    REMOTE POWER MONITORING SYSTEM USING

    MICROCONTROLLERA Project report

    Submitted in partial fulfillment of the requirement

    For the award of the degree of

    BACHELOR OF TECHNOLOGY

    IN

    ELECTRONICS AND COMMUNICATION ENGINEERING

    By

    B. MOHAN KRISHNA (05391A0468)B. VIDYA SAGAR (05391A0489)S.K. RABBANI (05391A0475)

    Under the guidance of

    (Mr. P.J.REGINALD)

    Assistant Professor

    Department of Electronics and Communication EngineeringVIGNANS ENGINEERING COLLEGE

    ISO Certified, NBA & NAAC Accredited with A Grade

    VADLAMUDI 522 213

    GUNTUR (Dt.)

    (2008-09)

  • 8/8/2019 Remote Power Monitor

    2/78

    CERTIFICATE

    This is to certify that this project report entitled

    REMOTE POWER MONITORING USING SYSTEMMICROCONTROLLER

    is a bonafide record of work done by

    B. MOHAN KRISHNA (05391A0468)B. VIDYA SAGAR (05391A0489)S.K. RABBANI (05391A0475)

    Under my guidance and supervision and submitted in partial fulfillment of the requirements for

    the award of the degree of Bachelor of Technology in Electronics and CommunicationEngineering by the Jawaharlal Nehru Technological University, Kakinada.

    (Mr. P.J.REGINALD)

    Guide

    Certified by the Head of the Department

    (Dr. D. VENKATA RAO)

    Professor and Head

    Department of Electronics and Communication Engineering

    VIGNANS ENGINEERING COLLEGE

    ISO Certified, NBA & NAAC Accredited with A Grade

    VADLAMUDI 522 213

    GUNTUR (Dt.)

    (2008-09)

  • 8/8/2019 Remote Power Monitor

    3/78

    ACKNOWLEDGEMENT

    The completion of any project brings with it a sense of satisfaction, but it is never

    complete without thanking those people who made it possible and whose constant support has

    crowned our efforts with success.

    We would also like to thank our guide, Mr. P.J.REGINALD Assistant

    professor, Dept. of Electronics And Communication for his expert guidance, encouragement

    and valuable suggestions at every step.

    We would also like to express our gratitude to Dr. D. VENKATA RAO, Head of the

    Department, Electronics and Communication V.E.C, Vadlamudi, for encouraging and

    inspiring us to carry out the project in the department lab.

    We are grateful to our esteemed principal, VIGNANS ENGINEERING COLLEGE,Vadlamudi, Dr. K.V.N.SRINIVASA RAO f o r supporting and funding this endeavor.

    We also would like to thank all the staff members of E&C dept., classmates for

    providing us with the required facilities and support towards the completion of the project.

    PROJECT ASSOCIATES

    B. MOHAN KRISHNA (05391A0468)B. VIDYA SAGAR (05391A0489)S.K. RABBANI (05391A0475)

  • 8/8/2019 Remote Power Monitor

    4/78

    ABSTRACT

    Electricity is the modern man's most convenient and useful form of energy without

    which the present social infrastructure would not be feasible. The increase in per capita

    production is the reflection of the increase in the living standard of people. When

    importance of electricity is on the increasing side, then how much should theft of this

    energy or illegal consumption of power from the transmission lines be averted? Power theft

    has become a great challenge to the electricity board. Our project identifies the Power theft

    and indicates it to the Electricity board through Power line. We had also dealt about the

    remote monitoring of an energy meter. The project is constructed with the popular

    microcontroller MC551 series 8051 microcontroller, power measurement IC, voltage,

    current transformers.

    The central office is having a PC connected to the different energy meters fixed at

    different organizations wireless link. The energy meter connected at the consumer point

    continuous reads power data and sends it to the PC. The program written in micro

    controller to read and transmit the power data to the PC on request. The PC can connected

    to number of users with there unique ID number. Initially PC transmits the ID code to the

    energy meters then the corresponding energy meters transmits the energy information to

    the PC with the help of this centrally we can monitor energy consumed by different

    consumers and useful for analyzing the unauthorized usage. The software is written in the

    PC for sending request to the energy meter and receiving the energy meter and receiving

    the energy data from consumer point.

  • 8/8/2019 Remote Power Monitor

    5/78

    1. INTRODUCTION 1

    2. BLOCK DIAGRAM 3

    3. POWER MEASURMENT

    3.1 VOLTAGE TRANSFORMERS

    3.1.1 PRINCIPLE OF OPERATION

    3.1.2 TYPICAL TERMS USED FOR SPECIFYING A PT

    3.2 CURRENT TRANSFORMERS

    3.2.1 PRINCIPLE OF OPERATION

    5

    5

    5

    6

    8

    8

    4. ADC0809

    4.1 PIN CONFIGURATION

    4.2 FEATURES

    4.3 KEY SPECIFICATIONS

    4.4 BLOCK DIAGRAM

    4.5 FUNCTIONAL DESCRIPTION

    4.5.1 MULTIPLEXER

    4.5.2 CONVERTER CHARACTERSTICS

    9

    10

    10

    11

    11

    12

    12

    12

    5. 89C52 MICROCONTROLLER

    5.1 INTRODUCTION

    5.2 DESCRIPTION

    5.3 FEATURES

    5.4 PIN DIGRAM

    5.5 PIN CONFIGURATIONS

    5.6 PIN DESCRIPTION

    5.7 MEMORY

    14

    14

    15

    15

    16

    17

    17

    23

    CONTENTS

  • 8/8/2019 Remote Power Monitor

    6/78

    5.7.1 ON-CHIP MEMORY

    5.7.2 EXTERNAL CODE MEMORY

    5.7.3 EXTERNAL RAM

    5.7.4 SPECIAL FUNCTION REGISTER (SFR) MEMORY

    5.8 ADDRESSING MODES

    5.8.1 IMMEDIATE ADDRESSING

    5.8.2 DIRECT ADDRESSING

    5.8.3 EXTERNAL INDIRECT

    5.9 PROGRAMMING THE FLASH MEMORY

    5.10 PROGRAMMING ALGORITHM

    24

    25

    25

    26

    27

    27

    28

    28

    28

    29

    6. SERIAL COMMUNICATION

    6.1 SPEED OF TRANSMISSION

    6.2 RS-232

    6.3 RS-232 CABLING

    6.4 MAX 232C

    6.4.1 LOGIC DIAGRAM6.4.2 OPERATING CIRCUIT

    6.4.3 FEATURES

    6.4.4 APPLICATIONS

    6.4.5 RS-232 DRIVERS

    6.4.6 RS-232 RECEIVERS

    32

    34

    34

    35

    38

    3939

    40

    40

    40

    41

    7.CIRCUIT DIAGRAM 42

    8. HARDWARE PHOTOGRAPHY

    9.RESULT

    45

    46

    10.CONCLUSION AND SCOPE OF FUTURE WORK 47

  • 8/8/2019 Remote Power Monitor

    7/78

    11. MICROCONTROLLER PROGRAM 48

    12. BIBLIOGRAPHY 71

  • 8/8/2019 Remote Power Monitor

    8/78

    1

    1. INTRODUCTIONWith the electric industry undergoing change, increased attention is being focused

    on power supply reliability and power quality. Power providers and users alike are

    concerned about reliable power, whether the focus is on interruptions and disturbances or

    extended outages. One of the most critical elements in ensuring reliability is monitoring

    power system performance. Monitoring can provide information about power flow and

    demand and help identify the cause of power system disturbances. It can even help identify

    problem conditions on a power system before they cause interruptions or disturbances.

    The implementation of this project is to monitor the power consumed by a model

    organization such a household consumers from a centrally located point. Monitoring the

    power means calculating the power consumed exactly by the user at a given time. The

    power consumed by the user is measured and communicated to the controlling substation

    when ever needed by the person at the sub station. The communication can be of two types

    1. Wired communication like using the existing transmission lines and sending thedata by modulating with high frequency carrier signal or using the existing

    telephone lines.

