100
Relion ® 615 series Feeder Protection and Control REF615 ANSI Application Manual

ref615ansi_appl_109554_enc

  • Upload
    dk1000

  • View
    75

  • Download
    4

Embed Size (px)

Citation preview

Page 1: ref615ansi_appl_109554_enc

Relion® 615 series

Feeder Protection and ControlREF615 ANSIApplication Manual

Page 2: ref615ansi_appl_109554_enc
Page 3: ref615ansi_appl_109554_enc

Document ID: 1MAC109554Issued: 01/20/2010

Revision: CProduct version: 2.0

© Copyright 2010 ABB. All rights reserved

Page 4: ref615ansi_appl_109554_enc

CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.

TrademarksABB and Relion are registered trademarks of ABB Group. All other brand or productnames mentioned in this document may be trademarks or registered trademarks of theirrespective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

ABB Inc.

Distribution Automation

4300 Coral Ridge Drive

Coral Springs, FL 33065, USA

Toll-free: 1 (800) 523-2620

Phone: +1 954-752-6700

Fax: +1 954 345-5329

http://www.abb.com/substationautomation

Page 5: ref615ansi_appl_109554_enc

DisclaimerThe data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failure wouldcreate a risk for harm to property or persons (including but not limited to personalinjuries or death) shall be the sole responsibility of the person or entity applying theequipment, and those so responsible are hereby requested to ensure that all measuresare taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.

Page 6: ref615ansi_appl_109554_enc

ConformityThis product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandards EN 50263 and EN 60255-26 for the EMC directive, and with the productstandards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED isdesigned in accordance with the international standards of the IEC 60255 series andANSI C37.90.

Page 7: ref615ansi_appl_109554_enc

Table of contents

Section 1 Introduction............................................................................5This manual..............................................................................................5Intended audience....................................................................................5Product documentation.............................................................................6

Product documentation set..................................................................6Document revision history...................................................................7Related documentation........................................................................8

Symbols and conventions.........................................................................8Safety indication symbols....................................................................8Manual conventions.............................................................................9Functions, codes and symbols............................................................9

Section 2 REF615 overview................................................................13Overview.................................................................................................13

Product version history......................................................................14PCM600 and IED connectivity package version................................14

Operation functionality............................................................................15Optional features...............................................................................15

Physical hardware..................................................................................15Local HMI................................................................................................17

LCD....................................................................................................18LEDs..................................................................................................18Keypad..............................................................................................19

Web HMI.................................................................................................19Authorization...........................................................................................20Communication.......................................................................................21

Section 3 REF615 variants..................................................................23REF615 variant list.................................................................................23Presentation of standard configurations.................................................23

Standard configurations ....................................................................24Connection diagrams.........................................................................27

Standard Configuration FA01: Current inputs only.................................29Applications.......................................................................................29Functions...........................................................................................29

Default I/O connections................................................................31

Table of contents

REF615 ANSI 1Application Manual

Page 8: ref615ansi_appl_109554_enc

Functional diagrams..........................................................................33Functional diagrams for protection...............................................34Functional diagrams for digital fault recorder and trip circuitmonitoring.....................................................................................40Functional diagrams for control and interlocking..........................44Functional diagram for optional ARC flash detection andautoreclosing................................................................................48Functional diagram for optional additional groundovercurrent protection...................................................................50Optional sensitive earth fault and high impedance faultdetection.......................................................................................52

Standard configuration FA02: Current and voltage inputs......................53Applications.......................................................................................53Functions...........................................................................................54

Default I/O connections................................................................56Functional diagrams..........................................................................58

Functional diagrams for protection...............................................58Functional diagrams for digital fault recorder and trip circuitmonitoring.....................................................................................64Functional diagrams for control and interlocking..........................67Functional diagram for voltage protections...................................72Functional diagram for optional ARC flash detection andautoreclosing................................................................................73Functional diagram for optional additional groundovercurrent protection...................................................................75Optional sensitive earth fault and high impedance faultdetection.......................................................................................76

Section 4 Requirements for measurement transformers.....................79Current transformers...............................................................................79

Current transformer requirements for non-directionalovercurrent protection........................................................................79

Current transformer accuracy class and accuracy limitfactor.............................................................................................79Non-directional overcurrent protection.........................................80Example for non-directional overcurrent protection......................82

Section 5 IED physical connections....................................................83Inputs......................................................................................................83

Energizing inputs...............................................................................83Phase currents.............................................................................83Ground current.............................................................................83

Table of contents

2 REF615 ANSIApplication Manual

Page 9: ref615ansi_appl_109554_enc

Phase voltages.............................................................................83Ground voltage.............................................................................84

Auxiliary supply voltage input............................................................84Binary inputs......................................................................................84Optional light sensor inputs...............................................................86

Outputs...................................................................................................86Outputs for tripping and controlling....................................................86Outputs for signalling.........................................................................87IRF.....................................................................................................88

Section 6 Glossary..............................................................................89

Table of contents

REF615 ANSI 3Application Manual

Page 10: ref615ansi_appl_109554_enc

4

Page 11: ref615ansi_appl_109554_enc

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelines sortedper function. The manual can be used to find out when and for what purpose a typicalprotection function can be used. The manual can also be used when calculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as communication andprotocols.

1MAC109554 C Section 1Introduction

REF615 ANSI 5Application Manual

Page 12: ref615ansi_appl_109554_enc

1.3 Product documentation

1.3.1 Product documentation set

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gde

inst

allin

g&

dis

posa

l

Application manual

Operation manual

Installation manual

Service manual

Engineering manual

Commissioning manual

Communication protocolmanual

Technical manual

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gde

inst

allin

g&

dis

posa

l

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gde

inst

allin

g&

dis

posa

l

Application manualApplication manual

Operation manualOperation manual

Installation manualInstallation manual

Service manualService manual

Engineering manualEngineering manual

Commissioning manualCommissioning manual

Communication protocolmanualCommunication protocolmanual

Technical manualTechnical manual

en07000220.vsd

IEC07000220 V1 EN

Figure 1: The intended use of manuals in different lifecycles

The engineering manual contains instructions on how to engineer the IEDs using thedifferent tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual also recommendsa sequence for engineering of protection and control functions, LHMI functions as wellas communication engineering for IEC 61850 and DNP3.

The installation manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel for assistance

Section 1 1MAC109554 CIntroduction

6 REF615 ANSIApplication Manual

Page 13: ref615ansi_appl_109554_enc

during the testing phase. The manual provides procedures for checking of externalcircuitry and energizing the IED, parameter setting and configuration as well asverifying settings by secondary injection. The manual describes the process of testingan IED in a substation which is not in service. The chapters are organized inchronological order in which the IED should be commissioned.

The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for monitoring, controlling andsetting the IED. The manual also describes how to identify disturbances and how toview calculated and measured power grid data to determine the cause of a fault.

The service manual contains instructions on how to service and maintain the IED. Themanual also provides procedures for de-energizing, de-commissioning and disposal ofthe IED.

The application manual contains application descriptions and setting guidelines sortedper function. The manual can be used to find out when and for what purpose a typicalprotection function can be used. The manual can also be used when calculating settings.

The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and during normalservice.

The communication protocol manual describes a communication protocol supported bythe IED. The manual concentrates on vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific tothe IED. The manual should be used in conjunction with the correspondingcommunication protocol manual.

Some of the manuals are not available yet.

1.3.2 Document revision historyDocument revision/date Product version HistoryA/03/28/2008 1.0.1 First release

B/12/22/2008 1.1 Content updated to correspond to theproduct version

C/01/20/2010 2.0 Content updated to correspond to theproduct version

1MAC109554 C Section 1Introduction

REF615 ANSI 7Application Manual

Page 14: ref615ansi_appl_109554_enc

Download the latest documents from the ABB web site http://www.abb.com/substationautomation.

1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MAC052634-MB

DNP3 Communication Protocol Manual 1MAC052460-MB

IEC 61850 Engineering Guide 1MAC106231-MB

Installation Manual 1MAC051065-MB

Operation Manual 1MAC050592-MB

Technical Manual 1MAC050144-MB

1.4 Symbols and conventions

1.4.1 Safety indication symbols

The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.

The warning icon indicates the presence of a hazard which could resultin personal injury.

The caution icon indicates important information or warning related tothe concept discussed in the text. It might indicate the presence of ahazard which could result in corruption of software or damage toequipment or property.

The information icon alerts the reader to important facts and conditions.

Section 1 1MAC109554 CIntroduction

8 REF615 ANSIApplication Manual

Page 15: ref615ansi_appl_109554_enc

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it should be understood thatoperation of damaged equipment could, under certain operational conditions, result indegraded process performance leading to personal injury or death. Therefore, complyfully with all warning and caution notices.

1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in thismanual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using the pushbutton icons, for example:To navigate between the options, use and .

• HMI menu paths are presented in bold, for example:Select Main menu/Settings.

• LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .

• Parameter names are shown in italics, for example:The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks, for example:The corresponding parameter values are "Enabled" and "Disabled".

• IED input/output messages and monitored data names are shown in Courier font,for example:When the function picks up, the PICKUP output is set to TRUE.

• Dimensions are provided both in inches and mm. If it is not specifically mentionedthen the dimension is in mm.

1.4.3 Functions, codes and symbolsTable 1: REF615 functions, codes and symbols

Function IEC 61850 IEC 60617 ANSIProtection

Three-phase transformer inrush detector INRPHAR1 3I2f> INR

Cold load timer 1 (Seconds) TPSGAPC1 TPS(1) 62CLD-1

Cold load timer 2 (Minutes) TPMGAPC1 TPM(1) 62CLD-2

Table continues on next page

1MAC109554 C Section 1Introduction

REF615 ANSI 9Application Manual

Page 16: ref615ansi_appl_109554_enc

Function IEC 61850 IEC 60617 ANSIThree-phase non-directional time overcurrentprotection, low stage

PHLPTOC1 3I>(1) 51P

Three-phase non-directional instantaneousovercurrent protection

PHIPTOC1 3I>>>(1) 50P-3

Three-phase non-directional time overcurrentprotection, high stage 1

PHHPTOC1 3I>>(1) 50P-1

Three-phase non-directional time overcurrentprotection, high stage 2

PHHPTOC2 3I>>(2) 50P-2

Three-phase non-directional long time overcurrentprotection

PHLTPTOC1 3I>(3) 51LT

Ground non-directional time overcurrent protection,low stage (Calculated)

EFLPTOC2 I0>(2) 51N

Ground non-directional instantaneous overcurrentprotection, (Calculated)

EFIPTOC2 I0>>> (2) 50N-3

Ground non-directional time overcurrent protection,high stage 1 (Calculated)

EFHPTOC3 I0>> (3) 50N-1

Ground non-directional time overcurrent protection,high stage 2 (Calculated)

EFHPTOC4 I0>> (4) 50N-2

Ground non-directional time overcurrent protection,high stage 1 (Measured)

EFHPTOC1 I0>> (1) 50G-1

Ground non-directional time overcurrent protection,high stage 2 (Measured)

EFHPTOC2 I0>> (2) 50G-2

Negative sequence non-directional timeovercurrent protection 1

NSPTOC1 I2>(1) 46-1

Negative sequence non-directional timeovercurrent protection 2

NSPTOC2 I2>(2) 46-2

Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD

Three-phase thermal protection for feeders, cablesand distribution transformers

T1PTTR1 3Ith>F 49F

Circuit breaker failure protection CCBRBRF1 3I>/IoBF(1) 50BF

Loss of load protection LOFLPTUC1 3I< 37

Three phase overvoltage protection, stage 1 PHPTOV1 3U>(1) 59-1

Three phase overvoltage protection, stage 2 PHPTOV2 3U>(2) 59-2

Three-phase undervoltage protection, stage 1 PHPTUV1 3U<(1) 27-1

Three-phase undervoltage protection, stage 2 PHPTUV2 3U<(2) 27-2

Ground overvoltage protection ROVPTOV1 U0>(1) 59G

Negative sequence overvoltage protection NSPTOV1 U2> 47

Directional ground-fault protection, low stage DEFLPDEF1 I0>->(1) 67/51N

Directional ground-fault protection, high stage 1 DEFLPDEF2 I0>->(2) 67/50N -1

Directional ground-fault protection, high stage 2 DEFHPDEF1 I0>>->(1) 67/50N -2

Three-phase directional overcurrent protection, lowstage

DPHLPDOC1 3I>->(1) 67/51P

Table continues on next page

Section 1 1MAC109554 CIntroduction

10 REF615 ANSIApplication Manual

Page 17: ref615ansi_appl_109554_enc

Function IEC 61850 IEC 60617 ANSIThree-phase directional overcurrent protection,high stage 1

DPHLPDOC2 3I>->(2) 67/50P-1

Three-phase directional overcurrent protection,high stage 2

DPHHPDOC1 3I>>->(1) 67/50P-2

Ground non-directional time overcurrent protection,low stage (Measured)

EFLPTOC1 I0>(1) 51G

Ground non-directional instantaneous overcurrentprotection, (Measured)

EFIPTOC1 I0>>> (1) 50G-3

Non-directional sensitive earth-fault protection EFLPTOC3 I0>(3) 50SEF

Arc flash detector 1 ARCSARC1 ARC(1) AFD-1

Arc flash detector 2 ARCSARC2 ARC(2) AFD-2

Arc flash detector 3 ARCSARC3 ARC(3) AFD-3

Low impedance restricted ground fault protection LREFPNDF1 dIoLo> 87LOZREF

High impedance fault detector PHIZ1 PHIZ1 HIZ

Control

Autoreclosing DARREC1 O->I 79

Circuit Breaker Control CBXCBR1 I<->O CB 52-1

Supervision and monitoring

Circuit breaker condition monitoring SSCBR1 CBCM 52CM

Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1

Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2

Current circuit supervision CCRDIF1 MCS 3I CCM

Fuse failure supervision SEQRFUF1 FUSEF 60

Measurement

Three-phase current measurement CMMXU1 3I IA, IB, IC

Three-phase voltage measurement VMMXU1 3U VA,VB,VC

Sequence current measurement CSMSQI1 I1,I2,I0 I1, I2, I0

Sequence voltage measurement VSMSQI1 U1,U2,U0 V1,V2,V0

Three-phase power and energy measurement PEMMXU1 P,E P,E

Ground current measurement RESCMMXU1 I0 IG

Ground voltage measurement RESVMMXU1 U0 VG

Digital fault recorder RDRE1 DR DFR

Sequence of events recorder SER SER SER

Fault recorder FLTMSTA FR FLR

Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1

Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2

1MAC109554 C Section 1Introduction

REF615 ANSI 11Application Manual

Page 18: ref615ansi_appl_109554_enc

12

Page 19: ref615ansi_appl_109554_enc

Section 2 REF615 overview

2.1 Overview

REF615 is a dedicated feeder IED (intelligent electronic device) designed for theprotection, control, measurement and supervision of utility substations and industrialpower systems. REF615 is a member of ABB’s Relion® product family and part of its615 protection and control product series. The 615 series IEDs are characterized bytheir compactness and withdrawable design.

