    OSMOSM AUTOMATICCIRCUIT RECLOSER15kV, 27kV & 38kV MOdELS

    PRODUCT GUIDE

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    2/8

    Introduction

    The OSM15, OSM27 an OSM38 automaticcircuit reclosers are esigne for use on overhea

    istribution lines as well as istribution substation

    applications for all voltage classes up to 15V, 27V

    an 38V respectively.

    The OSM tans are manufacture from stainless

    steel an power coate a light grey colour.

    The prouct is supplie complete with an RC control

    an communications cubicle. The RC control cubicleis a microprocessor base controller that provies

    all the protection, ata logging an communications

    functions in a single evice. The OSM has been

    esigne for use as a stan alone evice that is easily

    integrate into istribution automation an remote

    control schemes using the in-built communications

    capability.

    The prouct has been extensively type teste

    by inepenent laboratories to ensure long life

    an reliability uner the harshest environmental

    conitions. The OSM automatic circuit recloser is

    the only soli i-electric insulate recloser to provie

    controlle arc fault venting an the inepenent

    testing provies verification of this important safety

    feature.

    The prouct uses technology evelope an refine

    over the last ecae.

    The in-built user configurable istribution automation

    OSM recloser an RC Control an Communications Cubicle

    OSM15 Autorecloser OSM27 Autorecloser

    INTROdUCTION

    functionality can be use with or without a

    communications system an will reuce outage

    time an increase profitability in your networ.

    1. Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

    OSM38 Autorecloser

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    3/8

    Introduction 1.2.

    The OSM15, OSM27 an OSM38 automatic circuit

    reclosers incorporate vacuum interrupters insiea polycarbonate an an aromatic epoxy resin

    housing within an arc vente stainless steel tan

    respectively. This ensures the maximum in life an

    reliability with a fully insulate arrangement insie

    the long life housing.

    Voltage is measure on all six (6) bushings usingcapacitively couple screens. Current is measureon all three (3) phases using current transformers.

    The recloser mechanism is operate by three (3)separate magnetic actuators, one per phase. Thesemagnetic actuators are mechanically interloceto guarantee correct three (3) phase operation.The evice is latche in the close position bymagnetic latching. Each magnetic actuator usesa single coil.

    The recloser can be mechanically trippe using

    the yellow mechanical hoo stic operate lever

    in the base of the tan. The evice Open/Close

    inication, also locate in the base of the tan,

    uses a green 0 to esignate contacts are openan a re I to esignate contacts close.

    OVERVIEW

    The status of the recloser is also reflecte by a

    microswitch connecte to the control electronics.The electronic circuit boar where the microswitch

    is fitte has no active elements which ramatically

    improves impulse immunity.

    The main circuit bushings are manufacture from

    UV stable polymer encapsulate in silicone rubber

    an have a silicone rubber bushing boot proviing

    the require creepage istance.

    The magnetic actuators are operate from store

    energy charge capacitors locate in the RC10control cubicle. There is a rating plate locate

    in the base of the tan that provies tan rating

    etails in accorance with the requirements of

    ANSI C37.60. There is an earthing point on the

    sie of the tan.

    The OSM is supplie with tin plate brass cable

    connectors on each bushing. The cable connectors

    can be supplie in the form of tunnel terminals to

    suit cable up to 260mm2or 2 hole NEMA cable

    palms.

    The cross sectional iagram below etails the

    OSM tan configuration an main components.

    1. Bushing Connector2. Silicone Rubber Bushing Boot3. Polymer Bushing4. Current Transformers5. Capacitively Couple Voltage Sensor6. Stainless Steel Tan

    7. Magnetic Actuator

    8. Opening Spring9. Auxiliary Switches10. Insulate drive Ro11 . Polycarbonate Housing12. Vacuum Interrupter13. Ceramic Breather

    14. Mechanical trip Ring15. Vacuum interrupter

    16. Push ro - insulating17. Actuator18. Epoxy housing19. Silicone bushing extension20. Terminal21. Tan

    22. Auxiliary switches

    Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

    OSM38 Cross Sectional diagramOSM15 OSM27 Cross Sectional diagram

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    4/8

    Introduction3. Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

    The RC10 control an communications cubicle isa microprocessor base controller that provies airectional overcurrent, earth fault an sensitiveearth fault relay, auto reclosing relay, instantaneousmetering, event log, eman logger an remoteterminal unit (RTU) for remote control in a singlepacage.

