® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 1
=Rectifier Hariff APR 3G (System -48)=
Tampilan Hardware
MCB DC Load Priority MCB DC LoadNon Priorit
MCB Input TeganganAC 3 Phasa MCB AC Load
Distribution MCB Baterai
Modul "SC200" (SM45 nya APR 3G)
** APR System +24 VDC & APR System -48VDC : Prinsip Kerja : System Kontaktor
Maksudnya Saat LVD disconnect makaKontaktornya Terbuka sehingga mati site nya
Sehingga harus bypass LVD Modul Control : Modul SM 45 ** APR 3G (System -48 VDC) : Prinsip Kerja : System Latch
Maksudnya Saat LVD disconnect makakontaktor tetap nyambung sehingga nggakMati site nya
Sehingga nggak perlu bypass LVD Untuk men-disconnectkan LVD maka
kita harus disconnect manual by software Modul Control : Modul SC200
Modul Relay (Modul LVD Driver)
Koneksi RelayAlarm EAS
Kontaktor Non Priority(Sudah di Bypass)
Kontaktor NonPriority (Sudah di
Bypass)
KontaktorPriority (Sudah
di Bypass)
Kabel BypassKontaktor Baterai
KabelBypassKontaktor Non
Priority
Untuk BSC,Kontaktor Load
Priority & Bateraisudah di Bypasskedua-dua nya
Kontaktor Priority(Sudah di Bypass)
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
2/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 2
Kabel Menuju MCB DCLoad Priorit MCB DC Load Priority
MCB DC Load
Non Priority
Kabel Menuju MCBDC Load Non Priority
Modul "SC200" (SM 45 nya APR 3G) = TampakBelakang
Modul "SC 200" (SM 45 nya APR 3G) = TampakBelakang
Bar Live (-) - Negatif
Output (+) Positif dariBack lane rectifier
Output (-) Negatif dariBackplane rectifier
Input Tegangan ACdari Main MCB AC
Bar Common (+),Positif (load + Baterai)
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
3/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 3
Tampilan Menu
Kontaktor LVD 1 (Non Priority) dan LVD 2 (Baterai) Tampak atas.
LVD 2, KontaktorBaterai
LVD 1, Load Non-priority
Konektor Coil LVD
Konektor AuxilaryLVD
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
4/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 4
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
5/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 5
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
6/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 6
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
7/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 7
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
8/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 8
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
9/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 9
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
10/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 10
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
11/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 11
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
12/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 12
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
13/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 13
APR 3G System 48V: LVD1 Disconnect = 46.00 Volt LVD1 Reconnect = 51.00 Volt LDV2 Disconnect = 43.20 Volt LVD2 Reconnect = 48.00 Volt
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
14/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 14
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
15/16
8/17/2019 Rectifier Hariff APR 3G (Sys -48 Volt) = Tampilan & Menu
16/16
® Narko (Aftersales– Hariff Bandung)Sharing Session FMC Technical Support & Vendor Maintenance Page 16