Re-engineered from the ground up, the 615 series has been designed to unleash the fullpotential of the IEC 61850 standard for communication and interoperability betweensubstation automation devices.

The IED provides main protection for overhead lines and cable feeders in distributionnetworks. The IED is also used as back-up protection in applications, where anindependent and redundant protection system is required.

Depending on the chosen standard configuration, the IED is adapted for the protectionof overhead line and cable feeders in isolated neutral, resistance earthed, compensatedand solidly earthed networks. Once the standard configuration IED has been given theapplication-specific settings, it can directly be put into service.

The 615 series IEDs support a range of communication protocols including IEC 61850with GOOSE messaging, Modbus® and DNP3.

1MAC109554 C Section 2REF615 overview

REF615 ANSI 13Application Manual

Page 20: ref615ansi_appl_109554_enc

2.1.1 Product version historyProduct version Product history1.0.1 Product released

1.1 • Circuit breaker condition monitoring• Replaced EFIPTOC3 with EFLPTOC3• New communication modules COMB11A, COMB12A, COMB13A and

COMB14A• IRIG-B• CB interlocking functionality enhanced• TCS functionality in HW enhanced• Non-volatile memory added• Serial communications

2.0 • Support for DNP3 serial or TCP/IP• Voltage measurement and protection• Power and energy measurement• Disturbance recorder upload via WHMI• Fuse failure supervision

2.1.2 PCM600 and IED connectivity package version• Protection and Control IED Manager PCM600 Ver. 2.0 SP2 or later• IED Connectivity Package REF615 ANSI Ver. 1.2 or later

• Parameter Setting• Firmware Update• Disturbance Handling• Signal Monitoring• Lifecycle Traceability• Signal Matrix• Communication Management• Configuration Wizard• Label Printing• IED User Management• IED Users

Download connectivity packages from the ABB web site http://www.abb.com/substationautomation

Section 2 1MAC109554 CREF615 overview

14 REF615 ANSIApplication Manual

Page 21: ref615ansi_appl_109554_enc

2.2 Operation functionality

2.2.1 Optional features• Arc flash detector with three sensors

• Optional arc flash detectors can be added to all standard configurations.• Additional BIOs: 7BI+3BO

• Optional BIO (7 BI + 3 BO) can be added to all standard configurations.• Autorecloser

2.3 Physical hardware

The IED consists of two main parts: plug-in unit and case. The plug-in unit contentdepends on the ordered functionality.

Table 2: Plug-in unit and case

Main unit Slot ID Content optionsPlug-in unit - HMI Large (8 lines, 16 characters)

X100 Auxiliary power/BOmodule

48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contacts1 normally-open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact

X110 BI/O module Only with configurations FA01 and FA028 BIs4 SO contacts

X120 AI/BI module With configurations FA01 and FA023 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)4 BIs

Case X130 Optional BI/Omodule

Only with configuration FA016 BIs3 SO contacts

AI/BI module Only with configuration FA023 phase voltage inputs (100, 110, 115 or 120 V)1 residual voltage input (100, 110, 115 or 120 V)4 BIs

X000 Optionalcommunicationmodule

See technical manual for details about different type ofcommunication modules.

1MAC109554 C Section 2REF615 overview

REF615 ANSI 15Application Manual

Page 22: ref615ansi_appl_109554_enc

The rated input levels are selected in the IED software for phase current and groundcurrent. The binary input thresholds 18...176 V DC are selected by adjusting the IED'sparameter settings.

The optional BIO module can be added in the IED to all standardconfigurations.

The connection diagrams of different hardware modules are presented in this manual.

See the installation manual for more information about the case and theplug-in unit.

Table 3: Number of physical connections in standard configurations

Conf. Analog channels Binary channels CT VT BI BO

FA01 3 or 4 0 4 6

FA02 4 4 16 10

Section 2 1MAC109554 CREF615 overview

16 REF615 ANSIApplication Manual

Page 23: ref615ansi_appl_109554_enc

2.4 Local HMI

A070704-ANSI V1 EN

Figure 2: LHMI

The LHMI of the IED contains the following elements:

• Display• Buttons• LED indicators• Communication port

The LHMI is used for setting, monitoring and controlling.

1MAC109554 C Section 2REF615 overview

REF615 ANSI 17Application Manual

Page 24: ref615ansi_appl_109554_enc

2.4.1 LCDThe LHMI includes a graphical LCD that supports two character sizes. The charactersize depends on the selected language.

Table 4: Characters and rows on the view

Character size Rows in view Characters on rowLarge, variable width (13x14pixels)

4 rows8 rows with large screen

min 8

The display view is divided into four basic areas.

1 2

3 4

A070705-ANSI V2 EN

Figure 3: Display layout

1 Header

2 Icon

3 Content

4 Scroll bar (displayed when needed)

2.4.2 LEDsThe LHMI includes three protection indicators above the display: Normal, Pickup andTrip.

There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDscan be configured with PCM600 and the operation mode can be selected with theLHMI, WHMI or PCM600.

Section 2 1MAC109554 CREF615 overview

18 REF615 ANSIApplication Manual

Page 25: ref615ansi_appl_109554_enc

There are two additional LEDs which are embedded into the control buttons and. They represent the status of the circuit breaker.

2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in different viewsor menus. With the push-buttons you can give open or close commands to one primaryobject, for example, a circuit breaker, disconnector or switch. The push-buttons arealso used to acknowledge alarms, reset indications, provide help and switch betweenlocal and remote control mode.

A071176-ANSI V1 EN

Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

2.5 Web HMI

The WHMI enables the user to access the IED via a web browser. The supported webbrowser version is Internet Explorer 7.0 or later.

WHMI is enabled by default.

WHMI offers several functions.

• Alarm indications and event lists• System supervision• Parameter settings

1MAC109554 C Section 2REF615 overview

REF615 ANSI 19Application Manual

Page 26: ref615ansi_appl_109554_enc

• Measurement display• Oscillographic records• Phasor diagram

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

A070754-ANSI V2 EN

Figure 5: Example view of the WHMI

The WHMI can be accessed locally and remotely.

• Locally by connecting your laptop to the IED via the front communication port.• Remotely over LAN/WAN.

2.6 Authorization

The user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.

The default passwords can be changed with Administrator user rights.

Section 2 1MAC109554 CREF615 overview

20 REF615 ANSIApplication Manual

Page 27: ref615ansi_appl_109554_enc

User authorization is disabled by default but WHMI always usesauthorization.

Table 5: Predefined user categories

Username User rightsVIEWER Read only access

OPERATOR • Selecting remote or local state with (only locally)• Changing setting groups• Controlling• Clearing alarm and indication LEDs and textual indications

ENGINEER • Changing settings• Clearing event list• Clearing DFRs• Changing system settings such as IP address, serial baud rate or

DFR settings• Setting the IED to test mode• Selecting language

ADMINISTRATOR • All listed above• Changing password• Factory default activation

For user authorization for PCM600, see PCM600 documentation.

2.7 Communication

The IED supports different communication protocols: IEC 61850, Modbus® and DNP3.0 Level 2 - all using TCP/IP. DNP3 and Modbus also support serial communication.Operational information and controls are available through these protocols. However,some communication functionality, for example, horizontal peer-to-peercommunication between the IEDs and parameters setting, is only enabled by the IEC61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and controlfunctions. Additionally, parameter setting and DFR records can be accessed using theIEC 61850 protocol. Oscillographic files are available to any Ethernet-basedapplication in the standard COMTRADE format. Further, the IED can send andreceive binary signals from other IEDs (so called horizontal communication) using theIEC61850-8-1 GOOSE profile, where the highest performance class with a total

1MAC109554 C Section 2REF615 overview

REF615 ANSI 21Application Manual

Page 28: ref615ansi_appl_109554_enc

transmission time of 3 ms is supported. The IED meets the GOOSE performancerequirements for tripping applications in distribution substations, as defined by the IEC61850 standard. The IED can simultaneously report events to five different clients onthe station bus.

All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100BASE-TX) or the fiber-optic LC connector (100BASE-FX). An optional serial interface is available forRS-232/RS-485 communication.

Section 2 1MAC109554 CREF615 overview

22 REF615 ANSIApplication Manual

Page 29: ref615ansi_appl_109554_enc

Section 3 REF615 variants

3.1 REF615 variant list

REF615 is intended for protection and control mainly in MV feeder applications. Theproduct has two standard configurations covering a wide range of primary circuitconfigurations in distribution networks based on different system grounding methods.

Some of the functions included in the IED's standard configurations are optional at thetime of placing the order. The description of standard configurations covers the fullfunctionality including options, presenting the functionality, flexibility and externalconnections of REF615 with a specific configuration as delivered from the factory.

3.2 Presentation of standard configurations

Functional diagramsThe functional diagrams describe the IED's functionality from the protection,measuring, condition monitoring, recording, control and interlocking perspective.Diagrams show the default functionality with simple symbol logics forming principlediagrams. The external connections to primary devices are also shown, stating thedefault connections to measuring transformers. The positive measuring direction istowards the outgoing feeder, away from the bus bar.

The functional diagrams are divided into sections with each section constituting onefunctional entity. The external connections are also divided into sections. Only therelevant connections for a particular functional entity are presented in each section.

Protection function blocks are part of the functional diagram. They are identified basedon their ANSI function number/acronym, but the IEC based symbol and the IEC 61850names are also included. Some function blocks are used several times in theconfiguration. To separate the blocks from each other, the IEC 61850 name and ANSIfunction number are appended with a running number, that is an instance number, fromone upwards. The IED’s internal functionality and the external connections areseparated with a dashed line presenting the IED’s physical casing.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 23Application Manual

Page 30: ref615ansi_appl_109554_enc

Signal MatrixWith Signal Matrix in PCM600 the user can modify the standard configurationaccording to the actual needs. The IED is delivered from the factory with defaultconnections described in the functional diagrams for BI's, BO's, function to functionconnections and alarm LEDs. Signal Matrix has a number of different page views,designated as follows:

• Binary input• Binary output• Functions

There are four IED variant-specific setting groups. Parameters can be set independentlyfor each setting group.

The active setting group (1...4) can be changed with a parameter. The active settinggroup can also be changed via a binary input if the binary input is enabled for this. Toenable the change of the active setting group via a binary input, connect a free binaryinput with PCM600 to the ActSG input of the SGCB-block.

Table 6: Binary input states and corresponding active setting groups

BI state Active setting groupOFF 1

ON 2

The active setting group defined by a parameter is overridden when a binary input isenabled for changing the active setting group.

3.2.1 Standard configurationsThe feeder protection IED REF615 is available with two alternative standardconfigurations.

Table 7: Standard configurations

Description Std conf.Current inputs only FA01

Current and voltage inputs FA02

Section 3 1MAC109554 CREF615 variants

24 REF615 ANSIApplication Manual

Page 31: ref615ansi_appl_109554_enc

Table 8: Supported functions

Standard configuration functionality Stdconfig.FA01

Stdconfig.FA02

Protection

Three-phase transformer inrush detector ● ●

Three-phase non-directional time overcurrent protection, low stage ● ●

Three-phase non-directional time overcurrent protection, high stage 1 ●

Three-phase non-directional time overcurrent protection, high stage 2 ●

Three-phase non-directional instantaneous overcurrent protection ● ●

Three-phase non-directional long time overcurrent protection ●

Ground non-directional time overcurrent protection, low stage (Measured) ○ ○

Non-directional sensitive earth-fault protection ○ ○

Ground non-directional time overcurrent protection, high stage 1 (Measured) ○

Ground non-directional time overcurrent protection, high stage 2 (Measured) ○

Ground non-directional instantaneous overcurrent protection (Measured) ○ ○

Ground non-directional time overcurrent protection, low stage (Calculated) ● ●

Ground non-directional time overcurrent protection, high stage 1 (Calculated) ●

Ground non-directional time overcurrent protection, high stage 2 (Calculated) ●

Ground non-directional instantaneous overcurrent protection (Calculated) ● ●

Three phase overvoltage protection, stage 1 ●

Three phase overvoltage protection, stage 2 ●

Three-phase undervoltage protection, stage 1 ●

Three-phase undervoltage protection, stage 2 ●

Ground overvoltage protection ●

Negative sequence overvoltage protection ●

Directional ground-fault protection, low stage ●

Directional ground-fault protection, high stage 1 ●

Directional ground-fault protection, high stage 2 ●

Three-phase directional overcurrent protection, low stage ●

Three-phase directional overcurrent protection, high stage 1 ●

Three-phase directional overcurrent protection, high stage 2 ●

Negative sequence non-directional time overcurrent protection 1 ● ●

Negative sequence non-directional time overcurrent protection 2 ● ●

Phase discontinuity protection ● ●

Three-phase thermal protection for feeders, cables and distribution transformers ● ●