    The operator control panel is provie with a largebaclit LCd isplay an eypa to provie localcontrol functions.

    The control cubicle has three (3) main moules:

    The operator panel moule which proviesthe man machine interface.

    The Switchgear Interface Moule (SIM) whichprovies the power supply battery chargeran incorporates the capacitors that proviethe tripping an closing energy to the OSMtan.

    The Relay moule which provies the mainmicroprocessor an dSP functionality.

    Temperature compensate float charging isprovie to the seale lea aci batteries locate

    in the RC10 control cubicle.

    There is space provie insie the control cubicleto install any communications equipment to beconnecte to the inbuilt RTU or I/O moule.

    The equipment has been esigne for the RC10control cubicle to operate over a temperature rangeof -40 to +55C insie the IP65 seale enclosure.

    The cubicle is constructe out of power coatestainless steel for a long, maintenance free lifetime.

    RC10 CONTROL &

    COMMUNICATIONS CUBICLE

    The roof features a ceramic base insulatingcoating that provies a 16C reuction in internaltemperature when the cubicle is expose to 1.1Wof solar raiation.

    The entry point for the control cable is housewithin a vanal-proof enclosure an the cubicleoor has a three point hanle locing mechanismmaing it extremely ifficult to brea into.

    RC10 Control &Communications Cubicle

    IP65/NEMA 4 Vanal proofcable housing

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    5/8

    Introduction 4.Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

    4 Inepenent Protection Groups

    directional over current an earth fault protection Current Setting Range 10-1280A Setting Resolution 1A

    Inverse Time Protection Inepenent Curve Selection for Forwar

    & Reverse direction 4 x IEC255 Curves 8 x ANSI Curves User define Curves 42 x Custom Curves

    definite Time Protection 0-120 secons

    Time Resolution 0.01 secons High set Instantaneous element

    directional Sensitive Earth Fault Protection Current Setting Range 4-80A 1-80A option available Setting Resolution 1A definite Time 0-120 secons Time Resolution 0.01 secons

    Voltage Protection Element Phase unervoltage balance element

    (UV1) 3 phase loa sheing Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec

    Phase-to-Phase Unervoltage Element(UV2) Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec

    Loss of Supply (UV3) Trip time range: 0-180 sec

    Trip time setting resolution: 0.01 sec Reclose time: 0-180 sec Reclose time resolution: 0.01 sec

    Phase (OV1) & Line-to-Line (OV2) OverVoltage Trip time range: 0-180 sec Multiplier Setting Range: 1.00 -1.20

    Frequency Protection Element Uner Frequency (UF) Picup Range:

    46-50Hz (50Hz system), 55-60Hz(60Hz system)

    Over Frequency (OF) Picup Range: 50-55Hz (50Hz system), 60-65Hz (60Hz

    system) Frequency settings resolution: 0.01Hz Trip time range: 0-120 sec Trip time setting resolution: 0.01 sec

    Voltage reclose control with automatic bacfee restoration provies loop automationfunctionality.