    2. Wireless communication based on the available technologies like IRcommunication, Bluetooth technology or GSM technology.

    Among these two communications, the one used in our project is wired communication

    which suits best for long distance communication. A microcontroller is equipped at the

  • 8/8/2019 Remote Power Monitor

    9/78

    2

    consumers terminal to measure the power consumed by the user at a given instant. The

    process is not continuous it does this when ever there is a request from the substation

    control person. The power can be on and off to the user from the substation by operating a

    relay connected in series to the user. Whenever there is no supply at the user the

    information can be obtained at the substation. The practical application of the project can

    be implemented along with a data backup for billing and dispatching the bills with out

    manual labor and avoid any disturbances in supply at the user side.

    The project consists of the topics

    1. Power measurement unit2. 89C52 microcontroller3. ADC 08094. Serial communication with the PC

    Power measurement unit consists of the power measurement by using the

    instrument transformers and their features.

    Serial communication with the PC includes the hardware and softwaredescription of how the communication is done using the serial port of a PC

  • 8/8/2019 Remote Power Monitor

    10/78

    3

    2. BLOCK DIAGRAM

    The block diagram consists of Load, current transformer, voltage transformer, 89C52

    microcontroller, ADC 0809, and a differential relay. The household load to be supplied is

    connected in series to the AC supply mains through a switch which is operated by the action

    of a relay. Current transformer is used to measure the current required for the user and the

    voltage transformer is used to measure the voltage of operation for the user. The measured

    values are given to the ADC to convert the analog values to the digital values. These values

    are stored in microcontroller registers and the information is transmitted to the pc when ever

    there is a request for the data from the remote controlling station. Oscillator is provided for

    the ADC and microcontroller for the clock signal and the reference voltage is given for the

    each of the IC used.

  • 8/8/2019 Remote Power Monitor

    11/78

    4

    This supplier side is the basic for the operation of the project; the entire consumer

    side is controlled in accordance with the program written on this supplier side. The supplier

    side (substation) is located remotely at some distance away from the user and the signal is

    sent to the consumer side for data or to control the supply of power to the user. The request

    for information and the power data is received from the user side via RS232.

    Microcontroller is interfaced to the personal computer serial port through MAX23C to

    drive between RS232 and TTL levels.

    3. POWER MEASUREMENT

  • 8/8/2019 Remote Power Monitor

    12/78

    5

    The main aim of the Remote power monitoring is to measure the exact amount of

    power that is consumed by the user at a given instant of time so the power measurement

    unit is essential and is connected on the consumer side. The power is measured by using the

    instrument transformers. Instrument transformers are used for measurement and protective

    application, together with equipment such as meters and relays. Their role in electrical

    systems is of primary importance as they are a means of "stepping down" the current or

    voltage of a system to measurable values, such as 5A or 1A in the case of a current

    transformers or 110V or 100V in the case of a voltage transformer. This offers the

    advantage that measurement and protective equipment can be standardized on a few values

    of current and voltage. The types of instrument transformers available are

    Voltage transformers

    Current transformers

    3.1VOLTAGE TRANSFORMERS

    3.1.1PRINCIPLE OF OPERATION:

    The voltage transformer is one in which "the secondary voltage is substantially

    proportional to the primary voltage and differs in phase from it by an angle which is

    approximately zero for an appropriate direction of the connections." In an "ideal"

    transformer, the secondary voltage vector is exactly opposite and equal to the primary

    voltage vector, when multiplied by the turns ratio. In a "practical" transformer, errors are

  • 8/8/2019 Remote Power Monitor

    13/78

    6

    introduced because some current is drawn for the magnetization of the core and because of

    drops in the primary and secondary windings due to leakage reactance and winding

    resistance. One can thus talk of a voltage error, which is the amount by which the voltage is

    less than the applied primary voltage, and the phase error, which is the phase angle by

    which the reversed secondary voltage vector is displaced from the primary voltage vector.

    3.1.2 TYPICAL TERMS USED FOR SPECIFYING A PT

    a. RATED PRIMARY VOLTAGE: This is the rated voltage of the system whosevoltage is required to be stepped down for measurement and protective purposes.

    b. RATED SECONDARY VOLTAGE: This is the voltage at which the meters and protective devices connected to the secondary circuit of the voltage transformer

    operate.

    c. RATED BURDEN: This is the load in terms of volt-amperes (VA) posed by thedevices in the secondary circuit on the VT. This includes the burden imposed by the

    connecting leads. The VT is required to be accurate at both the rated burden and

    25% of the rated burden.

    d. RATED VOLTAGE FACTOR: Depending on the system in which the VT is tobe used, the rated voltage factors to be specified are different. The table below is

    adopted from Indian and International standards.

  • 8/8/2019 Remote Power Monitor

    14/78

    7

    Rated voltage

    factor

    Rated timeMethod of connecting primary winding in system

    1.2 Continuous Between phases in any network Between transformer

    star-point and earth in any network

    1.2-1.5 Continuous

    for 30 second

    Between phase and earth in an effectively earthed

    neutral system

    1.2-1.9 Continuous

    for 30 second

    Between phase and earth in a non-effectively earthed

    neutral system with automatic fault tripping

    1.2-1.9 Continuous

    for 8 hours

    Between phase and earth in an isolated neutral system

    without automatic fault tripping or in a resonant earthe

    system without automatic fault tripping

    e. TEMPERATURE CLASS OF INSULATION: The permissible temperature riseover the specified ambient temperature. Typically, classes E, B and F.

    f. RESIDUAL VOLTAGE TRANSFORMER (RVT): RVTs are used for residualearth fault protection and for discharging capacitor banks. The secondary residual

    voltage winding is connected in open delta. Under normal conditions of operation,

    there is no voltage output across the residual voltage winding. When there is an

    earth fault, a voltage is developed across the open delta winding which activates the

    relay. When using a three phase RVT, the primary neutral should be earthed, as

  • 8/8/2019 Remote Power Monitor

    15/78

    8

    otherwise third harmonic voltages will appear across the residual winding. 3 phase

    RVTs typically have 5 limb construction.

    3.2CURRENT TRANSFORMERS

    3.2.1 PRINCIPLE OF OPERATION:

    A current transformer is defined as "as an instrument transformer in which the

    secondary current is substantially proportional to the primary current (under normal

    conditions of operation) and differs in phase from it by an angle which is approximately

    zero for an appropriate direction of the connections." This highlights the accuracy

    requirement of the current transformer but also important is the isolating function, which

    means no matter what the system voltage the secondary circuit need be insulated only for a

    low voltage.

    The current transformer works on the principle of variable flux. In the "ideal"

    current transformer, secondary current would be exactly equal (when multiplied by the

    turns ratio) and opposite to the primary current. But, as in the voltage transformer, some of

    the primary current or the primary ampere-turns is utilized for magnetizing the core, thus

    leaving less than the actual primary ampere turns to be "transformed" into the secondary

    ampere-turns. This naturally introduces an error in the transformation. The error is

    classified into two-the current or ratio error and the phase error.

  • 8/8/2019 Remote Power Monitor

    16/78

    9

    4. ADC 0809

    The ADC0809, data acquisition component is a monolithic CMOS device with an 8-

    bit analog-to-digital converter, 8-channel multiplexer and microprocessor compatible control

    logic. The 8-bit A/D converter uses successive approximation as the conversion technique.

    The converter features a high impedance chopper stabilized comparator, a 256R voltage

    divider with analog switch tree and a successive approximation register. The 8-channel

    multiplexer can directly access any of 8-single-ended analog signals. The device eliminates

    the need for external zero and full-scale adjustments. Easy interfacing to microprocessors is

    provided by the latched and decoded multiplexer address inputs and latched TTL TRI-

    STATE outputs.