Loss of load protection ● ●

Low impedance restricted ground-fault protection ○ ○

Table continues on next page

1MAC109554 C Section 3REF615 variants

REF615 ANSI 25Application Manual

Page 32: ref615ansi_appl_109554_enc

Standard configuration functionality Stdconfig.FA01

Stdconfig.FA02

Cold load timer 1 (Seconds) ● ●

Cold load timer 2 (Minutes) ● ●

Arc flash detection with three sensors ○ ○

High impedance fault detector ○ ○

Circuit breaker failure protection ● ●

Control

Autoreclosing ○ ○

Circuit breaker control ● ●

Supervision and monitoring

Circuit breaker condition monitoring ● ●

Trip-circuit monitoring of two trip circuits ● ●

Current circuit supervision ● ●

Fuse failure supervision ●

Measurement

Three-phase current measurement ● ●

Three-phase voltage measurement ●

Sequence current measurement ● ●

Sequence voltage measurement ●

Ground current measurement ○ ●

Ground voltage measurement ●

Three-phase power and energy measurement ●

Disturbance recorder ● ●

Sequence of events recorder ● ●

Fault recorder ● ●

Electrically latched/self resetting trip output 1 and 2 ● ●

● = Included, ○ = Optional at the time of the order

Section 3 1MAC109554 CREF615 variants

26 REF615 ANSIApplication Manual

Page 33: ref615ansi_appl_109554_enc

3.2.2 Connection diagrams

16

151918

10

111213

14

22

23

24

SO2

TCM-2

PO4

SO1

TCM-1

PO3

COMMON PICKUP

COMMON TRIP

MASTER TRIP 1

MASTER TRIP 2

17

21

20

X120

12

3

4

567

89

1011

1213

14IG

IA

IB

BI 4

BI 3

BI 2

BI 1

IC

X110

12

56

7

89

10 BI 6

BI 5

BI 4

BI 3

BI 1

BI 8

BI 712

13

11

REF615

ABC

S1

S2

P1

P2

52

BA C

X100

67

89

10

2

1

3

45

PO2

PO1

IRF

+

-Vaux

X110

16

14

15

19

17

18

22

20

21

SO3

SO2

SO1

IED FAILURE ALARM

BREAKER CLOSE

BREAKER FAILURE

NOT AVAILABLE WITHCONFIGURATION AA

ONLY FORCONFIGURATION AA

24

23SO4

X130

12

10

11

15

13

14

18

16SO3

SO2

SO1

17

1)

4 BI 23

X13012

3

45

6 BI 4

BI 3

BI 2

BI 1

BI 6

BI 58

9

7

X1LAN

1) 2)

GND1)

GNDC

A/+ RXB/- RXA/+ TXB/- TXAGNDIRIG-B+IRIG-B-

1

109876

X5

432

5

X13Light sensor input 1

1)

X14Light sensor input 2

1)

X15Light sensor input 3

1)

1) Optional

1)

2) 100BaseFX / LC or 100BaseTX / RJ-45

GUID-A7A9B265-EF15-4220-8319-7337B50977D0 V1 EN

Figure 6: Connection diagram for configuration FA01

1MAC109554 C Section 3REF615 variants

REF615 ANSI 27Application Manual

Page 34: ref615ansi_appl_109554_enc

16

151918

10

111213

14

22

23

24

SO2

TCM-2

PO4

SO1

TCM-1

PO3

COMMON PICKUP

COMMON TRIP

MASTER TRIP 1

MASTER TRIP 2

17

21

20

X120

12

3

4

567

89

1011

1213

14IG

IA

IB

BI 4

BI 3

BI 2

BI 1

IC

X13012

56

78

9

10

VB

VA

BI 4

BI 3

BI 1

VG

VC

1213

11

REF615

ABC

S1

S2

P1

P2

52

BA C

X100

67

89

10

2

1

3

45

PO2

PO1

IRF

+

-Vaux

X110

16

14

15

19

17

18

22

20

21

SO3

SO2

SO1

IED FAILURE ALARM

BREAKER CLOSE

BREAKER FAILURE

24

23SO4

4 BI 23

X1LAN

1) 2)

GND1)

GNDC

A/+ RXB/- RXA/+ TXB/- TXAGNDIRIG-B+IRIG-B-

1

109876

X5

432

5

X13Light sensor input 1

1)

X14Light sensor input 2

1)

X15Light sensor input 3

1)

1) Optional2) 100BaseFX / LC or 100BaseTX / RJ-45

Not in use

16

15

18

17

14

dnda

a

nN

A

X110

12

56

7

89

10 BI 6

BI 5

BI 4

BI 3

BI 1

BI 8

BI 712

13

11

4 BI 23

GUID-E3D5CE1A-5EB8-4D7B-B52F-CD420869B354 V1 EN

Figure 7: Connection diagram for configuration FA02

Section 3 1MAC109554 CREF615 variants

28 REF615 ANSIApplication Manual

Page 35: ref615ansi_appl_109554_enc

3.3 Standard Configuration FA01: Current inputs only

3.3.1 ApplicationsThe standard configuration FA01 is meant for current inputs only. It is mainly intendedfor cable and overhead-line feeder applications in directly or resistance groundeddistribution networks.

The IED with this standard configuration is delivered from the factory with the defaultsettings and parameters. The end-user flexibility for incoming, outgoing and internalsignal designation within the IED enables this configuration to be further adapted todifferent primary circuit layouts and the related functionality needs by modifying theinternal functionality using PCM600. As a security measure, all functions except 51Pare disabled.

3.3.2 FunctionsTable 9: Functions included in the REF615 standard configuration FA01

Function IEC 61850 IEC 60617 ANSIIncluded functions

Three-phase current measurement CMMXU1 3I IA, IB, IC

Sequence current measurement CSMSQI1 I1,I2,I0 I1, I2, I0

Three-phase transformer inrush detector INRPHAR1 3I2f> INR

Cold load timer 1 (Seconds) TPSGAPC1 TPS(1) 62CLD-1

Cold load timer 2 (Minutes) TPMGAPC1 TPM(1) 62CLD-2

Three-phase non-directional time overcurrentprotection, low stage

PHLPTOC1 3I>(1) 51P

Three-phase non-directional time overcurrentprotection, high stage 1

PHHPTOC1 3I>>(1) 50P-1

Three-phase non-directional time overcurrentprotection, high stage 2

PHHPTOC2 3I>>(2) 50P-2

Three-phase non-directional instantaneousovercurrent protection

PHIPTOC1 3I>>>(1) 50P-3

Three-phase non-directional long timeovercurrent protection

PHLTPTOC1 3I>(3) 51LT

Ground non-directional time overcurrentprotection, low stage (Calculated)

EFLPTOC2 I0>(2) 51N

Ground non-directional time overcurrentprotection, high stage 1 (Calculated)

EFHPTOC3 I0>> (3) 50N-1

Ground non-directional time overcurrentprotection, high stage 2 (Calculated)

EFHPTOC4 I0>> (4) 50N-2

Table continues on next page

1MAC109554 C Section 3REF615 variants

REF615 ANSI 29Application Manual

Page 36: ref615ansi_appl_109554_enc

Function IEC 61850 IEC 60617 ANSIGround non-directional instantaneousovercurrent protection, (Calculated)

EFIPTOC2 I0>>> (2) 50N-3

Negative sequence non-directional timeovercurrent protection 1

NSPTOC1 I2>(1) 46-1

Negative sequence non-directional timeovercurrent protection 2

NSPTOC2 I2>(2) 46-2

Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD

Three-phase thermal protection for feeders,cables and distribution transformers

T1PTTR1 3Ith>F 49F

Circuit breaker failure protection CCBRBRF1 3I>/IoBF(1) 50BF

Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1

Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2

Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1

Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2

Disturbance recorder RDRE1 DR DFR

Sequence of events recorder SER SER SER

Fault recorder FLTMSTA FR FLR

Circuit breaker control CBXCBR1 I<->O CB 52-1

Loss of load protection LOFLPTUC1 3I< 37

Circuit breaker condition monitoring SSCBR1 CBCM 52CM

Current circuit supervision CCRDIF1 MCS 3I CCM

Optional functions

Ground current measurement RESCMMXU1 I0 IG

Ground non-directional time overcurrentprotection, low stage (Measured)

EFLPTOC1 I0>(1) 51G

Ground non-directional time overcurrentprotection, high stage 1 (Measured)

EFHPTOC1 I0>> (1) 50G-1

Ground non-directional time overcurrentprotection, high stage 2 (Measured)

EFHPTOC2 I0>> (2) 50G-2

Ground non-directional instantaneousovercurrent protection, (Measured)

EFIPTOC1 I0>>> (1) 50G-3

Non-directional sensitive earth-fault protection EFLPTOC3 I0>(3) 50SEF

Autoreclosing DARREC1 O->I 79

Arc flash detector 1 ARCSARC1 ARC(1) AFD-1

Arc flash detector 2 ARCSARC2 ARC(2) AFD-2

Arc flash detector 3 ARCSARC3 ARC(3) AFD-3

Low impedance restricted ground fault protection LREFPNDF1 dIoLo> 87LOZREF

High impedance fault detector PHIZ1 PHIZ1 HIZ

Section 3 1MAC109554 CREF615 variants

30 REF615 ANSIApplication Manual

Page 37: ref615ansi_appl_109554_enc

3.3.2.1 Default I/O connections

Table 10: Default connections for binary inputs

Binary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2

X120-BI2 Circuit breaker closed indication X120-3,2

X120-BI3 Circuit breaker open indication X120-4,2

X120-BI4 Reset of master trip lockout X120-5,6

Table 11: Default connections for binary outputs

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7

X100-PO2 Circuit breaker failure protection trip to upstream breaker X100-8,9

X100-PO3 Open circuit breaker/trip coil 1 X100-16,17,18,19

X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23

X100-SO1 General pickup indication X100-10,11,12

X100-SO2 General trip indication X100-13,14,15

Table 12: Order codes

LED label Order code optionsLED label 1 HAFAAAAxxAE1BNNxXC

HAFAAAAxxBE1BNNxXC

HAFAAAAxx3E1BNNxXC

LED label 2 HAFAAAAxxAE1BANxXC

HAFAAAAxxBE1BANxXC

HAFAAAAxx3E1BNNxXC

LED label 3 HAFAAAAxxFE1BNNxXC

HAFAAAAxxGE1BNNxXC

LED label 4 HAFAAAAxxFE1BANxXC

HAFAAAAxxGE1BANxXC

LED label 5 HAFAABAxxAE1BNNxXC

HAFAABAxxBE1BNNxXC

HAFAABAxx3E1BNNxXC

LED label 6 HAFAABAxxAE1BANxXC

HAFAABAxxBE1BANxXC

HAFAABAxx3E1BANxXC

Table continues on next page

1MAC109554 C Section 3REF615 variants

REF615 ANSI 31Application Manual

Page 38: ref615ansi_appl_109554_enc

LED label Order code optionsLED label 7 HAFAABAxxFE1BNNxXC

HAFAABAxxGE1BNNxXC

LED label 8 HAFAABAxxFE1BANxXC

HAFAABAxxGE1BANxXC

LED label 9 HAFAACAxxAE1BNNxXC

HAFAACAxxBE1BNNxXC

HAFAACAxx3E1BNNxXC

LED label 10 HAFAACAxxAE1BANxXC

HAFAACAxxBE1BANxXC

HAFAACAxx3E1BANxXC

LED label 11 HAFAACAxxFE1BNNxXC

HAFAACAxxGE1BNNxXC

LED label 12 HAFAACAxxFE1BANxXC

HAFAACAxxGE1BANxXC

Table 13: Configuration option LED assignments, LED labels 1...4

LED label 1 LED label 2 LED label 3 LED label 4LED1 Phase A Phase A Phase A Phase A

LED2 Phase B Phase B Phase B Phase B

LED3 Phase C Phase C Phase C Phase C

LED4 Neutral Neutral Neutral Neutral/Ground

LED5 Time Time Time Time

LED6 Instantaneous Instantaneous Instantaneous Instantaneous

LED7 Recloser lockout Recloser lockout

LED8 Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

LED9Overload alarm/Trip

Overload alarm/Trip Overload alarm/Trip

Overload Alarm/Trip

LED10 Arc flash detection Arc flash detection

LED11

Table 14: Configuration option LED assignments, LED labels 5...8

LED label 5 LED label 6 LED label 7 LED label 8LED1 Phase A Phase A Phase A Phase A

LED2 Phase B Phase B Phase B Phase B

LED3 Phase C Phase C Phase C Phase C

Table continues on next page

Section 3 1MAC109554 CREF615 variants

32 REF615 ANSIApplication Manual

Page 39: ref615ansi_appl_109554_enc

LED label 5 LED label 6 LED label 7 LED label 8LED4 Neutral/Ground Neutral/Ground Neutral/Ground Neutral/Ground

LED5 Time Time Time Time

LED6 Instantaneous Instantaneous Instantaneous Instantaneous

LED7 Recloser lockout Recloser lockout

LED8 Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

LED9 Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip

LED10 Arc Flash detection Arc Flash detection

LED11

Table 15: Configuration option LED assignments, LED labels 9...12

LED label 9 LED label 10 LED label 11 LED label 12LED1 Phase A Phase A Phase A Phase A

LED2 Phase B Phase B Phase B Phase B

LED3 Phase C Phase C Phase C Phase C

LED4 Neutral/SEF Neutral/SEF Neutral/SEF Neutral/SEF

LED5 Time Time Time Time

LED6 Instantaneous Instantaneous Instantaneous Instantaneous

LED7 Recloser lockout Recloser lockout

LED8 Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

Breaker failure/Alarm

LED9 Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip

LED10 Arc flash detection Arc flash detection

LED11 HIZ detection HIZ detection HIZ detection HIZ detection

3.3.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function tofunction connections. The default connections can be viewed with the Signal Matrixtool and changed according to the application requirements, if necessary.

The analog channels, measurements from CTs, have fixed connections to the differentfunction blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in the functionaldiagrams. The common signal marked with IA, IB, IC represents the three phasecurrents. The signal IG represents the measured ground current.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 33Application Manual

Page 40: ref615ansi_appl_109554_enc

3.3.3.1 Functional diagrams for protection

The following functional diagrams describe the IED’s protection functionality in detailand according to the factory set default connections in the Signal Matrix tool.

Five overcurrent stages are offered for phase overcurrent and short-circuit protection.The inrush detection block’s (INR) output BLK2H provides the possibility to eitherblock the function or multiply the active settings for any of the shown protectionfunction blocks.

3I>(1)

PICKUPIA, IB, ICBLOCK

ENA_MULT

51P

PHHPTOC1PICKUPIA, IB, IC

BLOCK

ENA_MULT

50P-1

PHIPTOC1PICKUPIA, IB, IC

BLOCK

ENA_MULT

50P-3

PHHPTOC2PICKUPIA, IB, IC

BLOCK

ENA_MULT

50P-2INRPHAR1

BLK2HIA, IB, IC

BLOCK

INR

TRIP_PhA

86/94 LED

TRIP_PhA

OR

LED 1

86/94 LEDOR

LED 2

PHASE B TRIP

86/94 LEDOR

LED 3

PHASE C TRIP

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhBTRIP_PhB

TRIP_PhCTRIP_PhC

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhA

TRIP_PhB

TRIP_PhC

PHASE A TRIP

Trip1

LEDPTRC

LEDPTRC

TRIP

TRIP

TRIP

TRIP

NOTE 1

NOTE 1

NOTE 1

NOTE 1

NOTE 1: AVAILABLE ONLY FOR LED INDICATION.

