger precession signals.

Both Overhauser and proton precession, measure the scalar value of the magnetic field based on the proportionality of precession frequency and magnetic flux density (which is linear and known to a high degree of accuracy). Measurement quality is also calculated using signal amplitude and its decay characteristics. Values are averaged over the sampling period and recorded.

With minor modifications (i.e. addition of a small auxiliary magnetic flux density while polarizing), it can also be adapted for high sensitivity readings in low magnetic fields. (ex. for equatorial work)

GPS - Positioning You for Effective Decision Making

The use of Global Positioning Satellite (GPS) technol­ogy is increasing in earth science disciplines due to the ability to make better decisions in locating and follow­ing up on anomalies, and in improving survey cost effectiveness and time management.

Examples of applications include: Surveying in remote locations with no grid

* High resolution exploration mapping * High productivity ferrous ordnance (UXO) detection * Ground portable magnetic and gradient surveying for environmental

and engineering applications * Base station monitoring for observing diurnal magnetic activity and

disturbances with integrated GPS time

The GSM-19 addresses customer requests for GPS and high-resolution Differ­ential GPS (DGPS) through both the industry’s only built-in GPS (as well as external GPS).

Built-in GPS offers many advantages such as minimizing weight and removing bulky components that can be damaged through normal surveying. The follow­ing table summarizes GPS options.

system (for example, in the high Arctic for diamond exploration)

Terraplus Inc. Tel: 905-764-5505 Email: [email protected] 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9 Fax: 905-764-8093 Website: www.terraplus.ca

Page 36: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

MAGNETOMETERS

Key System Components

Key components that differentiate the GSM-19 from other systems on the market include the sensor and data acquisition console. Specifications for components are provided on the right side of this page.

Sensor Technology

Overhauser sensors represent a propri­etary innovation that combines advances in electronics design and quantum magnetometer chemistry.

Electronically, the detection assembly includes dual pick-up coils connected in series opposition to suppress far-source electrical interference, such as atmos­pheric noise. Chemically, the sensor head houses a proprietary hydrogen-rich liquid solvent with free electrons (free radicals) added to increase the signal intensity under RF polarization.

From a physical perspective, the sensor is a small size, light-weight assembly that houses the Overhauser detection system and fluid. A rugged plastic housing protects the internal compo­nents during operation and transport.

All sensor components are designed from carefully screened non-magnetic materials to assist in maximization of signal-to-noise. Heading errors are also minimized by ensuring that there are no magnetic inclusions or other defects that could result in variable readings for different orientations of the sensor.

Optional omni-directional sensors are Performance available for operating in regions where the magnetic field is near-horizontal (i.e. Sensitivity: 0.022 nT / vHz@1Hzequatorial regions). These sensors Resolution: 0.01 nT maximize signal strength regardless of Absolute Accuracy: +/- 0.1 nTfield direction. Dynamic Range: 15,000

to 120,000 nTData Acquisition Gradient Tolerance: > 10,000 nT/m Console Technology Sampling Rate: 60+, 3, 2, 1,

0.5, 0.2 sec

Console technology comprises an Operating Temp: -40C to +55C

external keypad / display interface with internal firmware for frequency counting, Operating Modes system control and data storage / retrieval. For operator convenience, the Manual: display provides both monochrome text Coordinates, time, date and reading as well as real-time profile data with an stored automatically at minimum 3 easy to use interactive menu for per- second interval. forming all survey functions. Base Station:

Time, date and reading stored at 3 toThe firmware provides the convenience 60 second intervals. of upgrades over the Internet via its Remote Control: software. The benefit is that instrumen- Optional remote control using RS-232tation can be enhanced with the latest interface.technology without returning the system Input / Output:to us -- resulting in both timely imple­mentation of updates and reduced RS-232 or analog (optional) output

shipping / servicing costs. using 6-pin weatherproof connector

Storage - 32Mbytes (# of Readings) Mobile: 1,465,623Base Station: 5 ,373,951Gradiometer: 1,240,142Walking Magnetometer: 2 ,686,975

Dimensions Console: 223 x 69 x 240 mmSensor: 175 x 75mm diameter cylinder

Weights Console: 2.1 kgSensor and Staff Assembly: 1.0 kg

Standard Components GSM-19 console, GEMLinkW software, batteries, harness, charger, sensor with cable, RS-232/USB cable, staff, instruction manual and shipping case.