    The design of the ADC0809 has been optimized by incorporating the most desirable

    aspects of several A/D conversion techniques. The ADC0809 offers high speed, high

    accuracy, minimal temperature dependence, excellent long-term accuracy and repeatability,

    and consumes minimal power. These features make this device ideally suited to applications

    from process and machine control to consumer and automotive applications

  • 8/8/2019 Remote Power Monitor

    17/78

    10

    4.1 PIN CONFIGURATION

    4.2 FEATURES

    Easy interface to all microprocessors Operates ratio metrically or with 5 VDC or analog span adjusted voltage

    reference

    No zero or full-scale adjust required 8-channel multiplexer with address logic 0V to 5V input range with single 5V power supply Outputs meet TTL voltage level specifications Standard hermetic or molded 28-pin DIP package 28-pin molded chip carrier package

  • 8/8/2019 Remote Power Monitor

    18/78

    11

    4.3 KEY SPECIFICATIONS

    Resolution 8 Bits Total Unadjusted Error 12 LSB and 1 LSB Single Supply 5V DC Low Power 15 mW Conversion Time 100 s

    4.4 BLOCK DIAGRAM

  • 8/8/2019 Remote Power Monitor

    19/78

    12

    4.5 FUNCTIONAL DESCRIPTION

    4.5.1 MULTIPLEXER

    The device contains an 8-channel single-ended analog signal multiplexer. A

    particular input channel is selected by using the address decoder. Table shows the input

    states for the address lines to select any channel. The address is latched into the decoder on

    the low-to-high transition of the address latch enable signal.

    4.5.2 CONVERTER CHARACTERISTICS

    THE CONVERTER

    The heart of this single chip data acquisition system is its 8-bit analog-to-digital

    converter. The converter is designed to give fast, accurate, and repeatable conversions over a

    wide range of temperatures. The converter is partitioned into 3 major sections: the 256R

    ladder network, the successive approximation register, and the comparator. The converters

  • 8/8/2019 Remote Power Monitor

    20/78

    13

    digital outputs are positive true. The 256R ladder network approach was chosen over the

    conventional R/2R ladder because of its inherent monotonicity, which guarantees no missing

    digital codes. Monotonicity is particularly important in closed loop feedback control

    systems. A non-monotonic relationship can cause oscillations that will be catastrophic for the

    system. Additionally, the 256R network does not cause load variations on the reference

    voltage.

    The bottom resistor and the top resistor of the ladder network in are not the same

    value as the remainder of the network. The difference in these resistors causes the output

    characteristic to be symmetrical with the zero and full-scale points of the transfer curve. The

    first output transition occurs when the analog signal has reached +12 LSB and succeeding

    output transitions occur every 1 LSB later up to full-scale.

    The successive approximation register (SAR) performs 8 iterations to approximate

    the input voltage. For any SAR type converter, n-iterations are required for an n-bit

    converter. In the ADC0809, the approximation technique is extended to 8 bits using the

    256R network. The A/D converters successive approximation register (SAR) is reset on the

    positive edge of the start conversion start pulse. The conversion is begun on the falling edge

    of the start conversion pulse. A conversion in process will be interrupted by receipt of a new

    start conversion pulse. Continuous conversion may be accomplished by tying the end of

    conversion (EOC) output to the SC input. If used in this mode, an external start conversion

    pulse should be applied after power up. End-of-conversion will go low between 0 and 8

    clock pulses after the rising edge of start conversion.

  • 8/8/2019 Remote Power Monitor

    21/78

    14

    5. 89C52 MICROCONTROLLER

    5.1 INTRODUCTION

    Micro controller is a true computer on a chip. Microprocessors are intended to be

    general-purpose digital computers whereas micro controllers are intended to be special

    purpose digital controllers. Generally microprocessors contain a CPU, memory- addressing

    units and interrupt handling circuits. Micro controllers have these features as well as timers,

    parallel and serial I/O and internal RAM and ROM. Like the microprocessor, a micro

    controller is a general-purpose device, but one that is meant to read data, and control its

    environmental based on those calculations.

    The contrast between a micro controller and a microprocessor is best exemplified by

    the fact that microprocessors have many operational codes for moving data from external

    memory to CPU; microcontrollers may have one or two. Microprocessors may have one or

    two types of bit-handling instructions; micro controllers will have many. The microprocessor

    is concerned with the rapid movement of code and data from external addresses to the chip;

    the microcontroller is concerned with rapid movements of bits with in the chip. The micro

    controller can function as a computer with the addition of no external digital parts; the

    microprocessor must have many additional parts to be operational.

    Generally 4-bit microcontrollers are intended for use in large volumes as true 1-chip

    computers. Typical applications consist of appliances and toys. Eight bit micro controllers

    represent a transition zone between the dedicated, high volume, 4-bit micro controllers and

  • 8/8/2019 Remote Power Monitor

    22/78

    15

    the high performance, 16 and 32-bit units. Eight bit micro controllers are very useful word

    size for small computing tasks. 16-bit controllers have also been designed to take the

    advantage of high level programming languages in the expectation that very little assembly

    language programming will be done when employing these controllers in sophisticated

    applications. 32 bit controllers are also used in high speed control and signal processing

    applications.

    5.2 DESCRIPTION

    The AT89C52 is a low-power, high-performance CMOS 8-bit microcomputer with

    8K bytes of Flash programmable and erasable read only memory (PEROM). The device is

    manufactured using Atmels high-density nonvolatile memory technology and is compatible

    with the industry-standard MCS-51 instruction set and pin out. The on-chip Flash allows the

    program memory to be reprogrammed in-system or by a conventional nonvolatile memory

    programmer. By combining a versatile 8-bit CPU with Flash on a monolithic chip, the Atmel

    AT89C52 is a powerful microcomputer which provides a highly-flexible and cost-effective

    solution to many embedded control applications.

    5.3 FEATURES

    1. Compatible with MCS-51 Products2. 8K Bytes of In-System Reprogrammable Flash Memory

    (Endurance: 1,000 Write/Erase Cycles)

    3. Fully Static Operation: 0 Hz to 24 MHz

  • 8/8/2019 Remote Power Monitor

    23/78

    16

    4. Three-level Program Memory Lock5. 256 x 8-bit Internal RAM6.

    32 Programmable I/O Lines

    7. Two 16-bit Timer/Counters8. Six Interrupt Sources9. Programmable Serial Channel10.Low-power Idle and Power-down Modes5.4 PIN DIAGRAM:

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    15

    16

    17

    18

    19

    20

    40

    39

    38

    37

    36

    35

    34

    33

    32

    31

    30

    29

    28

    27

    26

    25

    24

    23

    22

    21

    ATMEL

    8

    9

    C

    5

    2

    (T2) P1.0

    (T2 EX) P1.1

    P1.2

    P1.3

    P1.4

    P1.5

    P1.6

    P1.7

    R S T

    (RXD) P3.0

    (TXD) P3.1

    (IN T0) P 3.2

    (IN T1) P 3.3

    (T0) P3.4

    (T1) P3.5

    (W R) P3.6

    (RD) P3.7

    X TA L 2

    X TA L 1

    G N D P 2.0(A 8 )

    P2.1(A9)

    P2.2(A10)

    P2.3(A11)

    P2.4(A12)

    P2.5(A13)

    P2.6(A14)

    P2.7(A15)

    V C C

    P0.0(AD0)

    P0.1(AD1)

    P0.2(AD2)

    P0.3(AD3)

    P0.4(AD4)

    P0.5(AD5)

    P0.6(AD6)

    P0.7(AD7)

    E A / V P P

    A L E / P R O G

    P S E N

  • 8/8/2019 Remote Power Monitor

    24/78

    17

    5.5 PIN CONFIGURATIONS

    The AT89C52 provides the following standard features: 4K bytes of Flash, 128 bytes

    of RAM, 32 I/O lines, two 16-bit timer/counters, five vector two-level interrupt architecture,

    a full duplex serial port, and on chip oscillator and clock circuitry. IN addition, the AT89C52

    is designed with static logic for operation down to zero frequency and supports two software

    selectable power selecting modes. The idle Mode stops the CPU while allowing the RAM,

    timer/counters, serial port and interrupt system to continue functioning. The Power down

    Mode saves the RAM contents but freezes the oscillator all other chip functions until the

    next hardware reset.

    5.6 PIN DESCRIPTION

    VCC

    Supply voltage.

    GND

    Ground.