AVAILABLE FOR MAPPING USINGSMT TOOL IN PCM TO ANY PROTECTION,DEPENDING ON APPLICATION.

PHLTPTOC1PICKUPIA, IB, IC

BLOCK

ENA_MULT

51LTTRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP

NOTE 1

OR

LED 6

INSTANTANEOUS TRIP

PHASE OVERCURRENT PROTECTION INDICATION

OR

LED 5

TIME TRIP

symbolIEC60617

Number/AcronymANSI Device/Function

LEDPTRC

Trip1

Trip1

PHLPTOC1

3I>>(1)

3I>>(2)

3I>>>(1)

3I>(3)

3I2f>

identificationIEC61850

GUID-E42BE42B-7540-48EF-88D3-F3EA495494E0 V1 EN

Figure 8: Phase overcurrent protection

The neutral overcurrent protections 51N, 50N-1/2 can be blocked by energizing thebinary input 1 (X120:1-2). Two negative sequence overcurrent stages (46-1 and 46-2)are included for phase unbalance protection along with a separate phase discontinuityprotection. The phase discontinuity protection (46PD) provides protection forinterruptions in the normal three-phase load supply, like in downed conductorsituations. Two separate cold load timers are provided with seconds and minutes

Section 3 1MAC109554 CREF615 variants

34 REF615 ANSIApplication Manual

Page 41: ref615ansi_appl_109554_enc

ranges to provide utmost flexibility in cold-load inrush protection. Any functions canbe selected to be blocked during the cold load timers pickup duration using the SignalMatrix tool.

EFLPTOC2PICKUP

BLOCK

51N

EFHPTOC3PICKUP

BLOCK

50N-1

EFIPTOC2PICKUP

BLOCK

50N-3

PICKUP

BLOCK

50N-2

ORTRIP

TRIP

TRIP

TRIP

EFHPTOC4

BI 1 (Blocking)

IA, IB, IC

BLOCK

ENA_MULT

IA, IB, IC

BLOCK

ENA_MULT

IA, IB, IC

BLOCK

ENA_MULT

IA, IB, IC

BLOCK

ENA_MULT

OR

TRIP_NEUT

86/94 LED

TRIP_NEUT

Trip 1

NEUTRAL OVERCURRENT PROTECTION

LED4

TRIPNEUTRAL

LED 6

TRIPINSTANTANEOUS

LED 5

TIME TRIP

LEDPTRC

I0>(2)

I0>>>(2)

I0>>(4)

I0>>(3)

GUID-5D3E8AF3-F761-44A7-9C32-5895506023CE V1 EN

Figure 9: Neutral overcurrent protection

1MAC109554 C Section 3REF615 variants

REF615 ANSI 35Application Manual

Page 42: ref615ansi_appl_109554_enc

NSPTOC1

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46-1

NSPTOC2

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46-2

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46PD

TRIP

TRIP

TRIP

PDNSPTOC1

I2>(2)

I2/I1>

I2>(1)

GUID-5A283316-A594-476E-9D4E-679F733DD128 V1 EN

Figure 10: Phase unbalance protection

Section 3 1MAC109554 CREF615 variants

36 REF615 ANSIApplication Manual

Page 43: ref615ansi_appl_109554_enc

COLD LOAD INRUSH PROTECTION

OR

TPSGAPC1

TRIP

TRIP

62CLD-1

TPMGAPC1

TRIP

TRIP

62CLD-2

PHHPTOC1

PICKUP

TRIP

BLOCK

50P-1

EFHPTOC1

BLOCK

50G-1

EFHPTOC3

BLOCK

50N-1

CLOSEBREAKER

PICKUP

TRIP

PICKUP

TRIP

NOTE: COLD LOAD INRUSH PROTECTION LOGIC MAY BE MODIFIED USING SMT IN PCM TOOL, AS REQUIRED.

internalExternal orSignalMappable

SIGNAL

TPS(1)

TPM(1)

3I>>(1)

I0>>(1)

I0>>(3)

GUID-20863AAD-BFF9-4B2C-84AF-E104ABA00DB2 V1 EN

Figure 11: Cold load inrush protection

The thermal overload protection (49F) provides indication for overload situations.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 37Application Manual

Page 44: ref615ansi_appl_109554_enc

THERMAL OVERLOAD PROTECTION

T1PTTR1TRIP

ALARM

IA, IB, IC

BLK_CLOSE

PICKUP

BLK_OPR

ENA_MULT

LED9

OVERLOAD ALARM

OR

3Ith>F

GUID-CAE27F81-EBCE-4CAC-A59D-3D644A9AB54A V1 EN

Figure 12: Thermal overload protection

All trip signals are connected to the Master Trip Logic and also to the alarm LEDs.

The breaker failure protection (50BF) is initiated via the pickup input by a number ofdifferent protection stages in the IED. The breaker failure protection function offersdifferent operating modes associated with circuit breaker position and the measuredphase and residual currents. The breaker failure protection has two operating outputs:TRRET and TRBU. The TRRET output is used for retripping its own breaker throughthe Master Trip. The TRBU output is used to give a back-up trip to the breakersassociated with the faulty breaker. For this purpose the TRBU trip output signal isconnected to output PO2 (X100: 8-9).

Section 3 1MAC109554 CREF615 variants

38 REF615 ANSIApplication Manual

Page 45: ref615ansi_appl_109554_enc

PO2

89

X100

BREAKER FAILURE PROTECTION

Circuit Breaker failureprotection trip toassociated breaker(s)

CCBRBRF1

TRRET

TRBU

IA, IB, IC

PICKUP

POSCLOSE

BREAKER FAILURE

CB_FAULT_AL

CB_FAULT

IN

BLOCK

LED8

50BF

51P Trip

50P-1 Trip

50P-2 Trip

50P-3 Trip

51LT Trip

51N Trip

50N-2 Trip

50N-1 Trip

50N-3 Trip

49F Trip

50BF Retrip

AFD-1 Trip

AFD-3 Trip

AFD-2 Trip

46PD Trip

46-1 Trip

46-2 Trip

OR

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

1)

3I>/Io>BF(1)

50G-1 Trip

51G Trip

BI 2 (Breaker Close Status)

50G-2 Trip

50G-3 Trip

50SEF Trip

87LOZREF Trip

GUID-69885C86-76F9-4981-B12F-8A612B83DF29 V1 EN

Figure 13: Breaker failure protection

Restricted earth-fault protection is used in applications where the IED is used as abackup for transformer protection.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 39Application Manual

Page 46: ref615ansi_appl_109554_enc

LREFPNDF1

PICKUP3I

IG

87LOZREF

TRIP

dIoLo>

REF_PICKUP

REF_TRIP

LED4

RESTRICTED EARTH FAULT PROTECTION

GUID-2B403B4C-8BB3-464F-B483-E69D7FE072F3 V1 EN

Figure 14: Restricted earth-fault protection

3.3.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring

The digital fault recorder has 64 digital inputs. All pickup and trip signals from theprotection stages are routed to trigger the digital fault recorder or alternatively only tobe recorded by the digital fault recorder depending on the parameter settings.

Section 3 1MAC109554 CREF615 variants

40 REF615 ANSIApplication Manual

Page 47: ref615ansi_appl_109554_enc

DIGITAL FAULT RECORDER

DREC

DFR

AI#2

AI#1

AI#4

AI#3

AI#6

AI#5

AI#8

AI#7

AI#10

AI#9

AI#12

AI#11

IA-A

IB-A

IC-A

IG-A

I1-A

I2-A

I0-A

Disabled

Disabled

Disabled

Disabled

Disabled

DR

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-5117344E-F9D8-4A21-8C94-A1D76A904FA0 V1 EN

Figure 15: Digital fault recorder analog inputs

1MAC109554 C Section 3REF615 variants

REF615 ANSI 41Application Manual

Page 48: ref615ansi_appl_109554_enc

DIGITAL FAULT RECORDER

DREC

DFR

BI#2

BI#1

BI#4

BI#3

BI#6

BI#5

BI#8

BI#7

BI#10

BI#9

BI#12

BI#11

BI#14

BI#13

BI#16

BI#15

BI#17

51P Trip

50P-1 Trip

50P-2 Trip

50P-3 Trip

51LT Trip

51G Trip

51N Trip

50G-1 Trip

50N-1 Trip

50G-2 Trip

50N-2 Trip

50G-3 Trip

50N-3 Trip

46-1 Trip

46-2 Trip

46PD Pickup

49F Trip

49F AlmThm

50BF Backup Trip

50BF Retrip

OR

BI#18

BI#20

BI#19

BI#22

BI#21

BI#24

BI#23

BI#25

AFD-11 FADet

AFD-21 FADet

AFD-31 FADet

AFD-21 Trip

AFD-11 Trip

79 PrgRec

AFD-31 Trip

INR Pickup

BI#26

BI#27

BI#28

79 UnsRec

79 Trip

HIZ

BI#30

BI#29

BI#31

BI#3250SEF

OR

OR

OR

TCM-1 Alarm

51G/50G-1 Trip

TCM-2 Alarm

50G-2/50G-3 Trip

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

DR

GUID-AB84979D-9313-4A32-846A-1EB9E5EADAD0 V1 EN

Figure 16: Digital fault recorder, binary inputs 1...32

Section 3 1MAC109554 CREF615 variants

42 REF615 ANSIApplication Manual

Page 49: ref615ansi_appl_109554_enc

DREC

DFR

BI#34

BI#33

BI#36

BI#35

BI#38

BI#37

BI#40

BI#39

BI#42

BI#41

BI#44

BI#43

BI#46

BI#45

BI#48

BI#47

BI#49

Spare

52CM-1 TRV_T_OP_ALM

52CM-1 TRV_T_CL_ALM

52CM-1 Alarm

52CM-1 CB_LIFE_ALM

BI#50

BI#52

BI#51

BI#54

BI#53

BI#56

BI#55

BI#57

BI#58

BI#59

BI#60

BI#62

BI#61

BI#63

BI#64

X110-7X110-5X110-3

X110-6X110-4X110-2X120-4 X110-8

X120-3

X120-2

X120-1

Spare

Spare

Spare

CCM Fail

CCM Alarm

Spare

37 Trip

87LOZREF Trip

CFD Trip

DIGITAL FAULT RECORDER

DR

X110-1 X130-1

X130-2

X130-3

X130-4

X130-5

X130-6

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-1A93270E-B5A8-4E23-AD71-8BE3A5A3C547 V1 EN

Figure 17: Digital fault recorder, binary inputs 33...64

Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) andTCM-2 for PO4 (X100:20-23). Both functions are indicated in LED 8.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 43Application Manual

Page 50: ref615ansi_appl_109554_enc

BI 2 (CB Close Status) OROR86/94-1 Trip

TRIP CIRCUIT MONITORING

TCM-1

ALARMBLOCK

TCSSCBR1

86/94-2 TripLED8

TRIP CIRCUIT FAILURE

TCM-2

ALARMBLOCK

TCSSCBR2

TCS(1)

TCS(2)

GUID-5B908A59-702C-4BD4-8DFA-85B6A1A7E18F V1 EN

Figure 18: Trip circuit monitoring

3.3.3.3 Functional diagrams for control and interlocking

The trip signals from the protections described above are connected to the two tripoutput contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the correspondingMaster Trip Logics 86/94-1 and 86/94-2. The open control commands to the circuitbreaker from local or remote 52-1-exe_op (or from the autorecloser 79-open_cb, whenavailable) are connected directly to the output PO3 (X100:16-19).

MASTER TRIP 1 LOGIC

16

151918TCM-1

PO317

51P Trip50P-1 Trip50P-2 Trip50P-3 Trip51LT Trip

51N Trip

50N-2 Trip50N-1 Trip

50N-3 Trip

49F Trip50BF RetripAFD-1 Trip

AFD-3 TripAFD-2 Trip

46PD Trip

46-1 Trip46-2 Trip

X100+

OR

OpenSignal to

86/94-1

TRIPCL_LKOUT

BLOCKTRIP

RST_LKOUT

With lock-out mode selection

TRPPTRC1OR

79 OPEN_CB

52 EXE_OP

Trip Coil 1

Breaker

2)

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

2) NON-LATCHED MODE AS DEFAULT.

Trip(1)

50SEF Trip50G-3 Trip50G-2 Trip50G-1 Trip51G Trip

87LOZREF Trip

GUID-095D3F46-D13E-4826-AAE6-0797F7D401FE V1 EN

Figure 19: Master trip 1

Section 3 1MAC109554 CREF615 variants

44 REF615 ANSIApplication Manual

Page 51: ref615ansi_appl_109554_enc

22

23

24TCM-2

PO421

20

MASTER TRIP 2 LOGIC

51P Trip50P-1 Trip50P-2 Trip50P-3 Trip51LT Trip

51N Trip

50N-2 Trip50N-1 Trip

50N-3 Trip

49F Trip50BF RetripAFD-1 Trip

AFD-3 TripAFD-2 Trip

46PD Trip

46-1 Trip46-2 Trip

20X100

+

OR

OpenSignal to

86/94-2

TRIP

CL_LKOUT

BLOCK

TRIP

RST_LKOUT

With lock-out mode selection

TRPPTRC2OR

79 OPEN_CB

52 EXE_OP

Trip Coil 2

Breaker

2)

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

2) NON-LATCHED MODE AS DEFAULT.

Trip(2)

50SEF Trip50G-3 Trip50G-2 Trip50G-1 Trip51G Trip

87LOZREF Trip

GUID-57A77F68-3DCA-4471-9F83-6E77DD010693 V1 EN

Figure 20: Master trip 2

The blocks 86/94-1 and 2 provide the lockout/latching function, event generation andthe trip signal duration setting. If the lockout operation mode is selected, one binaryinput can be reassigned to the RST_LKOUT input of the Master Trip Logics to enableexternal reset with a push button.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 45Application Manual

Page 52: ref615ansi_appl_109554_enc

BI 3 (Breaker Open Status)BI 2 (Breaker Close Status)

Always True

OR

67

PO1

+

X100

79 CLOSE_CB

CIRCUIT BREAKER CONTROL AND INTERLOCKING52-1 EXE_OP

52

SELECTEDENA_OPEN

ENA_CLOSE

BLK_OPEN

BLK_CLOSE

EXE_OP

EXE_CL

OPENPOS

CLOSEPOS

EXE_OP

EXE_CL

OPENPOS

CLOSEPOS

OKPOS

CBXCBR1

CloseBreaker

X110

56

7BI 4

BI 3PRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOW

TRV_T_OP_ALMTRV_T_CL_ALMDIFTRVTOPALMDIFTRVTCLALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINTERMPOSCLOSEPOS

BLOCKPOSOPEN

52CMCBCM

OR

LED8

(CB CONDMONITOR)

POSCLOSE

RST_CB_WEAR

CB Spring Charged

GAS Pressure Alarm

SSCBR1

I<->O CB

GUID-F6999B37-F933-43D0-967B-3FE127FE7811 V1 EN

Figure 21: Circuit breaker control and interlocking

The ENA_CLOSE input, which enables closing the circuit breaker, in the breakercontrol function block 52-1, is a combination of the status of the Master Trip Logics.The open operation is always enabled.