    Zone Sequence Co-orination

    Col Loa Picup Col loa time ramp up: 1-400 min Col loa time ramp own: 0-60 min Col loa time resolution: 1 min Col loa multiplier: 1-5 times picup current Col loa multiplier resolution: 0.1

    Inrush Restraint

    Inrush time: 0.01-10 sec Inrush time resolution: 0.01 sec Inrush multiplier: 1-20 Inrush multiplier resolution: 0.1

    Temporary Time Aition

    Provies a steppe time elay toautomatically isolate faulte sections ina feeer or correct graing of evices inseries.

    duty Cycle O-0.1sec-CO-1sec-CO-1sec-CO-60sec

    recovery time

    Reclosing Times 1st reclosing time range 0.1 - 180 secons 2n reclosing time range 1 - 180 secons 3r reclosing time range 1 - 180 secons Setting resolution 0.01 secons

    Auto Reclose User configurable 1-4 trips to locout,

    inepenently settable for overcurrentearth fault, sensitive earth fault an voltageprotection.

    Live Line Function & Hot Line Tag Function

    Local Control Panel

    PROTECTION

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    6/8

    Introduction5. Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

    Voltage is measure on all six (6) bushings ancurrent is measure on all three (3) phases of theOSM recloser using capacitively couple voltagesensors an current transformers.

    Phase to Earth Voltage:Range 0.3 - 22.0V, Accuracy 1% or 0.1V

    Phase to Phase Voltage:Range 0.5 - 38.0V, Accuracy 2% or 0.1V

    Phase Current:Range 0 - 630A, Accuracy 1% or 4A

    Resiual Current:Range 0 - 100A, Accuracy 5% or 0.5A

    Active, Reactive an Total Power:Range 40 - 630A, 4.5 - 38V, Accuracy 2%

    Single an Three Phase Active, Reactive anTotal Power:Range 0 - 30,000 W/VAR/VA, Accuracy 2%

    Frequency:Range 46-55Hz, 55-65HzAccuracy at F/T < 0.2Hz/s: 0.025Hz

    Range 46-55Hz, 55-65HzAccuracy at F/T < 0.5Hz/s: 0.05Hz

    Power Factor:Range 0-1, Accuracy 0.02

    A USB front panel interface is provie to connectto a PC running CMS. This provies full settingsan ata management facilities. An RS232 RTUinterface offering 300-19.2 & 3xUSB port bau,full an half uplex moes, is provie to connectto remote control systems. dNP3 communicationsprotocol is provie in the stanar prouctcombine with our ability to engineer new protocolsto meet specifie customer requests.

    The control cubicle has space to mount a raioor moem. The onboar raio power supply israte at 12V 20W continuous uty, 30 watts 50%uty cycle.

    I/O moules with eight (8) user configurableinputs an eight (8) user configurable outputs canbe orere as options in the RC10 control. Upto two I/O moules can be fitte extening thisto sixteen inputs an sixteen outputs. Three (3)user configurable sanitate inputs are inclue asstanar.

    MEASUREMENT

    EVENT LOG

    LOAd PROFILE LOG

    REMOTE CONTROL

    The RC10 control provies two metho to accessthe event logs time an ate stampe to a 0.01sec resolution.

    The first is metho is from the RC LCd isplay, itprovies critical operations ata for the linesmanan inclues close/open operations, fault types,

    phase an pea level of fault current.

    The secon is metho is by PC uploa usingCMS. It provies a full log of all operational historyincluing setting changes, operations an faulthistory.

    The fault history logs inclue 50 cycles of pre-triphistory to allow analysis of the fault propagation.

    The Loa Profile is logge with a user configureintegration perio of either 1, 5, 10, 15, 30, 60 an120 minutes.

    The following parameters are logge separately forboth positive an negative power flow.

    Up to 10000 events can be store in the memorywhich correspons to a 417 ay, 60 minute,integration perio.

    CMS can be use to uploa an plot the ata.

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    7/8

    Introduction

    Earthing shoul be in accorance with the

    technical manual. Earthing require is a

    main earth bon from the tan to groun

    an a tee-off to the RC10 control cubicle

    from this main earth bon. Minimum 35mm2

    earth cable shoul be use.

    Each HV terminal on the OSM has a tin-

    plate brass connector at the en with options

    for cable connection as follows:

    A Tunnel terminal arrangement

    suitable for cable sizes from 40mm2

    to 260mm2. Cables are secure in the

    connector with two hexagon socet

    screws.