    Port 0

    Port 0 is an 8-bit open-drain bi-directional I/O port. As an output port, each pin can

    sink eight TTL inputs. When 1s are written to port 0 pins, the pins can be used as high

    impedance inputs. Port 0 may also be configured to be the multiplexed low order

  • 8/8/2019 Remote Power Monitor

    25/78

    18

    address/data bus during accesses to external program and data memory. In this mode P0 has

    internal pull ups. Port 0 also receives the code bytes during Flash programming, and outputs

    the code bytes during program verification. External pull ups are required during program

    verification.

    Port 1

    Port 1 is an 8-bit bi-directional I/O port with internal pull ups. The Port 1 output

    buffers can sink/source four TTL inputs. When 1s are written to Port 1 pins they are pulled

    high by the internal pull ups and can be used as inputs. As inputs, Port 1 pins that are

    externally being pulled low will source current (IIL) because of the internal pull ups. Port 1

    also receives the low-order address bytes during Flash programming and verification.

    Port 2

    Port 2 is an 8-bit bi-directional I/O port with internal pull ups. The Port 2 output buffers can

    sink/source four TTL inputs. When 1s are written to Port 2 pins they are pulled high by the

    internal pull ups and can be used as inputs. As inputs, Port 2 pins that are externally being

    pulled low will source current (IIL) because of the internal pull ups. Port 2 emits the high-

    order address byte during fetches from external program memory and during accesses to

    external data memory that uses 16-bit addresses (MOVX @ DPTR). In this application, it

    uses strong internal pull-ups when emitting 1s. During accesses to external data memory that

    uses 8-bit addresses (MOVX @ RI); Port 2 emits the contents of the P2 Special Function

  • 8/8/2019 Remote Power Monitor

    26/78

    19

    Register. Port 2 also receives the high-order address bits and some control signals during

    Flash programming and verification.

    Port 3

    Port 3 is an 8-bit bi-directional I/O port with internal pull ups. The Port 3 output

    buffers can sink/source four TTL inputs. When 1s are written to Port 3 pins they are pulled

    high by the internal pull ups and can be used as inputs. As inputs, Port 3 pins that are

    externally being pulled low will source current (IIL) because of the pull ups. Port 3 also

    serves the functions of various special features of the AT89C51 as listed below:

    Port 3 also receives some control signals for Flash programming and verification.

    RST

    Reset input. A high on this pin for two machine cycles while the oscillator is running

    resets the device.

  • 8/8/2019 Remote Power Monitor

    27/78

    20

    ALE/PROG

    Address Latch Enable output pulse for latching the low byte of the address during

    accesses to external memory. This pin is also the program pulse input (PROG) during Flash

    programming. In normal operation ALE is emitted at a constant rate of 1/6 the oscillator

    frequency, and may be used for external timing or clocking purposes. Note, however, that

    one ALE pulse is skipped during each access to external Data Memory. If desired, ALE

    operation can be disabled by setting bit 0 of SFR location 8EH. With the bit set, ALE is

    active only during a MOVX or MOVC instruction.

    PSEN

    Program Store Enable is the read strobe to external program memory. When the

    AT89C51 is executing code from external program memory, PSEN is activated twice each

    machine cycle, except that two PSEN activations are skipped during each access to external

    data memory.

    EA/VPP

    External Access Enable:

    EA must be strapped to GND in order to enable the device to fetch code from

    external program memory locations starting at 0000H up to FFFFH. Note, however, that if

    lock bit 1 is programmed, EA will be internally latched on reset. EA should be strapped to

  • 8/8/2019 Remote Power Monitor

    28/78

    21

    VCC for internal program executions. This pin also receives the 12-volt programming enable

    voltage (VPP) during Flash programming, for parts that require 12-volt VPP.

    XTAL1

    Input to the inverting oscillator amplifier and input to the internal clock operating

    circuit.

    XTAL2

    Output from the inverting oscillator amplifier.

    OSCILLATOR CHARACTERISTICS

    XTAL1 and XTAL2 are the input and output, respectively, of an inverting amplifier

    which can be configured for use as an on-chip oscillator, as shown in Figure 1. Either a

    quartz crystal or ceramic resonator may be used. To drive the device from an external clock

    source, XTAL2 should be left unconnected while XTAL1 is driven as shown in Figure.

    There are no requirements on the duty cycle of the external clock signal, since the input to

    the internal clocking circuitry is through a divide-by-two flip-flop, but minimum and

    maximum voltage high and low time specifications must be observed.

  • 8/8/2019 Remote Power Monitor

    29/78

    22

    IDLE MODE

    In idle mode, the CPU puts itself to sleep while all the on chip peripherals remain

    active. The mode is invoked by software. The content of the on-chip RAM and all the special

    functions registers remain unchanged during this mode. The idle mode can be terminated by

    any enabled interrupt or by a hardware reset. It should be noted that when idle is terminated

    by a hardware reset, the device normally resumes program execution, from where it left off,

    up to two machine cycles before the internal reset algorithm takes control. On-chip hardware

    inhibits access to internal RAM in this event, but access to the port pins is not inhibited. To

    eliminate the possibility of an unexpected write to a port pin when Idle is terminated by

    reset, the instruction following the one that invokes Idle should not be one that writes to a

    port pin or to external memory.

  • 8/8/2019 Remote Power Monitor

    30/78

    23

    POWER DOWN MODE:

    In the power-down mode, the oscillator is stopped, and the instruction that invokes

    power-down is the last instruction executed. The on-chip RAM and Special Function

    Registers retain their values until the power-down mode is terminated. The only exit from

    power-down is hardware reset. Reset redefines the SFRs but does not change the on-chip

    RAM. The reset should not be activated before VCC is restored to its normal operating level

    and must be held active long enough to allow the oscillator to restart and stabilize.

    PROGRAM MEMORY LOCK BITS:

    On the chip are three lock bits which can be left un programmed (U) or can be

    programmed (P) to obtain the additional features listed in the table below. When lock bit 1 is

    programmed, the logic level at the EA pin is sampled and latched during reset. If the device

    is powered up without a reset, the latch initializes to a random value, and holds that value

    until reset is activated. It is necessary that the latched value of EA be in agreement with the

    current logic level at that pin in order for the device to function properly.

    5.7 MEMORY

    The 8051 has three very general types of memory. To effectively program the 8051 it

    is necessary to have a basic understanding of these memory types.

    The memory types are illustrated in the following graphic. They are:

  • 8/8/2019 Remote Power Monitor

    31/78

    24

    1. on-chip memory2. External Code Memory3.

    External RAM

    4. Special function register memory

    5.7.1 ON-CHIP MEMORY

    This refers to any memories (Code, RAM or other) that physically exist on the

    microcontroller itself. On- Chip memory can be of several types.

    The 8051 has a bank of 128 bytes if Internal RAM. This internal RAM available and

    it is also the most flexible in terms of reading, writing, and modifying its contents. Internal

    RAM is volatile, so when the 8051 is rest this memory is cleared.

    The first 8 bytes (00h-07h) are register bank 0. By manipulating certain SFRs, a

    program may choose to use register banks 1, 2 or 3. These alternative register banks are

    located in internal RAM in addresses 08h through 1Fh. Bit memory also lives and is part of

    internal RAM. The 80bytes remaining of Internal RAM, from addresses 30h through 7Fh,

    may be used by user variables that need to be accessed frequently or at a high speed. This

    area is also utilized by the microcontroller as a storage area for the operating stack. This fact

    severely limits the 8051s stack since, as illustrated in the memory map, the area reserved for

    the stack is only 80 bytes and usually it is less since this 80 bytes has to be shared between

    stack and user.

  • 8/8/2019 Remote Power Monitor

    32/78

    25

    5.7.2 EXTERNAL CODE MEMORY

    This is code (or program) memory that resides off-chip. This is often in the form of

    an external (EPROM). Code Memory is the memory that holds the actual 8051 program that

    is to be run. This memory is limited to 64K and comes in many shapes ands sizes. Code

    Memory may be found on-chip, either burned in to the microcontroller as ROM or EPROM.