If the ENA_CLOSE signal is completely removed from the breakercontrol function block 52-1 with the Signal Matrix tool, the functionassumes that the breaker close commands are allowed continuously.

The circuit-breaker condition monitoring function (52CM) supervises the circuitbreaker status based on the binary input information connected and measured currentlevels. The function introduces various supervision methods. The correspondingsupervision alarm signals are routed to LED 8.

The signal outputs from the IED are connected to give dedicated information onpickups and trips.

• Pickup of any protection function SO1 (X100:10-12)• Trip of any protection function SO2 (X100:13-15)

Section 3 1MAC109554 CREF615 variants

46 REF615 ANSIApplication Manual

Page 53: ref615ansi_appl_109554_enc

COMMON PICKUP SIGNAL

LEDPTRC1

86/94 LED

TPGAPC1

TP-1

PICKUP

TRIP

PICKUP

TRIP

PICKUP

TRIP

PICKUP

TRIP

Pickup SignalSO#1 (X100:10-11-12)

1) THERE ARE FOUR PULSE TIMERS AVAILABLE-ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS.ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPEDFOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.

NOTE:

1)

Trip1 TP-1

GUID-17F7E87F-230E-496D-94C4-B188BA549CE9 V1 EN

Figure 22: Common pickup signal

The TP-1 is a timer and used for setting the minimum pulse length for the outputs.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 47Application Manual

Page 54: ref615ansi_appl_109554_enc

TRPPTRC1

PICKUP

TRIP

PICKUP

TRIP

TRPPTRC2

PICKUP

TRIP

PICKUP

TRIP

Trip SignalSO#2 (X100:13-14-15)

Trip(1)

Trip(2)

GUID-7E976C74-3F94-4023-89FD-0E62CC5766C6 V1 EN

Figure 23: Common trip signal

3.3.3.4 Functional diagram for optional ARC flash detection and autoreclosing

Optional ARC flash detectors (AFD 1-3) are included in the standard configuration.The ARC flash detection offers individual function blocks for each of the three ARCsensors that can be connected to the IED.

Each ARC protection function block has two different operation modes, with orwithout the phase current check.

Section 3 1MAC109554 CREF615 variants

48 REF615 ANSIApplication Manual

Page 55: ref615ansi_appl_109554_enc

ARCSARC1

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODE

REM_FLT_ARC

IG

ARCSARC2

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODEREM_FLT_ARC

IG

ARCSARC3

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODE

REM_FLT_ARC

IG

LED10

ARC(1)

ARC(2)

ARC(3)

GUID-19A57C71-5055-4521-AA56-C8BD5F51EDA3 V1 EN

Figure 24: Arc flash detection

Trip signals from the ARC protection function blocks are connected to the Master TripLogic and also to the alarm LED 10 as a common arc flash detection.

The autorecloser is configured to be initiated by operate signals from a number ofprotection stages through the INIT1-5 inputs. It is possible to create individualautoreclosing sequences for each input.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 49Application Manual

Page 56: ref615ansi_appl_109554_enc

50P-1 -trip50P-2 -trip

46-1 -trip46-2 -trip

AFD-1 -trip52 -selected

AFD-2 -tripAFD-3 -trip

AUTORECLOSING (Optional)

X120 BI 3 (CB Open)

OR

CB_RDYCB_POS

THERMOVL_BLK

INHIBIT_RECL

ON/OFF

DEL_INIT_4

DEL_INIT_3

DEL_INIT_2

INIT_6

INIT_5

INIT_4

INIT_3

INIT_2

INIT_1

DARREC1

OPEN CB

79

CLOSE CB

INPRO

UNSUC_RECL

AR_ON

LOCKED

LED 7

RECLOSER LOCKOUT

External AR Blocking X120 BI 4

OR

50N-1 -trip50N-2 -trip50G-1 -trip50G-2 -trip

51P -trip51N -trip OR

50P-3 -trip50N-3 -trip

OR

Notes: Map PROT_CRD signal to Block 50P-1,50P-2, 50N-1 and 50N-2 using SMT.

PROT_CRD

O->I

51G -trip

50G-3 -trip

49F -InhRec DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-9E712054-3ECA-4AAB-8756-F157B5ACDB2C V1 EN

Figure 25: Autoreclosing

The autoreclosing function can be blocked with the INHIBIT_RECL input. As adefault, the operation of some selected protection functions are connected to this input.A control command to the circuit breaker, either local or remote, will also block theautoreclose function via the 52-1-selected signal.

The circuit breaker availability for the autoreclosure sequence is expressed with theCB_RDY input in 79. In the configuration, this signal is not connected to any of thebinary inputs. As a result, the function assumes that the breaker is available all the time.

3.3.3.5 Functional diagram for optional additional ground overcurrent protection

Optional additional ground overcurrent protection provides more sensitive groundovercurrent protection when necessary.

Section 3 1MAC109554 CREF615 variants

50 REF615 ANSIApplication Manual

Page 57: ref615ansi_appl_109554_enc

EFLPTOC1PICKUPIG

BLOCK

ENA_MULT

51G

EFHPTOC1PICKUPIG

BLOCK

ENA_MULT

50G-1

EFIPTOC1PICKUPIG

BLOCK

ENA_MULT

50G-3

EFHPTOC2

PICKUPIG

BLOCK

ENA_MULT

50G-2

TRIP_NEUT

86/94LED

TRIP_NEUT

OR

LED4

TRIP

TRIP

TRIP

TRIP

TRIPNEUTRAL / GROUND

TRIP(1)

OR

LED 6

TIME TRIP

INSTANTANEOUS

GROUND OVERCURRENT PROTECTION (OPTIONAL)

BI 1 (Blocking)

LED5

TRIP

LEDPTRC

I0>(1)

I0>>(1)

I0>>(2)

I0>>>(1)

GUID-A251AB3C-8465-441C-8E2E-55335AA2A332 V1 EN

Figure 26: Ground overcurrent protection

1MAC109554 C Section 3REF615 variants

REF615 ANSI 51Application Manual

Page 58: ref615ansi_appl_109554_enc

3.3.3.6 Optional sensitive earth fault and high impedance fault detection

TRIP

TRIP

TRIP

TRIP

TRIPNEUTRAL / SEF

EFHPTOC4

EFLPTOC3

PICKUP

BLOCK

50SEF

TRIP

IG

SENSITIVE EARTH FAULT PROTECTION

EFLPTOC2PICKUP

BLOCK

51N

EFHPTOC3PICKUP

BLOCK

50N-1

EFIPTOC2

PICKUP

BLOCK

50N-3

PICKUP

BLOCK

50N-2

OR

LED 4

I0>(3)

I0>(2)

I0>>(3)

I0>>(4)

I0>>>(2)

GUID-7B5D6C4F-BC2D-4BD4-A659-5F9329A1C20F V1 EN

Figure 27: Sensitive earth-fault protection

Section 3 1MAC109554 CREF615 variants

52 REF615 ANSIApplication Manual

Page 59: ref615ansi_appl_109554_enc

LED11

HIZ DETECTION

BLOCK

PHIZ1

TRIP

PHIZ1

GUID-81DC07F7-4A53-4918-8FDD-66BD24B6A191 V1 EN

Figure 28: High impedance fault detection

The sensitive earth-fault protection (50SEF) and high impedance fault detection (HIZ)provide protection against high impedance faults. If the load unbalance is high, 50SEFneeds to be set high to avoid misoperations which renders 50SEF ineffective for suchapplications. In those cases, HIZ can provide detection which would otherwise beundetected.

3.4 Standard configuration FA02: Current and voltageinputs

3.4.1 ApplicationsThe standard configuration FA02 is meant for voltage and current inputs, intended forcable and overhead-line feeder applications in directly or resistance groundeddistribution networks where directional application is a requirement.

The IED with this standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing and internalsignal designation within the IED enables this configuration to be further adapted todifferent primary circuit layouts and the related functionality needs by modifying theinternal functionality using PCM600.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 53Application Manual

Page 60: ref615ansi_appl_109554_enc

As a security measure, all functions except 51P are disabled.

3.4.2 FunctionsTable 16: Functions included in the REF615 standard configuration FA02

Function IEC 61850 IEC 60617 ANSIIncluded functions

Three-phase current measurement CMMXU1 3I IA, IB, IC

Three-phase voltage measurement VMMXU1 3U VA,VB,VC

Sequence current measurement CSMSQI1 I1,I2,I0 I1, I2, I0

Sequence voltage measurement VSMSQI1 U1,U2,U0 V1,V2,V0

Three-phase power and energy measurement PEMMXU1 P,E P,E

Three-phase transformer inrush detector INRPHAR1 3I2f> INR

Cold load timer 1 (Seconds) TPSGAPC1 TPS(1) 62CLD-1

Cold load timer 2 (Minutes) TPMGAPC1 TPM(1) 62CLD-2

Three-phase non-directional time overcurrentprotection, low stage

PHLPTOC1 3I>(1) 51P

Three-phase non-directional instantaneousovercurrent protection

PHIPTOC1 3I>>>(1) 50P-3

Ground non-directional time overcurrentprotection, low stage (Calculated)

EFLPTOC2 I0>(2) 51N

Ground non-directional instantaneous overcurrentprotection, (Calculated)

EFIPTOC2 I0>>> (2) 50N-3

Negative sequence non-directional timeovercurrent protection 1

NSPTOC1 I2>(1) 46-1

Negative sequence non-directional timeovercurrent protection 2

NSPTOC2 I2>(2) 46-2

Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD

Three-phase thermal protection for feeders,cables and distribution transformers

T1PTTR1 3Ith>F 49F

Circuit breaker failure protection CCBRBRF1 3I>/IoBF(1) 50BF

Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1

Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2

Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1

Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2

Disturbance recorder RDRE1 DR DFR

Sequence of events recorder SER SER SER

Fault recorder FLTMSTA FR FLR

Circuit breaker control CBXCBR1 I<->O CB 52-1

Loss of load protection LOFLPTUC1 3I< 37

Table continues on next page

Section 3 1MAC109554 CREF615 variants

54 REF615 ANSIApplication Manual

Page 61: ref615ansi_appl_109554_enc

Function IEC 61850 IEC 60617 ANSICircuit breaker condition monitoring SSCBR1 CBCM 52CM

Current circuit supervision CCRDIF1 MCS 3I CCM

Three phase overvoltage protection, stage 1 PHPTOV1 3U>(1) 59-1

Three phase overvoltage protection, stage 2 PHPTOV2 3U>(2) 59-2

Three-phase undervoltage protection, stage 1 PHPTUV1 3U<(1) 27-1

Three-phase undervoltage protection, stage 2 PHPTUV2 3U<(2) 27-2

Ground overvoltage protection ROVPTOV1 U0>(1) 59G

Negative sequence overvoltage protection NSPTOV1 U2> 47

Directional ground-fault protection, low stage DEFLPDEF1 I0>->(1) 67/51N

Directional ground-fault protection, high stage 1 DEFLPDEF2 I0>->(2) 67/50N -1

Directional ground-fault protection, high stage 2 DEFHPDEF1 I0>>->(1) 67/50N -2

Three-phase directional overcurrent protection,low stage

DPHLPDOC1 3I>->(1) 67/51P

Three-phase directional overcurrent protection,high stage 1

DPHLPDOC2 3I>->(2) 67/50P-1

Three-phase directional overcurrent protection,high stage 2

DPHHPDOC1 3I>>->(1) 67/50P-2

Fuse failure supervision SEQRFUF1 FUSEF 60

Ground current measurement RESCMMXU1 I0 IG

Ground voltage measurement RESVMMXU1 U0 VG

Optional functions

Ground non-directional time overcurrentprotection, low stage (Measured)

EFLPTOC1 I0>(1) 51G

Ground non-directional instantaneous overcurrentprotection, (Measured)

EFIPTOC1 I0>>> (1) 50G-3

Non-directional sensitive earth-fault protection EFLPTOC3 I0>(3) 50SEF

Autoreclosing DARREC1 O->I 79

Arc flash detector 1 ARCSARC1 ARC(1) AFD-1

Arc flash detector 2 ARCSARC2 ARC(2) AFD-2

Arc flash detector 3 ARCSARC3 ARC(3) AFD-3

Low impedance restricted ground fault protection LREFPNDF1 dIoLo> 87LOZREF

High impedance fault detector PHIZ1 PHIZ1 HIZ

1MAC109554 C Section 3REF615 variants

REF615 ANSI 55Application Manual

Page 62: ref615ansi_appl_109554_enc

3.4.2.1 Default I/O connections

Table 17: Default connections for binary inputs

Binary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2

X120-BI2 Circuit breaker closed position indication X120-3,2

X120-BI3 Circuit breaker open position indication X120-4,2

Table 18: Default connections for binary outputs

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7

X100-PO2Circuit breaker failure protection trip to upstreambreaker X100-8,9

X100-PO3 Open circuit breaker/trip coil 1 X100-16,17,18,19

X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23

X100-SO1 General pickup indication X100-10,11,12

X100-SO2 General trip indication X100-13,14,15

Table 19: Order codes

LED label Order code optionsLED label 1 HAFDDADAxAE1BNNxXC

HAFDDADAxBE1BNNxXC

HAFDDADAx3E1BNNxXC

LED label 2 HAFDDADAxFE1BNNxXC

HAFDDADAxGE1BNNxXC

LED label 3 HAFDDADAxAE1BANxXC

HAFDDADAxBE1BANxXC

HAFDDADAx3E1BANxXC

LED label 4 HAFDDADAxFE1BANxXC

HAFDDADAxGE1BANxXC

LED label 5 HAFDDBDAxAE1BNNxXC

HAFDDBDAxBE1BNNxXC

HAFDDBDAx3E1BNNxXC

LED label 6 HAFDDBDAxFE1BNNxXC

HAFDDBDAxGE1BNNxXC

Table continues on next page

Section 3 1MAC109554 CREF615 variants

56 REF615 ANSIApplication Manual

Page 63: ref615ansi_appl_109554_enc

LED label Order code optionsLED label 7 HAFDDBDAxAE1BANxXC

HAFDDBDAxBE1BANxXC

HAFDDBDAx3E1BANxXC

LED label 8 HAFDDBDAxFE1BANxXC

HAFDDBDAxGE1BANxXC

Table 20: Configuration option LED assignments, LED labels 1...4

LED label 1 LED label 2 LED label 3 LED label 4LED1 Phase A Phase A Phase A Phase A

LED2 Phase B Phase B Phase B Phase B

LED3 Phase C Phase C Phase C Phase C

LED4 Neutral/Ground Neutral/Ground Neutral/Ground Neutral/Ground

LED5 Time Time Time Time

LED6 Instantaneous Instantaneous Instantaneous Instantaneous

LED7 Recloser lockout Recloser lockout

LED8 Voltage Voltage Voltage Voltage

LED9Overload alarm/Trip

Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip

LED10 Arc flash detection Arc flash detection

LED11

Table 21: Configuration option LED assignments, LED labels 5...8

LED label 5 LED label 6 LED label 7 LED label 8LED1 Phase A Phase A Phase A Phase A

LED2 Phase B Phase B Phase B Phase B

LED3 Phase C Phase C Phase C Phase C

LED4 Neutral/SEF Neutral/SEF Neutral/SEF Neutral/SEF

LED5 Time Time Time Time

LED6 Instantaneous Instantaneous Instantaneous Instantaneous

LED7 Recloser lockout Recloser lockout

LED8 Voltage Voltage Voltage Voltage

LED9Overload alarm/Trip

Overload alarm/Trip Overload alarm/Trip Overload alarm/Trip

LED10 Arc flash detection Arc flash detection

LED11 HIZ detection HIZ detection HIZ detection HIZ detection

1MAC109554 C Section 3REF615 variants

REF615 ANSI 57Application Manual

Page 64: ref615ansi_appl_109554_enc

3.4.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function tofunction connections. The default connections can be viewed with the Signal Matrixtool and changed according to the application requirements, if necessary.

