TM Power Distribution Packs
Rental Accessories
� Kohler Rental Power provides one-sourceresponsibility for the generating system andaccessories.
� Select from a wide variety of power distributionconfigurations to meet your application needs.
� Nine models are available with UL NEMA 3R listing.
� The rubber enclosure power distribution packtypically has individual circuit breaker protection andquick setup with color-coded, cam-type electricalconnections or a twist-lock connector.
30 Amp Quad Box
DB200NT-ALL-S3
Model Number DB200NT-ALL-S3
Agency Approval UL NEMA 3R
Rating 150 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Five L21-30, 30 A,120/208 V, 3-phase,weatherproof receptacles
BreakerConfiguration
Five 30 A, 3-pole, branchcircuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
279 x 279 x 356(11 x 11 x 14)
Weight, kg (lb.) 15.9 (35)
30 Amp RV Distribution Box
7506G
Model Number 7506G
Agency Approval UL NEMA 3R
Rating 150 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Four male panel mount minicam connectors,100 A/220 V
Output Four 30A, TT--30R, 125 V, 1-phase straight bladereceptacle, see View AFour 20 A, duplex 5-20R, 125 V, 1-phasenon-GFI receptacle, see View B
View A View B
G
G
W
BreakerConfiguration
Four 30 A, 1-pole branch circuit-rated breakersFour 20 A, 1-pole branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
533 x 381 x 279(21 x 15 x 11)
Weight, kg (lb.) 13.2 (29)
G32-4 11/04d Page 2
50 Amp RV to 6-5/20 NEMA
DB50A-SPZ620FT
Model Number DB50A-SPZ620FT
Agency Approval UL NEMA 1
Rating 50 A, 120/240 V, 1-phase, 60 Hz, 3-wire
Input One CS63-65, 50 A plug, one feed throughCS63-69, 50 A, single locking receptacle
Output Six 20 A duplex receptacles,5-20R 125 V, non GFI G
W
BreakerConfiguration
Six 20 A, 1-pole, branchcircuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
358.3 x 368.3 x 317.5(14.5 x 14.5 x 12.5)
Weight, kg (lb.) 12.2 (27)
100 Amp Quad Box
DB100A-SPZ1000
Model Number DB100A-SPZ1000
Agency Approval UL NEMA 3R
Rating 100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Five L21-20, 20 A,120/208 V, 3-phase,weatherproof receptacles
BreakerConfiguration
Five 20 A, 3-pole, branchcircuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
317.5 x 317.5 x 317.5(12.5 x 12.5 x 12.5)
Weight, kg (lb.) 12 (26.5)
100 Amp RV Distribution Box
DB100A-SPZ6369
Model Number DB100A-SPZ6369
Agency Approval UL NEMA 3R
Rating 100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Four CS-63-69, 50 A,125/250 V, 1-phase,4-wire, weatherprooflocking receptacles
X
W
Y
G
BreakerConfiguration
Four 50 A, 2-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
317.5 x 317.5 x 317.5(12.5 x 12.5 x 12.5)
Weight, kg (lb.) 12.2 (27)
G32-4 11/04d Page 3
100 Amp Minicam Distribution Box
DBSPZ-100A-MC
Model Number DBSPZ-100A-MC
Agency Approval UL NEMA 3R
Rating 100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Two rows 60 A, 220 V, 1-phase, panel mountminicamsTwo rows 100 A, 220 V, 1-phase, panel mountminicams
BreakerConfiguration
Two 60 A, 2-pole, branch circuit-rated breakersTwo 100 A, 2-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
317.5 x 317.5 x 317.5(12.5 x 12.5 x 12.5)
Weight, kg (lb.) 14.5 (32)
100 Amp 3-Phase to Multiple 30 Amp and 20 Amp, 1-Phase Outputs
DBC100DP-A4T3
Model Number DBC100DP-A4T3
Agency Approval UL NEMA 3R
Rating 100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five male panel mount cams, 16 series
Output
View D View E
Two 30 A, TT-30R, 125 V, 1-phase, straight bladereceptacles, see View ATwo 30 A, L5-30R, 125 V, 1-phase, lockingreceptacles, see View BTwo 30 A, L6-30R, 250 V, 1-phase, lockingreceptacles, see View COne 30 A, L14-30R, 125/250 V, 1-phase, lockingreceptacle, see View DOne 20 A, L6-20R, 250 V, 1-phase, lockingreceptacle, see View E
View A View B View C
G
BreakerConfiguration
Four 30 A, 1-pole branch circuit-rated breakersThree 30 A, 2-pole branch circuit-rated breakersOne 20 A, 2-pole branch circuit-rated breaker
Overall Dimensions,L x W x H, mm (in.)