Optional VLF Frequency Range: Up to 3 stations between 15 to 30.0 kHz Parameters: Vertical in-phase and out-of phase

components as % of total field. 2 components of the horizontal field amplitude and total field strenght in pT Resolution: 0.1% of total field

Terraplus Inc. Tel: 905-764-5505 Email: [email protected] 52 West Beaver Cr. Rd. #12, Richmond Hill, ON. Canada L4B 1L9 Fax: 905-764-8093 Website: www.terraplus.ca

AF
Text Box
GPS Options: Description Range Services Time GPS Option A Reception only GPS Option B <1.5m DGPS* GPS Option C <1.0m Ag 114 DGPS*, OmniStar <0.7m GPS Option D <1.2m CDGPS, DGPS *, <1.0M OmniStar. Output Time, Lat / Long, UTM, Elevation and number of Satellites *DGPS with SBAS (WASS/EGNOS/MSAS)
AF
Text Box
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
AF
Pencil
Page 37: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

IPR-12

Induced Polarization

ELECTRICAL METHODS

Page 38: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

IPR­12 SPECIFICATIONS

Inputs 1 to 8 dipoles are measured simultaneously.

Input Impedance 16 Megohms

SP Bucking ± 10 volt range. Automatic linear correction operating on a cycle by cycle basis.

Input Voltage (Vp) Range 50 µvolt to 14 volt.

Chargeability (M) Range 0 to 300 millivolt/volt.

Tau Range 60 microseconds to 2000 seconds.

Reading Resolution of Vp, SP and M Vp, 10 microvolt; SP, 1 millivolt; M, 0.01 millivolt/volt.

Absolute Accuracy of Vp, Sp and M Better than 1% .

Common Mode Rejection At input more than 100db.

Vp Integration Time 10% to 80% of the current on time.

IP Transient Program Total measuring time keyboard selectable at 1,2,4,8,16 or 32 seconds. Normally 14 windows except that the first four are not measured on the 1 second timing, the first three are not measured on the 2 second timing and the first is not measured on the 4 second timing. An additional transient slice of minimum 10 ms width, and 10 ms steps, with delay of at least 40 ms is keyboard selectable. Programmable windows also available.

Transmitter Timing Equal on and off times with polarity change each half cycle. On/off times of 1,2,4,8,16 or 32 seconds. Timing accuracy of ±100 ppm or better is required.

External Circuit Test All dipoles are measured individually in sequence, using a 10 Hz square wave. The range is 0 to 2 Mohm with 0.1 kohm resolution. Circuit resistances are displayed and recorded.

Filtering RF filter, 10 Hz 6 pole low pass filter, statistical noise spike removal.

Internal Test Generator 1200 mV of SP; 807 mV of Vp and 30.28 mV/V of M.

Analog Meter For monitoring input signals; switchable to any dipole via keyboard.

Keyboard 17 key keypad with direct one key access to the most frequently used functions.

Display 16 lines by 40 characters, 128 x 240 dots, Backlit SuperTwist Liquid Crystal Display. Displays instrument status and data during and after reading. Alphanumeric and graphic displays.

Display Heater Available for below ­15°C operation.

Memory Capacity Stores approximately 400 dipoles of information when 8 dipoles are measured simultaneously.

Real Time Clock Data is recorded with year, month, day, hour, minute and second.

Digital Data Output Formattted serial data output for printer and PC, etc. Data output in 7 or 8 bit ASCII, one start, one stop bit, no parity format. Baud rate is keyboard selectable for standard rates between 300 baud and 57.6 kBaud. Selectable carriage return delay to accommodate slow peripherals. Hand­shaking is done by X­on/X­off.

Standard Rechargeable Batteries Eight rechargeable Ni­Cad D cells. Supplied with a charger, suitable for 100/230V, 50 to 60 Hz, 10W. More than 20 hours service at +25°C, more than 8 hours at ­30°C.

Ancillary Rechargeable Batteries An additional eight rechargeable Ni­ Cad D cells may be installed in the console along with the Standard Rechargeable Batteries. Used to power the Display Heater or as backup power. Supplied with a second charger. More than 6 hours service at ­30°C.