    Code may also be stored completely off-chip in an external ROM or, more commonly, an

    external EPROM. Flash RAM is also another popular method of storing program. Various

    combinations of these memory types may also be used-that is to say, it is possible to have 4K

    of code memory on-chip and 64K of code memory off-chip in an EPROM.

    When the program is stored in-chip the 64K maximum is often reduced to 4K, 8K or

    16K. This varies depending on the version of the chip that is being used. Each version offers

    how much ROM/EPROM spacer the chip has.

    However, code memory is most commonly implemented as off-chip EPROM. This is

    especially true in low-cost development systems.

    5.7.3 EXTERNAL RAM

    This RAM memory resides off-chip. This is often in the form of standard static RAM

    or flash RAM.

  • 8/8/2019 Remote Power Monitor

    33/78

    26

    As an obvious of Internal RAM, the 8051 also supports what is called External RAM.

    As the name suggests, External RAM is any random access memory which is found

    off-chip. Since the memory is off-chip it is not as flexible in terms of accessing, and is also

    slower. For example, to increment an Internal RAM location by 1 requires only 1 instruction

    and 1 instruction cycle. To increment a 1-byte value stored in External RAM requires 4

    instructions and 7 instruction cycles. In this case, external memory is 7 t imes slower.

    What external RAM loses in speed and flexibility it gains in quantity. While internal

    RAM is limited to 128 bytes (256 bytes with an 8052), the 8051 supports External RAM up

    to 64K.

    5.7.4 SPECIAL FUNCTION REGISTER (SFR) MEMORY

    Special Function Register (SFRs) are areas of memory that control specific

    functionality of the 8051 processor. For example, four SFRs permit access to the 8051s 32

    input/output lines. Another SFR allows a program to read or write to the 8051s serial port.

    Other SFRs allow the user to set the serial baud rate, control and access timers, and configure

    the 8051s interrupt system.

  • 8/8/2019 Remote Power Monitor

    34/78

    27

    5.8 ADDRESSING MODES

    An addressing mode refers to how you are addressing given memory location. In

    summary, the addressing modes are as follows, with an example of each:

    Immediate Addressing MOV A,#20H

    Direct Addressing MOVA,30H

    In Direct Addressing MOV A,@R0

    External Direct MOVX A,@DPTR

    Code Indirect MOVC @A+DPTR

    Each of these addressing modes provides important flexibility.

    5.8.1 IMMEDIATE ADDRESSING

    Immediate Addressing is so-named because the value to be stored in memory

    immediately follows the operation code in memory. That is to say, the instruction itself

    dictates what value will be stored in memory. For example, the instruction:

    MOV A, #20H

    This instruction uses Immediate Addressing because the Accumulator will be loaded

    with the value that immediately follows; in this case 20 (hexadecimal). Immediate

    addressing is very fast since the value to be loaded is included in the instruction. However,

    since the value to be loaded is fixed at compile-time it is not very flexible.

  • 8/8/2019 Remote Power Monitor

    35/78

    28

    5.8.2 DIRECT ADDRESSING

    Indirect Addressing is a very powerful addressing which in many cases provides an

    exceptional level of flexibility. Indirect Addressing is also only way to access the extra 128

    bytes of Internal RAM found on an 8052. Indirect Addressing appears as follows:

    MOV A,@R0

    5.8.3 EXTERNAL INDIRECT

    External memory can also be accessed using a form of indirect addressing which I

    call External Indirect Addressing. This form of addressing is usually only used in relatively

    small projects that have a very small amount of external RAM. An example of this

    addressing mode is

    Eg: MOVX @R0, A.

    5.9 PROGRAMMING THE FLASH MEMORY

    The AT89C52 is normally shipped with the on chip flash memory array in the

    erased state (that is, contents FFH) and ready to be programmed. The programming interface

    accepts either a high voltage (12-volt) or a low voltage (VCC) program enable signal. The low

    voltage programming mode provides enable signal. The low voltage programming mode

    provides convenient way to program the AT89C52 inside the users system, while the high-

    voltage programming mode is compatible with Flash or EPROM programmers. The

  • 8/8/2019 Remote Power Monitor

    36/78

    29

    AT89C52 is shipped with either the high voltage or low voltage programming mode enabled.

    The AT89C52 code memory array is programmed byte by byte in either programming mode.

    The program any non blank byte in the chip Flash Memory, the entire memory must be

    erased using the Chip Erase Mode.

    5.10 PROGRAMMING ALGORITHM:

    Before programming the AT89C52, the address, the data and control signals should

    be set up according to the flash programming mode table. To program the AT89C52, take

    the following steps:

    1. Input the desired memory location on the address line2. Input the appropriate data b byte on the data lines.3. Activate the correct combination of control signals.4. Raise EA/VPP to 12V for the high voltage programming mode.5. Pulse ALE/PROG once to program a byte in the Flash array or the lock bits. The

    byte write cycle is self timed and typically takes no more than 1.5ms. repeat steps 1

    through 5, changing the address and data for the entire array or until the end of the

    object file is reached.

    DATA POLLING:

    The AT89C52 features Data Polling to indicate the end of a write cycle. During a

    write cycle, an attempted read of the last byte written will result in the complement of the

  • 8/8/2019 Remote Power Monitor

    37/78

    30

    written datum on P0.7. Once the write cycle has been completed, true data are valid on all

    outputs, and the next cycle may begin. Data polling may begin any time after a write cycle

    had been initiated.

    Ready/Busy:

    The progress of byte programming can also be monitored by the RDY/BSY output

    signal. P3.4 is pulled low after ALE goes high during programming to indicate BUSY.P3.4.

    is pulled high again when programming is done to indicate READY.

    Program Verify:

    If the lock bits LB1 and LB2 have not been programmed, the programmed code data

    can be read via the address and data lines for verification. The lock bits cannot be verified

    directly. Verification of the lock bits is achieved by observing that their features are enabled.

    Chip Erase:

    The entire Flash array is erased electrically by using the proper combination of

    control signals and by holding ALE/PROG low for 10ms. The code array is written with

    all1s. The chip erase operation must be executed before the code memory can be re-

    programmed.

  • 8/8/2019 Remote Power Monitor

    38/78

    31

    READING THE SIGNATURE BYTES:

    The signature bytes are read by the same procedure as a normal verification of locations

    030H, 031H and 032H except that P3.6 and P3.7 must be pulled to a logic low. The values

    returned are as follows.

    (030H)=1EH indicates manufactured by Atmel

    (031H)=51H indicates 89C51

    (032H)=FFH indicates 12V programming

    (032H)=05H indicated 5V programming

    PROGRAMMING INTERFACE:

    Every code byte in the Flash array can be written and the entire array can be erased

    by using the appropriate combination of control signals. The write operation cycle is self

    timed and once initiated, will automatically time itself to completion

  • 8/8/2019 Remote Power Monitor

    39/78

    32

    6. SERIAL COMMUNICATION

    Serial communication is a popular means of transmitting data between a computer

    and a peripheral device such as a programmable instrument or even another computer. Serial

    communication uses a transmitter to send data, one bit at a time, over a single

    communication line to a receiver. You can use this method when data transfer rates are low

    or you must transfer data over long distances. Serial communication is popular because most

    computers have one or more serial ports, so no extra hardware is needed other than a cable to

    connect the instrument to the computer or two computers together

    Serial communication requires that you specify the following four parameters:

    The baud rate of the transmission The number of data bits encoding a character The sense of the optional parity bit The number of stop bits

    Each transmitted character is packaged in a character frame that consists of a single

    start bit followed by the data bits, the optional parity bit, and the stop bit or bits. Figure

    shows a typical character frame.

  • 8/8/2019 Remote Power Monitor

    40/78

    33

    Baud rate is a measure of how fast data are moving between instruments that use

    serial communication. RS-232 uses only two voltage states, called MARK and SPACE. In

    such a two-state coding scheme, the baud rate is identical to the maximum number of bits of

    information, including control bits, that are transmitted per second. MARK is a negative

    voltage, and SPACE is positive. Figure 2 shows how the idealized signal looks on an

    oscilloscope. The truth table for RS-232: Signal>3V=0 Signal>-3V=1. The output signal

    level usually swings between +12 V and -12 V. The dead area between +3 V and -3 V is

    designed to absorb line noise.

