i Prepared by UL LLC Project 4789065953, MH60915 for Mauser Packaging Solutions July 24, 2019 Copyright © 2019 UL LLC REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE BULK CONTAINERS (IBCs)

REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

i

Prepared by UL LLC

Project 4789065953, MH60915 for

Mauser Packaging Solutions July 24, 2019

Copyright © 2019 UL LLC

REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE BULK

CONTAINERS (IBCs)

Page 2: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

i

Executive Summary

The test described in this report was conducted for the Mauser Packaging Solutions at UL’s

Large Fire Test Facility located in Northbrook, IL. The fire exposure testing described herein

was conducted on composite IBC’s manufactured by Mauser that were constructed to be in

compliance with ANSI/UL 2368, Standard for Fire Exposure Testing of Rigid Nonmetallic and

Composite Nonmetallic Intermediate Bulk Containers for Combustible Liquids dated October

10, 2018.

One fire performance test was conducted in general accordance with ANSI/UL 2368, except

that the IBCs were filled with heptane (a flammable liquid having a nominal flash point of 25°F)

rather than mineral seal oil within 48 hours of the fire test. This test was conducted to generate

fire test data on a liquid having a higher vapor pressure and lower flash point compared to

mineral seal oil when stored within an IBC constructed to comply with ANSI/UL 2368.

During and after this test, there was no leakage from the IBCs. The IBCs maintained their

structural integrity such that the measured stack lean was approximately 2 degrees from the

vertical plane.

This test data shall not be used to substantiate the acceptability of these IBCs for use with

flammable liquids.

Page 3: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

ii

Note:

This report was prepared as an account of work sponsored by Mauser Packaging Solutions. In

no event shall UL LLC be responsible to anyone for whatever use or non-use is made of the

information contained in this Report and in no event shall UL LLC, or its agents, incur any

obligation or liability for damages, including, but not limited to consequential damages arising

out of or in connection with the use of, or inability to use, the information contained in this

Report.

Page 4: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

iii

Table of Contents

1. GENERAL ......................................................................................................................... 1

2. SAMPLES .......................................................................................................................... 1

3. TEST METHOD ............................................................................................................... 4

4. RESULTS ........................................................................................................................ 10

5. SUMMARY ..................................................................................................................... 13

Table of Figures

FIGURE 1 - TOP VIEW ................................................................................................................... 2 FIGURE 2 - OBLIQUE VIEW .......................................................................................................... 3 FIGURE 3 – REDUCED SCALE FIRE TEST ARRANGEMENT – ELEVATION VIEW ............................. 5 FIGURE 4 – REDUCED SCALE FIRE TEST ARRANGEMENT – PLAN VIEW – DETAIL ....................... 6 FIGURE 5 – PHOTOGRAPH OF TEST ARRANGEMENT ..................................................................... 7 FIGURE 6 – PHOTOGRAPH OF TEST DURING 1 MINUTE FREE BURN ............................................... 8 FIGURE 7 – PHOTOGRAPH OF TEST 15 MINUTES AFTER SPRINKLER DISCHARGE .......................... 9 FIGURE 8 – POST TEST – VIEW FROM NORTHWEST .................................................................... 10 FIGURE 9 - POST TEST – VIEW FROM EAST – SHOWING DOGHOUSE AREAS CENTRAL TO THE BASE

OF EACH IBC ...................................................................................................................... 11 FIGURE 10 - POST TEST – VIEW OF VALVE INSIDE DOGHOUSE FOR UPPER UNIT ....................... 12 FIGURE 11 - POST TEST – VIEW OF VALVE INSIDE DOGHOUSE FOR LOWER UNIT ...................... 12

Page 5: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 1 of 13

1. GENERAL

Mauser Packaging Solutions supplied all of the test samples for testing by UL.

The issuance of this report in no way implies that a UL Classified IBC is suitable for use

with flammable liquids.

Due to the nature of this investigation, it is understood that you will not use the name of

UL LLC, any abbreviation thereof, or symbol therefore, nor permit such use by others, in

connection with the release, publication, or other dissemination of the information obtained

under this application, unless specifically authorized in writing by UL LLC.

The sole purpose of this investigation is to subject two UL Classified, heptane filled IBCs

to a reduced-scale fire test and report the results. No conclusions have been made from the

data obtained. The information obtained by this investigation is being submitted to Mauser

Packaging Solutions for their use.

2. SAMPLES

Two samples were tested in accordance with the method stated below.

The samples were submitted by Mauser Packaging Solutions.

Representative photographs of the samples can be seen in Figures 1 and 2.

UL LLC did not select the samples nor witness the production of the test samples, however

Mauser Packaging Solutions has indicated that they were produced in accordance with the

UL follow-up service procedure for their UL Classified SM 13 EX UL design.

The test results apply only to the actual samples tested by UL.