The analog channels, measurements from CTs, have fixed connections to the differentfunction blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in the functionaldiagrams. The common signal marked with IA, IB, IC represents the three phasecurrents. The signal IG represents the measured ground current.

3.4.3.1 Functional diagrams for protection

The following functional diagrams describe the IED’s protection functionality in detailand according to the factory set default connections in the Signal Matrix tool.

Five overcurrent stages are offered for phase overcurrent and short-circuit protection.The inrush detection block’s (INR) output BLK2H provides the possibility to eitherblock the function or multiply the active settings for any of the shown protectionfunction blocks. Three of the overcurrent protections have directional feature and thesedirectional protections can also be used as non-directional protection with settingchanges.

Section 3 1MAC109554 CREF615 variants

58 REF615 ANSIApplication Manual

Page 65: ref615ansi_appl_109554_enc

3I>(1)

PICKUPIA, IB, ICBLOCK

ENA_MULT

51P

INRPHAR1

BLK2HIA, IB, IC

BLOCK

INR

TRIP_PhA

86/94 LED

TRIP_PhA

OR

LED 1

86/94 LEDOR

LED 2

PHASE B TRIP

86/94 LEDOR

LED 3

PHASE C TRIP

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhBTRIP_PhB

TRIP_PhCTRIP_PhC

PHASE A TRIP

Trip1

LEDPTRC

LEDPTRC

TRIP

NOTE 1

NOTE 1: AVAILABLE ONLY FOR LED INDICATION.

AVAILABLE FOR MAPPING USINGSMT TOOL IN PCM TO ANY PROTECTION,DEPENDING ON APPLICATION.

OR

LED 6

INSTANTANEOUS TRIP

PHASE OVERCURRENT PROTECTION INDICATION

OR

LED 5

TIME TRIP

symbolIEC60617

Number/AcronymANSI Device/Function

LEDPTRC

Trip1

Trip1

PHLPTOC1

3I2f>

identificationIEC61850

DPHLPDOC1

PICKUPIA, IB, IC

BLOCK

ENA_MULT

67/51P

DPHLPDOC2

PICKUPIA, IB, IC

BLOCK

ENA_MULT

67/50P-1

PHIPTOC1

PICKUPIA, IB, IC

BLOCK

ENA_MULT

50P-3

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP

TRIP

TRIP

NOTE 1

NOTE 1

NOTE 1

DPHHPDOC1

PICKUPIA, IB, IC

BLOCK

ENA_MULT

67/50P-2TRIP_PhA

TRIP_PhB

TRIP_PhC

TRIP

NOTE 1

3I>->(1)

3I>>>(1)

3I>>->(1)

3I>>->(2)

VA,VB,VC

VA,VB,VC

VA,VB,VC

GUID-7014C373-CE58-4086-85E6-384051F9E999 V1 EN

Figure 29: Phase overcurrent protection

The neutral overcurrent protection 51N can be blocked by energizing the binary input 1(X120:1-2). In addition, there are three more directional protection for ground faults.Two negative sequence overcurrent stages (46-1 and 46-2) are included for phaseunbalance protection along with a separate phase discontinuity protection. The phasediscontinuity protection (46PD) provides protection for interruptions in the normal three-phase load supply, like in downed conductor situations. Two separate cold load timersare provided with seconds and minutes ranges to provide utmost flexibility in cold-loadinrush protection. Any functions can be selected to be blocked during the cold loadtimers pickup duration using the Signal Matrix tool.

The thermal overload protection (49F) provides indication of overload situations.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 59Application Manual

Page 66: ref615ansi_appl_109554_enc

EFLPTOC2PICKUP

BLOCK

51N

EFIPTOC2PICKUP

BLOCK

50N-3

ORTRIP

TRIP

BI 1 (Blocking)IA, IB, IC

BLOCK

ENA_MULT

IA, IB, IC

BLOCK

ENA_MULT

OR

TRIP_NEUT

86/94 LED

TRIP_NEUT

Trip 1

NEUTRAL OVERCURRENT PROTECTION

LED4

TRIPNEUTRAL

LED 6

TRIPINSTANTANEOUS

LED 5

TIME TRIP

LEDPTRC

I0>(2)

I0>>>(2)

GUID-25B47047-EB9A-4262-AEFE-2C3FECC2BAD6 V1 EN

Figure 30: Neutral overcurrent protection

OR

DIRECTIONAL GROUND FAULT PROTECTION

I0>->(1)

PICKUPTRIP

IGVG

ENA_MULT

67/51N

RCA_CTL

BLOCK

DEFLPDEF1

I0>>(2)

PICKUPTRIP

IGVG

ENA_MULT

67/50N-1

RCA_CTL

BLOCK

DEFLPDEF2

I0>>->(1)

PICKUPTRIP

ENA_MULT

67/50N-2

RCA_CTL

BLOCK

DEFHPDEF1IGVG

TRIP_NEUT

86/94LED

TRIP_NEUT

TRIP(1)LEDPTRC

GROUND / NEUTRAL PROTECTIONS

LED4

LED5

To SENSITIVE EARTH FAULT PROTECTION

TIME TRIP

GUID-70E9F754-FE31-4F4A-BC58-191B4217C6D7 V1 EN

Figure 31: Directional ground overcurrent protection

Section 3 1MAC109554 CREF615 variants

60 REF615 ANSIApplication Manual

Page 67: ref615ansi_appl_109554_enc

NSPTOC1

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46-1

NSPTOC2

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46-2

PICKUPI1, I2, I0

BLOCK

ENA_MULT

46PD

TRIP

TRIP

TRIP

PDNSPTOC1

I2>(2)

I2/I1>

I2>(1)

GUID-5A283316-A594-476E-9D4E-679F733DD128 V1 EN

Figure 32: Phase unbalance protection

1MAC109554 C Section 3REF615 variants

REF615 ANSI 61Application Manual

Page 68: ref615ansi_appl_109554_enc

OR

TPSGAPC1

TRIP

TRIP

62CLD-1

TPMGAPC1

TRIP

TRIP

62CLD-2

DPHLPDOC2

BLOCK

67/50P-1

CLOSEBREAKER

PICKUP

TRIP

NOTE: COLD LOAD INRUSH PROTECTION LOGIC MAY BE MODIFIED USING SMT IN PCM TOOL, AS REQUIRED.

internalExternal orSignalMappable

SIGNAL

TPS(1)

TPM(1)

3I>>->(1)

DEFLPDEF2

BLOCK

67/50N-1

PICKUP

TRIP

I0>>(2)

COLD LOAD INRUSH PROTECTION

GUID-E8E78F22-20B2-4D87-91F4-1D7E4FC83E41 V1 EN

Figure 33: Cold load inrush protection

THERMAL OVERLOAD PROTECTION

T1PTTR1TRIP

ALARM

IA, IB, IC

BLK_CLOSE

PICKUP

BLK_OPR

ENA_MULT

LED9

OVERLOAD ALARM

OR

3Ith>F

GUID-CAE27F81-EBCE-4CAC-A59D-3D644A9AB54A V1 EN

Figure 34: Thermal overload protection

All trip signals are connected to the Master Trip Logic and also to the alarm LEDs.

Section 3 1MAC109554 CREF615 variants

62 REF615 ANSIApplication Manual

Page 69: ref615ansi_appl_109554_enc

The breaker failure protection (50BF) is initiated via the pickup input by a number ofdifferent protection stages in the IED. The breaker failure protection function offersdifferent operating modes associated with circuit breaker position and the measuredphase and residual currents. The breaker failure protection has two operating outputs:TRRET and TRBU. The TRRET output is used for retripping its own breaker throughthe Master Trip. The TRBU output is used to give a back-up trip to the breakersassociated with the faulty breaker. For this purpose the TRBU trip output signal isconnected to output PO2 (X100: 8-9).

PO2

89

X100

BREAKER FAILURE PROTECTION

Circuit Breaker failureprotection trip toassociated breaker(s)

TRRET

TRBU

IA, IB, IC

PICKUP

POSCLOSE

CB_FAULT_AL

CB_FAULT

IN

BLOCK

50BF

51P Trip

67/50P-1 Trip

67/50P-2 Trip

50P-3 Trip

67/51P Trip

51N Trip

67/50N-2 Trip

67/50N-1 Trip

50N-3 Trip

49F Trip

50BF Retrip

AFD-1 Trip

AFD-3 Trip

AFD-2 Trip

46PD Trip

46-1 Trip

46-2 Trip

OR

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

1)

3I>/Io>BF(1)

51G Trip

BI 2 (Breaker Close Status)

50G-3 Trip

50SEF Trip

67/51N Trip

87LOZREF Trip

CCBRBRF1

GUID-64F3E83A-E978-42D4-BA4B-B2C77C16F07F V1 EN

Figure 35: Breaker failure protection

Restricted earth-fault protection is used in applications where the IED is used as abackup for transformer protection.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 63Application Manual

Page 70: ref615ansi_appl_109554_enc

LREFPNDF1

PICKUP3I

IG

87LOZREF

TRIP

dIoLo>

REF_PICKUP

REF_TRIP

LED4

RESTRICTED EARTH FAULT PROTECTION

GUID-2B403B4C-8BB3-464F-B483-E69D7FE072F3 V1 EN

Figure 36: Restricted earth-fault protection

3.4.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring

The digital fault recorder has 64 digital inputs. All pickup and trip signals from theprotection stages are routed to trigger the digital fault recorder or alternatively only tobe recorded by the digital fault recorder depending on the parameter settings.

DIGITAL FAULT RECORDER

DREC

DFR

AI#2

AI#1

AI#4

AI#3

AI#6

AI#5

AI#8

AI#7

AI#10

AI#9

AI#12

AI#11

IA-A

IB-A

IC-A

IG-A

I1-A

I2-A

I0-A

Disabled

VA-kV

VB-kV

VC-kV

VG-kV

DR

GUID-478D7109-29FA-4702-8CF8-40EAFCA81206 V1 EN

Figure 37: Digital fault recorder analog inputs

Section 3 1MAC109554 CREF615 variants

64 REF615 ANSIApplication Manual

Page 71: ref615ansi_appl_109554_enc

DIGITAL FAULT RECORDER

DREC

DFR

BI#2

BI#1

BI#4

BI#3

BI#6

BI#5

BI#8

BI#7

BI#10

BI#9

BI#12

BI#11

BI#14

BI#13

BI#16

BI#15

BI#17

67/50P-2 Trip

50P-3 Trip

46-1 Trip

46-2 Trip

46PD Pickup

49F Trip

49F AlmThm

50BF Backup Trip

50BF Retrip

BI#18

BI#20

BI#19

BI#22

BI#21

BI#24

BI#23

BI#25

AFD-11 FADet

AFD-21 FADet

AFD-31 FADet

AFD-21 Trip

AFD-11 Trip

79 PrgRec

AFD-31 Trip

INR Pickup

BI#26

BI#27

BI#28

79 UnsRec

79 Trip

HIZ

BI#30

BI#29

BI#31

BI#3250SEF

TCM-1 Alarm

Spare

TCM-2 Alarm

50G-3

DR

50N-3 Trip

67/50N-2 Trip

67/50N-1 Trip

67/51N Trip

51N Trip

OR

67/51P Trip

51P Trip

OR

67/50P-1 Trip

51G

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-14BE59BC-34F1-4AC8-A94C-DAC1790C2343 V1 EN

Figure 38: Digital fault recorder, binary inputs 1...32

1MAC109554 C Section 3REF615 variants

REF615 ANSI 65Application Manual

Page 72: ref615ansi_appl_109554_enc

DREC

DFR

BI#34

BI#33

BI#36

BI#35

BI#38

BI#37

BI#40

BI#39

BI#42

BI#41

BI#44

BI#43

BI#46

BI#45

BI#48

BI#47

BI#49

59-1 Trip

52CM TRV_T_OP_ALM

52CM TRV_T_CL_ALM

52CM Alarm

52CM CB_LIFE_ALM

BI#50

BI#52

BI#51

BI#54

BI#53

BI#56

BI#55

BI#57

BI#58

BI#59

BI#60

BI#62

BI#61

BI#63

BI#64

X110-7X110-5X110-3

X110-6X110-4X110-2X120-4 X110-8

X120-3

X120-2

X120-1

27-1 Trip

59G Trip

47 Trip

CCM Fail

CCM Alarm

60 Pickup

37 Trip

87LOZREF

CFD

DIGITAL FAULT RECORDER

DR

X110-1 XA130-1

XA130-2

XA130-3

XA130-4

59-2 Trip

27-2 Trip

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-9F33B297-6E43-44EF-9942-532296092135 V1 EN

Figure 39: Digital fault recorder, binary inputs 33...64

Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) andTCM-2 for PO4 (X100:20-23). Both functions are indicated in LED 9 or 8.