    Two hole cable palms with NEMA

    spacing. The cable palms are supplie

    with two (2) M12x25mm stainless steel

    bolts together with flat an spring

    washers.

    Pole mounting bracets an surge arrester

    mounting bracets are provie stanar.

    Full installation etails are provie in thetechnical manual, this iagram is provie

    to show a typical arrangement only.

    OSM38 Pole Mounting ArrangementOSM15 an OSM27Pole Mounting Arrangement

    OSM15 an OSM27Terminal Connectors

    OSM38 Terminal Connectors

    Tunnel Connector

    OSM38

    OSM15 an OSM27

    Two Hole NEMAPa Option

    6.Product Guide OSM Automatic Circuit Recloser 15V 27V 38V Moels

  • 7/31/2019 Recloser Smart Grid - OSM15 27 38 Brochure

    8/8

    Altitues above 1000m shoul be erate in accorance with ANSI C37.60-2003

    NOJA-560-01

    NOJA Power is a registere traemars of NOJA Power Switchgear Pty Lt. This ocument is copyright an is intene for users an istributors of NOJA Power Switchgear prouct. It contains information that is theintellectual property of NOJA Power Switchgear an the ocument, or any part thereof, shoul not be copie or reprouce in any form without written permission from NOJA Power Switchgear.

    NOJA Power Switchgear applies a policy of continue funamental research an evelopment an reserves the right to change esigns an specifications of this prouct without notice. NOJA Power Switchgear oes notaccept any responsibility for loss or amage incurre by anyone as a result of acting or refraining from action base on information in this Prouct Guie.

    OSM15-16-6303 x Current Transformers

    6 x Voltage ScreensRC1015.5V630A16A40A16A30,00030,00020016A/4 secs630A25A10A

    110V110V50V50V-40C to +55C0-100%3000M85g

    Part NumberCurrent Sensing

    Voltage SensingControl TypeRate Maximum VoltageRate Continuous CurrentFault Mae Capacity RMSFault Mae Capacity PeaFault Brea CapacityMechanical OperationsFull Loa OperationsFault Brea Capacity OperationsShort Time Current WithstanMainly Active Breaing CapacityCable Charging CurrentLine Charging Current

    Impulse Withstan Phase to Earth & Phase to PhaseImpulse Across the InterrupterPower Frequency Withstan Phase to Earth (dry)

    Across the InterrupterAmbient TemperatureHumiity

    AltitueWeight of the Tan

    OSM27-12-6303 x Current Transformers

    6 x Voltage ScreensRC1027V630A12.5A31.5A12.5A30,00030,00020012.5A/4 secs630A25A5A

    125V (150V option)125V (150V option)60V60V-40C to +55C0-100%3000M85g

    OSM38-12-6303 x Current Transformers

    6 x Voltage ScreensRC1038V630A12.5A31.5A12.5A30,00030,00020012.5A/3 secs630A40A5A

    195V170V70V70V-40C to +55C0-100%3000M140g

    Scan to vie

    NOJA Poer

    ebsite

    NOJA POwER AUSTRAlIA

    NOJA Poer Sitchgear Pty ltd

    16 Archimees Place, Murarrie

    Brisbane Ql 4172, Australia

    Phone: +61 7 3907 8777Fax: +61 7 3399 6777

    Email: [email protected]

    Web: www.nojapower.com.au

    NOJA POwER UK

    NOJA Poer limited

    4 Stalyhill drive, Mottram RiseStalybrige, Cheshire Sk 15 2TR

    Phone: +44 (01865) 58 9499Fax: +44 (01865) 58 9400

    Email: [email protected]

    Web: www.nojapower.co.u

    NOJA POwER BRAZIl

    NOJA Poer do Brasi ltda

    Rua Alcntara, 825A

    So Paulo SP

    CEP 02110-011, Brasil

    Phone: +55 (11) 2615 4788

    Email: [email protected]

    Web: www.nojapower.com.br