Page 6: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 2 of 13

Figure 1 - Top View

Page 7: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 3 of 13

Figure 2 - Oblique View

Page 8: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 4 of 13

3. TEST METHOD

Reduced-Scale Fire Performance Test

The reduced-scale fire performance test was conducted in an enclosed test cell having a

smooth, flat 30-ft (9.2-m) high ceiling. A sprinkler system utilizing four open K=11

nominal 5/8-in (1.6-cm) orifice upright style sprinklers were installed on a nominal 8-by-

10 ft. (2.4-by-2.5 m) spacing and installed with the sprinkler deflectors 3 inches (76.2 mm)

below the ceiling. The piping system was supplied with water under adequate pressure and

flow to maintain a 0.60-gpm/ft2 discharge density.

A 50-ft2 (4.6-m2) square steel test tray at least 10 inches high was centered below the four

sprinklers and fitted with a solid flat steel platform to provide a 2 ft. open area along 2

adjacent sides of the tray. See Figures 3 and 4.

Water was added to the tray so as to maintain a liquid level within 1 - 2 inches (2.5 - 5.0

cm) below the platform which was resting directly on top of the tray. The test tray was then

fitted with a fuel supply pipe with the discharge end positioned at least 1 inch (2.5 cm)

below the water surface.

Page 9: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 5 of 13

Figure 3 – Reduced Scale Fire Test Arrangement – Elevation View

Page 10: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 6 of 13

Figure 4 – Reduced Scale Fire Test Arrangement – Plan View – Detail

Two IBCs identified in the sample section were filled to capacity with heptane. The IBC

was labeled with a 275 gallon capacity. The IBCs were then stacked one on top of the

other and positioned on the edge of the test platform as shown in Figure 4 and Figure 5.

One of the exposed sides of each IBC contained the outlet valve housing (doghouse).

Heptane was allowed to flow into the test tray at 2-gpm for 3 minutes. The heptane was

then ignited and the 2 gpm heptane flow maintained for the duration of the test. One minute

after ignition, water was discharged from the open sprinklers to provide a design density

of 0.60 gpm/ft2. The tray was fitted with a drain located near the bottom and arranged in

such a manner that the liquid level in the tray was maintained within 1 - 2 inches of the

bottom of the platform for the entire duration of the test.

The test was conducted for a total of 20 minutes, or until there was evidence of leakage or

loss of structural integrity of either IBC. If no leakage or loss of structural integrity was

observed, the heptane fuel flow was to be shut off and the pool fire extinguished within 1

minute after test termination. Each IBC was then to be examined for any signs of leakage.

A photograph of the test arrangement can be seen in Figure 5.

Photographs during the fire test can be seen in Figures 6 and 7.

Page 11: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 7 of 13

Figure 5 – Photograph of Test Arrangement

Page 12: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 8 of 13

Figure 6 – Photograph of Test During 1 minute Free burn

(from backside of test arrangement)

Page 13: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 9 of 13

Figure 7 – Photograph of Test 15 minutes after Sprinkler Discharge

(from backside of test arrangement)

Page 14: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 10 of 13

4. RESULTS

The test was conducted for 20 minutes after ignition with no noticeable leakage in either

the bottom or top IBCs. The residual fires were extinguished within a minute after

termination of the test.

Figure 8 and Figure 9 show the samples in the test pan after completion of the test.

Figure 8 – Post Test – View from Northwest

Page 15: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 11 of 13

Figure 9 - Post Test – View from East – Showing Doghouse Areas Central to the Base of

each IBC

Figures 10 and 11 show the units valves after the insulative materials were removed.

Page 16: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 12 of 13

Figure 10 - Post Test – View of Valve Inside Doghouse for Upper Unit

Figure 11 - Post Test – View of Valve Inside Doghouse for Lower Unit

Page 17: REDUCED SCALE FIRE TEST - HEPTANE FILLED INTERMEDIATE …

Issued: July 24, 2019

Page 13 of 13

5. SUMMARY

The fire exposure testing described herein was conducted on composite IBC’s

manufactured by Mauser that were constructed to be in compliance with ANSI/UL 2368,

Standard for Fire Exposure Testing of Rigid Nonmetallic and Composite Nonmetallic

Intermediate Bulk Containers for Combustible Liquids dated October 10, 2018.

One fire performance test was conducted in general accordance with ANSI/UL 2368,

except that the IBCs were filled with heptane (a flammable liquid having a nominal flash

point of 25°F) rather than mineral seal oil within 48 hours of the fire test. This test was

conducted to generate fire test data on liquid having a higher vapor pressure and lower

flash point compared to mineral seal oil when stored within an IBC constructed to comply

with ANSI/UL 2368.

The following are the acceptance criteria for ANSI/UL 2368, Reduced Scale Fire Test:

Leakage:

Requirement: There is to be no leakage as defined by loss of liquid from the IBC

at a location below its full liquid level. The units are to be examined 24 hours after

completion of the test for any sign of leakage.

Result: There was no leakage from either unit that resulted in a loss of heptane.

Structural Integrity:

Requirement: The IBC shall remain in an upright position without toppling over

or leaning more than 5 degrees from a vertical plane.

Result: The units did not topple over during the test. The post test measurement

on the upper IBC which had the highest amount of leaning was 2 degrees from

vertical.

This test data shall not be used to substantiate the acceptability of these IBCs for use with

flammable liquids.