Section 3 1MAC109554 CREF615 variants

66 REF615 ANSIApplication Manual

Page 73: ref615ansi_appl_109554_enc

BI 2 (CB Close Status) OR86/94-1 Trip

TRIP CIRCUIT MONITORING

TCM-1

ALARMBLOCK

TCSSCBR1

86/94-2 Trip

TCM-2

ALARMBLOCK

TCSSCBR2

TCS(1)

TCS(2)

GUID-1B534756-98AC-408A-92F1-91ABA66E3A1C V1 EN

Figure 40: Trip circuit monitoring

3.4.3.3 Functional diagrams for control and interlocking

The trip signals from the protections described above are connected to the two tripoutput contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the correspondingMaster Trip Logics 86/94-1 and 86/94-2. The open control commands to the circuitbreaker from local or remote 52-1-exe_op (or from the autorecloser 79-open_cb, whenavailable) are connected directly to the output PO3 (X100:16-19).

1MAC109554 C Section 3REF615 variants

REF615 ANSI 67Application Manual

Page 74: ref615ansi_appl_109554_enc

MASTER TRIP 1 LOGIC

16

151918TCM-1

PO317

X100+

OR

OpenSignal to

86/94-1

TRIPCL_LKOUT

BLOCKTRIP

RST_LKOUT

With lock-out mode selection

TRPPTRC1

79 OPEN_CB

52 EXE_OP

Trip Coil 1

Breaker

2)

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

2) NON-LATCHED MODE AS DEFAULT.

Trip(1)51P Trip

67/50P-1 Trip

67/50P-2 Trip

50P-3 Trip

67/51P Trip

51N Trip

67/50N-2 Trip

67/50N-1 Trip

50N-3 Trip

49F Trip

50BF Retrip

AFD-1 Trip

AFD-3 Trip

AFD-2 Trip

46PD Trip

46-1 Trip

46-2 Trip

OR

1)

51G Trip

50G-3 Trip

50SEF Trip

67/51N Trip

87LOZREF Trip

GUID-280A62F0-6D51-4BA4-BFB9-B373E670AADD V1 EN

Figure 41: Master trip 1

Section 3 1MAC109554 CREF615 variants

68 REF615 ANSIApplication Manual

Page 75: ref615ansi_appl_109554_enc

22

23

24TCM-2

PO421

20

MASTER TRIP 2 LOGIC

20X100

+

OR

OpenSignal to

86/94-2

TRIP

CL_LKOUT

BLOCK

TRIP

RST_LKOUT

With lock-out mode selection

TRPPTRC2

79 OPEN_CB

52 EXE_OP

Trip Coil 2

Breaker

2)

NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.

2) NON-LATCHED MODE AS DEFAULT.

Trip(2)51P Trip

67/50P-1 Trip

67/50P-2 Trip

50P-3 Trip

67/51P Trip

51N Trip

67/50N-2 Trip

67/50N-1 Trip

50N-3 Trip

49F Trip

50BF Retrip

AFD-1 Trip

AFD-3 Trip

AFD-2 Trip

46PD Trip

46-1 Trip

46-2 Trip

OR

1)

51G Trip

50G-3 Trip

50SEF Trip

67/51N Trip

87LOZREF Trip

GUID-F8A675E1-1C31-4C83-9569-CCB85F9ABC0E V1 EN

Figure 42: Master trip 2

The 86/94-1 and 2 blocks provide the lockout/latching function, event generation andthe trip signal duration setting. If the lockout operation mode is selected, one binaryinput can be re-assigned to the RST_LKOUT input of the Master Trip Logics to enableexternal reset with a push button.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 69Application Manual

Page 76: ref615ansi_appl_109554_enc

BI 3 (Breaker Open Status)BI 2 (Breaker Close Status)

Always True

OR

67

PO1

+

X100

79 CLOSE_CB

CIRCUIT BREAKER CONTROL AND INTERLOCKING52-1 EXE_OP

52

SELECTEDENA_OPEN

ENA_CLOSE

BLK_OPEN

BLK_CLOSE

EXE_OP

EXE_CL

OPENPOS

CLOSEPOS

EXE_OP

EXE_CL

OPENPOS

CLOSEPOS

OKPOS

CBXCBR1

CloseBreaker

X110

56

7BI 4

BI 3PRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOW

TRV_T_OP_ALMTRV_T_CL_ALMDIFTRVTOPALMDIFTRVTCLALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINTERMPOSCLOSEPOS

BLOCKPOSOPEN

52CMCBCM

OR

LED8

(CB CONDMONITOR)

POSCLOSE

RST_CB_WEAR

CB Spring Charged

GAS Pressure Alarm

SSCBR1

I<->O CB

GUID-F6999B37-F933-43D0-967B-3FE127FE7811 V1 EN

Figure 43: Circuit breaker control and interlocking

The ENA_CLOSE input, which enables closing the circuit breaker, in the breakercontrol function block 52-1, is a combination of the status of the Master Trip Logics.The open operation is always enabled.

If the ENA_CLOSE signal is completely removed from the breakercontrol function block 52-1 with the Signal Matrix tool, the functionassumes that the breaker close commands are allowed continuously.

The circuit-breaker condition monitoring function (SSCBR) supervises the circuitbreaker status based on the binary input information connected and measured currentlevels. The function introduces various supervision methods. The correspondingsupervision alarm signals are routed to LED 8.

The signal outputs from the IED are connected to give dedicated information onpickups and trips.

• Pickup of any protection function SO1 (X100:10-12)• Trip of any protection function SO2 (X100:13-15)

Section 3 1MAC109554 CREF615 variants

70 REF615 ANSIApplication Manual

Page 77: ref615ansi_appl_109554_enc

COMMON PICKUP SIGNAL

LEDPTRC1

86/94 LED

TPGAPC1

TP-1

PICKUP

TRIP

PICKUP

TRIP

PICKUP

TRIP

PICKUP

TRIP

Pickup SignalSO#1 (X100:10-11-12)

1) THERE ARE FOUR PULSE TIMERS AVAILABLE-ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS.ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPEDFOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.

NOTE:

1)

Trip1 TP-1

GUID-17F7E87F-230E-496D-94C4-B188BA549CE9 V1 EN

Figure 44: Common pickup signal

The TP-1 is a timer and used for setting the minimum pulse length for the outputs.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 71Application Manual

Page 78: ref615ansi_appl_109554_enc

TRPPTRC1

PICKUP

TRIP

PICKUP

TRIP

TRPPTRC2

PICKUP

TRIP

PICKUP

TRIP

Trip SignalSO#2 (X100:13-14-15)

Trip(1)

Trip(2)

GUID-7E976C74-3F94-4023-89FD-0E62CC5766C6 V1 EN

Figure 45: Common trip signal

3.4.3.4 Functional diagram for voltage protections

Two overvoltage (59-1,59-2) protections, two undervoltage (27-1,27-2) protections,one residual overvoltage (59G) protection and one negative-sequence undervoltage(47) protection are provided for alarm purpose only in the default configuration. Userscan select any or all of the protections for tripping using the Signal Matrix tool.

Section 3 1MAC109554 CREF615 variants

72 REF615 ANSIApplication Manual

Page 79: ref615ansi_appl_109554_enc

OVER & UNDER VOLTAGE PROTECTION

OR

59-1

PICKUPBLOCK TRIP

3U>(1)PHPTOV1

59-2

PICKUPBLOCK TRIP

3U>(2)PHPTOV2

59G

PICKUPBLOCK TRIP

U0>(1)ROVPTOV1

27-1

PICKUPBLOCKTRIP

3U<(1)PHPTUV1

27-2

PICKUPBLOCK

TRIP

3U<(2)PHPTUV2

47

PICKUPBLOCK

TRIP

U2>NSPTOV1

LED8

OVER & UNDER VOLTAGE PROTECTION

60-Pickup

VA,VB,VC

VA,VB,VC

VA,VB,VC

VA,VB,VC

VA,VB,VC

VG

GUID-B8A1B7D7-4F8F-46CE-B2E2-D5AAD79D2219 V1 EN

Figure 46: Overvoltage, undervoltage, and negative sequence voltage protections

3.4.3.5 Functional diagram for optional ARC flash detection and autoreclosing

Optional ARC flash detectors (AFD 1-3) are included in the standard configuration.The ARC flash detection offers individual function blocks for each of the three ARCsensors that can be connected to the IED.

Each ARC protection function block has two different operation modes, with orwithout the phase current check.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 73Application Manual

Page 80: ref615ansi_appl_109554_enc

ARCSARC1

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODE

REM_FLT_ARC

IG

ARCSARC2

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODEREM_FLT_ARC

IG

ARCSARC3

TRIP

ARC_FLT_DET

IA, IB, IC

BLOCK

OPR_MODE

REM_FLT_ARC

IG

LED10

ARC(1)

ARC(2)

ARC(3)

GUID-19A57C71-5055-4521-AA56-C8BD5F51EDA3 V1 EN

Figure 47: Arc flash detection

Trip signals from the ARC protection function blocks are connected to the Master TripLogic and also to the alarm LED 10 as a common arc flash detection.

The autorecloser is configured to be initiated by operate signals from a number ofprotection stages through the INIT1-5 inputs. It is possible to create individualautoreclosing sequences for each input.

Section 3 1MAC109554 CREF615 variants

74 REF615 ANSIApplication Manual

Page 81: ref615ansi_appl_109554_enc

46-1 -trip46-2 -trip

AFD-1 -trip52 -selected

AFD-2 -tripAFD-3 -trip

AUTORECLOSING (Optional)

X120 BI 3 (CB Open)

OR

CB_RDYCB_POS

THERMOVL_BLK

INHIBIT_RECL

ON/OFF

DEL_INIT_4

DEL_INIT_3

DEL_INIT_2

INIT_6

INIT_5

INIT_4

INIT_3

INIT_2

INIT_1

DARREC1

OPEN CB

79

CLOSE CB

INPRO

UNSUC_RECL

AR_ON

LOCKED

LED 7

RECLOSER LOCKOUT

External AR Blocking X120 BI 4

51P -trip51N -trip OR

50P-3 -trip50N-3 -trip

OR

PROT_CRD

O->I51G -trip

50G-3 -trip

67/50N-1 -trip67/50N-2 -trip

67/50P-1 -trip67/50P-2 -trip OR

67/51P -trip67/51N -trip OR

49F -InhRec

NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.

GUID-FE025888-1CCB-4B71-9BB5-2F188592AE62 V1 EN

Figure 48: Autoreclosing

The autoreclosing function can be blocked with the INHIBIT_RECL input. As adefault, the operation of some selected protection functions is connected to this input.A control command to the circuit breaker, either local or remote, will also block theautoreclose function via the 52-1-selected signal.

The circuit breaker availability for the autoreclosure sequence is expressed with theCB_RDY input in 79. In the configuration, this signal is not connected to any of thebinary inputs. As a result, the function assumes that the breaker is available all the time.

3.4.3.6 Functional diagram for optional additional ground overcurrent protection

Optional additional ground overcurrent protection provides more sensitive groundovercurrent protection when necessary.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 75Application Manual

Page 82: ref615ansi_appl_109554_enc

EFLPTOC1PICKUPIG

BLOCK

ENA_MULT

51G

EFIPTOC1PICKUPIG

BLOCK

ENA_MULT

50G-3

TRIP_NEUT

86/94LED

TRIP_NEUT

OR

LED4

TRIP

TRIP

TRIPNEUTRAL / GROUND

TRIP(1)

OR

LED 6

TIME TRIP

INSTANTANEOUS

GROUND OVERCURRENT PROTECTION (OPTIONAL)

BI 1 (Blocking)

LED5

TRIP

LEDPTRC

I0>(1)

I0>>>(1)

GUID-C91BD513-143F-4154-A045-399457B2D796 V1 EN

Figure 49: Ground overcurrent protection

3.4.3.7 Optional sensitive earth fault and high impedance fault detection

TRIP

TRIP

TRIPNEUTRAL / SEF

EFLPTOC3

PICKUP

BLOCK

50SEF

TRIP

IG

SENSITIVE EARTH FAULT PROTECTION

EFLPTOC2PICKUP

BLOCK

51N

EFIPTOC2

PICKUP

BLOCK

50N-3

OR

LED4

I0>(3)

I0>(2)

I0>>>(2)

FROM DIRECTIONAL GROUND FAULT PROTECTION

GUID-D9DBE355-6C7A-4D42-A679-CF3C2FAD22B9 V1 EN

Figure 50: Sensitive earth-fault protection

Section 3 1MAC109554 CREF615 variants

76 REF615 ANSIApplication Manual

Page 83: ref615ansi_appl_109554_enc

LED11

HIZ DETECTION

BLOCK

PHIZ1

TRIP

PHIZ1

GUID-81DC07F7-4A53-4918-8FDD-66BD24B6A191 V1 EN

Figure 51: High impedance fault detection

The sensitive earth-fault protection (50SEF) and high impedance fault detection (HIZ)provide protection against high impedance faults. If the load unbalance is high, 50SEFneeds to be set high to avoid misoperations which renders 50SEF ineffective for suchapplications. In those cases, HIZ can provide detection which would otherwise beundetected.

1MAC109554 C Section 3REF615 variants

REF615 ANSI 77Application Manual

Page 84: ref615ansi_appl_109554_enc

78

Page 85: ref615ansi_appl_109554_enc

Section 4 Requirements for measurementtransformers

4.1 Current transformers

4.1.1 Current transformer requirements for non-directionalovercurrent protectionFor reliable and correct operation of the overcurrent protection, the CT has to bechosen carefully. The distortion of the secondary current of a saturated CT mayendanger the operation, selectivity, and co-ordination of protection. However, when theCT is correctly selected, a fast and reliable short circuit protection can be enabled.

The selection of a CT depends not only on the CT specifications but also on thenetwork fault current magnitude, desired protection objectives, and the actual CTburden. The protection settings of the IED should be defined in accordance with theCT performance as well as other factors.

Appropriate 'C' class CT should be used based on the total resistances of the CTsecondary circuit. If other accuracy class CTs are used then refer the followingdiscussions.