    A start bit signals the beginning of each character frame. It is a transition from

    negative (MARK) to positive (SPACE) voltage. Its duration in seconds is the reciprocal of

    the baud rate. If the instrument is transmitting at 9,600 baud, the duration of the start bit and

    each subsequent bit is about 0.104 ms.

    Data bits are transmitted upside down and backwards. That is, inverted logic is used,

    and the order of transmission is from least significant bit (LSB) to most significant bit

  • 8/8/2019 Remote Power Monitor

    41/78

    34

    (MSB). To interpret the data bits in a character frame, you must read from right to left and

    read 1 for negative voltage and 0 for positive voltage. An optional parity bit follows the data

    bits in the character frame. The parity bit, if present, also follows inverted logic, 1 for

    negative voltage and 0 for positive voltage. This bit is included as a simple means of error

    handling. You specify ahead of time whether the parity of the transmission is to be even or

    odd. If the parity is chosen to be odd, the transmitter then sets the parity bit in such a way as

    to make an odd number of ones among the data bits and the parity bit. This transmission uses

    odd parity. There are five ones among the data bits, already an odd number, so the parity bit

    is set to 0.

    6.1 SPEED OF TRANSMISSION:

    Knowing the structure of a character frame and the meaning of baud rate as it applies

    to serial communication, you can calculate the maximum transmission rate, in characters per

    second, for a given communication setting. This rate is just the baud rate divided by the bits

    per frame. This is the maximum character transmission rate. The hardware on one end or the

    other of the serial link might not be able to reach these rates, for various reasons. There are

    many different recommended standards of serial port communication, the most common

    types is as following

    6.2 RS-232

    The RS-232 is a standard developed by the Electronic Industries Association (EIA)

    and other interested parties, specifying the serial interface between Data Terminal Equipment

  • 8/8/2019 Remote Power Monitor

    42/78

    35

    (DTE) and Data Communications Equipment (DCE). It is commonly used in computer serial

    ports. The RS-232 standard includes electrical signal characteristics (voltage levels),

    interface mechanical characteristics (connectors), functional description of interchange

    circuits (the function of each electrical signal), and some recipes for common kinds of

    terminal-to-modem connections. RS-232C is a long-established standard ("C" is the current

    version) that describes the physical interface and protocol for relatively low-speed serial data

    communication between computers and related devices. Parts of this standard have been

    adopted (with various degrees of fidelity) for use in serial communications between

    computers and printers, modems, and other equipment. The serial ports on standard IBM-

    compatible personal computers follow RS-232. Somewhere in your PC, typically on a

    Universal Asynchronous Receiver/Transmitter (UART) chip on your motherboard, the data

    from your computer is transmitted to a serial device from its Data Terminal Equipment

    (DTE) interface. Since data in your computer flows along parallel circuits and serial devices

    can handle only one bit at a time, the UART chip converts the groups of bits in parallel to a

    serial stream of bits. As your PC's DTE agent, it also communicates with the serial device,

    which, in accordance with the RS-232C standard, has a complementary interface called the

    Data Communications Equipment (DCE) interface.

    6.3 RS-232 CABLING

    Devices that use serial cables for their communication are split into two categories.

    These are DCE and DTE. DCE are devices such as a modem, TA adapter, plotter, and so on,

    while DTE is a computer or terminal. RS-232 serial ports come in two sizes, the D-Type 25-

  • 8/8/2019 Remote Power Monitor

    43/78

    36

    pin connector and the D-Type 9-pin connector. Both of these connectors are male on the

    back of the PC. Thus, you require a female connector on the device. Table 1 shows the pin

    connections for the 9-pin Type connectors.

    Function Signal PIN DTE DCE

    Data

    TxD 3 Output Input

    RxD 2 Input Output

    Handshake

    RTS 7 Output Input

    CTS 8 Input Output

    DSR 6 Input Output

    DCD 1 Input Output

    STR 4 Output Input

    Common Com 5 -- --

    Other RI 9 Output Input

  • 8/8/2019 Remote Power Monitor

    44/78

    37

    1. The TD (transmit data) wire is the one through which data from a DTE device istransmitted to a DCE device. This name can be deceiving, because this wire is used

    by a DCE device to receive its data. The TD line is kept in a mark condition by the

    DTE device when it is idle. The RD (receive data) wire is the one on which data is

    received by a DTE device, and the DCE device keeps this line in a mark condition

    when idle.

    2. RTS stands for Request To Send. This line and the CTS line are used when"hardware flow control" is enabled in both the DTE and DCE devices. The DTE

    device puts this line in a mark condition to tell the remote device that it is ready and

    able to receive data. If the DTE device is not able to receive data (typically because

    its receive buffer is almost full), it will put this line in the space condition as a

    signal to the DCE to stop sending data. When the DTE device is ready to receive

    more data (i.e. after data has been removed from its receive buffer), it will place this

    line back in the mark condition. The complement of the RTS wire is CTS, which

    stands for Clear To Send. The DCE device puts this line in a mark condition to tell

    the DTE device that it is ready to receive the data. Likewise, if the DCE device is

    unable to receive data, it will place this line in the space condition. Together, these

    two lines make up what is called RTS/CTS or "hardware" flow control. DTR

    stands for Data Terminal Ready. Its intended function is very similar to the RTS

    line. DSR (Data Set Ready) is the companion to DTR in the same way that CTS is

    to RTS. Some serial devices use DTR and DSR as signals to simply confirm that a

    device is connected and is turned on. The Software Wedge sets DTR to the mark

  • 8/8/2019 Remote Power Monitor

    45/78

    38

    state when the serial port is opened and leaves it in that state until the port is closed.

    The DTR and DSR lines were originally designed to provide an alternate method of

    hardware handshaking. It would be pointless to use both RTS/CTS and DTR/DSR

    for flow control signals at the same time. Because of this, DTR and DSR are rarely

    used for flow control.

    3. CD stands for Carrier Detect. Carrier Detect is used by a modem to signal that ithas a made a connection with another modem, or has detected a carrier tone.

    4. The last remaining line is RI or Ring Indicator. A modem toggles the state of thisline when an incoming call rings your phone.

    The Carrier Detect (CD) and the Ring Indicator (RI) lines are only available in connections

    to a modem. Because most modems transmit status information to a PC when either a

    carrier signal is detected (i.e. when a connection is made to another modem) or when the

    line is ringing, these two lines are rarely used.

    6.4 MAX 232C

    MAX 232C is used to interface the transmitter and receiver circuit to the PC. It is

    used to match between the RS232C and TTL levels. The MAX232 is a dual driver/receiver

    that includes a capacitive voltage generator to supply RS232C voltage levels from a single

    5V supply. Each receiver converts RS232C inputs to 5V TTL/CMOS levels. These receivers

    have a typical threshold of 1.3 V, a typical hysteresis of 0.5 V, and can accept 30V inputs.

    Each driver converts TTL/CMOS input levels into RS232C levels.

  • 8/8/2019 Remote Power Monitor

    46/78

    39

    6.4.1 LOGIC DIAGRAM:

    6.4.2 OPERATING CIRCUIT:

  • 8/8/2019 Remote Power Monitor

    47/78

    40

    6.4.3 FEATURES:

    Meets or Exceeds RS232C Operates From a Single 5-V Power Supply with 1.0 microF Charge-

    Pump Capacitors

    Operates Up To 120 kbit/s Two Drivers and Two Receivers 30-V Input Levels Low Supply Current of 8 mA Typical

    6.4.4 APPLICATIONS

    RS232C Battery-Powered Systems Terminals Modems Computers

    6.4.5 RS-232 DRIVERS

    The typical driver output voltage swing is 8V when loaded with a nominal 5k RS-

    232 receiver and VCC = +5V. Output swing is guaranteed to meet the RS-232C

    specification, which calls for 5V minimum driver output levels under worst-case

  • 8/8/2019 Remote Power Monitor

    48/78

    41

    conditions. These include a minimum 3k load, VCC = +4.5V, and maximum operating

    temperature. Unloaded driver output voltage ranges from (V+ -1.3V) to (V- +0.5V). Input

    thresholds are both TTL and CMOS compatible. The MAX232 has both a receiver three-

    state control line and a low-power shutdown control.