279.4 x 279.4 x 330.2(11 x 11 x 13)
Weight, kg (lb.) 14.5 (32)
G32-4 11/04d Page 4
200 Amp Quad Box
DB200A-F201000
Model Number DB200A-F201000
Agency Approval UL NEMA 3R
Rating 200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five male panel mount cams, 16 series
Output Ten L21-20, 20 A,120/208 V, 3-phase,weatherproof receptacles
BreakerConfiguration Ten 20 A, 3-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
381 x 444.5 x 558.8(15 x 17.5 x 22)
Weight, kg (lb.) 28.6 (63)
200 Amp RV Distribution Box
DB200AXO16369
Model Number DB200A-XO16369
Agency Approval UL NEMA 3R
Rating 200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Eight CS-63-69, 50 A,125/250 V, 1-phase,4-wire, weatherprooflocking receptacles
X
W
Y
G
BreakerConfiguration
Eight 50 A, 2-pole, branchcircuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
508 x 508 x 355.6(20 x 20 x 14)
Weight, kg (lb.) 24 (53)
200 Amp Minicam Distribution Box
DBXO1/6CAM
Model Number DBXO1/6CAM
Agency Approval UL NEMA 3R
Rating 200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five inline male cam connectors, 16 series tails
Output Six rows 100 A, 220 V, 1-phase, panel mountminicams
BreakerConfiguration Six 100 A, 2-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
508 x 508 x 355.6(20 x 20 x 14)
Weight, kg (lb.) 24.9 (55)
G32-4 11/04d Page 5
400 Amp Multibox
DBF20-MULTI
Model Number DBF20-MULTI
Agency Approval UL NEMA 3R
Rating 400 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five male panel mount cams, 16 series
Output Two rows 100 A, 220 V, 3-phase, panel mountminicams; two L21-20, 20 A, 120/208 V, 3-phase,weatherproof receptacles; see View AThree CS63-69, 50A, 125/250 V, 1-phase, 4-wire,weatherproof locking receptacles; see View BFour 20A, 125 V duplex receptacles; see View C
View A View B
X
W
Y
GView C
G
W
BreakerConfiguration
Two 100 A, 3-pole, branch circuit-rated breakersTwo 20 A, 3-pole, branch circuit-rated breakersThree 50 A, 2-pole, branch circuit-rated breakerFour 20 A, 1-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
381 x 444.5 x 558.8(15 x 17.5 x 22)
Weight, kg (lb.) 31.8 (70)
400 Amp Cam-Type Breakout Box
DB400A-F202000
Model Number DB400A-F202000
Agency Approval UL NEMA 3R
Rating 400 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Five male panel mount cams, 16 series
Output Four rows 100 A, 208 V, 3-phase, female panelmount cams, 16 series
Breaker Config. Four 100 A, 3-pole, branch circuit-rated breakers
Overall Dimensions,L x W x H, mm (in.)
381 x 444.5 x 558.8(15 x 17.5 x 22)
Weight, kg (lb.) 34 (75)
600 Amp Cam-Type Breakout Box
DB800-5704200
Model Number DB800-5704200
Agency Approval UL NEMA 3R
Rating 600 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input Two male panel mount cams, 3-phase, 16 seriesTwo rows of five for parallel input cables
Output Three rows 200 A, 3-phase, female panel mountcams, 16 series
Breaker Config. Three 200 A, 3-pole, branch circuit-rated
Overall Dimensions,L x W x H, mm (in.)
622.3 x 530.7 x 383.7 (24.5 x 20.5 x 15.5)with 88.9 (3.5) skids
Weight, kg (lb.) 47.2 (104)
Availability is subject tochangewithout notice.Kohler Co. reserves the rightto change the design or specifications without notice and without anyobligation or liability whatsoever. Contact your local Kohler� Rental Powerregional office for availability. 2001, 2002, 2004 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
KOHLER CO., Kohler, Wisconsin 53044 USAPhone 920-459-1634; Fax 920-459-1846For the nearest sales and service outlet in the USA andCanada, call 1-888-769-3794 or kohlerrentalpower.com
TM
G32-4 11/04d Page 6