4.1.1.1 Current transformer accuracy class and accuracy limit factor

The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primarycurrent to the rated primary current. For example, a protective current transformer oftype 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protectivecurrent transformers, the accuracy class is designed by the highest permissiblepercentage composite error at the rated accuracy limit primary current prescribed forthe accuracy class concerned, followed by the letter "P" (meaning protection).

Table 22: Limits of errors according to IEC 60044-1 for protective current transformers

Accuracy class Current error atrated primarycurrent (%)

Phase displacement at rated primarycurrent

Composite error atrated accuracy limitprimary current (%)minutes centiradians

5P ±1 ±60 ±1.8 5

10P ±3 - - 10

1MAC109554 C Section 4Requirements for measurement transformers

REF615 ANSI 79Application Manual

Page 86: ref615ansi_appl_109554_enc

The accuracy classes 5P and 10P are both suitable for non-directional overcurrentprotection. The 5P class provides a better accuracy. This should be noted also if thereare accuracy requirements for the metering functions (current metering, powermetering, and so on) of the IED.

The CT accuracy primary limit current describes the highest fault current magnitude atwhich the CT fulfils the specified accuracy. Beyond this level, the secondary current ofthe CT is distorted and it might have severe effects on the performance of theprotection IED.

In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limitfactor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden.

The actual accuracy limit factor is calculated using the formula:

F FS S

S Sa n

in n

in

≈ ×

+

+

A071141 V1 EN

Fn the accuracy limit factor with the nominal external burden Sn

Sin the internal secondary burden of the CT

S the actual external burden

4.1.1.2 Non-directional overcurrent protection

The current transformer selectionNon-directional overcurrent protection does not set high requirements on the accuracyclass or on the actual accuracy limit factor (Fa) of the CTs. It is, however,recommended to select a CT with Fa of at least 20.

The nominal primary current I1n should be chosen in such a way that the thermal anddynamic strength of the current measuring input of the IED is not exceeded. This isalways fulfilled when

I1n > Ikmax / 100,

Ikmax is the highest fault current.

The saturation of the CT protects the measuring circuit and the current input of theIED. For that reason, in practice, even a few times smaller nominal primary current canbe used than given by the formula.

Section 4 1MAC109554 CRequirements for measurement transformers

80 REF615 ANSIApplication Manual

Page 87: ref615ansi_appl_109554_enc

Recommended pickup current settingsIf Ikmin is the lowest primary current at which the highest set overcurrent stage is totrip, the pickup current should be set using the formula:

Current pickup value < 0.7 x (Ikmin / I1n)

I1n is the nominal primary current of the CT.

The factor 0.7 takes into account the protection IED inaccuracy, current transformererrors, and imperfections of the short circuit calculations.

The adequate performance of the CT should be checked when the setting of the highset stage overcurrent protection is defined. The trip time delay caused by the CTsaturation is typically small enough when the overcurrent setting is noticeably lowerthan Fa.

When defining the setting values for the low set stages, the saturation of the CT doesnot need to be taken into account and the pickup current setting is simply according tothe formula.

Delay in operation caused by saturation of current transformersThe saturation of CT may cause a delayed IED operation. To ensure the timeselectivity, the delay must be taken into account when setting the trip times ofsuccessive IEDs.

With definite time mode of operation, the saturation of CT may cause a delay that is aslong as the time the constant of the DC component of the fault current, when thecurrent is only slightly higher than the pickup current. This depends on the accuracylimit factor of the CT, on the remanence flux of the core of the CT, and on the trip timesetting.

With inverse time mode of operation, the delay should always be considered as beingas long as the time constant of the DC component.

With inverse time mode of operation and when the high-set stages are not used, the ACcomponent of the fault current should not saturate the CT less than 20 times the pickupcurrent. Otherwise, the inverse operation time can be further prolonged. Therefore, theaccuracy limit factor Fa should be chosen using the formula:

Fa > 20*Current pickup value / I1n

The Current pickup value is the primary pickup current setting of the IED.

1MAC109554 C Section 4Requirements for measurement transformers

REF615 ANSI 81Application Manual

Page 88: ref615ansi_appl_109554_enc

4.1.1.3 Example for non-directional overcurrent protection

The following figure describes a typical medium voltage feeder. The protection isimplemented as three-stage definite time non-directional overcurrent protection.

A071142-ANSI V2 EN

Figure 52: Example of three-stage overcurrent protection

The maximum three-phase fault current is 41.7 kA and the minimum three-phase shortcircuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be59.

The pickup current setting for low-set stage (51P) is selected to be about twice thenominal current of the cable. The trip time is selected so that it is selective with thenext IED (not visible in the figure above). The settings for the high-set stage andinstantaneous stage are defined also so that grading is ensured with the downstreamprotection. In addition, the pickup current settings have to be defined so that the IEDoperates with the minimum fault current and it does not trip with the maximum loadcurrent. The settings for all three stages are as in the figure above.

For the application point of view, the suitable setting for instantaneous stage (50P-3) inthis example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, thecriteria given by the current transformer selection formula is fulfilled and also the IEDsetting is considerably below the Fa. In this application, the CT rated burden couldhave been selected much lower than 10 VA for economical reasons.

Section 4 1MAC109554 CRequirements for measurement transformers

82 REF615 ANSIApplication Manual

Page 89: ref615ansi_appl_109554_enc

Section 5 IED physical connections

5.1 Inputs

5.1.1 Energizing inputs

5.1.1.1 Phase currents

The IED can also be used in single or two-phase applications byleaving one or two energizing inputs unoccupied. However, at leastterminals X120/7-8 must be connected.

Table 23: Inputs for phase currents

Terminal DescriptionX120-7, 8 IA

X120-9, 10 IB

X120-11, 12 IC

5.1.1.2 Ground current

Table 24: Inputs for ground current

Terminal DescriptionX120-13, 14 IG

5.1.1.3 Phase voltages

Table 25: Phase voltage input included in configuration FA02

Terminal DescriptionX130-11, 12 VA

X130-13, 14 VB

X130-15, 16 VC

1MAC109554 C Section 5IED physical connections

REF615 ANSI 83Application Manual

Page 90: ref615ansi_appl_109554_enc

5.1.1.4 Ground voltage

Table 26: Additional ground voltage input included in configuration FA02

Terminal DescriptionX130-17, 18 VG

5.1.2 Auxiliary supply voltage inputThe auxiliary voltage of the IED is connected to terminals X100/1-2. At DC supply,the positive lead is connected to terminal X100-1. The permitted auxiliary voltagerange is marked on the LHMI of the IED on the top of the HMI of the plug-in unit.

Table 27: Auxiliary voltage supply

Terminal DescriptionX100-1 + Input

X100-2 - Input

5.1.3 Binary inputsThe binary inputs can be used, for example, to generate a blocking signal, to unlatchoutput contacts, to trigger the digital fault recorder or for remote control of IEDsettings.

Terminals X120/1-6 are binary input terminals. An additional BIO module can beincluded in slot 110.

Table 28: Binary input terminals X110-1...13 included in configurations FA01 and FA02

Terminal DescriptionX110-1 BI1, +

X110-2 BI1, -

X110-3 BI2, +

X110-4 BI2, -

X110-5 BI3, +

X110-6 BI3, -

X110-6 BI4, -

X110-7 BI4, +

X110-8 BI5, +

X110-9 BI5, -

X110-9 BI6, -

Table continues on next page

Section 5 1MAC109554 CIED physical connections

84 REF615 ANSIApplication Manual

Page 91: ref615ansi_appl_109554_enc

Terminal DescriptionX110-10 BI6, +

X110-11 BI7, +

X110-12 BI7, -

X110-12 BI8, -

X110-13 BI8, +

Table 29: Binary input terminals X120-1...6

Terminal DescriptionX120-1 BI1, +

X120-2 BI1, -

X120-3 BI2, +

X120-2 BI2, -

X120-4 BI3, +

X120-2 BI3, -

X120-5 BI4, +

X120-6 BI4, -

Table 30: Binary input terminals X130-1...9, optional configuration FA01

Terminal DescriptionX130-1 BI1, +

X130-2 BI1, -

X130-2 BI2, -

X130-3 BI2, +

X130-4 BI3, +

X130-5 BI3, -

X130-5 BI4, -

X130-6 BI4, +

X130-7 BI5, +

X130-8 BI5, -

X130-8 BI6, -

X130-9 BI6, +

1MAC109554 C Section 5IED physical connections

REF615 ANSI 85Application Manual

Page 92: ref615ansi_appl_109554_enc

5.1.4 Optional light sensor inputsIf the IED is provided with the optional communication module with light sensorinputs, the pre-manufactured lens-sensor fibers are connected to inputs X13, X14 andX15, see the terminal diagrams.For further information, see arc flash detector.

The IED is provided with connection sockets X13, X14 and X15 only ifthe optional communication module with light sensor inputs has beeninstalled. If the arc flash detector option is selected when ordering anIED, the light sensor inputs are included in the communication module.

Table 31: Light sensor input connectors

Terminal DescriptionX13 Input Light sensor 1

X14 Input Light sensor 2

X15 Input Light sensor 3

5.2 Outputs

5.2.1 Outputs for tripping and controllingOutput contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable ofcontrolling most circuit breakers. On delivery from the factory, the trip signals from allthe protection stages are routed to PO3 and PO4.

Table 32: Output contacts

Terminal DescriptionX100-6 PO1, NO

X100-7 PO1, NO

X100-8 PO2, NO

X100-9 PO2, NO

X100-15 PO3, NO (TCM resistor)

X100-16 PO3, NO

X100-17 PO3, NO

X100-18 PO3 (TCM1 input), NO

X100-19 PO3 (TCM1 inputr), NO

X100-20 PO4, NO (TCM resistor)

X100-21 PO4, NO

Table continues on next page

Section 5 1MAC109554 CIED physical connections

86 REF615 ANSIApplication Manual

Page 93: ref615ansi_appl_109554_enc

Terminal DescriptionX100-22 PO4, NO

X100-23 PO4 (TCM2 input), NO

X100-24 PO4 (TCM2 input), NO

5.2.2 Outputs for signallingOutput contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot X110 orSO1, SO2 and SO3 in slot X130 (optional) can be used for signalling on pickup andtripping of the IED. On delivery from the factory, the pickup and alarm signals from allthe protection stages are routed to signalling outputs.

Output contacts of slot X110 are optional. Output contacts of slot X130 are available inthe optional BIO module (BIOB02A).

Table 33: Output contacts X100-10...14

Terminal DescriptionX100-10 SO1, common

X100-11 SO1, NC

X100-12 SO1, NO

X100-13 SO2, NO

X100-14 SO2, NO

Table 34: Output contacts X110-14...24

Terminal DescriptionX110-14 SO1, common

X110-15 SO1, NO

X110-16 SO1, NC

X110-17 SO2, common

X110-18 SO2, NO

X110-19 SO2, NC

X110-20 SO3, common

X110-21 SO3, NO

X110-22 SO3, NC

X110-23 SO4, common

X110-24 SO4, NO

1MAC109554 C Section 5IED physical connections

REF615 ANSI 87Application Manual

Page 94: ref615ansi_appl_109554_enc

Table 35: Output contacts X130-10...18

Terminal DescriptionX130-10 SO1, common

X130-11 SO1, NO

X130-12 SO1, NC

X130-13 SO2, common

X130-14 SO2, NO

X130-15 SO2, NC

X130-16 SO3, common

X130-17 SO3, NO

X130-18 SO3, NC

5.2.3 IRFThe IRF contact functions as an output contact for the self-supervision system of theprotection IED. Under normal operating conditions, the IED is energized and thecontact is closed (X100/3-5). When a fault is detected by the self-supervision system orthe auxiliary voltage is disconnected, the output contact drops off and the contactcloses (X100/3-4).

Table 36: IRF contact

Terminal DescriptionX100-3 IRF, common

X100-4 Closed; IRF, or Vaux disconnected

X100-5 Closed; no IRF, and Vaux connected

Section 5 1MAC109554 CIED physical connections

88 REF615 ANSIApplication Manual

Page 95: ref615ansi_appl_109554_enc

Section 6 Glossary

100BASE-FX A physical media defined in the IEEE 802.3 Ethernet standardfor local area networks (LANs) that uses fibre-optic cabling

100BASE-TX A physical media defined in the IEEE 802.3 Ethernet standardfor local area networks (LANs) that uses twisted-pair cablingcategory 5 or higher with RJ-45 connectors

ANSI American National Standards InstituteBI Binary inputBI/O Binary input/outputBO Binary outputCB Circuit breakerCT Current transformerDFR Digital fault recorderDNP3 A distributed network protocol originally developed by

Westronic. The DNP3 Users Group has the ownership of theprotocol and assumes responsibility for its evolution.

EMC Electromagnetic compatibilityGOOSE Generic Object Oriented Substation EventHMI Human-machine interfaceHW HardwareIEC 61850 International standard for substation communication and

modellingIED Intelligent electronic deviceIP address A set of four numbers between 0 and 255, separated by

periods. Each server connected to the Internet is assigned aunique IP address that specifies the location for the TCP/IPprotocol.

IRIG-B Inter-Range Instrumentation Group's time code format BLAN Local area networkLC Connector type for glass fiber cableLCD Liquid crystal display

1MAC109554 C Section 6Glossary

REF615 ANSI 89Application Manual

Page 96: ref615ansi_appl_109554_enc

LED Light-emitting diodeLHMI Local human-machine interfaceModbus A serial communication protocol developed by the Modicon

company in 1979. Originally used for communication in PLCsand RTU devices.

MV Medium voltagePCM600 Protection and Control IED ManagerPO Power outputRJ-45 Galvanic connector typeRS-232 Serial interface standardRS-485 Serial link according to EIA standard RS485SO Signal outputTCP/IP Transmission Control Protocol/Internet ProtocolTCS Trip-circuit supervisionWAN Wide area networkWHMI Web human-machine interface

Section 6 1MAC109554 CGlossary

90 REF615 ANSIApplication Manual

Page 97: ref615ansi_appl_109554_enc

91

Page 98: ref615ansi_appl_109554_enc
Page 99: ref615ansi_appl_109554_enc
Page 100: ref615ansi_appl_109554_enc

Contact us

ABB Inc.Distribution Automation4300 Coral Ridge DriveCoral Springs, FL 33065, USAPhone +1 (800) 523-2620Phone +1 954-752-6700Fax +1 954 345-5329

www.abb.com/substationautomation

1MA

C10

9554

Cop

yrig

ht 2

010

AB

B. A

ll rig

hts

rese

rved

.