    6.4.6 RS-232 RECEIVERS:

    RS-232C specifications define a voltage level greater than 3V as logic 0, so all

    receivers invert. Input thresholds are set at 0.8V and 2.4V, so receivers respond to TTL level

    inputs as well as RS-232C levels. The receiver inputs withstand an input overvoltage up to

    25V and provide input terminating resistors with nominal 5k values. The receiver input

    hysteresis is typically 0.5V with a guaranteed minimum of 0.2V.

  • 8/8/2019 Remote Power Monitor

    49/78

    42

    7. CIRCUIT DIAGRAM

    The above figure shows the circuit diagram for the consumer side. A relay operated

    switch is connected in series with the load. The switch is used to switch on and off the

    power. By the relay is initially in on state and whenever the voltage across its terminals

    changes the relay senses the voltage and trips which in turns closes the switch. The relay is

    connected to the port of the microcontroller through a transistor and zener diode to drive the

    relay. The current transformer primary is connected to the load in series to the mains and the

  • 8/8/2019 Remote Power Monitor

    50/78

    43

    secondary is connected across the variable resistance to change the measured value to the

    close actual value. The potential transformer primary is connected in parallel to the load to

    measure the applied voltage and the secondary is connected to the variable resistance to

    adjust the measured value to the close accurate value. The outputs of this are given to the

    ADC analog input pins. A 555 timer is connected in astable multivibrator mode and is given

    as clock signal to the ADC. The digital outputs are given as inputs to the microcontroller

    port. The control pins of the ADC are given from the microcontroller port to select the input

    to be received. The voltage and current measured are received in accordance to the inputs

    given to the status pins A, B, C by the controller. The ADC starts the conversion at the end

    of the pulse Start and sends data at the end of the pulse EOC these are also connected to the

    port of the microcontroller. The microcontroller is provided with a quartz crystal to provide

    the clock signal, the clock frequency is changed by the capacitors connected to the crystal the

    operating frequency in this circuit is 11.0592MHz. A series combination of the resistor and

    capacitor is taken and the capacitor voltage is given as the reset logic to the 9 th pin of the

    microcontroller. The 10th pin of the microcontroller is the RXD pin is connected to the

    receiver data pin of RS232. The data from the RXD is stored internally for further

    processing. The 11th pin of the microcontroller is the TXD pin is connected to the RS232

    which transmits the data from the microcontroller. The microcontroller baud rate is set in

    accordance to the frequency of the 555 timer to ensure consistency of data. Thus data is

    transmitted from the microcontroller at a preset frequency and the request for data is received

    by the microcontroller connected to the port and the further processing is done as per the

    code written to calculate the power by taking the correction factors in to consideration.

  • 8/8/2019 Remote Power Monitor

    51/78

    44

    The computer is programmed so as to send requests for data and receive data via the

    serial port. The work at TTL voltage levels and the computer works at RS232C voltage

    levels. So to bridge this voltage variation MAX 232C is used which is driver cum receiver.

    The driver is connected to the IR transmitter and the receiver is connected to the IR receiver.

    The data from data pin of IR receiver is given to the computer and displayed on the screen.

    IR transmitter is connected to the computer and the program is written to send the data via

    the serial port to the IR transmitter to send data at a given baud rate. The oscillator is

    connected to the transmitter to match the transmission with the baud rate. The oscillator used

    is 555 timer using astable multivibrator.

  • 8/8/2019 Remote Power Monitor

    52/78

    45

    8. HARDWARE PHOTOGRAPHY

  • 8/8/2019 Remote Power Monitor

    53/78

    46

    9. RESULT

    The consumer side is connected to the supply and power is given to the user from the

    ac supply mains and the software run on the system is run. Then a menu is displayed on the

    screen to select the operation to be done. We can select the buttons to switch on and off the

    power and to know the power consumed and the program written in the pc for maximum

    detecting the power thefts. Here the obtained power is compared with the maximum power

    and if it is more than the maximum power then we can say that the power is being theft.

    Thus the monitoring is done using the PC.

  • 8/8/2019 Remote Power Monitor

    54/78

    47

    10. CONCLUSIONS AND SCOPE OF FUTURE WORK

    The ability to remotely monitor and/or control power at the rack level can provide a

    huge return on investment by providing savings in both man hours and downtime. Remote

    monitoring capabilities eliminate the need for manual power audits as well as provide

    immediate alerts to potential problems. Remote control allows for quick response and

    recovery of stalled hardware either down the hall or across the country. This ability can save

    not only travel costs but minimize costly downtime.

    The project uses a serial communication technique which has got disadvantages like

    loss of data and speed of communication is also less so the more advantageous parallel

    communication technique can be used. The wireless technology used is IR communication

    which can be used only for short distances ranging up to some meters. So, available

    techniques like Bluetooth technology and the GSM technology can be used. The IR

    communication fails whenever there is a disturbance or an obstacle in the path from the

    transmitter to the receiver so an obstacle detector can be used to avoid this. Also an internet

    connection can be enabled to the system so as to provide backup central location or software

    extension can be written to provide a data backup.

  • 8/8/2019 Remote Power Monitor

    55/78

    48

    11. MICROCONTROLLER PROGRAM:

    ;This is remote power monitoring.

    ;P2.0 = RLY0

    ;P2.1 = buzzer

    ;P2.2 = RLY2

    ;P2.3 = POWER OFF JUMPER

    ;P2.4 = recharge jumper

    ;P1 = ADC DATA

    ;P3.5=B

    ;P3.4=A

    ;P3.3=START

    ;P3.2=ALE

    ;P0 = DISP DATA

    ;P2.7 = RS

    ;P2.6 = R/W

  • 8/8/2019 Remote Power Monitor

    56/78

    49

    ;P2.5 = EN

    ; 50H = DISP LOCATION ADD

    ; 51H = DISP VALUE

    ; 60H = voltage set value

    ; 61H = frq set value

    ; 70H = voltage READ value

    ; 71H = frq READ value

    ;***********************************************

    TXD MACRO ;TX R6 DATA TO PC

    JNB TI,$

    CLR TI

    MOV SBUF, R6

    MACEND

    RXD MACRO ; READ FROM PC PUT IT IN R7

    JNB RI, $

  • 8/8/2019 Remote Power Monitor

    57/78

    50

    CLR RI

    MOV R7, SBUF

    MACEND

    ORG 0

    LJMP START

    ORG 0050H

    START: LCALL LCDINI

    LCALL DEL

    MOV DPTR, #0900H

    LCALL TLINE

    MOV DPTR, #0910H

    LCALL BLINE

    LCALL SSEC

    MOV DPTR, #0960H

    LCALL TLINE

  • 8/8/2019 Remote Power Monitor

    58/78

    51

    MOV DPTR,#0930H

    LCALL BLINE

    SETB P2.0

    CLR P2.1

    LCALL SPINI

    MOV R6,#00H

    TXD

    NEXT:

    CLR RI

    LCALL XRXD

    CJNE R4,#01H,NEXT

    CJNE R1,#01H,N2

    LCALL DEL

    MOV DPTR,#0920H

    LCALL TLINE

  • 8/8/2019 Remote Power Monitor

    59/78

    52

    MOV R6,#01H

    TXD

    LCALL VSEN

    MOV R6, 51H

    TXD

    MOV 50H, #8BH

    LCALL VFDIS

    LJMP NEXT

    N2: CJNE R1, #02H, N3

    LCALL DEL

    CLR P2.0

    SETB P2.1

    LCALL SSEC

    LCALL SSEC

    LCALL SSEC

  • 8/8/2019 Remote Power Monitor

    60/78

    53

    CLR P2.1

    MOV R6, #02H

    TXD

    LCALL DEL

    MOV R6, #03H

    TXD

    MOV DPTR, #0940H

    LCALL TLINE

    LJMP NEXT

    N3: CJNE R1, #04H, N4

    LCALL DEL

    SETB P2.0

    MOV R6, #04H

    TXD

    LCALL DEL

  • 8/8/2019 Remote Power Monitor

    61/78

    54

    MOV DPTR, #0950H

    LCALL TLINE

    MOV R6, #05H

    TXD

    N4: LJMP NEXT

    SEC: MOV R5, #03H

    M1: MOV R6, #FFH

    M2: MOV R7, #FFH

    M3: DJNZ R7, M3

    DJNZ R6, M2

    DJNZ R5, M1

    RET

    SSEC: MOV R5, #06H

    SM1: MOV R6, #FFH

    SM2: MOV R7, #FFH

  • 8/8/2019 Remote Power Monitor

    62/78

    55

    SM3: DJNZ R7, SM3

    DJNZ R6, SM2

    DJNZ R5, SM1

    RET

    ;********* VOLTAGE SENSE ************

    VSEN:

    mov p1,#FFH

    ;mov p3,#FFH

    SETB P3.2

    SETB P3.3

    SETB P3.4

    SETB P3.5

    SETB P3.6

    SETB P3.7

    CLR P3.2

  • 8/8/2019 Remote Power Monitor

    63/78

    56

    CLR P3.3

    LCALL DEL

    CLR P3.4

    CLR P3.5

    LCALL DEL

    SETB P3.2

    LCALL DEL

    SETB P3.3

    LCALL DEL

    CLR P3.2

    LCALL DEL

    CLR P3.3

    LCALL SEC

    MOV R6,P1

    MOV 51H,R6

  • 8/8/2019 Remote Power Monitor

    64/78

    57

    RET

    ;********* FREQ SENSE ************

    *** 9600 bps, 8bit, 2 STOP Bits, NO PARITY ***

    SPINI:

    MOV A, #00H

    MOV TCON, #40H

    MOV TMOD, #20H

    MOV SCON, #52H

    MOV IE, #9AH

    MOV TH1, #A0H

    MOV TL1, #A0H

    RET

    ;*******************************************

    XRXD: MOV R4, #00H

    MOV R5, #1FH

  • 8/8/2019 Remote Power Monitor

    65/78

    58

    XAE: MOV R3, #FFH

    XAD: MOV R2, #FFH

    XAB: JNB RI, XAC

    CLR RI

    MOV R1, SBUF

    MOV R4, #01H ; STATUS R4 CHK #01 OK, #02 NOT OK

    RET

    XAC: DJNZ R2, XAB

    DJNZ R3, XAD

    DJNZ R5, XAE

    MOV R4, #02H

    RET

    ;********** LCD INI ****************

    LCDINI:

    CLR P0.0

  • 8/8/2019 Remote Power Monitor

    66/78

    59

    CLR P0.1

    CLR P0.2

    CLR P2.5

    CLR p2.7

    CLR p2.6

    MOV P0, #30H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #30H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #30H

    LCALL WRI

  • 8/8/2019 Remote Power Monitor

    67/78

    60

    CLR p2.7

    CLR p2.6

    MOV P0, #38H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #01H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #01H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #01H

  • 8/8/2019 Remote Power Monitor

    68/78

    61

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #02H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #0CH

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #1CH

    LCALL WRI

    CLR p2.7

    CLR p2.6

  • 8/8/2019 Remote Power Monitor

    69/78

    62

    MOV P0, #38H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #06H

    LCALL WRI

    CLR p2.7

    CLR p2.6

    MOV P0, #01H

    LCALL WRI

    RET

    TLINE: CLR p2.7

    CLR p2.6

    MOV P0, #80H

    LCALL WRI

  • 8/8/2019 Remote Power Monitor

    70/78

    63

    MOV R7, #00H

    TKL: CLR A

    MOVC A,@A+DPTR

    MOV P0, A

    LCALL WRD

    INC DPTR

    INC R7

    CJNE R7, #10H, TKL

    RET

    BLINE: CLR p2.7

    CLR p2.6

    MOV P0, #C0H

    LCALL WRI

    MOV R7, #00H

    BKL: CLR A

  • 8/8/2019 Remote Power Monitor

    71/78

    64

    MOVC A, @A+DPTR

    MOV P0, A

    LCALL WRD

    INC DPTR

    INC R7

    CJNE R7, #10H, BKL

    RET

    ;******** INSTRUCTION /DATA WRITE *********

    WRI: SETB P2.5

    MOV R0, #FFH

    DJNZ R0, $

    CLR P2.5

    MOV R0, #FFH

    DJNZ R0, $

    RET

  • 8/8/2019 Remote Power Monitor

    72/78

    65

    WRD: SETB p2.7 ; REGISTER

    CLR p2.6 ;READ WRITE

    SETB P2.5 ;ENABLE

    MOV R0, #FFH

    DJNZ R0, $

    CLR P2.5

    CLR p2.6

    CLR p2.7

    RET

    DEL: MOV R7, #FFH

    DJNZ R7, $

    RET

    DEL1: MOV R7, #FFH

    DJNZ R7, $

    RET

  • 8/8/2019 Remote Power Monitor

    73/78

    66

    XDEL:

    mov r4, #0FH

    djnz r4, $

    RET

    XDEL1: mov r4, #0FH

    djnz r4, $

    RET

    XDEL2: MOV R5, #5FH

    GB: mov r4, #FFH

    djnz r4, $

    DJNZ R5, GB

    RET

    ;*********** DISPLAY *************

    VFDIS:

    MOV PSW, #18H

  • 8/8/2019 Remote Power Monitor

    74/78

    67

    MOV R3, 51H

    CLR A

    MOV A, 50H

    MOV P0, A

    LCALL WRI

    MOV DPTR, #0400H ;DATA BASE

    CJNE R3, #00H, GHH

    LJMP DTX

    GHH: MOV R2, #03H

    GHG: INC DPTR

    DJNZ R2, GHG

    DJNZ R3, GHH

    DTX:

    CLR A

    MOVC A,@A+DPTR

  • 8/8/2019 Remote Power Monitor

    75/78

    68

    MOV P0, A

    LCALL WRD

    INC DPTR

    CLR A

    MOVC A, @A+DPTR

    MOV P0, A

    LCALL WRD

    INC DPTR

    CLR A

    MOVC A, @A+DPTR

    MOV P0, A

    LCALL WRD

    INC DPTR

    MOV PSW, #00H

    RET

  • 8/8/2019 Remote Power Monitor

    76/78

    69

    ;##############################

    ORG 0400H

    ;************ 0

    DB #30H

    DB #30H

    DB #30H

    ;************ 1

    DB #30H

    DB #30H

    DB #31H

    ;************ 2

    ;************ 255

    DB #32H

    DB #35H

    DB #35H

  • 8/8/2019 Remote Power Monitor

    77/78

    70

    ORG 0900H

    ;************ 1 LINE

    DB 'REMOTE POWER '

    DB ' MONITORING '

    DB 'POWER : W '

    DB ' '

    DB 'OVER POWER DETD.'

    DB ' NORMAL LOAD OK '

    DB ' WAIT FOR COMM. '

    END;

  • 8/8/2019 Remote Power Monitor

    78/78

    12. BIBILOGRAPHY:

    1. Microprocessor and interfacing programming and Hardware, 2nd Edition Douglas V-

    Hall, Tata Mc Graw Hill publishing company limited 1999, 290-336

    2. Advanced Microprocessor and peripherals architecture program and interfacing by A. K.

    Ray and Burichand, Tata Mc Graw Hill publishing company limited 2000, 601-643.

    3. A Course in electrical and electronic measurements and instrumentation by A. K. Ray,

    Burichand, Tata Mc Graw Hill publishing company limited 1999, 384-425.

    4. www.atmel.com.

    5. www.en.wikipedia.org.

    6. www.cnx.org.

    7. www.alldatasheet.com.

    8. www.projectguidance.com

    9. www.progress-energy.com

    10. www.phsmou.or.jp.