Use of Non­Rechargeable Batteries Can be powered by D size Alkaline batteries, but rechargeable batteries are recommended for lower cost over time.

Operating Temperature Range ­30°C to +50°C.

Storage Temperature Range ­30°C to +50°C.

Dimensions Console: 355 x 270 x 165 mm Charger: 120 x 95 x 55 mm

Weights Console: 5.8 kg Batteries: 1.3 kg Charger: 1.1 kg

Transmitters Available GGT­3 GGT­10

An ISO 9001:2000 registered company

* All specifications are subject to change without notice.

CANADA Scintrex 222 Snidercroft Road Concord, Ontario, Canada L4K 2K1 Telephone: +1 905 669 2280 Fax: +1 905 669 6403 e­mail: [email protected] Website: www.scintrexltd.com

USA Micro­g LaCoste 1401 Horizon Avenue Lafayette, CO 80026 Telephone: +1 303 828 3499 Fax: +1 303 828 3288 e­mail: [email protected] website: www.microglacoste.com

Page 39: Report on Spectra IP/Resistivity and Magnetic Surveys Tyko

SPECIFICATIONS Txll-1800 W Txll-3600 W

• Size: 21 x 34 x 39 em. • 51 X 41.5 X 21.5 em- built-in transportation box from Pelican. • Weight: approximately 20 kg. • Operating temperature: -40' C to 65' C.

ELECTRICAL CHARACTERISTICS Txll-1800 Wand Txll-3600 W

• Weight: approximately 32 kg. • Operating temperature: -40' C to 65' C.

• Standard time base of 2 seconds for time-domain: 2 seconds ON, 2 seconds OFF • Optional time base: DC, 0.5, 1, 2, 4 or DC, 1, 2, 4, 8 seconds. • Output current range: 0.030 to 10 A (normal operation).

0.000 to 10 A (cancel open loop). • Output voltage range: 150 to 2400 V /14 steps. • Ability to link 2 GOD transmitters to double power (Master I Slave).

CONTROLS Txll-1800 Wand Txll-3600 W

• Power ON/OFF • Output voltage range switch: 150 V, 180 V, 350 V, 420 V, 500 V, 600 V, 700 V,

840 V, 1000 V, 1200 V, 1400 V, 1680 V, 2000 V, 2400 V.

DISPLAYS Txll-1800 W and Txll-3600 W

• Output current LCD: reads to :t 0.001 A. • Electrode contact displayed when not transmitting. • Output power displayed when transmitting. • Automatic thermostat controlled LCD heater for readout. • Total protection against short circuits even at zero (0) ohm. • Indicator lamps in case of overload:

- High voltage ON/OFF - Generator over or undervoltage - Logic fail

POWER Txll-1800 W

Recommended generator:

- Output overcurrent - Overheating - Open Loop Protection

• Standard 120 VI 60 Hz backpackable Honda generator.

Txll-3600 W

Recommended generator: • Standard 220 V, 50/ 60 Hz Honda generator.

• Suggested Models: EU1000iC, 1000 W, 13.5 kg or EU2000iC, 2000 W, 21.0 kg.

• Suggested Models: EM3500XK1 C, 3500 W, 62 kg or EM5000XK1 C, 5000 kw, 77 kg.

DESCRIPTION Txll-1800 W Txll-3600 W

• Includes shipping box, instruction manual and 110 V plug. • Includes built-in shipping box, instruction manual and 220 V plug. • Optional backpackable frame for transmitter or generator. • Optional 220 V extension.

SERVICE Any instrument manufactured by GOD that breaks down while under warranty or service contract is replaced free of charge upon request, subject to instrument availability.

WARRANTY • Standard three-year warranty on parts and labour. • Repairs done at GOO's oflice in Sainte-Foy, QC, Canada.

Instrumentation GOD inc.

3700, bout. de Ia Chaudiere, suite 200 Sainte-Foy (Quebec) Canada G1X 467

Tel. : (418) 877-4249 Toll Free : 1·877·977-4249 Fax: (418) 877-4054

Web Site: www.gddinstrumentation.com E-Mail : [email protected]

Specifications subject to change without notice.

Taxes, transportation and duties are extra if applicable.

Instruments available for rental or sale.

© Copyright 2005 Instrumentation GOD inc.